Fixing and Bracing Guidelines For Timber Roof Trusses 2015 - Issue 1
Fixing and Bracing Guidelines For Timber Roof Trusses 2015 - Issue 1
Fixing and Bracing Guidelines For Timber Roof Trusses 2015 - Issue 1
R O O F
T R U S S E S
2015 - ISSUE 1
TABLE OF CONTENTS
Fixing & Bracing Guidelines For Timber Roof Trusses
General......................................................................................................................................................................................3
Design.......................................................................................................................................................................................3
Transport..................................................................................................................................................................................3
Job Storage...............................................................................................................................................................................3
Roof Layout..............................................................................................................................................................................4
Roofing Battens......................................................................................................................................................................12
Permanent Bracing.................................................................................................................................................................12
Girder Brackets.......................................................................................................................................................................20
Product Certification...............................................................................................................................................................32
GENERAL
The roof trusses you are about to install have been manufactured to
engineering standards. To ensure that the trusses perform as designed
it is essential that they be handled, erected and braced correctly.
The installation of prefabricated timber trusses is covered by the Australian
Standard AS 4440 Installation of nailplated timber trusses. The following
information is an abbreviated set of instructions designed to assist
with on site work and is not intended to replace the need to reference
AS 4440. The following recommendations apply to roof trusses on standard
domestic buildings where truss design details are obtained from MiTek
engineering programs. Details for commercial, industrial and non standard
domestic buildings, are to be provided by an Engineer responsible for the
overall building design.
DESIGN
1. Trusses are designed for normal roof, ceiling and wind loads to suit specific
jobs and conditions. Additional loading such as Solar Units, Hot Water
Tanks, Air Conditioning, etc. require special consideration. Advice should
be sought from the truss fabricator prior to commencing construction.
2. Wall frames and beams supporting trusses must be designed for the correct
roof loads. Refer AS 1684 Residential Timber-Framed Construction for
details.
3. Wind load is an important factor in the design and performance of roof
trusses. Ensure that you have correctly advised the truss fabricator with
regard to wind load requirements and that adequate provision has been
made to fix trusses to the support structure to withstand wind uplift forces.
4. Trusses are generally designed to be supported on the outer wall with inner
walls being non load bearing. Where it is necessary to use internal walls
for load bearing, these will be clearly shown on layouts. Note that the
supporting structure is stable in its own right.
5. Before ordering trusses, ensure that your particular requirements have
been provided for and that all relevant information has been supplied to
the truss manufacturer. If non standard trusses are being used, ensure
that erection and bracing details are known before erection commences.
6. For environments where the atmosphere may be conducive to corrosion,
such as some types of industrial and agricultural buildings, or buildings
near the ocean and subject to salt spray, consideration should be given to
the use of G8S stainless steel connector plates.
60 or less
Important Note
Spreader bar
TRANSPORT
Trusses must be fully supported when being transported in either a horizontal
or vertical plane. Care must be taken when tying down, not to put strain on
chords or webs.
Timber or metal right angle protectors are a satisfactory method of avoiding
damage. Unloading and handling is described opposite.
ROOF LAYOUT
NOTE: For 900mm spaced trusses, plasterers prefer to use 50mm battens.
Ridge
Dutch Hip
Standard truss
1. Lintel sizes suitable for truss loading. Consult AS 1684 or your truss
fabricator.
Jack truss/rafter
2. If trusses are not located directly over studs the top plate size must be in
accordance with AS 1684.
Hip truss/rafter
Ridge
Trusses
Standard truss
Gable
Jack truss/rafter
Top plate
Raking truss
Studs
Ridge
Trusses
Top plate
Verge trimming
Standard truss
NOTE: End gable truss to be located over end wall unless otherwise advised
by supplier.
T Shaped
Raking truss
Lintel at opening
Trusses
Top plate
Ridge
Studs
Frame Bracing
Ridge
Verge trimming
Girder truss
Saddle truss
L Shaped
The frame must be fully braced, plumb, and nailed home before the erection
of trusses is commenced.
Raking truss
It is convenient to mark the truss position on the wall plates before lifting
trusses. Use the layout drawing as your guide and note that the truss design
spacing must not be exceeded.
Verge trimming
Truncated girder
Standard truss
Hip truss/rafter
Jack truss/rafter
Girder truss
Ridge
Girder truss
GABLE ROOFS start with a gable truss at each end, fixing it to the top plate
at the position marked. These trusses must be temporarily braced back to the
ground or frame at the panel points.
Raking truss
HIP OR DUTCH GABLE start with the Dutch girder truss or the truncated
girder, placing it on the top plate at the position marked and temporarily
bracing it back to the frame. Locate hip and jack trusses and adjust girder
truss position before fixing.
Saddle truss
Ridge
Intermediate ties
as above
LINE Using a stringline along the Apex, place each intermediate truss
and fix it to the top plate at the position marked, spacing it with gauging
rods and ties.
Verge trimming
Gable Ends
Where a gable end is required, consult your truss fabricator for details of
construction and erection.
String line
A structure that is not level and is out of square will result in an ugly and
unsatisfactory roof line. Time is well spent in ensuring:
1. The load bearing top plates are level.
2. The structure is of the correct dimension.
3. The top plates as well as being level, are straight in their length .
4. The internal walls are set below the outer wall level by:
Unbattened ceiling 10mm. Battened ceiling 10mm plus
batten thickness.
Spacing Trusses
Camber
Trusses are built with a camber in the bottom chord. The camber is designed
to suit the span and load. A girder truss will have more camber than other
trusses. The camber is progressively taken up as the load from the roof
covering and ceiling is applied. Under no circumstances should trusses be
supported along the span (unless designed for) by blocking or propping.
The purpose of temporary bracing is to hold trusses straight and plumb prior
to fixing permanent bracing. All permanent bracing, ties, hold down, etc.
must be fixed prior to loading roof.
Camber
Erection Bracing
3000mm
(max)
3000mm
(max)
3000mm
(max)
3000mm
(max)
4000mm
(max)
The first truss should be erected straight and plumb to erection tolerances
given previously and temporarily braced to a rigid element, e.g. wall or
ground as shown on diagram following.
TrussSpacers.
Trusses
4000mm
(max)
4000mm
(max)
Alternative layout
3000mm
(max)
3000mm
(max)
4000mm
(max)
4000mm
(max)
Wall
Truss being
installed
TrussSpacers to
the Bottom Chord.
Solid props fixed to ground
at panel points.
Wall
IMPORTANT NOTE
TrussSpacers
These recommendations are a guide only for the erection of standard gable
trusses up to 13000mm span, and spaced at centres not exceeding 1200mm.
For trusses beyond these conditions, consult your truss fabricator.
TrussSpacer
Erection Tolerances
Tolerance is critical for both a good roof line and effective bracing. A stringline,
a plumb line or level should be used.
1. Trusses to be erected with minimal bow, in the truss and in any chord, with
a tolerance not exceeding the lesser of L/200 and 50mm, where L is as
defined as shown in diagrams.
Brace
Tie
Brace Top
Tie
Plate
Generally if a bow or tilt is evident to the eye, the truss has been erected
outside the tolerances.
