VIP45
VIP45
VIP45
NRJED311207EN 12/2011
VIP40, VIP45
NRJED311207EN
12/2011
www.schneider-electric.com
The information provided in this documentation contains general descriptions and/or technical characteristics of the performance of the products contained herein. This documentation is not intended as a
substitute for and is not to be used for determining suitability or reliability of these products for specific
user applications. It is the duty of any such user or integrator to perform the appropriate and complete
risk analysis, evaluation and testing of the products with respect to the relevant specific application or use
thereof. Neither Schneider Electric nor any of its affiliates or subsidiaries shall be responsible or liable for
misuse of the information contained herein. If you have any suggestions for improvements or
amendments or have found errors in this publication, please notify us.
No part of this document may be reproduced in any form or by any means, electronic or mechanical,
including photocopying, without express written permission of Schneider Electric.
All pertinent state, regional, and local safety regulations must be observed when installing and using this
product. For reasons of safety and to help ensure compliance with documented system data, only the
manufacturer should perform repairs to components.
When devices are used for applications with technical safety requirements, the relevant instructions must
be followed.
Failure to observe this information can result in injury or equipment damage.
2011 Schneider Electric. All rights reserved.
NRJED311207EN 12/2011
Table of Contents
Safety Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
About the Book . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Chapter 1 At a Glance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
5
7
9
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
10
13
Chapter 2 Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
15
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Equipment Receipt and Identification . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Mounting/Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the VIP to the Current Sensor . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connecting the VIP to the Mitop Trip Unit . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Earthing . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Connector Pinout. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
16
17
18
19
21
22
23
24
25
Chapter 3 Use . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
27
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Advanced Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
List of VIP40 and VIP45 Screens . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
28
30
32
33
35
36
40
43
44
45
46
47
48
49
51
Chapter 5 Reliability. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
53
General Principle. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Operation of the Self-test System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
54
55
Chapter 6 Commissioning. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
57
Safety Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Settings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checking VIP Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Checking the Complete Protection Chain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
58
59
60
61
64
67
Chapter 7 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
69
Expert Menu . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Preventive Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Pocket Battery Module . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Troubleshooting Assistance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Removing the VIP . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Replacing the VIP Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
70
73
75
77
79
80
Chapter 8 Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
83
Function Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Technical Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Environmental Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
Internal Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
84
86
87
89
NRJED311207EN 12/2011
NRJED311207EN 12/2011
Safety Information
Important Information
NOTICE
Read these instructions carefully, and look at the equipment to become familiar with the device before
trying to install, operate, or maintain it. The following special messages may appear throughout this
documentation or on the equipment to warn of potential hazards or to call attention to information that
clarifies or simplifies a procedure.
PLEASE NOTE
Electrical equipment should be installed, operated, serviced, and maintained only by qualified personnel.
No responsibility is assumed by Schneider Electric for any consequences arising out of the use of this
material.
A qualified person is one who has skills and knowledge related to the construction and operation of
electrical equipment and its installation, and has received safety training to recognize and avoid the
hazards involved.
NRJED311207EN 12/2011
NRJED311207EN 12/2011
At a Glance
Document Scope
This manual is intended for personnel responsible for installing, commissioning and using VIP protection
relays.
Validity Note
This manual is applicable to all versions of the VIP40 and VIP45 protection relays.
The table below lists the revisions of VIP software versions.
Software Version
Date
Revision
V1.0.0
March 2012
V1.2.0
October 2011
User Comments
We welcome your comments about this document. You can reach us by e-mail at techcomm@schneiderelectric.com.
NRJED311207EN 12/2011
NRJED311207EN 12/2011
VIP40, VIP45
VIP40, VIP45 - At a Glance
NRJED311207EN 12/2011
At a Glance
1
Whats in this Chapter?
This chapter contains the following topics:
Topic
NRJED311207EN 12/2011
Page
Introduction
10
Operation
13
Introduction
VIP40s and VIP45s
VIP40 and VIP45 protection relays are designed for the protection and operation of MV/LV utility
substations up to 200 A primary belonging to electrical distribution networks in industrial installations.
VIP40 and VIP45 are protection relays with a self-powered supply. They are powered by their current
sensor and operate without an auxiliary power supply.
10
NRJED311207EN 12/2011
Selection Table
The selection table lists the functions performed by VIP40s and VIP45s.
Function
VIP40
VIP45
Earth fault protection using the sum of the currents (ANSI 51N)
VIP References
Reference
Description
REL59910
REL59911
REL59912
REL59913
Accessory References
Reference
Description
LV434206
Current Sensor
VIPs operate exclusively with the dual core CUa current sensor (200 A primary).
This sensor provides:
The VIP power supply
Metering of all 3 phase currents and the earth fault current
Use of the dedicated sensor means the complete protection chain performance (sensor, VIP, Mitop trip
unit) can be guaranteed.
It is very easy to connect VIP relays to the CUa sensor by means of 2 prewired connectors from the
sensor:
1 x 9-pin SUBD connector for metering the phase and earth fault currents
1 x 6-pin lockable connector for the VIP power supply
The CUa current sensor consists of 2 windings per phase, one winding providing the VIP power supply,
the other winding enabling the VIPto measure the phase currents. The earth fault current is measured by
taking the sum of the 3 phase currents inside the sensor.
NRJED311207EN 12/2011
11
1
2
3
Metering windings
VIP power supply windings
dual core CUa sensor
CUa
200 A
0.0833 A
1/2400
72 V
4 mA
18.8 Ohm
1.8 Ohm
150 mV/ln
The power supply winding is a magnetic core winding that provides the VIP power supply.
Parameters
CUa
200 A
0.377 A
1/530
32.9 V
13.5 mA
oC
12.4 Ohm
75 mW
12
NRJED311207EN 12/2011
Operation
Mimic Diagram of VIP40 and VIP45 Operation
NRJED311207EN 12/2011
13
14
NRJED311207EN 12/2011
VIP40, VIP45
VIP40, VIP45 - Installation
NRJED311207EN 12/2011
Installation
2
Whats in this Chapter?
This chapter contains the following topics:
Topic
NRJED311207EN 12/2011
Page
Safety Precautions
16
Precautions
17
18
Mounting/Assembly
19
Connectors
21
22
23
Earthing
24
Connector Pinout
25
15
Safety Precautions
Before Starting
You are responsible for compliance with all the existing international and national electrical codes
concerning protective earthing of any device.
You should also carefully read the safety precautions described below. These instructions must be
followed strictly when installing, servicing or repairing electrical equipment.
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC, BURNS OR EXPLOSION
Only qualified personnel should install this equipment. Such work should be performed only after
reading this entire set of instructions.
NEVER work alone.
Turn off all power supplying this equipment before working on or inside it.
Always use a properly rated voltage sensing device (EN 61243) to confirm that all power is off.
Before performing visual inspections, tests, or maintenance on this equipment:
Disconnect all sources of electric power.
Assume that all circuits are live until they have been completely de-energized, tested and tagged.
Pay particular attention to the design of the power system: consider all sources of power, including
the possibility of backfeeding to the cubicle where the VIP is installed.
