CONTENT OF PRESENTATION
PRELIMINARY
PRODUCT FEATURES
PROJECT REFERENCE
❑ Minimize infection
❑ Maintain staff comfort
❑ Maintain patient comfort
One method of reducing the time and/or number of microbes to which a person is exposed is by
increasing the dilution rate of clean air into a space. This reduces the exposure time of microorganisms
generated within the room by objects, staff, or the patient. Table bellow indicates the length of time it
takes for a room to be flushed with filtered air, assuming perfect mixing.
2 138 207
4 69 104
6 46 69
8 35 52
10 28 41
12 23 35
15 18 28
20 14 21
50 6 8
Source: CDC (2003). Note: assumes perfect mixing
PRELIMINARY
AIR CHANGES REQUIREMENT
Year Source Temperature, °F [°C] RH, % ACH, ach OA, ach
The recommended air changes per hour (ACH) 1971 ASHRAE (1971) 68 to 76 [20 to 25] 50 25 5
1974 U.S HEW 68 to 76 [20 to 25] 50 to 60 25a 25
value has been 15-25 for 40 years. 1974 U.S HEW 68 to 76 [20 to 25] 50 to 60 25b 5
1978 U.S HEW 68 to 76 [20 to 25] 50 to 60 15a 15
1978 U.S HEW 68 to 76 [20 to 25] 50 to 60 25b 5
1983 AIA 70 to 75 [21 to 24] 45 to 60 20 4
1987 AIA 70 to 75 [21 to 24] 50 to 60 15 3
The current recommendation in the FGI 1987 ASHRAE (1987) 68 to 76 [20 to 25] 50 to 60 15/25 15/5
1992 AIA 70 to 75 [21 to 24] 50 to 60 15 3
Guidelines (AGI 2010) and ANSI/ASHRAE/ASHE 1999
2001
ASHRAE (1999)
AIA
62 to 80 [20 to 27]
68 to 73 [20 to 23]
45 to 55
30 to 60
25
15
5
3
2002 NFPA (2002) 68 to 73 [20 to 23] 50 25 5
Standard 170-2008 is 20 ach supply including 4 2003 ASHRAE (2003a) 62 to 80 [20 to 27] 45 to 55 25 5
2003 ASHRAE (2003b) 68 to 75 [20 to 24] 30 to 60 25 5
ach of outdoor air. 2005 NFPA (2005) 68 to 73 [20 to 23] 35 25 5
2006 AIA 68 to 73 [20 to 23] 30 to 60 15 3
2008 ASHRAE (2008) 68 to 75 [20 to 24] 20 to 60c 20 4
2010 FGI (2010 68 to 75 [20 to 24] 20 to 60c 20 4
Sources: Adapted from references cited in table, along with documents of the American Institute
Note that 100% outdoor air system have not of Architects (AIA) and the U.S. Department of Health, Education, and Welfare (U.S. HEW).
Notes:
been recommended since early 1980s. a. Requirement if 100% OA was preferred.
b. Requirement if recirculation was preferred.
c. Some AHJs require a minimum relative humidity (RH) of
30%.
PRELIMINARY
AIR MOVEMENT
Operating rooms must be at a positive pressure relative to adjacent corridors to prevent potentially harmful
microorganisms from entering the operating room. In contrast, airborne infection isolation (AII) rooms must be
maintained negative because patients in these rooms may be highly infectious with diseases such as tuberculosis
or SARS.
PRELIMINARY
PRESSURIZATION
Operating rooms must be designed for a positive
pressure differential of 0.01 in. of water [2.5 Pa], this
will require a 200–400 cfm [94–189 L/s] offset.
dp 15.8ᵒC
dp 12.0ᵒC
dp 11.1ᵒC
dp 9.6ᵒC
dp 5.1ᵒC
dp -0.3ᵒC
dp -3.2ᵒC
PRELIMINARY
CHILLED WATER SPOT
The figure shows a “spot” when supply air is about 7.8ᵒC dew point. At this condition, virtually all
of the commonly requested combinations of temperature and humidity can be maintained using
chilled water systems.