Brace
Bow
Plumb
Truss
Truss
Bow
L
Truss
If timber ties are used, they must be continuous and be no less than 70 x 35
F5. Fix to each truss with a minimum of one 65mm nail and splice the ends
by lapping over two adjacent trusses. Short timber noggings between trusses
are not acceptable.
Bow
L
Height of
any
section
Out of
plumb
Support Tolerances
SUPPORT AT HEEL/CUT-OFF
When truss heel or end of cut-off truss extends over support with no reduced
bearing, the maximum tolerance is 50mm.
3 nails
4 nails
50mm max.
When truss heel or end of cut-off truss is shorter than wall support, the maximum
tolerance is half the wall thickness, up to 50mm. Check bearing strength where
bearing area is reduced.
D
Not greater than, 2
up to 50mm max.
D
Not greater than, 2
up to 50mm max.
Truss at right
angle to wall
Gap between
wall top plate
and trimmer
Internal Support
The maximum allowable tolerance at internal support is 100mm.
Fix 8 nails
to top plate
100mm max.
Overhang Supported
For overhang supported truss, the maximum tolerance is half the wall thickness,
up to 50mm. Check bearing strength where bearing area is reduced.
Fix trimmer to
truss bottom
chord with
2 MSA1465
MiTek screws
Gap between wall top
plate and trimmer
Fix 8 nails
to top plate
Minimum Grade
Maximum Truss
Spacing (mm)
90 x 35
MGP12
600, 900
120 x 35
MGP12
1200
D
Not greater than, 2
up to 50mm max.
Bracing
Length
(m)
1.5
2.0
3.0
3.5
5.5
6.0
6.5
7.5
9.0
0.6
0.9
1.2
1.5
1.8
2.1
2.4
2.7
NAILS - Use 3.05mm diameter glue coated or ring shank nails, minimum
65mm long for truss thickness up to 38mm or 75mm long for truss thickness
up to 50mm
BOLTS - Use M12 bolts with 50 x 50 x 3.0mm square washers or 55 dia. x 3.0mm
round washers.
SCREWS - Use No. 14 gauge x 65mm long up to 38mm timber or 75mm long
up to 50mm timber.
Fixing of block
pieces to wall
top plate in
accordance
with AS1684
recommendations
There are a number of different ways in which gable ends and verge overhangs
can be constructed. These include:
Truss bottom
chord
Cantilevered Battens
Underpurlines
Outriggers over Raking Truss
Verge Sprockets
The selection of a particular method will depend on a number of factors
including verge overhang distance, roof and ceiling material, truss spacing,
end wall construction, wind load and preferred local building practice and
cost. The following are typical details for each fixing method. For connection
details refer to MIRS-0016
CANTILEVERED BATTENS
Verge rafter
or barge board
Blocking to suit
@ 1200mm max centres
Standard truss
Gable overhang
Ceiling batten
UNDERPURLINS
Underpurlin overhang (or verge overhang)
CycloneTie: CT600 (typical)
Fly rafter
300mm (T/c)
450mm (B/c, web)
Verge rafter
or barge board
TRIPLE TRUSS
(nail both sides with bolts or screws at panel points)
Standard truss
Underpurlin
Join outer trusses to centre truss using the double truss details. In addition,
join trusses at each panel point with one M12 bolt or alternatively with two
sufficiently long No. 14 screws from each side (i.e. 4 screws at each panel
point).
Gable overhang
Ceiling batten
Fly rafter
Trip-L-Grip: TGL/R
Verge rafter
or barge board
Outrigger
Waling plate to be fixed to each Dutch Hip girder chord and web crossing with
nails, screws or bolts in accordance with M2RS-0008.
Gable overhang
If screws are used in FastFit MkIII and MKIV Girder Bracket, use 65mm screws
in double 35mm girder. With triple 35mm ply girder, use 65mm screws
in bracket and fix additional 65mm screws in back of girder truss behind
bracket. Use 3 screws for FastFit MKIII and 8 screws for FastFit MKIV Girder
Bracket. Alternatively, use 100mm No. 14 Type 17 hex head screws in bracket.
With multiple 50mm ply girder, use bolts or longer screws.
Standard
truss
Raking
truss
15mm
Ceiling batten
VERGE SPROCKETS
TG BC
Verge sprocket
length
Fly rafter
TG BC
Hip BC
Hip BC
Barge board
Verge sprocket
CycloneTie
(typical)
Jack TC
Standard truss
Verge overhang
Gable end stud
@ 600mm max. centres
TG HTC
Ceiling batten
TG BC
Jack BC
NOTES:
1. These connections are adequate, based on general domestic construction
practices which include at least two 2.5mm skew nails, with a penetration
of 10 times of nail diameter to supporting member, connecting each
member.
TS HTC
Figure 1. Typical trussed hip end connection for Wind Classification N1,
N2, N3 or C1
Detail D1 - Jack Truss to Hip Truss (maximum jack station 1800 mm)
Detail A1 or B1
Detail A1 or E1
Detail D1 or E1
Hip TC
Detail C1
Detail B1
Jack TC
Hip BC
Jack BC
NOTES:
1. For effective skew nailing, the nail shall be driven into one member not
closer than 25mm to no more than 38mm from the arris in contact with
the adjacent member. The nail shall be driven at an angle between 30
and 45 to the face into which the nail is driven.
Detail E1 - Jack Truss to Hip Truss (maximum jack station 3000 mm)
Hip TC
2. Where nails are smaller than the nominated size or other than plain shank
nails, or machine driven, or both, their performance shall not be inferior to
the nail size given.
3. Roof battens or purlins and ceiling battens shall be fixed to trusses in
accordance with approved specifications.
Jack TC
Trip-L-Grip: TGL/R
TG HTC
TG HTC
Hip BC
Jack BC
Hip TC
Jack TC
Detail A2
Detail C2
Detail E2 or F2
Detail D2
Detail B2
TG HTC
NOTES:
1. For effective skew nailing, the nail shall be driven into one member not
closer than 25 mm to no more than 38 mm from the arris in contact with
the adjacent member. The nail shall be driven at an angle between 30
and 45 to the face into which the nail is driven.
Hip TC
2. Where nails are smaller than the nominated size or other than plain shank
nails, or machine driven, or both, their performance shall not be inferior to
the nail size given.
3. Roof battens or purlins and ceiling battens shall be fixed to trusses in
accordance with approved specifications.
TS HTC
Jack TC
Jack TC
Hip TC
One 30 x 0.8mm
Structural TieDown
Strap (TD2230) with
4/2.8mm x 30mm
reinforced head nails
into each leg.
TS HTC
TG HTC
TG BC
Jack TC
Hip TC
Hip BC
Jack BC
(see detail B2)
Jack TC
Jack TC
Hip BC
TG HTC
CreeperConnector CC200
Jack BC
Hip TC
TG BC
Creeper
TC
Top Chord.
One 30 x 0.8mm
Structural TieDown Strap (TD2230)
with 4/2.8mm x 30mm reinforced
head nails to each leg and one
CreeperConnector (CC200L/R) with 6/2.8mm
x 30mm reinforced head nails into face of
each top chord.
