Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Instructions 95-8578: Multispectrum IR Flame Detector With Pulse Output X3302

Download as pdf or txt
Download as pdf or txt
You are on page 1of 36

Instructions

95-8578
Multispectrum IR Flame Detector
with Pulse Output
X3302

6.1

Rev: 12/13

95-8578

Table of Contents
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . 15

Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

oi (Optical Integrity) . . . . . . . . . . . . . . . . . . . . . .

MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . 16

Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 3

oi Plate Removal and Replacement . . . . . . . .

Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

Periodic Checkout Procedure . . . . . . . . . . . . . . 17

Integral Wiring Compartment . . . . . . . . . . . . . . . 3

Clock Battery . . . . . . . . . . . . . . . . . . . . . . . . . . 17

16

Detector Sensitivity Levels . . . . . . . . . . . . . . . . . 3


FEATURES . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
General Application Information . . . . . . . . 4
Response Characteristics . . . . . . . . . . . . . . . . . . 4

SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . 17

Important Application Considerations . . . . . . . . . 4


REPLACEMENT PARTS . . . . . . . . . . . . . . . . . . . . . 19
Important Safety Notes . . . . . . . . . . . . . . . . . 4
DEVICE REPAIR AND RETURN . . . . . . . . . . . . . . 19
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Detector Positioning . . . . . . . . . . . . . . . . . . . . . . 5

ORDERING INFORMATION . . . . . . . . . . . . . . . . . . 19

Detector Orientation . . . . . . . . . . . . . . . . . . . . . . 6

Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

Protection Against Moisture Damage . . . . . . . . . 6

X3302 Model Matrix . . . . . . . . . . . . . . . . . . . . . 20

Startup Procedure . . . . . . . . . . . . . . . . . . . . 14
Manual oi Test (Output to Controller) . . . . . . . . . 14

APPENDIX A FM Approval AND


PERFORMANCE REPORT . . . . . . . . . . . . . . . . . . . 21

Count Test Mode (Output to Controller) . . . . . . . 14

APPENDIX B csa APPROVAL . . . . . . . . . . . . . . 29

Fire Alarm Test (Pulse Output to Fire Alarm Panel) . . 15

APPENDIX C ATEX / CE Approval . . . . . . . . . 30


APPENDIX D iecex Approval . . . . . . . . . . . . . 32
APPENDIX E ADDITIONAL ApprovalS . . . . . . 33

INSTRUCTIONS

Multispectrum IR Flame Detector


with Pulse Output
X3302
Important
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
ATTENTION
The X3302 includes the Automatic oi (Optical
Integrity) feature a calibrated performance test
that is automatically performed once per minute
to verify complete detector operation capabilities.
Testing with an external test lamp is not
approved or required.
The X3302 with pulse/relay output is designed for use
in controller based systems. In addition to use in new
systems, it can serve as a direct field replacement
for Detector Electronics Corporations (Det-Tronics)
controller based flame detectors that generate a pulse
output (not compatible with R7484 and R7409B/C).

DESCRIPTION
The X3302 brings multispectrum infrared (MIR) flame
detection to hydrogen-bearing fuels lacking carbon such
as hydrogen, arsine, silane and ammonia as well as light
hydrocarbons like methanol and methane. The result is
unsurpassed flame sensitivity and discrimination of nonflame sources in situations where existing multispectrum
IR detectors are unsuitable.

When used as a field replacement, all operating features


of the current controller are retained in addition to gaining
the advanced features of the X3302 Flame Detector. In
typical applications, the four wire X3302 can utilize all
existing system wiring.

Utilizing the X3301s multi-patented signal processing


algorithms, the X3302 provides a breakthrough in flame
detection of hazardous materials that produce mostly
water vapor, and little or no Carbon Dioxide (CO2) in the
combustion process. The detection capability of the
X3302 is double that of traditional UV and UVIR detectors.
At the same time, it attains complete solar resistance and
insensitivity to artificial lights, lightning, and blackbody
radiation, which still plague other detection technologies.

The detector has Division and Zone explosion-proof


ratings and is suitable for use in indoor and outdoor
applications.
A tri-color LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions.
Microprocessor controlled heated optics increase
resistance to moisture and ice.
The X3302 housing is available in copper-free aluminum
or stainless steel, with NEMA/Type 4X and IP66/IP67
rating.

6.1

Detector Electronics Corporation 2013

Rev: 12/13

95-8578

Outputs

oi (Optical Integrity)

Relays

Automatic oi

The detector is furnished with fire and fault relays. The


relays are rated 5 amperes at 30 Vdc.

The X3302 includes the Automatic oi feature a


calibrated performance test that is automatically
performed once per minute to verify complete detector
operation capabilities. No testing with an external test
lamp is required. The detector automatically performs
the same test that a maintenance person with a test
lamp would perform once every minute. However, a
successful Automatic oi test does not produce an alarm
condition.

The Fire Alarm relay has redundant terminals and normally


open / normally closed contacts, normally de-energized
operation, and latching or non-latching operation.
The Fault relay has redundant terminals and normally
open contacts, normally energized operation, and
latching or non-latching operation.

The X3302 signals a fault condition when less than half


of the detection range remains. This is indicated by the
Fault output and is evident by the yellow color of the
LED on the face of the detector. The oi fault condition
is self-clearing if the optical contamination is temporary.
If the contamination is not automatically cleared and the
oi fault remains, the detector may require cleaning or
service. See the Troubleshooting section for further
information.

Latching relays can be reset by removing input power


(0.1 second minimum).
An alarm condition will normally over-ride a fault condition,
unless the nature of the fault condition impairs the ability
of the detector to generate or maintain an alarm output,
i.e. loss of operating power.
LED

Magnetic oi / Manual oi

A tri-color LED on the detector faceplate indicates


normal condition and notifies personnel of fire alarm
or fault conditions. Table 1 indicates the condition of the
LED for each status.

CAUTION
These tests require disabling of all extinguishing
devices to avoid release resulting from a
successful test.
The detector also incorporates both Magnetic oi (Mag
oi) and Manual oi (Man oi) test capabilities. These

Table 1Detector Status Indicator

Detector Status

LED Indicator

Power On/Normal Operation


(no fault or fire alarm)

Green

Fault

Yellow

Fire (Alarm)

Red

Low Sensitivity

One Yellow Flash


During Power-up

Medium Sensitivity

Two Yellow Flashes


During Power-up

High Sensitivity

Three Yellow Flashes


During Power-up

Very High Sensitivity

Four Yellow Flashes


During Power-up

tests provide pulses (80 to 100 CPS) to the controller


(R7404 or R7494) when the detector is not in fault. If the
test is successful, the controller indicates a fire and the
appropriate zone output is active.
NOTE
If the detector is in a fault condition, a successful
Mag o i or Man o i test cannot be performed.

The Mag oi test is performed by placing a magnet at the


location marked MAG OI on the outside of the detector
(see Figure 2). This action causes the detector to
immediately send pulses to the controller. Controller
response is as follows:

The Zone LED blinks.

The digital display indicates which Zone is in alarm.

The status indicator shows 6 (fire).


important
Mag o i can be performed with the controllers
(R7404/R7494) keylock switch in either the
Normal or Test position. In Normal, the
controller goes into alarm and activates its outputs.
If no controller alarm output is desired, place
the keylock switch in the Test position before
touching the magnet to the outside of the detector.
Man o i operates only with the keylock switch in
the Test position.

6.1

95-8578

During the entire test, the detector gives no indication of


alarm.

Detector Sensitivity Levels


There are four factory configured sensitivity levels
available for the X3302 Flame Detector:

To reset the controller status and alarms, place the


keylock switch in Reset. Return the keylock switch to
Normal when testing is complete.

Very High, High, Medium, and Low.


The following criteria should be considered when
choosing a sensitivity level for the intended application:

The Man oi test is nearly identical to the Mag oi test,


except for the manner in which the test is initiated:

Detector placement

Speed of response based on fuel type and fire size


(see Appendix A for response times)
Distance between the hazard and the flame
detector

Place the keylock switch on the controller (R7404/


R7494) in the Test position.

Press the Select button to select the appropriate


detector for test.

Press the Test/Accept button to initiate the test.

Recommended sensitivity guidelines are as follows:

Controller and detector responses are identical to the


Mag oi test described above.
To reset the controller status and alarms, place the
keylock switch in Reset. Return the keylock switch to
Normal when testing is complete.

Very High:

Aerospace, Hydrogen Storage

High:

Fertilizer (indoor), Refrigerants,


Compressors, Battery Manufacturing

Medium:
General Duty, Fertilizer (outdoor),
Ammonia, Refrigerants
Low:
Hydrogen Fueling Stations, Turbine
Enclosures

NOTE
Refer to Appendix A for FM verification of the
o i function.

Additional information on X3302 Flame Detector


performance results and sensitivities can be found in
Appendix A, the FM Approval and Performance Report.

Communication
The X3302 is furnished with an RS-485 interface for
communicating status and other information with external
devices. The RS-485 supports MODBUS protocol, with
the detector configured as a slave device.

Consult the factory with any questions on how to choose


the optimum sensitivity level for the intended application.

Data Logging
Data logging capability is also provided.
Status
conditions such as normal, power down, general and
oi faults, fire alarm, time and temperature are recorded.
Each event is time and date stamped, along with the
temperature and input voltage. Event data is stored in
non-volatile memory when the event becomes active,
and again when the status changes. Data is accessible
using the Inspector Connector accessory or RS-485.
Integral Wiring Compartment
All external wiring to the device is connected within the
integral junction box. The detector is furnished with four
conduit entries, with either 3/4 inch NPT or M25 threads.

6.1

95-8578

GENERAL APPLICATION INFORMATION

Important Safety Notes

Response Characteristics

Warning
Do not open the detector assembly in a hazardous
area when power is applied. The detector contains
limited serviceable components and should never
be opened. Doing so could disturb critical optical
alignment and calibration parameters, possibly
causing serious damage.

Response is dependent on the detectors sensitivity


setting, distance, type of fuel, temperature of the fuel,
and time required for the fire to come to equilibrium. As
with all fire tests, results must be interpreted according
to an individual application.
See Appendix A for third-party approved fire test results.
Additional fire test results are available from Det-Tronics.

Caution
The wiring procedures in this manual are intended
to ensure proper functioning of the device under
normal conditions. However, because of the
many variations in wiring codes and regulations,
total compliance to these ordinances cannot be
guaranteed. Be certain that all wiring complies
with the NEC as well as all local ordinances. If
in doubt, consult the authority having jurisdiction
before wiring the system. Installation must be
done by a properly trained person.

