Professional Documents
Culture Documents
Peppers A2LCF Gland
Peppers A2LCF Gland
CERTIFication
CERTIFicate
GLAND MARKING
APPLICATION
Exd Equipment
E
A2L**F type glands will only maintain Flameproof Exd integrity when used with cable that is substantially round and
compact with extruded bedding. The cable shall be deemed to be effectively filled. Ref: IEC60079-14:2002 Section 10.4.2
Gas Group
IIC, IIB, IIA
IIB, IIA
IIB, IIA
Enclosure Volume
Any
Any
2 litres or less
EExe Equipment
Gas Group II, Zones 1 and 2
INGRESS
PROTECTION
MATERIALS
Which Zone
Zone 1 or 2
Zone 2
Zone 1
Other Equipment
Ignitable Dust, Zones 21 and 22
THREADS
ISO Metric; NPT; NPS; ISO Pipe Thread (BSP Taper, BSP Parallel); PG
Seals
plating
OPERATING
TEMPERATURES
accessories
example part
number
Gland Size
Entry Threads
Metric
Entry Thread
Length
Max Across
Corners
[B]
[A]
Conduit Connector
Min
Max
NPT/BSP
NPT
ISO
16
M20
12
or 34
16
28.0
4.0
8.4
12
or 34
M20
20s
M20
12
or 34
16
28.0
7.2
11.7
12
or 34
M20
12
34
12
34
20
M20
16
33.0
9.6
14.0
25
M25
34
or 1
16
41.4
13.5
20.0
34
or 1
M25
32
M32
1 or 114
16
50.6
19.5
26.3
1 or 114
M32
40
M40
114 or 112
16
60.5
23.0
32.2
114 or 112
M40
50s
M50
50
M50
or
112
or 2
2
2 or
212
16
71.5
28.2
38.2
16
71.5
33.2
44.1
or
112
or 2
2
212
M20
M50
M50
63s
M63
19
88.0
39.3
50.1
63
M63
212
19
88.0
46.7
56.0
212
M63
75s
M75
212 or 3
19
99.0
52.3
62.0
212 or 3
M75
75
M75
19
99.0
58.1
68.0
M75
2 or
M63
Suitable only for fixed installations. The cable must be clamped near the gland to prevent pulling and twisting
Gland Size does not necessarily equate to the entry thread size
Integral entry thread seal option is not available for glands with tapered entry threads. IP washers can be supplied if required
Please note that dimensions (A) and (B) may differ for glands with non-Metric entry threads. Please refer to our thread data tables
for specific dimensions
Unless otherwise stated ISO Metric entry threads have a 1.5mm pitch
For Flameproof Exd applications the female thread into which the gland is to be fitted must comply with clause 5.3 of EN
50018:2000 (clause 5.3 IEC 79-1) and an engagement of at least 5 full threads must be achieved for parallel threads and should be
achieved for tapered threads
Where A2LF type glands are fitted into non-metallic Increased Safety Exe enclosures they must be included within the earth circuit
of the system
The user should seek expert advice if intending to combine flammable gases and combustible dusts in one environment/
installation
Full assembly instructions are supplied with glands, the instructions must be read prior to installation and adhered to in full
Other conduit connection threads eg PG, BSP are available upon request
http://www.cableglands.com