Chapter 13 EX Wiring Methods
Chapter 13 EX Wiring Methods
Chapter 13 EX Wiring Methods
NORSOK Standards
The NORSOK standards are developed by the
Norwegian petroleum industry to ensure
adequate safety, value adding and cost
effectiveness for petroleum industry
developments and operations. Furthermore,
NORSOK standards are as far as possible intended
to replace oil company specifications and serve as
references in the authorities regulations. Key
Norsok Standard to reference are below:
1 Scope
2 Normative and informative references
3 Terms, definitions and abbreviations
4 General requirements and conditions (see IEC
61892-1)
5 System design (see IEC 61892-2)
6 Equipment (see IEC 61892-3)
7 Cables (see IEC 61892-4)
8 Mobile units (see IEC 61892-5)
9 Installation (see IEC 61892-6)
10 Hazardous areas (see IEC 61892-7)
Annex A (Normative) Data sheets
Annex B (Informative) Typical installation
drawings
Specific Guidance
on types of Ex
equipment and
gland usage
Typical International
Wiring Specification - Generalities
Multicore cables on racks or trays may be bunched in a maximum of two layers.
HV and LV single core cables shall be laid in trefoil groups with 150 mm clear spacing
between trefoils.
On trays or racks HV cables shall be segregated from the LV cables. Individual cables emerging from
floors or soil shall be protected against mechanical damage by means of galvanized steel pipes or
rigid PVC pipes. Single core cables emerging from floors or soil shall be protected by rigid PVC pipes.
These pipes shall extend at least 100 mm above ground or floor level.
Grouped cables emerging from floors or soil shall be protected collectively by a properly designed
metal shield or duct in such a way that heat dissipation of the sustained load carrying cables is not
hampered. The propagation of fire from one space to the other shall be prevented by proper sealing
of openings around cables.
Cables or cable supports shall not be fixed directly or indirectly to plant, equipment or process piping
which may require removal or replacement. Cables shall be laid on racks or trays strictly in
accordance with the laying patterns stated on the layout drawings. Metal parts of the cable racks and
trays shall be bonded and connected to the common earthing grid.
Typical International
Wiring Specification - Generalities
Bends and corners in the cable racks, trays or ladders shall take account of the minimum
cable bending radii. Cable racks and trays shall be closed by removable top covers,
allowing adequate ventilation, in situations where:
- mechanical damage of the cables is likely to occur during plant maintenance activities,
- oil or chemical spillages on the trays can be expected,
-sun shielding is required against direct solar radiation.
Vertical cable rack risers shall not be installed in front of, or over, pipe risers.
Flexible cabling
The application of flexible cables in industrial plants and installations shall be limited to:
- welding cables;
- trailing cables, e.g. for movable equipment, hand tools, hand lamps;
- winches, hoists, soot blowers, and electric motors, if connected by means of a nearby
intermediate junction box.
An earth continuity conductor, equal in cross-sectional area to the largest phase
conductor, shall be provided. This requirement applies even when the cable is armored.
Typical International
Wiring Specification - Generalities
Cable marking/numbering
Cable numbers shall be marked on the cables along their routes and at both termination
points. For underground cabling, the spacing between cable numbers along the route should
not exceed 5 m, and for above ground cabling, 25 m. Cables shall also be numbered where
they branch off from a main route.
For underground cable marking purposes non-corroding strips shall be used, each having
ample length to be wrapped twice around the cable and in which the cable number has been
imprinted by means of letter/cipher punches. For above ground cabling, plastic markers
resistant to the site conditions shall be strapped round the cables.
For underground cabling, above ground route markers shall also be provided at every change
of direction in the routing and at both sides of road or pipeline crossings, except when cable
routing is already indicated by colored concrete pavement.
Ex Installation Methods
Conduit or Cable Glands...
Rigid Conduit
Unarmored
Cable
Armored
Cable
IEC60332-3 categories
Test
Qty of material
Flame application
Supersedes
60332-3-22 Cat A
7.0 litres
40 minutes
IEC60332-3A
BS4066 pt 3A
60332-3-23 Cat B
3.5 litres
40 minutes
IEC60332-3B
BS4066 pt 3B
20 minutes
IEC60332-3C
BS4066 pt 3C
20 minutes
60332-3-21 Cat A F/R Used for large O.D cables instead of 3-22 Cat A. The cables are
mounted on the front and back of the ladder
A cables ability to continue operating safely during a fire. Also referred to as circuit integrity.
