HySelect User Guide
HySelect User Guide
User Manual
EN
December 2014
HySelect
Table of Contents
Table of Contents
What's New
1. Introduction
3. Software Interface
10
12
13
13
14
15
16
18
18
4. Individual Selection
21
21
22
22
22
24
24
26
27
4.2.6.1. Overview
27
4.2.6.2. Separators
28
30
34
4.2.6.5. Dp controllers
36
39
40
41
43
Table of Contents
45
46
HySelect
48
4.5. Selection
53
54
54
55
57
4.7. TAFusion
5. Hydronic Project Calculation
58
60
60
61
64
66
66
68
69
72
74
74
75
77
78
80
81
5.6.1. Overview
81
81
83
86
86
6. Results Management
87
6.1. Overview
87
88
90
90
91
92
93
95
Table of Contents
HySelect
97
101
7.1. Overview
101
102
106
107
110
111
8. System Configuration
112
8.1. Introduction
112
112
115
115
8.3.2. General
116
126
9. Additional Tools
134
134
136
137
140
144
9.6. TA Link
145
145
Table of Contents
HySelect
What's New
December 2014
New Features
Pressure maintenance devices added to the catalogue and selection.
See Pressure maintenance.
New presentation of the technical parameters in the individual selection contextual tab:
See Selection Steps.
Various
New software name and branding:
Ta Select 4 becomes HySelect,
Ta Hydronics becomes IMI Hydronic Engineering.
What's New
HySelect
1. Introduction
IMI Hydronic Engineering
IMI Hydronic Engineering is the leading global provider and expert in hydronic distribution systems and room
temperature control, with experience in more than 100,000 projects worldwide.
HySelect
HySelect is a computer program that helps you to control your hydronic system from design stage throughout the
buildings lifetime.
It makes it easy to determine the right valve size, pre-setting values and several other characteristics of your
plant circuits. And, together with our balancing instrument TA-SCOPE, it helps you to obtain the most
economical hydronic design.
1. Introduction
HySelect
HySelect
3. Software Interface
3.1. Interface Overview
HySelect is a software developed by IMI Hydronic Engineering. Its main interface is illustrated hereunder.
3. Software Interface
HySelect
The Ribbon
This part of the interface is composed of several tabs whose number depends on what task you are performing.
There are four standard tabs: Home, Project, Tools and Communication.
This part of the interface is described in details in The RibbonTabs section.
3. Software Interface
HySelect
3. Software Interface
10
HySelect
3. Software Interface
) when in auto
11
HySelect
3. Software Interface
12
HySelect
3. Software Interface
13
HySelect
allows to select all the pipe series with one click while the
The Set as default pipe series button allows you to set the selected pipe series as default. The result is the
same as selecting the default pipe directly in the Pipe series group.
3. Software Interface
14
HySelect
The Create series button allows you to create a new series if the required pipe of the system is not available in
HySelect. Left-click once on the new pipe series name in order to rename it.
When you select a pipe amongst the pipes list of an user input pipe series, the Create series button becomes
Create pipe and allows you to create a new pipe in the pipe series. Left-click once on the new pipe name in
order to rename it.
When creating a new pipe, you can input relevant specifications to pipe pressure drop:
Corresponding valve size: designer can input nominal valve size related to pipe specifications. HySelect
allows Device size, in the Technical Parameters group, to be made greater than or less than piping
diameter depending on allowance of design engineer.
Internal diameter: the measured inside diameter of the pipe. It will give a basis for pipe pressure drop
calculations.
Roughness: the roughness of the pipe affects the pipe pressure drop, so it also must be defined.
Max. Pressure: in order for HySelect to make a proper pipe selection and, thus, pipe pressure drop
estimation, there needs to be a maximum operating pressure for the pipe in order to avoid underrated
piping used in calculations.
Max. Temperature: similar to the pressure specification of the piping, the maximum temperature needs to be
defined in order to avoid using underrated piping in the pipe pressure drop calculations.
The Delete Series button allows you to delete the highlighted unlocked pipe series. As with the Create Series
button, the Delete Series button becomes Delete Pipe if you have selected and highlighted a pipe in an user
input pipe series. The Delete Pipe button allows you to delete the highlighted pipe from the highlighted user
input pipe series.
Technical parameters
This group is part of the Home tab and allows you to enter the information concerning pressures, pressure drops,
and fluid velocity in your system.
Device size
Size above: select the number of sizes above the selected pipe size to be considered for valve selection
(value=0 to 4/ default=0).
Size below: select the number of sizes below the selected pipe size to be considered for valve selection
(value=0 to 4/ default=2).
If the Pipe size is set to 25 (1"), and using the default values for the Size above and Size below,
HySelect will list relevant products designed for 25(1") pipes but also for 20(3/4") and 15(1/2").
Pipe pressure drop
Target: set the target linear pressure drop in the selected pipe (default = 150 Pa/m).
Max: set the maximum linear pressure drop accepted in the selected pipe (default = 200 Pa/m).
