Instructions: IR Flame Detector With Pulse Output X9800
Instructions: IR Flame Detector With Pulse Output X9800
Instructions: IR Flame Detector With Pulse Output X9800
DESCRIPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 TROUBLESHOOTING . . . . . . . . . . . . . . . . . . . . . . . 16
Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
LED . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 MAINTENANCE . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
oi (Optical Integrity) . . . . . . . . . . . . . . . . . . . . . . 2 Cleaning Procedure . . . . . . . . . . . . . . . . . . . . . . 17
Communication . . . . . . . . . . . . . . . . . . . . . . . . . . 3 oi Plate Removal and Replacement . . . . . . . . . 17
Data Logging . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 Periodic Checkout Procedure . . . . . . . . . . . . . . 17
Integral Wiring Compartment . . . . . . . . . . . . . . . 3 Clock Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
EOL Resistors . . . . . . . . . . . . . . . . . . . . . . . . . . 15
APPENDIX B – CSA APPROVAL . . . . . . . . . . . . . . 25
STARTUP PROCEDURE . . . . . . . . . . . . . . . . . . . . 15
Manual oi Test (Output to Controller) . . . . . . . . 15 APPENDIX C – ATEX APPROVAL . . . . . . . . . . . . . 26
IR Flame Detector
with Pulse Output
X9800
IMPORTANT
Be sure to read and understand the entire
instruction manual before installing or operating
the flame detection system. Any deviation from
the recommendations in this manual may impair
system performance and compromise safety.
ATTENTION
The X9800 includes the Automatic oi ® (Optical
Integrity) feature — a calibrated performance test
that is automatically performed once per minute
to verify complete detector operation capabilities.
Testing with an external test lamp is not
approved or required.
When used as a field replacement, all operating features
of the current controller are retained in addition to gaining
DESCRIPTION the advanced features of the X9800 Flame Detector. In
typical applications, the four wire X9800 can utilize all
The evolution continues with the new X9800 IR
existing system wiring.
Flame Detector. The X9800 meets the most stringent
requirements worldwide with advanced detection
The detector has Division and Zone explosion-proof
capabilities and immunity to extraneous sources,
ratings and is suitable for use in indoor and outdoor
combined with a superior mechanical design. The
applications. The X9800 housing is available in copper-
detector is equipped with both automatic and manual
free aluminum or stainless steel, with NEMA/Type 4X and
oi test capability.
IP66/IP67 rating.
The X9800 with pulse/relay output is designed for use
A tri-color LED on the detector faceplate indicates
in controller based systems. In addition to use in new
normal condition and notifies personnel of fire alarm or
systems, it can serve as a direct field replacement
fault conditions.
for Detector Electronics Corporation’s (Det-Tronics)
controller based flame detectors that generate a pulse
Microprocessor controlled heated optics increase
output (not compatible with R7484 and R7409B/C).
resistance to moisture and ice.
An alarm condition will normally override a fault The Mag oi test is performed by placing a magnet at
condition, unless the nature of the fault condition the location marked “MAG OI” on the outside of the
impairs the ability of the detector to generate or detector (see Figure 2). This action causes the detector
maintain an alarm output, i.e., loss of operating power. to immediately send pulses to the controller. Controller
response is as follows:
LED
A tri-color LED on the detector faceplate indicates • The Zone LED blinks.
normal condition and notifies personnel of fire alarm • The digital display indicates which Zone is in
or fault conditions. Table 1 indicates the condition of the alarm.
LED for each status. • The status indicator shows “6” (fire).
oi (OPTICAL INTEGRITY)
Table 1—Detector Status Indicator
Automatic oi
Detector Status LED Indicator
The X9800 includes the Automatic oi feature — a
calibrated performance test that is automatically Power On/Normal Auto oi Green
(no fault or fire alarm)
performed once per minute to verify complete detector
operation capabilities. No testing with an external test Green, flashing off for
Power On/Normal Man oi 0.5 sec. every 5 sec.
lamp is required. The detector automatically performs
the same test that a maintenance person with a test Fault Yellow
lamp would perform — once every minute. However, a Red, flashing on for
Pre-Alarm/Background IR
successful Automatic oi test does not produce an alarm 1 sec. and off for 1 sec.
