Application
The 2WR6 is a ready to build in heat meter for heat consumption measurement in flats. It is
not appropriate for systems with water-glycol mixtures.
Landis+Gyr GmbH
UH 504-101f
page 1/13
01.07.2005
Method of operation
The quantity of thermal energy transferred from the heating water to the heat consumer over a
defined period of time is proportional to the temperature difference between the flow and return and the volume of heating water that has flowed through.
The heating water volume is measured in the measuring tube by ultrasonic pulses which are
transmitted in the direction of flow and against the direction of flow. Downstream, the delay
between the transmitter and receiver is reduced, upstream it is increased. The heating water
volume is then calculated using the measured values for the delay.
The flow and return temperatures are determined using platinum resistors.
The heating water volume and the difference in temperature between the flow and return are
multiplied and its product integrated. The result which is the consumed quantity of thermal
energy or cold is registered and displayed in the physical units kWh / MWh, or MJ / GJ, the
quantity of volume in m3.
Calculator
A standard calculator is used for all flow rate values with identical operation and an integrated
service unit.
Under these conditions the life time of the battery remains unchanged.
Display content
The heat meter display is subdivided into two levels and may differ from the standard shown
below. The user loop display (level 1) is advanced cyclically each time the button is pressed
briefly. ( shows the type of value displayed)
Landis+Gyr GmbH
User loop
0054567
kWh
00065.43
Cumulated volume
888888
kWh
Segment test
Info
F---
Info
If button is held pressed for 10 seconds, the display switches from the user loop to the service
loop (level 2).
The service loop is exited by holding the button pressed for 3s or automatically after 30
minutes.
Service loop
kW
47
04.06.02
Date
84
786
Bh
Operating hours
56
Fh
Missing hours
3792701
PulSE
G
CH
Info
Info
123
Info
2345678
Info
18.02.01
F0
Info
3- 01
FW
Firmware version
Info
31.12.01
Prev. year
Prev. year
00923.12
Prev. year
12
Fh
Prev. year
- -.- -.- -
01.06.02
Info
Prv. month
Prv. month
00923.12
Prv. month
12
Fh
Prv. month
The monthly values are displayed at the end of the service loop. One of the previous 15
monthly values can be selected by pressing the button briefly. The corresponding data are
then opened by pressing the button for 3s. Each time the button is pressed briefly the next
value for the selected month is displayed.
Afterwards the corresponding monthly set day is displayed again and the next month can be
selected by pressing the button briefly.
Resolution of display
Heat
Heat
Volume
Power
Temperature
Temperature difference
1
0,001
0,01
0,1
1
0,1
kWh
MWh
m
kW
C
K
Landis+Gyr GmbH
Monthly values
The calculator stores for 15 months at the set day the values of
which can be read by using the PappaWin Standard software via the optical interface.
Power supply
6 or 11 year battery
or
as special version with 1.5m cable for 24V AC/DC external supply, with galvanic insulation to the electronic:
Voltage range AC:
12V to 36V
Voltage range DC:
12V to 42V
Temperature sensor
Approval
Technical data of
calculator
Landis+Gyr GmbH
EN 1434 class 3, PTB and in many European countries. Class 2 on request, dependent from
the country.
Installation
Control cable length
Temperature range
Temperature difference
range
Switch-off limit
Heat coefficient
t measurement error
without sensor (EN 1434)
Ambient temperature
Storage temperature
Protection class
Dimensions
Volume measuring
units
qp
m/h
Length
mm
Thread
G
Pressure stage
0.6
1.0
1.5
2.5
110
110
110
130
PN16
PN16
PN16
PN16
0.6
1.0
1.5
2.5
190
190
190
190
1
1
1
1
PN16
PN16
PN16
PN16
The specified lengths correspond to the overall lengths of conventional vane-type meters.
