Functional Safety and Explosion Protection
Functional Safety and Explosion Protection
Functional Safety and Explosion Protection
Functional Safety
and Explosion Protection
Fundamentals of Functional Safety in Accordance with IEC 61508 and
how it is Linked to Applications in Hazardous Areas
by Andr Fritsch
Ex-Magazine 2005
Who invented it ?
How did Functional Safety arise? One
should assume that safety of personnel does
not require specific legislation but, rather, is
in the interests of the user and should be
handled as a high priority. Unfortunately, this
is not always the case and, as has frequently
occurred in history, action is taken only after
an actual incident. This happened approximately 29 years ago on July 10, 1976, in
Seveso, northern Italy. A toxic gas accident
released highly toxic dioxin (TCDD), triggered
by an uncontrolled overheating reaction
whose excess pressure destroyed a plant
safeguard. The reactor in question featured
no automatic cooling systems whatsoever.
There were neither warning systems nor
alarm plans in the installation. The population
was informed 9 days later. Fortunately, there
were no specialist personnel in the plant
when the incident occurred and, by chance,
the quantity of toxic substance released was
limited. Nevertheless, approx. 2 kg of highly
toxic dioxin was released into the environment and caused illness, death of animals,
and serious environmental pollution.
As a consequence of this accident it was
decided to tighten up legislation and ordinances aimed at protecting humans, living
organisms and the environment.
The European Community published the
Seveso I Directive in the 1980s and later the
Seveso II Directive 96/82/EC on the control
of major-accident hazards involving dangerous substances.
In Germany for instance, this Directive
was adopted in national law with reference
to DIN V 19250. This Standard also included a
definition of the Requirement Classes AK 1-8
used internationally.
IEC 61508 Functional Safety of SafetyRelated Electrically/Electronically Program-
34 | 35
Technical jargon?
If we consider the topic of Functional
Safety in greater detail and if, for instance,
we read a corresponding test report, we
quickly encounter certain terms and abbreviations that are far from self-explanatory.
Consequently, we shall discuss the terminology and technical expressions which are
essential for understanding the topic in brief
below.
Let us start with a definition of terms
which are frequently confused and misinterpreted: safety and availability. The essential
difference can quickly be seen on the basis
of an everyday example. A railway crossing
is safeguarded with a barrier so that, when a
train approaches, a vehicle cannot drive over
the tracks at the same time. The two possible
error sources in this example are the nonopening and non-closing of the barrier. If
the barrier no longer opens after the train has
passed, the availability of the road is no
longer guaranteed. A parallel crossing, for
instance would remedy the situation in this
case as the probability of this barrier not
opening is extremely low. Of course, this must
be strictly rejected on the basis of safety
aspects since the error probability of nonclosing is doubled from two to four barriers.
Here, it is far better if we construct two
barriers, one behind the other, in order to
intercept an error if one of the four barriers
does not close. However, in turn, this counteracts availability. How do we find a solution
which avoids this dilemma and enhances
both safety and availability? There is more
than one solution, such as an overpass, but
all these solutions have one thing in common:
higher costs. We should not lose sight of the
cost aspect in all applications and measures
intended to enhance safety and/or availability.
Protection
equipment
Installation risk
reduction
SIL 1
10 ... 100
SIL 2
SIL 3
SIL 4
IEC 61511
DIN V 19250
VDI/VDE 2180
SIL 1
AK1
Risk area I
(low risk)
AK2
Table 2:
Relationship between
IEC 61511, DIN V 19250
and VDI/VDE 2180
(source:
IEC 61511-3; Annex E)
AK3
SIL 2
AK4
SIL 3
AK5
AK6
SIL 4
AK7
AK8
Risk area II
(high risk)
Not covered by PCS protection
equipment alone
Ex-Magazine 2005
Fault types
Non-fatal faults
Hazardous faults
Recognised faults
sd (= safe detected)
dd (= dangerous detected)
Unrecognised faults
su (= safe undetected)
du (= dangerous undetected)
Faults of components
which are not a part of the
protection system
np (= not part)
PFDa
Fault if system is needed;
low demand Systeme
SIL
SIL 1
SIL 2
SIL 3
SIL 4
36 | 37
1 / 01)
2 / 11)
< 60%
SIL 1
SIL 2
SIL 3
60 ... 90%
SIL 2
SIL 3
SIL 4
90 ... 99%
SIL 3
SIL 4
SIL 4
> 99%
SIL 3
SIL 4
SIL 4
1 / 01)
2 / 11)
< 60%
SIL 1
SIL 2
60 ... 90%
SIL 1
SIL 2
SIL 3
90 ... 99%
SIL 2
SIL 3
SIL 4
> 99%
SIL 3
SIL 4
SIL 4
Table 5: Interrelationship
between SFF and HFT on
simple devices (Type A)
01) or 11) in the case of
verification of proven
operation effectiveness
in accordance with IEC
61511
Table 6: Interrelationship
between SFF and HFT
in the case of more
complex devices (Typ B)
01) or 11) in the case of
verfification of proven
operational effectiveness
in accordance with
IEC 61511
Ex-Magazine 2005
W3
W2
W1
SIL 1
SIL 1
SIL 1
SIL 2
SIL 1
SIL 1
C1
P1
C = extent of damage
C1: slight injury
C2: serious irreversible injury to one or more
persons, or death of a person
C3: death of several persons
C4: catastrophic consequences many fatalities
38 | 39
Remarks:
SIL 4 cannot be
achieved with one
item of safety
equipment alone
F1
P2
C2
P1
F2
Start
P2
F1
SIL 3
SIL 2
SIL 1
SIL 3
SIL 3
SIL 2
SIL 4
SIL 3
SIL 3
SIL 4
SIL 4
SIL 3
C3
F2
C4
Figure 2: Risk graph for injury to persons in accordance with IEC 61508/61511
Figure 3: IS pac Ex i
isolator system for SIL 2
and SIL 3 applications
might initially be seen as annoying paperwork does, however, assist in designing new
safety circuits. If a safety system has been in
use for several years and if no or only a few
safety-critical faults have occurred during
this time, it is also possible to upgrade the
SIL for this application using the argumentation of proven in use. We should also point
out that a subsequent change in the result of
the conducted risk analysis is not recommended for downgrading the required SIL.