condition. Fire (Alarm) Steady Red
On Power-Up, The LED Flashes in Sequence as Follows,
The X9800 signals a fault condition when less than half of Indicating Sensitivity and Signal Processing Status
the detection range remains. This is indicated by the fault
Low IR Sensitivity One Green Flash
relay and is evident by the yellow color of the LED on the Medium IR Sensitivity Two Green Flashes
face of the detector. See the “Troubleshooting” section High IR Sensitivity Three Green Flashes
for further information. Very High IR Sensitivity Four Green Flashes
Quick Fire / TDSA IR Signal One Yellow Flash
TDSA only IR Signal Two Yellow Flashes
Quick Fire only Three Yellow Flashes
6.1 2 95-8555
IMPORTANT INTEGRAL WIRING COMPARTMENT
Mag oi can be performed with the controller’s All external wiring to the device is connected within
(R7404/R7494) keylock switch in either the the integral junction box. The detector is furnished with
NORMAL or TEST position. In NORMAL, the four conduit entries, with either 3/4 inch NPT or M25
controller goes into alarm and activates its outputs. threads.
If no controller alarm output is desired, place
the keylock switch in the TEST position before
touching the magnet to the outside of the detector.
SIGNAL PROCESSING OPTIONS
Man oi operates only with the keylock switch in The X9800 features signal processing options. These
the TEST position. options determine the type of logic that the detector will
use for processing fire signals to customize the X9800
During the entire test, the detector gives no indication to the application. Two signal processing options are
of alarm. available for the X9800:
To reset the controller status and alarms, place the –– TDSA enabled
keylock switch in RESET. Return the keylock switch to
NORMAL when testing is complete. –– Both TDSA and Quick Fire enabled (either initiates
fire alarm).
The Man oi test is nearly identical to the Mag oi test,
except for the manner in which the test is initiated: Time Domain Signal Analysis (TDSA)
The TDSA signal processing technique analyzes the
• Place the keylock switch on the controller (R7404/ input signal in real time, requiring the IR signal to flicker
R7494) in the TEST position. randomly in order to recognize it as a fire condition.
• Press the SELECT button to select the appropriate
detector for test. Using TDSA signal processing, the X9800 ignores
regularly chopped blackbody sources (occurring in areas
• Press the TEST/ACCEPT button to initiate the test. where moving conveyors and hot objects in proximity
to one another result in a regularly chopped IR signal),
Controller and detector responses are identical to the because it looks for a less uniform signal. However, in
Mag oi test described above. the presence of a regularly chopped signal, the unit is
more susceptible to false alarms due to sporadic IR that
To reset the controller status and alarms, place the functions as a trigger when occurring in conjunction with
keylock switch in RESET. Return the keylock switch to the regularly chopped signal.
NORMAL when testing is complete.
Quick Fire (High Speed)
NOTE The Quick Fire (High Speed) feature can be used in
Refer to Appendix A for FM verification of the conjunction with the TDSA signal processing method.
Det-Tronics o i function. This method overrides TDSA requirements in the event
of an intense signal. When Quick Fire is activated, the
COMMUNICATION detector is capable of responding to an intense fire signal
The X9800 is furnished with an RS-485 interface for in less than 30 milliseconds (0.030 seconds). Using
communicating status and other information with external the Quick Fire feature in conjunction with TDSA signal
devices. The RS-485 uses Modbus protocol, with the processing allows the detector to provide a high speed
detector configured as a slave device. response to a large, non-flickering fire (such as in high
pressure gas applications) while maintaining an ability to
DATA LOGGING respond to smaller fires.
Data logging capability is also provided. Status conditions
such as normal, power down, general and oi faults, pre-
alarm, fire alarm, time, and temperature are recorded.
Each event is time and date stamped, along with the
temperature and input voltage. Event data is stored in
non-volatile memory when the event becomes active,
and again when the status changes. Data is accessible
using the Det-Tronics Inspector Connector accessory or
RS-485.
6.1 3 95-8555
GENERAL APPLICATION FALSE ALARM SOURCES
INFORMATION The detector has been designed to ignore steady state
infrared sources that do not have a flicker frequency
RESPONSE CHARACTERISTICS
characteristic of a fire, however, it should be noted that
Response is dependent on the detector’s sensitivity if these steady state infrared sources are hot enough
setting, distance, type of fuel, temperature of the fuel, to emit adequate amounts of infrared radiation in the
and time required for the fire to come to equilibrium. As response range of the IR sensor and if this radiation
with all fire tests, results must be interpreted according to becomes interrupted from the view of the detector in a
an individual application. pattern characteristic of a flickering flame, the IR sensor
can respond.
See Appendix A for third-party approved fire test results.
