Typical Desuperheater Installations: Block 15
Typical Desuperheater Installations: Block 15
Typical Desuperheater Installations: Block 15
Module 15.4
Typical Desuperheater
Installations
15.4.1
Block 15 Desuperheating
There are a number of important considerations to take into account when installing a
desuperheater, namely:
o
The control valves used on the cooling water line and the superheated steam line.
Safety
valve
Desuperheater
Superheated
steam
supply
Temperature
regulating
control valve
Temperature
controller
Non
return
valve
Cooling
water
Temperature - The most effective desuperheating will be achieved using cooling water that
is hot, preferably as close to the saturation temperature as possible. However, cooling water
temperatures as low as 5C could be used if absolutely necessary.
The use of hot water has the following advantages:
- It minimises the time period for which water particles are suspended in the steam.
- It evaporates more quickly.
- It minimises the amount of water falling to the inside walls of the pipework.
There are however, two disadvantages to using high temperature cooling water:
1. The higher the temperature of the cooling water, the greater the required flowrate due to
its lower cooling effect.
2. Unless a supply of the water at the required temperature is available, additional heating
mechanisms may have to be incorporated.
Due to the benefits of using hot water, it is logical to insulate the hot water supply pipes to
minimise heat loss, and to protect personnel.
15.4.2
Block 15 Desuperheating
Quality - The quality of the injected water is important. The Total Dissolved Solids (TDS) content
of the injection water should be as low as possible, as any solids that come out of solution will be
deposited on:
- The faces of valves.
- The small orifices in the desuperheater nozzles.
- The inner side of the piping downstream of the desuperheater.
In addition to reducing the TDS levels, all cooling water should be passed through a suitable
strainer installed before the water control valve.
o
Pressure and flowrate - As mentioned in Module 15.2, the pressure of the cooling water,
along with the area of the nozzles, determines the flow of cooling water into the desuperheater.
Table 15.3.1 shows the typical minimum pressures (above the superheated steam pressure)
required for each type of desuperheater. It should be noted that these might vary between
manufacturers and for different steam pressures.
If a booster pump is used, a spill back line will be required to ensure that there is always
sufficient flow through the pump at times of low cooling water demand.
Control - A pressure drop will inevitably be required over the water control valve. When using
cooling water close to saturation temperature, care is needed to ensure that the pressure drop
is not large enough to cause the water to flash into steam.
An equal percentage characteristic plug in the water control valve may be selected, which will
usually complement the pump characteristic.
Source - The availability of water at high pressure and temperature may be difficult. There are
a number of possible sources of the cooling water; and options include:
- Water from the pressure side of the boiler feedpump (providing the boiler uses modulating
level control).
- De-mineralised water.
- Condensate.
- Town water. This however may require treatment to improve the quality, otherwise salts may
be deposited on the inside of the desuperheater downstream pipework.
Desuperheater installation
The total installed length of a desuperheater station will vary with size and type, but it is typically
about 7.5 m.
Most desuperheaters can be installed in any direction (the variable orifice type is a notable
exception), but if installed vertically, the flow should be upwards. The venturi type is best installed
in a vertical pipe with the flow in the upward direction, as this aids mixing of the water and the
steam. However, such installations are not usually possible due to the vertical space required.
15.4.3
Block 15 Desuperheating
The minimum distance from the point of water injection to the temperature sensing point is
critical:
o
If the sensor is too close to the water injection point, the mixing of the steam and the water
will not have been completed, and the temperature sensor will give a false output.
If the sensor is too far away, it will make the installation unnecessarily long.
The minimum installation distance will vary between different types of desuperheater and with
different manufacturers. It is usually specified as a function of the temperature difference between
the required outlet temperature and either the inlet temperature or the coolant temperature.
Figure 15.4.2 shows a typical manufacturers sensor positioning chart.