dp 8.4ᵒC
dp 7.8ᵒC
PRELIMINARY
OPERATING ROOM COOLING LOAD
4%
10%
43%
Reheat
Minimum OA
43% Lighting & Equipment
Staff/Patient
PRELIMINARY
ROOM SIZE REQUIREMENT
Minor Surgery Room (36 m2) General Surgery Room (42 m2)
Mayor Surgery Room (50 m2) Cardiac Surgery Room (60 m2)
PRELIMINARY
OPERATING ROOM UNIT SPECIFICATION DATA
No Kriteria Ruang Area Volume Min Total ACH Min Outdoor ACH Design Temperature RH
1 R. Operasi Minor 36 108 25 5 19-24 40-60
2 R. Operasi Umum 42 126 25 5 19-24 40-60
3 R. Operasi Mayor/Khusus 50 150 25 5 19-24 40-60
4 R. Operasi Cardiac 60 180 25 5 19-24 40-60
Fresh Air
Intake
HEPA Filter Motorized
Volume Damper Fan Motor & EH
Mini Chiller
Remote Control
Notes:
Control Wiring
Ducting Supply
Ducting Return
CHWS
CHWR
MOTOR OPTION
• 380-415 Volt / 3 phase/ 50 Hz ( standard)
• 230/380/440 Volt/ 3 phase/ 60Hz
• Motor efficiency from IE1, IE2, IE3 up to IE4 (EC motor)
• Motor with space heater & Thermistor
• Explosion / Flame proof
• 2, 4, 6, 8 poles
• Variable frequency drives
PRODUCT FEATURES
ELECTRIC HEATER
Electric heaters are optional with either single step or
multi step of heating process. It depends much on the
heating capacity. Heaters are available in 220-240V and
the wiring can be in single phase / 3 phase for contactor
or thyristor control.
PRODUCT FEATURES
FILTER SECTION
PRODUCT FEATURES
MINI CHILLER INVERTER
Optimized fan blade Dust and water protection grade reaching IP54
Energy-saving variable speed fan motor
Environment-friendly refrigerant R410A
Imported 480-step
Plate heat exchanger with new type of heat exchange Electronic expansion valve
technology by cross forced convection
◆ Optional configurations:
Unit model UAL 030ER5 040ER5 050ER5 060ER5 070ER5 080ER5 100DR5 120DR5 150DR5
Standard
15 14 18 22 24 22 25 22 18
external lift (m)
Optional
— — — — — — 31 28 26
external lift (m)
PRODUCT FEATURES
MODULAR CHILLER
5) Investment Flexibility
• Modular chiller can be installed separately in phases
to reduce high initial investment and installation cost
PRODUCT FEATURES
MODULAR CHILLER
6) Easy Installation
• It can be lifted without large lifting tools
• Can be installed on rooftop, balcony or any outdoor space
• Space utilization can be maximized in a non-uniform compound
7) Partial Loading
• Two separate refrigerant circuits with individual compressor
• Better reliability and energy efficiency during low loading operations
8) Redundant Operation
• Independent refrigerant system design
• Unit can still operate with either one system breaks down
2009 PEMBANGUNAN GEDUNG RS. UNAIR GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 3 DRM (MALAYSIA) SURABAYA
2011 RSCM NEC GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 13 DRM (MALAYSIA) JAKARTA
2011 RS Mayapada COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 33 DRM (MALAYSIA) JAKARTA
2012 RS Fatmawati GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 2 DRM (MALAYSIA) JAKARTA
2012 RSPP Sentul COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 7 DRM (MALAYSIA) SENTUL
2013 RS Semen Padang COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 3 DRM (MALAYSIA) PADANG
2013 RSUD Kota Tangerang AHU GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 12 DRM (MALAYSIA) TANGERANG
2013 RS Persahabatan COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD MAC 3 SHENZHEN JAKARTA
2013 RS Persahabatan COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD M4AC 2 DAMA (MALAYSIA) JAKARTA
2013 RS CULUMBIA COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 38 DRM (MALAYSIA) SEMARANG
2014 RS Gading Pluit COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAE050C 2 DAMA (MALAYSIA) JAKARTA
2014 RSUD Tarakan GOVERNMENT HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL230 2 SHENZHEN JAKARTA
2014 RS Unand Padang GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 5 DRM (MALAYSIA) PADANG
2014 RSUP Fatmawati GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 8 DRM (MALAYSIA) JAKARTA
2014 RSPI add COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 3 DRM (MALAYSIA) JAKARTA
2014 RSUD BANJARBARU GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 4 DRM (MALAYSIA) BANJARBARU
2014 RSUD BANJARBARU GOVERNMENT HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD MAC210D5 1 SHENZHEN BANJARBARU