Pipe water velocity
Target: set the target fluid velocity in the selected pipe (default = 1 m/s).
Max: set the maximum fluid velocity accepted in the selected pipe (default = 2 m/s).
3. Software Interface
15
HySelect
3. Software Interface
16
HySelect
3. Software Interface
17
HySelect
3. Software Interface
18
HySelect
Update HySelect
The Update HySelect button opens the following window.
3. Software Interface
19
HySelect
Follow the window instructions if any. The download and update process is displayed in this window.
Once the update is complete, the following window is displayed. After you click on the Close button, HySelect will
restart (the application only, not your Windows operating system) then it will be again ready for use.
Properties
The Properties button open the following window.
In this window, select the update scheme you want to apply either automatic each time you start the application,
on a regular basic, or no automatic check of availability of updates.
3. Software Interface
20
HySelect
4. Individual Selection
4.1. How to Select a Valve
One of the main functions of HySelect is to help you to select TAHydronics products and valves.
Selection methods
Two ways are proposed to help you in selecting the best suited products according to your needs:
A selection based on technical parameters: this search will display a list of products corresponding to your
search parameters and highlight the recommended ones.
A direct or a batch selection in TAHydronics database: this way you have direct access to TAHydronics
catalogue and datasheets.
In batch selection mode, use data copied from an Excel sheet to search the database for multiple
devices in one step.
Selection environment
To perform a product selection:
1. Go to the Select Control Panel Bottom Menu view as illustrated hereunder:
4. Individual Selection
21
HySelect
4. Individual Selection
22
HySelect
There are 8 types of products. If all those types do not appear in your ribbon, click on the highlighted drop-down
arrow in the above illustration to display the complete list as illustrated hereunder.
4. Individual Selection
23
HySelect
Fluid Characteristics
In the Fluid Characteristics group in the Product contextual tab of the ribbon, enter the information concerning the
fluid used in your system.
4. Individual Selection
24
HySelect
Pipe series: select the material of the pipes used, among several kinds of copper, steel, PEX, etc. according
to various standards. If you do not know the type of pipes to be used or do not mind, use the default ** Generic
Steel Pipes **.
Technical parameters
In the Technical parameters group in the Tech. parameters contextual tab of the ribbon, enter the information
concerning pressures, pressure drops, and fluid velocity in your system.
4. Individual Selection
25
HySelect
4. Individual Selection
26
HySelect
Technical parameters
In the Technical parameters group in the Tech. parameters contextual tab of the ribbon, enter the maximum number
of vessels and of Vento (degassing device) you accept to install in parallel.
4. Individual Selection
27
HySelect
Some parameters are common to all or most products types while some are specific. There are described in the
following sections, for each product types.
Pressurisation & Water quality
"Separators" (page 28)
Pressure maintenance
Balancing & Control
Manual balancing valves
Dp controllers
Balancing and control valves
Pressure independent balancing and control valves
Control valves
Thermostatic control
Radiator valves
Once you have set these parameters, click on the Suggest button to generate a list with the products that best suit
your requests and preferences. These results are described in the Selection Results section.
4.2.6.2. Separators
: The control panel for separators is illustrated hereunder:
4. Individual Selection
28
HySelect
Enter or select a value for the following parameters before performing a search in the products database:
Mandatory parameters:
Select and check a parameter set between Flow and Power + DT as these are exclusive. Then enter a value
for the corresponding parameters:
Flow: enter the supported liquid flow through the separator.
Power: enter the power that goes through the separator.
DT: enter the supported temperature difference supported by the separator.
Optional parameters:
Enter a value for some or all of these parameters if you want to further filter the proposed list of products.
Type: select the type of separator you are looking for such as Micro bubble separator, Dirt separator...
Family: select the family of separators such as ZUV, ZIO... within the separator type selected before.
Connection: select the connection and fitting type, such as Thread, Flange, Welding...
Version: select the separator version, such as Standard, Lateral, Magnetic...
You can leave these parameters with their default value, launch a first suggestion, and, according to the
results, narrow your search by using more parameters.
Search results
Then, press the ENTER key or click on the Suggest button to get a list of proposed products as detailed in the
Selection Results section.
4. Individual Selection
29
HySelect
Static Height [Hst] (mandatory for the SWKI norm): static height of your installation.
Optional parameters:
Enter a value for some or all of these parameters if you want to further filter the proposed list of products.
Installed power [Qs]: total power of your installation.
4. Individual Selection
30
HySelect
Safety valve response pressure: opening pressure of the overpressure safety device.
Safety temp. limiter [TAZ] (heating and solar applications only): maximum temperature that will be allowed to
enter the vessel.
Max temperature [tsmax] (cooling applications only): maximum temperature of the fluid in your installation.
Supply temperature: temperature of the fluid in the supply circuit.
Return temperature: temperature of the fluid in the return circuit. The vessel is always installed on the return
circuit to limit the temperature applied to the bladder or the membrane.
Min. temperature [tsmin]: minimum temperature of the fluid when the system is not in use.
