Albatros2 - Hydraulic Partial Diagrams and Auxiliary Functions
Albatros2 - Hydraulic Partial Diagrams and Auxiliary Functions
Albatros2 - Hydraulic Partial Diagrams and Auxiliary Functions
Albatros2
Hydraulic partial diagrams and auxiliary functions
Partial diagram catalog
CE1P2359en_10
25.03.2011
Building Technologies
2 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Table of contents
Key
..................................................................................................................5
Introduction..............................................................................................................8
1
Boiler ........................................................................................................9
1.1
1.1.1
1.1.2
1.1.3
1.1.4
1.1.5
Boiler .........................................................................................................9
Oil/Gas staged ..........................................................................................9
Oil / gas modulating ................................................................................13
Solid fuel (wood) .....................................................................................15
Auxiliary functions oil/gas and solid fuel .................................................17
Supplementary source ............................................................................17
1.2
1.2.1
1.2.2
1.2.3
1.2.4
1.2.5
Heat pump...............................................................................................18
HP brine / water ......................................................................................18
HP water .................................................................................................21
HP air ......................................................................................................24
HP external .............................................................................................25
Auxiliary functions heat pump .................................................................25
1.3
1.3.1
1.3.2
1.3.3
Solar........................................................................................................26
1 collector field ........................................................................................26
2 collector fields ......................................................................................33
Auxiliary functions solar ..........................................................................37
2.1
2.2
3.1
3.1.1
3.1.2
3.1.3
3.1.4
3.1.5
3.2
3.3
3 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Distribution ............................................................................................50
4.1
4.1.1
4.1.2
4.1.3
4.1.4
4.1.5
4.1.6
4.1.7
4.2
4.2.1
4.3
4.3.1
4.4
4.5
4.6
4.7
4.8
4.9
Overview of use.....................................................................................77
Index
................................................................................................................83
4 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Key
General abbreviations
Mains voltage
Multifunctional input EX
BX
EM
EX
HX
MG
QX
UX
PX
ZX
Multifunctional outputs
QX
Multifunctional input/sensor
Extension module
Multifunctional power input
Multifunctional low voltage input
Mixing group
Multifunctional output, relay
Multifunctional low voltage output
Multifunctional PWM output
Multifunctional output (Triac)
Low-tariff E5
Electrical utility lock E6
Low-pressure switch E9
High-pressure switch E10
Overload compressor 1 E11
Overload compressor 2 E12
Overload source E14
Flow switch source E15
Manual defrost E17
Compressor stage 1 K1
Compressor 2 K2
El imm heater DHW K6
Solar ctrl elem buffer K8
Solar pump ext exch K9
Alarm output K10
Excess heat discharge K11
Time program 5 K13
El imm heater buffer K16
Flue gas relay K17
Solar ctrl elem swi pool K18
Source pump Q8/fan K19
El imm heater 1 flow K25
El imm heater 2 flow K26
Heat request K27
Refrigeration request K28
Air dehumidifier K29
Assisted firing fan K30
Hot-gas temp K31
Suppl source control K32
Water refill K34
Status output K35
Status information K36
Flue gas damper K37
Fan shutdown K38
* The output can be configured for speed control via "Configuration > Function output UX/ PX/ZX". The
following combinations are possible: As relay and speed controlled; speed control only.
K4 (T2)**
K5 (T8)**
Y17/Y18**
** The setting for parameter "Source type" (5770) defines the assignment of the boiler outputs
(Definition of K4, K5, Y17, Y18).
Terminal labeling is specific to the device and is available in the corresponding User's Guide.
5 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Multifunctional outputs
QX
Boiler pump Q1
Q2*
Q3*
Q4
Q5*
Q6*
Q8*
Q9
Q10*
Q11
Q12
Q14
Q15
Q16*
Q18
Q19
Q20*
Q21
Q22
Q23
Q24
Q25
Q27
Q28
Q29
Q33*
Q34*
Q35
* The output can be configured for speed control via "Configuration > Function output UX/ PX/ZX". The
following combinations are possible: As relay and speed controlled; speed control only.
Multifunctional
outputs
Y21
Y22
Y23/Y24***
Y25/Y26***
Y9/Y10***
Y11/Y12***
Y15
Y19/Y20***
Y28
Y31/Y32***
Y33/Y34***
Y41/42***
Y43/44***
Y45
Y46
*** These outputs are not configured individually via Relay output QX1, but rather via "Configuration >
Function extension module 1" or "> Function mixing group 1"
6 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Low voltage
Multifunctional
inputs BX
B4
Buffer sensor B4
B5
B6
B7
B8
B9
B10
B12***
B13
B14***
B15***
B16***
Room sensor B5
Collector sensor B6
Return sensor B7
Flue gas temp sensor B8
Outside sensor B9
Common flow sensor B10
Flow temperature sensor HC2
Swimming pool sensor B13
Flow sensor HC3
Flow sensor prim controller
Flow sensor CC1
B17***
B18***
B21
B22
B26
B31
B35***
B36
B37
B38
B39
B41
B42
B52
B53
B61
B62
B63
B64
B70
B71
B72
B73
B81
B82
B83
B84
B91
B92
*** These inputs are not configured individually via Sensor input BX1, but rather via "Configuration >
Function extension module 1" or "> Function mixing group 1"
RG1
RG2
FS
Room unit 1
Room unit 2
Flow switch
7 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Introduction
Content of the document
8 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Boiler
1.1
Boiler
1.1.1
Oil/Gas staged
OeG1
Required settings:
Configuration > Source type (5770): 1-stage
BX: Boiler sensor B2
Plant variant (without graphic):
Configuration > Source type (5770): Without boiler sensor
Optional settings:
BX: Return sensor B7
Additional notes on K4 in the key.
OeG2
Required settings:
Configuration > Source type (5770): 2-stage
Plant variant (without graphic):
Configuration > Source type (5770): 2x1 cascade
BX: Boiler sensor B2
Optional settings:
BX: Return sensor B7
Additional notes on K4/K5 in the key.
B2
K5
K4
B7
T
9 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
OeG3
Required settings:
Configuration > Source type (5770): 1-stage
BX: Boiler sensor B2
Plant variant (without graphic):
Configuration > Source type (5770): Without boiler
sensor
QX: Boiler pump Q1*
Optional settings:
BX: Return sensor B7
Additional notes on K4 in the key.
OeG4
Required settings:
Configuration > Source type (5770): 2-stage
Plant variant (without graphic):
Configuration > Source type (5770): 2x1 cascade
BX: Boiler sensor B2
QX: Boiler pump Q1*
Optional settings:
BX: Return sensor B7
Additional notes on K4/K5 in the key.
B2
K5
K4
OeG5
Required settings:
Configuration > Source type (5770): 1-stage
BX: Boiler sensor B2
Plant variant (without graphic):
Configuration > Source type (5770): Without boiler sensor
QX: Bypass pump Q12
Optional settings:
BX: Return sensor B7
Additional notes on K4 in the key.
10 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
OeG6
Required settings:
Configuration > Source type (5770): 2-stage
Plant variant (without graphic):
Configuration > Source type (5770): 2x1 cascade
BX: Boiler sensor B2
QX: Bypass pump Q12
Optional settings:
BX: Return sensor B7
Additional notes on K4/K5 in the key.
B2
K5
K4
OeG7
Required settings:
Configuration > Source type (5770): 1-stage
BX: Boiler sensor B2
Plant variant (without graphic):
Configuration > Source type (5770): Without boiler
sensor
QX: Boiler pump Q1*, Bypass pump Q12
Optional settings:
BX: Return sensor B7
Additional notes on K4 in the key.
11 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
OeG8
Required settings:
Configuration > Source type (5770): 2-stage
Plant variant (without graphic):
Configuration > Source type (5770): 2x1 cascade
BX: Boiler sensor B2
QX: Boiler pump Q1*, Bypass pump Q12
Optional settings:
BX: Return sensor B7
Additional notes on K4/K5 in the key.
