Where :
Ib = Base current or load current (A)
L = cable length (m)
Cable Vd factor and we get it from the tables below
Life Safety and central Battery system
The voltage drop on any branch circuit shall not exceed 3 % and
the accumulated V.D % = 5 % according to NEC
Accumulated V.D % = 2.5 % according to Egyptian , KAHRAMAA
and (MEW) Kuwait codes
Accumulated V.D % = 5 % according to DPS
Accumulated V.D % = 4 % according to ADDC and DEWA
Life Safety and central Battery system
NEC-210.19
Life Safety and central Battery system
KAHRAMAA-604
Life Safety and central Battery system
POWER SYSTEM
DESIGN
Short Circuit
Calculations
Life Safety and central Battery system
Where:
Ztr = Actual ohmic impedance (m.Ω)
VL = L-L secondary Voltage on open circuit (V)
KVAtr = Transformer rating in KVA
Z % = p.u. impedance of transformer
Life Safety and central Battery system
R = ρL/A X = 0.15L mΩ
ρ(CU) = 22.5
ρ(AL) = 36
L Length A cross section area
ZB.B = √(R^2 + X^2)
ZB.B busbar impedance very small value can be (neglected)
Life Safety and central Battery system
Where:
Isc = Short circuit rating of cable (kA)
A = Cross sectional area of conductor (mm2)
t = Time to trip (seconds)
K = Cable short circuit factor