Fill temperature (cooling applications only): temperature of the fluid used to fill your installation.
Max. width: maximum width allowed for the device. This measurement is important to make sure that you will
be able to move and install the device in your building.
Max. height: height of the room where you will install the device. The selected device will be smaller to allow
its manipulation during installation (including straightening up).
You can leave these parameters with their default value, launch a first suggestion, and, according to the
results, narrow your search by using more parameters.
4. Individual Selection
31
HySelect
4. Individual Selection
32
HySelect
Search results
Then, press the ENTER key or click on the Suggest button to get a list of proposed products.
One product is always proposed in all 3 families of products (Statico, Compresso, and Transfero) as
illustrated below.
4. Individual Selection
33
HySelect
The Pressurisation maintenance graphs tab, available at the bottom of the table:
Displays the available graphs for the selected device.
4. Individual Selection
34
HySelect
Enter or select a value for the following parameters before performing a search in the products database:
Mandatory parameters:
Select and check a parameter set between Flow and Power + DT as these are exclusive. Then enter a value
for the corresponding parameters:
Flow: enter the supported liquid flow through the valve.
Power: enter the power that goes through the valve.
DT: enter the supported temperature difference supported by the valve.
Type of regulating valve: select the type of valve you are looking for such as Balancing Valve, Double Regulating
Valve, Fixed Orifice...
Optional parameters:
Enter a value for some or all of these parameters if you want to further filter the proposed list of products.
Dp: check and enter a value to define a pressure difference over the valve.
Family: select the family of valves such as STAD, TBV, MD 01... within the valve type selected before.
Body Material: select the material of the valve, such as Ametal, Bronze, Cast iron, Stainless steel...
Connection: select the connection and fitting type, such as Thread, Flange, Solder...
Version: select the valve version, such as Without drain, With drain 1/2", High temp...
PN: select the pressure class.
You can leave these parameters with their default value, launch a first suggestion, and, according to the
results, narrow your search by using more parameters.
Search results
Then, press the ENTER key or click on the Suggest button to get a list of proposed products as detailed in the
Selection Results section.
4. Individual Selection
35
HySelect
4.2.6.5. Dp controllers
: The control panel for Dp controllers is illustrated hereunder:
4. Individual Selection
36
HySelect
Optional parameters:
Enter a value for some or all of these parameters if you want to further filter the proposed list of products.
Depending on previous mandatory parameters settings, some of the following ones may propose only
one value and thus cannot be changed.
Show DpC connection scheme: check this option to display a diagram of the controller connection in the circuit
as illustrated below.
Type: select the controller type, such as DpC-Std HVAC or DpC-High Dp.
Family: select the family of controllers such as STAP, DA50, DAF50... within the controller type selected
before.
Body Material: select the material of the controller, such as Ametal, Bronze, Cast iron, Stainless steel...
Connection: select the connection and fitting type, such as Thread, Flange, Solder...
Version: select the controller version, such as Standard, PT90...
PN: select the pressure class.
Select Dp control set: check this option to propose only complete kit, including the controller and its
accessories.
You can leave these parameters with their default value, launch a first suggestion, and, according to the
results, narrow your search by using more parameters.
Search results
Then, press the ENTER key or click on the Suggest button to get a list of proposed products as detailed in the
Selection Results section.
4. Individual Selection
37
HySelect
4. Individual Selection
38
HySelect
4. Individual Selection
39
HySelect
Connection: select the connection and fitting type, such as Thread, Flange, Solder...
Version: select the valve version, such as 3-way, 4-way...
PN: select the pressure class.
Power suply: select the type of power supply, such as 24VAC, 24VDC, 230VDC...
Input signal: select the type of input signal, such as 0-10V, On-off, 3-point...
Fail safe: select the type of fail safe, such as None, Extending, Retracting...
Select valve and actuator set: check this option to propose only complete kit, including the controller and its
accessories.
You can leave these parameters with their default value, launch a first suggestion, and, according to the
results, narrow your search by using more parameters.
Search results
Then, press the ENTER key or click on the Suggest button to get a list of proposed products as detailed in the
Selection Results section.
New TAFusion valves and kits are available from this search windows.
4. Individual Selection
40
HySelect
Enter or select a value for the following parameters before performing a search in the products database:
Mandatory parameters:
Select and check a parameter set between Flow and Power + DT as these are exclusive. Then enter a value
for the corresponding parameters:
Flow: enter the supported liquid flow through the valve.
Power: enter the power that goes through the valve.
DT: enter the supported temperature difference supported by the valve.
Type: select the type of valve you are looking for such as Classical, PICV-High Dp, PICV-Std HVAC...
Ctrl type: select the type of control you are looking for such as Proportional, 3-point, On-Off...
Optional parameters:
Enter a value for some or all of these parameters if you want to further filter the proposed list of products.
Family: select the family of valves such as TBV-CMP, TA-FUSION-P... within the valve type selected before.