B2
K5
K4
OeG9
Required settings:
Function mixing group 1: Return temp controller
Configuration variants:
Function extension module 1: Return temp controller
Configuration > Source type (5770): 1-stage
BX: Boiler sensor B2
Plant variant (without graphic):
Configuration > Source type (5770): Without boiler sensor
Additional notes on K4 in the key.
12 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
OeG10
Required settings:
Function mixing group 1: Return temp controller
Configuration variants:
Function extension module 1: Return temp controller
Configuration > Source type (5770): 2-stage
Plant variant (without graphic):
Configuration > Source type (5770): 2x1 cascade
BX: Boiler sensor B2
Additional notes on K4/K5 in the key.
B2
K5
K4
1.1.2
Modulating oil/gas burner with 3-point damper actuator or voltage output UX.
OeG11
Required settings:
Configuration > Source type (5770): Modulating 3-position
Plant variants (without graphic):
Configuration > Source type (5770): Modulating UX
BX: Boiler sensor B2
Optional settings:
BX: Return sensor B7
Required settings (graphics below):
Source type (fixed preselection): Modulating 3-position
BX: Boiler sensor B2
Optional settings:
BX4/BX4 Sec: Return sensor B7
Additional notes on Y17/Y18 and K4 in the key.
13 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
OeG12
Required settings (graphics below):
Configuration > Source type (5770): Modulating 3-position
Plant variants (without graphic):
Configuration > Source type (5770): Modulating UX
BX: Boiler sensor B2
QX: Boiler pump Q1*
Optional settings:
BX: Return sensor B7
Required settings (graphics below):
Source type (fixed preselection): Modulating 3-position
BX: Boiler sensor B2
QX: Boiler pump Q1*
Optional settings:
BX4/BX4 Sec: Return sensor B7
Additional notes on Y17/Y18 and K4 in the key.
* see key.
OeG13
Required settings:
Configuration > Source type (5770): Modulating 3-position
Plant variants (without graphics):
Configuration > Source type (5770): Modulating UX
BX: Boiler sensor B2
QX: Bypass pump Q12
Optional settings:
BX: Return sensor B7
Required settings (graphics below):
Source type (fixed preselection): Modulating 3-position
BX: Boiler sensor B2
QX: Bypass pump Q12
Optional settings:
BX4/BX4 Sec: Return sensor B7
Additional notes on Y17/Y18 and K4 in the key.
14 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
OeG14
Required settings (graphics below):
Configuration > Source type (5770): Modulating 3-position
Plant variants (without graphic):
Configuration > Source type (5770): Modulating UX
BX: Boiler sensor B2
QX: Boiler pump Q1*, Bypass pump Q12
Optional settings:
BX: Return sensor B7
Required settings (graphics below):
Source type (fixed preselection): Modulating 3-position
BX: Boiler sensor B2
QX: Boiler pump Q1*, Bypass pump Q12
Optional settings:
BX4/BX4 Sec: Return sensor B7
Additional notes on Y17/Y18 and K4 in the key.
* see key.
OeG15
Required settings:
Function mixing group 1: Return temp controller
Configuration variants:
Function extension module 1: Return temp controller
Configuration > Source type (5770): Modulating 3-position
Plant variants (without graphic):
Configuration > Source type (5770): Modulating UX
BX: Boiler sensor B2
Additional notes on Y17/Y18 and K4 in the key.
1.1.3
Ho1
Required settings:
BX: Solid fuel boiler sensor B22
QX: Solid fuel boiler pump Q10*
Optional settings:
BX: Solid fuel boil ret sens B72
Old devices:
Solid fuel boiler > Comparative temp (4133): Flow temp setpoint or Setpoint min
* see key.
15 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Ho2
Required settings:
Solid fuel boiler > Connection DHW stor tank (4134): With B3 or With B31
oder With B3 and B31
Solid fuel boiler > DHW charging with Q3 (4136): No
BX: Solid fuel boiler sensor B22
QX: Solid fuel boiler pump Q10*
Optional settings:
BX: Solid fuel boil ret sens B72
Old devices:
Solid fuel boiler > Comparative temp (4133): DHW sensor B3 or DHW
sensor B31 oder Buffer sensor B4 oder Buffer sensor B41
* see key.
Ho3
Required settings:
Function mixing group 1: Ret temp contr sol fuel boil
BX: Solid fuel boiler sensor B22
Configuration variants:
Function extension module 1: Solid fuel boiler
Ho4
Required settings:
Function mixing group 1: Ret temp contr sol fuel boil
BX: Solid fuel boiler sensor B22
Configuration variants:
Function extension module 1: Solid fuel boiler
Solid fuel boiler > Connection DHW stor tank (4134): With B3 or With B31
oder With B3 and B31
Solid fuel boiler > DHW charging with Q3 (4136): No
16 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
1.1.4
Flue gas temperature
sensor
Required settings:
BX: Flue gas temp sensor B8
Optional settings:
QX:Flue gas relay K17, Assisted firing fan K30
1.1.5
Supplementary source
Supplementary source
Required settings:
QX: Heat request K27
Optional settings:
QX: Suppl source control K32
Configuration > Function output UX > Output request or Heat
request
17 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
1.2
Heat pump
1.2.1
HP brine / water
WP10
Required settings:
Configuration > Heat source (5800): Brine
.. > Refrigeration (5807): Off
.. > Source prot sens brine HP (5804): Source inlet B91
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source inlet sensor B91, HP return sensor B71
QX: Compressor stage 1 K1, Source pump Q8/fan K19*
Optional settings:
EX: Overload compressor 1 E11
BX: HP flow sensor B21, Hot-gas sensor B81, Refrig sensor liquid
B83, Source outl sens B92/B84
QX: Condenser pump Q9
* see key.
WP11
Required settings:
Configuration > Heat source (5800): Brine
.. > Refrigeration (5807): Off
.. > Source prot sens brine HP (5804): Source inlet B91
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source inlet sensor B91, HP return sensor B71
QX: Compressor stage 1 K1, Compressor 2 K2, Source pump
Q8/fan K19*
Optional settings:
EX: Overload compressor 1 E11, Overload compressor 2 E12
BX: HP flow sensor B21, Hot-gas sensor B81, Hot-gas sensor B82,
Refrig sensor liquid B83, Source outl sens B92/B84
QX: Condenser pump Q9
* see key.
18 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
WP14
Required settings:
Configuration > Heat source (5800): Brine
.. > Refrigeration (5807): 4-pipe system cooling
.. > Source prot sens brine HP (5804): Source inlet B91
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source inlet sensor B91, HP return sensor B71
QX: Compressor stage 1 K1, Source pump Q8/fan K19*
Optional settings:
EX: Overload compressor 1 E11
BX: HP flow sensor B21, Hot-gas sensor B81, Refrig sensor liquid
B83, Source outl sens B92/B84
QX: Div valve cool source Y28, Condenser pump Q9
* see key.
WP15
Required settings:
Configuration > Heat source (5800): Brine
.. > Refrigeration (5807): 4-pipe system cooling
.. > Source prot sens brine HP (5804): Source inlet B91
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source inlet sensor B91, HP return sensor B71
QX: Compressor stage 1 K1, Compressor 2 K2, Source pump
Q8/fan K19*
Optional settings:
EX: Overload compressor 1 E11, Overload compressor 2 E12
BX: HP flow sensor B21, Hot-gas sensor B81, Hot-gas sensor B82,
Refrig sensor liquid B83, Source outl sens B92/B84
QX: Div valve cool source Y28, Condenser pump Q9
* see key.