Important Application Considerations


In applying any type of sensing device as a fire detector,
it is important to know of any conditions that can prevent
the device from responding to fire, and also to know
what other sources besides fire can cause the device to
respond.
Welding
Arc welding should not be performed within 20
feet (6.0 m) of the detector configured to very high
sensitivity, within 15 feet (4.6 m) at high sensitivity,
within 10 feet (3.0 m) at medium sensitivity, or within 5
feet (1.5 m) at low sensitivity. Gas welding mandates
system bypass, since the gas torch is an actual fire.
Arc welding rods can contain organic binder materials
in the flux that burn during the welding operation
and are detectable by the X3302. Welding rods with
clay binders do not burn and will not be detected
by the X3302. However, system bypass is always
recommended, since the material being welded may
be contaminated with organic substances (paint, oil,
etc.) that will burn and possibly cause the X3302 to
alarm.

Caution
To prevent unwanted actuation or alarm,
extinguishing devices must be disabled prior to
performing system tests or maintenance.
Caution
The multispectrum IR flame detectors are to be
installed in places where the risk of mechanical
damage is low.
Attention
Remove the protective cap from the front of the
detector before activating the system.
Attention
Observe precautions for handling electrostatic
sensitive devices.

Artificial Lighting
The X3302 should not be located within 2 feet (0.6 m)
of artificial lights. Excess heating of the detector could
occur due to heat radiating from the lights.
EMI/RFI Interference
The X3302 is resistant to interference by EMI and RFI,
and is EMC Directive compliant. It will not respond to a 5
watt walkie-talkie at distances greater than 1 foot (0.3 m).
Do not operate a walkie-talkie within 1 foot (0.3 m) of the
X3302.
Carbon Containing Fires
The X3302 is a multiple spectrum IR device with detection
limited to flames that produce water vapor as a by-product
of combustion. These include hydrogen, ammonia,
arsine, silane, and light hydrocarbons such as methane
and methanol. Some lighter carbonaceous fuels may be
detectable by the X3302, but heavier carbon containing
substances that burn with a dark yellow-orange flame
and emit dense sooty smoke may not be sensed with this
device. Other fuels that are not detectable include sulfur
and burning metals.
6.1

95-8578

Installation
NOTE
The recommended lubricant for threads and
O-rings is a silicone free grease (p/n 005003001) available from Det-Tronics. Under no
circumstances should a lubricant containing
silicone be used.

CENTER AXIS
OF DETECTOR
FIELD OF VIEW

INCORRECT

Detector Positioning
Detectors should be positioned to provide the best
unobstructed view of the area to be protected. The
following factors should also be taken into consideration:

Identify all high risk fire ignition sources.

Be sure that enough detectors are used to adequately


cover the hazardous area.

Be sure that the unit is easily accessible for cleaning


and other periodic servicing.

Verify that all detectors in the system are properly


located and positioned so that any fire hazards are
within both the Field of View (FOV) and detection
range of the detector. The Q1201C Laser Aimer
is recommended for establishing the detectors
FOV. Refer to Appendix A for specific information
regarding detector range and FOV.

CORRECT

The detector should be aimed downward at least 10


to 20 degrees to allow lens openings to drain. See
Figure 1. The detector should be positioned so
that its FOV does not cover areas outside the
hazardous area. This will minimize the possibility
of false alarms caused by activities outside the area
requiring protection.

The detector must be mounted on a rigid surface in


a low vibration area.

D1974

NOTE: DETECTOR MUST ALWAYS BE AIMED


DOWNWARD AT LEAST 10 TO 20 DEGREES.

Figure 1Detector Orientation Relative to Horizon

Multispectrum IR detectors are less likely than


other detectors to false alarm to non-flame infrared
sources, as verified by the data shown in the False
Alarm Immunity table (page 24) in Appendix A.
However, in some instances, sustained modulation
of these sources will cause a level of desensitization
resulting in diminished detection range (refer to
Modulated Source table on page 24). For this
reason, the X3302 should be sited/located to
avoid these sources if there is likely to be frequent,
sustained modulation of IR sources such as those
shown. It is important to point out that these same
sources have no effect on sensitivity if there is no
modulation (refer to Unmodulated Source table on
page 24).

6.1

CENTER AXIS
OF DETECTOR
FIELD OF VIEW

Dense fog, rain or ice can absorb IR radiation and


reduce the sensitivity of the detector. To ensure
optimum performance, be certain that the internal
optical heater is enabled on detectors that are used
in applications where snow, ice, and/condensation
are likely to occur.

Although IR detectors are less affected by smoke


than other detectors, the X3302 should not be placed
where rising combustion products can obscure
its vision. If smoke is expected before fire, smoke
or other alternative detectors should be used in
conjunction with the X3302. For indoor applications,
if dense smoke is expected to accumulate at the
onset of a fire, mount the detector on a side wall at
least a few feet (approximately 1 meter) down from
the ceiling.

If possible, fire tests can be conducted to verify


correct detector positioning and coverage.

For ATEX installations, the X3302 Flame Detector


housing must be electrically connected to earth
ground.

95-8578

Detector Orientation

Wiring Procedure

Refer to Figure 2 and ensure that the oi plate will be


oriented as shown when the X3302 is mounted and
sighted. This will ensure proper operation of the oi
system and will also minimize the accumulation of
moisture and contaminants between the oi plate and the
viewing windows.

Wire Size and Type


The system should be wired according to local codes.
The wire size selected should be based on the number
of detectors connected, the supply voltage, and the
cable length. Typically 16 AWG or 2.5 mm2 shielded
cable is recommended. Wires should be stripped
3/8 inch (9 mm). In some cases where the X3302 is
replacing existing pulse output detectors, the wiring
and power supplies may not be adequate. Consult the
factory for assistance.

IMPORTANT
If removed, the o i plate must be securely
tightened to ensure proper operation of the o i
system (40 oz./inches [28.2 N . cm] recommended).

IMPORTANT
A minimum input voltage of 18 Vdc must be
present at the X3302.
The use of shielded cable is required to protect against
interference caused by EMI and RFI. When using cables
with shields, terminate the shields as shown in Figures 6
through 10. Consult the factory if not using shielded cable.

oi PLATE
PLACE MAGNET
HERE TO INITIATE
MAGNETIC oi
VIEWING WINDOW (3)

The B (pulse output) and D (oi driver) leads from


each detector should be shielded from the B and
D leads of all other detectors in order to prevent
false alarms resulting from crosstalk between zones.
It is recommended that the A and C leads also be
shielded to provide maximum immunity to EMI/RFI. (See
Figures 6 to 10.)

oi MAGNET
F2068

DETECTOR
STATUS INDICATOR

Figure 2Front View of the X3302

In applications where the wiring cable is installed in


conduit, the conduit must not be used for wiring to other
electrical equipment.
If disconnection of power is required, separate disconnect
capability must be provided.

Protection Against Moisture Damage


It is important to take proper precautions during
installation to ensure that moisture will not come in contact
with the electrical connections or components of the
system. The integrity of the system regarding moisture
protection must be maintained for proper operation and
is the responsibility of the installer.

CAUTION
Installation of the detector and wiring should be
performed only by qualified personnel.

If conduit is used, we recommend installing drains,


according to local codes, at water collection points to
automatically drain accumulated moisture. It is also
recommended to install at least one breather, according
to local codes, at upper locations to provide ventilation
and allow water vapor to escape.

Detector Mounting
Install the mounting arm assembly on a rigid surface.
The ideal installation surface should be free of vibration
and suitable to receive 3/8 inch or M10 bolts with a
length of at least 1 inch (25 mm). The surface must
also have sufficient capacity to hold the detector and
mounting arm weights (see Specifications section).
Refer to the Q9033 Mounting Arm and Collar Attachment
manual (95-8686) for additional mounting information.
See Figure 3 for dimensions.

Conduit raceways should be inclined so that water will


flow to low points for drainage and will not collect inside
enclosures or on conduit seals. If this is not possible,
install conduit drains above the seals to prevent the
collection of water or install a drain loop below the
detector with a conduit drain at the lowest point of the
loop.
Conduit seals are not required for compliance with
explosion-proof installation requirements, but are highly
recommended to prevent water ingress in outdoor
applications. Units with M25 threads must use an IP66/
IP67 washer to prevent water ingress.
6.1

95-8578

4X 0.42
(1.1)

3.0
(7.6)

4.0
(10.2)

13.1
(33.3)
NOTE: THIS ILLUSTRATION SHOWS THE
DETECTOR MOUNTED AT THE 10 MINIMUM.
THESE DIMENSIONS WILL CHANGE BASED
ON THE DETECTORS MOUNTING ANGLE.

3.0
(7.6)
4.0
(10.2)

10.6
(27.0)

F2069

Figure 3Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation.)

Detector Wiring

19

IMPORTANT
If installing an X3302 in place of an existing
detector, be sure to move the A Lead (detector
power) at the controller from the +290 Vdc source
to the +24 Vdc source. Do not apply 290 Vdc to
the X3302.

18

1. Make field connections following local ordinances


and guidelines in this manual.

Figure 4 shows the wiring terminal strip located


inside the detectors integral junction box.

Figure 5 shows the wiring terminal identification for


the X3302 Flame Detector with pulse output.

29

SPARE

28

SPARE

COM FIRE

17

COM FIRE

27

N.O. FIRE

16

N.O. FIRE

26

N.C. FIRE

15

N.C. FIRE

25

COM FAULT

14

COM FAULT

24

RS-485 A

N.O. FAULT

13

N.O. FAULT

23

RS-485 B

24 VDC +

12

24 VDC +

22

MAN Oi

24 VDC

11

24 VDC

21

24 VDC
B2070

Figure 5X3302 Pulse Wiring Terminal Identification

Leave the shield open at the detector end and


permanently isolate it from accidental contact with
the case and/or other conductors. At the controller/
fire panel end, connect the shield and power minus
() to chassis (earth) ground either directly or
through a 0.47 F 400 Volt non-polarized capacitor
(not supplied). (Refer to Figures 6 through 10.)

Figures 11 and 12 provide examples of typical


installations with a X3302 wired to a fire alarm
panel.

Figure 13 shows an EOL resistor installed within the


integral wiring compartment of the detector (refer to
EOL Resistors for details).

2. Check all field wiring to be sure that the proper


connections have been made.