Beware of potential hazards, wear personal protective equipment, and carefully inspect the work
area for tools and objects that may have been left inside the equipment.
Successful VIP operation depends upon proper installation, setting, and operation.
Setting the VIP relay requires relevant expertise in the field of electrical network protection. Only
competent people who have this expertise are allowed to set this product.
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
Never leave the current sensor secondary in open circuit. The high voltage that would result from
opening the circuit is dangerous for the operator and for the equipment.
Never disconnect the VIP protection relay current sensor connectors unless the MV circuit breaker
is in the open position and completely isolated.
Wear insulating gloves to avoid any contact with a conductor that has accidentally been energized.
Wear personal protective equipment in compliance with current regulations.
Screw tight all terminals, even those not in use.
CAUTION
RISK OF DAMAGE TO THE VIP
Before performing Dielectric (Hi-Pot) or Megger testing on any equipment in which the relay is
installed, disconnect all input and output wires to the VIP relay. High voltage testing may damage
electronic components contained in the VIP relay.
Do not open the VIP case. The VIP relay contains components that are susceptible to electrostatic
discharge. It is assembled in specially equipped premises. The only permitted operation is removal
of the depleted battery from its compartment on a VIP relay.
16
NRJED311207EN 12/2011
Precautions
Introduction
VIP protection relays are supplied in one of the following ways:
Individually packaged
Installed in a cubicle
The transport, handling and storage precautions for VIP relays vary depending on which of these two
methods is used.
VIP in its Original Packaging
Transport
VIP relays can be shipped to any destination by all suitable means of transport, without taking any
additional precautions.
Storage
VIP relays can be stored in their original packaging in a location with the following environmental
characteristics:
Temperature: 40...+70C (40...+158F)
Humidity 90%
Storage is limited to a maximum of one month if the relative humidity is higher than 93% and the
temperature higher than +40C (+104F).
If the relays are to be stored for an extended period, we recommend the following:
Do not unpack the VIP prior to its intended period of use.
Check the environment and the condition of the packaging annually.
Once the VIP relay has been unpacked, it should be energized as soon as possible.
More information on handling and storage is available in VIP Technical Characteristics (see page 86).
VIP Installed in a Cubicle
Transport
VIP relays can be shipped by all suitable means of transport in the usual conditions for cubicles.
Storage conditions should be taken into consideration for a long period of transport.
Handling
If the cubicle is dropped, check the VIPs condition by visual inspection and energizing.
Storage
We recommend keeping the cubicle protective packaging for as long as possible.
VIP relays, like all electronic units, should not be stored in a damp environment for more than
one month. They should be energized as quickly as possible. If this is not possible, the cubicle
reheating system should be activated.
NRJED311207EN 12/2011
21 days duration
25C (77F), 75% relative humidity
0.5 ppm H2S, 1 ppm SO2
17
A VIP
A certificate of conformity
Identification Label
The identification label on the front panel is used to identify the VIP:
1
2
3
Product name
Product reference
Serial number
18
NRJED311207EN 12/2011
Mounting/Assembly
Introduction
VIP relays weigh 380 g (0.84 lb) maximum and are flush-mounted in a mounting plate 1 to 2.5 mm (0.04
to 0.1 in) thick.
They are designed to be mounted indoors.
To ensure a waterproof seal, the surface of the panel must be smooth and solid.
Dimensions
Cut-out
Cut out the mounting plate as indicated:
CAUTION
HAZARD OF CUTS
Trim the edges of the cut-out plates to remove any jagged edges.
Failure to follow these instructions can result in injury or equipment damage.
NRJED311207EN 12/2011
19
20
NRJED311207EN 12/2011
Connectors
Introduction
All the VIP connectors can be accessed on the rear panel. They are removable.
Identification of the Connectors on the Rear Panel
NRJED311207EN 12/2011
21
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
Never leave the current sensor secondary in open circuit. The high voltage that would result from
opening the circuit is dangerous for the operator and for the equipment.
Never disconnect the VIP protection relay current sensor connectors unless the MV circuit breaker
is in the open position and completely isolated.
Wear insulating gloves to avoid any contact with a conductor that has accidentally been energized.
Wear personal protective equipment in compliance with current regulations.
22
NRJED311207EN 12/2011
NRJED311207EN 12/2011
23
Earthing
Connection Characteristics
Label
Wiring
Type of Terminal
Screwdriver
Tightening Torque
Green-yellow wire 6 mm
M5 screw
Philips no. 2
2...2.3 Nm
(17.7...20.4 lb-in)
(AWG 10)
Lug with internal diameter 5
24
NRJED311207EN 12/2011
Connector Pinout
Connector B Pinout
Connecting the VIP Self-Powered
Supply
Connector D Pinout
Connecting the Mitop Trip Unit to the
VIP
Connector E Pinout
Connecting the Phase and Earth Fault
Current Measurement Inputs
NRJED311207EN 12/2011
25
26
NRJED311207EN 12/2011
VIP40, VIP45
VIP40, VIP45 - Use
NRJED311207EN 12/2011
Use
3
Whats in this Chapter?
This chapter contains the following topics:
Topic
NRJED311207EN 12/2011
Page
Operation
28
Settings
30
Advanced Settings
32
33
27
Operation
Front Panel
The User-Machine Interface (UMI) on the front panel of VIP40 and VIP45 relays consists of a display,
LEDs, keys and adjustment dials.
A transparent sealable pivoting flap can prevent access to the adjustment dials by unauthorized persons.
1
2
3
4
5
6
7
8
9
10
11
Display
Lugs for opening the transparent protective flap
Transparent protective flap
Imax. peak demand display button
Sealing ring
Test/Reset button
Status LED
Space for a user-customizable label
Trip fault indication LED
Identification label
Symbol indicating that it is necessary to read the manual
Display
The display is an LCD unit.
During operation, the display indicates the value of the current on each phase in succession. Each phase
remains displayed for 3 seconds before automatically changing to the next. The display is in amps, on
three digits.
NOTE: If the phase current is less than the pick-up current (see page 86), the VIP is not activated and
the display is off.
Lugs for Opening the Transparent Protective Flap
To open the flap, pull both lugs simultaneously. The flap pivots open on its 2 bottom hinges.
Transparent Protective Flap
The sealable flap can prevent modification of the VIP settings. Because the flap is transparent, the
settings are legible when it is closed.
Imax. Button: Peak Demand Display
Pressing the Imax. button triggers a sequence displaying the peak demand currents for all 3 phases in
succession. After this sequence, the VIP automatically returns to displaying the phase currents.
28
NRJED311207EN 12/2011
Test/Reset Button
After a trip, pressing this button stops the flashing trip indication.
This button can also be used to:
Test the built-in battery. When pressing the Test/Reset button, the fault indication LED lights up
immediately to indicate that the battery is OK.
Perform the lamp test if the relay is supplied with power. Pressing the Test/Reset button for
Status LED
The status LED provides information about the VIPs general status:
Pictogram
Color
Event
Red
LED permanently on: the VIP has gone into the fail-safe position following
tripping. In this case, the VIP has not gone into the fail-safe position.
