Sbs 2000
Sbs 2000
Sbs 2000
Circuit breaker indicators shown in this booklet are for illustration purposes only. Circuit
breakers are to be installed in Discharged and Open positions only.
IMPORTANT
The information contained herein is general in nature and not intended for specific
application purposes. It does not relieve the user of responsibility to use sound practices
in application, installation, operation, and maintenance of the equipment purchased.
Siemens reserves the right to make changes in the specifications shown herein or to
make improvements at any time without notice or obligations. Should a conflict arise
between the general information contained in this publication and the contents of
drawings or supplementary material or both, the latter shall take precedence.
NOTE
*Authorized and qualified personnel
For the purpose of this manual a qualified person is one who is familiar with the installation,
construction or operation of the equipment and the hazards involved. In addition, he has
the following qualifications:
(a) is trained and authorized to de-energize, clear, ground, and tag circuits and
equipment in accordance with established safety practices.
(b) is trained in the proper care and use of protective equipment such as rubber gloves,
hard hat, safety glasses or face shields, flash clothing, etc., in accordance with
established safety practices.
(c) is trained in rendering first aid.
SUMMARY
These instructions do not purport to cover all details or variations in equipment, nor to
provide for every possible contingency to be met in connection with installation,
operation, or maintenance. Should further information be desired or should particular
problems arise which are not covered sufficiently for the purchasers purposes, the
matter should be referred to the local sales office, listed on back of this instruction guide.
The contents of this instruction manual should not become part of or modify any prior
or existing agreement, commitment or relationship. The sales contract contains the entire
obligation of Siemens Energy & Automation, Inc. The warranty contained in the contract
between the parties is the sole warranty of Siemens Energy & Automation, Inc. Any
statements contained herein do not create new warranties or modify the existing
warranty.
Page
General Information
Introduction
Frame Sizes and Frame Ratings
Rating Plugs
Interruption and Short Time Ratings
Overcurrent Protection Configurations
RMS Current Sensing
Accessories
2
3
3
3
3
3
3
Description
Insulated - Encased Construction
Compact Size
Bus Spacing and Connections
Two-Step Stored Energy Mechanism
Centralized Controls and Indicators
Simplified Minimum Depth Drawout Mechanism
Electronic Trip Unit
Overcurrent Protection Configurations
4
5
6
6
6
7
8
8
9
10
11
12-14
14-15
Operating Instructions
Part One - Operating the SB Encased
Systems Breaker
Manually Charging the
Stored Energy Mechanism
Discharging the Stored Energy Mechanism
Locally Closing the Circuit Breaker
Locally Opening the Circuit Breaker
Part Two - Manipulating the Moveable
Drawout Element
Racking Controls
Directional Shift Lever
Racking Pump Handle
Drawout Position Indicator
Moving Drawout Breaker between:
Fully Withdrawn and Unlocked Position
Unlocked to Test Position
Test to Connected Positions
Connected to Test Position
Test to Unlocked Position
Rotating the Moveable Drawout Element
Part Three - Monitoring the Electronic Trip Unit
16
17
18
18
18
19
20
20
21
21
22
23
24
25
26
27
28-35
Page
Internal Accessories
Preliminary Installation Procedures
Electric Motor Operator
Local Electric Close
Remote Close Assembly
Auxiliary Switches
Undervoltage Release
Shunt Trip
Electronic Bell Alarm
Remote Indicator Panel
36-37
38-47
47
48-51
52-53
54-55
56-57
58-59
60-62
External Accessories
Ground Fault Monitor
Display Module
Ground Fault Sensing and Relaying
Key Interlock
Drawout Padlock
Closing Blocking Device
Cell Switches
Drawout Safety Shutters
Secondary Disconnects
Control Terminal Blocks
Sliding Secondary Disconnects
Pressure Wire Connectors
Neutral Sensing Transformer
Lifting Device Bracket
Auxiliary Power Source
Universal Test Kit, TS-31
Dead Front Shield
63
63
64-66
67
68
68
69
70-71
72
72
73
74
75-76
77
78
79-80
81
82-83
84-85
86-87
88-89
90-91
92-93
Ordering Information
SB Encased Systems Breakers
Electronic Trip Units
Rating Plugs
Internal Accessories
External Accessories
Accessory Wiring Diagrams
94
94
95
96
96-97
98-100
97
General Information
Introduction
Siemens SB Encased Systems Breakers bridge the performance gap between Molded Case Circuit Breakers (MCCB)
and Low Voltage Power Circuit Breakers (LVPCB). Modern
computer-aided design and manufacturing tools were used
to effectively blend the technologies of the MCCB and
LVPCB. This combination has resulted in a family of encased
systems circuit breakers that exhibit the most desirable
characteristics of each of the parent technologies. Included
in these characteristics are high interrupting capacities, high
withstand capabilities (magnetic stress), high short-time capabilities (overcurrent heating), and high mechanical and
electrical endurances, without maintenance.
Applications for SB breakers include main, tie, feeder, and
emergency source breakers in industrial plants, large com-
General Information
Frame Sizes and Frame Ampere Ratings
SB breakers come in three frame sizes with frame ampere
ratings ranging from 400 to 4000 amperes. All frames are
rated for 100% continuous operation. This particular instruction guide provides detailed SB breaker information for the
800, 1200 and 2000 ampere frame sizes. Frame ampere
ratings for these 3 (three) sizes range from 400 amperes to
2000 amperes.
Breaker
Frame Ampere Rating (In)
800 Amperes
400 Amperes
800 Amperes
1200 Amperes
1200 Amperes
2000 Amperes
1600 Amperes
2000 Amperes
Rating Plugs
SB breakers are designed to use interchangeable rating
plugs. These rating plugs allow the user to customize the
effective ampere rating of the breaker to meet specific
applications. The label on the front of the breaker identifies
the rating plugs that may be used with that particular breaker.
AAAA
AAAAAAAA
AAAA
Available Rating Plugs
400
800
1200
1600
2000
AAAA
AAAAAAAA
AAAAAA
Measurement
UL
489
Voltage
AC
400
800
1200
2000
65,000
65,000
42,000
65,000
65,000
42,000
65,000
65,000
42,000
65,000
65,000
50,000
100,000
100,000
65,000
100,000
100,000
65,000
240
480
600
100,000
100,000
65,000
100,000
100,000
65,000
200,000
150,000
100,000
200,000
150,000
100,000
200,000
150,000
100,000
200,000
150,000
100,000
25,000
25,000
25,000
35.000
Icu
Ics
100000
100,000
100,000
100,000
Icw
25,000
25,000
25,000
35.000
Icu
Ics
65,000
65,000
65,000
65,000
Icw
25,000
25,000
25,000
35.000
The trip unit that may be used with a specific circuit breaker
is identified on the front cover label.
415
Interrupting
RatingsSymmetrical
RMS Amperes
(50 Hz)
LSIG
Accessories
Identifier
LS
LI
LSI
LSG
LIG
Standard
Protection Configuration
Long Time/Short Time
Long Time/Instantaneous
Long Time/Short Time/Instantaneous
Long Time/Short Time/Ground Fault
Long Time/Instantaneous/Ground Fault
Long Time/Short Time/Instantaneous/
Ground Fault
690
Description
In addition to the performance achieved by combining the
MCCB and LVPCB technologies, several installation, operation, and safety features have been incorporated into the SB
breakers.