WP18
Required settings:
Configuration > Heat source (5800): Brine
.. > Refrigeration (5807): 2-pipe system cooling
.. > Source prot sens brine HP (5804): Source inlet B91
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source inlet sensor B91, HP return sensor B71
QX: Compressor stage 1 K1, Process revers valve Y22, Source
pump Q8/fan K19*
Optional settings:
EX: Overload compressor 1 E11
BX: HP flow sensor B21, Hot-gas sensor B81, Refrig sensor liquid
B83, Source outl sens B92/B84
QX: Condenser pump Q9
* see key.
19 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
WP19
Required settings:
Configuration > Heat source (5800): Brine
.. > Refrigeration (5807): 2-pipe system cooling
.. > Source prot sens brine HP (5804): Source inlet B91
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source inlet sensor B91, HP return sensor B71
QX: Compressor stage 1 K1, Compressor 2 K2, Process revers
valve Y22, Source pump Q8/fan K19*
Optional settings:
EX: Overload compressor 1 E11, Overload compressor 2 E12
BX: HP flow sensor B21, Hot-gas sensor B81, Hot-gas sensor B82,
Refrig sensor liquid B83, Source outl sens B92/B84
QX: Condenser pump Q9
* see key.
WP22
Required settings:
Configuration > Heat source (5800): Brine
.. > Refrigeration (5807): 4-pipe system cooling
.. > Source prot sens brine HP (5804): Source inlet B91
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source inlet sensor B91, HP return sensor B71
QX: Compressor stage 1 K1, Process revers valve Y22, Source
pump Q8/fan K19*
Optional settings:
EX: Overload compressor 1 E11
BX: HP flow sensor B21, Hot-gas sensor B81, Refrig sensor liquid
B83, Source outl sens B92/B84
QX: Div valve cool source Y28, Condenser pump Q9
* see key.
WP23
Required settings:
Configuration > Heat source (5800): Brine
.. > Refrigeration (5807): 4-pipe system cooling
.. > Source prot sens brine HP (5804): Source inlet B91
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source inlet sensor B91, HP return sensor B71
QX: Compressor stage 1 K1, Compressor 2 K2, Process revers
valve Y22, Source pump Q8/fan K19*
Optional settings:
EX: Overload compressor 1 E11, Overload compressor 2 E12
BX: HP flow sensor B21, Hot-gas sensor B81, Hot-gas sensor B82,
Refrig sensor liquid B83, Source outl sens B92/B84
QX: Div valve cool source Y28, Condenser pump Q9
* see key.
20 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
1.2.2
HP water
WP30
Required settings:
Configuration > Heat source (5800): Water
Configuration > Refrigeration (5807): Off
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source outl sens B92/B84, HP return sensor B71
QX: Compressor stage 1 K1, Source pump Q8/fan K19*
Optional settings:
EX: Overload compressor 1 E11
BX: HP flow sensor B21, Hot-gas sensor B81, Refrig sensor liquid
B83, Source inlet sensor B91
QX: Condenser pump Q9
* see key.
WP31
Required settings:
Configuration > Heat source (5800): Water
Configuration > Refrigeration (5807): Off
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source outl sens B92/B84, HP return sensor B71
QX: Compressor stage 1 K1, Compressor 2 K2, Source pump
Q8/fan K19*
Optional settings:
EX: Overload compressor 1 E11, Overload compressor 2 E12
BX: HP flow sensor B21, Hot-gas sensor B81, Hot-gas sensor B82,
Refrig sensor liquid B83, Source inlet sensor B91
QX: Condenser pump Q9
* see key.
WP34
Required settings:
Configuration > Heat source (5800): Water
Configuration > Refrigeration (5807): 4-pipe system cooling
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source outl sens B92/B84, HP return sensor B71
QX: Compressor stage 1 K1, Source pump Q8/fan K19*
Optional settings:
EX: Overload compressor 1 E11
BX: HP flow sensor B21, Hot-gas sensor B81, Refrig sensor liquid
B83, Source inlet sensor B91
QX: Condenser pump Q9, Div valve cool source Y28
* see key.
21 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
WP35
Required settings:
Configuration > Heat source (5800): Water
Configuration > Refrigeration (5807): 4-pipe system cooling
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source outl sens B92/B84, HP return sensor B71
QX: Compressor stage 1 K1, Compressor 2 K2, Source pump
Q8/fan K19*
Optional settings:
EX: Overload compressor 1 E11, Overload compressor 2 E12
BX: HP flow sensor B21, Hot-gas sensor B81, Hot-gas sensor B82,
Refrig sensor liquid B83, Source inlet sensor B91
QX: Condenser pump Q9, Div valve cool source Y28
* see key.
WP38
Required settings:
Configuration > Heat source (5800): Water
Configuration > Refrigeration (5807): 2-pipe system cooling
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source outl sens B92/B84, HP return sensor B71
QX: Compressor stage 1 K1, Source pump Q8/fan K19*, Process
revers valve Y22
Optional settings:
EX: Overload compressor 1 E11
BX: HP flow sensor B21, Hot-gas sensor B81, Refrig sensor liquid
B83, Source inlet sensor B91
QX: Condenser pump Q9
* see key.
WP39
Required settings:
Configuration > Heat source (5800): Water
Configuration > Refrigeration (5807): 2-pipe system cooling
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source outl sens B92/B84, HP return sensor B71
QX: Compressor stage 1 K1, Compressor 2 K2, Source pump
Q8/fan K19*, Process revers valve Y22
Optional settings:
EX: Overload compressor 1 E11, Overload compressor 2 E12
BX: HP flow sensor B21, Hot-gas sensor B81, Hot-gas sensor B82,
Refrig sensor liquid B83, Source inlet sensor B91
QX: Condenser pump Q9
* see key.
22 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
WP42
Required settings:
Configuration > Heat source (5800): Water
Configuration > Refrigeration (5807): 4-pipe system cooling
EX: Low-pressure switch E9, High-pressure switch E10
BX: HP return sensor B71, Source outl sens B92/B84
QX: Compressor stage 1 K1, Source pump Q8/fan K19*, Process
revers valve Y22
Optional settings:
EX: Overload compressor 1 E11
BX: HP flow sensor B21, Hot-gas sensor B81, Refrig sensor liquid
B83, Source inlet sensor B91
QX: Condenser pump Q9, Div valve cool source Y28
* see key.
WP43
Required settings:
Configuration > Heat source (5800): Water
Configuration > Refrigeration (5807): 4-pipe system cooling
BX: HP return sensor B71, Source outl sens B92/B84
EX: Low-pressure switch E9, High-pressure switch E10
QX: Compressor stage 1 K1, Compressor 2 K2, Source pump
Q8/fan K19*, Process revers valve Y22
Optional settings:
EX: Overload compressor 1 E11, Overload compressor 2 E12
BX: HP flow sensor B21, Hot-gas sensor B81, Hot-gas sensor B82,
Refrig sensor liquid B83, Source inlet sensor B91
QX: Condenser pump Q9, Div valve cool source Y28
* see key.
23 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
1.2.3
HP air
WP50
Required settings:
Configuration > Heat source (5800): Air
Configuration > Refrigeration (5807): Aus oder 2-pipe system cooling
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source outl sens B92/B84, Source inlet sensor B91, HP return
sensor B71
QX: Compressor stage 1 K1, Source pump Q8/fan K19*, Process
revers valve Y22
Optional settings:
EX: Overload compressor 1 E11
BX: HP flow sensor B21, Hot-gas sensor B81, Refrig sensor liquid
B83
QX: Condenser pump Q9
* see key.
WP51
Required settings:
Configuration > Heat source (5800): Air
Configuration > Refrigeration (5807): Aus oder 2-pipe system cooling
EX: Low-pressure switch E9, High-pressure switch E10
BX: Source outl sens B92/B84, Source inlet sensor B91, HP return
sensor B71
QX: Compressor stage 1 K1, Compressor 2 K2, Source pump
Q8/fan K19*, Process revers valve Y22
Optional settings:
EX: Overload compressor 1 E11
BX: HP flow sensor B21, Hot-gas sensor B81, Hot-gas sensor B82,
Refrig sensor liquid B83
QX: Condenser pump Q9
* see key.
