On/Off Watertight

Hydramotor Actuator

For use withV710 Gas Valve Body

SERIES

AH2D

General Description
The AH2 Hydramotors are push-type, self-contained, electrohydraulic linear actuators which extend when powered and retract
by spring force upon power interruption.
AH2 Hydramotors provide a fast spring return shutoff time of one
second or less. When the actuator is mounted to a V710 gas
valve, position indicators on both sides of the actuator show the
open or closed position of the valve.
The AH2 Hydramotor/V710 gas valve combination provides reliable
main line gas control for a wide range of applications, including
boilers, furnaces, ovens and all types of industrial and commercial
burners. It is available in either a slow or fast opening construction.

Specifications:
Power Requirement: 220 VA max.
Closing Time: One second max.

Series AH2D Hydramotor with V710 valve body.

Opening Time:
Fast Opening: 14 seconds max.
Slow Opening: 26 seconds max.

Installation:

Note: Opening time is double between -30F and -40F ambient.


Opening time increased 20% when operating on 50Hz.

Enclosure:
Type 1, 2, 3, 3S, 4, 12, and 13 Combination General Purpose, Watertight,
Dusttight and Driptight.

Ambient Temperature:

AH2 Hydramotor mounts in any position


directly to a V710 valve with 4 set screws.

Damper Arm Rating:


Drives damper in one direction only. 20 lb. max. at
2.85" radius at 20F to 150F and 10 lb. max. at
-40F to 20F.

-40F to 150F (-40C to 66C)

Electrical:

Approvals:

Actuator:
Standard voltages:
24, 120, 240 volts, AC, 60 Hz (or 110,
220 volts AC, 50 Hz)

AH2 Hydramotor with V710 valve.

Proof of Closure Switch: (optional)


A factory set, non-field adjustable SPDT switch. 1800VA max. connected
load (e.g. one 15A load @ 120V or two 3.75A loads @ 240V).

CSA Certified to:


1) Automatic Gas Valves Z21.21 (6.5), File 109157
and 113070.
2) Automatic Gas Safety Shutoff Valves C/I (3.9),
File 113070.

Auxiliary Switches: (optional)


One or two integral SPDT switches; field adjustable to actuate at any
position of stroke. 1800 VA max.
connected load (e.g. one 15A load @ 120V or two 3.75A loads @ 240V).

Electrical Characteristics
Amperes
Voltage
24V

Inrush
28

Opening
8.00

Holding
0.73

120V

5.6

1.85

0.11

240V

2.8

0.92

0.05

File # MP932, Vol. 17, Sec. 3;


Safety Valves

JI 3000606
Gas Safety Shut-off Valves

Ordering Information:
Important: Order by Catalogue Number and add suffix
number for desired optional feature.
e.g. AH2D112A5

33

2/2

SERIES

AH2D

Specifications
Applications
On-Off Slow Opening (14 to 26 seconds)

24 V

Catalogue Number
120 V

240 V

Standard on-off

AH2D101A

AH2D102A

AH2D104A

Proof of closure

AH2D101S

AH2D102S

AH2D104S

Standard on-off

AH2D111A

AH2D112A

AH2D114A

Proof of closure

AH2D111S

AH2D112S

AH2D114S

On-Off Fast Opening (6 to 14 seconds)

Optional Features:
(add appropriate suffix number to catalogue number)
One Auxiliary Switch (add suffix 2)
Spring Return Damper Arm (add suffix 3)
Damper Shaft & Arm (add suffix 4)
Damper Shaft, Arm & one Auxiliary Switch, (add suffix 5)
Manual Reset (add suffix R)

Dimensions: inches

34

2-Way Normally Closed

V710 Valve Body


Pipe Sizes 3/4" to 3" NPT, 4" Flange

SERIES

V710

General Description
These 2 way normally closed globe type valve bodies are designed
for on/off or proportional control of commecial or industrial gas
burners. The V710 is designed exclusively for use with the AH
Hydramotor actuator. The AH Hydramotor valve consists of two
assemblies; the valve body and the AH Hydramotor actuator.
The V710 is a Push-to-Open valve which opens when the valve
stem is depressed by an AH Hydramotor actuator. An internal
return spring closes the valve when the Hydramotor actuator is
de-energized.

