Advantech AE Technical Share Document

Date
Category
Abstract
Keyword
Related Product

2015 / 08 / 12
FAQ SOP

SR#
Related OS

How To Setup WebOP and S7-300 MPI Port


S7-300/ MPI
WOP-2000 Series/ WOP-3000 Series

Problem Description:

This tech note introduces how to connect Siemens S7-300 MPI Port with WebOP Designer HMI.

MPI Port
<S7-300 CPU>

Brief Solution - Step by Step:


Note: Panel Express doesnt support MPI Port driver

1) PLC Parameter setting:


Execute the STEP7 software to link with the S7-300 CPU via PC Adapter program cable.

Create a new project follow below steps and set the CPU communication format.

Page 1

<Create the S7-300 Station>

<Enter Hardware option>

<Insert a Rail from RACK option>

Page 2

<Insert a CPU unit into slot2, double it enter the properties window.>
Under CPU properties window, you can see the standard transmission rate is 187.5Kbps. Please use it to
link with PV series HMI directly.

Page 3

Connection Cable diagram


HMI Side
COM1 9-PIN Male
485 +
485 SG

1
6
5

PLC Cable Side


MPI Port 9-PIN Male
(RS485)
3
485+
8
4855
SG

1
4
5

PLC Cable Side


MPI Port 9-PIN Male
(RS485)
3
485+
8
4855
SG

HMI Side
COM2 T.B. 5-PIN
485 TX+
485 TXSG

Note:
We will suggest you the PLC and HMI address node do not set 0 or 1:
Node 0: reserve for PC / WinCC
Node 1: Step7 Software
2) HMI setting:
Select Device/Server Siemens AG Simatic S7-300 (MPI Port)

NOTE: WebOP Driver named as C39021.dll and C39021.mod

Page 4

Set the HMI link port parameter identical with PLC communication parameter

3) PLC Memory Address


Bit Devices:

NOTE: Device named DBXn.b specified same as DB10.DBXn.b.

Page 5

Word Devices:

NOTE: Device named DBDn/VDn specified same as DB10.DBDn

Reference:
N/A

Page 6