Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Auxiliary Power Consumption

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 3

Auxiliary Power Consumption Reduction in

Thermal Power Stations


Most of the thermal power plant uses 30-40% of energy value of primary
fuels and remaining 60-70% is lost during generation, transmission and
distribution of which major loss is in the
form of heat. Power plant produces electrical energy and also consumes a
substantial amount of energy in the form of auxiliary consumption
required for various plant equipments and services. National level average
auxiliary power consumption is around 8%-12%, reduction of even 0.5 1.0 % can result in huge savings and additional output of a few
Megawatts.

APC REDUCTION OPPORTUNITIES


1. Air & flue gas cycle:a. Optimizing excess air ratio: - It reduces FD fan & ID fan loading.
b. Replacement of oversize FD and PA fan: - Many thermal power
plants have oversize fan causing huge difference between design &
operating point which leads to lower efficiency. Hence fan efficiency can
be improved by replacing correct size of fan. If replacement is not
possible, Use of HT VFD for PA & ID fan can be the solution.
c. Attending the air & flue gas leakages: - Leakages in air & flue gas
path increases fan loading. Use of Thermo vision monitoring can be
adopted to identify leakages in flue gas path. Air preheater performance is
one crucial factor in leakage contribution. If APH leakage exceeds design
value then it requires corrective action.
2. Steam, Feed water and condensate cycle:a. BFP scoop operation in three element mode instead of DP
mode: - In three element mode throttling losses across FRS valve
reduces, leads to reduction in BFP power.
b. Optimization of level set point in LP & HP heater: - Heater drip
level affects TTD & DCA of heater which finally affect feed water O/L temp.
Hence it requires setting of drip level set point correctly.
c. Charging of APRDS from CRH line instead of MS line: -APRDS
charging from cold reheat (CRH) is always more beneficial than from MS
line charging.
d. Isolation of steam line which is not in use: - It is not advisable to
keep steam line unnecessary charge if steam is not utilized since there
energy loss occurred due to radiation. For example deaerator extraction

can be charged from turbine Extraction/CRH or from APRDS. In normal


running APRDS Extraction is not used so same can be kept isolated.
e. Replacement of BFP cartridge: - BFP draws more current if cartridge
is wore out, causing short circuit of feed water flow inside the pump. It
affects pump performance. Hence cartridge replacement is necessary.
f. Attending passing recirculation valve of BFP: - BFP Power
consumption increases due to passing of R/C valve. It requires corrective
action.
g. Installation of HT VFD for CEP: - CEP capacity is
underutilized and also there is pressure loss occurs across Deaerator
level control valve. There is large scope of energy saving which can be
accomplished by use of HT VFD for CEP or impeller trimming.
3. Fuel & ash Cycle:a. Optimized ball loading in Ball tube mill: - Excessive ball loading
increases mill power. Hence ball loading is to be Optimized depending
upon coal fineness report.
b. Use of Wash Coal or Blending with A- grade coal: - F-grade coal
has high ash content. Overall performance can be improved by using
wash coal or blending of F-grade coal with A- grade coal instead of only
using F- grade coal.
c. Avoiding idle running of conveyors & crusher in CHP
d. Use of Dry ash Evacuation instead of WET deashing System: Dry deashing system consumes less power & also minimizes waste
reduction.
e. Optimize mill maintenance:-Mill corrective/preventive maintenance
is to be optimized depending parameter like- running hrs, mill fineness,
bottom ash unburnt particle, degree of reject pipe chocking etc.
4. Electrical & lighting system:a. Optimizing Voltage level of distribution transformer: - It is found
that Operating voltage level is on higher side than required causing more
losses. It is required to reduce the voltage level by tap changing.
b. Use of Auto star/delta/star converter for under loaded motor
Lighting: - Use of electronic chock instead of conventional use copper
Chock, Use of CFL, Replacement of mercury vapor lamp by metal Halide
lamp. Use of timer for area lighting is the methods can be used. Lighting
has tremendous potential of saving.
5. ECW & ACW system:-

a. Isolating ECW supply of standby auxiliaries: - Many times standby


coolers are kept charged from ECW side. Also Standby equipments
auxiliaries like Lube oil system kept running for reliability. We can isolate
Standby cooler from ECW system & switching of standby auxiliaries, doing
trade off between return & reliability.
b. Improving condenser performance by condenser tube cleaning
& use of highly efficient debris filter: - Tube cleaning by bullet shot
method increases condenser performance, condenser tube cleaning is
necessary which is to be carried out in overhaul. Also highly advanced
debris filter contribute condenser performance.
c. Application of special coating on CW pump impeller: - It improves
pump impeller profile condition, increasing pump performance.
6. Compressed air system:a. Optimizing discharge air pressure by tuning
loading/unloading cycle: - It helpful to reduce sp. Power
consumption.
b. Use of heat of compression air dryer instead of electrically
heated air dryer: - Heat of compression air dryer use heat generated in
compression cycle, thus reduces sp. Power consumption.
c. Use of screw compressor instead reciprocating compressor: Sp. Power consumption of screw compressor is less than reciprocating air
compressor leads to reduce aux. power consumption.
7. Other areas:a. Cooling tower performance improvement
b. Installing absorption refrigeration system instead of vapor compression
system
c. Use of wind turbo ventilators instead of conventional motor driven
exhauster
d. Monitoring the power consumption of each equipment before and after
overhaul

You might also like