24 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
1.2.4
HP external
WP60
Required settings:
Configuration > Heat source (5800): Externally
Configuration > Refrigeration (5807): Off or 2-pipe system cooling
QX: Compressor stage 1 K1
Optional settings:
EX: Low-pressure switch E9, High-pressure switch E10, Overload
compressor 1 E11
BX: HP flow sensor B21, HP return sensor B71, Hot-gas sensor B81,
Refrig sensor liquid B83, Source inlet sensor B91, Source outl sens
B92/B84
QX: Source pump Q8/fan K19*, Condenser pump Q9, Process
revers valve Y22
* see key.
WP61
Required settings:
Configuration > Heat source (5800): Externally
Configuration > Refrigeration (5807): Off or 2-pipe system cooling
QX: Compressor stage 1 K1, Compressor 2 K2
Optional settings:
EX: Low-pressure switch E9, High-pressure switch E10, Overload
compressor 1 E11, Overload compressor 2 E12
BX: HP flow sensor B21, HP return sensor B71, Hot-gas sensor B81,
Hot-gas sensor B82, Refrig sensor liquid B83, Source inlet sensor
B91, Source outl sens B92/B84
QX: Source pump Q8/fan K19*, Condenser pump Q9, Process
revers valve Y22
* see key.
1.2.5
Flow
electric immersion heater
1, 2
Required settings:
QX: El imm heater 1 flow K25, El imm heater 2
flow K26
25 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
1.3
Solar
1.3.1
1 collector field
Sol1
Required settings:
QX: Collector pump Q5*
BX: Collector sensor B6
* see key.
Sol3
Required settings:
QX: Collector pump Q5*, Solar pump ext exch K9*
BX: Collector sensor B6
* see key.
Sol5
Required settings:
Configuration > Solar controlling element (5840): Charging pump
QX: Collector pump Q5*, Solar ctrl elem buffer K8*
BX: Collector sensor B6
* see key.
26 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Sol6
Required settings:
Configuration > Solar controlling element (5840): Diverting valve
QX: Collector pump Q5*, Solar ctrl elem buffer K8
BX: Collector sensor B6
* see key.
Sol8
Required settings:
Configuration > Solar controlling element (5840): Charging
pump
Configuration > External solar exchanger (5841): Jointly
QX: Collector pump Q5*, Solar ctrl elem buffer K8*, Solar pump
ext exch K9*
BX: Collector sensor B6
* see key.
Sol9
Required settings:
Configuration > Solar controlling element (5840): Diverting valve
Configuration > External solar exchanger (5841): Jointly
QX: Collector pump Q5*, Solar ctrl elem buffer K8, Solar pump
ext exch K9*
BX: Collector sensor B6
* see key.
27 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Sol10
Required settings:
Configuration > Solar controlling element (5840): Charging pump
Configuration > External solar exchanger (5841): DHW storage
tank
QX: Collector pump Q5*, Solar ctrl elem buffer K8*, Solar pump
ext exch K9*
BX: Collector sensor B6
* see key.
Sol11
Required settings:
Configuration > Solar controlling element (5840): Diverting valve
Configuration > External solar exchanger (5841): DHW storage
tank
QX: Collector pump Q5*, Solar ctrl elem buffer K8, Solar pump
ext exch K9*
BX: Collector sensor B6
* see key.
Sol12
Required settings:
Configuration > Solar controlling element (5840): Charging pump
Configuration > External solar exchanger (5841): Buffer storage
tank
QX: Collector pump Q5*, Solar ctrl elem buffer K8*, Solar pump
ext exch K9*
BX: Collector sensor B6
* see key.
28 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Sol13
Required settings:
Configuration > Solar controlling element (5840): Diverting valve
Configuration > External solar exchanger (5841): Buffer storage
tank
QX: Collector pump Q5*, Solar ctrl elem buffer K8, Solar pump
ext exch K9*
BX: Collector sensor B6
* see key.
Sol14
Required settings:
Configuration > Solar controlling element (5840): Charging pump
QX: Collector pump Q5*, Solar ctrl elem swi pool K18*
BX: Collector sensor B6
* see key.
Sol15
Required settings:
Configuration > Solar controlling element (5840): Diverting valve
QX: Collector pump Q5*, Solar ctrl elem swi pool K18
BX: Collector sensor B6
* see key.
Sol17
Required settings:
Configuration > Solar controlling element (5840): Charging pump
QX: Collector pump Q5*, Solar pump ext exch K9*, Solar ctrl
elem swi pool K18*
BX: Collector sensor B6
* see key.
29 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Sol18
Required settings:
Configuration > Solar controlling element (5840): Diverting valve
QX: Collector pump Q5*, Solar pump ext exch K9*, Solar ctrl
elem swi pool K18
BX: Collector sensor B6
* see key.
Sol19
Required settings:
Configuration > Solar controlling element (5840): Charging pump
QX: Collector pump Q5*, Solar ctrl elem buffer K8*, Solar ctrl
elem swi pool K18*
BX: Collector sensor B6
* see key.
Sol20
Required settings:
Configuration > Solar controlling element (5840): Diverting valve
QX: Collector pump Q5*, Solar ctrl elem buffer K8, Solar ctrl elem
swi pool K18
BX: Collector sensor B6
* see key.
30 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Sol22
Required settings:
Configuration > Solar controlling element (5840): Charging
pump
Configuration > External solar exchanger (5841): Jointly
QX: Collector pump Q5*, Solar ctrl elem buffer K8*, Solar pump
ext exch K9*, Solar ctrl elem swi pool K18*
BX: Collector sensor B6
* see key.
Sol23
Required settings:
Configuration > Solar controlling element (5840): Diverting
valve
Configuration > External solar exchanger (5841): Jointly
QX: Collector pump Q5*, Solar ctrl elem buffer K8, Solar pump
ext exch K9*, Solar ctrl elem swi pool K18
BX: Collector sensor B6
* see key.
Sol24
Required settings:
Configuration > Solar controlling element (5840): Charging
pump
Configuration > External solar exchanger (5841): DHW storage
tank
QX: Collector pump Q5*, Solar ctrl elem buffer K8*, Solar pump
ext exch K9*, Solar ctrl elem swi pool K18*
BX: Collector sensor B6
* see key.
31 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Sol25
Required settings:
Configuration > Solar controlling element (5840): Diverting
valve
Configuration > External solar exchanger (5841): DHW storage
tank
QX: Collector pump Q5*, Solar ctrl elem buffer K8, Solar pump
ext exch K9*, Solar ctrl elem swi pool K18
BX: Collector sensor B6
* see key.
Sol26
Required settings:
Configuration > Solar controlling element (5840): Charging
pump
Configuration > External solar exchanger (5841): Buffer
storage tank
QX: Collector pump Q5*, Solar ctrl elem buffer K8*, Solar pump
ext exch K9*, Solar ctrl elem swi pool K18*
BX: Collector sensor B6
* see key.
Sol27
Required settings:
Configuration > Solar controlling element (5840): Diverting
valve
Configuration > External solar exchanger (5841): Buffer
storage tank
QX: Collector pump Q5*, Solar ctrl elem buffer K8, Solar pump
ext exch K9*, Solar ctrl elem swi pool K18
BX: Collector sensor B6
* see key.
