700W1000W User Manual
700W1000W User Manual
700W1000W User Manual
List of Contents
1. Features
1-1
Application
1-2
Electrical performance
1-3
Mechanical drawings
2
3
5
2. Introduction
2-1
2-2
2-3
2-4
2-5
2-6
2-7
2-8
6
7
9
10
11
11
13
15
3. Maintenance
15
4. Troubleshooting guide
16
5. Warranty
17
17
17
7. Appendices A
7-1
7-2
18
18
1.
Features
n
n
n
n
n
n
n
Model
YKPSW1270
Item
YKPSW2470
YKPSW4870
700W
780W (3Min.)
Surge Rating
1400W
Input Voltage
12V
24V
48V
12V
24V
48V
10-16VDC
20-32VDC
42-62VDC
10-16VDC
20-32VDC
42-62VDC
15.5VDC
31.0VDC
61.0VDC
15.5VDC
31.0VDC
61.0VDC
16.0VDC
32.0VDC
62.0VDC
16.0VDC
32.0VDC
62.0VDC
10.5VDC
21.0VDC
43.0VDC
10.5VDC
21.0VDC
43.0VDC
10.0VDC
20.0VDC
42.0VDC
10.0VDC
20.0VDC
42.0VDC
Output Voltage
Frequency
Peak Output Current
13A
6A
88%
90%
91%
92%
93%
94%
0.87A
0.43A
0.23A
0.83A
0.43A
0.22A
Optional
Output Waveform
Protection
Overload, Short circuit, Reverse Polarity (Fuse), Over/Under Input Voltage, Over Temp.
Safety
EN60950-1:2006 &
EMC
FCC Class B
IEC61000-4-3:2002/A1:2002
IEC61000-4-4:2004
IEC61000-4-5:1995/ A1:2000
IEC61000-4-6:1996/A1:2001
IEC61000-4-8:1993/A1:2000
IEC61000-4-11:2004
Digital Display
-20C to 50C
-30C to 70C
Cooling
Dimensions
Weight
2.8kgs
Note: The specifications are subject to change without notice.
3
Electrical Performance1000W
Specification
Model
YKPSW12100
Item
YKPSW24100
1000W
1150W (3Min.)
Surge Rating
2000W
Input Voltage
12V
24V
48V
12V
24V
48V
10-16VDC
20-32VDC
42-62VDC
10-16VDC
20-32VDC
42-62VDC
15.5VDC
31.0VDC
61.0VDC
15.5VDC
31.0VDC
61.0VDC
16.0VDC
32.0VDC
62.0VDC
16.0VDC
32.0VDC
62.0VDC
10.5VDC
21.0VDC
43.0VDC
10.5VDC
21.0VDC
43.0VDC
10.0VDC
20.0VDC
42.0VDC
10.0VDC
20.0VDC
42.0VDC
100/110/115/120V(Switch Selectable)
RMS3%
Output Voltage
200/220/230/240V(Switch Selectable)
RMS3%
Frequency
Peak Output Current
18A
9A
86%
88%
89%
87%
90%
92%
1.07A
0.63A
0.43A
0.93A
0.47A
0.31A
Optional
Output Waveform
Protection
Overload, Short Circuit, Reverse Polarity (Fuse), Over/Under Input Voltage, Over Temp.
Safety
EN60950-1:2006 &
EMC
FCC Class B
Digital Display
Operating Temperature
Range
-20C to 50C
-30C to 70C
Cooling
Dimensions
Weight
3.8kgs
Note: The specifications are subject to change without notice.
4
2.
Introduction
The power inverter series are the member of the most advanced line of mobile AC power
systems available.
To get the most out of the power inverter, it must be installed and used properly.
Please read the instructions in this manual before installing and using this model.
WARNING!
Do not connect the 12V model to a 24V battery. The unit will
be destroyed immediately.
2-2-3 RS-232
Connect to remote control unit (option accessory) or connect to computer to remote
control working status.
WARNING!
Any damages caused by using incorrect RS232 cable will be
outside of our warranty scope. If you are not sure which one
is correct RS232 cable, please purchase the correct RS232
cable from us directly.