Intervention is required as soon as possible (see page 77). The LED stops
flashing as soon as the failure disappears.
NOTE: The VIPs built-in battery only supplies power to the fault indication LED and displays the type of
fault. It has no role in operating the protection functions.
Identification Label
The identification label on the front panel is used to identify the VIP:
Product name
Product reference
Serial number
Symbol: Necessary to Read the Manual
The
product.
NRJED311207EN 12/2011
symbol indicates that it is necessary to read the VIP reference manual before working on the
29
Settings
Front Panel
When the protective flap is opened, you can enter the protection settings by means of the rotary switches.
To do this, use a 3 mm flat blade screwdriver.
VIP40
VIP45
1
2
3
4
5
1
2
3
4
5
6
7
NRJED311207EN 12/2011
Frequency
The network frequency (50 Hz or 60 Hz) is a parameter that must be known for operation of the VIP40
and VIP45 signal processing algorithms. They therefore have an automatic frequency recognition
system. The recognized value (50 Hz or 60 Hz) is stored and the VIP works permanently with this value.
This stored value will be used each time the VIP starts.
For the VIP to recognize the network frequency and store it, it has to detect a current on phase 1 for a
minimum period of 5 seconds in the range 50 Hz +/- 2 Hz or 60 Hz +/- 2 Hz. This detection happens when
the VIP starts.
NRJED311207EN 12/2011
31
Advanced Settings
Front Panel
To access the advanced settings, remove the advanced settings protective cover.
Both settings can be entered using a single selector switch:
Discrimination with the LV CB
Earth fault protection inrush current delay
NOTE: These settings are entered, if necessary, when the installation is commissioned. By default, they
are in the OFF position.
VIP40
1
2
VIP45
Description
ON
An additional time delay is implemented to provide discrimination with the downstream circuit breaker
short time set point.
OFF
When the transformer secondary is protected by LV fuses, it is advisable to leave the function OFF.
More information is available in the section describing Overcurrent Protection (see page 36).
Earth Fault Protection Inrush Current Delay
The earth fault protection inrush current delay function is only found on the VIP45. On the front panel, it
is identified by EF inrush delay.
Setting
Description
ON
Time delay activated routinely when the VIP45 starts up. This time delay only applies to earth fault
protection and does not apply to overcurrent protection.
OFF
More information is available in the section describing Earth Fault Protection (see page 40).
32
NRJED311207EN 12/2011
Screen
Description
Displays an error code after I3 only when a a failure not involving a risk of
nuisance tripping is detected, see Operation of the Self-test System
(see page 55) chapter.
Screen
Description
Displays the data tag for peak demand phase current I1.
Displays the data tag for peak demand phase current I2.
Displays the data tag for peak demand phase current I3.
Expert Menu
See the Expert (see page 70) menu.
NRJED311207EN 12/2011
33
34
NRJED311207EN 12/2011
VIP40, VIP45
VIP40, VIP45 - Functions and Parameters
NRJED311207EN 12/2011
4
Whats in this Chapter?
This chapter contains the following topics:
Topic
NRJED311207EN 12/2011
Page
36
40
43
44
45
46
47
48
49
Fault Acknowledgement
51
35
The phase-to-phase fault tripping curve (at the primary or the secondary) is based on the measurement
of the fundamental component of the currents produced by all 3 phase CTs. This type of measurement
can be used to reduce the sensitivity of the transformer inrush currents.
Tripping Curve
1
2
3
4
5
Setting the I> set point triggers movement of the whole curve. The characteristics of the 3 tripping
curve zones are detailed below.
36
NRJED311207EN 12/2011
where:
E(t): Thermal capacity used value at time t
E(t-t): Thermal capacity used value at time t-t
I(t): Current value measured at time t
I>: Value of the ANSI 50-51 protection setting set point
: Heating/cooling time constant, defined at 10 minutes, typical value for MV/LV transformers
The heat transfer of the current I(t) is defined by the term below:
The protection trips if the thermal capacity used is more than 100%.
The asymptote of the tripping curve is defined by the I> setting multiplied by a fixed coefficient of 1.2.
Calculating the Tripping Time
For a continuous current higher than the tripping set point, it is possible to calculate the tripping time using
the equation below:
where:
I: Overload current (maximum of the 3 phase currents)
I>: ANSI 50-51 protection setting set point
: Heating/cooling time constant (10 min = 600 s)
Ito: Equivalent thermal current before application of the overload
ln(): Natural logarithm function
The equivalent thermal current Ito corresponds to the continuous current which would have resulted in
the same thermal capacity used before application of the overload.
The tripping curve shown in the figure above is given for a zero initial thermal current Ito.
This curve, called "cold curve", is defined by the equation below:
The dotted-line curve in the overload zone corresponds to the tripping time for an initial thermal capacity
used equal to the I> setting set point.
This curve, called "warm curve", is defined by the equation below:
NRJED311207EN 12/2011
Td (Where Ito = 0)
1.5 I>
613.0 s
260.3 s
2 I>
267.8 s
95.2 s
2.5 I>
157.1 s
52.5 s
3 I>
104.6 s
33.9 s
3.5 I>
75.0 s
23.9 s
37
Depending on the initial thermal capacity used caused by changes in the load current, the tripping time
in the event of an overload will be in the range of times indicated above.
The current thermal capacity used is not saved in the event of loss of the VIP power supply, or when the
phase currents fall below the value of the VIP pick-up current. Each time the VIP wakes up, the equivalent
thermal current Ito is reset to zero.
Secondary Fault Pick-up Curve (Between 3.5 and 20 I>)
The secondary fault pick-up curve is IDMT type, with a tripping time that depends on the current value.
It allows the phase-to-phase fault at the MV/LV transformer secondary to be eliminated, while ensuring
coordination with the downstream fuses or LV circuit breakers.
This curve, called FUSE, is defined by the special equation below:
where:
I: Measured fault current (maximum of the 3 phase currents)
I>: 50-51 protection setting set point
The main characteristics of the FUSE curve are:
An asymptote defined at 3.5 I>
3
A 1/I slope to obtain a slope comparable with the LV or MV blown fuse curves This similarity
simplifies coordination with downstream LV fuses or upstream MV fuses.
This IDMT curve is managed in accordance with the recommendations of standard CEI 60255-151, which
defines the standardized IDMT curves (IEC or IEEE curves). In particular, this curve applies the concept
of integration if the current amplitude changes during the fault (open-ended fault). This concept can
ensure discrimination between the VIP curve and an upstream protection relay that uses standardized
IDMT curves.
FUSE/CB Curve Selection:
By default, the VIP uses the FUSE curve over the whole range 3.5 I> to 20 I>. This curve simplifies
coordination with downstream LV fuses.
If the VIP is upstream of an LV circuit breaker, it is advisable to activate the CB curve via the setting on
the front panel.