Figure 4X3302 Terminal Block


6.1

PULSE OUT

95-8578

Important
Do not test any wiring connected to the detector
with a meg-ohmmeter. Disconnect wiring at
the detector before checking system wiring for
continuity.
3. Make the final sighting adjustments and use a 14
mm hex wrench to ensure that the mounting arm
assembly is tight.

NOTE: DO NOT CONNECT THE X3302 "A" LEAD (#2/12) TO


TERMINAL J1-3 (290 VDC).

X3302

#2
#1
#19
#22

#2
#1
#19
#22

DETECTOR 1

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-5
J1-13

DETECTOR 2

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-6
J1-14

DETECTOR 3

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-7
J1-15

DETECTOR 4

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-8
J1-16

DETECTOR 5

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-9
J1-17

DETECTOR 6

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-10
J1-18

DETECTOR 7

X3302

#2
#1
#19
#22

#2
#1
#19
#22

24
VDC

J1

J2

R7404 CONTROLLER
ZONE OUTPUT 1

33

ZONE OUTPUT 2

34

(A) +290 VDC

ZONE OUTPUT 3

35

B - INPUT 1

ZONE OUTPUT 4

36

B - INPUT 2

ZONE OUTPUT 5

37

B - INPUT 3

ZONE OUTPUT 6

38

B - INPUT 4

ZONE OUTPUT 7

39

B - INPUT 5

ZONE OUTPUT 8

40

B - INPUT 6

FIRE LOGIC A

41

10

B - INPUT 7

FIRE LOGIC B

42

11

B - INPUT 8

ALARM OUTPUT

43

12

D1-1 oi DRIVER

EXTERNAL RESET/INHIBIT

44

13

D1-2 oi DRIVER

OUTPUTS INHIBITED

45

14

D1-3 oi DRIVER

FAULT OUTPUT

46

15

D1-4 oi DRIVER

EXTERNAL ACCEPT

47

16

D1-5 oi DRIVER

STATUS & DET. OUTPUT S1

48

17

D1-6 oi DRIVER

STATUS & DET. OUTPUT S2

49

18

D1-7 oi DRIVER

STATUS & DET. OUTPUT S3

50

19

D1-8 oi DRIVER

STATUS & DET. OUTPUT S4

51

20

D2-1 oi DRIVER

STATUS & DET. OUTPUT S5

52

21

D2-2 oi DRIVER

STATUS & DET. OUTPUT S6

53

22

D2-3 oi DRIVER

STATUS & DET. OUTPUT S7

54

23

D2-4 oi DRIVER

STATUS & DET. OUTPUT S8

55

24

D2-5 oi DRIVER

DATA BUS 0

56

25

D2-6 oi DRIVER

DATA BUS 1

57

26

D2-7 oi DRIVER

DATA BUS 2

58

27

D2-8 oi DRIVER

DATA BUS 3

59

28

DMA OUT AVAILABLE

DATA BUS 4

60

29

DMA OUT

DATA BUS 5

61

30

DMA IN

DATA BUS 6

62

31

DATA STROBE

DATA BUS 7

63

32

DMA IN AVAILABLE

} 10 TO 38 VDC

CHASSIS (EARTH) GND

64
A2266

J1-11
J1-19

DETECTOR 8

TO J1-2
TERMINAL IDENTIFICATION FOR X3302
WITH PULSE OUTPUT.
TERMINAL NO.

FUNCTION

1/11

DC ("C" LEAD)

2/12

DC+ ("A" LEAD)

19

SIGNAL ("B" LEAD)

22

oi ("D" LEAD)

NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED


TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 F 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.

62

NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.

64

63

0.47 F / 400 VDC


NON-POLARIZED

NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE


0.5 REQUIREMENTS (SIGNALING LINES A AND C).

GROUND FAULT PROTECTED SYSTEMS

Figure 6A Typical System, X3302 Detectors Wired to R7404 Controller

6.1

95-8578

NOTE: DO NOT CONNECT THE X3302 "A" LEAD (#2/12) TO


TERMINAL J1-3 (290 VDC).

X3302

#2
#1
#19
#22

#2
#1
#19
#22

DETECTOR 1

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-5
J1-13

DETECTOR 2

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-6
J1-14

DETECTOR 3

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-7
J1-15

DETECTOR 4

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-8
J1-16

DETECTOR 5

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-9
J1-17

DETECTOR 6

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-10
J1-18

DETECTOR 7

X3302

24
VDC

J1

+24 VDC

ZONE OUTPUT 1

33

CIRCUIT GROUND

ZONE OUTPUT 2

34

+290 VDC

ZONE OUTPUT 3

35

B1 - INPUT SIGNAL

ZONE OUTPUT 4

36

B2 - INPUT SIGNAL

ZONE OUTPUT 5

37

B3 - INPUT SIGNAL

ZONE OUTPUT 6

38

B4 - INPUT SIGNAL

ZONE OUTPUT 7

39

B5 - INPUT SIGNAL

ZONE OUTPUT 8

40

B6 - INPUT SIGNAL

FIRE LOGIC A

41

10

B7 - INPUT SIGNAL

FIRE LOGIC B

42

11

B8 - INPUT SIGNAL

ALARM OUTPUT

43

12

D1 oi DRIVER

EXTERNAL RESET/INHIBIT

44

13

D2 oi DRIVER

OUTPUTS INHIBITED

45

14

D3 oi DRIVER

FAULT OUTPUT

46

15

D4 oi DRIVER

EXTERNAL ACCEPT

47

16

D5 oi DRIVER

STATUS & DET. OUTPUT S1

48

17

D6 oi DRIVER

STATUS & DET. OUTPUT S2

49

18

D7 oi DRIVER

STATUS & DET. OUTPUT S3

50

19

D8 oi DRIVER

STATUS & DET. OUTPUT S4

51

20

DATA BUS OUT

STATUS & DET. OUTPUT S5

52

21

DATA BUS OUT

STATUS & DET. OUTPUT S6

53

22

DATA BUS OUT

STATUS & DET. OUTPUT S7

54

23

DATA BUS OUT

STATUS & DET. OUTPUT S8

55

24

DATA BUS OUT

DATA BUS 0

56

25

DATA BUS OUT

DATA BUS 1

57

26

DATA BUS OUT

DATA BUS 2

58

27

DATA BUS OUT

DATA BUS 3

59

28

NOT USED

DATA BUS 4

60

29

NOT USED

DATA BUS 5

61

30

DATA STROBE IN

DATA BUS 6

62

31

NOT USED

DATA BUS 7

63

32

NOT USED

EARTH GROUND

J2

R7404 STAR LOGIC CONTROLLER

64
A2267

#2
#1
#19
#22

#2
#1
#19
#22

J1-11
J1-19

DETECTOR 8
TO J1-2

TERMINAL IDENTIFICATION FOR X3302


WITH PULSE OUTPUT.
TERMINAL NO.

FUNCTION

1/11

DC ("C" LEAD)

2/12

DC+ ("A" LEAD)

19

SIGNAL ("B" LEAD)

22

oi ("D" LEAD)

62

NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED


TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 F 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.

63

0.47 F / 400 VDC


NON-POLARIZED

64

NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.


NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).

GROUND FAULT PROTECTED SYSTEMS

Figure 7A Typical System, X3302 Detectors Wired to R7404 Star Logic Controller

6.1

95-8578

X3302

#2
#1
#19
#22

#2
#1
#19
#22

DETECTOR 1

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-5
J1-13

DETECTOR 2

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-6
J1-14

DETECTOR 3

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-7
J1-15

DETECTOR 4

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-8
J1-16

DETECTOR 5

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-9
J1-17

DETECTOR 6

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J1-10
J1-18

DETECTOR 7

X3302

24
VDC

J1

+24 VDC

ZONE OUTPUT 1

33

CIRCUIT GROUND

ZONE OUTPUT 2

34

+24 VDC

ZONE OUTPUT 3

35

B1 - INPUT SIGNAL

ZONE OUTPUT 4

36

B2 - INPUT SIGNAL

ZONE OUTPUT 5

37

B3 - INPUT SIGNAL

ZONE OUTPUT 6

38

B4 - INPUT SIGNAL

ZONE OUTPUT 7

39

B5 - INPUT SIGNAL

ZONE OUTPUT 8

40

B6 - INPUT SIGNAL

FIRE LOGIC A

41

10

B7 - INPUT SIGNAL

FIRE LOGIC B

42

11

B8 - INPUT SIGNAL

ALARM OUTPUT

43

12

D1 oi DRIVER

EXTERNAL RESET/INHIBIT

44

13

D2 oi DRIVER

OUTPUTS INHIBITED

45

14

D3 oi DRIVER

FAULT OUTPUT

46

15

D4 oi DRIVER

EXTERNAL ACCEPT

47

16

D5 oi DRIVER

STATUS & DET. OUTPUT S1

48

17

D6 oi DRIVER

STATUS & DET. OUTPUT S2

49

18

D7 oi DRIVER

STATUS & DET. OUTPUT S3

50

19

D8 oi DRIVER

STATUS & DET. OUTPUT S4

51

20

DATA BUS OUT

STATUS & DET. OUTPUT S5

52

21

DATA BUS OUT

STATUS & DET. OUTPUT S6

53

22

DATA BUS OUT

STATUS & DET. OUTPUT S7

54

23

DATA BUS OUT

STATUS & DET. OUTPUT S8

55

24

DATA BUS OUT

DATA BUS 0

56

25

DATA BUS OUT

DATA BUS 1

57

26

DATA BUS OUT

DATA BUS 2

58

27

DATA BUS OUT

DATA BUS 3

59

28

NOT USED

DATA BUS 4

60

29

NOT USED

DATA BUS 5

61

30

DATA STROBE IN

DATA BUS 6

62

31

NOT USED

DATA BUS 7

63

32

NOT USED

EARTH GROUND

J2

R7494 CONTROLLER

64
A2268

#2
#1
#19
#22

#2
#1
#19
#22

J1-11
J1-19

DETECTOR 8

TO J1-2
TERMINAL IDENTIFICATION FOR X3302
WITH PULSE OUTPUT.
TERMINAL NO.

FUNCTION

1/11

DC ("C" LEAD)

2/12

DC+ ("A" LEAD)

19

SIGNAL ("B" LEAD)

22

oi ("D" LEAD)

NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED


TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 F 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.

62

NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.