After all, the analysis was conducted to the
best of the knowledge and ability of the
analyst. If there have been no real changes
in the installation there is no logical reason
Manufacturer
Note
SILence
HIMA
SILver
EXIDA
Internet application
TRAC
ABB
TRAMS
ABB
for documentation
Table 8: Selection of
available software tools
with device databases
Ex-Magazine 2005
for safety circuits for the required safety level. Thus, for instance, while a value of 5 10-3
suffices for an SIL 2, only a maximum of 5 10-4
of this should be attributable to the corresponding isolator. Figure 4 shows how the
typical distribution of the failure probabilities
in a safety function with isolators should
look.
If this is not possible or if no corresponding isolator is available, one remaining alternative is redundancy, as already described
above. One other alternative consists in
using additional diagnostics. One interesting
solution in this case is the HART communication signal which supplies a wide variety
of parameters that can also be used for
early detection of faults, among other uses.
Special HART Management Systems, for
example, which read in and evaluate the
HART signals collectively via a HART multiplexer are available for evaluation of the
HART information. The HART multiplexer
must, of course, also have SIL assessment
since it does, after all, intervene in the safety
circuit and could falsify the relevant analogue process signals (Figure 5). Consequently, the SIL assessment of the HART
multiplexers does not include use of the
HART information for control and monitoring
of the safety chain but, rather, a verification
that the HART multiplexer has no safetyrelated influence on the analogue signal.
Modern bus technology has been used to
an increasing extent in recent years on many
new installations. Solution concepts and
products are also available for configuring
safety systems. Bus protocols configured
specifically for safety applications include
PROFISafe or INTERBUS-Safety. Universal
usability and, thus, acceptance does, however, frequently fail owing to the narrow
selection of field devices available for this.
In this case, Remote I/O Technology offers
40 | 41
more selection options. Conventional analogue field devices with SIL classification
can be operated easily on the Remote I/O.
However, the most important requirement for
this is, of course, that the Remote I/O System
also be assessed on the basis of the SIL
criteria. The only system currently on the
market, R. STAHLs Remote I/O System IS1,
complies with the requirements of SIL 1
(Figure 6).
In order to prevent users from having to
deal with the relatively complex structure
of this safety function, it is advisable to consider the overall system as one component.
On IS1, the fieldbus isolating repeaters for
the intrinsically safe Profibus DP (Profibus
RS485-IS), the intrinsically safe Profibus DP
itself, the CPU module of the system and the
analogue and digital input/output modules
are allowed for jointly in the SIL assessment,
i.e. the user can take only one value for
the failure probability of his or her safety
function, and then add the corresponding
values of the field devices and the automation system to this. Unfortunately, only a
few automation systems with SIL assessment
have been available to date. Consequently,
an empirical value of 0.001 for the failure
probability is taken in practice when designing systems without SIL.
control
15%
actuator and
isolator 2
actuator and
50%
isolator 1
35%
Figure 5: HART multiplexer with HART connector circuit board for applications up to SIL 3
Ex-Magazine 2005
Bibliography
1. Council Directive 96/82/EC of 9 December 1996 on the control of major-accident hazards involving
dangerous substances (SEVESO II)
Official Journal of the European Communities 1996
2. DIN V 19250 Grundlegende Sicherheitsbetrachtung fr MSR-Schutzeinrichtungen
(Fundamental Safety Consideration for Control and Instrumentation System Safety Facilities)
(withdrawn on 31 July 2004)
3. IEC 61508:1998 Functional safety of electrical/electronical/programmable electronic safety related
systems Part 1 Part 6
4. IEC 61511 12/2003 Functional safety-Safety instrumented systems for the process industry sector
5. IEC 62061 (2005-01) Safety of machinery Functional safety of safety-related electrical,
electronical and programmable electronic control systems
6. Siemens Safety Integrated Safety Systems Application Manual, available at www.siemens.de/safety
7. Homepage of the IEC (FAQ lists and brochures etc.) available at http://www.iec.ch/zone/fsafety
8. Homepage of the EXIDA company www.exida.com with information publications, specialist articles
and specialist literature
42 | 43