Description
Compact Size
The 800A, 1200A and 2000A frame sizes have a common
width of 15 1/2 inches, a common depth of only 12 l/8 inches,
common bus center lines, and a common mounting footprint. This compact, shallow-depth (even with drawout breakers) permits stacking of six 800 ampere, 1200 ampere or four
2000 ampere breakers in a standard
Description
Bus Spacing and Connections
Centralized Controls
Specific installation features of the SB breakers include 5inch pole spacing, and vertical or horizontal bus connections.
The 5-inch pole spacing allows for a standard bus connection
as specified in UL 891, eliminating the requirement for
additional thermal testing. The optional vertical or horizontal
bus connection is available on both fixed or drawout constructed breakers. Detailed outline drawings are contained in
the Outline Dimensions section, pages 82-93.
Description
Stationary and Moveable Drawout Elements
Simplified Minimum Depth Drawout Mechanism The two
elements of a drawout constructed SB Encased Systems
Breaker are referred to as the Stationary Drawout Element
and the Moveable Drawout Element. The stationary drawout
element mounts from the front or bottom into a standard
switchboard. Bottom mounting flanges are provided for
optional mounting arrangements. The moveable drawout
element mounts onto the stationary drawout elements two
extension rails. This allows the moveable drawout element to
be racked into and out of the stationary drawout element. For
inspection purposes, the moveable drawout element may be
rotated on the extension rails when the rails are fully extended. Detailed outline drawings of the stationary and
moveable drawout elements are in the Outline Dimensions
section.
There are four positions of the moveable drawout element: 1.)
connected, 2.) test, 3.) unlocked (only), and 4.) unlocked/
withdrawn. A racking mechanism with a low-force pump
handle is used to move the moveable drawout element
between the connected, test, and unlocked positions. Since
the pump handle is an integral part of the racking mechanism,
no auxiliary racking device or tool is required. In the unlocked
Description
Electronic Trip Units For Siemens SB Encased Systems Breakers
Information
The Electronic Trip Unit is a microprocessor controlled multifunction overcurrent protective device for application with
Siemens state-of-the-art family of SB Encased Systems
Breakers. The adjustment flexibility provided by the trip unit
allows the user to easily accommodate load changes and
other protective requirements while still assuring optimum
coordination. In addition to the adjustable protection functions, the trip unit is designed to use field interchangeable
rating plugs. These rating plugs allow the ampere rating of the
breaker to be changed to meet specific applications.
Identifier
(LS)
(LI)
(LSI)
(LSG)
(LIG)
(LSIG)
General Instructions
Installation instructions for systems breakers, trip units, and
rating plugs are presented in this section. Installation instructions for accessories that may be installed in the field are
presented in the Accessories section.
10
11
Installation Instructions
Electronic Trip Unit
NOTE: For more complete information on other standard and optional features of the Electronic Trip Unit,
see Siemens Electronic Trip Unit for Type SB Circuit
Breakers Information and Instruction Guide, Bulletin
2.20-3A.
To install the trip unit, the front cover of the breaker must first
be removed. This is done by removing the four (4) recessed
Phillips head screws in positions 2, 3, 6, and 7 and the four
(4) Phillips head screws in positions 1 ,4, 5 and 8 that hold the
front cover in place.
12
Installation Instructions
Electronic Trip Unit
scheme .
Before attempting to install the trip unit, check the label on the
side of the unit to make sure that it is the proper unit for the
SB breaker. A built-in rejection scheme will prevent the
installation of a trip unit into a breaker for which it is not
intended.
13
Installation Instructions
Electronic Trip Unit and Rating Plug
1.) Remove the trip unit screws that hold the transparent
cover.
The rating plug and adjustments on the front panel of the trip
unit are protected by a transparent cover. Prior to installing
a rating plug or setting the adjustments on the trip unit, this
cover must be removed. Unscrew the two screws that hold
it in place.
9.) Re-install the eight screws that hold the front cover in
place.
14
Installation Instructions
Rating Plug
CAUTION: Do not attempt to force an improper rating
plug into a trip unit, mechanical damage may occur.
To prevent the insertion of a rating plug into a trip unit for
which it is not intended, the receptacle in the trip unit has been
keyed to reject improper rating plugs.
4.) To insert rating plug, align plug with plug receptacle and
press into place.
To insert a rating plug in the trip unit, align the plug with the
plug receptacle and press the plug into place. The clips on the
plug and the compression fit hold the plug in place, eliminating the need for screws or latches.
To remove a rating plug, squeeze the clips and pull the plug
from the plug receptacle. Since the plug is held in place by
compression, some force will be required to remove the plug.
Do not close the breaker with the rating plug removed from
the trip unit.
6.) The cover may be sealed with a lead seal for tamper
evident protection .
After the cover has been replaced, a wire may be inserted
through the holes in the screws and secured with a meter
seal. This will help prevent tampering.
15
Operating Instructions
Part One - Operating the SB Encased Systems Breaker
General Instructions
16
Operating Instructions
Part One - Operating the SB Encased Systems Breaker
To manually charge the stored energy mechanism, pull the
charging handle. Four or five full strokes, or several partial
strokes are required to fully charge the stored energy mechanism. When the stored energy mechanism is fully charged,
the charging handle will be restrained by an internal stop, and
the Spring Charged/ Spring Discharged indicator will
point to Spring Charged. The charging handle will return to
the stowed position when released .
To manually charge the stored energy mechanism, pull the charging handle downward four or five strokes.
17
Operating Instructions
Part One - Operating the SB Encased Systems Breaker
Discharging the Stored Energy Mechanism
Without Closing the SB Breaker
Discharging the energy in the stored energy mechanism
without closing the SB breaker creates an abnormally high
shock condition on the breaker. The procedure should be
avoided except for safety and/or emergency reasons. To
discharge the energy, push and hold the Open pushbutton
then push the Close pushbutton.
On electrically-operated SB breakers, the electric operator
should be disabled (one way is to remove the fuse) prior to
discharging the stored energy. Otherwise, the electric operator will automatically recharge the springs.
18
Operating Instructions
Part Two - Manipulating the Moveable Drawout Element
Manipulating the Moveable Drawout Element
There are four positions of the moveable drawout element.
These four positions are defined as Connected, Test, Unlocked, and Withdrawn. The connected position is the
normal operating position of the breaker. In this position the
primary stabs and secondary contacts are connected and
the moveable drawout element is locked into position. In the
test position, the primary stabs are disconnected, the secondary contacts are connected, and the moveable drawout
element is locked into position. The unlocked position is a
transition position between the test
19
Operating Instructions
Part Two- Manipulating the Moveable Drawout Element
Directional Shift Lever
Racking Controls
A built-in, low-force pump handle and two control levers are
used to rack the moveable drawout element between the
connected, test, and withdrawn positions.
20
The directional shift lever determines the direction the movable drawout element will move when it is racked. The lever
has three positions: racking-out, neutral, and racking-in.