Jack BC
Load direction E
Hip TC
CreeperConnectors
Installation:
55 for = 65
70 for = 90
75mm
45
Jack/cut-off truss
top chord
Hip/boomerang girder
truss top chord
mm
130
Suitable for pitches from 13 to 25 and that suffix L and R defines that the
product is designed for left hand or right hand connection.
30 to 80
2. With the short leg against the girder, align the Boomerang Connector with
the incoming truss with a 6mm offset above bottom edge of the bottom
chord. If necessary, bend the Boomerang Connector to the skew angle
before aligning.
Hip/boomerang
girder truss
bottom chord
Fix 3 nails
to mitred face
6mm
Jack/cut-off truss
bottom chord
SQUARE CUT
Hip/Boomerang
girder truss
3. Ensure the connector is flush with the chord surface and fix 15 nails into
the hip/boomerang girder bottom chord and 15 nails into vertical web and
bottom chord of the jack/cut-off truss.
Hip/boomerang
girder truss
bottom chord
Jack/Cut-off
truss
Creeper/Boomerang Connectors
Jack/cut-off truss
bottom chord
Suits double mitred jack/cut-off truss with skew angle from 17to 30.
Single mitre and square cut ends are not suitable for this method.
1. Locate jack/cut-off truss into position and fix 3/75mm nails through each
top and bottom chord to the hip/boomerang girder truss.
Jack/cut-off truss
top chord
Wind Classification
N2
N3
N4
N5
C1
C2
C3
Hip/boomerang girder
truss top chord
16.0
16.0
10.3
6.3
9.3
5.8
3.9
JD4
16.0
16.0
10.3
6.3
9.3
5.8
3.9
JD5
15.5
15.5
10.3
6.3
9.3
5.8
3.9
16.0
16.0
16.0
11.8
16.0
10.2
6.3
JD4
15.8
15.8
15.8
11.8
15.8
10.2
6.3
JD5
12.2
12.2
12.2
11.8
12.2
10.2
6.3
Jack/cut-off truss
bottom chord (min 90mm)
10
17 to 30
2. With the short leg against the girder, position the bend line along the tip of
the double mitre. Offset 6mm above the bottom of the bottom chords.
Hip/boomerang
girder truss bottom chord
6mm
Saddle
truss
One effective
65mm skew nail
driven through saddle
truss bottom chord
into supporting truss
top chord at each
intersection
of the truss
Jack/cut-off truss
bottom chord
Supporting truss
top chord
Hip/boomerang
girder truss bottom chord
Supporting
truss top chord
4. Wrap the Boomerang Connector around the mitre cut face and fix 3 nails
into the mitre fold.
Hip/boomerang
girder truss bottom chord
>450mm
Saddle truss
65mm nails
Fix 3 nails
into mitre
Jack/cut-off truss
bottom chord
Tap
65mm nails
5. Further wrap the connector flush with the jack/cut-off truss. Then fix another
15 nails into the vertical web and bottom chord of the jack/cutoff truss.
Hip/boomerang
girder truss bottom chord
Jack/cut-off truss
bottom chord
Saddle
truss
Fixing Details
1 x Universal Trip-L-Grip
N4, C2 & C3
Supporting
truss top chord
>450mm
Valley
truss
Roof Pitch 15
Saddle
truss
Saddle
truss
Supporting truss
top chord
One effective
65mm skew nail
driven through saddle
truss bottom chord
into supporting truss
top chord at each
intersection
of the truss
65mm nails
65mm nails
Block infill (minimum 75 x 35) to where the
saddle truss is cantilevered more than 450mm
or where the saddle truss is not supported by
two truss top chords, fixed to the saddle truss bottom
chord with 2/65mm nails, and to each
end to supporting truss top chord with 2/65mm nails
Supporting truss
top chord
11
One Trip-L-Grip
with 4/2.8 nails
to each face
OPTION 1
Saddle
truss
Y
Valley
truss
Splice
40 min.
45 min.
Truss
Top Chord
Supporting truss
top chord
OPTION 2
Splice
ROOFING BATTENS
45 min.
The stability of any roof system is reliant on the tile or sheeting battens.
The contract with the roofer should include the following provisions:
Roofing battens should be fixed securely to all truss top chords in accordance
with AS 1684 unless otherwise specified by local building regulations.
For multiple ply trusses, battens should be fixed securely to each ply of truss
top chord with at least one nail or other mechanical fixing. Battens wider than
50mm should be secured with two fixings to each ply.
Truss
Top Chord
Roof Battens at
max. 1200 crs.
Battens to be arranged so that on any truss top chord, not more than 1 in 3
battens are spliced and no two splices are adjacent.
OPTION 3
In the areas of roof not bounded on both sides by diagonal bracing, battens
should be continuous, if not use Batten Strapnails to splice.
Truss
Top Chord
Roof should not be loaded until all roofing battens are securely fixed.
WARNING: Some types of steel tile battens do not provide adequate
lateral restraint to truss top chords. Before using steel tile battens obtain
certification from your steel batten supplier confirming that their product
will provide at least the same lateral restraint as timber battens.
Splice
40 min.
40 min.
Bridging Batten same size and grade as the batten fixed to
Truss Top Chord using 1/14g type 17 screw with minimum
45mm penetration into top truss chord or equivalent
OPTION 4
Roof Battens at max 1200 crs. fixed to each truss
using 1/14g type 17 screw with minimum 45mm
penetration into truss top chord or equivalent
Roof truss
Roof batten
70 min.
Splice
45 min.
210 min.
Truss
Top Chord
Note: Batten splices.
Not more than 1 in 3 battens are
spliced on any truss top chord,
and no splices in battens over
girder trusses.
Note: Batten splices.
No two splices are to be
adjacent on any truss top chord.
OPTION 5
Metal Batten
40 min. overlap
Truss
Top Chord
Refer to manufacturers
specifications for
fixing lap splice
PERMANENT BRACING
The splice details have been designed to resist axial loads on battens
transmitted by truss top chord under the following criteria:
Before loading, roof trusses must be permanently braced back to the rigid
building element, such as support walls, to prevent rotation or buckling of
trusses under the weight of roof and ceiling material or under wind uplift.
Tie Downs -Batten to truss fixing should be checked for adequacy against
tie-down requirement.
NOTE: Either bugle or hexagon head screw types can be used for all of the
fixing options.
12
SpeedBrace
SpeedBrace is a bracing system for the bracing of trussed roofs in both low
wind speed and cyclone areas.
The forces in a roof of less than 8000 mm span are relatively low and may be
restrained by the use of a single SpeedBrace in a V configuration. The angle
of SpeedBrace to wall frame should be between 30 and 45, and each truss
should be crossed with a least two braces.
For roof lengths less than half span (h) use detail for Very Short Roofs below.
1. Very Short Roof where the roof length L is 1 to 11/2 times the half span
h of the roof truss.
BR
BR
Ridge
BR
BR
Pre-punched nailing made quick and easy with special MiTek 30 x 2.8
galvanized reinforced head nails.
Uniform strength assured performance.