Model Types:
Quick Opening Trim: (Standard)
For applications where metered flow control is not required.
Quick Opening w/Valve Seal Overtravel Trim: (Suffix V22)
For any on-off application where the user, code or approval agency
requires a valve seal overtravel arrangement.
Linear Trim: (Suffix V15)
For applications that require flow control, such as slow opening, low
fire turn down, or proportional control.
Linear w/Valve Seal Overtravel Trim: (Suffix V25)
For applications where both valve seal overtravel and flow control are
required. (Not available in 4" flange size.)

Specifications:
Pressure Taps:
Two 1/4" NPT downstream, two 1/4" NPT upstream.
Fluid: Fuel Gas

Series V710 Valve Body with AH Hydramotor

Installation:
V710 valve body mounts in any position
directly to AH2, AH4, AH8 Hydramotor actuator.

Approvals:
V710 valve with AH Hydramotor.

File # MP932, Vol. 17, Sec. 3;


Safety Valves
CSA Certified to:
1) Automatic Gas Valves Z21.21 (6.5), File 109157
and 113070.
2) Automatic Gas Safety Shutoff Valves C/I (3.9),
File 113070.

Valve Parts in Contact with Fluid:


Body: 3/4" to 3" NPT, Die-cast aluminum, 4" Flange - cast iron
Bonnet: Die-cast aluminum
Seals: Nitrile
Springs: Zinc-plated music wire
Stem Bushing: Delrin
Valve Stem: 303 s.s.
Retaining Pin: 303 s.s.
Retaining Ring: 17-7 s.s.
Pipe Plugs: Zinc-plated steel

JI 3000606
Gas Safety Shut-off Valves

Ordering Information:
Important: Order by Catalogue Number.
e.g. V710EASV22

Seal Ring: Teflon (models with overtravel)


Closeoff Pressure: 25 psi maximum

39

SERIES

V710

Specifications
Operating Pressure
Differential (psi)
Pipe
Min. Cv
Min.
Size
Flow
Gas Capacity*
(ins.)
Factor
Btu/hr
Normally Closed (Closed when released)
3/4
1
1 1/4
1 1/2
2
2 1/2
3
4

12
17
25
30
64
75
92
180

665,000
960,000
1,406,000
1,717,000
3,620,000
4,250,000
5,230,000
10,200,000

Fluid & Ambient


Temp.F

Min.

Max.

Min.

Max.

Quick
Opening Trim

0
0
0
0
0
0
0
0

15
15
15
15
10
10
10
15

-40
-40
-40
-40
-40
-40
-40
-40

150
150
150
150
150
150
150
150

V710EAS
V710FAS
V710GAS
V710HAS
V710JAS
V710KAS
V710LAS
V710NCF

Catalogue Numbers
Quick Opening
w/Valve Seal
Linear
Overtravel Trim
Trim
V710EASV22
V710FASV22
V710GASV22
V710HASV22
V710JASV22
V710KASV22
V710LASV22
V710NCFV22

V710EASV15
V710FASV15
V710GASV15
V710HASV15
V710JASV15
V710KASV15
V710LASV15
V710NCFV15

Linear
w/ValveSeal
OvertravelTrim
V710EASV25
V710FASV25
V710GASV25
V710HASV25
V710JASV25
V710KASV25
V710LASV25
N/A

* 1" W. C. Drop @ 2" W. C. Inlet Pressure, 1,000 Btu/Cu. Ft or more, 0.64 Spec. Grav. Gas

Trim Types

Quick Opening Trim


(Standard)

Quick Opening with


Valve Seal Overtravel Trim
Suffix V22

Linear Trim
Suffix V15

Linear with
Valve Seal Overtravel Trim
Suffix V25

Dimensions: inches

3/4" - 3" NPT

Pipe
Size
3/4
1
1 1/4
1 1/2
2
2 1/2
3
4

A
5.78
5.78
5.78
5.78
8.12
9.00
9.00
13.88

B
1.95
1.95
2.01
2.01
2.66
2.96
2.96
5.00

C
2.64
2.64
2.94
2.94
3.05
3.87
3.87
7.40

D
5.19
5.19
5.19
5.19
8.01
8.01
8.01
9.00

4" FLANGE

40

E
1.16
1.16
0.70
0.70
0.96
0.70
0.70
0.00

Shipping
Weight (lbs.)
4.0
4.0
4.2
4.2
9.5
13
12
100