Difference between saturation and outlet temperatures (C)
125
100
75
50
25
24
22
20
18
Single nozzle
axial injection
type
16
14
12
10
8
Variable orifice
type
6
4
2
0
100
50
150
200
Difference between coolant and outlet temperatures (C)
250
Separator station
Efficient drainage of the pipework following the desuperheater is essential. To ensure that water
cannot accumulate at any point, the pipe should be arranged to fall approximately 20 mm per
metre in the direction of flow, and should be provided with a separator station.
The steam trap used to drain the separator should be carefully selected to prevent air binding,
and the discharge pipe from the steam trap should have ample capacity to deal with the drainage
and it should be fixed as near to vertical as possible. In addition, there must be sufficient space
in the drainage pipe for the water to flow down and air to pass up the pipe. The steam trap must
also be able to withstand superheat conditions.
On critical applications, for example, prior to a turbine, a separator is even more important; the
separator station will remove entrained water in the case of control failure, and prevent too
much water being added to the steam.
15.4.4
Block 15 Desuperheating
Isolation valves
To allow maintenance to be safely carried out, isolation valves are recommended upstream of:
o
The desuperheater.
Typically, these should be installed approximately, but no less than 10 pipe diameters from the
item they are isolating.
Safety valve
A safety valve may be required to protect equipment downstream of the desuperheating station
from overpressure, in the event of failure of the pressure control station.
It is necessary to ensure discharge pipework from the safety valve is led away to a safe area. This
is of particular importance as high temperature superheated steam may be discharged.
Most equipment to be used on steam systems is designed with saturated steam in mind. It is
therefore important that all equipment used in a desuperheater station will tolerate both the
maximum temperature and pressure of the superheated steam.
Most equipment will have specified pressure and temperature limitations that are based on the
nominal pressure (PN) rating of the material and the specific design of the device. By definition,
the PN rating is the maximum pressure that a material can withstand at 120C. For example, a
PN16 rating means that the material will withstand a pressure of 16 bar g at 120C. At higher
temperatures, the maximum pressure will decrease, however, the exact relationship varies and
depends on the material.
In addition, components such as gaskets, fasteners and internal components may have a further
limiting effect on the maximum temperature and pressure.
45
Pressure (bar g)
40
30
PN40
25
20
PN25
16
10
PN16
100
120
140
160
180
200
220
240
260
280
300
Temperature (C)
Fig. 15.4.3 PN rating - Temperature / pressure limitations
Controls
The selection and installation of the control devices to be used in a desuperheater station are an
important consideration, as they can affect the overall turndown of the desuperheater. If the
controls installed have a lower turndown ratio than the desuperheater itself, the turndown of the
desuperheater station will be reduced (refer to Module 15.2)
Further information on basic control theory and practice can be found in Blocks 5 to 8 inclusive.
The Steam and Condensate Loop
15.4.5
Block 15 Desuperheating
Selection
When selecting a suitable type of desuperheater for a particular application, the following factors
need to be considered:
o
Separator station - This is probably one of the most important considerations, as the different
types of desuperheater vary significantly in the range of superheated steam flowrates that can
be effectively desuperheated.
It is important to note here that, although ensuring that the device will have sufficient turndown
for the flow likely to be encountered, it is important not to specify more turndown capability
than is really needed. This predominantly affects cost, but it can also lead to poor system
performance. Poor performance is often aggravated by the fact that most desuperheaters
tend to perform better at the higher end of the specified flowrates and a system designer
would tend to allow for increases in capacity due to expansion. As an extreme example, if the
maximum flow specified was ten times the current requirement (in order to take into account
future growth), the desuperheater will operate between 1 and 10% of its full flowrate instead
of the 10% to 100% it is designed for.
Available coolant supply pressure - The choice of desuperheater type will also depend on
the availability of cooling water at the necessary pressure. It would provide a cost advantage
to use cooling water that is already available, for example, from the pressure side of a boiler
feedwater pump.
If the available pressure were not sufficient for a particular type of desuperheater, additional
pumping arrangements would have to be made.