When the lever is in the racking-out position (pulled all the
way out), the moveable drawout element may be racked
from the connected position to the test position, and from the
test position to the unlocked position. When the lever is set
in the neutral position (located midway between the rackingin and racking-out positions), the racking pump handle is
disengaged from the racking mechanism. In the racking-in
position (pushed all the way forward), the moveable drawout
element may be racked from the unlocked position to the test
position, and from the test position to the connected position.
Operating Instructions
Part Two - Manipulating the Moveable Drawout Element
Racking Pump Handle
21
Operating Instructions
Part Two - Manipulating the Moveable Drawout Element
Fully Withdrawn and Unlocked Positions To move the moveable drawout element from the fully withdrawn position to the
unlocked position, push toward the bus connections until the
moveable drawout element hits a solid stop. The secondary
disconnects on both sides of the moveable and stationary
drawout elements will mate as the moveable drawout element moves into the unlocked position. When the moveable
drawout element is in the unlocked position, the pointer on
the position indicator will point to the unlocked symbol. To
move the moveable drawout element from the unlocked
position to the fully withdrawn position, pull the moveable
drawout element outward until the extension rails are fully
extended .
Pushing and pulling the moveable drawout element between the withdrawn and unlocked positions
22
Operating Instructions
Part Two - Manipulating the Moveable Drawout Element
Unlocked Position to Test Position
Racking the moveable drawout element from the unlocked
position to the test position engages the moveable drawout
element with the stationary drawout element. The physical
position of the moveable drawout element will be unchanged.
To rack the moveable drawout element from the unlocked
position to the test position:
23
Operating Instructions
Part Two- Manipulating the Moveable Drawout Element
Test Position to Connected Position
To rack the moveable drawout element from the test position
to the connected position:
24
Operating Instructions
Part Two - Manipulating the Moveable Drawout Element
25
Operating Instructions
Part Two - Manipulating the Moveable Drawout Element
Test Position to Unlocked Position
Racking the moveable drawout element from the test position to the unlocked position disengages the moveable
drawout element from the stationary drawout element. The
physical position of the moveable drawout element will be
unchanged.
To rack the moveable drawout element from the test position
to unlocked position:
4.) When the moveable drawout element reaches the unlocked position, the interlock lever will automatically
return to the interlock engaged position. and the position
indicator will display the unlocked position .
26
Operating Instructions
Part Two- Manipulating the Moveable Drawout Element
Rotating the Moveable Drawout Element
For inspection purposes, the moveable drawout element can
be rotated on the extension rails. Clearances required to
rotate the moveable drawout element are on drawings
located in the Outline Dimension Drawing section. Note that
the moveable drawout element is designed to be rotated only
in the illustrated direction. Do not attempt to rotate the
moveable drawout element in the opposite direction.
1.) Pull the moveable drawout element to the fully withdrawn position, holding the moveable drawout element
as depicted above.
27
28
29
30
Adjustable Short Time Delay The Short Time Delay adjustment is used to set the time interval the breaker will wait
before responding to the current value selected on the Short
Time Pickup adjustment. There are two modes of operation
of this adjustment on all Siemens Electronic Trip Units; one is
a fixed delay, the other is an inverse 12t ramp delay. The 12t
Delay has the characteristic of being inversely proportional to
the square of the magnitude of the overcurrent condition. This
means that higher overcurrent conditions have shorter delays
and conversely lower overcurrent conditions have longer
delays. This characteristic allows for better coordination with
downstream circuit breakers and fuses. In the fixed delay
mode, the Short Time Delay may be set to .07, .1, .15, .2, or
.3 seconds. In the inverse 12t ramp Short Time Delay mode,
the delay may be set to a calibrated value of .07, .1, .15, .2,
or .3 seconds at a current equal to 8 times Ir.
31
Instantaneous Pickup
32
Breaker
Frame Size
800A
1200A
2000A
25
25
35
Available Setting % In
400A
800A
20 25 30 40 50 60 70 80 90 l00
20 25 30 40 50 60 70 80 90 l00
1200A
1600A
20 25 30 40 50 60 70 80 90 100
20 26 32 38 44 50 56 62 68 75
2000A
20 23 27 30 35 40 45 50 55 60
33
Residual Sensing, Circuit Breaker Wiring for Ground Protection (3-Phase, 4-Wire System Shown).
34
Operating Instructions
Part Three - Monitoring the Electronic Trip Unit
Trip Unit Test and Monitoring Functions
The integral test function enables the user to exercise the trip
unit electronics, the magnetic latch, and the breaker mechanism. The purpose of the integral test function is to provide
the user an easy means to conduct a go/no go type test
before bringing the breaker on-line. After the breaker has
been brought on-line, it may be used during routine inspection and maintenance.
Both phase fault current protection and ground fault current
protection may be tested . The integral ground fault test
function tests the circuit breakers ground fault protection
system in accordance with NEC Article 230-95(c).
Electrical power to operate the integral test function is
provided internally, if the breaker is closed and the phase
currents are greater than 20% of the frame ampere rating In,
or by a plug-in power source (see Accessories section).
Trip Status
The trip Query button and Trip Status indicator lights provide
the user the means for determining what type of fault caused
the trip unit to trip the breaker. Fault indicators are provided
for:
O.L. - Overload or Long Time Fault
S.T. - Short Time Fault
S.C. - Short Circuit or Instantaneous Fault
G.F. - Ground Fault
When a fault occurs, the fault information is stored in the trip
unit by latching the appropriate red LED fault indicator to the
On position. When the Query button is depressed, the
latched fault indicator will light. The electrical power to the
indicators is automatically stored in the trip unit, eliminating
the need for a battery pack. A hole is provided in the
transparent cover to allow the user access to the Query
button.
35
Internal Accessories
Preliminary Installation Procedures
36
2.) Push the close button and then repeat pushing of the
open button.
Internal Accessories
Preliminary Installation Procedures
3.) Remove the breaker cover by first removing the (4) #10
Phillips head screws at the corners and the (4) head
screws in recesses in cover.
6a.) Slide the trip unit up to clear the support bracket pins.
b.) Remove the trip unit by pulling the trip unit away from the
trip unit plug.
37
Internal Accessories
Preparation For Installation of Electric Motor Operator
on the drawout elements, or at remote locations. When the
installation location is referred to as the right side or left
side, it is with reference to the users right or left side when
facing the front of the breaker.
Components required to access or activate an accessory
such as a switch or indicator at a remote location are
assumed to be user supplied unless otherwise stated.
Accessories
The full family of accessories available for Siemens SB
breakers are presented in this section. The accessories are
divided into two groups: accessories that are installed in the
front compartment of the circuit breaker (Internal Accessories) and accessories that are installed or used outside of the
front compartment (External Accessories). The External Accessories are installed on the exterior of the circuit breaker,
Internal Accessories
Preparation For Installation of Electric Motor Operator
SB Breaker Cover Removal
(See page 37, steps 3 and 4)
NOTE: When placing the drawout removable element on a
workbench, ensure that the plug-in finger clusters are not
supporting the weight of the breaker.
1.) Remove the E rings from the bar cap pin on each side.