64

63

0.47 F / 400 VDC


NON-POLARIZED

NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE


0.5 REQUIREMENTS (SIGNALING LINES A AND C).

GROUND FAULT PROTECTED SYSTEMS

Figure 8A Typical System, X3302 Detectors Wired to R7494 Controller

6.1

10

95-8578

R7495 CONTROLLER
(NOT FM APPROVED)

X3302

#2
#1
#19
#22

#2
#1
#19
#22

24
VDC

J1

+24 VDC

GROUND

DETECTOR 1

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J2-44
J2-36

J2

31
32

DETECTOR 2

X3302

#2
#1
#19
#22

#2
#1
#19
#22

33
34

J2-45
J2-37

DETECTOR 3

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J2-46
J2-38

DETECTOR 4

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J2-47
J2-39

DETECTOR 5

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J2-48
J2-40

35

D1

36

D2

37

D3

38

D4

39

D5

40

D6

41

D7

42

D8

43

B1

44

B2

45

B3

46

B4

DETECTOR 6

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J2-49
J2-41

DETECTOR 7

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J2-50
J2-42

DETECTOR 8

47

B5

48

B6

49

B7

50

B8

A2269

TO J1-2
TERMINAL IDENTIFICATION FOR X3302
WITH PULSE OUTPUT.
TERMINAL NO.

FUNCTION

1/11

DC ("C" LEAD)

2/12

DC+ ("A" LEAD)

19

SIGNAL ("B" LEAD)

22

oi ("D" LEAD)

NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED


TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 F 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5.

NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.

NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE


0.5 REQUIREMENTS (SIGNALING LINES A AND C).

0.47 F / 400 VDC


NON-POLARIZED

GROUND FAULT PROTECTED SYSTEMS

Figure 9A Typical System, X3302 Detectors Wired to R7495 Controller

6.1

11

95-8578

NOTE: DO NOT CONNECT THE X3302 "A" LEAD (#2/12) TO


TERMINAL J2-34 (290 VDC).
R7405 CONTROLLER
(NOT FM APPROVED)

X3302

#2
#1
#19
#22

#2
#1
#19
#22

24
VDC

J1

+24 VDC

GROUND

DETECTOR 1

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J2-44
J2-36

J2

31
32

DETECTOR 2

X3302

#2
#1
#19
#22

#2
#1
#19
#22

33
J2-45
J2-37

DETECTOR 3

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J2-46
J2-38

DETECTOR 4

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J2-47
J2-39

DETECTOR 5

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J2-48
J2-40

34

+290 VDC

35

D1

36

D2

37

D3

38

D4

39

D5

40

D6

41

D7

42

D8

43

B1

44

B2

45

B3

46

B4

47

B5

48

B6

49

B7

50

B8

DETECTOR 6

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J2-49
J2-41

DETECTOR 7

X3302

#2
#1
#19
#22

#2
#1
#19
#22

J2-50
J2-42

DETECTOR 8
A2270

TO J1-2
TERMINAL IDENTIFICATION FOR X3302
WITH PULSE OUTPUT.
TERMINAL NO.

FUNCTION

1/11

DC ("C" LEAD)

2/12

DC+ ("A" LEAD)

19

SIGNAL ("B" LEAD)

22

oi ("D" LEAD)

NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED


TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 F 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5.

NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.

NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE


0.5 REQUIREMENTS (SIGNALING LINES A AND C).

0.47 F / 400 VDC


NON-POLARIZED

GROUND FAULT PROTECTED SYSTEMS

Figure 10A Typical System, X3302 Detectors Wired to R7405 Controller

6.1

12

95-8578

X3302 DETECTOR
FIRE ALARM PANEL

19

8
7
6
5

ALARM

4
3

+
24 VDC

PULSE OUT

18
COM FIRE2

SPARE

29

SPARE

28

17

N.O. FIRE2

27

16

N.C. FIRE2

26
END OF
LINE DEVICE 4

15

COM FAULT1
N.O. FAULT1
24 VDC +

14

RS-485 A

24

13

RS-485 B

23

MAN Oi

22

12

24 VDC

25

24 VDC

11

21

oi TEST 3

WIRING NOTES:

A2271

1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.

Figure 11Ex d Wiring Option

X3302 DETECTOR
FIRE ALARM PANEL

19

8
ALARM
EOL
DEVICE 4

ALARM

6
5
4
3

+
24 VDC

PULSE OUT

18
COM FIRE2
N.O. FIRE2
N.C. FIRE2
COM FAULT1
N.O. FAULT1
24 VDC +
24 VDC

SPARE

29

SPARE

28

17

27

16

26

15

25

14

RS-485 A

24

13

RS-485 B

23

MAN Oi

22

12
11

24 VDC

21

oi TEST 3

A2272

WIRING NOTES:
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE CONTACTS ARE CLOSED.
2 ALARM RELAY IS NORMALLY DE-ENERGIZED WITH NO ALARM CONDITION PRESENT.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
4 EOL RESISTOR SUPPLIED BY PANEL.

Figure 12Ex e Wiring Option

6.1

13

95-8578

Startup Procedure

EOL Resistors
To ensure that the insulating material of the wiring
terminal block will not be affected by the heat generated
by EOL resistors, observe the following guidelines when
installing the resistors.

When installation of the equipment is complete, perform


one or more of the following tests:

1. Required EOL resistor power rating must be 5 watts


minimum.
note
EOL resistors must be ceramic, wirewound
type, rated 5 watts minimum, with actual power
dissipation not to exceed 2.5 watts. This applies
to ATEX/IEC installations only.

Man oi Test Tests detector output and wiring,


without generating a fire alarm.

Count Test Mode Measures actual detector output


to controller (cps), without generating a fire alarm.

Fire Alarm Test For complete system test including


detector relays. Generates fire alarm output.

Manual oi Test (Output to Controller)


1. Place the keylock switch in the TEST position.

2. Resistor leads should be cut to a length of


approximately 1 1/2 inches (40 mm).

2. Press the SELECT button to display the desired


zone on the ZONE indicator on the front panel of the
controller.

3. Bend the leads and install the EOL resistor as shown


in Figure 13.

3. Press and hold the TEST button. The ZONE OUTPUT


LED for the tested zone flashes and the SYSTEM
STATUS display indicates a 6 (fire condition) if the
test is successful.

3/8 INCH (10 MM) GAP MINIMUM

4. Release the TEST button. The ZONE OUTPUT LED


for the tested zone should remain on steadily.
5. Return to step 2 to test the next detector.
If the system responds differently than indicated above,
proceed with the count test for the problem zone to verify
detector and wiring operation.

19 18 17 16 15 14 13 12 11
B2126

Count Test Mode (Output to Controller)

BULKHEAD

When in the Count Test mode, the frequency of the digital


pulses from the detector is displayed on the ZONE and
DETECTOR indicators on the controller faceplate. The
Count Test mode may be used to check the signal (cps)
from a test fire or false alarm source. This can be useful
during system set-up for sensitivity and time delay
settings. This test is performed in the following manner:

Figure 13EOL Resistor Installation

4. Maintain a 3/8 inch (10 mm) minimum gap between


the resistor body and the terminal block or any other
neighboring parts.

1. Place the keylock switch in the TEST position.


2. Simultaneously press and release the SELECT and
TEST buttons. The Status display will change from
a 1 to an 8 indicating that the controller is in the
Count Test mode of operation.

NOTE
The EOL resistor can only be used within the
flameproof terminal compartment. Unused
apertures shall be closed with suitable blanking
elements.

6.1

3. Press the SELECT button until the desired zone is


displayed on the ZONE indicator on the controller
front panel.

14

95-8578

4. Press and hold the TEST button. The DETECTOR/


ZONE display indicates the counts per second (cps)
received from the detector. If the counts per second
exceeds 99, the FIRE LOGIC LEDs are illuminated to
indicate that the number shown on the display must
be multiplied by 10. The normal reading for an oi
test is 80 to 110 cps. For a live fire test, 270 - 330
cps will be generated.

TROUBLESHOOTING

A zero reading may indicate a dirty window, oi problem,


faulty detector or defective wiring.

1. Disable any extinguishing


connected to the unit.

Warning
The sensor module (front half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.

Fire Alarm Test (Pulse Output to Fire Alarm Panel)


equipment

that

that

is

2. Inspect the viewing windows for contamination


and clean as necessary. The detector is relatively
insensitive to airborne contaminants, however, thick
deposits of ice, dirt, or oil will reduce sensitivity.
(Refer to the Maintenance section for complete
information regarding cleaning of the detector
viewing windows.)

Release the Test button, the ZONE and DETECTOR


display should drop to a reading of 0 to 1 counts per
second.

1. Disable any extinguishing


connected to the system.

equipment

is

3. Check input power to the unit.

2. Apply input power to the system.

4. Check system and detector logs.

3. Initiate a live fire test or a Mag oi test (see Magnetic


oi / Manual oi under Optical Integrity in the
Description section of this manual).

5. Turn off the input power to the detector and check all
wiring for continuity. Important: Disconnect wiring
at the detector before checking system wiring for
continuity.

4. Repeat this test for all detectors in the system. If


a unit fails the test, refer to the Troubleshooting
section.

6. If all wiring checks out and cleaning of the oi plate/


window did not correct the fault condition, check for
high levels of background IR radiation by covering
the detector with the factory supplied cover or
aluminum foil. If the fault condition clears within 6
minutes or less, extreme background IR is present.
Re-adjust the view of the detector away from the IR
source or relocate the detector.

5. Verify that all detectors in the system are properly


aimed at the area to be protected. (The Q1201C
Laser Aimer is recommended for this purpose.)
6. Enable extinguishing equipment when the test is
complete.

If none of these actions corrects the problem, return the


detector to the factory for repair.
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
NOTE
For additional troubleshooting guides, refer to the
Flame Inspector Monitor manual (95-8581).

6.1

15

95-8578

MAINTENANCE

LOOSEN TWO CAPTIVE SCREWS

IMPORTANT
Pe r i o d i c fl a m e p a t h i n s p e c t i o n s a re n o t
recommended, since the product is not intended
to be serviced and provides proper ingress
protection to eliminate potential deterioration of the
flamepaths.
GRASP VISOR AND
REMOVE oi PLATE

Warning
The sensor module (front half of the detector)
contains no user serviceable components
and should never be opened. The terminal
compartment is the only part of the enclosure that
should be opened by the user in the field.

B2106

Figure 14oi Plate Removal

To maintain maximum sensitivity and false alarm


resistance, the viewing windows of the X3302 must be
kept relatively clean. Refer to the following procedure for
cleaning instructions.

oi Plate Removal and Replacement

Cleaning Procedure

1. Disable any extinguishing equipment that is


connected to the unit.