Body Material: select the material of the valve, such as Ametal, Ductile iron...
Connection: select the connection and fitting type, such as Thread, Flange...
Version: select the valve version, such as Standard, PT 90...
PN: select the pressure class.
Power suply: select the type of power supply, such as 24VAC, 24VDC, 230VDC...
Input signal: select the type of input signal, such as 0-10V, On-off, 3-point...
Fail safe: select the type of fail safe, such as None, Extending, Retracting...
Select control set: check this option to propose only complete kit, including the controller and its accessories.
You can leave these parameters with their default value, launch a first suggestion, and, according to the
results, narrow your search by using more parameters.
Search results
Then, press the ENTER key or click on the Suggest button to get a list of proposed products as detailed in the
Selection Results section.
New TAFusion valves and kits are available from this search windows.
4. Individual Selection
41
HySelect
4. Individual Selection
42
HySelect
Body Material: select the material of the valve, such as Bronze, Brass, Cast iron...
Connection: select the connection and fitting type, such as Thread, Flange...
Version: select the valve version, such as Standard, 3-way, 4-way...
PN: select the pressure class.
Power suply: select the type of power supply, such as 24VAC, 24VDC, 230VDC...
Input signal: select the type of input signal, such as 0-10V, On-off, 3-point...
Fail safe: select the type of fail safe, such as None, Extending, Retracting...
Select valve and actuator set: check this option to propose only complete kit, including the controller and its
accessories.
You can leave these parameters with their default value, launch a first suggestion, and, according to the
results, narrow your search by using more parameters.
Search results
Then, press the ENTER key or click on the Suggest button to get a list of proposed products as detailed in the
Selection Results section.
4. Individual Selection
43
HySelect
Enter or select a value for the following parameters before performing a search in the products database:
Mandatory parameters:
q: enter the supported liquid flow through the valve.
Optional parameters:
Enter a value for some or all of these parameters if you want to further filter the proposed list of products.
Dp: check and enter a value to define a pressure difference over the valve.
Radiator with integrated valves: check if you are looking for radiator with integrated valves.
Supply valve: select the type of supply valve, such as V-exact II, Standard, LowRes...
Return valve: select the type of return valve, such as TRIM, STK, Regutec...
Connection: select the connection and fitting type of the supply valve (such as Rad. union/Thread, Rad.
elbow/Thread, Flat sealing...) and of the return valve (such as Thread, Thread male/Thread, Rad. union/Thread...).
Version: select the valve version of the supply valve (such as Straight, Angle, Reverse angle...) and of the
return valve (such as Straight, Angle...).
Thermostatic head and Electro actuator: check the corresponding box if you are looking for a radiator valve with
a thermostatic head or with an electro actuator.
Type: select the type of radiator valve, such as Built-in sensor, Remote sensor, Thermo-electric...
Family: select the family of radiator valves such as K-Head (built-in), DX Head, B Head... within the valve type
selected before.
Version: select the radiator valve version, such as Standard, Public buildings, Indoor swimming pools...
You can leave these parameters with their default value, launch a first suggestion, and, according to the
results, narrow your search by using more parameters.
Search results
Then, press the ENTER key or click on the Suggest button to get a list of proposed products as detailed in the
Selection Results section
4. Individual Selection
44
HySelect
4. Individual Selection
45
HySelect
Product selection
Click on a product in the list to highlight it.
If accessories are available for this product, an additional table is displayed at the bottom of the results list with
these accessories as illustrated hereunder. You can check some of these accessories to include them in your bill
of material. In this case, they will be linked with the selected product for easy reading.
4. Individual Selection
46
HySelect
4. Individual Selection
47
HySelect
Example of open Product categories and a selected Product with its compatible accessories
4. Check the accessories you want to select, if any.
5. The selected product and its accessories are listed in the Selection column.
6. Click the Select button to select these items and add them to your Results table as described in the Selection
section.
4. Individual Selection
48
HySelect
4. Individual Selection
49
HySelect
The Batch selection table with selected devices (and additional columns)
4. Individual Selection
50
HySelect
4. Individual Selection
51
HySelect
4. Individual Selection
52
HySelect
4.5. Selection
Once you have selected a product, either by a direct or a parameterised selection, the following window opens.
4. Individual Selection
53
HySelect
Click on the
4. Individual Selection
54
HySelect
The Search and Replace window - Constitute or split control valve and actuator sets
4. In the right pane, select the operation to perform (split sets or group products in sets).
5. In the left pane, select the products on which you want to apply the selected operation. Check or uncheck the
products individually or use the buttons available at the bottom of the window.
6. Click on the Start button.
7. Check the proposed operation as illustrated.
4. Individual Selection
55
HySelect
8. Click on the Apply button to accept the change and check the next one or click on the Apply all button to
accept changes for all products.
4. Individual Selection
56
HySelect
The Search and Replace window - Add or remove actuator on selected product
4. In the right pane, select the operation to perform (remove or add actuators on control valves).
5. In the right pane, also set the different options according to your needs.
6. In the left pane, select the products on which you want to apply the selected operation. Check or uncheck the
products individually or use the buttons available at the bottom of the window.