39
Internal Accessories
Preparation For Installation of Electric Motor Operator
5.) Install the bar cap pins through the bar caps and left and
right mechanism assemblies with the head of the pins
toward the center of the breaker.
3.) Install the crankshaft assembly by positioning the crankpin anywhere between the unlocked and connected
positions as shown and lowering the crankshaft to the
bottom of the slot. During crankshaft assembly installation the lock bar must be held in the proper position. This
may be done by inserting a screwdriver into the doubled hole (if present) and pushing until a solid stop is felt If
the double-d hole is not present use the rectangular
cutout to gain access to the lockbar
40
Internal Accessories
Electric Motor Operator
1.) Install the cam mechanism, gear box and motor assembly
2.) Align the keyway of the shaft with the keyway of the
charging arm.
41
Internal Accessories
Electric Motor Operator
4.) Locate and slide the Remote Close Lever on the Closing
D Shaft located on the Mechanism. Secure the Lever by
tightening the Set Screw to 6-8 in-lbs.
42
Internal Accessories
Electric Motor Operator
7.) Adjust the switch while holding the Actuator against the
switch body. Adjust the switch so that there is .11-12
inch clearance between the switch Actuator and the
Latch Lever. Tighten screws to 9-11 in. Ibs. Check
adjustment after tightening screws and read just if
necessary.
8.) Plug J1-6 and J1-7 Connectors into the Connector Strip
until latch tabs snap into slots Gently pull wires to ensure
they are latched into the Connector Strip.
43
Internal Accessories
Electric Motor Operator
Mounting of B Switch
10.) Connect the MTR-Connector and the Fuse Connector
to the Motor and Fuse Holder. Connect the RC+ Connector and RC- Connector to the Remote Close Solenoid.
11.) Install the B Switch assembly on the reset mechanism
assembly. Make sure to install the Insulator between the
Switch and metal bracket. Secure the assembly with the
two #4-40 x 1/2" screws. Torque screws to 4-6 in-lbs.
Check to be sure the Actuator fits into the slot in the push
link and does not bind
12.) Route the two wires attached to the B Switch from the
right side of the breaker to the left side of the breaker.
The wires need to be fed under the mechanism plates.
13.) Connect the J 1-8 Connector and the J 1-9 Connector.
B Switch Assembly
44
Internal Accessories
Electric Motor Operator
18.) Before replacing the breaker cover remove the fuse hole
plug from the inside of the cover as illustrated above.
Also cut out the Fuse not installed area of the rating
label.
16.) Replace the trip unit by pushing it onto the plug. Slide the
trip unit over the bracket pins.
19.) Replace front cover being careful not to pinch the wires
that are routed to the secondary disconnects or terminal
block.
20.) Replace the (4) #10 Phillips head screws at the corners
and the (4)1/4" Phillips head screws in recesses in cover.
45
Internal Accessories
Electric Motor Operator
Legend
1. Motor Operator Assembly
2. Remote Closing Solenoid Switch
3. Connector Strip
4. Motor Fuse Connector
5. UL Label
6. DC or AC ECMC Assembly
7. Electric Operator Label
8. B Switch Assembly (Motor Operator)
9. #10-32 UNC-2B x 1/4" PHMS
10. #10-32 UNC-2B x 3/8" PHMS
46
11.
12.
13.
14.
15.
16.
17.
18.
Internal Accessories
Electric Motor Operator and Local Electric Close
A charging status indication (contact accessible at terminal
point <LT4>) provides the capability to remotely monitor the
stored energy mechanism . The contact is on if the springs
are fully charged . The contact will be alternately on for 300
milliseconds and off for 300 milliseconds as the springs are
charging or until 20 seconds have elapsed, approximately
twice the time required to charge the springs. If the springs
are not charged after 20 seconds, the contact alternates
between 1 second on and 1 second off, indicating that
there is a problem. SB breakers with an electric operator may
be charged manually if the electric operator is disabled for
any reason.
47
Internal Accessories
Remote Close Assembly
For preliminary installation procedures review procedures
outlined on pages 36 and 37.
1.) Remove the rubber band from the solenoid plunger.
Slide the remote close lever on the closing D-shaft but
do not tighten the set screw at this time (Figure 1 )
2.) Place the return spring over the solenoid plunger and
slide the solenoid over the solenoid plunger (Figure 1).
48
Internal Accessories
Remote Close Assembly
5.) Install the latch check switch assembly (see Figure 2).
Secure the latch check switch assembly to the mechanism plate using (2) #6 screws provided. Do not tighten
screws until the latch check switch assembly is properly
adjusted.
6.) Adjust switch (see Figure 3). When switch is properly
adjusted tighten screws. Note: Torque screws to 8-11
in. Ibs.
7.) After tightening screws check to ensure that tightening
of screws did not affect switch adjustment.
8.) Locate the reset mechanism (See Figure 5).
9.) To mount the B switch, first make sure that the switch
lever is inside the top cavity of the pusher link (See Figure
4).
10.) Make sure that the switch lever rests on the pusher link
when the breaker main contacts are open (See Figure 4).
Place insulator between B switch and bracket. Secure
that B Switch with the (2) #4 screws provided. Note:
Torque screws to 5-6 in. Ibs.
11.) Route wires from B switch (See Figure 5). Route wires
beneath mechanism plates as shown. Install cable tie
mounts and cable ties (See Figure 5).
12.) Connect wire marked RC from B switch to solenoid
connector. (See Figures 4 and 5). Connect wires marked
LC-B together.
49
Internal Accessories
Remote Close Assembly
Internal Accessories
Remote Close Assembly
51
Internal Accessories
Auxiliary Switches
The auxiliary switches are installed on the right side of the
front compartment, behind the trip unit and below the reset
plate.
Auxiliary Switches
Auxiliary switches are used as signal contacts to indicate the
open/closed status of the breakers main contacts. The
status of the main contacts is indicated by the open/closed
status of the auxiliary switches as follows:
A or NO Open when main contacts are open.
Contacts:
Closed when main contacts are closed.
3.) Secure the assembly in place.
B or NC Closed when main contacts are open.
Contacts:
Open when main contacts are closed.
A maximum of six A and B auxiliary switches can be
installed in the breaker. The switch contact ratings are:
Ampere Rating
120V ac
240V ac
480V ac
24V dc
125V dc
10 Amps
10 Amps
6 Amps
3 Amps
0.5 Amps
Internal Accessories
Auxiliary Switches
5.) Secure the trip unit in place with the retaining screw
located at the top of the trip unit. Torque to 6-8 in. lbs. If
trip unit top is not secured properly, the interlock will
prohibit closing of the breaker.
Wiring Information
6.) Replace the front cover of the breaker, being careful not
to pinch wire leads routed to secondary disconnects or
terminal blocks. Secure with eight (8) Phillips head screws.
Installation of the auxiliary switch is complete.
Internal Accessories
Undervoltage Release (UVR) Solenoid
If practical, the UVR should be installed prior to the SB breaker
being installed in the switchboard. Before starting the installation, the breaker should be in the open position and the
stored energy mechanism should be discharged. A drawout
constructed breaker, already installed in the switchboard,
should be placed in the fully withdrawn position to allow
access to the secondary disconnects. If being installed in a
drawout breaker, use access-hole in right side mechanism
assembly.