CAUTION
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.

2. Loosen the two captive screws, then grasp the oi


plate by the visor and remove it from the detector.
See Figure 14.
3. Install the new (or cleaned) oi plate.

To clean the windows and oi plate, use the window


cleaner (p/n 001680-001) and a soft cloth, cotton swab,
or tissue and refer to the following procedure.

Note
When installing the stainless steel plate, ensure
that the gasket is present and correctly seated to
prevent moisture or contaminants from penetrating
behind the plate. To ensure even seating, tighten
both screws equally.

1. Disable any extinguishing equipment that is


connected to the unit.
2. Since the X3302 is less affected by contamination
than other detectors, removal of the oi plate is
needed only under extreme conditions. In addition,
it is not necessary to achieve perfect cleanliness,
because IR is not significantly absorbed by slight
films of oil and/or salt. If a fault condition is still
indicated after cleaning, remove and clean the oi
plate using the oi Plate Removal and Replacement
procedure.

4. Recalibrate the detectors oi system. Refer to the


Inspector Monitor Manual (95-8581) for instructions
regarding oi plate replacement and oi system
recalibration.
Caution
Do not replace the o i reflector plate without also
recalibrating the o i system.

3. In all environments, clean all three viewing windows


and reflector surfaces thoroughly. Use a cotton
swab and the Det-Tronics window cleaning solution.
Use Isopropyl alcohol for contaminations that the
Det-Tronics window cleaning solution can not
remove.

Recalibration of the oi system requires the use of the


Inspector Connector Cable and Inspector Monitor
Software. These two items are included in the oi
replacement kit, or they can be purchased separately.
See Ordering Information for details.

Important
When used in extreme environments, the reflective
surface of the detector o i plate may eventually
deteriorate, resulting in reoccurring o i faults and
the need for o i plate replacement.

6.1

X3302 Reflector Plates


X3302 models are supplied with either a black or a
stainless steel reflector plate. These plates are not
interchangeable. Order the replacement that matches
the reflector plate on your X3302 detector.

16

95-8578

SPECIFICATIONS

Periodic Checkout Procedure


A checkout of the system using the Man oi or Mag oi
feature should be performed on a regularly scheduled
basis to ensure that the system is operating properly. To
test the system, perform the Manual oi Test, Count
Test Mode or Fire Alarm Test as described in the
Startup Procedure section of this manual.

OPERATING VOLTAGE
24 volts dc nominal (18 Vdc minimum, 30 Vdc maximum).
Maximum ripple is 2 volts peak-to-peak.
 
For CSA compliance, the power source must
utilize a SELV (Safety Extra Low Voltage) or Class
2 style power supply.

Clock Battery
The real time clock has a backup battery that will operate
the clock with no external power. Return the device to
the factory for battery replacement if needed.

POWER CONSUMPTION
Without heater: 4 watts at 24 Vdc nominal;
4.6 watts at 24 Vdc in alarm.

4.5 watts at 30 Vdc nominal;
5.9 watts at 30 Vdc in alarm.
Heater only: 8 watts maximum.
Total Power:
17 watts at 30 Vdc with EOL resistor installed
and heater on maximum.
EOL resistor must be ceramic, wirewound type, rated
5 watts minimum, with actual power dissipation not to
exceed 2.5 watts.

NOTE
If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.

FEATURES

POWER UP TIME
Fault indication clears after 0.5 second; device is ready
to indicate an alarm condition after 30 seconds.

Unequaled false alarm rejection

Responds to a fire in the presence of modulated


blackbody radiation (i.e. heaters, ovens, turbines)
without false alarm

Pulse output for compatibility with controller based


systems

Microprocessor controlled heated optics


increased resistance to moisture and ice

Automatic, manual or magnetic oi testing

Easily replaceable oi plate

Fire and fault relays

Multiple sensitivities

Fault relay, Form A, 5 amperes at 30 Vdc:


The Fault relay has redundant terminals and
normally open contacts, normally energized
operation, and latching or non-latching operation.

A tri-color LED on the detector faceplate indicates


normal condition and notifies personnel of fire
alarm or fault conditions
Operates under adverse weather conditions and in
dirty environments

TEMPERATURE RANGE
Operating: 40F to +167F (40C to +75C).
Storage:
67F to +185F (55C to +85C).
Hazardous location ratings from 55C to +125C.

for

Mounting arm allows easy sighting

Integral wiring compartment for ease of installation.

Explosion-proof/flame-proof
detector
housing.
Meets FM, CSA, ATEX Directive , and CE certification
requirements

Class A wiring per NFPA-72 (Pulse output version is


equivalent to class A when detectors are installed in
a redundant configuration)

5 year warranty

RFI and EMC Directive Compliant

6.1

OUTPUT RELAYS
Fire Alarm relay, Form C, 5 amperes at 30 Vdc:
The Fire Alarm relay has redundant terminals and
normally open / normally closed contacts, normally
de-energized operation, and latching or nonlatching operation.

HUMIDITY RANGE
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
CONE OF VISION
The detector has a 90 cone of vision (horizontal) with
perfect cone of vision (full coverage at maximum
detection distance, both on and off axis) for hydrogen
and methanol flame detection.
Refer to Appendix A for FM Approved cone of vision data.

17

95-8578

RESPONSE TIME
Typical response times are under 10 seconds.
Appendix A for actual response times.

Thread SIZE
Conduit connection: Four entries, 3/4 inch NPT or M25.
Conduit seal not required.

See

ENCLOSURE MATERIAL
Copper-free aluminum (painted) or Stainless Steel (316/
CF8M Cast).

SHIPPING WEIGHT (Approximate)


Aluminum:
7 pounds (3.2 kilograms).
Stainless Steel:
13.8 pounds (6.3 kilograms).
Mounting Arm (AL): 6 pounds (2.75 kilograms).
Mounting Arm (SS): 14 pounds (6.4 kilograms).

Vibration
Conformance per FM 3260: 2000, MIL-STD 810C (Curve
AW).

WARRANTY PERIOD
5 years.

DIMENSIONS
See Figure 15.

CERTIFICATION

WIRING
Field wiring screw terminals are UL/CSA rated for up to
14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire.
Screw terminal required torque range is 3.54.4 in.-lbs.
(0.4-0.5 Nm).
Important: 18 Vdc minimum must be available at the
detector. For ambient temperatures below 10C (14F)
and above +60C (140F) use field wiring suitable for
both minimum and maximum ambient temperature.

FM

APPROVED

For complete approval details, refer to the appropriate


Appendix:
Appendix A - FM
Appendix B - CSA
Appendix C - ATEX/CE
Appendix D - IECEx
Appendix E - Additional approvals

4.7
(11.9)

B2067

10.0
(25.4)

4.8
(12.2)

Figure 15X3302 Dimensions in Inches (cm)

6.1

18

95-8578

REPLACEMENT PARTS

ORDERING INFORMATION

The detector is not designed to be repaired in the field.


If a problem should develop, refer to the Troubleshooting
section. If it is determined that the problem is caused by
an electronic defect, the device must be returned to the
factory for repair.

When ordering, please specify:


X3302 Multispectrum IR Flame Detector with Pulse Output
Refer to the X3302 Model Matrix for details
Q9033 Mounting Arm is required:
Q9033A for aluminum detectors only
Q9033B for aluminum and stainless steel detectors

Replacement Parts
Part Number

Description

009208-003

oi Replacement kit for X3302 (5 Black Reflector Plates)


with Inspector Connector and Monitor
oi Replacement kit for X3302 (5 Stainless Steel Reflector Plates)
with Inspector Connector and Monitor
Replacement oi Reflector Plate for X3302 with Black plate
(requires Inspector Connector to calibrate)
Replacement oi Reflector Plate for X3302 with Stainless Steel
plate (requires Inspector Connector to calibrate)

010831-002
007307-003
010830-002

Accessories
Part Number

Description

000511-029
103881-001

Converter RS485 to RS232


Converter RS485 to USB
W6300B1002 Serial Inspector Connector
(Inspector Monitor software included)
W6300B1003 USB Inspector Connector
(Inspector Monitor software included)
Flame Inspector Monitor CD
Model 475 HART Communicator
Magnet
Magnet and Adapter for Extension Pole
Magnet and Extension Pole
Q1116A1001, Air Shield (AL)
Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS)
Q1120A1001 Paint Shield mounting ring (AL)
Q1130A1001 Flange Mount Assembly
Q1201 Laser
Laser Battery, 3V Lithium (laser)
Q1201C1001 X-Series Laser Holder (AL/Plastic)
Q2000A1001 X-Series Weather Shield (AL)
Q2033A10R X3301/X3302 FOV Limiter 10 (AL)
Q2033A20R X3301/X3302 FOV Limiter 20 (AL)
Q2033A30R X3301/X3302 FOV Limiter 30 (AL)
Spare Restrictor Plate 10 (AL)
Spare Restrictor Plate 20 (AL)
Spare Restrictor Plate 30 (AL)
Q9033B Stainless Steel Mounting Arm Assembly is for
aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum
detectors only
Q9033 Collar Attachment
Stop Plug, 3/4 NPT, AL
Stop Plug, 3/4 NPT, SS
Stop Plug, M25, AL, IP66
Stop Plug, M25, SS, IP66
Stop Plug, 20 Pack, 3/4NPT, AL
Stop Plug, 20 Pack, 3/4NPT, SS
Stop Plug, 20 Pack, M25, AL, IP66
Stop Plug, 20 Pack, M25, SS, IP66
14 mm Hex Wrench (Steel)
Screwdriver
O-ring - Rear Cover (Viton)
1 oz grease for detectors (non-silicon)
Window cleaner (6 pack)

007819-001
007819-002
009207-001
103922-001
102740-002
008082-001
007739-001
007240-001
007818-001
007818-002
009177-001
010857-001
006097-001
102871-001
007255-001
007338-001
007338-010
007338-020
007338-030
007912-010
007912-020
007912-030

NOTE: Refer to Instruction Manual 95-8530 to determine the correct oi Replacement Plate.

DEVICE REPAIR AND RETURN


Prior to returning devices, contact the nearest local Detector
Electronics office so that a Return Material Identification
(RMI) number can be assigned. A written statement
describing the malfunction must accompany the
returned device or component to assist and expedite
finding the root cause of the failure.
Pack the unit properly. Always use sufficient packing
material. Where applicable, use an antistatic bag as
protection from electrostatic discharge.