32 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
1.3.2
2 collector fields
Sol31
Required settings:
QX: Collector pump Q5*, Collector pump 2 Q16*
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
Sol33
Required settings:
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar pump
ext exch K9*
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
Sol35
Required settings:
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem buffer K8
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
33 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Sol37
Required settings:
Configuration > Solar controlling element (5840): Charging
pump
Configuration > External solar exchanger (5841): Jointly
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem buffer K8*, Solar pump ext exch K9*
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
Sol38
Required settings:
Configuration > Solar controlling element (5840): Diverting
valve
Configuration > External solar exchanger (5841): Jointly
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem buffer K8, Solar pump ext exch K9*
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
Sol 39
Required settings:
Configuration > Solar controlling element (5840): Charging
pump
Configuration > External solar exchanger (5841): DHW
storage tank
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem buffer K8*, Solar pump ext exch K9*
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
Sol40
Required settings:
Configuration > Solar controlling element (5840): Diverting
valve
Configuration > External solar exchanger (5841): DHW
storage tank
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem buffer K8, Solar pump ext exch K9*
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
34 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Sol41
Required settings:
Configuration > External solar exchanger (5841): Buffer
storage tank
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem buffer K8, Solar pump ext exch K9*
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
Sol42
Required settings:
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem swi pool K18
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
Sol44
Required settings:
Configuration > Solar controlling element (5840): Charging
pump
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar pump
ext exch K9*, Solar ctrl elem swi pool K18*
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
Sol45
Required settings:
Configuration > Solar controlling element (5840): Diverting
valve
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar pump
ext exch K9*, Solar ctrl elem swi pool K18
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
35 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Sol46
Required settings:
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem buffer K8, Solar ctrl elem swi pool K18
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
Sol48
Required settings:
Configuration > Solar controlling element (5840): Charging
pump
Configuration > External solar exchanger (5841): Jointly
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem buffer K8*, Solar pump ext exch K9*, Solar ctrl elem
swi pool K18*
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
Sol49
Required settings:
Configuration > Solar controlling element (5840): Diverting
valve
Configuration > External solar exchanger (5841): Jointly
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem buffer K8, Solar pump ext exch K9*, Solar ctrl elem
swi pool K18
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
Sol50
Required settings:
Configuration > Solar controlling element (5840): Charging
pump
Configuration > External solar exchanger (5841): DHW
storage tank
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem buffer K8*, Solar pump ext exch K9*, Solar ctrl elem
swi pool K18*
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
36 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Sol51
Required settings:
Configuration > Solar controlling element (5840): Diverting
valve
Configuration > External solar exchanger (5841): DHW
storage tank
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem buffer K8, Solar pump ext exch K9*, Solar ctrl elem
swi pool K18
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
Sol52
Required settings:
Configuration > External solar exchanger (5841): Buffer
storage tank
QX: Collector pump Q5*, Collector pump 2 Q16*, Solar ctrl
elem buffer K8, Solar pump ext exch K9*, Solar ctrl elem
swi pool K18
BX: Collector sensor B6, Collector sensor 2 B61
* see key.
1.3.3
Required settings:
BX: Solar flow sensor B63 (hot), Solar return sensor B64
(cold)
B63
B64
37 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
2.1
Sp1
Required settings:
Buffer storage tank > With solar integration (4783): No
BX: Buffer sensor B4
Optional settings:
BX: Buffer sensor B41, Buffer sensor B42
Sp2
Required settings:
Buffer storage tank > With solar integration (4783): Yes
BX: Buffer sensor B4
Optional settings:
BX: Buffer sensor B41, Buffer sensor B42
Sp4
Required settings:
Buffer storage tank > With solar integration (4783): No
BX: Buffer sensor B4
QX: Heat gen shutoff valve Y4
Optional settings:
BX: Buffer sensor B41, Buffer sensor B42
38 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Sp5
Required settings:
Buffer storage tank > With solar integration (4783): Yes
BX: Buffer sensor B4
QX: Heat gen shutoff valve Y4
Optional settings:
BX: Buffer sensor B41, Buffer sensor B42
2.2
39 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
40 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
3.1
3.1.1
DHWSp1
Required settings:
DHW storage tank > With solar integration (5093): No
Configuration > DHW ctrl elem Q3 (5731): None
BX: DHW sensor B3
Optional settings:
BX: DHW sensor B31
DHWSp2
Required settings:
DHW storage tank > With solar integration (5093): Yes
Configuration > DHW ctrl elem Q3 (5731): None
BX: DHW sensor B3
Optional settings:
BX: DHW sensor B31
3.1.2
DHWSp4
Required settings:
DHW storage tank > With solar integration (5093): No
Configuration > DHW ctrl elem Q3 (5731): Charging pump
BX: DHW sensor B3
QX: DHW ctrl elem Q3*
Optional settings:
BX: DHW sensor B31, DHW charging sensor B36
* see key.
41 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
DHWSp5
Required settings:
DHW storage tank > With solar integration (5093): Yes
Configuration > DHW ctrl elem Q3 (5731): Charging pump
BX: DHW sensor B3
QX: DHW ctrl elem Q3*
Optional settings:
BX: DHW sensor B31, DHW charging sensor B36
* see key.
3.1.3
Diverting valve
DHWSp13
Required settings:
DHW storage tank > With solar integration (5093): No
Configuration > DHW ctrl elem Q3 (5731): Diverting valve
BX: DHW sensor B3
QX: DHW ctrl elem Q3
Optional settings:
BX: DHW sensor B31, DHW charging sensor B36
DHWSp4
Required settings:
DHW storage tank > With solar integration (5093): Yes
Configuration > DHW ctrl elem Q3 (5731): Diverting valve
BX: DHW sensor B3
QX: DHW ctrl elem Q3
Optional settings:
BX: DHW sensor B31, DHW charging sensor B36
42 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
3.1.4
Primary controller
DHWSp16
Required settings:
Configuration > Function mixing group 1..: DHW primary controller
Configuration variants:
Configuration > Function extension module 1..: DHW primary
controller
DHW storage tank > With solar integration (5093): No
BX: DHW sensor B3
Optional settings:
BX: DHW sensor B31
DHWSp17
Required settings:
Configuration > Function mixing group 1..: DHW primary controller
Configuration variants:
Configuration > Function extension module 1..: DHW primary
controller
DHW storage tank > With solar integration (5093): Yes
BX: DHW sensor B3
Optional settings:
BX: DHW sensor B31
3.1.5
DHWSp19
Required settings:
DHW storage tank > With solar integration (5093): No
Configuration > DHW ctrl elem Q3 (5731): None
BX: DHW sensor B3
QX: DHW interm circ pump Q33*
Optional settings:
BX: DHW sensor B31, DHW charging sensor B36
* see key.
43 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
DHWSp20
Required settings:
DHW storage tank > With solar integration (5093): Yes
Configuration > DHW ctrl elem Q3 (5731): None
BX: DHW sensor B3
QX: DHW interm circ pump Q33*
Optional settings:
BX: DHW sensor B31, DHW charging sensor B36
* see key.
DHWSp22
Required settings:
DHW storage tank > With solar integration (5093): No
Configuration > DHW ctrl elem Q3 (5731): Charging pump
BX: DHW sensor B3
QX: DHW ctrl elem Q3*, DHW interm circ pump Q33*
Optional settings:
BX: DHW sensor B31, DHW charging sensor B36
* see key.
DHWSp23
Required settings:
DHW storage tank > With solar integration (5093): Yes
Configuration > DHW ctrl elem Q3 (5731): Charging pump
BX: DHW sensor B3
QX: DHW ctrl elem Q3*, DHW interm circ pump Q33*
Optional settings:
BX: DHW sensor B31, DHW charging sensor B36
* see key.
44 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
DHWSp25
Required settings:
DHW storage tank > With solar integration (5093): No
Configuration > DHW ctrl elem Q3 (5731): Diverting valve
BX: DHW sensor B3
QX: DHW ctrl elem Q3, DHW interm circ pump Q33*
Optional settings:
BX: DHW sensor B31, DHW charging sensor B36
* see key.