Performance requirement
3 hours at 750C (1970 edition)
90 minutes @ 750C (unless alt. stated in the cable
Standard
IEC60331
IEC60331-21
spec)
IEC60331-23
IEC60331-25
IEC60331-31
Data cables
Optical fibre
Cables 0.6/1kV
90 minutes @ 750C
90 minutes @ 750C
120 minutes @ 830C with vibration
VDE0472
FE180
DIN 4102
E30
DIN 4102
E90
Obscuration of vision and toxic gas are the main threat to people during a fire leading to
disorientation and chocking from fumes. Death is normally caused by . choking rather than
flames. Reducing smoke & fume emissions is vital to enable safe evacuation.
Equipment damage is caused by HCl gases mixing with moisture from the sprinkler systems
and creates acid rain leading to long term component failure even if the equipment does not
look damaged.
Not all materials that are low smoke are halogen free, examples :
LS-PVC (Limited Smoke PVC to UL1685)
Fluorocarbons (PTFE, FEP etc.)
Type B CSP to BS6883 (1991)
Measurement method :
100W halogen light source sensed by a photoelectric
cell positioned on the opposite side of the smoke
cube.
IEC60754-1 (BS EN 50267 pt1) measures the amount of hydrochloric acid (HCl)
evolved during burning. The result is normally expressed as a percentage of the
sample weight. There is no pass/fail criteria.
This method is not suitable for testing cables classed as Zero Halogen and
compounds containing less than 5mg/g (5%)
IEC60754-2 (BS EN 50267 pt2) measures the corrosiveness of the evolved gas in
terms of acidity (pH) and conductivity. IEC 60754-2 recommended values are :
Label
PE
N
L
L1
L2
L3
The United Kingdom now follows the IEC AC wiring color codes. The table below lists these
along with the obsolete domestic color codes.
Function
Protective Earth
Neutral
Line, single Phase
Line, 3 phase
Line, 3 phase
Line, 3 phase
Label
PE
N
L
L1
L2
L3
Current Color UK
Green-Yellow
Blue
Brown
Brown
Black
Grey
Old Color UK
Green-Yellow
Black
Red
Red
Yellow
Blue
The use of color coded ferrules or sleeves is typically left up to the client/user
preference. Either practice is acceptable to relevant IEC standards.
Wiring Methods
Wiring concepts Offshore follow the established & prevailing Marine
standards, e.g. IEC 60092-352
Metallic parts (including armour) shall be earthed effectively to
prevent them from becoming live.
Cable Armour/Braid provides a means of good earth continuity as well
as mechanical protection.
Normal practice has been to use external grounding as the most direct
route to earth.
This is easily achieved with metallic cable glands in non metallic
enclosures by the use of an earth tag
Shrouds have been found to be an ineffective means of keeping water
out of enclosures and glands are typically not used for North Sea
applications any more
Armor Cone
Inner Seal
Clamping Ring
Back End
Outer Seal
Installation of Ex ed gland
Inner & Outer Seals
Locknut
Ex d & Ex e
Installation of Ex d barrier
gland
Flame Path
Exhaust
Routes
Seal required to
withstand
a pressure of 450 PSI
(31 bar)
for 2 minutes
Pressure Flame
Hot Gases
Flame Path
Epoxy Resin
Compound
Cable A
Incorrect Shape,
Cables Should
be Round
Cable B
Cable C
No Inner Sheath,
Extruded Bedding
or Suitable Fillers
Cable D
Correct Cable,
e.g. has an
extruded
inner bedding
Cable E
In general, about 90% of the application for hazardous location cable glands can be
fulfilled with the use of a non-barrier compound gland
Ignition Source
Due to this
Market Sector
UK Offshore
Hazardous Areas
Ex e 90%
Ex d 10%
Braid Armor
98%
Brass "Armored"
Exd / Ex e
Cable Gland
99%
Equipment
Cable
Brass "Armored"
Ex d Compound
Barrier Gland
1%
Unarmored
2%
Brass "Unarmored"
Ex d / Ex e
Cable Gland
99%
Cable Glands
"Unarmored"
Plastic Ex e
Cable Gland
1%