Emerg Lighting-0601597 A-Install Instr
Emerg Lighting-0601597 A-Install Instr
Emerg Lighting-0601597 A-Install Instr
Class I, Zone 2
Group IIB + H2
Type 3R
WARNING:
Before installation, ensure that units comply with hazardous area classification. Failure to do so may result in bodily
injury and/or property damage. To prevent ignition of hazardous atmospheres, area must be free of hazardous vapors
before opening enclosure or servicing fixtures. To reduce the possibility of static sparking, do not attach metallic parts
to the outside of unit (i.e., metallic screws, tags, decals, etc.)
DO NOT ATTEMPT INSTALLATION UNTIL YOU ARE FAMILIAR WITH THE
FOLLOWING PRECAUTIONS AND PROCEDURES.
CAUTION: SERVICE BY QUALIFIED PERSONNEL ONLY.
DE-ENERGIZE BEFORE OPENING.
When using electrical equipment, basic safety precautions should always be followed including the following:
Do not mount near gas or electric heaters.
Equipment should be mounted in locations and at heights where it will not readily be subjected to tampering by
unauthorized personnel.
The use of accessory equipment not recommended by the manufacturer may cause an unsafe condition.
Caution: Halogen cycle lamp(s) are used in this equipment. To avoid shattering: Do not operate lamp in excess
of rated voltage, protect lamp against abrasion and scratches and against liquids when lamp is operating, dispose
of lamp with care.
Halogen cycle lamps operate at high temperatures. Do not store or place flammable materials near lamp.
Do not use this equipment for other than intended use.
Servicing of this equipment should be performed by qualified service personnel.
Wiring and installation should be performed in accordance with the National Electrical Code (NEC) and other applicable local code requirements.
To reduce the risk of electric shock, disconnect AC power before servicing. To prevent arcing, avoid shorting
battery terminals.
Do not attempt to service the battery. This unit uses a sealed, pure lead battery, which requires no maintenance.
For replacement, contact the factory.
Refer to fixture nameplate for suitability in specific hazardous locations.
Input Voltage:
120, 220, 240 or 277VAC, 60Hz.
Input Wattage (Maximum):
25W
6VDC & 12VDC
Output:
36 Watts Maximum for 2 hours (C1D2-6V36, C1D2-12V36)
72 Watts Maximum for 2 hours (C1D2-6V72, C1D2-12V72)
Listed Lighting Fixtures:
Voltage:
6VDC 8W, 12VDC 8W
Lamp Type:
Halogen PAR 36 Sealed Beam, 12W Option for 6 & 12V
Maximum Ambient
40OC
Temperature:
Temperature Code:
T5 (100OC)
-0 Unit supplied without lighting heads
Options:
-1 Unit supplied with single lighting head
Figure 1
3001
Figure 2
Emergency Lamps
Unit Mounted
Conduit Hub
Antirotation Bracket
Lighting Fixture
Set Screw
Ground Screw
Lighting Fixture
Set Screw
Fuse
Transformer
P.C. Board
Vent
AC On
Pilot Light
Terminal Block
Terminal Cover
Test
Switch
12.5
9.7
Battery
Battery
Battery Strap
11.7
0726
12.03
Mounting Feet
Figure 3
Listed Remote Fixture (shown with cover removed)
Lamps
Conduit
Blue (+)
Ground Plate
Watertight Hub
Yellow (-)
Watertight Hub
Conduit
2.875
Ground Screw
Mounting Feet
Ground Plate
0725
Remote (-)
Ground Screw
Wire Nut
Remote (+)
12.625
Installation:
Be sure intended AC power supply to the enclosure is off before proceeding.
Refer to: wiring diagram (Figure 1 opposite, and on the back of the enclosure cover), for all electrical connections; Figure 2 for enclosure and components layout; and Figure 3 for Listed Remote Fixtures.