Additional fire test results are available from Det-Tronics. Any object having a temperature greater than 0° Kelvin
(–273°C) emits infrared radiation. The hotter the object,
Welding the greater the intensity of the emitted radiation. The
It is recommended that the system be bypassed during closer the infrared source is to the detector, the greater
welding operations in situations where the possibility of a the potential for a false alarm. The IR sensor can respond
false alarm cannot be tolerated. Gas welding mandates to IR radiation sources that can meet the amplitude and
system bypass, since the gas torch is an actual fire. Arc flicker requirements of the detector such as vibrating hot
welding rods can contain organic binder materials in objects.
the flux that burn during the welding operation and are
detectable by the X9800. Welding rods with clay binders Although the detector is designed to reduce false
do not burn and will not be detected by the X9800. actuations, certain combinations of ambient radiation
However, system bypass is always recommended, since must be avoided. For example, if IR radiation with an
the material being welded may be contaminated with intensity that exceeds the fire threshold of the IR sensor
organic substances (paint, oil, etc.) that will burn and should reach the detector as a flickering signal, and if at
possibly cause the X9800 to alarm. the same time an electric arc welding signal also reaches
the detector, an alarm output will be generated.
Artificial Lighting
NOTE
The X9800 should not be located within 3 feet (0.9 m) Radiation generated by false alarm sources such
of artificial lights. Excess heating of the detector could as periodic lightning or sparks in the area can be
occur due to heat radiating from the lights. effectively ignored by the detector using the arc
rejection feature or time delay.
EMI/RFI Interference
The X9800 is resistant to interference by EMI and RFI,
and is EMC Directive compliant and CE marked. It will
not respond to a 5 watt walkie-talkie at distances greater
than 1 foot (0.3 m).
Non-Carbon Fires
The response of the X9800 is limited to carbonaceous
fuels. It should not be used to detect fires from fuels that
do not contain carbon, such as hydrogen, sulfur, and
burning metals.
6.1 4 95-8555
FACTORS INHIBITING DETECTOR RESPONSE IMPORTANT SAFETY NOTES
Windows
WARNING
Glass and Plexiglas windows significantly attenuate Do not open the detector assembly in a hazardous
radiation and must not be located between the detector area when power is applied. The detector contains
and a potential flame source. If the window cannot be limited serviceable components and should never
eliminated or the detector location changed, contact be opened. Doing so could disturb critical optical
Det-Tronics for recommendations regarding window alignment and calibration parameters, possibly
materials that will not attenuate radiation. causing serious damage. This type of damage
could be undetected and could result in failure to
Obstructions see a fire and/or false alarm.
Radiation must be able to reach the detector in order
for it to respond. Care must be taken to keep physical CAUTION
obstructions out of the line of view of the detector. The wiring procedures in this manual are intended
to ensure proper functioning of the device under
Smoke normal conditions. However, because of the
many variations in wiring codes and regulations,
Smoke will absorb radiation. If accumulations of dense
total compliance to these ordinances cannot be
smoke can be expected to precede the presence of a flame,
guaranteed. Be certain that all wiring complies
then detectors that are used in enclosed areas should be
with the NEC as well as all local ordinances. If in
mounted on the wall approximately 3 feet (0.9 m) from the
doubt, consult the authority having jurisdiction
ceiling where the accumulation of smoke is reduced.
before wiring the system. Installation must be done
by a properly trained person.
Detector Viewing Windows
It is important to keep the detector viewing windows as CAUTION
free of contaminants as possible in order to maintain To prevent unwanted actuation or alarm,
maximum sensitivity. Commonly encountered substances extinguishing devices must be disabled prior to
that can significantly attenuate IR radiation include, but performing system tests or maintenance.
are certainly not limited to, the following:
CAUTION
–– Dust and dirt buildup The IR flame detectors are to be installed in
–– Paint overspray places where the risk of mechanical damages is
–– Water and ice low.
ATTENTION
Remove the protective cap from the front of the
detector before activating the system.
ATTENTION
Observe precautions for handling electrostatic
sensitive devices.
6.1 5 95-8555
INSTALLATION • Dense fog and rain as well as certain gases and
vapors can absorb IR radiation and reduce the
NOTE sensitivity of the detector.
The recommended lubricant for threads and
• If possible, fire tests can be conducted to verify
O‑rings is a silicone free grease (p/n 005003-
correct detector positioning and coverage.
001) available from Detector Electronics. Under
no circumstances should a lubricant containing • For ATEX/IECEx installations, the X9800 Flame
silicone be used. Detector housing must be electrically connected to
earth ground.