Undervoltage Release
The undervoltage release (UVR) trips the SB breaker in accordance with the pick-up and dropout requirements of UL-4.89.
The monitored voltage is normally the voltage on the line side
of the breaker. Available UVR coil ratings are 120, 240. 480.
or 600V ac or 12, 24, 48, or 125V dc. The UVR will instantaneously (no intentional delay) trip the breaker when the voltage
drops below the trip value. Tripping can be delayed up to 0.5
seconds by using the external time delay undervoltage accessory with the UVR.
The UVR accessory kit consists of a trip solenoid to trip the
breaker, mounting hardware, and internal wiring . The trip
solenoid is installed on the right side of the front compartment,
behind the trip unit and beneath the reset plate.
Notes:
1. Wire markings are shown in brackets <like this>.
2. LT indicates left-top terminal block or secondary connector
54
3 ) Route the UVR solenoid wire leads across the back of the
stored energy mechanism located between the wire
shield and the mid-barrier to the left side of the breaker.
Internal Accessories
Undervoltage Release (UVR) Solenoid
5.) Secure the trip unit in place with the retaining screw
located at the top of the trip unit Torque to 6-8 in. Ibs. If
trip unit top is not secured properly, the interlock will
prohibit closing of the breaker.
Catalog Number
Operating Voltage
SBUV12
SBUV24
SBUV48
SBUV125
.12
.06
.03
.02
12V dc
24V dc
48V dc
125V dc
SBUV120
SBUV240
SBUV480
SBUV600
.02
.02
.02
.02
120V ac
240V ac
480V ac
600V ac
Internal Accessories
Shunt Trip
Figure 1.
CAUTION: Do not attempt to install an accessory with
the breaker Closed or Charged. Make certain breaker
is Open and Discharged as shown above. Personal
injury or mechanical damage may occur. Preliminary
installation procedures are outlined on pages 36-37.
Shunt Trip
The shunt trip provides the capability to open the SB breaker
from a remote location . Shunt trips are available to operate
with a source power of 120, 240, or 480V ac, 12, 24, 48, or
125V dc. The shunt trip accessory kit consists of a trip
solenoid to open the breaker, a clearing switch to remove
voltage from the solenoid coil upon the breakers opening and
mounting hardware.
To install the shunt trip, first remove the breaker front cover
and trip unit, if previously installed (see page 37). Pinching
wires is not a problem when removing the cover.
Figure 3.
7.) After the B switch and the shunt trips solenoid are
secured, route wires into the three wire clips (see Figure
3) Make sure that wires fit inside the wire clips and do not
interfere with the pusher link.
1.) Remove the rubber band from the shunt trip assembly.
Be careful not to drop and damage the plunger.
2.) Align the shunt trip solenoid on the reset mechanism.
Make sure that the secondary latch is positioned inside
the groove of the solenoid plunger. (See Figure 1)
3.) Secure the shunt trip solenoid with the tow #6-32 SEMS
screws provided. (See Figure 1) Note: Torque screws to
18-20 in. Ibs.
4.) Check the plunger for binding after the screws are
tightened. The plunger should move freely when the
secondary latch is moved.
5.) To mount the B switch, first make sure that the switch
lever is inside the bottom cavity of the pusher link. (See
Figure 2)
Figure 3.
56
Internal Accessories
Shunt Trip Schematic Layout
10.) Replace trip unit and breaker front cover. being careful
not to pinch wire leads routed to secondary disconnects
or terminal block. (See Figure 6)
11.) Apply the shunt trip accessory label to side of the breaker
cover (see Figure 7) Mark the label that is on the opposite
side of the cover to indicate that the shunt trip has been
installed.
Figure 4.
8.) Route all wires between the wire shield and mid barrier,
make Sure to route the wires toward the bottom of the
trough, So that the wires fit into the mid barrier trough
(See Figure 4)
9.) Add cable tie mounts and cable tie as directed in accessory instructions (See Figure 5)
Operating Voltage
SBST12
SBST24
SBST48
SBST125
SBST120
SBST240
SBST480
2.50
1.75
1.10
1.02
.63
.41
.35
12V dc
24V dc
48V dc
125V dc
120V dc
240V dc
480V dc
Figure 5.
Figure 6.
57
Internal Accessories
Electronic Bell Alarm - Display Module Relay
2. ) Connect bell alarm lead wires (# 1 and #22) to corresponding numbered holes in pin connector. (Note: If a
display module relay is being installed instead of a bell
alarm connect lead wires to #4 and #22 holes respectively. )
To install the bell alarm, first remove the breaker front cover
and trip unit, if previously installed (see page 37).
4.) Route bell alarm lead wires RT9 through RT12 through
right side of the circuit breaker.
1.) With a small screwdriver, press in tab on right side of 36pin trip unit connector and release from mounting bracket.
58
Internal Accessories
Electronic Bell Alarm
59
Internal Accessories
Remote Indicator Panel
1.) With a small screwdriver, press in tab on right side of 36pin trip unit connector and release from mounting bracket.
60
2.) Connect the wires provided between the trip unit 36 pin
connector and the External Terminal Block
Internal Accessories
Remote Indicator Panel
The Remote Indicator Panel can be either panel mounted or
wall mounted. The intent is mounting versatility yet keeping all
electrical connections within the switch board or panel.
Panel Mounting
This style mounting is intended for surface use inside of the
switchboard or panel.
Panel Mounting
1.
1.
Wiring
Note that these terminal blocks are removable for ease of
wiring. Pull them straight out to unplug, insert wires and
tighten screws then plug them back into circuit board.
Wire Remote Indicator Panel to circuit breaker using terminals
on left side marked LB4-LB8. Connect them to the corresponding terminal block positions located on left bottom side
of SB breaker. These wires must be 18AWG with a maximum
length of 10 feet.
2.
Remove both Flange Brackets and insert Remote Indicator Panel into the opening
3.
61
Internal Accessories
Remote Indicator Panel
Relay Functions
62
External Accessories
Ground Fault Monitor and Display Module
Display Module and Ground Fault Monitor
Display Module
Display
The Ground Fault Monitor displays the ground fault cur-rent in
amps. Then the ground fault current reaches a level 12
percent below the selected pickup setting, the amps display
will start to flash. Then the ground setting, the display will flash
-OL- for overload and the alarm line will be set to its ON
state.
Display Module
External Accessories
Ground Fault Sensing and Relaying
This system will provide Class 1 ground fault protection as
described in UL STANDARD 1053. GROUND-FAULT SENSING AND RELAYING EQUIPMENT.
