1MRG008054 en Application Note Function Description For High Impedance Busbar Protection PDF
1MRG008054 en Application Note Function Description For High Impedance Busbar Protection PDF
1MRG008054 en Application Note Function Description For High Impedance Busbar Protection PDF
Type des.
Prep.
Appr.
Part no.
/ Hamdy Faramawy
/ Apell Gert
Doc. kind
2013-07-16
Approved
Resp. dept
Title
Information
Application note: Function description
for high impedance busbar protection
Doc. no.
ABB AB
FILE: 1MRG008054; SAVEDATE: 2013-07-10 07:51; TEMPLATE: TECHN_DOC_STAND_P.dot C; SKELETON:
Lang.
1MRG008054
en
Rev. ind.
No. of p.
13
Page
Table of contents.
1
Introduction.............................................................................................................. 3
Doc. no.
ABB AB
Lang.
1MRG008054
en
Rev. ind.
Page
Introduction
High impedance protection system is a simple technique which requires that all CTs used in the
protection scheme have relatively high knee point voltage, similar magnetizing characteristic and the
same ratio. These CTs shall be installed in all ends of the protected object. In order to make the scheme,
all CTs belonging to one phase shall be connected in parallel.
Typical high impedance differential scheme is shown in Figure 1. Note that only one phase is shown in
this figure. Due to the parallel CT connections the high impedance differential relay can only measure
the operating quantity. That means that there is no any stabilizing quantity in such schemes. Therefore in
order to guaranty the stability of the relay during external faults the operating quantity must not exceed
the set pickup value.
Doc. no.
ABB AB
Lang.
1MRG008054
en
Rev. ind.
Page
High impedance function as implemented in 670 and 650 Series is based on phase segregated
protection function. Depending on the ordered type of the IED, up to nine single-phase high impedance
function can be available.
For each of such single phase function, the measuring principle is based on one single CT input into
the IED with external stabilizing resistor and voltage dependent resistor (see Figure 1).
The tables 1, shows, examples of the operating currents for different sets of operating voltages and
selected resistances for 1A CT input.
Figure 2: Simplified logic diagram for measured analogue quantities within one phase.
Doc. no.
ABB AB
Lang.
1MRG008054
en
Rev. ind.
Page
2.1
Any interruption of a CT secondary circuit up to the paralleling interconnections will cause an unbalance
current in the protection function equivalent to the load being carried by the relevant primary circuit. Even
though this degree of spurious output is below the effective setting the condition cannot be ignored,
since it is likely to lead to differential protection unwanted operation under any through fault condition.
In the conventional schemes, the supervision was carried out to detect such conditions by connecting a
separate sensitive alarm relay across the bus wires of each zone. Since a relay of this order of sensitivity
is likely to operate during through faults, a time delay, of few seconds, is applied to avoid unnecessary
alarm Signals.
2.2
In the present design of high impedance function as available in 670 and 650 Series, the supervision of
CT bus wires is integrated within the main protection function (setting U>Alarm). Each single phase high
impedance function has separate operating alarm level with settable time delay which is used to give
alarm for problems with associated CT secondary circuit. The output of the alarm stage shall be used to
activate an external shorting of the differential circuit CT bus wires and hence avoiding continuous high
voltage in the CT circuit and the possible unwanted operation of the differential protection function.
CT input
Blocking input
Doc. no.
ABB AB
Lang.
1MRG008054
en
Rev. ind.
Page
Doc. no.
ABB AB
Lang.
1MRG008054
en
Rev. ind.
Page
U R1
I Max
* RCT R L
CT _ ratio
U R1
= Voltage developed across the relay for through fault conditions associated with fully saturated
CT (V).
I Max = Magnitude of the maximum primary through fault current.
CT_ratio = Ratio of the used CTs in the scheme
RCT = CT secondary winding resistance ()
RL
= The resistance of the secondary cable from the CT up to a common junction point (). The loop
resistance containing the phase and neutral wires must be used. Note that typically the CT
circuits with longest cable run from the CT summation point shall be used for this calculation.
If voltage UR1 is smaller than the set voltage, then the relay will not operate for external fault and will
remain stable. This condition defines the stability limit for the scheme and used also as base to set
scheme pick up level for internal fault. Thus, the relay set value Us shall be set higher than value
calculated for external fault.
During internal fault, all CTs conducting the fault current will be feeding into high impedance relay, which
will be actually connected in parallel with any idle CTs (passive load circuits). The voltage developed
across the relay will approach the open circuit secondary voltage that the CTs can produce. Even for a
moderate internal fault this voltage will be in excess of the value calculated for the maximum external
fault as described above. Hence the current through the relay can reach value which is several times
higher than the actual set value.