The CB curve activates a minimum time delay of 600 ms, which is applied between 8 I> and 20 I> (dottedline curve in the above figure). This time delay ensures coordination with the short time set point of the
downstream LV trip unit. This short time set point is usually set with a DT time delay of 0.2 s to 0.4 s,
which could overlap with the FUSE curve and make both protection stages non-discriminating. If
necessary, activation of the CB curve can ensure discrimination with the LV circuit breaker.
Primary Fault Pick-Up Curve (Above 20 I>)
The primary fault pick-up curve is DT type, with an instantaneous tripping time delay for a current higher
than 20 I>. It allows a phase-to-phase fault at the MV/LV transformer primary to be eliminated quickly.
If the I> set point is set to a value higher than or equal to the rated current for the protected MV/LV
transformer, this high set point, above 20 In, does not see faults at the secondary. This current discrimination ensures coordination with LV protection functions.
The VIP tripping time in this range is less than 20 ms (VIP already supplied with power) for short-circuit
currents higher than 40 I>.
Minimum tripping time:
Depending on the device used, a minimum tripping time can be activated to comply with the circuit
breaker breaking capacities. In this example, an additional 30 ms time delay is added to the primary fault
pick-up curve.
More information is available in the section describing Minimum Tripping Time (see page 47).
38
NRJED311207EN 12/2011
Protection Operation
If the maximum of the 3 phase currents exceeds the 1.2 I> set point, the Trip fault indication LED flashes
quickly. If the current falls back below the 1.2 I> set point before the time delay expires, the Trip LED goes
out.
After expiry of the tripping time delay:
The Trip LED flashes slowly.
The Mitop trip unit output is activated.
The OC error message is displayed on the screen.
Pressing the Test/Reset button acknowledges the fault (see page 51) and causes the Trip LED to go out.
Settings
Setting
I> set
point
Authorized Values
VIP40 100 A
VIP45 100 A
5 A, 6 A, 7 A, 8 A, 10 A, 12 A, 15 A, 18 A, 21 A, 25 A, 30 A, 35 A, 40 A,
50 A, 60 A, 70 A, 80 A, 100 A
VIP40 200 A
VIP45 200 A
5 A, 6 A, 8 A, 10 A, 12 A, 15 A, 20 A, 25 A, 30 A, 35 A, 45 A, 55 A, 70 A,
85 A, 105 A, 130 A, 160 A, 200 A
Discrimination with LV CB
(Discrimination with LV CB)
OFF / ON
extrait de CT192
These inrush currents have a strong aperiodic component, as can be seen in the curve below:
I
I(t) = I(0).e t
If the VIP I> set point is set to a value higher than or equal to the transformer rated current, the VIP
protection relay IDMT curve will not be affected by the inrush currents.
In addition, the VIP current measurement used for the secondary fault and primary fault pick-up curves
is based on the measurement of the current fundamental component (50 Hz or 60 Hz component). De
facto, it is unaffected by the presence of an aperiodic component. Typically, the maximum current
measured by the VIP during closing will be 35% of the inrush current peak value stated by the transformer
manufacturer.
This 35% factor takes account of:
The 1/2 factor for switching from the peak value to the rms value
The 1/2 factor associated with elimination of the DC component
NRJED311207EN 12/2011
39
Additional Functions
The VIP integrates functions that complement earth fault protection:
Harmonic 2 restraint:
Since the earth fault current measurement is calculated from the sum of the 3 phase CTs, the aperiodic
component of the transformer inrush currents can cause transient saturation of the phase CTs and
lead to incorrect earth fault current measurement likely to result in nuisance tripping of the earth fault
protection. To authorize relatively sensitive settings, without a risk of nuisance tripping when the
transformer is energized, operation of the earth protection function is dependent upon a restraint
based on detection of the second harmonic component in the phase currents. This harmonic 2
restraint is always active.
Inrush current delay (inrush current delay):
In certain cases, the harmonic 2 restraint may not be enough to avoid nuisance tripping of the earth
fault protection when the transformer trips. In these scenarios, it is possible to implement a 1-second
time delay, activated at the time the VIP wakes up, which is added to the to> earth fault protection time
delay. This time delay can avoid tripping of the earth fault inrush current protection. Other application
scenarios for this time delay are described in the rest of this section. By default, this inrush current
delay is not active.
Protection Operation
If the residual current exceeds the Io> set point, the Trip LED flashes quickly. If the current falls back
below the Io> set point before the time delay expires, the Trip LED goes out.
After expiry of the to> tripping time delay:
The Trip LED flashes slowly.
The Mitop trip unit output is activated.
The EF error message is displayed on the screen.
Pressing the Test/Reset button acknowledges the fault (see page 51) and causes the Trip LED to go out.
Earth Fault Protection Harmonic 2 Restraint Operation
Harmonic 2 restraint is based on the continuous calculation of the harmonic 2 ratio in all 3 phase currents.
This ratio is calculated on the basis of the quadratic sums of the fundamental (H1) and harmonic 2 (H2)
components.
This ratio is compared to a fixed set point of 17%. If the set point is exceeded, the Io> set point is inhibited.
An increase in the harmonic 2 ratio in the phase currents is typical of saturation of the phase CTs on a
primary current with an aperiodic component. On power transformer energizing, the aperiodic component
of the magnetizing currents usually results in saturation of the CTs. Detection of harmonic 2 can be used
to inhibit the earth fault protection throughout energization. This restraint automatically disables itself
once the H2 ratio decreases.
40
NRJED311207EN 12/2011
The graph below illustrates the incorrect residual current and the change in the transformer inrush
current harmonic 2 ratio:
1
2
3
4
NRJED311207EN 12/2011
41
Settings
Setting
Io> set point
Values
Settings (A) for:
VIP40 100 A
VIP45 100 A
Settings (s)
OFF / ON
NOTE:
(1)
In the event of an earth fault, with the load current previously lower than the pick-up current or in the event of
closure on a fault, the tripping time is equal to the time delay that has been set plus the VIP45 pick-up time.
For an earth fault current higher than 10 A, the pick-up time is between 15 ms and 120 ms depending on the fault
discrimination with the upstream relay. In this particular scenario, the pick-up time can lead to the VIP45 relay and
the upstream relay tripping twice.
Additional setting:
Activation of the inrush current delay: OFF by default
42
NRJED311207EN 12/2011
The 2 integrated protection functions and tripping in temporary test mode cause activation of the Mitop
trip unit. The Mitop trip unit is integrated in the circuit breaker opening mechanism.
Operation
The Mitop trip unit output activation logic is defined by the following block diagram:
NRJED311207EN 12/2011
43
44
NRJED311207EN 12/2011
NRJED311207EN 12/2011
45
Action
Press and release the Imax. button to start displaying the peak demand values.
Press the Imax. and Test/Reset buttons simultaneously while the peak demand values are scrolling to
reset all 3 peak demand values.
NOTE:
46
When the VIP is first initialized (on leaving the factory), the values of the 3 peak demand values display
0 A. The VIP needs to have run for at least 5 minutes with a current other than zero for the peak
demand values to display values other than zero.
All 3 peak demand values are saved in the event of loss of the VIP power supply (phase currents lower
than the pick-up current).
NRJED311207EN 12/2011
NRJED311207EN 12/2011
47
48
The
status LED on the front panel flashes as long as the failure is present.