DETECTOR POSITIONING
Detectors should be positioned to provide the best DETECTOR ORIENTATION
unobstructed view of the area to be protected. The
Refer to Figure 2 and ensure that the oi plate will be
following factors should also be taken into consideration:
oriented as shown when the X9800 is mounted and
• Identify all high risk fire ignition sources. sighted. This will ensure proper operation of the oi
• Be sure that enough detectors are used to adequately system and will also minimize the accumulation of
cover the hazardous area. moisture and contaminants between the oi plate and the
viewing windows.
• Be sure that the unit is easily accessible for cleaning
and other periodic servicing.
IMPORTANT
• Verify that all detectors in the system are properly If removed, the o i plate must be securely
located and positioned so that any fire hazards are tightened to ensure proper operation of
within both the Field of View (FOV) and detection the o i system (40 oz./inches [28.2 N . cm]
range of the detector. The Det-Tronics Q1201C recommended).
Laser Aimer is recommended for establishing the
detector’s FOV. Refer to Appendix A for specific
information regarding detector range and FOV.
• The detector should be aimed downward at least 10
to 20 degrees to allow lens openings to drain (see
Figure 1). The detector should be positioned so
that its FOV does not cover areas outside the oi PLATE
hazardous area. This will minimize the possibility
of false alarms caused by activities outside the area PLACE MAGNET
HERE TO INITIATE
requiring protection. MAGNETIC oi
DETECTOR
STATUS INDICATOR
CENTER AXIS
Figure 2—Front View of the X9800
OF DETECTOR
FIELD OF VIEW
6.1 6 95-8555
Conduit raceways should be inclined so that water will
WARNING
flow to low points for drainage and will not collect inside
All entries must contain appropriately rated plugs
enclosures or on conduit seals. If this is not possible,
or fittings. It is required that each plug or fitting
install conduit drains above the seals to prevent the
be wrench-tightened to an appropriate installation
collection of water or install a drain loop below the
torque and meet the minimum thread engagement
detector with a conduit drain at the lowest point of the
requirements per the applicable local standards,
loop.
codes, and practices in order to retain the defined
Conduit seals are not required for compliance with ratings. PTFE sealant or equivalent should be used
explosion-proof installation requirements, but are on NPT threads.
highly recommended to prevent water ingress in
outdoor applications. Units with M25 threads must use IMPORTANT
an IP66/IP67 washer to prevent water ingress. Devices certified for hazardous locations shall be
installed in accordance with EN/IEC 60079-14 and
WIRING PROCEDURE NEC 505.
In applications where the wiring cable is installed in Leave the shield open at the detector end and
conduit, the conduit must not be used for wiring to other permanently isolate it from accidental contact with
electrical equipment. the case and/or other conductors. At the controller/
fire panel end, connect the shield and power minus
If disconnection of power is required, separate disconnect (–) to chassis (earth) ground either directly or
capability must be provided. through a 0.47 µF 400 Volt non-polarized capacitor
(not supplied). (Refer to Figures 6 through 10.)
CAUTION
Installation of the detector and wiring should be
performed only by qualified personnel.
6.1 7 95-8555
4.0
(10.2)
4X ø0.42 3.0 13.1
(1.1) (7.6) (33.4)
4.0
(10.2)
10.6
(27.0)
E2069
Figure 3—Q9033 Mounting Arm without Collar Attachment Dimensions in Inches (cm)
(See Figure 1 for Correct Detector Orientation.)
Figures 11 and 12 provide examples of typical 2. Check all field wiring to be sure that the proper
installations with a X9800 wired to a fire alarm connections have been made.
panel.
IMPORTANT
Figure 13 shows an EOL resistor installed within the Do not test any wiring connected to the detector
integral wiring compartment of the detector (refer to with a meg-ohmmeter. Disconnect wiring at
“EOL Resistors” for details). the detector before checking system wiring for
continuity.