7. Click on the Start button.
8. Check the proposed operation as illustrated.
4. Individual Selection
57
HySelect
9. Click on the Apply button to accept the change and check the next one or click on the Apply all button to
accept changes for all products.
4.7. TAFusion
HySelect supports and proposes in its selection, the TAFusion components as well as complete sets including a
balancing valve, an actuator, and all relevant accessories.
4. Individual Selection
58
HySelect
These innovative pressure independent control and balancing valves for heating and cooling systems
combine the key hydronic functions of control and balancing in one valve.
Adjustable maximum flow and inherent independent EQM characteristics allow correct valve sizing and
optimum system controllability.
The measuring points enable accurate measurement of flow, differential pressure, temperature and available
differential pressure.
4. Individual Selection
59
HySelect
60
HySelect
Hydronic modules
A hydronic module is made of several circuits connected in parallel as illustrated hereunder.
61
HySelect
Plant decomposition
The following figure illustrates a plant example.
Example of a plant
62
HySelect
Pending circuits
Projects are often designed with possible future extensions in order to manage the staging of investments. This
means that the hydronic calculation should be sized based on these future extensions and that the valves should
be configured according to the current situation.
During circuit design, HySelect enables you to insert what is called a pending circuit, that is a single circuit that
will represent the future extension. This circuit will be taken into account for the components and pipes sizing but
will not be considered for the initial valves configuration.
After commissioning a future extension, HySelect will recalculate the settings of some of these valves to cope
with the new plant configuration. At that time, as the components have been selected based on the complete
plant, no replacement will be necessary and you will only need to perform some adjustments of already installed
valves.
Of course, you can add several pending circuits in different places in your plant according to your specific
configuration and future developments.
63
HySelect
Injection circuits
HySelect supports injection circuits. These circuits include a pump device and are used for circuits that require:
A temperature regime different from the plant temperature regime (for ex. for floor heating, cooling ceiling,
chilled beams...)
Circuits with a supply water temperature adjusted according to specific conditions such as the outdoor
temperature (for ex. radiator branches, floor heating...).
These injection circuits require specific parameters that are explained in the circuit design section.
Project Info
64
HySelect
icon to automatically retrieve the User references data entered in the ribbon Home
Project Parameters
65
HySelect
66
HySelect
67
HySelect
68
HySelect
69
HySelect
The editable purple fields are fields that should be manually completed as they are related to plant and
circuit setup that the software uses as inputs and cannot compute (such as the pipe length or the terminal
unit power...).
The editable white fields have default values defined globally but may be changed locally if desired.
Values displayed in red means the current value is not allowed (for example, in heating systems, the
supply temperature is lower than the return temperature).
The non-editable white fields display values automatically calculated by HySelect.
The icon enables you to lock the values in this table to ensure that the calculation will not change them.
Once locked, the icon is and the locked values are bold.
A icon next to a field indicates additional or alternate fields that can or must be completed.
The icon next to the Accessories fields opens an additional window in which you can add accessories on
the primary, secondary, or distribution pipe (such as a tee...).
Click on the icon next to a balancing valve to remove it from the circuit (such an optional valve is
displayed with a number sign (#) in the circuits proposed during the wizard first step).
3. In the wizard window bottom area:
Enter the number of identical circuits to be added at once (these circuits will be added in parallel and the
names will be incremented).
Click on the <<Previous button to go back to the wizard first step if you want to change the circuit type.
Once all mandatory fields are completed, click on the Add button to add the circuit(s) in the whole circuit.
4. Once a circuit is added with the Add button:
The circuit is added in the circuit and cannot be changed anymore from this wizard.
The circuit name is incremented.
You can specify again a similar circuit and add it to the circuit.
5. When all desired circuits are added, click on the Close button.
Pipe lengths
To determine the different pipe lengths required according to your circuit configuration, please refer to the
information and notes described in the Pipe Lengths section.
Balancing valves
An additional feature is available for balancing valves only, once the required circuit parameters have been
entered:
Move the mouse over the table title to open a pop-up displaying the overflow that would occur when the
control valve closes if the by-pass is not balanced as illustrated hereunder:
70
HySelect
Pending circuits
When you add a pending circuit (see Hydronic Circuit Description), you should provide the total flow that will
circulate in that circuit to be added at a later stage in the plant building and, if you already know them, the circuit
pipe length(s) and Dp of that circuit. The components will be selected to fit the final complete installation but will
be configured only for the currently installed part.
71
HySelect
Injection circuits
When you add an injection circuit (see Hydronic Circuit Description), you should also provide some of the circuit
pump characteristics as well as the supply and return temperatures.
The calculation of such circuits take into account the parameters defined in the Fluid Characteristics window:
The fluid characteristics adjusted in this window are specific for the current projet (and can differ from the
general fluid configuration).