The Er14 message is displayed on the front panel as long as the failure is present.
NRJED311207EN 12/2011
Color
Event
Red
LED permanently on: the VIP has gone into the fail-safe position following
tripping. The VIP remains operational. The LED stops flashing as soon as the
failure disappears.
Slow Flashing
Tripping:
By the phase overcurrent protection
By the earth fault protection (VIP45 only)
By the temporary test mode
Quicker flashing may occur before the protection trips, to indicate the following information:
Pictogram
Quick Flashing
Trip
Overshoot of the instantaneous set point for phase overcurrent protection (pick-up output)
Overshoot of the instantaneous set point for earth fault protection (VIP45 only: pick-up output)
Downcounting of the tripping time delay in temporary test mode
If the VIP is still supplied with power by the primary current after the fault, the error message can
appear temporarily on screen, then disappear because it is automatically acknowledged if the primary
current remains higher than the pick-up current after the trip. This example is not an actual operating
scenario, but may be encountered during a lab test.
If the battery is missing or depleted, the cause of the last trip is displayed automatically (if it had not been
acknowledged earlier) when the pocket battery module is connected (see page 75).
NRJED311207EN 12/2011
49
NOTE: Display of the last fault disappears when the operator presses the Test/Reset button or when
primary current is present. However, it is still possible to view the last recorded fault in the Expert menu.
Particular Scenarios
Scenario 1: If power is restored to the VIP (primary current or test battery module) during the 24 hours
after tripping on a fault that has not been acknowledged, the 24-hour time delay is reactivated (fault
message displayed and fault LED flashing).
Scenario 2: At the end of the 24-hour time delay, if the fault has not been acknowledged, restoring power
to the VIP causes the last fault message to be re-displayed and the LED to flash. The 24-hour time delay
is not restarted.
50
NRJED311207EN 12/2011
Fault Acknowledgement
Description
Faults are acknowledged:
Manually, by pressing the Test/Reset button when the error message is displayed
Automatically when primary current is present
NRJED311207EN 12/2011
51
52
NRJED311207EN 12/2011
VIP40, VIP45
VIP40, VIP45 - Reliability
NRJED311207EN 12/2011
Reliability
5
Whats in this Chapter?
This chapter contains the following topics:
Topic
NRJED311207EN 12/2011
Page
General Principle
54
55
53
General Principle
Taking Account of Protection Relay Failures
Operational reliability is the property that allows its users to have well-placed confidence in the service
that the VIP protection relay delivers. For a VIP, operational reliability consists of ensuring the safety and
availability of the installation.
This means avoiding the following 2 situations:
Nuisance tripping of the protection:
Continuity of the electrical power supply is as vital for a manufacturer as it is for an electricity
distribution company. Nuisance tripping caused by the protection can result in considerable financial
losses. This situation affects the availability of the protection.
Failure of the protection to trip:
The consequences of a fault that is not eliminated can be catastrophic. For safety of operation, the
protection relay must detect faults in the electrical network as quickly as possible, using discrimination.
This situation affects the safety of the installation.
To comply with this approach, the VIP is equipped with self-tests that continuously check all its electronics
and embedded software are operating correctly.
The purpose of the self-tests is to put the VIP into a deterministic position, called the fail-safe position, in
the event of failure or malfunction of one of its internal components.
The VIPs failure must never cause the circuit breaker to open. However, in the event of a failure, the
protection is no longer operational and discrimination no longer occurs. This is not a problem while no
other faults exist downstream and the network can be used temporarily as it is.
When a new downstream fault occurs, the circuit breaker upstream trips and a larger part of the network
is shut down. To avoid leaving the network permanently in this state, with a failure that has not been
announced, it is essential to monitor that the VIP is operating correctly.
Fail-Safe Position
In fail-safe position:
The VIP is no longer operational and the network is no longer protected.
54
The
status LED is permanently on, if there is sufficient network current to power the VIP.
NRJED311207EN 12/2011
The
A 2-digit code is displayed on the front panel: this allows Schneider Electric to make a diagnosis (E
xx message).
NOTE: Once the VIP has gone into the fail-safe position, it remains in this mode, even in the event of
restarting following loss and return of the power supply.
Scenario 2: When a failure not involving a risk of nuisance tripping is detected, the VIP does not go into
the fail-safe position and remains operational (if the VIP is supplied with power):
The
status LED on the front panel flashes as long as the failure is present.
A 2-digit code is displayed on the front panel after display of the I3 current as long as the failure is
present. This code allows the customer to make an initial diagnosis (Erxx message).
More information is available in the section describing Troubleshooting Assistance (see page 77).
NOTE: To check that a VIP not supplied with power has not gone into the fail-safe position, use the pocket
battery module to make a routine check (see page 73).
List of Self-Tests
The self-tests are described in the table below.
NRJED311207EN 12/2011
Name
Description
Execution Period
During operation
NO
During operation
NO
On energization and
during operation
YES
YES
Reset detection
On energization and
during operation
YES
During operation
YES
During operation
YES
On VIP restarting
after a failure
YES
During operation or
on VIP restarting
after a failure
YES
YES
55
56
Name
Description
Execution Period
During operation or
on VIP restarting
after a failure
YES
On energization
YES
On energization and
during operation
YES
On energization and
during operation
YES
During operation
NO
Key test
NO
On energization and
during operation
NO
NO
NRJED311207EN 12/2011
VIP40, VIP45
VIP40, VIP45 - Commissioning
NRJED311207EN 12/2011
Commissioning
6
Whats in this Chapter?
This chapter contains the following topics:
Topic
NRJED311207EN 12/2011
Page
Safety Precautions
58
Introduction
59
Settings
60
61
64
Commissioning
67
57
Safety Precautions
Before Starting
You are responsible for compliance with all the existing international and national electrical codes
concerning protective earthing of any device.
You should also carefully read the safety precautions described below. These instructions must be
followed strictly when installing, servicing or repairing electrical equipment.
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC, BURNS OR EXPLOSION
Only qualified personnel should install this equipment. Such work should be performed only after
reading this entire set of instructions.
NEVER work alone.
Turn off all power supplying this equipment before working on or inside it.
Always use a properly rated voltage sensing device (EN 61243) to confirm that all power is off.
Before performing visual inspections, tests, or maintenance on this equipment:
Disconnect all sources of electric power.
Assume that all circuits are live until they have been completely de-energized, tested and tagged.
Beware of potential hazards, wear personal protective equipment, and carefully inspect the work
area for tools and objects that may have been left inside the equipment.
Successful VIP operation depends upon proper installation, setting, and operation.
Setting the VIP relay requires relevant expertise in the field of electrical network protection. Only
competent people who have this expertise are allowed to set this product.
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
Never leave the current sensor secondary in open circuit. The high voltage that would result from
opening the circuit is dangerous for the operator and for the equipment.
Never disconnect the VIP protection relay current sensor connectors unless the MV circuit breaker
is in the open position and completely isolated.
Wear insulating gloves to avoid any contact with a conductor that has accidentally been energized.