8 18 28 SPARE
D2070
6.1 8 95-8555
NOTE: DO NOT CONNECT THE X9800 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
24
VDC J1 R7404 CONTROLLER J2
#2 + 1 +
X9800
#2
#1
#1
– 2 – } 10 TO 38 VDC ZONE OUTPUT 1
ZONE OUTPUT 2
33
34
#19 #19
#22 3 (A) +290 VDC ZONE OUTPUT 3 35
#22
4 B - INPUT 1 ZONE OUTPUT 4 36
DETECTOR 1
5 B - INPUT 2 ZONE OUTPUT 5 37
#2 #2
6 B - INPUT 3 ZONE OUTPUT 6 38
#1 #1
X9800 #19 7 B - INPUT 4 ZONE OUTPUT 7 39
#19 J1-5
#22 #22
J1-13 8 B - INPUT 5 ZONE OUTPUT 8 40
DETECTOR 2 9 B - INPUT 6 FIRE LOGIC “A” 41
#2 10 B - INPUT 7 FIRE LOGIC “B” 42
#2
#1 #1 11 B - INPUT 8 ALARM OUTPUT 43
X9800 #19
#19 J1-6 12
#22 D1-1 oi DRIVER EXTERNAL RESET/INHIBIT 44
#22 J1-14
13 D1-2 oi DRIVER OUTPUTS INHIBITED 45
DETECTOR 3
14 D1-3 oi DRIVER FAULT OUTPUT 46
#2 #2 15
#1 D1-4 oi DRIVER EXTERNAL ACCEPT 47
#1
X9800 #19 16 D1-5 oi DRIVER STATUS & DET. OUTPUT S1 48
#19 J1-7
#22 #22 17
J1-15 D1-6 oi DRIVER STATUS & DET. OUTPUT S2 49
DETECTOR 4 18 D1-7 oi DRIVER STATUS & DET. OUTPUT S3 50
#2 19 D1-8 oi DRIVER STATUS & DET. OUTPUT S4 51
#2
#1 #1 20 D2-1 oi DRIVER STATUS & DET. OUTPUT S5 52
X9800 #19
#19 J1-8 21 D2-2 oi DRIVER
#22 STATUS & DET. OUTPUT S6 53
#22 J1-16
22 D2-3 oi DRIVER STATUS & DET. OUTPUT S7 54
DETECTOR 5
23 D2-4 oi DRIVER STATUS & DET. OUTPUT S8 55
#2 #2 24
#1 D2-5 oi DRIVER DATA BUS 0 56
#1 25
X9800 #19 D2-6 oi DRIVER DATA BUS 1 57
#19 J1-9
#22 #22 26
J1-17 D2-7 oi DRIVER DATA BUS 2 58
DETECTOR 6 27 D2-8 oi DRIVER DATA BUS 3 59
#2 28 DMA OUT AVAILABLE DATA BUS 4 60
#2
#1 #1 29 DMA OUT DATA BUS 5 61
X9800 #19
#19 J1-10 30 DMA IN DATA BUS 6 62
#22 #22
J1-18
31 DATA STROBE DATA BUS 7 63
DETECTOR 7
32 DMA IN AVAILABLE CHASSIS (EARTH) GND 64
#2 #2
#1 #1 A2182
X9800 #19
#19 J1-11
#22 #22 J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X9800 NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
WITH PULSE OUTPUT. TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC 62 0.47 μF / 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64. 63 NON-POLARIZED
TERMINAL NO. FUNCTION
64
1/11 DC– ("C" LEAD) NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
2/12 DC+ ("A" LEAD)
19 SIGNAL ("B" LEAD) NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
22 oi ("D" LEAD) 0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
6.1 9 95-8555
NOTE: DO NOT CONNECT THE X9800 "A" LEAD (#2/12) TO
TERMINAL J1-3 (290 VDC).
24
VDC J1 R7404 STAR LOGIC CONTROLLER J2
#2 + 1 +24 VDC ZONE OUTPUT 1 33
#2
#1 2 CIRCUIT GROUND 34
#1 – ZONE OUTPUT 2
X9800 #19
#19 3 +290 VDC ZONE OUTPUT 3 35
#22 #22
4 B1 - INPUT SIGNAL ZONE OUTPUT 4 36
DETECTOR 1
5 B2 - INPUT SIGNAL ZONE OUTPUT 5 37
#2 #2 6 B3 - INPUT SIGNAL ZONE OUTPUT 6 38
#1 #1
X9800 #19 7 B4 - INPUT SIGNAL ZONE OUTPUT 7 39
#19 J1-5
#22 #22 8 B5 - INPUT SIGNAL ZONE OUTPUT 8 40
J1-13
DETECTOR 2 9 B6 - INPUT SIGNAL FIRE LOGIC “A” 41
10 B7 - INPUT SIGNAL FIRE LOGIC “B” 42
#2 #2
#1 11 B8 - INPUT SIGNAL ALARM OUTPUT 43
#1
X9800 #19 12 D1 oi DRIVER EXTERNAL RESET/INHIBIT 44
#19 J1-6
#22 #22
J1-14 13 D2 oi DRIVER OUTPUTS INHIBITED 45
DETECTOR 3 14 D3 oi DRIVER FAULT OUTPUT 46
#2 15 D4 oi DRIVER EXTERNAL ACCEPT 47
#2
#1 #1 16 D5 oi DRIVER STATUS & DET. OUTPUT S1 48
X9800 #19
#19 J1-7 17 STATUS & DET. OUTPUT S2 49
#22 D6 oi DRIVER
#22 J1-15
18 D7 oi DRIVER STATUS & DET. OUTPUT S3 50
DETECTOR 4
19 STATUS & DET. OUTPUT S4 51