15.4.6
Block 15 Desuperheating
A typical manufacturers selection chart is shown in Figure 15.4.4. It is based on the typical
performance and installation characteristics, which can be found in Table 15.3.1.
The method used to size a desuperheater will vary depending on the particular manufacturer
and the type of desuperheater, and therefore it is outside the scope of this publication.
Is required steam
flow turndown
<3:1
Yes
No
Is required steam
flow turndown
<5:1
Is final
temperature
>Ts + 10C
Yes
Is final
temperature
>Ts + 3C
Yes
No
No
Yes
Is coolant available
with superior pressure
>0.5 bar
Yes
Is coolant available
with superior pressure
>1 bar
Single
nozzle,
axial
injection
No
Yes
Venturi
type
No
No
No
No
Is required steam
flow turndown
<8:1
Is final
temperature
>Ts + 8C
Is coolant available
with superior pressure
>4 bar
Multiple
nozzle, axial
injection
(fixed area)
Yes
Yes
Yes
No
No
No
No
Is required
steam flow
turndown
<12:1
Is final
temperature
>Ts + 8C
Is coolant available
with superior pressure
>3.5 bar
Multiple
nozzle, axial
injection
(variable area)
Yes
Yes
Yes
No
No
No
No
Is required
steam flow
turndown
<50:1
Is final
temperature
>Ts + 6C
Is coolant available
with superior pressure
>steam pressure
Is atomising
steam
available
>4 bar
Yes
No
No
Is required
steam flow
turndown
>50:1
Yes
Yes
Is final
temperature
>Ts + 2.5C
No
Yes
Is coolant available
with superior pressure
>0.4 bar
Yes
No
Yes
Steam
atomising
type
Yes
Variable
office type
Fig. 15.4.4 Desuperheater selection chart
15.4.7
Block 15 Desuperheating
Typical applications
Applications
Food
Textiles
Tobacco
Methanol plants.
Sulphur plants.
Polymerisation plants.
Chemical.
Vacuum distillation start-up heaters.
Glycol and ethylene plants.
Aromatics recovery.
Vinyl chloride plants.
Thermal and catalytic crackers.
Vacuum distillation.
Refineries
Brewing and distilling
Boiler and turbine installations
15.4.8
Polymerisation plants.
Sulphur plants.
De-salting.
Isomerisation processes.
Thermal and catalytic crackers.
Vacuum distillation.
Sulphur plants.
Steam heating systems.
Power generation.
Shipbuilding.
Block 15 Desuperheating
Questions
1. Which of the following are advantages of using hot, instead of cold water as the cooling
fluid in a desuperheater?
i. Water particles spend less time suspended in the steam.
ii. Less water impinges on the inside walls of downstream pipework.
iii. It reduces the absorption length as the water is evaporated more quickly.
a| i only
b| ii only
c| i and ii
d| i, ii and iii
2. Why is tap water not an ideal source for cooling water for most types of desuperheater?
a| It is generally available at low pressures
b| It is at room temperature
3. Why do most desuperheaters not reduce the temperature of the superheated steam
to saturation temperature?
i. The decrease in temperature difference between the cooling water and the steam
makes this difficult.
ii. The sensitivity of the cooling water flowrate controller will cause flooding of the
pipework at temperatures close to saturation.
iii. Producing steam at saturation temperature is not beneficial.
a| i only
b| ii only
c| i and ii
d| i, ii and iii
c| It will increase the amount of cooling water required for a given superheated steam flowrate
d| The statement is false and all desuperheaters should be specified with a significantly larger
turndown to allow for expansion
15.4.9
Block 15 Desuperheating
5. Using the selection chart (figure 15.4.4), which type of desuperheater would be most
suitable for use in a sugar refinery for the following conditions? The site already has a
boiler producing 10 bar g saturated steam. Coolant is available at 14 bar g.
Maximum superheated steam flow
16 000 kg / h
2 000 kg / h
TS + 7C
Answers
1: d, 2: d, 3: c, 4: a, 5: c, 6: d
15.4.10