Specific Gravity 20mm

Download as xls, pdf, or txt
Download as xls, pdf, or txt
You are on page 1of 4
At a glance
Powered by AI
The document describes tests performed on coarse aggregates to determine their specific gravity, absorption, and other properties. Multiple samples were tested according to ASTM and BS standards.

Tests were performed to determine the specific gravity, absorption, bulk specific gravity, apparent specific gravity of coarse aggregates using methods like ASTM C127 and C128.

Properties like oven dry bulk specific gravity, SSD bulk specific gravity, apparent specific gravity, and absorption of coarse aggregates were measured.

civicon

Description
of sample:

20MM AGGREGATE

Specification:

6.1

Location

KITENGELA

Test Standard:

ASTM/BS

Date of sampling:

Station:

WRIGLEY -ATHIRIVER

Sample Received:

Sample No:

Test Doc No.: CODE

KASAN RAMJI

Source:

Date of testing:

Fine Aggregate

CONCRETE & ASPHALT WORKS

Description of sample

Test1

Pycnometer No.
-1

Wt. of Pycnometer

(g)

-2

Wt. of Pycnometer + Water

(g)

-3

Wt. of SSD sample+ water + Pycnometer

(g)

-4

Wt. of Oven Dry Sample in air

(g)

-5

Wt. of SSD sample (500 10g)

(g)

Test 2

Test 3

R6

R6

R5

Coarse Aggregate 20MM AGGREGATE


Description of sample

Test1

Container No.

Test 2

Test 3

(g)

1275.0

1269.0

-2 Wt. of container +SSD sample

(g)

2366.0

2044.0

-3 Wt. of container + Dry sample

(g)

2357.0

2026.0

-4 Wt. of SSD sample in water

(g)

817

460

-1 Wt. of container

Remarks:

Weight of sampling: ASTM C 127 - 73


Maximum agg. Size
( mm )
5/10

"

10/20
20/40
40/60
60/80

"

Min.wt. of sample
kg.
2
3
5
7
10

0.0

SPG-14-20-01
11/10/2015
11/10/2015
11/10/2015

Average

Average

CIV-T-QAC-00134A

REHABILITATION OF THE G-SECTION (KPA


MOMBASSA - PORT - KENYA)

civicon Limited

DETERMINATION OF SPECIFIC GRAVITY AND ABSORPTION OF AGGREGATE


ASTM C 127 / ASTM C 128 / BS 812:Part 2: 1975
Description
of sample:

Specification:

6.1

Location

KITENGELA

Test Standard:

ASTM/BS

Date of sampling:

11/10/2015

Station:

WRIGLEY -ATHIRIVER

Sample Received:

11/10/2015

Date of testing:

11/10/2015

Sample No:

KASAN RAMJI

Source:

Fine Aggregate

Test Doc No.: CODE

SPG-14-20-01

20MM AGGREGATE

CONCRETE & ASPHALT WORKS

Description of sample
Pycnometer No.
-1

Wt. of Pycnometer

(g)

-2

Wt. of Pycnometer + Water

(g)

-3

Wt. of SSD sample+ water + Pycnometer

(g)

-4

Wt. of Oven Dry Sample in air

(g)

-5

Wt. of SSD sample (500 10g)

(g)

-6

Oven Dry Bulk Specific Gravity , 4/(2+5-3)

-7

SSD Bulk Specific Gravity 5/(2+5-3 )

-8

Apparent Specific Gravity , 4/ ( 2+4-3 )

-9

Absorption , [ ( 5-4)/4]*100

Test1

Test 2

Test 3

R6

R6

R5

Average

#DIV/0!

(%)

#DIV/0!

Coarse Aggregate
Description of sample
Container No.

Test1

Test 2

Test 3

Average

-1 Wt. of container

(g)

1275

1269

-2 Wt. of container +SSD sample

(g)

2366

2044

-3 Wt. of container + Dry sample

(g)

2357

2026

-4 Wt. of SSD sample in water

(g)

817

460

-5 Wt. of SSD sample in air = 2 - 1

(g)

1091

775

-6 Wt. of dry sample in air = 3 - 1

(g)

1082.0

757.0

-7 Bulk specific gravity = 6 / (5 - 4 )

3.949

2.403

3.176

-8 SSD bulk specific gravity = 5 / ( 5 - 4 )

3.982

2.460

3.221

-9 Apparent Specific Gravity = 6 / ( 6 - 4 )

4.083

2.549

3.316

0.832

2.378

1.6

-10 Absorption = [ ((2) - (3)) / (6) ] * 100

Remarks:

Weight of sampling: ASTM C 127 - 73


Maximum agg. Size
( mm )
5/10

"

10/20
20/40
40/60
60/80

"

Min.wt. of sample
kg.
2
3
5
7
10

civicon CONTRACTOR

Spe.gravity.axls

(%)

HOWARD HUMPHREYS CONSULTANT

CIV-T-QAC-00134A

REHABILITATION OF THE G-SECTION (KPA


MOMBASSA - PORT - KENYA)

civicon Limited

DETERMINATION OF SPECIFIC GRAVITY AND ABSORPTION OF AGGREGATE


ASTM C 127 / ASTM C 128 / BS 812:Part 2: 1975
Description
of sample:

Specification:
Test Standard:

Location

Test Doc No.: CODE


ASTM/BS

Sample No:

Station:

Date of sampling:
Sample Received:
Date of testing:

Source:

Fine Aggregate

CONCRETE & ASPHALT WORKS

Description of sample

Average

Pycnometer No.
-1

Wt. of Pycnometer

(g)

-2

Wt. of Pycnometer + Water

(g)

-3

Wt. of SSD sample+ water + Pycnometer

(g)

-4

Wt. of Oven Dry Sample in air

(g)

-5

Wt. of SSD sample (500 10g)

(g)

-6

Oven Dry Bulk Specific Gravity , 4/(2+5-3)

-7

SSD Bulk Specific Gravity 5/(2+5-3 )

-8

Apparent Specific Gravity , 4/ ( 2+4-3 )

-9

Absorption , [ ( 5-4)/4]*100

(%)

Coarse Aggregate
Description of sample

Average

Container No.
-1 Wt. of container

(g)

-2 Wt. of container +SSD sample

(g)

-3 Wt. of container + Dry sample

(g)

-4 Wt. of SSD sample in water

(g)

-5 Wt. of SSD sample in air = 2 - 1

(g)

-6 Wt. of dry sample in air = 3 - 1

(g)

-7 Bulk specific gravity = 6 / (5 - 4 )


-8 SSD bulk specific gravity = 5 / ( 5 - 4 )
-9 Apparent Specific Gravity = 6 / ( 6 - 4 )
-10 Absorption = [ ((2) - (3)) / (6) ] * 100

Remarks:

Weight of sampling: ASTM C 127 - 73


Maximum agg. Size
( mm )
5/10

"

10/20
20/40
40/60
60/80

"

(%)

Min.wt. of sample
kg.
2
3
5
7
10

civicon CONTRACTOR

HOWARD HUMPHREYS CONSULTANT