D8 oi DRIVER
#2 #2 20 STATUS & DET. OUTPUT S5 52
#1 DATA BUS OUT
#1 21 STATUS & DET. OUTPUT S6 53
X9800 #19 DATA BUS OUT
#19 J1-8
#22 #22 22 STATUS & DET. OUTPUT S7 54
J1-16 DATA BUS OUT
DETECTOR 5 23 STATUS & DET. OUTPUT S8 55
DATA BUS OUT
24 DATA BUS 0 56
#2 DATA BUS OUT
#2 25 DATA BUS 1 57
#1 #1 DATA BUS OUT
X9800 #19 26 DATA BUS 2 58
#19 J1-9 DATA BUS OUT
#22 #22 27 59
J1-17 DATA BUS OUT DATA BUS 3
DETECTOR 6 28 DATA BUS 4 60
NOT USED
29 DATA BUS 5 61
#2 #2 NOT USED
#1 30 DATA BUS 6 62
#1 DATA STROBE IN
X9800 #19 31 63
#19 J1-10 NOT USED DATA BUS 7
#22 #22
J1-18 32 EARTH GROUND 64
NOT USED
DETECTOR 7
A2183
#2 #2
#1 #1
X9800 #19
#19 J1-11
#22 #22 J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X9800 NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED 62 0.47 μF / 400 VDC
WITH PULSE OUTPUT. TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC NON-POLARIZED
63
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64.
TERMINAL NO. FUNCTION 64
1/11 DC– ("C" LEAD) NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
2/12 DC+ ("A" LEAD)
19 SIGNAL ("B" LEAD) NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
22 oi ("D" LEAD) 0.5 REQUIREMENTS (SIGNALING LINES A AND C). GROUND FAULT PROTECTED SYSTEMS
Figure 7—A Typical System, X9800 Detectors Wired to R7404 Star Logic Controller
6.1 10 95-8555
24
VDC J1 R7494 CONTROLLER J2
#2 + 1 +24 VDC ZONE OUTPUT 1 33
#2
#1 2 CIRCUIT GROUND 34
#1 – ZONE OUTPUT 2
X9800 #19
#19 3 +24 VDC ZONE OUTPUT 3 35
#22 #22
4 B1 - INPUT SIGNAL ZONE OUTPUT 4 36
DETECTOR 1
5 B2 - INPUT SIGNAL ZONE OUTPUT 5 37
#2 #2 6 B3 - INPUT SIGNAL ZONE OUTPUT 6 38
#1 #1
X9800 #19 7 B4 - INPUT SIGNAL ZONE OUTPUT 7 39
#19 J1-5
#22 #22 8 B5 - INPUT SIGNAL ZONE OUTPUT 8 40
J1-13
DETECTOR 2 9 B6 - INPUT SIGNAL FIRE LOGIC “A” 41
10 B7 - INPUT SIGNAL FIRE LOGIC “B” 42
#2 #2
#1 11 B8 - INPUT SIGNAL ALARM OUTPUT 43
#1
X9800 #19 12 D1 oi DRIVER EXTERNAL RESET/INHIBIT 44
#19 J1-6
#22 #22
J1-14 13 D2 oi DRIVER OUTPUTS INHIBITED 45
DETECTOR 3 14 D3 oi DRIVER FAULT OUTPUT 46
#2 15 D4 oi DRIVER EXTERNAL ACCEPT 47
#2
#1 #1 16 D5 oi DRIVER STATUS & DET. OUTPUT S1 48
X9800 #19
#19 J1-7 17 STATUS & DET. OUTPUT S2 49
#22 D6 oi DRIVER
#22 J1-15
18 D7 oi DRIVER STATUS & DET. OUTPUT S3 50
DETECTOR 4
19 STATUS & DET. OUTPUT S4 51
D8 oi DRIVER
#2 #2 20 STATUS & DET. OUTPUT S5 52
#1 DATA BUS OUT
#1 21 STATUS & DET. OUTPUT S6 53
X9800 #19 DATA BUS OUT
#19 J1-8
#22 #22 22 STATUS & DET. OUTPUT S7 54
J1-16 DATA BUS OUT
DETECTOR 5 23 STATUS & DET. OUTPUT S8 55
DATA BUS OUT
24 DATA BUS 0 56
#2 DATA BUS OUT
#2 25 DATA BUS 1 57
#1 #1 DATA BUS OUT
X9800 #19 26 DATA BUS 2 58
#19 J1-9 DATA BUS OUT
#22 #22 27 59
J1-17 DATA BUS OUT DATA BUS 3
DETECTOR 6 28 DATA BUS 4 60
NOT USED
29 DATA BUS 5 61
#2 #2 NOT USED
#1 30 DATA BUS 6 62
#1 DATA STROBE IN
X9800 #19 31 63
#19 J1-10 NOT USED DATA BUS 7
#22 #22
J1-18 32 EARTH GROUND 64
NOT USED
DETECTOR 7
A2184
#2 #2
#1 #1
X9800 #19
#19 J1-11
#22 #22 J1-19
DETECTOR 8
TO J1-2
TERMINAL IDENTIFICATION FOR X9800 NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
WITH PULSE OUTPUT. TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC 62 0.47 μF / 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J2-64. NON-POLARIZED
63
TERMINAL NO. FUNCTION
64
1/11 DC– ("C" LEAD) NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS.