Technical data for flow measurement
Nominal flow rate
Metrological class
Maximum flow
Minimum flow
Operating limit ***
Pressure drop at qp,
(110 resp. 130/190mm)
Flow rate at p = 1 bar,
(110 resp. 130/190mm)
Weight (110/190mm)
Mounting orientation
Straight pipe sections
Temperature range
Maximum flow rate
Nominal pressure
Admissible measuring
error acc. to
EN 1434 (class 3)
qp
m3/h
0.6
1:100*
1.2
6**
2,4
140/176
1.0
1:100*
2.0
10**
4,0
60/76
1.5
1:100*
3,0
15**
6,0
130/162
2.5
1:100*
5,0
25**
10
205/140
m3/h
l/h
l/h
mbar
KV
1.6/1.4
4.1/3.6
4.2/3.7
5,5/6.7
m3/h
1 / 1,5
1 / 1,5
1 / 1,5
any
not necessary
15 to 105 C
2,8 x qp
1.6 MPa (PN 16)
1,5
kg
qs
qi
PN
3 + 0.05 qp/q
max. 5%
* in Germany 1:50
** in Germany: multiply value by 2
Notes
Regulations for the use of heat meters must be observed, in particular EN 1434,
Part 6!
Ensure by appropriate mounting of the meter that flooding the meter or water dripping is
avoided.
Heat meter safety marks relevant for calibration must not be damaged or removed!
Doing so void the warranty and calibration validity of the device.
The transport of the flow meter is permitted only in the original package.
Installation and commissioning instructions are added to each meter
Landis+Gyr GmbH
Nominal
Pressure
PN
qp 0,6
110
G 3/4
16
qp 1,0
110
G 3/4
16
qp 1,5
110
G 3/4
16
qp 0,6
110
G 3/4
16
qp 1,0
110
G 3/4
16
qp 1,5
110
G 3/4
16
Mounting element for temperature sensor DS, M 10 x 1 mm 1/2"
with Cu seal
Fitting R 1/2 " with seals
pair
Order No.
2WR6051-7BBxx-xxxx
2WR6151-7BBxx-xxxx
2WR6211-7BBxx-xxxx
2WR6051-7CBxx-xxxx
2WR6151-7CBxx-xxxx
2WR6211-7CBxx-xxxx
WZTA12
WZME34
qp 0,6
110
G 3/4
qp 1,0
110
G 3/4
qp 1,5
110
G 3/4
qp 0,6
110
G 3/4
qp 1,0
110
G 3/4
qp 1,5
110
G 3/4
Protection pocket G B MS, 5.2 x 35 mm
for temperature sensors 5 x 45 mm
Fitting R 1/2 " with seals
Landis+Gyr GmbH
Nominal
Pressure
PN
Order No.
16
16
16
16
16
16
2WR6051-7HBxx-xxxx
2WR6151-7HBxx-xxxx
2WR6211-7HBxx-xxxx
2WR6051-7JBxx-xxxx
2WR6151-7JBxx-xxxx
2WR6211-7JBxx-xxxx
WZTM35
pair
WZME34
Overall length
mm
Connection
Nominal
Pressure
PN
qp 0,6
qp 1,0
qp 1,5
qp 2,5
qp 2,5
qp 0,6
qp 1,0
qp 1,5
qp 2,5
qp 2,5
190
190
190
130
190
190
190
190
130
190
G1
G1
G1
G1
G1
G1
G1
G1
G1
G1
16
16
16
16
16
16
16
16
16
16
Order No.
2WR6071-7BBxx-xxxx
2WR6171-7BBxx-xxxx
2WR6231-7BBxx-xxxx
2WR6361-7BBxx-xxxx
2WR6381-7BBxx-xxxx
2WR6071-7CBxx-xxxx
2WR6171-7CBxx-xxxx
2WR6231-7CBxx-xxxx
2WR6361-7CBxx-xxxx
2WR6381-7CBxx-xxxx
Mounting element for temperature sensor DS, M 10 x 1 mm WZTA12
1/2", with Cu seal
pair
WZME1
Nominal
Pressure
PN
qp 0,6
190
G1
16
qp 1,0
190
G1
16
qp 1,5
190
G1
16
qp 2,5
130
G1
16
qp 2,5
190
G1
16
qp 0,6
190
G1
16
qp 1,0
190
G1
16
qp 1,5
190
G1
16
qp 2,5
130
G1
16
qp 2,5
190
G1
16
Protection pocket G B MS, 5.2 x 35 mm
for temperature sensors 5 x 45 mm
Fitting R 3/4 " with seals
pair
Landis+Gyr GmbH
Order No.
