How To Solve Short Circuit Calculation Using Point To Point Method PDF
How To Solve Short Circuit Calculation Using Point To Point Method PDF
com
http://electricalengineering-access.blogspot.com/2015/03/introduction-point-to-point-method-of.html
Introduction
Point to point method of short circuit calculation is one of the basic method in finding the short circuit current.
Before an engineer use a computer software to determine short circuit current it is recommended that he needs to
understand the basic principle and know how to do the manual calculation.
Before we begin the short circuit analysis let us first familiarize the important formula, viz:
2. f - factor (the impedance of the cable or busbar between two points where the fault is
calculated)
f = 2 x L x Isc-x / ( C x n x VLL) , for single phase installation
f = 1.73 x L x Isc-x / ( C x n x VLL), for three phase installation
where:
f = f - factor
L = length of the conductor relative to the immediate upstream fault point.
Isc-x = fault current at any point in the circuit.
C = conductor factor and the values are given in the table below.
n = number of parallel run of conductor.
VLL = Line to line voltage
3. M- factor (Multiplier to be used against the value of the fault current in the immediate
fault point)
M = 1/ (1 +f )
The 0.9 exist in the equation since the transformer has +/- 10% tolerance and we take the negative value
so that we can take the maximum fault current. Take note that the lesser the impedance the higher the fault
current.
If the tolerance is +/- 5% then the factor that will appear in our equation will be 0.95.
Fault at Point 2:
Point 2 has 400 ft. length conductor with 2 conductor per phase. We can apply formula number 3 and 4 at this
point, thus:
f = 1.73 x L x Isc-x / ( C x n x VLL), for three phase installation
In this case we can use conductor factor C = 22, 965 based on the following data
Therefore,
f = (1.73 x 400ft x 16.7 kA) / (22, 965 x 2 x 480) = 0.524
M = 1 + (1 + f ) = 1 / 1.524 = 0.66
Isc-2 = M x Isc-1 = 0.66 x 16.7 kA
Isc-2 = 11 kA
Fault at Point 3:
Again we will use the same process and refer to the table given above for the value of conductor factor C.
f = (1.73 x 500 ft. x 11 kA) / (16, 673 x 1 x 480) = 0.476
M = 1 / 1.476
Isc-3 = M x Isc-2 = 0.68 x 11 kA
Isc-3 = 7.48 kA
Fault Point 4:
In fault point 4 we can use the same process but we need to add the locked rotor current (LRA)of the motor during
fault condition.
Why we need to add the motor LRA?
During fault condition the motor whether it is synchronous or induction motor, it will
contribute electric current to the fault point.
During fault condition the supply voltage of the motor will be tend to approach the value of
zero and since the rotor still have the effect of inertia (will not stop abruptly), thus it will
continue to rotate momentarily right after the fault happen.
The momentary rotation together with the induced voltage developed in the rotor just before
the fault happened will transform the motor into a generator.
In case of induction motors this scenario will continue until the magnetic flux in the rotor
disappear since there is no permanent supply voltage in the rotor of the induction motor.
Worst case in part of the synchronous motor since the rotor has separate and steady supply,
thus the effect of the "motor to generator" transformation will take longer until the rotor stop
rotating.
The value of the current that the motor can contribute during fault condition is equal to the
locked rotor current LRA of that motor which is equal to 400% to 600% of the full load
amperes of that motor.
In this case the motor is rated 20 HP, operating at 480 Volts, thus:
FLA = (20 HP x 746) / (1.73 x 480 x 0.85 x 0.8) = 26 Amperes
LRA = 26 x 600% = 158 Amperes
The value of LRA is the contribution of the motor to the fault current during fault condition.
The effect of LRA during fault condition based on the rating of the motor, thus we can say that large motors
have significant effect on the system during fault condition.
Calculate the fault current at point 4,
f = (1.73 x 200 x 11 kA) / ( 20, 867 x 1 x 480) = 0.38
M = 1 / 1.38 = 0.72
Isc-4 = (M x Isc-2) + LRA = (0.72 x 11 kA) + 158 = 8, 078 Amperes or 8.1 kA
Isc-4 = 8.1 kA
Summary of Results:
Short Circuit Current at Point 1 = 16.7 kA
Short Circuit Current at Point 2 = 11 kA
Short Circuit Current at Point 3 = 7.48 kA
Short Circuit Current at Point 4 = 8.41 kA
These data are three phase symmetrical short circuit current values. This is a value where we presume that the
fault happened because all the three phase are connected or bolted together.
What if the fault happened is not a symmetrical three phase fault (Phase to Phase to Phase fault)? We can
consider the following rule of the thumb to compute the following faults:
Phase to Phase (two lines are connected) = use 87% x 3 ph. symmetrical fault current.
Phase to ground (one line and ground are connected) = 25% x 3 ph. symmetrical fault current.
Thus,
References:
Schneider Electric Cahier no. 158
General Electric
Cooper Busman