System Components
UL Listed Circuit Breaker Components and Accessory Components
1. Circuit Breaker
2. Trip Unit3. Rating Plug4. GF Monitor Module
5. Display Module Relay
or Remote Indicator Panel-
Table 2
Table 1
Table 3
SBGFM
Table 4
SBRIP120
Table 5
SB12TLI
SB12TLS
SB12TLSI
SB12TLIG
SB12TLSG
SB12TLSIG
SB16TLI
SB16TLS
SB16TLSI
SB16TLIG
SB16TLSG
SB16TLSIG
SB20TLI
SB20TLS
SB20TLSI
SB20TLIG
SB20TLSG
SB20TLSIG
SB25TLI
SB25TLS
SB25TLSI
SB25TLIG
SB25TLSG
SB25TLSIG
SBS0804
SBS0808
SBS1212
SBS2016
SBS2020
SBS4025
SBS4032
SBS4040
SBH0804
SBH0808
SBH1212
SBH2016
SBH2020
SB32TLI
SB32TLS
SB32TLSI
SB32TLIG
SB32TLSG
SB32TLSIG
SB40TLI
SB40TLS
SB40TLSI
SB40TLIG
SB40TLSG
SB40TLSIG
Table 4-Display
Module
SBDMR24
SBDMR48
SBDMR120
SBDMR125
System Operation:
The user must first set the desired ground fault pickup and
delay settings on the Ground Fault Monitor Module (Page 63).
These settings are independent from the trip unit built-in
ground fault settings (if available). When a ground fault above
the selected pickup occurs, the breaker will delay based on
the module settings and when the proper time has elapsed.
Issue a signal to the internal Display Module Relay or External
Remote Indicator Panel. The output contacts of the relay can
then be used to trigger the Shunt Trip Device, thus tripping the
circuit breaker.
Testing:
04SB200
04SB225
04SB250
04SB300
04SB350
04SB400
04SB400
04SB450
04SB500
04SB600
04SB700
04SB800
12SB600
12SB700
12SB800
12SB1000
12SB1200
16SB800
16SB1000
16SB1200
16SB1600
20SB1000
20SB1200
20SB1600
20SB2000
25SB1600
25SB2000
25SB2500
32SB1600
32SB2000
32SB2500
32SB3000
40SB2000
40SB2500
40SB3000
40SB3200
SBST12
SBST24
SBST48
SBST125
SBST120
SBST240
SBST480
System Description:
This Ground Fault Relaying system is based on the Type SB
insulated case circuit breaker. The breaker must be equipped
with an electronic Trip Unit and Rating Plug. The trip unit can
be the type with or without the built-in ground fault tripping
function. The breaker must also have a GF Monitor Module, a
Shunt Trip Device, and either a Display Module Relay or
Remote Indicator Panel. For a system completely enclosed
within the breaker case, the internally mounted Display Module Relay is used . If remote cause of trip information is
required, the Remote Indicator Panel may be used in place of
the Display Module Relay.
64
General Instructions
1. The interconnected system shall be evaluated when
initially installed by qualified personnel. It is also recommended that this be done periodically thereafter.
2. The proper location of the sensors around the bus of the
circuit to be protected shall be determined. This can be
done visually with knowledge of which bus is involved.
3. The grounding points of the system shall be verified to
determine that ground paths do not exist that would
bypass the sensors.
4. The polarity of the sensor connections must agree with
the installation instructions to avoid improper operations.
5. A simulated test is to be done using a low voltage, high
current source. This test is not intended to verify that it is
properly functioning.
6. The results of this testing should be recorded on the form
provided at the end of this document or other appropriate
forms and should be available to the inspection authority.
7 . These breakers may be set for different modes of operation. Residual or Ground Return, as described in the
information on applications, refer to the NEMA standards
publication No. PB 2.2 Application Guide for Ground
Fault Protective Devices for Equipment.
External Accessories
Ground Fault Sensing and Relaying
Test Operation
GF Type Switch set to RESIDUAL
Outgoing Circuit Method (if trip unit does not provide
ground fault protection, this is the method used.)
3 Phase / 3 Wire
Using Figures 2, and 1 or 5, individually test breaker poles A,
B, and C, for proper Ground Fault operation.
Each of the circuit breaker s front panel controls should be set
to the highest setting. Set the Ground Fault Monitor to the LO
pickup on the .1 second delay band. Using a low voltage
current source, apply a test current equal to 50% of the rating
plug value. The circuit breaker must trip.
3 Phase / 4 Wire
Using Figures 3, and 1 or 5, individually test breaker poles A,
B, and C, in conjunction with the proper neutral sensor for
Ground Fault operation.
Figure 1.
65
External Accessories
Ground Fault Sensing and Relaying
66
External Accessories
Key Interlock and SB Breaker Padlock Device
Key Interlock on SB Breaker
To remove the key from the key interlock, press and hold the
open pushbutton; turn and remove key.
The breaker key interlock is not field installable. It is installed
at the factory in the central escutcheon of the front panel,
directly above the push-to-open pushbutton switch.
Mechanical Interlock
The mechanical interlock device provides the capability to
prevent simultaneous closing of two SB breakers. The first
breaker to close will keep the other breaker in the open/
tripped position. The interlock device is available for fixed
mounted breakers installed side-by-side or in the same vertical section. On drawout configured breakers, the interlock
device is available for breakers installed in adjacent cubicles,
either vertically or horizontally.
Mechanical Interlock
67
External Accessories
Drawout Padlock and Close Blocking Devices
Padlock Device on Drawout Mechanism
68
External Accessories
Cell Switches
B or NC contacts - Closed when the moveable drawout
element is in the test, unlocked, or
withdrawn position.
Open when the moveable draw out
element is in the connected position
A maximum of four A and B cell switches may be installed
in a breaker. The switch contact ratings are given in the
following table.
Supply Voltage
Ampere Rating
120 VAC
240 VAC
480 VAC
24 VDC
125 VDC
10 Amps
10 Amps
6 Amps
3 Amps
0.6 Amps
69
External Accessories
Drawout Safety Shutters
The drawout safety shutters kit consists of two shutter assemblies and mounting hardware. The shutters are symmetrical
so that either shutter can be used to cover the line or load
stabs. The shutters are installed on the sides of the stationary
drawout.
If practical, the drawout safety shutters should be installed
prior to the stationary drawout element being installed in the
switchboard. If the drawout elements have already been
installed, the moveable drawout element will have to be
removed from the switchboard to allow access to the installation location.
To install the safety shutters:
70
External Accessories
Drawout Safety Shutters
6.) Install shutter springs (zinc silver spring is used for the top
shutter, white springs are used for the bottom shutter).
Installation of the bottom shutter is similar to the top.
7.) Push down on the top shutter and pull up on the bottom
shutter to ensure that they will move freely in the tracks
4.) Slide top of shutter slide block into bottom of grooved top
shutter rail
5.) Install top shutter section with #6-32 x 1/4" screws and
lock washers, to the sides of the stationary drawout
element.
71
External Accessories
Secondary Disconnects and Control Terminal Blocks
Secondary Disconnects
Secondary wiring connections to remote locations are made
to secondary disconnects on drawout breakers and to
control terminal blocks on fixed-mounted breakers. The
secondary disconnects and terminal blocks are located along
the sides of the breakers, as many as two on each side. They
are referenced as left top (LT), left bottom (LB), right top (RT),
and right bottom (RB). Left and right are with respect to the
user facing the breaker. The terminal points of factory installed
internal accessories are identified on page 62. The same
terminal point locations should be used when an accessory is
installed in the field.
72
External Accessories
Sliding Secondary Disconnects
To install the secondary disconnects:
73
External Accessories
Pressure Wire Connectors T Connectors
T Connectors
T connectors are used to connect power buses to the SB
breakers. The connectors are rotatable to allow for vertical or
horizontal bus connections.
