BATTERY TEST EQUIPMENT

MULTI-AMP
Model BGL

Locates ground faults on


floating battery systems

Operates on live
battery systems

4
5

Multiple fault detection


and tracking

Automatic operation

Battery operated

Battery Ground-Fault Locator


DESCRIPTION
The Multi-Amp Battery Ground-Fault
Locator (BGL) simplifies the tracking of
ground faults on floating dc-powered
control systems.
It features automatic operation, can be
used on live battery systems and has the
unique capability of detecting, tracking
and locating multiple faults on a battery
system without having to resort to
sectionalizing.
This is accomplished by injecting a lowamplitude 25 Hertz test signal on either
the positive or negative side of the
power bus and tracking the signal with
one of several available clamp-on
sensor probes.
A fault simulator also is provided with
the instrument, allowing the periodic
verification of the resistance and capacitance ranges of the BGL.
APPLICATIONS
The BGL allows tracking and locating of
ground faults on live or dead battery
systems. Its locating ability is only
limited by the accessibility of the
battery cable.
The instrument can make measurements in the presence of dc current (up
to 20 amperes) and ac ripple (charging
current up to 0.5 ampere).
The BGL is useful for locating grounds on
any type of battery system, including
those in refineries, mines and utilities
as well as UPS and continuous process
systems.

AC-4 AVO-651 07.97

The BGL operates on battery systems


that are either floating or grounded
through a resistor. Operators can determine
both the direction and magnitude of faults,
allowing them to ignore high-impedance
faults and concentrate on serious faults.

This method allows the instrument to


effectively eliminate the effects of
charging current due to capacitance on
the battery system or surge suppression
capacitors that may be installed on the
system.

The BGL is designed to work on battery


systems up to 260 volts dc. The instrument
even operates in the presence of surgesuppression capacitors, effectively ignoring
them. It is only sensitive to the power
dissipated in the grounding resistance,
hence the resistive paths to ground.

The wide dynamic range of the


instrument allows the operator to
simultaneously track two or more ground
faults that may be different in value. The
injected signal is low enough in
amplitude that it should not interfere
with the operation of relays, even of the
sensitive variety, under normal operation.

An additional feature of the BGL is its


ability to measure battery system total
capacitance to ground, or the capacitors of any branch of the system. This
allows the operator to determine the
maximum practical fault-resistance
range and provides the user with information on the battery system.
PRINCIPLE OF OPERATION
The instrument operates by injecting a
25 Hertz signal between the battery
system and the ground. The resulting
current is tracked by a clamp-on current
probe. The magnitude of the injected signal is
only 3.5 volts and will not cause any interference with the operation of sensitive
protective relays on the system.
The instruments circuitry measures the
25 Hertz power dissipated in the grounding
resistance and calculates the value of
the grounding resistance from knowledge
of the applied voltage.

FEATURES AND BENEFITS


Reads resistance directly (1 ohm
to 100 kilohms)
Locates single or multiple ground
faults
Operates on floating or resistancegrounded battery systems

10
11
12
13
14
15
16
17

Operates on live battery systems


Operates in the presence of surgecorrection capacitors
Fused output leads for maximum
user safety

18
19

Battery operated with internal


automatic charger

20

Measures capacitance
Lightweight and portable

21

Tough polyethylene plastic sealed


enclosure that provides high shock
and vibration resistance

AVO INTERNATIONAL

4-11

22

BATTERY TEST EQUIPMENT

SPECIFICATIONS

Input (specify one)


120 V, 60 Hz, 30 VA
OR
240 V, 50 Hz, 30 VA

Battery
Lead-acid rechargeable

Resistance Range
1 to 100 k

Capacitance Range
1 to 100 F

Accuracy
20%

7
8

Environmental
Operating Temperature
32 to 122 F (0 to 50 C)

Dimensions
13 H x 14 W x 10 D in.
330 H x 356 W x 254 D mm

Storage Temperature
-40 to +149 F (-40 to +65 C)

Weight
25 lb (11.3 kg)

Relative Humidity: Up to 80%

Injected Signal
25 Hz nominal, 3.5 V rms maximum,
110 mA maximum
Maximum Ripple Current
0.5 A (ac)

9
10
11

The BGL with clamp-on current sensor and fault simulator

12
13
14
15
16
17
ORDERING INFORMATION

18
Item (Qty)

Cat. No.

19

Battery Ground-Fault Locator


120 volt, 60 Hz ....................................................... 835140
240 volt, 50 Hz .................................................... 835140-1

20

Included Accessories
Clamp-on current sensor, 33 ft (10 m), 2 in. (50 mm)
opening maximum dc current: 20 A [1] ........... 835142
Fault simulator [1] .................................................... 835145
Output lead extension, 14.9 ft (4.5 m) [1] .............. 835144
Output lead, 6.6 ft (2 m) [1] ..................................... 835143
Power cord, ac ............................................................. 17032
Instruction manual [1] ................................... AVTM835140

21
22

4-12

AVO INTERNATIONAL

Item

Cat. No.

Optional Accessories
Mini clamp-on current sensor, 0.5 in. (127 mm)
opening maximum dc current: 5 A ................... 835146
Busbar clamp-on sensor, 2 x 4 in. (50 x 101 mm)
opening maximum dc current: 50 A ................. 835147