2/12 DC+ ("A" LEAD)
19 SIGNAL ("B" LEAD) NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
22 oi ("D" LEAD) 0.5 REQUIREMENTS (SIGNALING LINES A AND C).
GROUND FAULT PROTECTED SYSTEMS
6.1 11 95-8555
R7495 CONTROLLER
(NOT FM APPROVED)
24
VDC J1
+ 1 +24 VDC
#2
#2
#1
#1 – 2 GROUND
X9800 #19
#19
#22 #22
3
DETECTOR 1
4
#2 #2 J2
#1 #1
X9800 #19 5 31
#19 J2-44
#22 #22
J2-36
32
DETECTOR 2
#2 33
#2
#1 #1
X9800 #19 34
#19 J2-45
#22 #22
J2-37
DETECTOR 3 35 D1
#2 #2 36 D2
#1 #1
X9800 #19
#19 J2-46 37 D3
#22 #22
J2-38
DETECTOR 4 38 D4
#2 #2
#1 39 D5
#1
X9800 #19
#19 J2-47
#22 #22 40 D6
J2-39
DETECTOR 5
41 D7
#2 #2
#1 #1 42 D8
X9800 #19
#19 J2-48
#22 #22
J2-40 43 B1
DETECTOR 6
44 B2
#2 #2
#1 #1
X9800 #19 45 B3
#19 J2-49
#22 #22
J2-41
46 B4
DETECTOR 7
#2 47 B5
#2
#1 #1
X9800 #19 48 B6
#19 J2-50
#22 #22 J2-42
DETECTOR 8 49 B7
50 B8
A2185
TO J1-2
TERMINAL IDENTIFICATION FOR X9800 NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
WITH PULSE OUTPUT. TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5. 3 0.47 μF / 400 VDC
TERMINAL NO. FUNCTION 4 NON-POLARIZED
1/11 DC– ("C" LEAD) NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. 5
2/12 DC+ ("A" LEAD)
19 SIGNAL ("B" LEAD) NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
0.5 REQUIREMENTS (SIGNALING LINES A AND C).
22 oi ("D" LEAD)
GROUND FAULT PROTECTED SYSTEMS
6.1 12 95-8555
NOTE: DO NOT CONNECT THE X9800 "A" LEAD (#2/12) TO
TERMINAL J2-34 (290 VDC).