There is an additional parameter, Default DT (default temperature variation). In case of adjustment, the new
value will be used for any injection circuit added from now on.
The Default DT sign depends on the project type setting (heating or cooling).
The pump Dp is optional and will be taken into account only if it is higher than the minimum required Dp.
72
HySelect
Pipe length measurement: (1) - red - Distribution pipe length, and (2) - blue - Circuit pipe length
73
HySelect
74
HySelect
The listed distribution pipes are sized taking into account the pending circuits.
The listed flows represent the current value, that is without taking into account the pending circuits.
Injection circuits
The injection circuits are visible in the Circuit Type column.
Reverse return circuits
The Distribution pipe and the corresponding Accessories sections of the table are duplicated, once for the
supply pipes and once for the return pipes.
75
HySelect
Circuits tab
The second tab, Circuits, displays the components selected by HySelect calculation algorithm to optimise your
circuit as illustrated hereunder.
This window displays a table with all valves and components selected by the calculation as well as the
respective operating conditions and settings.
76
HySelect
77
HySelect
78
HySelect
79
HySelect
80
HySelect
81
HySelect
To remove a dropped element (in red), click on it then press the DEL key, or drag and drop it outside the
destination area.
82
HySelect
The diversity factor can be regarded as the probability that a piece of equipment will come on during the
peak load in the plant.
During the hydronic calculations, HySelect will review possible patterns and determine for each pipe the design
flow required to:
Be as close as possible to the specified diversity factor.
Allow full flow and full power at each terminal unit.
This means that regarding:
Production units: the diversity factor is applied in full to the sizing of production units such as boilers,
chillers... They are downsized accordingly.
Distribution circuits: the diversity factor impacts partially the circuits by partially reducing the design flow
in some pipe segments.
Terminal units: there is no impact on the sizing of the end circuits as each terminal unit is always able to
provide its full power.
83
HySelect
84
HySelect
85
HySelect
Please note that the Fluid Characteristics you enter when performing different operations such as
individual selection, hydronic calculation, or using the additional tools are independent from one another. If
you change the fluid or its temperature here, these values will NOT be changed in other HySelect parts.
This group is active and can be used only when you have previously imported measurement data from a
TA-SCOPE for the current project.
Only the measurements performed during the selected period will be displayed. Please refer to the TA Scope
Data Processing chapter for more information about measurements management.
In this group, the following data are displayed:
Start: the beginning date of the interval to be used for data filtering.
End: the end date of this interval.
Click on the Choose period button to change these dates.
86
HySelect
6. Results Management
6.1. Overview
After products selection, either manually or after calculation, you can review the selected components and the
complete bill of material in the control panel Results tab as illustrated hereunder.
6. Results Management
87
HySelect
6. Results Management
88
HySelect
6. Results Management
89
HySelect
Click on the
Click on the
Click on the
6. Results Management
90
HySelect
The Search and Replace window - Search and replace pipe series
4. In the left pane, select the products on which you want to apply the selected operation. Check or uncheck the
products individually or use the buttons available at the bottom of the window.
5. In the right column, select the type of pipe to be replaced and the type of pipe to use as a replacement in all
the selected circuits.
If the type of pipe to replace cannot be selected, that means that this is the only type of pipe used
over the whole circuit.
6. In the right column, select the additional options for the replacement process.
7. Click on the Start button.
8. The replacements performed are displayed in the bottom right text area.
6. Results Management
91
HySelect
The Search and Replace window - Search and replace hydraulic circuits
4. In the left pane, select the products on which you want to apply the selected operation. Check or uncheck the
products individually or use the buttons available at the bottom of the window.
5. In the right column, select the type of circuit to be replaced.
6. Depending on the previous selection, additional parameters may or not be adjusted to fine tune the
replacement targets.
7. In the right column, select the additional options for the replacement process.
8. Click on the Start button.
9. A window similar to the one illustrated hereunder opens with the replacements to be performed.
6. Results Management
92
HySelect
10.Confirm each replacement individually with the Apply button, or all at one with the Apply All button.
11.The replacements performed are displayed in this window bottom text area.
The Search and Replace window - Constitute or split control valve and actuator sets
6. Results Management
93
HySelect
4. In the right pane, select the operation to perform (split sets or group products in sets).
5. In the left pane, select the products on which you want to apply the selected operation. Check or uncheck the
products individually or use the buttons available at the bottom of the window.
6. Click on the Start button.
7. Check the proposed operation as illustrated.
8. Click on the Apply button to accept the change and check the next one or click on the Apply all button to
accept changes for all products.
6. Results Management
94
HySelect
The Search and Replace window - Add or remove actuator on selected product
4. In the right pane, select the operation to perform (remove or add actuators on control valves).
5. In the right pane, also set the different options according to your needs.
6. In the left pane, select the products on which you want to apply the selected operation. Check or uncheck the
products individually or use the buttons available at the bottom of the window.
7. Click on the Start button.
8. Check the proposed operation as illustrated.
6. Results Management
95
HySelect
9. Click on the Apply button to accept the change and check the next one or click on the Apply all button to
accept changes for all products.