2. Short Roof where the roof length L is 11/2 to 31/2 times the half span h
of the roof truss.
BR
Ridge
BR
120
When plasterboard ceilings are fixed direct to the bottom chords of trusses
or via battens in accordance with AS 1684, the horizontal wind load on the
roof and walls of a house is normally transferred to the bracing walls through
the diaphragm action of the plasterboard ceiling. This structural ceiling
diaphragm also provides lateral restraint to the truss bottom chords of the
trusses.
3. Long Roof where the roof length L is 31/2 to 4 times the half span h of
the roof truss.
BR
BR
Ridge
BR
BR
4. Very Long Roof where the roof length L is more than 4 times the half
span h of the roof truss.
BR
Ridge
The bracing layout is related to the span and shape of the roof.
BR
BR
Ridge
BR
BR
BR
Ridge
BR
SPEEDBRACE
BR
The increase in span increases the forces to be restrained requiring the use
of SpeedBrace in an X configuration. The angle of the SpeedBrace to the
frame should be between 30 and 45. Use a single or double SpeedBrace
with maximum overall truss length not exceeding values in Table 4.
BR
BR
Roof Pitch
Wind Classification
N3, C1
N4, C2
C3
Single Brace
LEGEND:
TRUSS/
SUPPORT
BRACING
BR
< 15
13.0
13.0
12.0
15 to 20
13.0
13.0
11.0
21 to 30
12.5
10.5
8.5
31 to 35
11.5
9.5
Not Suitable
36 to 45
9.5
8.0
Not Suitable
13.0
13.0
13.0
Double Brace
RIDGE
up to 45
13
Each truss should be crossed with at least four braces and bracing bays
should extend from the end trusses of the building unless noted otherwise.
1. Very Short Roofs. Where the
roof length L is very short
compared to the half span h
of the roof trusses and would
result in a brace angle greater
than 45, a diagonal bracing
arrangement is required each
side of the ridge line as given
below. Bracing bays should
be spaced across roof such
that the brace angle is always
between 30 and 45.
BR
BR
Ridge
BR
Roof Pitch
h
BR
BR
N4, C2
C3
< 15
16.0
15.5
Not Suitable
15 to 20
16.0
13.0
Not Suitable
< 15
16.0
16.0
16.0
15 to 20
16.0
16.0
15.5
21 to 30
16.0
14.5
Not Suitable
31 to 35
16.0
13.5
Not Suitable
36 to 45
13.5
Not Suitable
Not Suitable
Double Brace
BR
Ridge
BR
BR
N3, C1
Single Brace
Wind Classification
Timber
Noggings
Approx. span/6
3. Long Roofs. Where the roof length L is long compared to the half span
h of the roof trusses and would result in a brace angle less than 30,
two or more crossed bracing bays are required each side of the ridge to
ensure the brace angle is between 30 and 45 as shown.
BR
Ridge
Span
BR
BR
Ridge
BR
BR
BR
BR
1. Where the horizontal top chord length (HTL) is less than the truncated
girder station (TGS).
4. Very Long Roofs. As for long roofs, except continue bracing for length of
building such that each truss is crossed with at least four braces.
BR
BR
BR
BR
Ridge
BR
BR
BR
BR
BR
BR
TGS
HTL
2. Where the horizontal top chord length (HTL) is 1 to 1.5 times the truncated
girder station (TGS).
BR
Double Speedbrace
BR
BR
BR
BR
BR
HTL
14
TGS
BELL ROOF
3. Where the horizontal top chord length (HTL) is longer than 1.5 times the
truncated girder station (TGS).
BR
BR
BR
Jack
Truss/Rafter
TGS
BR
Bell Truncated
Standard
Breaking pitch
BR
BR
Ridge
BR
Bracing
requirement
for Jack
Trusses as
required
(not shown
for clarity)
HTL
BR
SKILLION
HIP ROOF
Where the roof consists of half trusses, the span of the half truss should be
taken as the half span h when using the above recommendations, and the
apex braced to supporting structure. See section on Treatment of Internal
Supports etc.
For roofs on buildings of rectangular plan with trussed hip ends or dutch
hip ends, bracing is required between apex of hip ends only. In such
cases the roof length L is taken as being the distance between the two
intersections of hip and ridgeline at each end of the building. One of the
recommended bracing layouts for gable roof then can be applied as
shown in (a) for roof length L half span h of the roof truss, except
where roof length L of standard truss is less than the half span h of
the roof truss, in which case bracing should be arranged as shown in (b).
NOTE:
The previous are typical layouts for bracing. However, for special
circumstances, e.g. small spans and complex roof shapes, bracing layout
will be supplied.
1. Always use MiTek 30mm x 2.8mm dia. Galvanized Reinforced Head Nails
when fixing SpeedBrace.
BR
BR
BR
2. At each truss, fix SpeedBrace to the top of the top chord with two nails.
Select nail holes most central to the timber edge. Flatten bracing while
nailing to avoid interference with battens.
Ridge
3. At end truss fix off the SpeedBrace as shown. A pair of tinsnips will cut
the brace. After fixing to top of top chord use your hammer to form a tight
bend and fix to face of top chord with three nails.
BR
BR
Ridge
h
BR
BR
End truss
(of braced bay)
4. To splice SpeedBrace, overlap or wrap around over one truss and fix with
three nails. Splice to be located at least 2500mm from heel end fixing,
measured along brace.
DUAL PITCHED
On dual pitched roofs and cut-off roofs where the ridge line is not central
on the building it may be necessary to determine bracing layout from a
combination of 1, 2, 3 and 4 above. In such cases each side of the ridge shall
be considered as a separate case.
BR
BR
BR
BR
Ridge
BR
BR
BR
BR
15
In addition to top chord bracing, cut-off and half trusses require bracing from
top chord to top plate at end nearest apex. Apply one bay of diagonal bracing
at each end of the run of trusses and intermediate bays at 10m centres for
long runs of trusses.
45 or less
CAUTION
The SpeedBrace must be positively fixed to the top plate otherwise the
bracing will be ineffective.
An alternative method can be used where it is desired to extend the brace to
the last truss or where the angles do not permit ready fixing to the top plate.
The last two trusses should be fixed to the wall top plate with a minimum of
two Trip-L-Grips to each truss, and timber block between trusses as shown.
Two nails to
each top chord
Trip-L-Grip
each side
SpeedBrace fixed
with two nails
Minimum 35mm
thick wall plate
(Refer to AS 1684 for
fixing of wall plate to
brickwork)
Cut-off or
half trusses
Trip-L-Grip, one to
each side of truss
Trip-L-Grip, one to
each side of truss
Angle of brace to
wall to be between 30 and 45
Where the standard trusses are supported by a girder truss or a beam rather
than a wall top plate, fix SpeedBrace at truss heel as shown following.
Brickwork
Girder Truss
or Beam
Girder
Bracket
Standard Truss
Two nails to the top of the truss and three to the side
Hip side
Treatment at Cantilevers
The force in the top chord bracing must be carried through to the wall plate by
diagonal bracing from the top chord to wall plate, as shown below.
