Field Testing of Overcurrent Trip Units For Low Voltage Circuit Breakers Used in DC Applications
Field Testing of Overcurrent Trip Units For Low Voltage Circuit Breakers Used in DC Applications
Field Testing of Overcurrent Trip Units For Low Voltage Circuit Breakers Used in DC Applications
TR-104513
Prepared by
Eddie L. Davis, Edan Engineering Corp.
Daniel L. Funk, Edan Engineering Corp.
Prepared for
Nuclear Maintenance Applications Center
1300 Harris Boulevard
Charlotte, North Carolina 28262
Operated by
Electric Power Research Institute
3412 Hillview Avenue
Palo Alto, California 94304
EPRI Project Manager
Jim Sharkey
Nuclear Power Division
operated by EPRI
Introduction
This Tech Note investigates and
provides recommendations for
field testing the overcurrent trip
units of low voltage circuit
breakers used in direct current
(DC) applications. Although
industry guidance is available for
field testing low voltage circuit
breakers in alternating current (AC)
applications, guidance for testing
breakers used in DC circuits is
virtually nonexistent.
Fault theory and breaker operating
principles are discussed at a depth
necessary to technically
substantiate recommended
practices contained in this Tech
Note. The response of low voltage
circuit breaker overcurrent trip
units to AC and DC current is
compared to facilitate an
understanding of the issues and
concerns surrounding overcurrent
test methods for low voltage circuit
breakers used in dc applications.
Table of Contents
1.0
2.0
3.0
4.0
5.0
6.0
Scope l
Background l
Comparison of DC to AC Characteristics
in Overcurrent Trip Units
Comparison of DC to AC Ratings of
Low Voltage Circuit Breakers l
Field Testing of Low Voltage Circuit Breakers
for DC Applications
Conclusions and Recommendations l
Bibliography l
Appendix A
3
5
7
17
19
25
27
29
10
Scope
The scope of this document is limited to field testing issues associated with
low voltage circuit breaker used in DC applications. Low voltage circuit
breakers are generally defined as breakers rated for service in systems up to
600 VAC or 250 VDC. There are two main categories - molded case circuit
breakers (MCCBs) and low voltage power circuit breakers (LVPCBs). Both
breaker types are evaluated within the scope of this Tech Note. Breakers
equipped with solid-state trip units are not normally used in DC circuits and
are not discussed.
This Tech Note focuses on overcurrent testing. Accordingly, discussions are
primarily concerned with characterizing the response of low voltage circuit
breaker overcurrent trip units to different levels of DC overcurrent and
explaining how the expected response potentially affects field test methods.
Although other field inspections and tests are recommended for breaker
maintenance programs in addition to overcurrent testing, existing industry
guidance is considered adequate for these other inspections and tests, as
discussed in the Background section.
The discussion in this document is geared toward nuclear power plants.
Nuclear plants operate within strict safety and regulatory criteria and are
required to periodically demonstrate the operability of plant safety
equipment. The technical information presented, however, is applicable to
all low voltage circuit breakers used in DC applications.
An overcurrent test program for DC circuit breakers should consider the
following
Available time-current characteristic curves available from the
manufacturer
Available test equipment - AC or DC test equipment
Type of test - instantaneous or thermal trip unit
Acceptance criteria for the test
This Tech Note addresses the above program elements for the overload trip
test and the instantaneous trip test. It also provides a technical overview of
the differences between AC and DC current effects on MCCBs and LVPCBs.
The emphasis is on MCCBs because of their greater industry use in DC
systems.
20
Background
2.
3.
Little industry effort to resolve the issue due to the limited market for DC
breakers
3.0
Some fully magnetic MCCBs are also capable of providing a time delay trip
function, although this type of design is seldom used for DC applications.
Magnetic forces generated in the breakers coil are concentrated in a movable
iron core. In response to overcurrent, the core is drawn closer to the trip
mechanism armature until the magnetic force on the armature trips the
breaker. The trip time delay is obtained by use of a damping fluid which
slows movement of the iron core. AC and DC current can cause a different
response in this type of trip unit. The response of magnetic trip units is
discussed in the next section.
3.2 MCCB Instantaneous (Magnetic) Trip Units
Magnetic trip units protect against short circuits. They are often called
instantaneous trip units since they are actuated without any intentional time
delay. A magnetic trip unit consists of an electromagnet connected to the
breaker trip bar (see Figure 4). Line current passing through the magnetic
element results in an attractive force on the armature (a movable iron slug).