6. Results Management
96
HySelect
6. Results Management
97
HySelect
Exporting results
Click on the Export data command then select one of the export options (depending on the data available) to
export the Results tables as Excel data files.
All available tabs are exported as Excel sheets with the same name as illustrated hereunder.
6. Results Management
98
HySelect
Printing results
Click on the Print command then select:
Print Setup to select your printer and printer configuration.
Print to print your data. The following window opens with the selection option for printing:
6. Results Management
99
HySelect
6. Results Management
100
HySelect
101
HySelect
102
HySelect
Software update
If the TA-SCOPE software version is older than your HySelect software version, you can only download
the TA-SCOPE data,without being able to upload any data.
If HySelect detects that it has a newer version available for the connected TA-SCOPE, the following message is
displayed. Click on it to update the TA-SCOPE software version.
Download
Click on the Download button to open the following window. In this window, select:
On the left side, the quick measurements and the loggings stored in the TA-SCOPE.
On the right side, the plants stored in the TA-SCOPE.
Once you have selected all items you want to download, click on the Download button to transfer the data from
the TA-SCOPE. The downloaded data are displayed in the Logged Data screen, the Quick Measurements
screen, or in the TA-Diagnostic tab.
103
HySelect
Upload
Click on the Upload button to open the following window.
In this window, select on the left side, the circuits and subcircuits you want to transfer:
Check the box next to the (sub)circuit name to select it for upload.
Click on the box icon on the right of the (sub)circuit name line:
The open box icon means that the child circuits will be uploaded with the circuit.
The closed box icon means that the child circuits will NOT be uploaded with the circuit.
Once you have selected all circuits you want to upload, click on the Upload button to transfer the data to the TASCOPE.
104
HySelect
Maintenance
Click on the Maintenance button to open the following window. In this window, the following buttons are available
to perform maintenance operations on your TA-SCOPE:
Delete downloaded TA-SCOPE files: HySelect keeps a backup copy of all downloaded data from TA-SCOPE.
This function performs a purge of these backup file.
Clean-up TA-SCOPE memory: All data (hydronic circuits, quick measurements, and loggings) stored in the TASCOPE will be deleted.
Reload TA-SCOPE software: TA-SCOPE software as well as the products database will be reloaded using the
last available update pack. This operation preserves all user data.
105
HySelect
button to delete all saved plant data from the TA-CBI memory.
Click on the
Click on the Next>> button to start the data transfer then follow the displayed instructions.
106
HySelect
107
HySelect
108
HySelect
109
HySelect
110
HySelect
111
HySelect
8. System Configuration
8.1. Introduction
This chapter describes technical settings that are used in several operation performed by HySelect such as the
fluid characteristics settings or the advanced technical parameters that can be configured from different places
within the interface and during the software operation.
Water
Temperature: select the temperature at which the fluid calculations will be made such as the pressure
drop... This is the mean temperature between the temperature of the incoming flow and the temperature of
the outgoing flow in the plant (for example, if the incoming flow is 70C and the outgoing one is 50C, then
you should use 60C as the mean temperature and enter that value in the Temperature field).
Default DT: set the value used by default as the difference between the temperature of the incoming flow and
the temperature of the outgoing flow.
8. System Configuration
112
HySelect
8. System Configuration
113
HySelect
If you click on the icon, the following warning message is displayed reminding you of standard consigns to
follow regarding your fluid mix.
8. System Configuration
114
HySelect
8. System Configuration
115
HySelect
8.3.2. General
The General section
Valve displayed as a TA Product image (left) or a the HVAC Symbol (from TA) (right)
If the TA Product image is not available for a particular valve, the HVAC Symbol (from TA) will be used.
8. System Configuration
116
HySelect
8. System Configuration
117
HySelect
8. System Configuration
118
HySelect
8. System Configuration
119
HySelect
8. System Configuration
120
HySelect
8. System Configuration
121
HySelect
8. System Configuration
122
HySelect
8. System Configuration
123
HySelect
8. System Configuration
124
HySelect
8. System Configuration
125
HySelect
8. System Configuration
126
HySelect
8. System Configuration
127
HySelect
8. System Configuration
128
HySelect
8. System Configuration
129
HySelect
8. System Configuration
130
HySelect
8. System Configuration
131
HySelect
8. System Configuration
132
HySelect
8. System Configuration
133
HySelect
9. Additional Tools
9.1. Viscosity Correction
The Viscosity correction tool is used to compute the true flow of liquid in a valve according to the actual liquid
characteristics and viscosity.
Usually, all computations are based on a strictly turbulent flow regime. Nevertheless,HySelect, thanks to its
highly specialized mathematical models and algorithms, is able to determine the actual flow regime in a valve
(turbulent, intermediary, or laminar) according to its operation conditions and thus take this flow regime into
account to compute the true flow going through the selected valve in the specified conditions.