8
2-2-4 Connect chassis ground terminal to earth or to vehicle chassis using # 8 AWG wire.
WARNING!
Operation of the inverter without a proper ground, connection
may result in an electrical safety hazard.
WARNING!
Shock Hazard. Before proceeding further, carefully check the
inverter is NOT connected to any batteries, and that all wiring
is disconnected from any electrical sources. Do not connect
the output terminals of the inverter to an incoming AC source.
2-3 Installation:
Where to install
The power inverter should be installed in a location that meets the following requirements.
2-3-1 Dry Do not allow water to drip or splash on the inverter.
2-3-2 Cool Ambient air temperature should be between -20C and 50C, the cooler the
better.
2-3-3 Safe Do not install in a battery compartment or other areas where flammable
fumes may exist, such as fuel storage areas or engine compartments.
2-3-4 Ventilated Allow at least 3 inch of clearance around the inverter for airflow. Ensure
the ventilation openings on the rear and bottom of the unit are not obstructed.
2-3-5 Dust-free Do not install the inverter in a dusty environments where are dust, wood
particles or other filings/shavings.
These dusts can be pulled into the unit when the cooling fan is operating.
2-3-6 Close to batteries Avoid excessive cable lengths but do not install the inverter in
the same compartment as batteries.
Use the recommended wire lengths and sizes (see section 2-6).
Also do not mount the inverter where it will be exposed to the gases produced by the
battery. These gases are very corrosive and prolonged exposure that will damage
the inverter.
WARNING!
You may observe a spark when you make this connection
since current may flow to charge capacitors in the power
inverter.
Do not make this connection in the presence of flammable
fumes. Explosion or fire may result.
WARNING!
Make sure all the DC connections are tight (torque to 9-10
ft-lbs, 11.7-13Nm). Loose connections will overheat and could
result in a potential hazard.
2-4-3 Before proceeding further, carefully check that cable you have just connected
negative terminal of inverter to the negative output power source.
CAUTION!
Reverse polarity connection will blow a fuse in inverter and
may permanently damage the inverter.
Damage caused by reversing polarity connection is not
covered by our warranty.
2-4-4 Connect the cable from the negative terminal of the inverter to the negative terminal
of the power source. Make a secure connection.
WARNING!
You may observe a spark when you make this connection
since current may flow to charge capacitors in the power
inverter.
Do not make this connection in the presence of flammable
fumes. Explosion or fire may result.
10
2-4-5 Set the power switch to the ON position; you will hear the bi-bi-bi sound. At the
same time, the display shows the word ASIAN for two times. After that, you will
hear the continuous sound from internal alarm. Then, the AC voltage shows on the
display. It means the device has done the operation.
2-4-6 Set the power switch to the OFF position; the device shut down completely.
2-4-7 Please use a power meter to accurately measure the true output R.M.S. voltage of
inverter.
Our company uses a power meter such as IDRC CP-350 or ABM 2019 to measure
our product.
2-5 AC Safety Grounding:
During the AC wiring installation, AC input and output ground wires are connected to the
inverter. The AC input ground wire must connect to the incoming ground from your AC
utility source.
The AC output ground wire should go to the grounding point for your loads (for example, a
distribution panel of bus chassis).
WARNING!
Do not operate the power inverter without connecting it to
Ground.
Electrical shock hazard may result.
WARNING!
The installation of a fuse must be on positive cable.
Failure to place a fuse on + cables running between the
inverter and battery may cause damage to the inverter and
will void warranty.
11
Model No
Wire AWG
Inline Fuse
YK-PSW1270
#4
100A
YK-PSW1270E
#4
100A
YK-PSW2470
#6
50A
YK-PSW2470E
#6
50A
YK-PSW4870
#8
30A
YK-PSW4870E
#8
30A
Model No
Wire AWG
Inline Fuse
YK-PSW12100
#2
150A
YK-PSW12100E
#2
150A
YK-PSW24100
#4
80A
YK-PSW24100E
#4
80A
YK-PSW48100
#6
40A
YK-PSW48100E
#6
40A
1000W
Also, use only high quality copper wiring and keep cable length short from 3-6 feet.
