Grade Slab ACI-150thk
Grade Slab ACI-150thk
Grade Slab ACI-150thk
Subject
Rev
Doc. No.
Section
.
-
h
fc
=
=
150 mm
40 N/mm2
Grade of steel
fy
460 N/mm2
66700
~
4060 psi
Specifi.comp.strength of concrete
f'c
28 N/mm2
25 kN/m3
75 mm
12 mm
=
c
Dmain.
Sv
d
=
=
=
=
200 mm
69 mm
2.717 in.
0.9
=
=
0.75
1000 mm
60900 psi
39.370 in.
0.17
200 mm x 600 mm
Width
0.20 m
Length
0.60 m
0.2 + 2 x 0.15
0.50 m
0.6 + 2 x 0.15
45
0.90 m
Contact area
0.450 m2
0.45 x 150/1000 x 25
1.69 KN
7.00 KN
8.69 KN
f2
3q / h2 [1-( r 2 / r2 )0.6]
At an edge
f3
Ec
4700
=
=
=
=
4700*sqrt(28)
24870 N/mm2
0.004 N
0.450 m2
=
=
450000 mm2
/2
(area x 4 / )
=
=
sqrt(450000*4/3.14)/2
378.47
mm
RMK/ST
f'c
>
258.60
mm
04/03/2016
Project
Subject
Doc. No.
Rev
Section
.
-
RMK/ST
04/03/2016
Project
Subject
Rev
Doc. No.
Section
.
-
r1
r1
400.43044 mm
378.47 mm
r1
r2
=
=
(24870.0623240072*150^3/(12*(1-0.17^2)*0.004)^0.25
1158 mm
5 r2
r3
Coefficient
=
=
378 mm
5792 mm
1023
0.828
0.4
15K [(r2/r3)]2
0.240
f1
f2
0.266
=
=
0.430
0.514
=
=
0.45*4060
1827.000 psi
Dimensionless coefficient
f3
fallow.
fCalc
=
=
0.45*28
12.600 N/mm2
0.514 N/mm2
0.514 N/mm2
<
12.600 N/mm2
Safe
Bending moment ( un factored)
Mu
=
=
factual . (b x d2) / 6
407837 Nmm/m
=
=
0.408 kNm/m
0.091 ft-kips
=
=
1.6 x M
0.653 kNm/m
0.145 ft-kips
Design of reinforcement:
Calculate Ast(req.)
Mn
0.59 fy / f'c
9.69
Mn/ fybd
b
c
=
=
-1
0.0003
As(req.)
=
=
Solving qua.equation
0.00033
xbxd
0.035 sq.in
RMK/ST
04/03/2016
Project
Subject
Doc. No.
Rev
Section
.
-
22.72 mm2
RMK/ST
04/03/2016
Project
Subject
Rev
Doc. No.
Section
.
-
565.49 mm2
(prov.)
0.88 sq.in
0.0269
As(min.)
=
=
As(prov.)
(prov.)
Vu
Vc
Vc
=
=
Vn
Vn
0.0018 b x D
270 mm2
565 mm2
OK SAFE
>
270 mm2
0.0269
9 kN
f'c ( b x d ) / 6
60852.28 N
60.85 kN
Vu/
=
=
ie
11.59 kN
11.59 kN
<
<
Vc
60.85
kN
Vpu
9 kN
bo
73.9 in.
(i)
Vc1
(2+ 4/c)
=
=
(ii)
c
Vc1
Vc2
=
s =
f' c x
(bo x d)
76.7 kips
(sd/b0+2)
f' c x
40
(bo x d)
(iii)
Minimum of the above values,
Vc2
Vc3
Vc
=
=
=
vVc
=
=
197 kN
148 kN
Vpu
<
Vc
44.38 kips
4
f' c x
51 kips
44 kips
(bo x d)
RMK/ST
04/03/2016
Subject
Rev
EC-523-07-925
R0
Section
Annex - D
Doc. No.
Sheet No.
-
S.No.
Equipment Name
Nos.
kN
No. of
Supports
Load on
each
Support
Wheel Load
considered for
Grade Slab
Remarks
Design
kN
kN
TOC
Vendor
Drawing
Number
2400
24
4.000
100
SAFE
EL(+) 0.200
DC_357
750
7.5
1.250
100
SAFE
EL(+) 0.200
DC_358
13300
133
12
11.083
100
SAFE
EL(+) 0.180
DC_359
4750
47.5
7.917
100
SAFE
EL(+) 0.000
DC_360
Accumualtor
1150
11.5
1.917
100
SAFE
EL(+) 0.150
DC_372
(Refer Annex C)
Maximum Load on each support of the equipment is 12.5 kN. i.e., less than 100 kN.
Hence it is safe to rest the equipments in the grade slab of 250 mm thick.
Local thickening of grade slab is done to meet the vendor requirement of top of concrete.
RMK/ST
04/03/2016
Subject
Section
Annex - D
Rev
Doc. No.
R0
EC-523-07-925
Sheet No.
-
S.No.
Pipe Support ID
Nos.
Pedestal
Size
Wheel
Vertical
Vertical
Load
Load on Load on considered
Pipe
Pipe
for Grade Remarks
Supports Supports
Slab
Design
kg
kN
kN
10-BQ-251A,10-BQ251B
350 x 300
20.00
0.2
100
SAFE
10-BQ-252
400 x 300
25.00
0.25
100
SAFE
10-BQ-253
1900 x 400
250.00
2.5
100
SAFE
10-BQ-254,10-BQ256,10-BQ-258
950 x 400
50.00
0.5
100
SAFE
10-BQ-255
1900 x 400
325.00
3.25
100
SAFE
10-BQ-257
1900 x 400
400.00
100
SAFE
10-BQ-259, 10-BQ260
1300 x 400
225.00
2.25
100
SAFE
10-BQ-261
1400 x 400
225.00
2.25
100
SAFE
1050 x 400
60.00
0.6
100
SAFE
900 x 400
50.00
0.5
100
SAFE
450 x 350
80.00
0.8
100
SAFE
700 x 350
200.00
100
SAFE
600 x 400
200.00
100
SAFE
600 x 400
200.00
100
SAFE
9
10
11
12
13
14
10-BQ-262, 10-BQ263,10-BQ-264
10-BQ-265, 10-BQ266
10-BQ-267A, 10-BQ267B,10-BQ-269A, 10BQ-269B, 10BQ_271A, 10-BQ271B
10-BQ-268, 10-BQ270,10-BQ-272
10-BQ-274, 10-BQ275,10-BQ-276
10-BQ-277, 10-BQ278
15
10-BQ-279
1050 x 400
50.00
0.5
100
SAFE
16
10-BQ-280
1600 x 400
225.00
2.25
100
SAFE
TOC
EL (-) 0.097 /
EL (-) 0.100
RMK/ST
04/03/2016