9. Additional Tools
134
HySelect
Water characteristics
Click on the
Please note that the Fluid Characteristics you enter when performing different operations such as
individual selection, hydronic calculation, or using the additional tools are independent from one another. If
you change the fluid or its temperature here, these values will NOT be changed in other HySelect parts.
Valve characteristics
There are 4 parameters in the right area of this window. Enter a value for 2 of these parameters in order for the
application to automatically compute the remaining 2 values as illustrated hereunder.
The values you should enter are marked by a small green icon. The values that will be computed are
marked by a small red icon. To change the values that you know and want to enter, simply click on the red
icon.
Setting (0,0 - xxx): the valve current setting (in number of turns) up to the xxx value (maximum possible
depending on the valve type).
Pressure Drop: the drop of presure through the selected valve.
Chart flow: the theoretical flow value assuming a strictly turbulent flow regime.
True flow: the true flow value based on the actual flow regime (turbulent, intermediary, or laminar).
If the true flow is similar to the chart flow, then the flow regime is turbulent. On the opposite, if these
values highly differ,a s in the illustrated example hereunder, then the actual flow regime is laminar (or
intermediary).
9. Additional Tools
135
HySelect
Please note that the Fluid Characteristics you enter when performing different operations such as
individual selection, hydronic calculation, or using the additional tools are independent from one another. If
you change the fluid or its temperature here, these values will NOT be changed in other HySelect parts.
9. Additional Tools
136
HySelect
Pressure drop
Once you have entered a Flow value, the application automatically computes the recommended pipe size and the
corresponding pressure drop. These results are adjusted in real time whenever you change any parameter (Flow,
Pipe Name or water characteristics).
The result is a table as illustrated hereunder. Each line corresponds to a pipe size and presents the pressure drop,
the fluid velocity and the flow regime (turbulent, intermediary, or laminar). The green text line highlights the
recommended pipe size according to your current parameters.
9. Additional Tools
137
HySelect
Parallel assembly
Series assembly
Example of a Kv calculation
9. Additional Tools
138
HySelect
When you have entered a Kv or the data required to calculate it in on of the left tabs:
The corresponding Kv value is displayed in the top right Current Kv field.
Click on the Add=> button to add this value in the right area.
The Kv Total resulting value is displayed in real time in the bottom right corner of the window as illustrated
hereunder.
At any time, if you want to remove a value, simply click on it then click on the Remove button.
The Nominal Condition tab
where:
q is the fluid flow (m3/h)
is the fluid density (kg/m3) retrieved from the fluid characteristics.
p (or Dp) is the pressure drop (bar)
The Kv tab
In this tab, simply enter the Kv value you want to add.
The Cv tab
In this tab, enter the Cv or flow coefficient value (usually used with imperial units). The Kv is calculated using the
following factor:
9. Additional Tools
139
HySelect
where:
is zeta pressure drop coefficient
D is the pipe internal diameter (m)
Kv is the flow factor
9. Additional Tools
140
HySelect
All these calculations are dependent on the water characteristics. In all 3 tabs, click on the
Water Characteristics window as illustrated hereunder:
q-Kv-Dp calculation
In this tab you have access to the following parameters:
Flow: the current flow in your system.
Kv (Valve coefficient): the flow factor of your valve.
Dp: the current pressure drop in your system.
Click on the radio button of the parameter you want to calculate and enter a value for both other parameters as
illustrated hereunder.
The unknown parameter is computed in real time and displayed according to the following formula:
where:
9. Additional Tools
141
HySelect
q-P-DT calculation
In this tab you have access to the following parameters:
Flow: the current flow in your system.
Power: the terminal unit emitted power.
DT: the temperature drop or rise in the terminal unit.
Click on the radio button of the parameter you want to calculate and enter a value for both other parameters as
illustrated hereunder.
The unknown parameter is computed in real time and displayed according to the following formula:
where:
P is the terminal unit emitted power (W)
q is the fluid flow (l /h)
T (or DT) is the temperature difference (K)
is the fluid density (kg/m3) retrieved from the fluid characteristics.
Cp is the fluid specific heat (J/kg.K) retrieved from the fluid characteristics.
9. Additional Tools
142
HySelect
q-Valve-Dp calculation
In this tab you have access to the following parameters:
Flow: the current flow in your system.
Seeting: setting of your valve.
DpT: pressure drop in your system.
Valve (Type, Family, and Valve): type of valve used
Select your valve (Type, Family, and Valve) then click on the radio button of the parameter you want to calculate
and enter a value for both other parameters as illustrated hereunder.
The unknown parameter is computed in real time and displayed according to the selected valve characteristics.
9. Additional Tools
143
HySelect
9. Additional Tools
144
HySelect
9.6. TA Link
The TA Link tool is used to check the connection with a TA Link and to compute, according to the TA Link type,
the analogue signal output it will issue when mounted on the selected valve in the specified configuration.
9. Additional Tools
145
HySelect
The catalogue is displayed in a tree form in the control panel as illustrated hereunder.
9. Additional Tools
146