Refer to
End Fixing Details
Valley side
Nogging spacing
SpeedBrace continuous
to truss heel
Two nails to
top chord
90 x 35 F5 minimum
noggings at spacing equal
to designed top chord
restraint centres between
incoming trusses
(see section A A- for details)
SECTION A-A
Cut-off
truss
SpeedBrace
back to point
over wall plate
90 x 35 F5 minimum timber block
fixed in line with bottom of bottom
chord fitted tightly between trusses
using framing anchors as shown.
Boomerang or Valley
girder truss directly
under the valley
Refer to
End Fixing Details
16
Cut-off
truss
Web stiffeners may be specified in lieu of web ties where it is difficult to fit
web ties because of the small number of trusses or the varying position of the
webs. eg. Truncated trusses and Hip trusses.
TrussGrip (TRG)
Roof truss
Angle of brace to
web tie to be between
30 and 45
4 nails
Angle of brace
to be between
30 and 45
2 nails
4 nails
Trip-L-Grip (TGL/R)
Load Direction A
The TrussSpacer can also be used as permanent lateral bracing for webs in
standard roof trusses for domestic constructions. The TrussSpacer can be
used as a web tie where truss designs require bracing to be applied to webs
for the following conditions.
Roof materials:
Ceiling material:
Spacing:
Pitch:
45max.
Span:
16m
Wind Classification:
Up to C2
Roof truss
4 nails
2 nails
4 nails
17
CT900
Timber
lintel
Top plate
CT400
3 nails to
each leg
CT900
Top plate
1 nail to Top Chord
3 nails to
each leg
CT600
600mm
max.
2 nails to ribbon
plate on each leg
3 nails to
underside of
top plate on
each leg
Top plate
Table 6
CT600
CT900
4 or 6 nails to timber
lintel on each leg
Timber
lintel
Maximum
Top Chord size
Maximum Pitch
(degree)
140 x 35
90 x 35
26.0
140 x 45
90 x 35
22.5
140 x 35
90 x 45
19.0
140 x 45
90 x 45
16.0
90 x 35
2 / 90 x 35
37.5
90 x 45
2 / 90 x 35
33.5
90 x 35
2 / 90 x 45
22.5
90 x 45
2 / 90 x 45
19.0
1 nail to
Top Chord
CT600
Top
Plate
3 nails to
underside of
Top Plate on
each leg
Top plate
18
Timber lintel
BLOCKFAST (BF)
1 nail to top of
truss in each leg
1 nail to
Top Chord
Timber
lintel
NEARSIDE
4 nails in each leg
into the target rings
on near side
Top plate
3 nails to
each leg
25 approx.
1 nail to Top Chord
FARSIDE
Top plate
1 nail to
top plate
on each leg
3 nails to
each leg
25 approx.
CycloneTie
(CT1200)
Top plate
NOTES:
1. Nails are to be FAP 32 V5 GKN pneumatically driven.
2. Safety gear must be worn when nailing.
3. See product data sheet for other fixing variations.
BearingPlate (BP80)
The BearingPlate has been developed to improve the crushing resistance of
wall plates under heavily loaded trusses. The positioning of a ConnectorPlate
onto the bottom chord of the truss above the BearingPlate as shown in these
specifications, will also improve the crushing resistance of the bottom chord
to match the wall plate.
4,6 or 8 Nails
to stud on each leg
Stud
Position the BearingPlate centrally along the top of the wall plate and
such that it projects at least 20mm on either side of the supported truss.
Fix with four 30 x 2.8mm MiTek Reinforced Head Nails. The bottom chord
of the truss is to be reinforced with a ConnectorPlate located not more
than 6mm above the BearingPlate, and projects at least 10mm beyond the
BearingPlate, as illustrated.
Fix MiTek MSA1430 screws onto the base of the cleat into the support.
(Use longer MiTek MSA1465 screws if fixing down to double top plates or
supporting beams for higher uplift capacity). The required number of screws
depends on the width of the support as shown in the Table 7.
4 MiTek
MSA1430
screws into
truss
See Table 7
10mm
maximum
Support
Typical Gang-Nail
ConnectorPlate
MiTek
BearingPlate
(BP80)
Table 7
Minimum support width (mm)
90
70
45
10mm
minimum
ConnectorPlate
projection
Wall width
19
INTERNAL SUPPORT
FastFit MKIII Girder Bracket can also be installed with M12 bolts for speedy
installation.
Typical Gang-Nail
ConnectorPlate
6mm maximum gap between
BearingPlate (BP80)
and ConnectorPlate
10mm minimum
ConnectorPlate
projection on both sides
20mm mimimum
BearingPlate (BP80)
projection on both sides
FastFit MKIII Girder Bracket can be used in cyclonic wind areas to restrain
large uplift if additional washers and screws are used as specified.
Wall plate
Prop stud width
GIRDER BRACKETS
Girder Brackets have been developed to support standard trusses on the
bottom chord of girder trusses or beams, and may also be used to connect
beams to beams. The brackets have been designed and tested to ensure
that the load of the standard truss is transferred to the girder truss or beam
without inducing rotation in the supporting member.
FastFit MKIV Girder Bracket can also be installed with M12 bolts.
FastFit MKIII Girder Bracket can be installed with MiTek self tapping screws for
speedy installation.
20
MKII
A Hip Girder Bracket HGB35 can be installed on one or both sides of FastFit
Girder Brackets GB340, GB440 and GB475 using screw holes which are
aligned with the screw holes in the FastFit Girder Bracket.
Supported Truss
M12 Bolts
MkII
Girder Bracket
1 locating
nail to
each wing
to hold bracket
while drilling holes
4 nails to under side
4 nails to under side of
for 45mm Girder
Supported Truss
Truss Bottom Chords.
See below for 35mm bottom chords
120
min.
2. If bolts are used to fix bracket, drill through 12mm pre-punched holes
into girder. Fix bracket with bolts and washers. No additional fasteners are
required for multiple ply girders beyond nominal fixing.
3. If screws are used in FastFit MkIII and MkIV Girder Bracket, drive screws
through 7mm pre-punched holes into girder. Use 30mm screws in single
ply and 65mm screws in double 35mm ply girder. With triple 35mm ply
girder, use 65mm screws in bracket and fix 3 additional 65mm screws in
back of girder truss behind bracket. Alternatively, use 100mm No. 14 Type
17 hex head screws in bracket. With multiple 50mm ply girder, use bolts
or longer screws.
M12 Bolts
Washer
5. Fix supported truss to bracket according to diagram for type of Girder Bracket.
6. All Fasteners (bolts, screws and nails) must be tightly secured before
trusses are loaded.
Supported Truss
M12 bolts
Double Truss
Fasten all chords and webs together with 3.05 x 75mm glue coated or ring
shank nails (at angle), or No. 14 x 65mm screws (35mm timber) or 75mm
screws (50mm timber) at 300 centres, staggered on one side only.
FastFit MkIII
Girder Bracket
Triple Truss
Fasten each outer ply to middle ply using details for double truss. In addition,
join trusses at each panel joint with one M12 bolt.