Amp
Rating
Cables per
Connector
Connector
Wire Range
Catalog
Number
800
800
1-3
1/0-500 kcmil
Cu/Al
TA3K500S
1200
1200
1-4
250-500 kcmil
Cu/Al
TA4N8500
2000
1200
1-4
250-500 kcmil
Cu/Al
TA4P8500
2000
1600
1-5
300-600 kcmil
Cu/Al
TA5P600S
2000
2000
1-5
250-600 kcmiI
Cu
TA6R600S
74
External Accessories
Neutral Sensing Transformer
Introduction
This neutral sensing transformer is designed to be mounted
on a bus bar with maximum dimensions of 3.00" x .75".
1.) Turn off power feeding this device before starting the
installation.
2.) Also turn off any line power within the immediate vicinity
to prevent the incidental or accidental contact of tools by
the installer.
Use transformers with the following breaker frame ratings only
NO4SB
NO8SB
N12SB
N16SB
N20SB
SBA0400
SBA0800
SBA1200
SBAl60
SBA2000
SBS0400
SBS0800
SBSl200
SBS1600
SBS2000
SBH0400
SBH0800
SBH1200
SBH1600
SBH2000
Mounting
Position the neutral sensor as close as possible to the associated circuit breaker and fabricate two .312 diameter holes
1.75 inches apart in bus, as shown below. Mount the neutral
sensor to the bus as shown with 1/4-20 hardware (not
provided). Torque mounting bolts to 50 in. lbs. maximum.
Bus Mounting
75
External Accessories
Neutral Sensing Transformer
Important
The SB series of electronic trip circuit breakers equipped with
ground fault protection may be used in the Residual or Ground
Return modes. When used in the Residual mode the orientation of the neutral sensing transformer is important for proper
operation. See illustrations below for proper orientation of the
neutral sensor for Residual mode Ground Fault. Orientation of
the neutral sensor is not required when used in the Ground
Return mode of Ground Fault.
Installation of neutral transformer
Terminal Connections
After properly orienting and mounting the neutral sensing
transformer, maintain the correct polarity by connecting terminal LT1 1 on the circuit breaker to terminal X1 on the neutral
sensor, and terminal LT12 on circuit breaker to terminal X2 on
the neutral sensor.
Standard Connection
Reverse Connection
76
External Accessories
Lifting Device Bracket
CAUTION: SB breakers and Stationary Drawout Elements are heavy. Personal injury or mechanical damage
may occur if care is not used in lifting these pieces of
equipment.
77
External Accessories
Auxiliary Power Supply
Auxiliary Power Supply
The auxiliary power supply is a plug-in supply for bench testing
the Electronic Trip Unit The supply may also be used to power
the trip unit during the execution of a go/no-go type test
before bringing the SB breaker on-line (see Monitoring the Trip
Unit in the Operating Instructions section). The auxiliary power
supply operates from 120V ac source power.
Test Procedures
1.
2.
3.
78
External Accessories
Universal Test Kit (TS-31)
Searching Catalog . . .
Searching Family/Series . . .
General Information
(detailed instructions supplied with kit)
TS-31 Procedures
Operating Instructions
A.
B.
C.
Select the appropriate ribbon cable assembly and connect it between the TS-31 and the circuit breaker, making
sure of alignment and polarity. After pressing ENTER, the
TS-31 will prompt:
G.
79
External Accessories
Universal Test Kit (TS-31)
Enter one of the following letters:
APhase A or Left Pole
BPhase B or Center Pole
CPhase C or Right Pole
H.
The TS-31 will report the type of test you selected and
give you a chance to abort the test. For example, if I was
pressed above. The TS-31 will display:
Instantaneous Test
Press ENTER to Continue or A to Abort.
If you pressed the letter A to abort. you will be asked to
enter again
Change: 1 - Test 2 - Catalog 3 - Settings:
I.
Press Enter again to start the test. Press any other key to
STOP the test. Once a test has been started, the TS-31
will respond with:
Trip test. Press Any Key to Abort.
Time Remaining: xx.xxx Sec.
Be careful at this time. Any keypress will abort the test.
J.
and then for the phase to test. A message will then appear
stating the test results. For example:
CT Resistance Test. Phase X PASSED.
Press any key to continue.
M. There are additional ERROR messages which may appear on the display during this operation which were not
covered previously:
Test Not RunningCheck Test Cable.
Press enter to continue.
The test set has sensed that current is not flowing
properly in the breaker under test and that there is either
an open or short circuit between the TS-31 and the
breaker trip unit
Ground Fault is NOT available on a SJD69300.
Press any key to continue.
You will get this error message if you enter a choice that
is not available, such as entering G in step F for ground
fault test on a catalog number that does have ground
fault.
Inconclusive Test, Check Settings.
Press any key to continue or A to abort
Note:
K.
Note:
80
Note:
Note:
External Accessories
Dead Front Shield
Note: Accessory installation should be completed before the
breaker is racked into the Connected position. If the
breaker is in the Connected position, rack the breaker
out to the Unlocked position. Turn off and lock out all
power supplying the switchboard before installing any
accessories.
1.
2.
3.
4.
5.
Figure 1.
