Short Circuit Calculations
Short Circuit Calculations
by R.A.Deshpande,
Main : Graphs
150
100
50
0
-50
-100
-150
150
100
50
0
-50
-100
-150
0.080
voltage
current
0.100
0.120
0.140
0.160
0.180
0.200
0.220
0.1 [H]
RRL
Fault
Main : Graphs
150
100
50
0
-50
-100
-150
current
100
voltage
-60
0.075
0.100 0.125
0.150 0.175
0.200
0.225 0.250
0.275 0.300
0.325
Main : Graphs
150
100
50
0
-50
-100
-150
current
100
voltage
-60
0.075
0.100
0.125
0.150
0.175
0.200
0.225
0.250
0.275
0.300
0.325
Short-circuit Current
i(t) = Vmax
Z
{ sin ( t + )
- sin ( -). e t*(R/L) }
= tan-1 (L/R)
= angle at the instance when fault
occurs
Short-circuit Current
Case a : - = 0
Symmetrical current
Case b: - = /2
Asymmetrical current
Generators
Power Utility grid
Power Transformer
Cables & Conductors
Motors
Calculation Methods
MVA Method
Impedance Method
1500 MVA
33 kV
R=0
1500/1
544.5
33 x 33/2.0
200
20/0.10
C1
1500
Line
2.0 ohms
#1
Fault
Fault
R=0
#2
20 MVA
33/11 kV, 10%
15 MVA
Xd = 0.2
75
15/0.2
Impedance Method
Z grid = 33 * 33 / 1500 = 0.726 ohms
Z line = 2 ohms
Z tfr = 0.1 * 33 * 33 /20 = 5.445 ohms
Z total = 8.171 ohms
Converted to 11 kV side Z total = 8.171/9
= 0.908 ohms
Z motor = 0.2 * 11 * 11 /15 = 1.613 ohms
Impedance Method
Total impedance = 0.581 ohms
I sc = 11 / (3 * 0.581)
= 10.93 kA rms
Z can be replaced with R+jX , then
I sc peak = 2 * Isc rms * ( 1 + e /(X/R))
Classification of faults
Classification of faults
The first three types of fault are
asymmetrical fault
The last two types of fault are
symmetrical fault
Unsymmetrical faults
Sequence impedance called as positive
sequence, negative sequence and zero
sequence are used for short-circuit calculation
These sequence impedances are designated
as Z1, Z2 and Z0
Unsymmetrical faults
Generated voltages are of positive
sequence only
positive sequence network : voltage source
in series with +ve seq impedance
Overhead line circuits and cables: +ve & -ve
seq impedances are equal
following ratio may be used as
guideline if actual values are not known
Unsymmetrical faults
Z0 /Z1 =2 when no earth wire present
Z0 /Z1 =3.5 when earth wire present
Z0 /Z1 =5.5 for double circuit line
Z0 /Z1 = 1 ~ 1.25 for single core cable
Z0 /Z1 = 3 ~ 5
Unsymmetrical faults
Transformers : Z1= Z2
Z0 depends on connection
Fault
R=0
B
Va = 0 ; Ib = Ic = 0
Ia1 = Ia2 = Iao
Ia1= V/( Z1+Z2+Z0)
Fault
R=0
B
Ia = 0 ; Ib = - Ic
Vb= Vc
Va1 = Va2
Ia1= V/( Z1+Z2)
Ia1= -Ia2
Ia0 = 0 so Ia1+Ia2+Iao = 0
Ib= -Ic = a2 Ia1+aIa2+Iao
Fault
C
R=0
B
Ia = 0 ; Ib = - Ic
Vb= Vc = 0
Va1 = Va2 = Va0
Ia1= V/( Z1+Z2 Z0/ (Z2+Z0))
Ia1= -Ia2
Ia0 = 0 so Ia1+Ia2+Iao = 0
Ib= -Ic = a2 Ia1+aIa2+Iao
Important points
Important points
Sometimes it may be necessary to
determine both the resistance and
reactance component, say for designing
distance protection scheme. Whereas the
magnitude of short-circuit current is
sufficient for over current protection scheme.
If the resistance component is less than 0.3
times reactance component, the calculations
can be made by taking only reactance.
Important points
When the short-circuit currents are
calculated, the load currents in the circuit
prior to short-circuit are neglected, the line is
considered to be unloaded.
**
NODES
NODE01 UB=400 AREA=1
NODE02 UB=400 AREA=1
END
LINES
NODE01 NODE02 NO=1 TYPE=12 R=0.00115 X=0.01734
B=0.6438
NODE01 NODE03 NO=1 TYPE=12 R=0.00525 X=0.08290
B=3.293
END
TRANSFORMERS
NODE04 NODE14 SN=1000 UN1=400 UN2=220 ER12=0.001
EX12=0.05
NODE12 NODE15 SN=1000 UN1=400 UN2=220 ER12=0.001
EX12=0.05
END
SHUNT IMPEDANCES
NODE02 Q=300 UN=400
END
1
1
0
0.000 KV
PHASE
PHASE
PHASE
PHASE
2.316 KA
2.637 KA
1.113 KA
6.047 KA
NODE04
NODE04
NODE04
NODE12
NODE05
NODE14
1
2
1
1
1
0
126.590 KV
PHASE
PHASE
PHASE
PHASE
PHASE
PHASE
PHASE
1.180 KA
1.180 KA
0.734 KA
2.264 KA
0.555 KA
1.304 KA
0.373 KA