GENERAL NOTES
Apply to all Girder Bracket types:
1 locating
nail to each
wing to hold
bracket while
drilling holes
1. Holes to be drilled to suit M12 bolts. Do not drill oversized holes. Use
hexagonal head bolts. DO NOT USE REDUCED SHANK OR CUP HEAD BOLTS.
2. Use 50 x 50 x 3 mm square or 56 mm diameter x 3 mm round washer for
M12 bolts.
3. Nails, where specified, to be MiTek 30 x 2.8mm diameter hot dipped
galvanised reinforced head nails.
4. Minimum Girder Truss bottom chords apply to each type of Girder Bracket.
Refer Installation Instruction drawings.
90
min.
M12 bolts
21
Washer
M12 bolts
Supported
Truss
FastFit
MkIII
Girder
Brackett
120
6 screws to
each wing
4 screws to each
wing and
each flange
1 locating nail
Optional locator tabs.
to each wing to
For anti-rotation tab
hold bracket
fix with 2 nails
while driving screws
Girder Truss Bottom Chord
MiTek screws
8 screws to
each flange
90
min.
Supported Truss
Fix FastFit MkIV Girder Bracket with 16 screws to the girder truss bottom
chord and 16 screws in round holes to the supported truss.
MiTek screws
Girder Truss Bottom Chord
Use 3 MiTek screws to each wing in addition to M12 bolts. Washers are also
required on both sides of flanges. If length of heel plate is less than 175mm
then the supported truss should be either manufactured with GQ4075 Anti
Split plates, or alternatively have 3T10 Tylok Plates installed on site.
(See diagram).
90
min.
Supported Truss
Supported Truss
GQ4075 or 3T10
Tylok AntiSplit plates
(both sides)
10mm from end of
MkIII Girder Bracket
(If heel plate less than
175mm long).
55mm x 3.0mm
thick washers both sides
FastFit
MkIII
Girder
Bracket
140
min.
3 screws and
1 M12 bolt to
each wing for
cyclonic wind
conditions
1 locating nail
to each wing to
hold bracket
3 MiTek Screws
120
min.
4 bolts to
flange
Supported
Truss
M12 Bolts
2. Position and align the screw holes of the Hip Girder Bracket HGB35 with
the screws holes in the FastFit Girder Bracket.
M12 Bolts
22
1 locating nail
into each wing
The HiLoad Girder Bracket is suitable for girder truss bottom chords of
130mm and deeper. Whereas, the MidLoad Girder Bracket incorporates M12
bolts, therefore reducing cost and allowing the use of 90mm bottom chords.
Girder Truss
Bottom Chord
GBM
FastFit
Girder Bracket
HGB35
80
250
Girder Truss
Bottom Chord
GBH
100
320
When ordering specify left hand (LH) or right hand (RH) and the angle
required. Boomerang Girder Brackets are available with 22.5 or 45 cleats
only. For other angles use a wedge as specified in installation instructions.
5. Drive 2 MiTek screws through common holes in HGB35 and FastFit Girder
Bracket flange and fix the remaining screws into the supported truss.
6. Position hip truss/rafter on HGB35 and optionally secure with 2 nails under.
7. Drive MSA1465 screws through both inclined sides of HGB35 into hip
truss/rafter.
Hip Truss/Rafter
23
GBBL22
GBBL45
LEFT HAND
HiLoad
GBBR22
GBBR45
RIGHT HAND
Supported Truss
22.5 or 45
22.5 or 45
M16 Bolts
6. Ensure washers are fitted and all bolts are tightened before loading roof.
NOTES:
130
min.
1. Holes to be drilled to suit M16 bolts for Girder Bracket HiLoad and M12 bolts
for Girder Bracket MidLoad. Do not drill oversized holes and use hexagonal
head bolts. DO NOT USE REDUCED SHANK OR CUP HEAD BOLTS.
2. Girder Truss bottom chords to be a minimum of 130mm (nominal) for
Girder Bracket HiLoad and 90mm for Girder Bracket MidLoad.
2. For trusses with intersecting angles that do not correspond to cleat angle,
cut suitable dry timber wedges to match angle.
Midload
3. Install standard truss and clamp wedges on both sides as shown at right.
4. Drill through pre-punched holes and fit 2/M16 bolts.
Supported Truss
NOTES:
M12 Bolts
1. Holes to be drilled to suit M16 all thread bolts for Girder Bracket Boomerang.
Do not drill oversized holes and use hexagonal head nuts. DO NOT USE
REDUCED SHANK OR CUP HEAD BOLTS.
2. Where ceiling is to be fixed directly to bottom chord, notching of the heel
of supported trusses is recommended to obtain a better ceiling line.
3. Supported Truss bottom chords to be a minimum of 90 mm (nominal) for
Girder Bracket Boomerang.
Boomerang
M16 All Thread Bolts
Supported Truss
Nail to secure bracket
while drilling
M12 Bolts
M12 Bolts
Washer
Nail to secure bracket
while drilling
Universal Girder Bracket
Boomerang
Girder Truss Bottom Chord
24
130
min.
OVERHANG STRUTTING
Supported Truss
Stiffener, if required
Eve Trimmer
Propping effect
on stud wall
requires checking
CycloneTie 1200 can be used for Hip hold down in conjunction with
Mid/HiLoad girder brackets.
Ledger plate
1. Secure the incoming girder and locate the hip truss into position.
Bend a CycloneTie 1200 over the top chord of the hip truss and move
about 200mm along top chord and fix with one nail.
Equal
Supported
Truss
Propping effect
on stud wall
requires checking
Ledger plate
45
CycloneTie
(CT1200)
Hip Truss
Fix 1 nail
Strut
(Eaves Trimmer)
as required
by AS 4440
Girder Truss
bottom chord
2. Bend one leg under the bottom chord of the incoming girder and the
other under the supporting girder. Tap slightly to make a tight bend then
wrap them under the chords and fix with 4 nails as shown in diagram
below.
Fix 4 nails
100 x 25 F8 min.
Fascia to support
creeper rafter on
hip overhang
Supported
Truss
NOTES:
The hip corner detail is not suitable for the following situations:
Hip Truss
1. Where the hip corners have a cantilevered section of roof on either side of
the overhang. Special engineering is required in the case of cantilevered roof.
2. The standard roof overhang exceeds 900mm.
3. The truss spacing exceeds 900mm.
25
GUARDRAIL SYSTEMS
Detail A. (N.T.S.)
a) Standard truss
Guardrail post
200
Stiffener
b) Truncated truss
5. A guardrail post is not to be fixed to a jack rafter whose total length is less
than twice its overhang.
6. Guardrail posts are not fixed to the gable end or raking trusses. All guardrail
systems used on gable ends are to restrain guardrail system loads
independently of raking truss.
Guardrail post
200
Stiffener
2. Truss modifications in this sheet have been checked for top chord/jack
rafter fixed guardrail systems only.
c) Jack rafter
3. No truss members are to be cut or drilled, to enable the fixing of guardrail posts.
Truss Modifications
Stiffener on
jack rafter
Guardrail post
Hip truss
Ceiling joist
Stiffener is to be the same grade as the overhang and fixed with minimum
65mm long by 2.8mm diameter nails, staggered to one side only as shown
in Figure 3. In addition, fix two nails at the truss heel (or support point) and
at ends of the stiffener. Where screws are used in lieu of nails, use minimum
No. 10 gauge screws at the same spacing and pattern, provided that they
penetrate a minimum of 75% into the thickness of the final receiving member.