Wear personal protective equipment in compliance with current regulations.
CAUTION
RISK OF DAMAGE TO THE VIP
Before performing Dielectric (Hi-Pot) or Megger testing on any equipment in which the relay is
installed, disconnect all input and output wires to the VIP relay. High voltage testing may damage
electronic components contained in the VIP relay.
Do not open the VIP case. The VIP relay contains components that are susceptible to electrostatic
discharge. It is assembled in specially equipped premises. The only permitted operation is removal
of the depleted battery from its compartment on a VIP relay.
58
NRJED311207EN 12/2011
Introduction
At a Glance
The VIP is a protection relay that uses digital technology. This technology ensures the reproducibility of
its performance. The whole VIP protection chain has been performance-tested at one time and factorytested at the time of mounting on the circuit breaker. As a result, the VIP is ready to operate without
requiring any additional tests. The VIP is equipped with internal self-tests that continuously provide
information on the state of its electronic components and the integrity of the internal functions.
As a result, when commissioning, user intervention is limited to:
Entering settings
Checking the physical integrity of the complete protection chain: sensor, VIP, Mitop trip unit. If
necessary, this can be used to ensure that it has not suffered any damage during transport and
installation.
NRJED311207EN 12/2011
59
Settings
Determining Settings
All the VIP protection settings are determined beforehand by the design department in charge of the
application and should be approved by the customer.
It is presumed that the study has been carried out with all the attention necessary, or even consolidated
by a discrimination study. All the VIP settings must be available for commissioning.
Entering Settings
More information on entering settings is available in the section describing Settings (see page 30).
NOTE: The sensor rating is not set on the VIP40s and VIP45s, as these only work with the CUa sensors.
Particular Scenario Concerning Network Frequency
The network frequency (50 Hz or 60 Hz) is a parameter that must be known for operation of the VIP40
and VIP45 signal processing algorithms. They therefore have an automatic frequency recognition
system. The recognized value (50 Hz or 60 Hz) is stored and the VIP works permanently with this value.
This stored value will be used each time the VIP starts.
For the VIP to recognize the network frequency and store it, it has to detect a current on phase 1 for a
minimum period of 5 seconds in the range 50 Hz +/- 2 Hz or 60 Hz +/- 2 Hz. This detection happens when
the VIP starts.
Ex works, the VIP is initialized with a network frequency value of 50 Hz.
60
NRJED311207EN 12/2011
Action
Connect the pocket battery module and move the slide switch to the Test (see page 75) position.
Check that the VIP starts and displays the phase currents.
3
Make sure that the status LED
is off. If so, this means that the VIP self-tests do not detect a
malfunction.
Result: The VIP processor is working correctly.
NRJED311207EN 12/2011
Action
Illustration
61
Step
Action
Illustration
62
NRJED311207EN 12/2011
NRJED311207EN 12/2011
Manually:
When the Test/Reset button is pressed
After the Trip test button is released during the 5-second countdown before the trip order is sent
63
For these tests, the MV circuit breaker must not be connected to any MV power source, so that it can be
opened and closed safely.
NOTE: For the primary injection test, it is advisable to control injection stopping by using a circuit breaker
auxiliary contact. Otherwise, if the primary injection is not stopped the VIP may continue to send trip
pulses to no purpose.
Scenario 1:
If the protection settings are low and the injection device used can deliver sufficient current to activate the
protections, the integrity of the VIP and the complete protection chain can be checked directly by primary
injection. This test can be performed by single-phase injection, in succession on each of the 3 phases, in
order to check that the protections trip.
Scenario 2:
Depending on the protection setting values, it is not always possible to inject sufficient primary current to
achieve the level required for tripping. If this is the case, to get round this difficulty, it is possible to activate
a protection temporarily with a low set point dedicated to this test, in order to check operation of the
sensors and the VIP, until the circuit breaker trips. For this test, it is necessary to switch the VIP to its
temporary test mode before activating the protection dedicated to the test.
The rest of this section describes the procedure to be followed for scenario 2.
The characteristics of the test protection are:
Phase overcurrent protection with definite time delay
10 A/5 s
Accuracy: same accuracy as the I> protection function (see page 84)
This protection is independent of the VIP phase and earth fault protection functions. Its temporary nature
guarantees a return to the current settings.
The VIP exits temporary test mode:
Automatically:
After sending the opening order
After 5 seconds
When its power supply from the sensors has been removed
Manually:
When the Test/Reset button is pressed
After the Trip test button is released during the 5-second countdown before the trip order is sent
64
NRJED311207EN 12/2011
Primary Injection Circuit Block Diagram (if the Cubicle has one)
In this case, 1 primary injection winding per phase is prewired in the cubicle and connected to a C60 type
BT circuit breaker. Refer to the cubicle documentation to identify the terminals.
Step
Action
Action
Inject a primary current on phase 1 using the cubicles primary injection circuit if it has a value of 10 A.
3
4
Check that the VIP displays the injected current (accuracy = +/- 5%) and that the
Action
Close the MV circuit breaker.
Activate test protection to trip the circuit breaker by using a pointed tool to press and hold down the Trip
test button:
The Trip LED flashes quickly to indicate that tripping is about to occur.
5 seconds are counted down on the display.
Result: After the countdown, the VIP gives a trip order via the Mitop trip unit and the circuit breaker
opens. The VIP displays the TRIP message.
NOTE: The Trip testbutton must be pressed a second time within 5 seconds of TEST being displayed. If
not, the VIP exits temporary test mode.
NRJED311207EN 12/2011
65
Manually:
When the Test/Reset button is pressed
After the Trip test button is released during the 5-second countdown before the trip order is sent
66
NRJED311207EN 12/2011
Commissioning
Prerequisites
Operational commissioning of the cubicle must not take place before the following checks have been
performed:
Checking the VIP protection relay by one of the methods described above (see page 61)
Cubicle and circuit breaker tests in line with the recommendations mentioned in their specific
documentation
Checks and Settings
In the event of uncertainty or a missing report, check the settings:
VIP40: values of the I> set point
VIP45: values of the I>, Io> and to> set points
Values of the 2 configuration parameters: Discrimination with the LV CB and EF inrush delay
Correct the setting values if required.
Once this check has been made, you should make no further changes to the settings, which are now
deemed to be definitive.
Frequency Value Check
Check that the VIP electrical network has been initialized with the correct rated frequency. To do this,
read the frequency value in the Expert (see page 70) menu.
If it has not, the earth fault protection does not work during automatic recognition of the rated frequency,
which takes around 5 seconds (see page 60). This frequency initialization is essential for the H2 restraint
associated with the earth fault protection to work correctly.
Commissioning
After circuit breaker closing, compare the current circulating in the network with the pick-up current:
If...
Then...
currents
the current in the network is lower than the pick-up current The VIP displays nothing.
NRJED311207EN 12/2011
67
68
NRJED311207EN 12/2011
VIP40, VIP45
VIP40, VIP45 - Maintenance
NRJED311207EN 12/2011
Maintenance
7
Whats in this Chapter?