DHWSp26
Required settings:
DHW storage tank > With solar integration (5093): Yes
Configuration > DHW ctrl elem Q3 (5731): Diverting valve
BX: DHW sensor B3
QX: DHW ctrl elem Q3, DHW interm circ pump Q33*
Optional settings:
BX: DHW sensor B31, DHW charging sensor B36
* see key.
DHWSp28
Required settings:
Configuration > Function mixing group 1..: DHW primary controller
Configuration variants:
Configuration > Function extension module 1..: DHW primary
controller
DHW storage tank > With solar integration (5093): No
BX: DHW sensor B3
QX: DHW interm circ pump Q33*
Optional settings:
BX: DHW sensor B31, DHW charging sensor B36
* see key.
45 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
DHWSp29
Required settings:
Function mixing group 1: DHW primary controller
Configuration variants:
Function extension module 1:DHW primary controller
DHW storage tank > With solar integration (5093): Yes
BX: DHW sensor B3
QX: DHW interm circ pump Q33*
Optional settings:
BX: DHW sensor B31, DHW charging sensor B36
* see key.
3.2
DHWDl2
Required settings:
BX: DHW outlet sensor B38
Optional settings:
Function input H1 > DHW flow switch
DHWDl3
Required settings:
Instantaneous water heater > With DHW storage tank (5551): Yes
Plant variants:
Instantaneous water heater > With buffer (5552): Yes
BX: DHW outlet sensor B38
QX: Instant WH ctrl elem Q34*
Optional settings:
BX: DHW circulation sensor B39/Instant WH sensor B37
Note: Also requires a valid DHW storage tank or buffer storage partial diagram
46 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
DHWDl4
Required settings:
Configuration > DHW controlling element (5731): Charging pump
BX: DHW outlet sensor B38
QX: Instant WH ctrl elem Q34*
Optional settings:
BX: DHW circulation sensor B39/Instant WH sensor B37
Function input H1 > DHW flow switch
* see key.
DHWDl6
Required settings:
Configuration > DHW controlling element (5731): Diverting valve
BX: DHW outlet sensor B38
QX: Instant WH ctrl elem Q34
Optional settings:
BX: DHW circulation sensor B39/Instant WH sensor B37
Function input H1 > DHW flow switch
DHWDl8
Required settings:
Instantaneous water heater > With DHW storage tank (5551): Yes
Plant variants:
Instantaneous water heater > With buffer (5552): Yes
Function mixing group 1: Instantaneous water heater
Configuration variants:
Function extension module 1: Instantaneous water heater
BX: DHW outlet sensor B38
Optional settings:
BX: DHW circulation sensor B39/Instant WH sensor B37
Note: Also requires a valid DHW storage tank or buffer storage partial diagram
47 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
DHWDI9
Required settings:
Function mixing group 1: Instantaneous water heater
Configuration variants:
Function extension module 1: Instantaneous water heater
BX: DHW outlet sensor B38
Optional settings:
BX: DHW circulation sensor B39/Instant WH sensor B37
3.3
48 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
49 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Distribution
4.1
4.1.1
Heating circuit
Rh1
Required settings:
Configuration > Heating circuit 1 (5710): On
Rh2
Required settings:
Configuration > Heating circuit 1 (5710): On
QX: Heat circuit pump HC1 Q2*
Optional settings:
QX: 2nd pump speed HC1 Q21
* see key.
50 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh3
Required settings:
Function mixing group 1: Heating circuit 1
Configuration variants:
Function extension module 1: Heating circuit 1
Configuration > Heating circuit 1 (5710): On
4.1.2
Rh5
Required settings:
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
51 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh6
Required settings:
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
Configuration > Use of mixing valve 1 (5712): Heating and cooling
QX: Heat circuit pump HC1 Q2*
Optional settings:
QX: 2nd pump speed HC1 Q21
* see key.
Rh7
Required settings:
Function mixing group 1: Heating circ/cooling circ 1
Configuration variants:
Function extension module 1: Heating circ/cooling circ 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
4.1.3
Rh8
Required settings:
Configuration > Heating circuit 1 (5710): Off
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
52 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh9
Required settings:
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
QX: Cooling circ pump CC1 Q24
Rh10
Required settings:
Function mixing group 1: Cooling circuit 1
Configuration variants:
Function extension module 1: Cooling circuit 1
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
53 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
4.1.4
Rh12
Required settings:
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
QX: Diverting valve cooling Y21, Heat circuit pump HC1 Q2*
Optional settings:
QX: 2nd pump speed HC1 Q21
* see key.
Rh14
Required settings:
Function mixing group 1: Heating circ/cooling circ 1
Configuration variants:
Function extension module 1: Heating circ/cooling circ 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
Configuration > Use of mixing valve 1 (5712): Heating and cooling
QX: Diverting valve cooling Y21
54 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh15
Required settings:
Function mixing group 1: Heating circ/cooling circ 1
Configuration variants:
Function extension module 1: Heating circ/cooling circ 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
Configuration > Use of mixing valve 1 (5712): Heating
QX: Diverting valve cooling Y21
* see key.
Rh16
Required settings:
Function mixing group 1: Heating circ/cooling circ 1
Configuration variants:
Function extension module 1: Heating circ/cooling circ 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
Configuration > Use of mixing valve 1 (5712): Cooling
QX: Diverting valve cooling Y21
Optional settings:
QX: 2nd pump speed HC1 Q21
* see key.
55 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
4.1.5
Rh20
Required settings:
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
Configuration > Use of mixing valve 1 (5712): Heating
QX: Heat circuit pump HC1 Q2*
Optional settings:
QX: 2nd pump speed HC1 Q21
* see key.
Rh21
Required settings:
Function mixing group 1: Heating circuit 1
Configuration variants:
Function extension module 1: Heating circuit 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
56 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh22
Required settings:
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
QX: Cooling circ pump CC1 Q24
Rh23
Required settings:
Function mixing group 1: Cooling circuit 1
Configuration variants:
Function extension module 1: Cooling circuit 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
Rh24
Required settings:
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
QX: Heat circuit pump HC1 Q2*, Cooling circ pump CC1 Q24
Optional settings:
QX: 2nd pump speed HC1 Q21
* see key.
57 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh25
Required settings:
Function mixing group 1: Cooling circuit 1
Configuration variants:
Function extension module 1: Cooling circuit 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
QX: Heat circuit pump HC1 Q2*
Optional settings:
QX: 2nd pump speed HC1 Q21
* see key.
Rh26
Required settings:
Function mixing group 1: Heating circuit 1
Configuration variants:
Function extension module 1: Heating circuit 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
QX: Cooling circ pump CC1 Q24
Rh27
Required settings:
Function mixing group 1: Heating circuit 1
Function mixing group 1: Cooling circuit 1
Configuration variants:
Function extension module 1: Heating circuit 1
Function extension module 1: Cooling circuit 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 2-pipe system cooling
58 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
4.1.6
Rh30
Required settings:
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
Rh31
Required settings:
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
QX: Cooling circ pump CC1 Q24
59 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh32
Required settings:
Function mixing group 1: Cooling circuit 1
Configuration variants:
Function extension module 1: Cooling circuit 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
Rh33
Required settings:
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
QX: Heat circuit pump HC1 Q2*
BX: Outside sensor B9
Optional settings:
QX: 2nd pump speed HC1 Q21
* see key.
60 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh34
Required settings:
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
QX: Heat circuit pump HC1 Q2*, Cooling circ pump CC1 Q24
Optional settings:
QX: 2nd pump speed HC1 Q21
* see key.
Rh35
Required settings:
Function mixing group 1: Cooling circuit 1
Configuration variants:
Function extension module 1: Cooling circuit 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
QX: Heat circuit pump HC1 Q2*
Optional settings:
QX: 2nd pump speed HC1 Q21
* see key.