1. Select a mounting location that will provide suitable strength and rigidity for supporting enclosure and
mounted lighting fixtures.
2. Loosen (do not remove) the 4 captive cover screws. Set the cover safely aside for later reassembly.
3. Attach the four mounting feet (included in the hardware package ) to the enclosure. Securely fasten the
unit to the desired mounting location. See Figure 2.
Proper mounting position is with the rear of the enclosure fastened to a vertical supporting surface, with the
pilot light and push-to-test switch located on the right side of the enclosure. Any other mounting position
may impair operation or damage the equipment.
5. Feed the AC power conductors through the hub assembly on the top of the unit.
An Appleton polymeric enclosed hub with ground lug is provided for entrance of AC power supply.
Following final conductor routing, use a thread sealant in the conduit-to-hub joint to maintain maximum
environmental protection.
Remove the cover from the terminal block assembly and connect the AC power supply as shown on the
wiring diagram. The printed circuit board, mounting plate and hub must be grounded.
6. Install and connect Listed remote lighting fixture(s) (if applicable). Note connections on the wiring diagram.
Refer to Figure 3 for mounting methods. Note: Hub must be grounded.
7. Place the battery(ies) flat on the bottom of the enclosure, with the terminals facing up and to the front of
the enclosure. Connect the battery leads, following the placement and connections exactly as shown on
the wiring diagram. Do not short the battery leads against the metal shelf during installation. For 12-volt
units, a jumper connector is attached to the battery leads with the label. Connect battery strap to secure
batteries to the enclosure. Emergency lamps will not light at this time.
8. Loosen (do not remove) the set screws at the base of the lighting fixture mounting stems. Adjust the lighting fixtures to the desired position, and tighten the set screws.
9. A time delay circuit holds the unit in emergency operation for 15 minutes following restoration of normal
utility power, after a power failure.
10. Check all connections for continuity and grounding integrity. Reinstall terminal block cover. Reinstall
enclosure cover, and securely tighten (4) cover screws. Energize AC power supply; AC pilot light should
illuminate. After 15 minutes, push test switch; emergency lamps should be illuminated. Releasing test
switch extinguishes emergency lamps.
Installation complete.
Troubleshooting Guide
Trouble
Possible Cause
Remedy
Check AC power
Replace fuse
Remove excess load
Check battery
Wait 15 minutes, push
test switch
Replace
Replace
Charge battery
Replace charger board
Replace battery
Check wire run size
Maintenance
1. Sealed pure-lead batteries require no maintenance.
2. Test operation of the emergency circuit monthly for
30 seconds minimum, using the TEST SWITCH.
Emergency lamps must illuminate.
Replacement Parts
Charger Circuit Board
Model
Volts, Watts
Part
Number
6V, 36W
6V, 72W
12V, 36W
12V, 72W
0980932
0980932-01
0980933
0980933
Transformer:
6V Units
0230847
12V Units
0230848
Total Watts
On Wire Run
6
7.2
8
9
12
13
18
25
28
36
44
50
56
70
6-Volt System
Wire Gauge
#12
#10
#8
#6
Max. Length of Wire Run (Feet)
89
74
67
59
44
42
30
21
19
15
12
10
9
7
141
118
106
94
70
65
47
34
30
23
19
17
15
12
225
187
168
150
112
103
75
54
48
37
30
27
24
19
357
298
268
238
178
165
119
85
77
60
48
43
38
30
Total Watts
On Wire Run
6
7.2
8
9
12
13
18
25
28
36
44
50
56
70
12-Volt System
Wire Gauge
#12
#10
#8
#6
Max. Length of Wire Run (Feet)
356
296
267
237
178
164
118
85
76
59
48
42
38
30
566
471
424
377
283
261
188
135
121
94
77
67
60
48
900
750
675
600
450
415
300
216
193
150
122
108
96
77
1431
1193
1073
954
715
660
477
343
306
238
195
171
153
122
0283001 D