When a short circuit occurs, the magnetic force generated by the short circuit
current is strong enough to overcome internal spring tension. The armature
then moves and actuates the latch on the breaker trip mechanism. This
tripping action has no intentional built-in time delay; trip actuation is a
function of the short circuit current magnitude.
10
where,
I
2x
11
2)
12
13
14
delay. After this short time delay, the armature moves a lever on the trip
shaft which trips the breaker. Some designs use a mechanical timer or a
secondary armature interlocked with the long-time delay trip unit rather
than a ratchet gear arrangement. The pickup point of this device can usually
be varied from 200% to 1000% of rated current.
The instantaneous overcurrent trip device consists of a trip armature
restrained by a calibration spring and a common series coil. When the
magnetic force produced by an overcurrent condition in the series coil
overcomes the calibration spring force, the armature operates a lever on the
trip shaft which trips the breaker.
A comparison of AC to DC overcurrent response is similar to that described
for MCCB magnetic trip units because the trip elements of LVPCBs are
actuated by magnetic force. Although a time-delay function is included in the
design for LVPCB overcurrent trip units, the sensing element is unlike the
thermal trip unit in an MCCB. For this reason, a LVPCBs response may be
different for AC and DC overcurrents in both the time delay and the
instantaneous trip regions. Manufacturers usually performed extensive
testing of LVPCBs and the associated trip units during their development to
characterize the response to both AC and DC currents. This information is
reflected on the manufacturers time-current curves; they should be reviewed
to determine any variations in response between AC and DC.
LVPCB overcurrent trip units used in DC applications may have design
differences from those used in AC applications, even if the model number for
a given trip unit is the same for either application. In particular, the trip
unit calibration spring and the armature air gap may be adjusted for a DC
application. The net result of this design modification is that the DC
time-current curves may be almost identical in shape to the AC curves. A
review of the AC and DC time-current curves might prompt an interpretation
that the trip response to AC and DC currents is identical. However, the
previous discussion regarding the different response between AC and DC
currents in a magnetic trip unit still applies; in this case, the identical
characteristics possibly shown on the time-current curves was achieved by
varying the design depending on whether the application was AC or DC. The
manufacturer should be contacted to determine any design differences for
overcurrent trip units in AC or DC applications that might affect an
interpretation of the time-current curves. Also, the manufacturer should be
able to provide a DC to AC conversion factor to account for the different trip
response obtained with an AC test current on a DC trip unit.
15
40
Low voltage circuit breakers for DC applications are often identical in design
to standard AC breakers. Breakers designed for AC applications, but used in
DC systems, will generally have a higher continuous current capability
because of the absence of skin effect, hysteresis, and eddy currents. However,
for convenience, the manufacturer may provide the same current rating for
both applications.
The maximum current that a DC breaker can interrupt and the maximum
voltage that can be applied will be less than for an equivalent design AC
breaker because of the nature of DC current. Interruption of DC current is
distinctly different and is usually more difficult than interruption of AC
current at comparable voltages and currents. An AC current interrupter
does not have to develop a large voltage drop across the fault current arc
between the breaker contacts because the sinusoidal current passes through
zero during each half cycle. DC current does not pass through a current zero
and a DC current interrupter must develop an arc voltage drop greater than
the applied circuit voltage while current is flowing to force the fault current
to zero across the contacts. For this reason, the DC breaker must absorb
considerably more energy during the fault clearing process than an
equivalent AC breaker; a given breaker contact and arc chute design will
have a lower DC than AC voltage and current interrupting rating. For
example, a breaker rated for 65,000 RMS symmetrical amperes at 480 VAC
may only be rated for 10,000 amperes at 250 VDC.
17
50
19
20
A test current applied just below the low tolerance limit for the
instantaneous trip might initiate a breaker trip, falsely indicating a
tendency for premature tripping. Per NEMA AB4-1991, the low tolerance
is normally -30% below the minimum instantaneous trip point. Some
nuclear plants test with a smaller tolerance to assure that premature
tripping cannot occur; a smaller tolerance increases the likelihood of a
breaker trip due to asymmetrical test current.
A test current applied at the high tolerance limit is more likely to trip
because of the presence of offset. Thus, the offset might introduce enough
additional magnetic force to trip the breaker when the breaker might not
have otherwise met the acceptance criteria of NEMA AB4-1991 had the
current been only symmetrical.
