Effect of Capillary Tube Length On The Vcrs Performance: Experiment No. (1) Mechanical Lab
Effect of Capillary Tube Length On The Vcrs Performance: Experiment No. (1) Mechanical Lab
Effect of Capillary Tube Length On The Vcrs Performance: Experiment No. (1) Mechanical Lab
College Of Engineering
Mechanical Department
Grope:A
1
Introduction:
Hermetic compressors are almost universally used in small systems such as domestic
refrigerators, water coolers, air conditioners and deep freezer, where efficiency is
not as important as customer convenience. In addition to this, the use of hermetic
compressors is ideal in systems, which use capillary tubes as expansion devices to
reduce the pressure in evaporator section. In capillary tube the refrigerant has to
overcome the frictional resistance offered by tube walls which leads to some
pressure drop, and also the liquid refrigerant flashes into wet vapour, as its pressure
reduces through the capillary tube. Both variables mentioned above increase the
pressure drop across the capillary tube, this pressure drop controls the mass flow rate
of refrigerant, and for a given value of condenser pressure, there is a definite value
of evaporator pressure at which the mass flow rates through the compressor and the
evaporator are the same. Thus the mass flow rate through the capillary tube increases
as the condenser pressure increases and/or the evaporator pressure decreases. One
of the most variables affect the pressure drop across a given capillary tube is the
capillary geometry, like the number of coils and pitch between the coils
Concept:
a vapor-compression refrigeration system is a system that uses liquid refrigerant in
a closed system which circulates the refrigerant through four stages in which it is
alternately compressed and expanded, changing it from liquid to vapor. As this
change happens, heat is either absorbed or expelled by the system, resulting in a
change in temperature of the surrounding air that is passing over the unit's
components.
2
PURPOSE:
APPARATUS:
3
4
3. THEORY:
The ideal refrigeration cycle shown in figure (3), includes the following processes:
1-2: Isentropic compression, s2=s1
2-3: constant pressure heat rejection in the condenser.
3-4 : Throttling in the expansion valve, h3=h4 .
4-1 : constant pressure heat addition in the evaporator.
The refrigeration effect (evaporator) may be calculated as follows:
𝑹𝑬 = 𝒒𝒆𝒗𝒂𝒑 = 𝒒𝑳 = 𝒉𝟏 − 𝒉𝟒
Where h1 is the enthalpy at evaporator outlet (compressor inlet) at evaporator pressure, kJ/kg.
h4 is the enthalpy at evaporator inlet (expansion valve outlet) at evaporator pressure, kJ/kg.
The work added to the compressor, per unit mass, is
𝐰𝒄𝒐𝒎𝒑. = 𝒉𝟐 − 𝒉𝟏
Where h2 is the enthalpy at compressor outlet (condenser inlet) at condenser pressure, kJ/kg.
The rejected heat from the condenser is:
𝒒𝒄𝒐𝒏𝒅 = 𝒒𝑯 = 𝒉𝟐 − 𝒉𝟑
Where h3 is the enthalpy at condenser outlet, kJ/kg.
The coefficient of performance of the refrigeration system is:
𝑹𝑬 𝒉𝟏 − 𝒉𝟒
𝑪𝑶𝑷 = =
𝐰𝒄𝒐𝒎𝒑. 𝒉𝟐 − 𝒉𝟏
5
EXPERIMENTAL PROCEDURE:
1. Switch on electrical power.
2. Change the capillary tube length from 1.5 m to 3m and then 5m.
3. Record the readings of the temperatures and pressures of the evaporator and condenser at
𝑅𝐸 = 𝑞𝑒𝑣𝑎𝑝 = 𝑞𝐿 = ℎ1 − ℎ4
w𝑐𝑜𝑚𝑝. = ℎ2 − ℎ1
𝑞𝑐𝑜𝑛𝑑 = 𝑞𝐻 = ℎ2 − ℎ3
𝑅𝐸 ℎ1 − ℎ4
𝐶𝑂𝑃 = =
w𝑐𝑜𝑚𝑝. ℎ2 − ℎ1
6
For length 1.5m:
No Length(m) 𝑷𝒍𝒐𝒘 (bar) 𝑷𝒉𝒊𝒈𝒉 (bar) 𝑻𝒆𝒐 𝑻𝒆𝒊 𝑻𝒄𝒊 𝑻𝒄𝒐
1 1.5 3 11 3 1 40 36
𝒉𝟏 = 𝒉𝒈 @𝑇𝑙𝑜𝑤 = 1°𝐂
𝒉𝟏 =248. 15
7
For length 3m :
No Length(m) 𝑷𝒍𝒐𝒘 (bar) 𝑷𝒉𝒊𝒈𝒉 (bar) 𝑻𝒆𝒐 𝑻𝒆𝒊 𝑻𝒄𝒊 𝑻𝒄𝒐
2 3 2.5 9 -2 -5 35 31
• Note / we use the Table (A-11 and A-13) and interpolation
ℎ3 = ℎ = ℎ @𝑇ℎ𝑖𝑔ℎ = 35°C
4 𝑓
𝒉𝟑 = 𝒉𝟒 =98.94
we can find
𝑆2 = 𝑆3 = 𝑆𝑔 @𝑇𝑙𝑜𝑤 = −5°C 𝑺𝟐 = 𝑺 = 0.94
𝟑
8
For Length 5m :
No Length(m) 𝑷𝒍𝒐𝒘 (bar) 𝑷𝒉𝒊𝒈𝒉 (bar) 𝑻𝒆𝒐 𝑻𝒆𝒊 𝑻𝒄𝒊 𝑻𝒄𝒐
3 5 2 8 -8 -9 35 30
ℎ1 = ℎ𝑔 @𝑇𝑙𝑜𝑤 =-9 °C
𝒉𝟏 =242.49
ℎ3 = ℎ = ℎ @𝑇ℎ𝑖𝑔ℎ = 35°C
4 𝑓
𝒉𝟑 = 𝒉𝟒 =98.8
We can find
𝑆2 = 𝑆3 = 𝑆𝑔 @𝑇𝑙𝑜𝑤 = −9°C 𝑺𝟐 = 𝑺 =0.925
𝟑
9
Discussion:
1.Draw p-h and T-s diagram for each case.
For length 1.5m
Phigh
plow
h3=h4=250kj/k
h1 = 385kj/kg h2 = 445kj/kg
g
10
For length 3m
phig
h
plow
11
For length 5m
phig
h
plow
h3=h4=250kj/kg
h1=390kj/k h2=443kj/k
g g
12
5.Calculate the coefficient of performance for refrigeration system, COP for each case.
Ans/ I determined from calculation
6.Draw the capillary tube lengths with Refrigeration effect and discuss it.
Ans/
length&RE
145.5
145 144.63
144.44
144.5
144
RE(kj/kg)
143.5
143
142.5 142.13
142
141.5
1 1.5 2 2.5 3 3.5 4 4.5 5 5.5
length(m)
The refrigeration effect increased with increase length of capillary tube the relationship is direct
7.Draw the capillary tube lengths with compressor work and discuss it.
Ans/
length&wc
30
27.65 28.07
28
26
wc(kj/kg)
24
22 20.65
20
18
16
length(m)
Increase of length capillary tube increased the work compressor the relationship is direct.
13
8.Draw the capillary tube lengths with COP and discuss it.
length&COP
7 6.7839
6.5
6
COP
4.5
4
1 1.5 2 2.5 3 3.5 4 4.5 5 5.5
length(m)
Increase of length of capillary tube decrease the COP the relationship is inversely.
14
Conclusion:
15