FMP 16.

48
Rectifier Module

Description
The Power-One FMP 16.48 rectifier provides
extremely reliable DC power in the highest
possible density. The module incorporates the
latest in power monitoring solutions through an
internal microprocessor giving up to the second
updates to the system controller and adjacent
rectifiers. This guarantees tightly controlled
load sharing among rectifiers and provides
status and identification information to the
controller.
At only four rack units high, these compact
rectifiers provide up to 1600W and allow up to
ten rectifier modules in a 23in. subrack or eight
modules in a 19in. subrack. Designed with
diversity in mind, the FMP 16.48 rectifier is able
to operate in a complete range of indoor and
outdoor applications.

Features

23in. PPR 16
Subrack

Compact 4 rack unit height


717 W/L (11.75 W/in2)
208/240 single phase input
Input overvoltage disconnection
Thermal protection
Hot-swappable
No adjustments required
93,5% typical efficiency
Active and droop current sharing
International Standards Compliance

www.power-one.com

FMP 16.48
Rectifier Module
Input

Mechanical

Model

FMP 16.48

Input Voltage

100-240V AC 15% single phase


(44-66Hz)
(185-85V at de-rated output power)

Current (max.)

<10A

Soft Start

<13A/1ms

Harmonics

EN 61000-3-2
(Power factor > 0.98 typical)

Surge
Immunity

EN 61000-4-5

Fuse

2 x F 12.5A (line & neutral)

Connection

FCI 51939-066

EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15 Class B

(WxHxD)

51 x 177 x 280mm
(2.0 x 6.97 x 11.02in.)

Weight

2.2kg (4.85 lbs.)

Cooling

Fan cooled (front to back), speed


controlled and alarmed

Insulation

Reinforced insulation, tested at:


4.25 KV DC primary-secondary
2.12 KV DC primary-ground
0.75 KV DC secondary-ground

Enclosure

IP20

Mounting

19in./ 4U subrack up to 8 modules


23in./ 4U subrack up to 10 modules

Dimensions

Other Technical Data


Safety

EN 60950
UL 1950 and IEC60950
CSA C22-2 No. 950

Protection

Short circuit proof, automatic current


limiting, selective shutdown of
modules at excessive output voltage.
Thermal protection reduces the
output power at environmental
temperatures above maximum level.
Shut down at >75C with an
automatic restart*. Input over-voltage
disconnecting at >275 VAC with
automatic reset at >260VAC.

Alarms

High output voltage/ shutdown, Low


voltage/ module failure. Each alarm
has an LED indicator on the front
panel.

Output
Model

FMP 16.48

Output Voltage

45-56VDC

Power (max.)

1600W @ 50-56V DC
(input >185V AC)
675W @ 50-56V DC
(input 185 - 85V AC)

Current (max.)

32A

Efficiency
(at 40-90% load)

>93%, typical 93,5%

Tolerance

Vout +/- 1.0%,

Transient
Response

+/- 5% at load variation


10-90% or 90-10%,
recovery time 50ms

Load Sharing

<5% of nominal current

Ripple

<100mV p-p (BW. 30Mhz)

Psophometric

<2mV, according to CCITT


norms

Connection

FCI 51939-066

EMC

EN 61000-6-2, EN 61000-6-4

Note: All specifications are subject to change without notification.

Green LED

Power ON

Yellow LED

Current limit/ thermal


protection. Com.
failure (flashing)

Red LED

Module failure/ high


output voltage/
shutdown

Indications

Audible
Noise

<60dBA

Operating
Temperature

-40 to +65C up to 2000m


-40 to +55C above 2000m

Storage
Temperature

-60 to +85C

Radiated EMC

EN 61000-6-2, EN 61000-6-3,
FCC Part 15, Class B

Environment

Storage:
Transport:
Operation
Earthquake

ETS 300 019-2-1


ETS 300 019-2-2
ETS 300 019-2-3
GR 63 Core Zone 4

*Average performance for a single module.

11V0005-041 FMP 16 V3.0 Rev. B