2D max.
F8
F11
F14
F17
75 x 38
800
75 x 50
800
850
950
100 x 38
650
900
1000
1100
100 x 50
900
1050
1150
1250
Additional nails at
end of member
and support point
75 x 38
75 x 50
650
700
700
800
100 x 38
600
750
850
950
100 x 50
750
850
1000
1100
650
700
75 x 50
550
700
100 x 38
450
800
850
900
100 x 50
850
900
900
950
NOTES:
1. N denotes Not Suitable
2. NA denotes size is Not Available
26
F5
F8
F11
MGP10
MGP12
MGP15
Hychord
F17
750
700
70 x 45
90 x 35
90 x 45
400
650
800
750
NA
800
700
900
950
900
750
900
800
1000
NA
1050
Jack rafters/trusses with sheet roof @ 1200 mm maximum spacing. Wind Classification N4 & C2
70 x 35
350
650
600
70 x 45
550
650
NA
700
90 x 35
700
600
750
800
800
90 x 45
650
750
700
850
NA
900
Jack rafters/trusses with terracotta tile roof @ 600 mm maximum spacing. Wind Classification N4 & C2
70 x 35
250
700
550
70 x 45
400
800
NA
800
90 x 35
850
650
1000
900
950
90 x 45
850
950
1000
1050
NA
1000
NOTES:
1. N denotes Not Suitable
2. NA denotes size is Not Available
3. Maximum roof pitch = 35
Truss Installation
Trusses and jack rafters that support guardrail loads are to be installed
in accordance with AS 4440 and with additional fixing as specified in
Figure 4.
Hip TC
TS
TG
JR
JR
JR
HI
JR
Guardrails are to be
continuous around corner
JR
Jack
TC
Detail B
JR
TG HTC
JR
JR
Stiffener
Detail C
J1
J1A
Hip truss
Jack rafters/trusses
fixed to hip trussas
per AS 4440
MiTek
Creeper
Connectors
(CC200L/R)
Stiffeners fixed to hip truss using MiTek
CreeperConnector with 4 No. 30 x 2.8 diameter
reinforced head nails to each leg
27
Product
Brief Description
Reference
3.15DIA -2
AS 1684 &
AS 4440
standards
BC200
Single Fold
(Double Fold)
Boomerang Connector,
to fold method shown
Fix Boomerang Connector with 3.15 dia. MiTek nails using Single Fold or Double Fold
method around mitre cut. (Refer data sheet for folding instructions)
Boomerang
Connector
data sheet
Fix BlockFast to concrete masonry with FAP32V5 GKN coated nails in method shown:
Heel Fix at truss heel
BF
BlockFast
BlockFast
data sheet
Fix BearingPlate with 3.15 dia. MiTek nails to top plate directly under girder.
BearingPlate
data sheet
BP80
BearingPlate
CC200
CreeperConnector, in
straight, (L)eft or (R)ight
hand version as shown
Join members together with 3/75mm framing nails before fixing CreeperConnector
with 3.15 dia. MiTek nails. (Refer data sheet for folding instructions)
CreeperConnector
data sheet
CC200R
& CT600 Under
CreeperConnector
+ CycloneTie combination
CreeperConnector
& CycloneTie
data sheet
CG90
CycloneGrip
CycloneGrip
data sheet
CPC80 4x1430
Sup/4x1430 Tr
Fix CPC80 with 4 MiTek screws into support (Sup) and 4 MiTek screws into truss (Tr).
Install a pair if Dbl is indicated.
Concealed
Purlin Cleat
data sheet
CT400
(CT600, CT900)
8 Face
CycloneTie, in 400mm,
600mm or 900mm length
with number of
nails shown
Fix CycloneTie to support Face with 8/3.15 dia. MiTek nails, i.e. 4 nails in each leg.
Wrap and fix legs under support if Fixed Under is indicated.
Install a pair of CycloneTies if Dbl is indicated.
CycloneTie
data sheet
CT1200 Type A
CycloneTie, in 1200mm
length to method shown
CT600SS 8 Face
CycloneTie, in stainless
steel with number of
nails shown
Fix stainless steel CycloneTie to support face with 8 stainless steel MiTek nails,
i.e. 4 nails in each leg. Install a pair if Dbl is indicated.
Stainless Steel
CycloneTie
data sheet
CT160LSS Dbl
CeilingTie, in stainless
steel (L)eft or (R)ight
hand version shown
Fix stainless steel CeilingTie with 3 stainless steel MiTek nails in each leg.
Install a pair if Dbl is indicated.
Stainless Steel
CeilingTie
data sheet
28
CycloneTie 1200
data sheet
GB275 Bolt
Fix MkII Girder Bracket with M12 bolts. Girder is Dbl or Trpl ply where indicated.
Girder Brackets
data sheet
GB340 Bolt
(or Screw)
Fix MkIII Girder Bracket with M12 bolts (or MiTek screws).
Girder is Dbl or Trpl ply where indicated.
Girder Brackets
data sheet
GB340
Bolt & Screw
Fix MkIII Girder Bracket with M12 bolts in wings and MiTek screws in shoe.
Girder is Dbl or Trpl ply where indicated.
Girder Brackets
data sheet
GB340
Screw & Bolt
Fix MkIII Girder Bracket with MiTek screws in wings and M12 bolts in shoe.
Girder is Dbl or Trpl ply where indicated.
Girder Brackets
data sheet
GB340 Cyc
Fix MkIII Cyclonic Girder Bracket with MiTek screws and M12 bolts.
Girder is Dbl or Trpl ply where indicated.
Girder Brackets
data sheet
GB340 + HGB35
Fix MkIII Cyclonic Girder Bracket together Hip Girder Bracket with MiTek screws.
Girder is Dbl or Trpl ply where indicated.
Girder Brackets
data sheet
GB440 (GB475)
Bolt (or Screw)
Fix MkIV Girder Bracket with M12 bolts (or MiTek screws).
Girder is Dbl or Trpl ply where indicated.
Girder Brackets
data sheet
GB440 120BC
FastFit MkIV
Girder Bracket
Fix MkIV Girder Bracket with MiTek screws for 120mm girder truss bottom chord.
Girder is Dbl or Trpl ply where indicated.
Girder Brackets
data sheet
GB440 + HGB35
Fix MkIV Cyclonic Girder Bracket together Hip Girder Bracket with MiTek screws.
Girder is Dbl or Trpl ply where indicated.
Girder Brackets
data sheet
Fix HiLoad Girder Bracket with M16 bolts into double (Dbl) girder to (Sup)port
triple (Trpl) truss. Install additional CT1200 if Strap is indicated.
Universal
Girder Brackets
data sheet
GBH Bolt
CT1200
Fix HiLoad Girder Bracket with M16 bolts and strap diagonal hip truss down
with CT1200 CycloneTie.