12
Model
YK-PSW1270
YK-PSW12100
YK-PSW1270E YK-PSW12100E
YK-PSW2470
16.0VDC
15.5VDC
10.5VDC
10.0VDC
32.0VDC
31.0VDC
21.0VDC
20.0VDC
62.0VDC
61.0VDC
43.0VDC
42.0VDC
YK-PSW24100
YK-PSW2470E YK-PSW24100E
YK-PSW4870
DC Input Over
DC Input
DC Input
DC Input Over
Under Voltage Under Voltage
Voltage
Voltage Alarm
Shut-down
Alarm
Shut-down
YK-PSW48100
YK-PSW4870E YK-PSW48100E
2-7-7
VAC
AMP
WATT
Ranges
100-120 200-240
VAC
VAC
0-10A
0-1KW
1% 0.5A
3%
Accuracy
1%
1%
VDC
TEMP
Frequency
2%
2%
1%
60Hz
0.01 0.01
2-7-8
2-7-9
2-7-10
14
2-7-11
3.
Maintenance:
Very little maintenance is required to keep your inverter operating properly.
You should clean the exterior of the unit periodically with a dry cloth to prevent
accumulation of dust and dirt. At the same time, tighten the screws on the DC input
terminals.
15
4.
Troubleshooting Guide:
WARNING!
Do not open or disassemble the inverter. Attempting to service
the unit yourself may result in a risk of electrical shock or fire.
Possible Cause
Solution
Over load
Reduce load
Recharge battery,
check connections and cable.
( Ref. point 2-5 & point 2-6)
Thermal shutdown
Improve ventilation.
Make sure ventilation openings
in inverter are not obstructed.
Reduce ambient temperature.
No output voltage
Fault input voltage
No output voltage
Over temp indicator
Load less than 800W
No output voltage
Over load indicator
16
5.
Warranty:
We warrant this product against defects in materials and workmanship during warranty
period and will repair or replace any defective power inverter when directly returned
(postage paid) to us.
This warranty will be considered void if the unit has suffered any obvious damage by
natural and man-made factors, or alteration either internal or external and does not cover
damage arising from improper use such as plugging the unit into an unsuitable power
sources attempts to operate products with excessive power consumption requirement, or
use in unsuitable environments. This is the only warranty that the company makes.
No other warranties express or imply including warranties of merchantability and fitness for
a particular purpose. Repair and replacement are your sole remedies and the company
shall not be liable for damages, whether direct, incidental, special or consequential, even
though caused by negligence or other fault.
6.
7.
Appendices A
FREQ. (Hz)
S2
S3
BAUD RATE
S4
S5
ON
60
OFF
OFF
2400
OFF
OFF
VOLTAGE OUTPUT
(VAC)
100
OFF
50
OFF
ON
4800
OFF
ON
110
-------
-------
ON
ON
OFF
ON
9600
19200
ON
ON
OFF
ON
115
120
S1 ( FREQ. Hz ) 50Hz/60Hz
S2 S3 (BAUD RATE ) 2400 / 4800 / 9600 / 19200
S4 S5 (VOLTAGE OUTPUT ) 100VAC / 110VAC / 115VAC / 120VAC
When you set up S1~S5, please reset the inverter and let update data through CPU.
7-2 220VAC Dip Switch (at the left side of inverter)
S1
FREQ. (Hz)
S2
S3
BAUD RATE
S4
S5
ON
60
OFF
OFF
2400
OFF
OFF
VOLTAGE OUTPUT
(VAC)
200
OFF
50
OFF
ON
4800
OFF
ON
220
-------
-------
ON
ON
OFF
ON
9600
19200
ON
ON
OFF
ON
230
240
S1 ( FREQ. Hz ) 50Hz/60Hz
S2 S3 (BAUD RATE ) 2400 / 4800 / 9600 / 19200
S4 S5 (VOLTAGE OUTPUT ) 200VAC / 220VAC / 230VAC / 240VAC
When you set up S1~S5, please reset the inverter and let update data through CPU.
RE-MARK:
The user manual is subject to change without notice.
18