007290-001
007290-002

Note
Det-Tronics reserves the right to apply a service
charge for repairing returned product damaged as
a result of improper packaging.

011385-001
101197-001
101197-004
101197-005
101197-003
010816-001
010817-001
010818-001
010819-001
103363-001
103406-001
107427-040
005003-001
001680-001

Return all equipment transportation prepaid to the factory


in Minneapolis.
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.

6.1

19

95-8578

X3302 MODEL MATRIX


MODEL
X3302

DESCRIPTION
Multispectrum IR Flame Detector
TYPE

MATERIAL

Aluminum

Stainless Steel (316)


TYPE

THREAD TYPE

4M

4 Port, Metric M25

4N

4 Port, 3/4" NPT


TYPE
15

OUTPUTS
Relay and Pulse
TYPE

APPROVALS

INMETRO (Brazil)

VNIIPO/VNIIFTRI (Russia)

FM/CSA/ATEX/CE/IECEx
TYPE

6.1

20

CLASSIFICATION

Division/Zone Ex d e

Division/Zone Ex d

95-8578

APPENDIX A
FM Approval and Performance Report
THE FOLLOWING ITEMS, FUNCTIONS AND OPTIONS DESCRIBE THE FM APPROVAL:

Explosion-proof for Class I, Div. 1, Groups B, C and D (T4A) Hazardous (Classified) Locations per FM 3615.

Dust-ignition proof for Class II/III, Div. 1, Groups E, F and G (T4A) Hazardous (Classified) Locations per FM 3615.

Nonincendive for Class I, Div. 2, Groups A, B, C and D (T3C) Hazardous (Classified) Locations per FM 3611.

Nonincendive for Class II, Div. 2, Groups F and G (T3C) Hazardous (Classified) Locations per FM 3611.

Enclosure rating NEMA/Type 4X per NEMA 250.

Ambient Temperature Limits: 40F to +167F (40C to +75C).

Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).

Flameproof per ANSI/ISA 60079-0, -1, -7, -31


for Class I, Zone 1 AEx d e IIC Gb; T6 (Tamb 40C to +60C); T5 (Tamb 40C to +75C)
AEx d IIC Gb; T6 (Tamb 40C to +60C); T5 (Tamb 40C to +75C)

for Zone 21 AEx tb T130C Db


Tamb 40C to +75C

Degree of protection provided by Enclosure IP66/67, Hazardous Locations for use in the U.S.

The following accessories are FM approved for use with the X3302 Flame Detector:
Part Number

Description

102740-002
007739-001
010857-001
007290-001
007290-002
011385-001

Magnet
Magnet and Extension Pole
Q1130A1001 Flange Mount Assembly
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment

The following performance criteria were verified:


AUTOMATIC OPTICAL INTEGRITY TEST:
The detector generated an optical fault in the presence of contamination on any single or combination of lens surfaces
resulting in a loss of approximately 50% of its detection range, verifying that the detector performs a calibrated
Automatic oi test for each sensor. Upon removal of the contamination, the detector fault was cleared and the detector
was verified to detect a fire.
MANUAL OPTICAL INTEGRITY TEST:
The Manual / Magnetic oi performs the same calibrated test as the Automatic oi, and additionally actuates the alarm
relay to verify output operation. If there is a 50% loss of its detection range, an alarm signal is not generated.
The oi test procedure, as described in the Magnetic oi / Manual oi section of this instruction manual, is the approved
external optical test method for this detector to verify end-to-end detector function. This test replaces the function and
need of a traditional external test lamp.

6.1

21

95-8578

FM Approval and Performance Report Continued

RESPONSE CHARACTERISTICS
Very High Sensitivity
Fuel

Size/Flow Rate

Hydrogen
Methanol

30 inch plume/100 SLPM*


1 x 1 foot

Distance
feet (m)
100 (30.5)
70 (21.3)

Average Response
Time (seconds)
3
5

* Standard Liters Per Minute (Standard conditions defined as +25C and 14.696 PSIA).

High Sensitivity
Fuel

Size/Flow Rate

Hydrogen
Methanol

30 inch plume/100 SLPM*


1 x 1 foot

Distance
feet (m)
75 (22.9)
52.5 (16.0)

Average Response
Time (seconds)
3
2

* Standard Liters Per Minute (Standard conditions defined as +25C and 14.696 PSIA).

Medium Sensitivity
Fuel

Size/Flow Rate

Hydrogen
Methanol

30 inch plume/100 SLPM*


1 x 1 foot

Distance
feet (m)
50 (15.2)
35 (10.7)

Average Response
Time (seconds)
4
4

* Standard Liters Per Minute (Standard conditions defined as +25C and 14.696 PSIA).

Low Sensitivity
Fuel

Size/Flow Rate

Hydrogen
Methanol

30 inch plume / 100 SLPM*


1 x 1 foot

Distance
feet (m)
25 (7.6)
17.5 (5.3)

Average Response
Time (seconds)
3
3

* Standard Liters Per Minute (Standard conditions defined as +25C and 14.696 PSIA).

6.1

22

95-8578

FM Approval and Performance Report Continued

FIELD OF VIEW
Very High Sensitivity
Fuel

Size/
Flow Rate

Distance
feet (m)

Horizontal
(degrees)

Avg. Horiz.
Response Time
(seconds)

Vertical
(degrees)

Avg. Vert.
Response Time
(seconds)

Hydrogen

30 inch plume/
100 SLPM*

100 (30.5)

+45
-45

2
2.5

+45
-30

8
1.5

Methanol

1 x 1 foot

70 (21.3)

+45
-45

10
6

+45
-30

8.5
6

* Standard Liters Per Minute (Standard conditions defined as +25C and 14.696 PSIA).

High Sensitivity
Fuel

Size/
Flow Rate

Distance
feet (m)

Horizontal
(degrees)

Avg. Horiz.
Response Time
(seconds)

Vertical
(degrees)

Avg. Vert.
Response Time
(seconds)

Hydrogen

30 inch plume/
100 SLPM*

75 (22.9)

+45
-45

4
2.5

+45
-30

3
3

Methanol

1 x 1 foot

52.5 (16.0)

+45
-45

4.5
3.5

+45
-30

4.5
2.5

* Standard Liters Per Minute (Standard conditions defined as +25C and 14.696 PSIA).

Medium Sensitivity
Fuel

Size/
Flow Rate

Distance
feet (m)

Horizontal
(degrees)

Avg. Horiz.
Response Time
(seconds)

Vertical
(degrees)

Avg. Vert.
Response Time
(seconds)

Hydrogen

30 inch plume/
100 SLPM*

50 (15.2)

+45
-45

4.5
3.5

+45
-30

3
5

Methanol

1 x 1 foot

35 (10.7)

+45
-45

9.5
6

+45
-30

10.5
5.5

* Standard Liters Per Minute (Standard conditions defined as +25C and 14.696 PSIA).

Low Sensitivity
Fuel

Size/
Flow Rate

Distance
feet (m)

Horizontal
(degrees)

Avg. Horiz.
Response Time
(seconds)

Vertical
(degrees)

Avg. Vert.
Response Time
(seconds)

Hydrogen

30 inch plume/
100 SLPM*

25 (7.6)

+45
-45

2
2.5

+45
-30

2.4
2

Methanol

1 x 1 foot

17.5 (5.3)

+45
-45

7
8.5

+45
-30

5.5
6

* Standard Liters Per Minute (Standard conditions defined as +25C and 14.696 PSIA).

NOTE
Refer to the High Resolution Field of View charts (page 27) for additional information.

6.1

23

95-8578

FM Approval and Performance Report Continued


FALSE ALARM IMMUNITY
Distance feet (m)
Very High

High

Medium

Low

Modulated
Response

Unmodulated
Response

Sunlight, direct, reflected

No alarm

No alarm

Vibration

N/A

N/A

Arc welding

20 (6.1)

15 (4.6)

10 (3.0)

5 (1.5)

No alarm

No alarm

70 w sodium vapor lamp

10 (3.0)

8 (2.4)

5 (1.5)

3 (0.9)

No alarm

No alarm

False Alarm Source

250 w vapor lamp

10 (3.0)

8 (2.4)

5 (1.5)

3 (0.9)

No alarm

No alarm

300 w incandescent lamp

10 (3.0)

8 (2.4)

5 (1.5)

3 (0.9)

No alarm

No alarm

500 w shielded quartz halogen lamp

15 (4.6)

10 (3.0)

8 (2.4)

5 (1.5)

No alarm

No alarm

1500 w electric radiant heater

10 (3.0)

8 (2.4)

5 (1.5)

3 (0.9)

No alarm

No alarm

Two 34 w fluorescent lamps

5 (1.5)

4 (1.2)

3 (0.9)

2 (0.6)

No alarm

No alarm

RESPONSE CHARACTERISTICS IN THE PRESENCE OF FALSE ALARM SOURCES


Very High Sensitivity
False Alarm Source

Distance
feet (m)

Fire Source

Distance
feet (m)

Average Response
Time (seconds)

Hydrogen @ 50 SLPM

50 (15.2)

Hydrogen @ 100 SLPM

50 (15.2)

Hydrogen @ 200 SLPM

15 (4.6)

Hydrogen @ 50 SLPM

50 (15.2)

2.5

Sunlight, direct, unmodulated*

Sunlight, direct, modulated*

Sunlight, reflected, unmodulated*

Hydrogen @ 100 SLPM

50 (15.2)

3.5

Sunlight, reflected, modulated*

Hydrogen @ 100 SLPM

50 (15.2)

Arc welding, steady, #7014

20 (6.1)

Hydrogen @ 100 SLPM

100 (30.5)

7.5

Arc welding, modulated, #7014

20 (6.1)

Hydrogen @ 100 SLPM

70 (21.3)

70 w sodium vapor, unmodulated

10 (3.0)

Hydrogen @ 100 SLPM

100 (30.5)

2.5

70 w sodium vapor, modulated

10 (3.0)

Hydrogen @ 100 SLPM

100 (30.5)

3.5

250 w vapor lamp, unmodulated

10 (3.0)

Hydrogen @ 100 SLPM

100 (30.5)

250 w vapor lamp, modulated

10 (3.0)

Hydrogen @ 100 SLPM

70 (21.3)

2.5

300 w incandescent lamp, unmodulated

10 (3.0)

Hydrogen @ 100 SLPM

100 (30.5)

300 w incandescent lamp, modulated

10 (3.0)

Hydrogen @ 100 SLPM

60 (18.2)

500 w shielded quartz halogen lamp, unmodulated

15 (4.6)

Hydrogen @ 100 SLPM

100 (30.5)

500 w shielded quartz halogen lamp, modulated

15 (4.6)

Hydrogen @ 100 SLPM

35 (10.7)

1500 w electric radiant heater, unmodulated

10 (3.0)

Hydrogen @ 100 SLPM

100 (30.5)

1500 w electric radiant heater, modulated

10 (3.0)

Hydrogen @ 100 SLPM

40 (12.2)

Two 34 w fluorescent lamps, unmodulated

5 (1.5)

Hydrogen @ 100 SLPM

100 (30.5)

2.5

Two 34 w fluorescent lamps, modulated

5 (1.5)

Hydrogen @ 100 SLPM

100 (30.5)

2.5

* Outdoor test conditions.