For an internal fault, the CTs attempt to force secondary current through the high-impedance differential
relay and a relatively high voltage is developed to operate the measuring unit. However, for reliable
performance and to obtain high speed operation for internal faults, rated equivalent secondary e.m.f. Eal
of the used CTs must be higher than the set voltage, Us. This is essential so that the operating current
through the relay is a sufficient multiple of the applied current setting.
In accordance with the data stated in the application manual, for reliable and secure performance of the
high impedance differential function in 670 and 650 Series, the rated equivalent secondary e.m.f. Eal
(i.e. the knee point voltage) of the CTs must be larger than or equal to the required equivalent secondary
e.m.f. Ealreq below:
Doc. no.
ABB AB
Lang.
1MRG008054
en
Rev. ind.
Page
In simple words the knee point voltage of used CTs shall be at least twice the set voltage level!
Note that all used CTs within the high-impedance differential protection scheme should have identical
turn ratios. Consequently auxiliary CTs cannot normally be used. Finally the used CT core shall be
dedicated to this protection. Thus the other protection devices shall not be connected to this scheme.
Doc. no.
ABB AB
Lang.
1MRG008054
en
Rev. ind.
Page
Fig 7. Time /Current characteristics for high impedance function in 670 and 650 Series.
Doc. no.
ABB AB
Lang.
1MRG008054
en
Rev. ind.
Page
1.2
43
1.2
27
17
10
10
Table 2: Typical operate time for high impedance function in 670 and 650 Series
The minimum operate time of the protection function is 8msec at 10 times pick up set value. The operate
time will remains at 8 msec for higher applied voltage.
Doc. no.
ABB AB
Lang.
1MRG008054
en
Rev. ind.
Page
10
Guidelines for the setting calculation for high impedance protection in 670 and 650 Series
5.1
The stability of a high impedance differential scheme depends upon the fact that the relay set voltage is
greater than the maximum false voltage which can appear across the relay circuit under a maximum
through fault condition (i.e. external fault). This voltage can be determined by means of a simple
calculation, which is already described in this document:
U R1
I Max
* RCT R L
CT _ ratio
For stability, the relay set voltage (setting U>Trip) should be made higher than this calculated value UR1.
A safety factor of 1,1 can be used if it is necessary to accommodate future fault current variations.
Then check that the selected set voltage value does not exceed the 50% of the saturation voltage (i.e.
knee point voltage or Eal) of the used CTs.
5.2
Since the current measuring relay used in the scheme has a low burden, an external stabilizing resistor
is required. The stabilizing resistor value RS is then given by:
RS= U>Trip / IS
U>Trip = relay set voltage (see Figure 3)
IS = Desired relay pick up current
Note that pickup current IS shall not be less than 4% of the CT input rating (i.e. 40mA for 1A rated CT
input). At the same time the relay pickup for the built-in Alarm Stage shall not correspond to current less
than 2% of the CT input rating (i.e. 20mA for 1A rated CT input). This alarm pickup is calculated as
follows:
IA=U>Alarm / RS
U>Alarm = relay alarm voltage (see Figure 3)
IA = relay pick up current for the built-in alarm feature
Setting resistors which are offered together with 670 and 650 Series are adjustable. The selected RS
value shall be adjusted for every installation. For more details see ABB Document with ID: SA2007000725.
The actually used RS value shall be set in the IED under parameter SeriesResistor (see Figure 3).
5.3
During internal fault, the current will cause high voltage spikes across the relay. The peak voltage value
Vpeak produced under internal fault conditions can be estimated in accordance with the following formula:
=2 2
Doc. no.
ABB AB
Lang.
1MRG008054
en
Rev. ind.
Page
11
Note that all symbols used in this formula are previously defined in this document.
To protect the CTs, the secondary wiring, and the relay from damage due to excessively high voltages,
a non-linear resistor is typically connected in parallel with the relay circuit (see Figure 1). These nonlinear resistors (metrosils) are externally mounted together with the setting resistor. Refer to the IED
Product Guide and the ABB Document with ID: SA2007-000725 for additional information.
5.4
The minimum primary operating current or the relay sensitivity can be calculated as follows:
=
Doc. no.
ABB AB
Lang.
1MRG008054
en
Rev. ind.
Page
12
REVISION
Rev. ind. Page (P)
Description
Chapt. (C)
Date
Dept./Init.
A
B
C
2012.11.30
2013.02.25
2013.07.09
7/3
11/5
09/07
Doc. no.
ABB AB
Lang.
1MRG008054
en
Rev. ind.
Page
13