61 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh36
Required settings:
Function mixing group 1: Heating circuit 1
Configuration variants:
Function extension module 1: Heating circuit 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
Optional settings:
QX: 2nd pump speed HC1 Q21
Rh37
Required settings:
Function mixing group 1:Heating circuit 1
Configuration variants:
Function extension module 1: Heating circuit 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
QX: Cooling circ pump CC1 Q24
62 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh38
Required settings:
Function mixing group 1: Heating circuit 1
Function mixing group 1: Cooling circuit 1
Configuration variants:
Function extension module 1: Heating circuit 1
Function extension module 1: Cooling circuit 1
Configuration > Heating circuit 1 (5710): On
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
4.1.7
Rh40
Required settings:
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
63 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh41
Required settings:
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
QX: Cooling circ pump CC1 Q24
Rh42
Required settings:
Function mixing group 1: Cooling circuit 1
Configuration variants:
Function extension module 1: Cooling circuit 1
Configuration > Cooling circuit 1 (5711): 4-pipe system cooling
64 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
4.2
4.2.1
Rh1
Required settings:
Configuration > Heating circuit 2 (5715): On
Rh2
Required settings:
Configuration > Heating circuit 2 (5715): On
QX: Heat circuit pump HC2 Q6*
Optional settings:
QX: 2nd pump speed HC2 Q22
65 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh3
Required settings:
Function mixing group 1: Heating circuit 2
Configuration variants:
Function extension module 1: Heating circuit 2
Configuration > Heating circuit 2 (5715): On
4.3
4.3.1
Rh1
Required settings:
Configuration > Heating circuit 3 (5721): On
66 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Rh2
Required settings:
Configuration > Heating circuit 3 (5721): On
QX: Heat circuit pump HC3 Q20*
Optional settings:
QX: 2nd pump speed HC3 Q23
* see key.
Rh3
Required settings:
Function mixing group 1: Heating circuit 3
Configuration variants:
Function extension module 1: Heating circuit 3
Configuration > Heating circuit 3 (5721): On
67 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
4.4
Consumer circuit 1
Le1
Required settings:
Configuration > Function input H1: Consumer request VK1 or Consumer
request VK1 10V
Configuration > Consumer circuit 1 (5750): Heating
Le2
Required settings:
Configuration > Function input H1: Consumer request VK1 or Consumer
request VK1 10V
Configuration > Consumer circuit 1 (5750): Heating
QX: Cons circuit pump VK1 Q15
Le4
Required settings:
Configuration > Function input H1: Consumer request VK1 or Consumer
request VK1 10V
Configuration > Consumer circuit 1 (5750): 2-pipe system cooling
68 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Le5
Required settings:
Configuration > Function input H1: Consumer request VK1 or Consumer
request VK1 10V
Configuration > Consumer circuit 1 (5750): 2-pipe system cooling
QX: Cons circuit pump VK1 Q15
Le7
Required settings:
Configuration > Function input H1: Consumer request VK1 or Consumer
request VK1 10V
Configuration > Consumer circuit 1: (5750): 4-pipe system cooling
Le8
Required settings:
Configuration > Function input H1: Consumer request VK1 or Consumer
request VK1 10V
Configuration > Consumer circuit 1: (5750): 4-pipe system cooling
QX: Cons circuit pump VK1 Q15
69 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
4.5
Consumer circuit 2
Le1
Required settings:
Configuration > Function input H1: Consumer request VK2 or Consumer
request VK2 10V
Configuration > Consumer circuit 2 (5751): Heating
Le2
Required settings:
Configuration > Function input H1: Consumer request VK2 or Consumer
request VK2 10V
Configuration > Consumer circuit 2 (5751): Heating
QX: Cons circuit pump VK2 Q18
Le4
Required settings:
Configuration > Function input H1: Consumer request VK2 or Consumer
request VK2 10V
Configuration > Consumer circuit 2 (5751): 2-pipe system cooling
70 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Le5
Required settings:
Configuration > Function input H1: Consumer request VK2 or Consumer
request VK2 10V
Configuration > Consumer circuit 2 (5751): 2-pipe system cooling
QX: Cons circuit pump VK2 Q18
Le7
Required settings:
Configuration > Function input H1: Consumer request VK2 or Consumer
request VK2 10V
Configuration > Consumer circuit 2: (5751): 4-pipe system cooling
Le8
Required settings:
Configuration > Function input H1: Consumer request VK2 or Consumer
request VK2 10V
Configuration > Consumer circuit 2: (5751): 4-pipe system cooling
QX: Cons circuit pump VK2 Q18
71 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
4.6
Le1
Required settings:
Configuration > Function input H1: Min flow temp setpoint or Heat request
10V
Le2
Required settings:
Configuration > Function input H1: Min flow temp setpoint or Heat request
10V oder Release swimming pool
QX: H1 pump Q15 or H2 pump Q18 or H3 pump Q19
Le4
Required settings:
Pump Hx > H1 refrigeration request (2015, 2040, 2051): 2-pipe system
cooling
Configuration > Function input H1: Refrigeration request or Refrigeration
request 10V
Le5
Required settings:
Pump Hx > H1 refrigeration request (2015, 2040, 2051): 2-pipe system
cooling
Configuration > Function input H1: Refrigeration request or Refrigeration
request 10V
QX: H1 pump Q15 or H2 pump Q18 or H3 pump Q19
72 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Le7
Required settings:
Pump Hx > H1 refrigeration request (2015, 2040, 2051): 4-pipe system
cooling
Configuration > Function input H1: Refrigeration request or Refrigeration
request 10V
Le8
Required settings:
Pump Hx > H1 refrigeration request (2015, 2040, 2051): 4-pipe system
cooling
Configuration > Function input H1: Refrigeration request or Refrigeration
request 10V
QX: H1 pump Q15 or H2 pump Q18 or H3 pump Q19
73 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
4.7
Uf1
Required settings:
QX: System pump Q14
Uf2
Required settings:
Function mixing group 1: Primary contr/system pump
Configuration variants:
Function extension module 1: Primary contr/system pump
74 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
4.8
Swimming pool
Sb1
Required settings:
BX: Swimming pool sensor B13
Sb2
Required settings:
Swimming pool > With solar integration (2080): Yes
BX: Swimming pool sensor B13
Sb3
Required settings:
Configuration > Function input H1: Release swi pool source heat
BX: Swimming pool sensor B13
QX: Swimming pool pump Q19
Old devices:
Configuration > Function input H1: Release swimming pool
QX: H1 pump Q15 or H2 pump Q18 or H3 pump Q19
Sb4
Required settings:
Swimming pool > With solar integration (2080): Yes
Configuration > Function input H1: Release swi pool source heat
BX: Swimming pool sensor B13
QX: Swimming pool pump Q19
Old devices:
Configuration > Function input H1: Release swimming pool
QX: H1 pump Q15 or H2 pump Q18 or H3 pump Q19
75 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
4.9
Pressureless header
HWe1
Required settings:
BX: Common flow sensor B10
HWe2
Required settings:
LPB system> Device address (6600): 1 (cascade master)
BX: Common flow sensor B10
Optional settings:
BX: Cascade return sensor B70
HWe3
Required settings:
LPB system > Device address (6600): 216 (Kaskaden-Slave)
HWe4
Required settings:
LPB system > Device address (6600): 1 (cascade master)
QX: Cascade pump Q25
BX: Common flow sensor B10
Optional settings:
BX: Cascade return sensor B70
HWe6
Required settings:
Function mixing group 1: Return controller cascade
Configuration variants:
Function extension module 1: Return controller cascade
LPB system > Device address (6600): 1 (cascade master)
76 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Overview of use
Solar
Heat
pump
zones
RVA78.690
RVA78.690
OeG 8
RVS46.530
RVS46.530
OeG 7
RVS46.543
OeG6
RVS46.543
RVS21.826
OeG5
RVS21.826
OeG4
RVS41.813
RVS41.813
OeG3
RVS61.84
Boiler
X
LMS 14/15
OeG2
RVS43.345
RVS43.143
OeG1
RVS63.243
RVS63.283
RVS13.123
RVS13.143
RVS53.183
Partial diagrams
Oil / gas
OeG
X
X
X
X
X
OeG 10
OeG 11
X
X
OeG 12
OeG 13
OeG 14
OeG 15
RVS43.143
OeG 9
X
X
Heat
pump
RVS43.345
LMS 14/15
RVS61.84
Solar
zones
Boiler
RVS63.243
RVS63.283
RVS13.123
RVS13.143
RVS53.183
Partial diagrams
Oil / gas
Ho
Ho1
Ho2
Ho3
Ho4
77 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Heat
pump
RVS61.843:
RVS41.813
RVS21.826
RVA78.690
RVA78.690
Solar
RVS46.530
RVS46.530
RVS46.543
zones
Boiler
LMS 14/15
RVS43.345
RVS63.243
RVS63.283
RVS43.143
RVS13.123
RVS13.143
RVS53.183
Partial diagrams
Oil / gas
Heat pump
WP
WP10
WP11
WP14
WP15
WP18
WP19
WP22
WP23
WP30
WP31
WP34
WP35
WP38
WP39
WP42
WP43
WP50
WP51
WP60
WP61
RVS43.345
LMS 14/15
RVS61.843:
RVS41.813
RVS21.826
RVS46.543
Sol213
Sol1427
Sol3141
Sol4247
Sol4852
Solar
zones
RVS63.243
RVS63.283
Heat
pump
RVS43.143
Boiler
RVS13.123
RVS13.143
RVS53.183
Partial diagrams
Oil / gas
Solar
Sol
Sol1
X
X
X
78 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Heat
pump
RVS43.345
LMS 14/15
RVS61.843:
Sp 2
Sp 4
Sp 5
Solar
RVA78.690
RVS46.530
RVS46.543
RVS21.826
RVS41.813
zones
Boiler
RVS63.243
RVS63.283
Sp1
RVS13.123
RVS13.143
RVS53.183
RVS43.143
Partial diagrams
Oil / gas
Sp
TWWSp 2
TWWSp 4
TWWSp 5
TWWSp 13
TWWSp 14
TWWSp 16
TWWSp 17
TWWSp 19
TWWSp 20
TWWSp 22
TWWSp 23
TWWSp 25
TWWSp 26
Solar
zones
LMS 14/15
TWWSp 28
TWWSp 29
RVA78.690
RVS46.530
RVS46.543
RVS43.345
RVS21.826
RVS63.243
RVS63.283
RVS41.813
Heat
pump
RVS43.143
TWWSp 1
RVS61.843:
Boiler
RVS13.123
RVS13.143
RVS53.183
Partial diagrams
Oil / gas
TWWSp
79 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Heat
pump
RVS61.843:
RVS41.813
RVS21.826
RVS46.543
RVS46.530
RVA78.690
Boiler
Heat
pump
LMS 14/15
RVS61.843:
RVS41.813
RVS21.826
RVS46.543
RVS46.530
RVA78.690
Rh 3
RVS43.345
RVS43.345
RVS63.243
RVS63.283
Rh 2
RVS43.143
Rh1
RVS13.123
RVS13.143
RVS53.183
RVS63.243
RVS63.283
Solar
zones
Boiler
LMS 14/15
RVS43.143
Oil / gas
Partial diagrams
RVS13.123
RVS13.143
RVS53.183
Instantaneous
DHW heater
TWWDl
TWWDl 2
TWWDl 3
TWWDl 4
TWWDl 6
TWWDl 8
Solar
Partial diagrams
zones
Heating/cooling
circuit 1
Oil / gas
TWWDl 9
Rh
Rh 57
Rh 810
Rh 12
Rh 14
Rh 15
Rh 16
Rh 2027
Rh 30
Rh 3132
Rh 33
Rh 3435
Rh 36
Rh 3738
Rh 40
Rh 4142
X
X
80 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
Siemens
Building Technologies
Heat
pump
RVS43.345
LMS 14/15
RVS61.843:
RVS41.813
RVS21.826
RVS46.543
RVS46.530
Partial diagrams
Le1
Le 2
zones
RVS43.345
LMS 14/15
RVS61.843:
RVS41.813
RVS21.826
RVS46.543
RVS46.530
Solar
zones
Heat
pump
Boiler
Heat
pump
RVS43.345
LMS 14/15
RVS61.843:
RVS41.813
RVS21.826
RVS46.543
RVS46.530
X
X
X
X
X
X
X
X
X
X
X
X
X
X
X
Rh 3
X
X
X
X
X
X
X
X
X
Rh1
X
X
X
X
X
X
X
X
X
Rh 2
X
X
X
X
X
X
X
X
X
Rh 3
X
X
X
X
X
X
X
Le 4
Le 5
Le 7
Le 8
RVA78.690
Boiler
RVS63.243
RVS63.283
X
Solar
zones
Oil / gas
RVS43.143
RVS13.123
RVS13.143
RVS53.183
X
Rh 2
RVA78.690
RVS63.243
RVS63.283
Partial diagrams
Oil / gas
Rh
Rh1
RVA78.690
Boiler
RVS63.243
RVS63.283
Rh
RVS43.143
RVS13.123
RVS13.143
RVS53.183
Partial diagrams
Oil / gas
RVS43.143
Le
RVS13.123
RVS13.143
RVS53.183
Heating circuit 2
Heating circuit P / 3
Consumer circuits
81 / 84
CE1P2359en_10
25.03.2011
Siemens
Building Technologies
Heat
pump
LMS 14/15
RVS61.843:
RVS41.813
RVS21.826
RVS41.813
RVS21.826
Sb 1
X
X
X
X
X
X
X
Sb 2
X
X
X
X
X
X
X
Sb 3
X
X
X
X
X
X
X
Sb 4
X
X
X
X
X
X
X
Partial diagrams
HWe 1
HWe 2
HWe 3
HWe 4
HWe 6
RVS46.530
RVA78.690
RVA78.690
Pressureless header
RVS46.530
Solar
zones
X
X
X
X
X
X
X
RVA78.690
RVS46.530
RVS46.543
RVS21.826
RVS41.813
Heat
pump
RVS61.843:
Solar
RVS61.843:
Boiler
LMS 14/15
RVS46.543
Heat
pump
LMS 14/15
RVS43.345
zones
Boiler
RVS43.345
Uf2
Solar
zones
Oil / gas
RVS63.243
RVS63.283
RVS13.123
RVS13.143
RVS53.183
RVS43.143
Uf
Uf1
RVS46.543
Boiler
RVS43.345
Partial diagrams
Oil / gas
RVS63.243
RVS63.283
Sb
RVS43.143
RVS13.123
RVS13.143
RVS53.183
Partial diagrams
Oil / gas
RVS63.243
RVS63.283
HWe
RVS43.143
RVS13.123
RVS13.143
RVS53.183
Primary
controller/system pump
(heat exchanger)
Swimming pool
82 / 84
CE1P2359en_10
25.03.2011
Index
D
Diagram key............................................................ 5
K
Key plant diagrams ................................................. 5
P
Partial diagram
Instantaneous DHW heater............................... 46
Pump heating circuit.......................................... 66
Partial diagrams
Buffer storage tank.............................................38
Heat pump .........................................................18
Heating / cooling circuit 1...................................51
Heating circuit 2 (EM) ........................................65
Pressureless header..........................................76
Primary controller / system pump ......................74
Solar...................................................................26
Swimming pool...................................................75
83 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011
84 / 84
Siemens
Building Technologies
CE1P2359en_10
25.03.2011