6.1

24

95-8578

FM Approval and Performance Report Continued

High Sensitivity
Distance
feet (m)

Fire Source

Distance
feet (m)

Average Response
Time (seconds)

Sunlight, direct, unmodulated*

Hydrogen @ 100 SLPM

50 (15.2)

Sunlight, direct, modulated*

Hydrogen @ 100 SLPM

10 (3.0)

Sunlight, reflected, unmodulated*

Hydrogen @ 100 SLPM

50 (15.2)

Sunlight, reflected, modulated*

Hydrogen @ 100 SLPM

25 (7.6)

Arc welding, steady, #7014

15 (4.6)

Hydrogen @ 100 SLPM

75 (22.9)

Arc welding, modulated, #7014

15 (4.6)

Hydrogen @ 100 SLPM

52.5 (16)

3.5

70 w sodium vapor, unmodulated

8 (2.4)

Hydrogen @ 100 SLPM

75 (22.9)

3.5

70 w sodium vapor, modulated

8 (2.4)

Hydrogen @ 100 SLPM

75 (22.9)

2.5

250 w vapor lamp, unmodulated

8 (2.4)

Hydrogen @ 100 SLPM

75 (22.9)

2.5

250 w vapor lamp, modulated

8 (2.4)

Hydrogen @ 100 SLPM

52.5 (16)

2.5

300 w incandescent lamp, unmodulated

8 (2.4)

Hydrogen @ 100 SLPM

75 (22.9)

300 w incandescent lamp, modulated

8 (2.4)

Hydrogen @ 100 SLPM

45 (13.7)

False Alarm Source

500 w shielded quartz halogen lamp, unmodulated

10 (3.0)

Hydrogen @ 100 SLPM

75 (22.9)

2.5

500 w shielded quartz halogen lamp, modulated

10 (3.0)

Hydrogen @ 100 SLPM

26 (7.9)

1.5

1500 w electric radiant heater, unmodulated

8 (2.4)

Hydrogen @ 100 SLPM

75 (22.9)

2.5

1500 w electric radiant heater, modulated

8 (2.4)

Hydrogen @ 100 SLPM

30 (9.1)

5.5

Two 34 w fluorescent lamps, unmodulated

4 (1.2)

Hydrogen @ 100 SLPM

75 (22.9)

Two 34 w fluorescent lamps, modulated

4 (1.2)

Hydrogen @ 100 SLPM

75 (22.9)

2.5

Distance
feet (m)

Fire Source

Distance
feet (m)

Average Response
Time (seconds)

Sunlight, direct, unmodulated*

Hydrogen @ 100 SLPM

50 (15.2)

Sunlight, direct, modulated*

Hydrogen @ 200 SLPM

10 (3.0)

Sunlight, reflected, unmodulated*

Hydrogen @ 100 SLPM

50 (15.2)

Sunlight, reflected, modulated*

Hydrogen @ 100 SLPM

25 (7.6)

Arc welding, steady, #7014

10 (3.0)

Hydrogen @ 100 SLPM

50 (15.2)

Arc welding, modulated, #7014

10 (3.0)

Hydrogen @ 100 SLPM

35 (10.7)

70 w sodium vapor, unmodulated

5 (1.5)

Hydrogen @ 100 SLPM

50 (15.2)

2.5

70 w sodium vapor, modulated

5 (1.5)

Hydrogen @ 100 SLPM

50 (15.2)

250 w vapor lamp, unmodulated

5 (1.5)

Hydrogen @ 100 SLPM

50 (15.2)

250 w vapor lamp, modulated

5 (1.5)

Hydrogen @ 100 SLPM

35 (10.7)

300 w incandescent lamp, unmodulated

5 (1.5)

Hydrogen @ 100 SLPM

50 (15.2)

300 w incandescent lamp, modulated

5 (1.5)

Hydrogen @ 100 SLPM

30 (9.1)

500 w shielded quartz halogen lamp, unmodulated

8 (2.4)

Hydrogen @ 100 SLPM

50 (15.2)

500 w shielded quartz halogen lamp, modulated

8 (2.4)

Hydrogen @ 100 SLPM

17.5 (5.3)

1500 w electric radiant heater, unmodulated

5 (1.5)

Hydrogen @ 100 SLPM

50 (15.2)

1500 w electric radiant heater, modulated

5 (1.5)

Hydrogen @ 100 SLPM

20 (6.1)

Two 34 w fluorescent lamps, unmodulated

3 (0.9)

Hydrogen @ 100 SLPM

50 (15.2)

2.5

Two 34 w fluorescent lamps, modulated

3 (0.9)

Hydrogen @ 100 SLPM

50 (15.2)

* Outdoor test conditions.

Medium Sensitivity
False Alarm Source

* Outdoor test conditions.

6.1

25

95-8578

FM Approval and Performance Report Continued

Low Sensitivity
Distance
feet (m)

Fire Source

Distance
feet (m)

Average Response
Time (seconds)

Sunlight, direct, unmodulated*

Hydrogen @ 100 SLPM

25 (7.6)

3.5

Sunlight, direct, modulated*

Hydrogen @ 200 SLPM

10 (3.0)

3.5

False Alarm Source

Sunlight, reflected, unmodulated*

Hydrogen @ 100 SLPM

25 (7.6)

2.5

Sunlight, reflected, modulated*

Hydrogen @ 100 SLPM

15 (4.6)

2.5

5 (1.5)

Hydrogen @ 100 SLPM

25 (7.6)

Arc welding, steady, #7014


Arc welding, modulated, #7014

5 (1.5)

Hydrogen @ 100 SLPM

17.5 (5.3)

2.5

70 w sodium vapor, unmodulated

3 (0.9)

Hydrogen @ 100 SLPM

25 (7.6)

70 w sodium vapor, modulated

3 (0.9)

Hydrogen @ 100 SLPM

25 (7.6)

250 w vapor lamp, unmodulated

3 (0.9)

Hydrogen @ 100 SLPM

25 (7.6)

250 w vapor lamp, modulated

3 (0.9)

Hydrogen @ 100 SLPM

17.5 (5.3)

300 w incandescent lamp, unmodulated

3 (0.9)

Hydrogen @ 100 SLPM

25 (7.6)

300 w incandescent lamp, modulated

3 (0.9)

Hydrogen @ 100 SLPM

15 (4.6)

500 w shielded quartz halogen lamp, unmodulated

5 (1.5)

Hydrogen @ 100 SLPM

25 (7.6)

3.5

500 w shielded quartz halogen lamp, modulated

5 (1.5)

Hydrogen @ 100 SLPM

10 (3.0)

2.5

1500 w electric radiant heater, unmodulated

3 (0.9)

Hydrogen @ 100 SLPM

25 (7.6)

1500 w electric radiant heater, modulated

3 (0.9)

Hydrogen @ 100 SLPM

10 (3.0)

Two 34 w fluorescent lamps, unmodulated

2 (0.6)

Hydrogen @ 100 SLPM

25 (7.6)

Two 34 w fluorescent lamps, modulated

2 (0.6)

Hydrogen @ 100 SLPM

25 (7.6)

3.5

* Outdoor test conditions.

6.1

26

95-8578

FM Approvals Description and Performance Report Continued


HIGH RESOLUTION FIELD OF VIEW
0
15 100 (30.5) 15
90 (27.4)
80 (24.4)
70 (21.3)
60 (18.3)
50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)

30
45

10 (3)
20 (6.1)
30 (9.1)
40 (12.2)
50 (15.2)
60 (18.3)
70 (21.3)
80 (24.4)
90 (27.4)
100 (30.5)

30

30

45

0
15 70 (21.3)

30

60 (18.3)

45

45

50 (15.2)
40 (12.2)
30 (9.1)
20 (6.1)
10 (3)

10 (3)

30

20 (6.1)

30

30 (9.1)

15

15

40 (12.2)
50 (15.2)

30

70 (21.3)
45

Field of View at Indicated Distance in Feet (m) for Hydrogen at


Very High Sensitivity (30 inch plume, with 100 SLPM flow rate)

0
15 75 (22.9)
30

15

30

30
45

55 (16.8)

15
30

45

45 (13.7)
35 (10.7)
25 (7.6)
15 (4.6)

15 (4.6)

5 (1.5)
10 (3)
15 (4.6)
20 (6.1)
25 (7.6)
30 (9.1)
35 (10.7)
40 (12.2)
45 (13.7)
50 (15.2)
52.5 (16)

30

25 (7.6)
35 (10.7)

15

45 (13.7)
55 (16.8)

65 (19.8)

15

75 (22.9)

45

30

DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45 FROM HORIZONTAL.

Field of View at Indicated Distance in Feet (m) for


Methanol at Very High Sensitivity (1 x 1 ft)

15

65 (19.8)

45

60 (18.3)

DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45 FROM HORIZONTAL.

15

45

DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45 FROM HORIZONTAL.

Field of View at Indicated Distance in Feet (m) for Hydrogen at


High Sensitivity (30 inch plume, with 100 SLPM flow rate)

6.1

15

0
52.5 (16)
50 (15.2)
45 (13.7)
40 (12.2)
35 (10.7)
30 (9.1)
25 (7.6)
20 (6.1)
15 (4.6)
10 (3)
5 (1.5)

15
30
45

30

15
0
15
45

30

DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45 FROM HORIZONTAL.