81
82
83
84
85
86
87
88
89
90
91
92
93
Ordering Information
Encased Systems Circuit Breakers and Electronic Trip Units
Type SB Encased Systems Breaker Frames Alternate Interrupting Rating (To 85 A.l.R. (kA))
Breaker Type
Fixed Mounted
Catalog Number
Ampere Rating
Frame Size
400
800
1200
1600
2000
800
800
1200
2000
2000
SBA0804F
SBA0808F
SBA1212F
SBA2016F
SBA2020F
SBA0804DV
SBA0808DV
SBA1212DV
SBA2016DV
SBA2020DV
SBA0804DH
SBA0808DH
SBA1212DH
SBA2016DH
SBA2020DH
SBA08DFV
SBA08DFV
SBA12DFV
SBA20DFV
SBA20DFV
SBA08DFH
SBA08DFH
SBA12DFH
SBA20DFH
SBA20DFH
Type SB Encased Systems Breaker Frames Standard Interrupting Rating (To 100 A.l.R. (kA))
Breaker Type
Fixed Mounted
Catalog Number
Ampere Rating
Frame Size
400
800
1200
1600
2000
800
800
1200
2000
2000
SBS0804F
SBS0808F
SBS1212F
SBS2016F
SBS2020F
SBS0804DV
SBS0808DV
SBS1212DV
SBS2016DV
SBS2020DV
SBS0804DH
SBS0808DH
SBS1212DH
SBS2016DH
SBS2020DH
SBS08DFV
SBS08DFV
SBS12DFV
SBS20DFV
SBS20DFV
SBS08DFH
SBS08DFH
SBS12DFH
SBS20DFH
SBS20DFH
Type SB Encased Systems Breaker Frames High Interrupting Rating (To 200 A.l.R. (kA))
Breaker Type
Fixed Mounted
Catalog Number
Ampere Rating
Frame Size
400
800
1200
1600
2000
800
800
1200
2000
2000
SBH0804F
SBH0808F
SBH1212F
SBH2016F
SBH2020F
SBH0804DV
SBH0808DV
SBH1212DV
SBH2016DV
SBH2020DV
SBH0804DH
SBH0808DH
SBH1212DH
SBH2016DH
SBH2020DH
SBH08DFV
SBH08DFV
SBH12DFV
SBH20DFV
SBH20DFV
SBH08DFH
SBH08DFH
SBH12DFH
SBH20DFH
SBH20DFH
Short Time
Pickup/Delay
Ground Fault
Pickup/Delay
Continuous Current
Setting
Instantaneous Pickup
SB04TLI
SB04TLS
SB04TLSI
400
400
400
x
x
x
x
x
x
SB04TLIG
SB04TLSG
SB04TLSIG
SB04TMLI
400
400
400
400
x
x
x
x
x
x
SB08TLI
SB08TLS
SB08TLSI
800
800
800
x
x
x
x
x
x
SB08TLIG
SB08TLSG
SB08TLSIG
SB08TMLI
800
800
800
800
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Short Time
Pickup/Delay
Ground Fault
Pickup/Delay
Continuous Current
Setting
Instantaneous Pickup
SB12TLI
SB12TLS
SB12TLSI
1200
1200
1200
x
x
x
x
x
x
SB12TLIG
SB12TLSG
SB12TLSIG
SB12TMLI
1200
1200
1200
1200
x
x
x
x
x
x
94
x
x
x
x
x
x
x
x
x
Ordering Information
Encased Systems Circuit Breakers and Electronic Trip Units (Continued)
Electronic Trip Unit, 2000A Frame
Catalog Number
Continuous Current
Setting
Instantaneous Pickup
SB16TL
SB16TLS
SB16TLSI
1600
1600
1600
x
x
x
x
x
x
SB16TLIG
SB16TLSG
SB16TLSG
SB16TMLI
1600
1600
1600
1600
x
x
x
x
x
x
SB20TL
SB20TLS
SB20TLSI
2000
2000
2000
x
x
x
x
x
x
SB20TLIG
SB20TLSG
SB20TLSIG
SB20TMLI
2000
2000
2000
2000
x
x
x
x
x
x
x
x
x
x
Short Time
Pickup/Delay
Ground Fault
Pickup/Delay
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Rating Plugs
Rating Plugs, 400 Ampere Frame Rating
Catalog
Number
Plug
Rating
Catalog
Number
Plug
Rating
04SB200
04SB225
04SB250
200
225
250
16SB800
16SB1000
800
1000
04SB300
04SB350
04SB400
300
350
400
16SB1200
16SB1600
1200
1600
Plug
Rating
08SB400
08SB450
08SB500
400
450
500
08SB600
08SB700
08SB800
600
700
800
Plug
Rating
20SB1000
20SB1200
1000
1200
20SB1600
20SB2000
1600
2000
Plug
Rating
12SB600
12SB700
12SB800
600
700
800
12SB1000
12SB1200
1000
1200
95
Ordering Information
Internal Accessories/External Accessories
Electric Motor Operator
Accessory
Catalog Number
Accessory
Catalog Number
Voltage
120VAC
24VDC
48VDC
125VDC For Fix Mount Only
125VDC For Drawout Only
SBEO120
SBEO24
SBEO48
SBEO125
SBEO125D
SBDMR24
SBDMR48
SBDMR125
SBDMR120
24V dc
48V dc
125V dc
120V dc
Accessory
Catalog Number
Accessory
Catalog Number
Consult Siemens
120VAC
24VDC
48VDC
SBEO120CCX
SBEO24CCX
SBEO48CCX
Accessory
800A, 1200A
2000A
SB08DF
SB20DF
Accessory
Catalog Number
800A Envelope
1200A Envelope
2000A Envelope
SBSS08
SBSS20
Accessory
Accessory
Catalog Number
120VAC
24VDC
48VDC
125VDC
SBRCS120
SBRCS24
SBRCS48
SBRCS125
Catalog Number
SBSDLT, SBSDLB,
SBSDRT, SBSDRB
The catalog number for the secondary disconnects include one each 12-point A and
B block.
Shunt Trip
Accessory
Catalog Number
Accessory
120VAC
240VAC
480VAC
12VDC
24VDC
48VDC
125VDC
SBST120
SBST240
SBST480
SBST12
SBST24
SBST48
SBST125
Catalog Number
Undervoltage Release
Accessory
Catalog Number
120VAC
240VAC
480VAC
12VDC
24VDC
48VDC
125VDC
SBUV120
SBUV240
SBUV480
SBUV12
SBUV24
SBUV48
SBUV125
Accessory
Catalog Number
TA3K500SB
TA4N8500SB
TA4P8500SB
TA5P600SB
TA6R600SB
"T" Connectors
Auxiliary Switches
Accessory
Catalog Number
1A & 1B
2A & 2B
3A & 3B
4A & 4B
5A & 5B
6A & 6B
SBAS2
SBAS4
SBAS6
SBAS8
SBAS10
SBAS12
Accessory
Catalog Number
800A Envelope
1200A Envelope
2000A Envelope
SB12TCON
SB20TCON
Catalog Number
SBLD
Catalog Number
Voltage
Bell Alarm
SBBA24
SBBA48 SBBA125
SBBA120
24V dc
48V dc
125V dc
120V dc
96
Accessory
Catalog Number
N04SB
N08SB
N12SB
N16SB
N20SB
Ordering Information
External Accessories
Key Interlocks
Accessory
Catalog Number
Accessory
Catalog Number
Installed on Breaker
KISB, SISB
SBRIP
Provision only
Circuit Breaker
Drawout
KIPOF
SKIPOD, 20KIPOD
Padlock Devices
Accessory
Catalog Number
Installed on Breaker
Installed on Drawout
SBPLB
SBPLD
Catalog Number
SBBD
Capacitor Trip
Display Module
Accessory
Catalog Number
Display Module
SBDM
Catalog Number
SBGFM
Catalog Number
SBAPM
Accessory
Catalog Number
Capacitor Trip
Consult Siemens
Cell Switches
Accessory
Catalog Number
Accessory
Catalog Number
Test Kit
TS31
1A & 1B
2A & 2B
3A & 3B
4A & 4B
CEL1
CEL2
CEL3
CEL4
Mechanical Interlock
Accessory
Catalog Number
SBMIF08
SBMID08
2000A Envelope
Fixed Circuit Breaker
Drawout Circuit Breaker
SBMIF20
SBMID20
UL Listing
File Number
Trip Unit
Breaker
Draw Assembly
Accessories
CSA Guides
E9896
E9896
E135453
E57501
LR57039
Catalog Number
TD7210
Solutions
1.
2.
3.
4.
5.
1. Remove power from LT1 and LT5, manually charge breaker. Reapply power to LT1 and LT5 motor should run for less than
10 seconds and shut off. Lamp on LT4 should remain on.
1.
2.
3.
4.
5.
1. Remove power from LT1 and LT5, manually charge breaker springs. Reapply power to LT1 and LT5. Lamp on LT4 should
remain on.
97
98
Electrical Diagrams
99
Electrical Diagrams
100