Refrigeration Test Rig
Refrigeration Test Rig
Refrigeration Test Rig
AIM: To study the refrigeration system and its control where throttling of the refrigerant is accomplished in a capillary tube and a thermostatic expansion
valve.
SPECIFICATIONS:
PRINCIPLE:
A basic refrigerating unit has 4 main components. The compressor, condenser, expansion device and the evaporator. The compressor is assumed to be an
isentropic device. The expansion device is a throttling device to create pressure drop of refrigerant is assumed to be operated at isenthalpic conditions. The
condenser and the evaporator are heat exchangers which operate at constant pressure. The four processes are as shown on the PH chart below:
VAPOUR COMPRESSION SYSTEM
= KJ/s or Kw
()
= KJ/s or Kw
()
=
()
PROCEDURE:
1. Fill the chilled water calorimeter with pure water so that the evaporator coils are completely immersed.
2. Select the thermostatic valve line by switching on the solenoid manual switch. Keep the shut off valve on the
capillary line closed.
3. Start the compressor and run for some time.
4. The chilled water temperature may vary slightly during measurement. It is important that the temperature is kept
within narrow temperature range.
5. Note the time taken for 5 revolutions of the energy meter disc.
6. Note the temperature and pressure readings at locations 1,2,3 & 4.
7. Switch off the solenoid switch.
8. Select the capillary tube line by opening the shut off valve on this line and closing the one of the thermostatic
expansion valve line. The solenoid manual switch is switched off.
9. Note the time taken for 5 revolutions of the energy meter disc. Note the temperature and pressure readings at
locations 1,2,3 & 4.
10. Switch off the mains.
Sample Calculations:
1) Capillary Tube
1. Heat equivalent of work done by compressor =
KJ/s or Kw =
()
2. Actual Refrigeration Effect = KJ/s or Kw =
()
( = ) =
2) Solenoidal Valve
1. Heat equivalent of work done by compressor = KJ/s or Kw =
()
2. Actual Refrigeration Effect =
KJ/s or Kw =
()
( = ) =
OBSERVATIONS
Energy Meter constant = 750 rev/Kwh
2 Chilled water
Temperature (C)
3 Time taken for 5
revolutions of
energy meter disc
4 Pressure Temp h Pressure Temp h
Evaporator Outlet/
Compressor Suction
Compressor Outlet/
Condenser Inlet
Expansion Device Inlet/
Condenser Outlet
Expansion Device
Outlet/
Evaporator Inlet
5 Refrigerant Flow
Rate : m (LPH)
6 Actual COP
7 Theoretical COP