The DC component of an asymmetrical current decays rapidly and is
generally gone within a few cycles. For this reason, asymmetrical current
will not measurably affect overcurrent testing of time-delay thermal trip
units.
A DC offset in the AC test current may erroneously indicate a potential for
premature instantaneous tripping at the low end and the high end might
inappropriately appear to be acceptable. Because the AC trip response is
related to the DC trip response by a design-dependent conversion factor, any
21
error in the AC test results will also be present in predictions of the DC trip
response.
5.3 DC Overcurrent Testing of MCCBs
Commercially available DC test equipment can provide the necessay DC
current levels to verify the functionality of the thermal and instantaneous
trip units. The accuracy and repeatability of DC test equipment is similar to
that obtained with AC test equipment. The use of DC current to test DC
MCCBs does not guarantee a better correlation between field test results and
the factory calibration data represented by the time-current characteristic
curves. The following variations in field testing can cause differences from
the factory test results:
Rate of rise
Initial overshoot
In the instantaneous region, DC test equipment should deliver current with a
time constant of 8 ms or shorter to meet the criteria established by UL-489,
Molded-Case Circuit Breakers and Circuit-Breaker Enclosures. A longer time
constant may yield results different than the manufacturers predictions.
When testing MCCBs with a DC current source, particular care must be
taken to ensure that the correct time-current characteristic curves are used.
Many MCCBs mainly have AC time-current characteristic curves and
manufacturers provide conversion factors to adjust the instantaneous trip
region for DC applications. As discussed previously, the thermal trip region
usually does not require any adjustment for DC testing since AC RMS
current is equivalent to DC current of the same magnitude.
The manufacturer should be consulted to confirm that the information
provided on the time-current curves is applicable. Not all manufacturers
time-current characteristic tunes readily indicate a difference between AC
and DC in the instantaneous region. For example, one manufacturer
provides the same curves for AC and DC applications; however, another
document must be consulted to determine the correction factor to apply to the
instantaneous region for DC applications. Other manufacturers provide the
conversion information directly on the time-current curves. Also, each
manufacturer may provide a different conversion factor for each MCCB
model and rating, ranging from as low as 10% to as high as 40%.
22
23
6.0
2.
25
6.
7.
26
Bibliography
1.
2.
3.
ANSI C37. 17-1979, American National Standard for Trip Devices for AC
and General Purpose DC Low-Voltage Power Circuit Breakers.
4.
5.
6.
7.
8.
9.
10.
11.
12.
13.
14.
15.
27
16. Square D Company Letter dated March 23, 1994, George Gregory to Eddie
Davis, Molded-Case Circuit Breakers in dc Circuits.
17. Square D Circuit Breaker Application Guide SD390, 9/88, Determining
Current Carrying Capacity in Special Applications.
18.
28
20.
21.
22.
where,
The lower case letters for power and current above indicate that these are the
values at a particular instant in time.
represents the peak value of the
sinusoidal current. The cosine term is present due to the sinusoidal nature of
the current which may be out of phase with the applied voltage by the phase
angle q. In summary, the power delivered at any instant in time by a
sinusoidal AC current can be expressed as
The average power associated with a sinusoidal current is the average of the
instantaneous power over one complete period, T. In equation form, the
average power is expressed by integrating the instantaneous power starting
at some time,
, over a full period,
+ T.
or,
29
Using this identity, the expression for instantaneous AC power is given by:
Returning to the integral relationship for the average power, the second term
in the above expression will integrate to zero since it is symmetrical about
the zero axis over one complete period. Thus, the average power in a
sinusoidal circuit is given by
or
30
31
ABOUT EPRI
The mission of the Electric Power Research Institute is to discover, develop, and deliver advances in
science and technology for the benefit of member utilities, their customers and society.
Funded through annual membership dues from some 700 member utilities, EPRIs work covers a wide
range of technologies related to the generation, delivery, and use of electricity, with special attention
paid to cost-effectiveness and environmental concerns. At EPRIs headquarters in Palo Alto, California,
more than 350 scientists and engineers manage some 1600 ongoing projects throughout the world.
Benefits accrue in the form of products, services, and information for direct application by the electric
utility industry and its customers.