Field of View at Indicated Distance in Feet (m) for


Methanol at High Sensitivity (1 x 1 ft)

27

95-8578

FM Approval and Performance Report Continued

15
30
45

5 (1.5)
10 (3)
15 (4.6)
20 (6.1)
25 (7.6)
30 (9.1)
35 (10.7)
40 (12.2)
45 (13.7)
50 (15.2)

0
50 (15.2)
45 (13.7)
40 (12.2)
35 (10.7)
30 (9.1)
25 (7.6)
20 (6.1)
15 (4.6)
10 (3)
5 (1.5)

15

15

30

30

15
30

30 (9.1)

45

45

0
35 (10.7)

45

25 (7.6)
20 (6.1)
15 (4.6)
10 (3)
5 (1.5)

5 (1.5)

30

15 (4.6)

15

45

30

25 (7.6)

45

30

Field of View at Indicated Distance in Feet (m) for


Methanol at Medium Sensitivity (1 x 1 ft)

30

15
30

20 (6.1)

DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45 FROM HORIZONTAL.

15

35 (10.7)

15

0
25 (7.6)

30
45

30 (9.1)

DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45 FROM HORIZONTAL.

Field of View at Indicated Distance in Feet (m) for Hydrogen at


Medium Sensitivity (30 inch plume, with 100 SLPM flow rate)

15

15

20 (6.1)

0
15

30

10 (3)

0
17.5 (5.3)

15
30

15 (4.6)

45

45

45
10 (3)

15 (4.6)

5 (1.5)

10 (3)
5 (1.5)

5 (1.5)

30
15

15 (4.6)

20 (6.1)

15
25 (7.6)
45

30

30

5 (1.5)

10 (3)

15

10 (3)

15 (4.6)

DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45 FROM HORIZONTAL.

15

17.5 (5.3)

45

Field of View at Indicated Distance in Feet (m) for Hydrogen at


Low Sensitivity (30 inch plume, with 100 SLPM flow rate)

30

DETECTOR VERTICAL
FIELD OF VIEW
WITH DETECTOR AT
45 FROM HORIZONTAL.

Field of View at Indicated Distance in Feet (m) for


Methanol at Low Sensitivity (1 x 1 ft)

NOTE
FM Approvals minimum requirements are response distance measurements at 0 (on axis) and the limits of
the field of view. These high resolution field of view diagrams show the measured response distances at all the
indicated angles in the horizontal plane.
6.1

28

95-8578

APPENDIX B
CSA Approval
Multispectrum IR Flame Detector/Controller X3302 Series, rated 18-30 Vdc, 4.6 Watts to 17 Watts.
Relay contacts rated 30 Vdc, 5 Amps.
Note
Hazardous location testing has been successfully completed on the Model X3302 series from an ambient
temperature range of 55C to +125C; however, the detector label marking indicates 40C to +75C.
The following accessories are CSA approved for use with the X3302 Flame Detector:
Part Number

Description

102740-002
007739-001
010857-001
007290-001
007290-002
011385-001

Magnet
Magnet and Extension Pole
Q1130A1001 Flange Mount Assembly
Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment

DIVISION CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Class I, Division 1, Groups B, C, and D (T4A); Class II, Division 1, Groups E, F, and G (T4A);
Class I, Division 2, Groups A, B, C, and D (T3C); Class II, Division 2, Groups F and G (T3C);
Class III; Enclosure NEMA/Type 4X;
Conduit seal not required.
APPLICABLE REQUIREMENTS
CSA Std C22.2 No. 25-1966

Enclosures for use in Class II Groups E, F & G Hazardous Locations.

CSA Std C22.2 No. 30-M1986

Explosion-Proof Enclosures for use in Class I Hazardous Locations.

CAN/CSA C22.2 No. 94-M91

Special Purpose Enclosures.

CSA Std C22.2 No. 142-M1987

Process Control Equipment.

CSA Std C22.2 No. 213-M1987

Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations.

ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Ex d e IIC T5-T6
T6 (Ta 50C to +60C)
T5 (Ta 50C to +75C)
Seal required adjacent to enclosure
IP66/IP67.
Ex d IIC T4-T6
T6 (Ta 55C to +60C)
T5 (Ta 55C to +75C)
T4 (Ta 55C to +125C)
Seal required adjacent to enclosure
IP66/IP67.
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0:07 Electrical apparatus for explosive gas atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1:11

Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures "d"

CAN/CSA-C22.2 No. 60079-7:12

Explosive atmospheres. Part 7: Equipment protection by increased safety "e"

6.1

29

95-8578

APPENDIX C
ATEX / CE Approval
EC-TYPE EXAMINATION CERTIFICATE
DEMKO 01 ATEX 130204X
Increased Safety Model
FM
APPROVED

Flameproof Model

II 2 G
II 2 G
FM
0539
II 2 D
II 2 D
Ex d e IIC T6T5 Gb
Ex d IIC T6T4 Gb
Ex tb IIIC T130C
Ex tb IIIC T130C
T6 (Tamb = 50C to +60C)
T6 (Tamb = 55C to +60C)
T5 (Tamb = 50C to +75C)
T5 (Tamb = 55C to +75C)
IP66/IP67.
T4 (Tamb = 55C to +125C)
IP66/IP67.
0539

APPROVED

Compliance with:
EN 60079-0: 2009
EN 60079-1: 2007
EN 60079-7: 2007
EN 60079-31: 2009
EN/IEC 60529: 2001.
Installation instructions
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from
14-24 AWG or 2.5-0.2 mm2.
The Multispectrum infrared (IR) flame detector type X3302 shall be installed according to the instructions given by the
manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the
terminal compartment in type of explosion protection flameproof enclosure "d", or in type of explosion protection
increased safety "e" for use with the terminal compartment in type of explosion protection increased safety "e". They
shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Multispectrum infrared (IR) flame detector type X3302 must be electrically connected to earth
ground.
For ambient temperatures below 10C and above +60C use field wiring suitable for both minimum and maximum
ambient temperature.
Special conditions for safe use:
The front window assembly contains a special cemented joint construction. In accordance with EN60079-1 clause
5.1.c, all inspections, repair and/or adjustments to this front window assembly shall be done by Detector Electronics
Corporation only.
The EOL resistor can only be used within the flameproof terminal compartment.
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed
2.5 watts.
The Multispectrum infrared (IR) flame detector type X3302 is to be installed in places where there is a low risk of
mechanical damage.
6.1

30

95-8578

NOTE
Operational performance verified from 40C to +75C.
note
An optional third party addressable module can only be used within the Ex d flameproof model unless the
addressable module is component certified as Ex e for use within the Ex d e increased safety model.
NOTE
Refer to EOL Resistors section for installation details. All cable entry devices and blanking elements shall be
certified to E-generation or ATEX standards, in type of explosion protection increased safety e or flameproof
enclosure d (as applicable), suitable for the conditions of use and correctly installed. They shall maintain the
degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed with suitable
blanking elements.
Note
For ATEX installations, the X3302 detector housing must be electrically connected to earth ground.

The following accessories are ATEX approved for use with the X3302 Flame Detector:
Part Number

Description

007290-001
007290-002
011385-001

Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment

6.1

31

95-8578

APPENDIX D
IECEx Approval
IECEx Certificate of Conformity
DEMKO
IECEx ULD 06.0017X
Ex d e IIC T6-T5 Gb
Ex d IIC T6-T4 Gb
Ex tb IIIC T130C
Ex tb IIIC T130C
T6 (Tamb = 50C to +60C)
or
T6 (Tamb = 55C to +60C)
T5 (Tamb = 50C to +75C)
T5 (Tamb = 55C to +75C)
IP66/IP67. T4 (Tamb = 55C to +125C)
IP66/IP67.
Compliance with:
IEC 60079-0: 2007, ed. 5
IEC 60079-1: 2007, ed. 6
IEC 60079-7: 2006, ed. 4
IEC 60079-31: 2008, ed. 1
EN/IEC 60529: 2001.
Installation instructions
The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from
14-24 AWG or 2.5-0.2 mm2.
The Multispectrum infrared (IR) flame detector type X3302 shall be installed according to the instructions given by the
manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure "d" for use with the terminal
compartment in type of explosion protection flameproof enclosure "d" or in type of explosion protection increased safety "e"
for use with the terminal compartment in type of explosion protection increased safety "e".
They shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
Unused entries shall be closed with suitable certified blanking elements.
The metal housing for the Multispectrum infrared (IR) flame detector type X3302 must be electrically connected to earth
ground.
For ambient temperatures below 10C and above +60C use field wiring suitable for both minimum and maximum ambient
temperature.
Special conditions for safe use:
The front window assembly contains a special cemented joint construction. In accordance with IEC 60079-1 clause 5.1.c,
all inspections, repair and/or adjustments to this front window assembly shall be done by Detector Electronics Corporation
only.
The EOL resistor can only be used within the flameproof terminal compartment.
EOL resistors must be ceramic, wirewound type, rated 5 watts minimum, with actual power dissipation not to exceed 2.5 watts.
The Multispectrum infrared (IR) flame detector type X3302 is to be installed in places where there is a low risk of
mechanical damage.
The following accessories are IECEx approved for use with the X3302 Flame Detector:
Part Number

Description

007290-001
007290-002
011385-001

Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
Q9033 Collar Attachment

6.1

32

95-8578

APPENDIX E
additional Approvals
RUSSIA
Note
ThefollowingRussian approval applies to existing installations that include Det-Tronics R7XXX controllers and require
a factory replacement of older pulse detectors.

VNIIPO
CERTIFICATE OF CONFORMITY TO TECHNICAL REGULATIONS, GOST R 53325-2009

BRAZIL

UL-BR 12.0093X
Ex d e IIC T6-T5 Gb IP66/IP67
Ex tb IIIC T130C
T6 (Tamb = 50C to +60C)
T5 (Tamb = 50C to +75C).
OR
Ex d IIC T6-T4 Gb IP66/IP67
Ex tb IIIC T130C
T6 (Tamb = 55C to +60C)
T5 (Tamb = 55C to +75C)
T4 (Tamb = 55C to +125C).

6.1

33

95-8578

95-8578

Detector Electronics Corporation


6901 West 110th Street
Minneapolis, MN 55438 USA

X3301 Multispectrum
IR Flame Detector

PointWatch Eclipse
IR Combustible Gas Detector

FlexVu Universal Display


w/ GT3000 Toxic Gas Detector

Eagle Quantum Premier


Safety System

T: 952.941.5665 or 800.765.3473
F: 952.829.8750
W: http://www.det-tronics.com
E: det-tronics@det-tronics.com

Det-Tronics and oi (Optical Integrity) are registered trademarks or trademarks of Detector Electronics Corporation in the
United States, other countries, or both. Other company, product, or service names may be trademarks or service marks of others.
Copyright Detector Electronics Corporation 2013. All rights reserved

You might also like