Basics of SC
Basics of SC
The program calculates the total short circuit currents as well as the
contributions of individual motors, generators, and utility ties or various
circuits in the system.
Fault duties are usually in compliance with the latest editions of the
ANSI/IEEE Standards (C37 series) and IEC Standards (IEC 60909 and
others).
• 3 Phase Fault Device Duty :- This study calculates at all specified bus
the following
ETAP calculates and checks the protective device rated making and
breaking capacities against the actual system fault currents and flags in
RED all inadequate devices.
• LLL, LG, LL-G & LL Fault As Per IEC 60909 Calculation:- This study
performs line-to-ground, line-to-line, line-to-line-to-ground, and three-
phase fault studies per IEC 60909 Standard.
1 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
Using this module the software plots the decay of AC symmetrical rms
fault current wave with respect to time, the DC decay with respect to time
etc.
Td” & Td’ are = Subtransient & Transient short circuit time
constant in seconds
DC decay in both IEC uses the fault circuits equivalent time constant
-t/Tau
Τau = (X/R of circuit) / (2.π.f) where Idc(t) = √2.I”k.e
2 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
3 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
4 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
5 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
Where:-
• C is Voltage factor
Note that with transformer primary side tap set at higher than nominal value
the fault current on secondary increases at compared to its value at nominal
value. On the other hand with transformer primary side tap set at lower than
nominal value the fault current on secondary decreases at compared to its
value at nominal value
C is Voltage factor thus accounts for tap and voltage variation in operation of
the plant. In IEC all fault currents are calculated at nominal voltages and
nominal transformer taps. With fault currents multiplied by Voltage Factor “c”
to account for variation in voltage or tap setting that results in maximum fault
current.
VOLTAGE FACTOR C
This is the factor used to adjust the value of the equivalent voltage source for
minimum and maximum current calculations according to the following table:
6 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
Ip = √2 . k. I”k
Hence IEC Standards provide three methods for calculating the k factor:
• Method B - R/X ratio at the short circuit location. The value of the k
factor is determined by multiplying the k factor by a safety factor of
1.15, which covers inaccuracies caused after obtaining the R/X
ratio from a network reduction with complex impedances.
In all other cases, the short circuit contributions are considered as from a
meshed network.
7 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
Ib = I”k
8 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
where µ and q are factors that account for AC decay. They are functions of
the ratio of the minimum time delay and the ratio of the machine’s initial short
circuit current to its rated current, as well as real power per pair of poles of
asynchronous machines.
The DC component of the short circuit current for the minimum delay time of a
protective device is calculated based on initial symmetrical short circuit
current and system X/R ratio:
–tmin/Τau
Idc (tmin) = √2 x Iac rms x e
where f is the system frequency, tmin is the minimum delay time of the
protective device under concern, and X/R is the system value at the faulted
bus.
The asymmetrical short circuit breaking current for comparison with circuit
breaker rating is calculated as the rms value of symmetrical and DC
components of the short circuit current.
Ikmax = λmax.IrG
Ikmin = λmin.IrG
9 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
Depending on the Rotor type, the IEC Exciter Type is used for determining
the ëmax factor for generators in the calculation of steady-state short-circuit
currents per IEC Standard 909. λmax is proportional to µfmax, which takes
different values based on exciter types as shown in the following table.
10 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
90 Deg or
t=1/2 cycle
0 deg Voltage
Wave
Voltage Zero Axis
t=0
Current Wave
(90 Deg Lag) 90 Deg
0 deg
Current & Voltage
Zero Axis
t=0
Iac-p=
Sqrt(2)xIac rms
11 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
When Voltage & Current Axis are same, the instantaneous value of
current is not zero but negative peak value because the current lags
voltage by 90 degree if the circuit impedance Z is purely inductive.
The shift in current axis from voltage reference zero axis is representative
of the dc component of the fault current.