2WR6071-7HBxx-xxxx
2WR6171-7HBxx-xxxx
2WR6231-7HBxx-xxxx
2WR6361-7HBxx-xxxx
2WR6381-7HBxx-xxxx
2WR6071-7JBxx-xxxx
2WR6171-7JBxx-xxxx
2WR6231-7JBxx-xxxx
2WR6361-7JBxx-xxxx
2WR6381-7JBxx-xxxx
WZTM35
WZME1
Ordering data:
MLFB-digit: 1
10 11 12 -
13 14 15 16
urement cycle);
With standard battery for 6 years lifetime
With M-bus; *
Landis+Gyr GmbH
MLFB-digit: 1
10 11 12 -
13 14 15 16
Z*
Z*
Z*
Z*
Z*
Z*
Z*
Z*
Z*
Display: kWh;
Display: MJ;
mark.
Certified according to CEN 1434 class 3. **
Landis+Gyr GmbH
Example of type
codes
Type reference:
2WR6
38
- 7B
3 (-Z) xyz
Basic type
Nominal flowrate
Integration
Temperature
sensor
Calculator design
Power supply
Communication
interface
Manufacturer's
label
Country
Unit of energy
Certification
ATG(s)
2 WR 6 0 5 1 - 7 B B 1 0 - 0 Z B 2
P 2 A
The most used ATGs can be taken from the table next page:
Landis+Gyr GmbH
Meaning
ATG
14th digit is Z
P1A
14th digit is Z
P2A
14th digit is Z
14th digit is Z
14th digit is Z
14th digit is Z
14th digit is Z
14th digit is Z
14th digit is Z
P3A
P4A
P7A
P5B
P6B
P7B
P8B
11th digit is 1
IT 08
12th digit is 1
KV
Description
Ordering No.
MTS-T34-110
for mounting of the T sensor in flow, a spacer 100mm and of meter fittings
(in transparent bag, including gaskets)
Mounting set for 130mm, 3/4" consisting of a protection pocket (brass)
MTS-T01-130
for mounting of the T sensor in flow, a spacer 130mm and of meter fittings
(in transparent bag, including gaskets)
Special mounting
accessories for tubes
Landis+Gyr GmbH
WZTS43V
WZT-M35
WZT-M50
WZT-A12
WZT-K1
WZT-K12
WZT-K34
WZT-G10
WZT-G12
WZT-GLG
WZM-E34
WZM-E1
Kit extension from 110 mm G3/4 B to 130 mm G 1 B (in pairs with gaskets)
Kit extension from 110 mm G3/4 B to 190 mm G 1 B (in pairs with gaskets)
Spacer for heat meter G 3/4 - 110 mm, incl. flat gaskets
WZM-V130.1
WZM-G130
WZM-G190
WZM-V190
WZM-G110
Optical read head with 9 pin plug for PC (COM) interface (PappaWin)
not for pulsing interface on test rigs
9956467001
Software PappaWin, first license, CD-ROM, with dongle for parallel port
2WR9300-0AA11-0A
2WR9300-0AC11-0A
2WR9300-1AC11-0A
2WR9300-0AD11-0A
2WR9300-1AD11-0A
2WR9300-2AC11-0A
2WR9300-3AC11-0A
Software PappaWin Profi, first license, CD-ROM, with dongle as USB stick 2WR9300-2AD11-0A
Software PappaWin Profi, second license, CD-ROM, with dongle as USB
stick
2WR9300-3AD11-0A
Landis+Gyr GmbH
Dimensions
Meter dimensions:
Mounting element:
Wall mounting:
Protection pocket:
Landis+Gyr GmbH
P.O. Box 4806
D-90026 Nrnberg
Germany
www.landisgyr.com
Landis+Gyr GmbH