EPRILeadership in Science and Technology
BY OPENING THIS SEALED REPORT YOU ARE AGREEING TO THE TERMS OF THIS AGREEMENT. IF YOU DO NOT AGREE TO THE TERMS OF THIS AGREEMENT, PROMPTLY RETURN
THE UNOPENED REPORT TO EPRI AND THE PURCHASE PRICE WILL BE REFUNDED.
1. GRANT OF LICENSE
EPRI grants you the non-exclusive and nontransferable right during the term of this agreement to use
this report only for your own benefit and the benefit of your organization. This means that the following
may use this report: (I) your company (at any site owned or operated by your company);(II) its subsidiaries
or other related entities; and (III) a consultant to your company or related entities, if the consultant has
entered into a contract agreeing not to disclose the report outside of its organization or to use the report
for its won benefit or the benefit of any party other than your company. This shrink-wrap license
agreement is subordinate to the terms of the Master Utility License Agreement between most U.S. EPRI
member utilities and EPRI. Any EPRI member utility that does not have a Master Utility License
Agreement may get one on request.
2. COPYRIGHT
This report, including the information contained in it, is owned by EPRI and is protected by United States
and international copyright laws. You may not, without the prior written permission of EPRI, reproduce,
translate or modify this report, in any form, in whole or in part, or prepare any derivative work based on
this report.
3. RESTRICTIONS
You may not rent, lease, license, disclose or give this report to any person or organization, or use the
information contained in this report, for the benefit of any third party or for any purpose other than as
specified above unless such use is with the prior written permission of EPRI. You agree to take all
reasonable steps to prevent unauthorized disclosure or use of this report. Except as specified above,
this agreement does not grant you any right to patents, copyrights, trade secrets, trade names,
trademarks or any other intellectual property, rights or licenses in respect of this report.
4. TERM AND TERMINATION
This license and this agreement are effective until terminated. You may terminate them at any time by
destroying this report. EPRI has the right to terminate the license and this agreement immediately if you
fail to comply with any term or condition of this agreement. Upon any termination you may destroy this
report, but all obligations of nondisclosure will remain in effect.
5. DISCLAIMER OF WARRANTIES AND LIMITATION OF LIABILITIES
NEITHER EPRI, ANY MEMBER OF EPRI, ANY COSPONSOR, NOR ANY PERSON OR ORGANIZATION ACTING ON BEHALF OF ANY OF THEM:
(A) MAKES ANY WARRANTY OR REPRESENTATION WHATSOEVER, EXPRESS OR IMPLIED, (I)
WITH RESPECT TO THE USE OF ANY INFORMATION, APPARATUS, METHOD, PROCESS OR
SIMILAR ITEM DISCLOSED IN THIS REPORT, INCLUDING MERCHANTABILITY AND FITNESS FOR
A PARTICULAR PURPOSE, OR (II) THAT SUCH USE DOES NOT INFRINGE ON OR INTERFERE
WITH PRIVATELY OWNED RIGHTS, INCLUDING ANY PARTYS INTELLECTUAL PROPERTY, OR
(Ill) THAT THIS REPORT IS SUITABLE TO ANY PARTICULAR USERS CIRCUMSTANCE; OR
(B) ASSUMES RESPONSIBILllY FOR ANY DAMAGES OR OTHER LIABILITY WHATSOEVER
(INCLUDING ANY CONSEQUENTIAL DAMAGES, EVEN IF EPRI OR ANY EPRI REPRESENTATIVE
HAS BEEN ADVISED OF THE POSSIBILITY OF SUCH DAMAGES) RESULTING FROM YOUR
SELECTION OR USE OF THIS REPORT OR ANY INFORMATION, APPARATUS, METHOD, PROCESS OR SIMILAR ITEM DISCLOSED IN THIS REPORT.
6. EXPORT
The laws and regulations of the United States restrict the export and re-export of any portion of this
report, and you agree not to export or re-export this report or any related technical data in any form
without the appropriate United States and foreign government approvals.
7. CHOICE OF LAW
This agreement will be governed by the laws of the State of California as applied to transactions taking
place entirely in California between California residents.
8. INTEGRATION
You have read and understand this agreement, and acknowledge that it is the final, complete and
exclusive agreement between you and EPRI concerning its subject matter, superseding any prior related
understanding or agreement. No waiver, variation or different terms of this agreement will be enforceable
against EPRI unless EPRI gives its prior written consent, signed by an officer of EPRI.