If both Ac & DC fault current are assumed not to hace decay then the
maximum instantaneous value of fault current occurs at ½ cycle i.e 10
msec after the zero point of the voltage way . The instantaneous value of
this maximum current is called the peak fault making current or
momentary current. The peak making fault current with non decaying AC
& DC fault components = Iac-p+Idc= √2 x Iac rms + √2 x Iac rms =
2 x √2 x Iac rms
12 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
X/R is easily derived from circuit X & R values, and the expression of Τ =
TAU in terms of X/R is Τ = L/R = 2 π f *L / 2 π f * R = (X/R)/ 2 π f
i.e Τ = (X/R)/ 2 π f
If Iac rms is assumed not to decay and if Idc decay due to system X/R
ratio, then the decay of Idc with respect to time =
–t/Τau )=
Idc (t) = Idc (t=0) x e , But Idc (t=0 Iac-p= √2 x Iac rms
–t/Τau
Hence Idc (t) = √2 x Iac rms x e
With Fault Source Circuit X/R =14, Τ = Τau = (X/R)/ 2 π f = 14/314.2 (if
frequency = f =50 Hz)
With X/R = 14, Τau = 0.0445761 second ( 0r 44.576 milli-sec)
13 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
Thus peak fault making current factor = 2.54 (usually rounded off to 2.5)
14 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
3.1 General
The IEC 60909 standard entitled" short circuit current calculation in three-
phase AC systems " provides very conservative results as per the objective of
the standard set out in its Clause 2.0, which is to establish a general,
practicable and concise procedure leading to conservative results with
sufficient accuracy.
3.2.1 General
The HV switchgear ratings are as per IEC-61227 (which replaces old IEC
60056). These are based on Figure 8 of IEC-60056 (i.e. the figure for
"Determination of short-circuit making & breaking currents, and of percentage
D.C. component"); and based on Figure 9 of IEC-60056 (i.e. figure for
"Percentage D.C. component in relation to time interval t"). These figures
have been based on the following considerations, which needs to be
assessed for the HV switchgear rating selection:-
• The fault inception occurs at the zero point of AC sine wave of system
voltage, which results in a maximum offset of the resulting fault current.
See Figure-1 For Details. Also Refer Calculation on last page that shall
form part of Figure 1 for calculation of
• peak fault making current i.e the maximum instantaneous fault
current occurring at ½ cycle or 10 miilisec in 50 HZ system.
–10/Τau in milli-sec
I peak at t=10 millisec = √2 x Ik ‘’ ( 1 + e )
15 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
2 2
I asymm (t) in rms = Sqrt [ (Iac sym rms(t)) + Idc(t) ]
• The fault is remote from the generation, and hence AC component of fault
is essentially constant. The D.C. component time constant is determined
by the X/R ratio, with a value of 44.5 milli-second( i.e L/R), which is
equivalent to source X/R ratio of 14 at 50 Hz or a equivalent X/R value of
16.8 at 60 Hz..
16 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
The LV 415 V circuit breakers / switchgear have been based on the use of air
break magnetic type Air Circuit breakers or MCCBs. For 415 V switchgear /
circuit breakers, IEC 439 & IEC 947 applies and accordingly the LV circuit
breaker should have the ability to make on to a peak fault current equivalent
to the following multiple of their symmetrical break capacity.
3.2.2 Criteria used in the study for assessing the adequacy of the switchgear
by comparing evaluated fault current with the corresponding switchgear
fault ratings.
• The peak fault make, symmetrical fault break and asymmetrical fault
break ratings evaluated at the switchgear exceeds by a margin of 5.0 %
over the corresponding switchgear peak, symmetrical break and
asymmetrical break fault levels evaluated using IEC 909.
17 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
• The source system time constant (or equivalent X/R ratio) evaluated at
the HV switchgear is less than the IEC standard of 44.5 milli-sec (i.e X/R
ratio < 14 at 50 Hz) against which the circuit breakers i.e. HV circuit
breakers are normally tested as a standard. With source system time
constant at the HV switchgear less than 44.5 milli-sec (i.e X/R ratio 14 at
50 Hz as per IEC), the peak make fault current would not exceed its rating
provided the calculated initial symmetrical fault current (Ik") is less than
the breaker symmetrical fault rating [(Ib or Iac (rms)].
• For LV Air Break Circuit breakers / MCCBs, the peak & symmetrical fault
ratings are related based on source system time constant or power factor
and fault levels as given in Table in Section 5.2 B of the report.
18 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
19 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
20 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
21 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
22 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
23 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
24 of 25
Nandakumar
FAULT CURRENT CALCULATION NOTES
25 of 25
Nandakumar