This chapter contains the following topics:
Topic
NRJED311207EN 12/2011
Page
Expert Menu
70
Preventive Maintenance
73
75
Troubleshooting Assistance
77
79
80
69
Expert Menu
Introduction
The VIP contains an Expert menu that allows the user to view additional information useful for
commissioning or maintaining devices.
Each item in the Expert menu is displayed on 2 screens, displayed alternately.
The items in the Expert menu are as follows:
Io earth fault current value (VIP45 only)
Cause of the last trip: OC, EF or TRIP
Network frequency: 50 or 60 Hz
Phase overcurrent protection set point: I> selector switch position
Earth fault protection set point: Io> selector switch position (VIP45 only)
Earth fault protection time delay: to> selector switch position (VIP45 only)
"Advanced settings" selector switch position
Activation of the minimum tripping time
Type of VIP
Last failure detected by the VIP
Method
Step
Action
To display the Expert menu, press and hold down the Imax. button for 15 seconds.
Items in the Expert menu are displayed on 2 screens for each item.
It is possible to:
Scroll through all the items automatically by holding down the Imax. button
Stay on a given item by releasing the Imax. button
The next item can be viewed after pressing the Imax. button.
70
NRJED311207EN 12/2011
List of Screens
Screen
Description
Earth fault current value (VIP45 only)
Network frequency:
50 Hz
60 Hz
NOTE: The VIP automatically detects the network frequency (50 or 60 Hz), from phase
1. The Expert menu screen displays the frequency detected by the VIP and should
correspond to the frequency of the protected network.
Earth fault protection set point (Io> selector switch position, VIP45 only)
Earth fault protection time delay (to> selector switch position, VIP45 only)
NRJED311207EN 12/2011
71
Screen
Description
Advanced settings selector switch position:
The first two characters (ON/OFF) correspond to the discrimination setting with an
LV breaker (Discrimination with the LV CB).
The last two characters (ON/OFF) correspond to the earth fault protection inrush
current delay setting (EF inrush delay).
Type of VIP:
100 P for VIP40 100 A
200 P for VIP40 200 A
100 E for VIP45 100 A
200 E for VIP45 200 A
72
NRJED311207EN 12/2011
Preventive Maintenance
Introduction
To obtain maximum availability of the installation, it is essential to ensure that the VIP is operational at all
times. The VIP internal self-tests alert the user in the event of failure of the VIP (see page 55).
Nonetheless, elements outside the VIP are not subject to these self-tests and it is therefore necessary to
carry out regular preventive maintenance..
Apart from the battery, which can be accessed on the rear panel, nothing inside the VIP can be replaced
by the user.
List of Interventions
The table below gives the typical frequency of interventions. The intervals between visual inspections
depends on the installation operating conditions.
Intervention
Frequency
Routine check
Annual
Every 5 years
Routine Check
status LED are working correctly. To perform this test, the VIP must be supplied with power.
If the network load is insufficient, power the VIP using the pocket battery module (see page 75).
Step
NRJED311207EN 12/2011
Action
Illustration
73
Step
3
Action
Illustration
4
The
74
NRJED311207EN 12/2011
1
2
3
4
5
6
7
8
Not used
3-position slide switch:
Left = Test position; Center = OFF; Right = pocket flashlight
Not used
Green LED for checking the battery status
Two illumination LEDs
Two 1.5 V type AA batteries (not supplied)
Connector for the VIP test socket
Stylus/screwdriver
NRJED311207EN 12/2011
Action
Illustration
75
Step
Action
Illustration
Refer to...
Routine check
NOTE: At the end of the checks and inspections, de-energize the VIP by positioning the pocket battery
module switch on 0 before disconnecting it from the VIP.
76
NRJED311207EN 12/2011
Troubleshooting Assistance
Introduction
The paragraphs below list the actions to be taking after observing abnormal VIP behavior.
LEDs and Display Unit Off
Symptom
Possible Causes
Action/Remedy
Refer to...
Commissioning
(see page 57)
Preventive
Maintenance
(see page 73)
In this case, the VIP is no longer operational. Make a note of the code and change the VIP (see page 79).
NRJED311207EN 12/2011
The
status LED is flashing
Cyclic display of an ERROR screen containing a 2-digit code.
77
Fault Code
Possible Causes
Action/Remedy
Refer to...
Er 19
Checking the MV
Circuit Breaker
(see page 61) Trip
Circuit
Removing the VIP
(see page 79)
Er 18
Er 16
Er 15
Er 14
78
Symptoms
Possible Causes
MV circuit breaker
open and no fault
indication LED lit up
on the VIP.
Action/Remedy
Refer to...
NRJED311207EN 12/2011
DANGER
HAZARD OF ELECTRIC SHOCK, ELECTRIC ARC OR BURNS
Wear insulating gloves to avoid any contact with a conductor that has accidentally been energized.
Open the MV circuit breaker so you can disconnect the VIP protection relay from the sensors.
Action
If the VIP allows you to, read and make a note of the last trip that occurred. Use the pocket battery module
if necessary.
Make a note of the symptoms observed, in particular the failure code displayed.
End of Life
If the VIP needs to be replaced:
Step
NRJED311207EN 12/2011
Action
Dismantle the VIP in accordance with the End-of-Life Recycling for the VIP document.
79
Action
Illustration
Battery Recycling
WARNING
HAZARD OF EXPLOSION
Failure to follow these instructions can result in death, serious injury, or equipment damage.
The used battery should be disposed of by an approved certified recycling company in compliance with
current regulations.
80
NRJED311207EN 12/2011
Battery Characteristics
Replacement Procedure
When depleted, the battery is replaced as follows:
Step
Action
Insert a battery with the above characteristics, respecting the polarity (+ facing up).
Test the battery by pressing the Test/Reset button for 2 to 3 seconds: the Trip LED should remain on clearly
without fading for the whole time the button is pressed.
Cleaning Product
To clean the product (especially when dusting), simply use a damp cloth.
NRJED311207EN 12/2011
81
82
NRJED311207EN 12/2011
VIP40, VIP45
VIP40, VIP45 - Characteristics
NRJED311207EN 12/2011
Characteristics
8
Whats in this Chapter?
This chapter contains the following topics:
Topic
NRJED311207EN 12/2011
Page
Function Characteristics
84
Technical Characteristics
86
Environmental Characteristics
87
Internal Operation
89
83
Function Characteristics
General Remarks
In the tables below:
In is the phase CT primary rated current.
All the accuracy values are stated in the reference conditions (IEC 60255-6). Unless stated otherwise,
the sensor accuracy is included in the values indicated.