Universal
Girder Brackets
data sheet
Fix HiLoad Girder Bracket with M16 bolts and heavy duty over-strap to supported truss
when Strap is shown. Refer to MiTek User Guide MIUG-0041 for details of over-strap.
Universal
Girder Brackets
data sheet
& MIUG-0041
user guide
GBM Bolt
Fix MidLoad Girder Bracket with M12 bolts. Girder is Dbl or Trpl ply where indicated.
Strap down diagonal hip truss with CycloneTie if CT1200 is shown.
Universal
Girder Brackets
data sheet
GBBL22
Bolt Strap
Boomerang Girder
Fix Boomerang Girder Bracket with M16 bolts and heavy duty over-strap to supported
Bracket, in (L)eft or (R)
truss when Strap is shown. Refer to MiTek User Guide MIUG-0041 for details
ight hand version of angle
of over-strap.
shown and over-strap
29
Universal
Girder Brackets
data sheet
& MIUG-0041
user guide
HurricaneTie H2.5A
IBHF20050
4 Screws
FaceFix I-BeamHanger,
in size shown
and fixing indicated
Fix 50x200 FaceFix I-BeamHanger into supporting beam with 4 MiTek screws in each
flange and into supported joist with 3.75 dia. nails through dimples.
I-BeamHangers
data sheet
IBHT24090
6 Nails Top
TopFix I-BeamHanger
Fix 90x240 TopFix I-BeamHanger into top of supporting beam with 6 nails
and into supported joist with 3.75 dia. nails through dimples.
I-BeamHangers
data sheet
JH3590
JoistHanger, in size
shown
JH4090 Nog
Fix HurricaneTie H2.5A with 3.75 dia. MiTek nails. Install a pair if Dbl is indicated.
HurricaneTie H2.5A
data sheet
H2.5A Dbl A
JH40120
+4x3.15 nails
JoistHanger, to size
shown + framing nails
JH4790SS Nog
JoistHanger, in stainless
steel to size shown
JHAL
(or JHAR) Typ 1
45 Degree JoistHanger,
to (L)eft or (R)ight
hand version shown
JST 3 Nails
JoistStrap
MIUG25 1A
MIUG26 3B
Fix components together with 4/3.15 dia. framing nails in addition to JoistHanger.
Fix 47x90 stainless steel JoistHanger with stainless steel MiTek nails.
Fix nogging/back-blocking behind truss if Nog is indicated.
Fix 45 Degree JoistHanger with MiTek nails according to one of the following methods:
Typ 1: Both legs wrapped over truss
Typ 2: Both legs up side of web
Typ 3: One leg over truss, one leg up side of web
(Refer product specifications for nailing pattern)
JoistHanger
data sheet
JoistHanger
data sheet
JoistHanger
data sheet
Stainless Steel
JoistHanger
data sheet
45 Degree
JoistHanger
data sheet
JoistStrap
data sheet
Refer to MiTek User Guide MIUG-0025 for details of truss hold down in blockwork
using method type 1A.
MIUG-0025
user guide
Refer to MiTek User Guide MIUG-0026 for details of truss hold down to timber framing
using method type 3B.
MIUG-0026
user guide
Special hold down bracket, Refer to supplier for details of 25kN capacity truss hold down bracket fixed
to uplift capacity shown to side of truss.
M2UG-0030
user guide
MIUG30U 40kN
Special hold down bracket, Refer to supplier for details of 40kN capacity truss hold down bracket fixed with
to uplift capacity shown strap over joint.
M2UG-0030
user guide
MIUG30V 50kN
Special hold down bracket, Refer to supplier for details of 50kN capacity truss hold down bracket fixed to vertical
to uplift capacity shown web of truss.
M2UG-0030
user guide
MIUG30 25kN
30
MIUG43 1A
Refer to supplier for details of truss hold down with cleat over truss held down by
anchor rods on both sides using method type 1A.
MIUG-0043
user guide
SPH140
6 Scrw/6 Scrw
SplitHangers,
to size and fixing shown
Fix a pair of 140mm deep SplitHangers with 6 MiTek Screws in each flange.
SplitHanger
data sheet
TBS (TBS+)
Special hanger
(or special hold down)
Trip-L-Grip,
(L)eft or (R)ight
hand version
TGM E
MultiGrip
TGU A
Universal Trip-L-Grip
Universal Trip-L-Grip
data sheet
TGUSS A
Universal Trip-L-Grip,
in stainless steel
to orientation shown
Stainless Steel
Universal Trip-L-Grip
data sheet
TRG
TrussGrip
Fix TrussGrip to side of truss and support. Install a pair if Dbl is indicated.
TrussGrip
data sheet
UL7550 Floor
UniLedger
Fix UniLedger to supporting beam with MiTek screws, and with 10g screw to supported
member. Also fix top of members together with framing nails.
UniLedger
data sheet
UL7550
+ 2xCT1200
UniLedger + CycloneTie,
to number shown
Fix UniLedger to girder truss with MiTek screws, and strap down each supported truss
to girder truss with CT1200 CycloneTie.
UniLedger
data sheet
Supplier to provide
Fix Trip-L-Grip in orientation A (Refer product sheet). Install a pair if Dbl is indicated.
Trip-L-Grip
data sheet
Fix MultiGrip in orientation E (Refer product sheet). Install a pair if Dbl is indicated.
MultiGrip
data sheet
31
Permanent Bracing
Supporting Structure
Check that all top plates that support trusses are level and straight.
(Any misalignment of supporting structure will be reflected in the
straightness of the roof.)
Check that the distance between supporting walls match the spans of the
trusses.
Are the tops of internal non-load bearing walls set down below that of
external load bearing walls?
Are lintels in load bearing walls suitable for truss loading?
Is supporting structure fully braced, plumb and stable?
Roof Trusses
Have trusses been stored and lifted in accordance with these instructions?
Are roof battens fixed to each truss including to each ply of double & triple
girders using the correct size nails?
Does the truss design criteria on the documentation conform to the job
specification for roof cladding and special loads, eg roof mounted hot
water tanks, air conditioners, etc?
out of vertical?
(b) Bow - All chord bows less than 50mm or chord length/200?
Are all multiple ply trusses nailed/screwed/bolted together?
(b) jack truss to hip truss - large station i.e. Creeper Connector?
(c) hip truss & jack trusses to truncated girder and to truncated
standard truss as per AS 4440?
(d) structural fascia and/or strutted overhangs?
Temporary Bracing
Are standard truss to girder truss fixing type according to approved plans
and are all nails/bolts installed and tight?
Has all strengthening been completed for guard rail systems(if applicable)?
PRODUCT CERTIFICATION
For more information about MiTeks Engineered Building Products or any other MiTek products or your nearest
licensed MiTek fabricator, please call your local state office or visit: mitek.com.au
FBG-TRT 02/15
All MiTek products specified in this guideline are engineered building products that have been designed,
developed and tested in the corporate engineering laboratory of MiTek Australia to comply with the requirements
of the Building Code of Australia. The design values, applications and specifications of these products are certified
by qualified chartered engineers and they are published in individual product brochures freely available on the
MiTek website. Further information, support and guidance on any of these products may be obtained by contacting
one of our offices listed below.