2015 RS. DIPONEGORO 21 GOVERNMENT HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAE120 2 DAMA (MALAYSIA) KLATEN
2015 NATIONAL HOSPITAL COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAP100C 1 DAMA (MALAYSIA) SURABAYA
2015 CIPUTRA BANNJARMASIN COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL230 6 DAMA (MALAYSIA) BANJARMASIN
2015 SCM TEGOLREJO COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 7 DRM (MALAYSIA) SEMARANG
2015 NATIONAL HOSPITAL ADD COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAP100C 1 DAMA (MALAYSIA) SURABAYA
2015 RS TELOGOREJO GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 27 DRM (MALAYSIA) SEMARANG
2016 RS. TELOGOREJO GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 23 DRM (MALAYSIA) SEMARANG
2016 RSP UNAIR COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 7 DRM (MALAYSIA) SURABAYA
2016 RS SINGARAJA BALI COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 2 DRM (MALAYSIA) SINGARAJA
2016 RS SINGARAJA BALI COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL340 2 DAMA (MALAYSIA) SINGARAJA
2016 RSPI BINTARO JAYA ADD COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 1 DRM (MALAYSIA) BINTARO
2016 RS. ABDI WALUYO GOVERNMENT HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAE120 3 DAMA (MALAYSIA) JAKARTA
2016 RSUD DEPOK GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 7 DRM (MALAYSIA) DEPOK
2016 RS TARAKAN COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL230 3 DAMA (MALAYSIA) TARAKAN
2016 RSUD JAKARTA GOVERNMENT HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL-ER 2 SHENZHEN JAKARTA
2017 SARANA SURYA JAYA COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL060 3 DAMA (MALAYSIA) SURABAYA
2017 Yarsi COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 30 DRM (MALAYSIA) JAKARTA
2017 RSUD Bogor tahap 2 GOVERNMENT HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL210 10 DAMA (MALAYSIA) BOGOR
2017 RSUD Bogor tahap 2 GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 5 DRM (MALAYSIA) BOGOR
2017 Persahabatan AHU GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 1 DRM (MALAYSIA) JAKARTA
2017 RS Boromeus Bandung COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL060ER 4 SHENZHEN BANDUNG
2018 RS Pelabuhan Palembang COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 8 DRM (MALAYSIA) PALEMBANG
2018 RS OMNI Pekayon COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 6 DRM (MALAYSIA) BEKASI
2018 RSPI Pondok Indah Area IVF Lantai 6 COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 2 DRM (MALAYSIA) JAKARTA
2018 RS IMC COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL210DM5 2 DAMA (MALAYSIA) JAKARTA
2018 RS IMC COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 4 DRM (MALAYSIA) JAKARTA
2018 RSCM GOVERNMENT HEALTH CARE/MEDICAL BUILDING AHU DDM 1 DRM (MALAYSIA) JAKARTA
2018 Eka Hospital Cibubur COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL340D5 4 SHENZHEN CIBUBUR
2018 Eka Hospital Cibubur COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 4 DRM (MALAYSIA) CIBUBUR
2018 Eka Hospital Bekasi COMMERCIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL340D5 4 SHENZHEN BEKASI
2018 Eka Hospital Bekasi COMMERCIAL HEALTH CARE/MEDICAL BUILDING AHU DDM 4 DRM (MALAYSIA) BEKASI
2018 Otsuka Lawang 2018 INDUSTRIAL HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL UAL340D5 2 SHENZEN LAWANG
2019 RS Koja Gedung A GOVERNMENT HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL210DM5M 3 DAMA (MALAYSIA) JAKARTA
2019 RS Koja Gedung A GOVERNMENT HEALTH CARE/MEDICAL BUILDING CHILLER AIR COOLED SCROLL STANDARD UAL230DM5M 9 DAMA (MALAYSIA) JAKARTA
DAIKIN 24/7 CUSTOMER CARE SERVICE
Call us at anytime...
….We ensure our
customer comfort and
peace of mind ☺
Call Center
Jakarta : +6221 - 7943939
Surabaya : +6231 - 5343939
Website : www.daikinapplied.co.id
JAKARTA OFFICE
L'Avenue Office Building Lt.25
Jl.Raya Pasar Minggu Kav.16, Pancoran, Jakarta Selatan 12780
Indonesia
Phone : +62-21-8066-7118
Fax : +62-21-8066-7119
JAKARTA OFFICE
L'Avenue Office Building Lt.25
Jl.Raya Pasar Minggu Kav.16, Pancoran, Jakarta Selatan 12780
Indonesia
Phone : +62-21-8066-7118
Fax : +62-21-8066-7119