Sensor Rating
Sensor
Characteristics
Values
Phase CT
CUa: 200 A
Values
Measuring range
0...999 A
Accuracy
Resolution
Display format
3 digits
Values
Measuring range
0...999 A
Accuracy
Resolution
Display format
3 digits
Time delay
Characteristic
times
84
Values
Settings (A) for:
VIP40 200 A
VIP45 200 A
5, 6, 8, 10, 12, 15, 20, 25, 30, 35, 45, 55, 70, 85, 105, 130, 160,
200
5, 6, 7, 8, 10, 12, 15, 18, 21, 25, 30, 35, 40, 50, 60, 70, 80, 100
Accuracy
+/- 5% or 0.01 ln
Transient overshoot
Setting
None
Accuracy
Overshoot time
< 40 ms at 2 I>
NRJED311207EN 12/2011
Characteristic
times
Values
Settings (A) for:
VIP45 200 A
Accuracy
+/- 5% or 0.01 ln
Transient overshoot
< 10%
DT settings (s)
Accuracy
+/- 2% or -15/+ 25 ms
Overshoot time
< 40 ms at 2 Io>
NRJED311207EN 12/2011
85
Technical Characteristics
General Characteristics
Characteristics
Values
Dimensions
Weight
380 g/0.84 lb
Type of battery
10 years(1)
150 mW
NOTE:
(1)
Current Inputs
The VIP current inputs are designed to operate exclusively with the dual core CUa sensor.
Characteristics
Values
1.3 In
Frequency
50 Hz, 60 Hz
Values
Pick-up time
10 A
< 120 ms
12 A
< 80 ms
16 A
< 30 ms
240 A
< 20 ms
1 kA
< 15 ms
The pick-up time is the time the VIP takes to start when not supplied with power. In the event of a fault,
this time is added to the time delay that has been set. The pick-up time values are indicated for a fault
current equal to 1.2 times the tripping set point.
Characteristics
Pick-up current
Values
Sensor
Single-phase
Three-phase
CUa
6A
4A
NOTE: Around the pick-up current, you may see the display switch on and off. This is quite normal and
does not affect operation of the protection functions.
86
NRJED311207EN 12/2011
Environmental Characteristics
Electromagnetic Compatibility
Electromagnetic Compatibility
Standard
Level/C Values
lass
Emission
Radiated disturbances
CISPR 22
CISPR 16
Immunity
tests
Radiated radiofrequency
fields
IEC 61000-4-3
IACS - E10
IEC 61000-4-2
8 kV air; 6 kV contact
Electrostatic discharge
IEC 60255-22-3
IEC 60255-22-2
IACS - E10
8 kV air; 6 kV contact
IEC 61000-4-8
Conducted radiofrequency
disturbances
IEC 61000-4-6
IEC 60255-22-6
IACS - E10
Electrical fast
transients/burst
IEC 61000-4-4 4
IEC 60255-22-4
IACS - E10
IEC 61000-4-18 3
IEC 61000-4-18 3
Surges
IEC 61000-4-5
IEC 60255-22-1
2 kV MC, 1 kV MD
IEC 60255-22-5 3
2 kV MC, 1 kV MD
IACS - E10
1 kV, 0.5 kV MD
Mechanical Robustness
Standard
Level/C Values
lass
Energized
IEC 60255-21-1 2
IACS - E10
Mechanical Robustness
Deenergized
Enclosure
protection
Packaging
NRJED311207EN 12/2011
Vibration response
Shock response
IEC 60255-21-2 2
Seismic response
IEC 60255-21-3 2
2 Gn horizontal, 1 Gn vertical
Inclination
IEC 60092-504
static: 22.5
dynamic: 22.5
Vibration withstand
IEC 60255-21-1 2
Shock withstand
IEC 60255-21-2 2
Jolt withstand
IEC 60255-21-2 2
Tightness
IEC 60529
IEC 62262
IK7
2J
EN 22248
87
Climatic Withstand
Climatic Withstand
Standard
Level/C Values
lass
IEC 60068-2-1
Ad
Bd
Corrosive
atmosphere
IEC 60068-2-2
Temperature variation
IEC 60068-2-14 Nb
Temperature variation
in damp heat
IEC 60068-2-30 Db
Exposure to cold
IEC 60068-2-1
Ab
IEC 60068-2-2
Bb
Temperature variation
IEC 60068-2-14 Na
Temperature variation
in damp heat
IEC 60068-2-30 Db
Salt mist
2-gas test
IEC 60068-2-60 Ke
(1)
NOTE:
Below 25C, the display may be more difficult to read. This does not affect operation of the protection
functions.
Safety
Safety
Standard
Values
General
IEC 61010
Power frequency
dielectric withstand
IEC 61010
IACS - E10
2 kV 50 Hz or 60 Hz
Surge
IEC 61010
Insulation resistance
IACS - E10
Fire withstand
IEC 60695-2-11
IEC 60695-2-10
850C (1562F)
Certification
Reference Document
Certification
88
NRJED311207EN 12/2011
Internal Operation
Block Diagram
The VIP is a multifunctional digital protection relay with a self-powered supply.
Electronic Components
The control electronics consist of the following items:
An ASIC component, responsible mainly for acquisition and analog/digital conversion of the current
inputs.
A microprocessor, responsible for all processing operations:
Protection and metering
Alarm and annunciation
Management of the user-machine interface
Self-tests
An SRAM memory, that contains all the VIP working data. This data is not saved if the power supply
fails.
A Flash memory, containing the processing program.
A standard EEPROM memory, that mainly contains the users parameters and settings, as well as the
fault log.
These values are saved if the power supply fails.
NRJED311207EN 12/2011
status LED.
89
Current Inputs
The VIP is designed to be connected exclusively to the dual core sensor, type CUa (200 A). This sensor
consists of 2 windings per phase, one winding providing the VIP power supply, the other winding enabling
the VIP to measure the phase currents. The earth fault current is measured by taking the sum of the 3
phase currents inside the sensor.
Measurement circuit:
The VIP incoming electronic circuit adapts the signals from the metering sensors for processing by an
analog to digital converter (ASIC). Low-pass filtering allows harmonic numbers up to 13 at 60 Hz and 15
at 50 Hz to pass through.
Power supply circuit:
The VIPs self-powered supply uses the energy available at the secondary of the CUa sensor power
supply windings.
Self-Powered Supply
This power supply supplies the power required by the VIP to perform its protection functions without
having recourse to any other external power source. The power required comes from the specific current
sensor integrated in the circuit breaker.
The VIPs self-powered supply has redundant regulation guaranteeing peoples safety by restricting the
sensor voltage to a safe value.
Display
The segmented display, based on simple, robust technology can withstand several years of operation in
a harsh environment: -40... +70C (-40...+158F).
The display is managed directly by the microprocessor.
Since the VIP is entirely self-powered, it is unable to backlight the display. However, it has sufficient
contrast to be viewed with a minimal external light source.
Battery
The battery maintains the tripping indicator status for 24 hours after a a power outage.
The battery life is more than 10 years in normal use. Absence or failure of the battery has no effect on
the VIP protection functions.
Safety of People
The user is permanently protected from hazardous voltages on the front panel. This is achieved by
restricting the voltages at the product input to safe values. The user is also asked to connect the product
to a protective earth.
90
NRJED311207EN 12/2011
NRJED311207EN
Schneider Electric Industries SAS
35, rue Joseph Monier
CS30323
F - 92506 Rueil Malmaison Cedex
www.schneider-electric.com
As standards, specifications and designs change from time to time, please ask for confirmation
of the information given in this publication.
12/2011