R7405 CONTROLLER
(NOT FM APPROVED)
24
VDC J1
+ 1 +24 VDC
#2
#2
#1
#1 – 2 GROUND
X9800 #19
#19
#22 #22
3
DETECTOR 1
4
#2 #2 J2
#1 #1
X9800 #19 5 31
#19 J2-44
#22 #22
J2-36
32
DETECTOR 2
#2 33
#2
#1 #1
X9800 #19 34 +290 VDC
#19 J2-45
#22 #22
J2-37
DETECTOR 3 35 D1
#2 #2 36 D2
#1 #1
X9800 #19
#19 J2-46 37 D3
#22 #22
J2-38
DETECTOR 4 38 D4
#2 #2
#1 39 D5
#1
X9800 #19
#19 J2-47
#22 #22 40 D6
J2-39
DETECTOR 5
41 D7
#2 #2
#1 #1 42 D8
X9800 #19
#19 J2-48
#22 #22
J2-40 43 B1
DETECTOR 6
44 B2
#2 #2
#1 #1
X9800 #19 45 B3
#19 J2-49
#22 #22
J2-41
46 B4
DETECTOR 7
#2 47 B5
#2
#1 #1
X9800 #19 48 B6
#19 J2-50
#22 #22 J2-42
DETECTOR 8 49 B7
50 B8
A2186
TO J1-2
TERMINAL IDENTIFICATION FOR X9800 NOTE: IF THE POWER SUPPLY MINUS CANNOT BE CONNECTED
WITH PULSE OUTPUT. TO CHASSIS (EARTH) GROUND, CONNECT A 0.47 μF 400 VDC
NON-POLARIZED CAPACITOR BETWEEN J1-2 AND J1-5. 3 0.47 μF / 400 VDC
TERMINAL NO. FUNCTION NON-POLARIZED
4
1/11 DC– ("C" LEAD) NOTE: 2.5 AMPERES @ 24 VDC REQUIRED PER EIGHT DETECTORS. 5
2/12 DC+ ("A" LEAD)
19 SIGNAL ("B" LEAD) NOTE: DETECTOR/CONTROLLER CIRCUITS MEET CLASS B, STYLE
22 oi ("D" LEAD) 0.5 REQUIREMENTS (SIGNALING LINES A AND C).
6.1 13 95-8555
X9800 DETECTOR
FIRE ALARM PANEL
9 19 PULSE OUT SPARE 29
8 18 SPARE 28
COM FIRE2
7 17 27
N.O. FIRE2
6 16 26
N.O. FAULT1
3 13 RS-485 B 23
+ + Vin
2 12 MAN Oi 22
24 VDC
– – Vin – Vin
1 11 21
oi TEST 3
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE CONTACTS ARE CLOSED.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
(TEST SWITCHES ARE NOT NEEDED IF MAGNETIC oi IS USED.)
4 REFER TO SPECIFICATIONS SECTION FOR EOL RESISTOR VALUES. REFER TO EOL RESISTORS SECTION
FOR INSTALLATION DETAILS.
X9800 DETECTOR
FIRE ALARM PANEL
9 19 PULSE OUT SPARE 29
8 18 SPARE 28
COM FIRE2
EOL ALARM 7 17 27
DEVICE 4
N.O. FIRE2
ALARM 6 16 26
N.C. FIRE2
5 15 25
COM FAULT1
4 14 RS-485 A 24
N.O. FAULT1
3 13 RS-485 B 23
+ + Vin
2 12 MAN Oi 22
24 VDC
– – Vin – Vin
1 11 21
oi TEST 3
1 IN NORMAL OPERATION WITH NO FAULTS OCCURRING, THE FAULT RELAY COIL IS ENERGIZED AND
THE CONTACTS ARE CLOSED.
3 INDIVIDUAL MANUAL oi TEST SWITCHES CAN BE INSTALLED REMOTELY OR A DETECTOR SELECTOR AND
ACTIVATION SWITCH CAN BE INSTALLED AT THE FIRE PANEL. TEST SWITCHES ARE NOT SUPPLIED.
(TEST SWITCHES ARE NOT NEEDED IF MAGNETIC oi IS USED.)
6.1 14 95-8555
EOL RESISTORS STARTUP PROCEDURE
To ensure that the insulating material of the wiring
When installation of the equipment is complete, apply
terminal block will not be affected by the heat generated
power and allow 20 to 30 minutes for the detector’s
by EOL resistors, observe the following guidelines when
heated optics to reach equilibrium. Then perform one or
installing the resistors:
more of the following tests:
1. Required EOL resistor power rating must be 5 watts
minimum. Man oi Test — Tests detector output and wiring, without
generating a fire alarm.
NOTE Count Test Mode — Measures actual detector output to
EOL resistors must be ceramic, wirewound controller (cps), without generating a fire alarm.
type, rated 5 watts minimum, with actual power
Fire Alarm Test — For complete system test including
dissipation not to exceed 2.5 watts. This applies to
detector relays. Generates fire alarm output.
ATEX/IECEx installations only.
3. Bend the leads and install the EOL resistor as 2. Press the SELECT button to display the desired
shown in Figure 13. zone on the ZONE indicator on the front panel of the
controller.
4. Maintain a 3/8 inch, 10 mm minimum gap between
the resistor body and the terminal block or any 3. Press and hold the TEST button. The ZONE
other neighboring parts. OUTPUT LED for the tested zone flashes and
the SYSTEM STATUS display indicates a “6” (fire
NOTE condition) if the test is successful.
The EOL resistor can only be used within the
flameproof terminal compartment. Unused 4. Release the TEST button. The ZONE OUTPUT LED
apertures shall be closed with suitable blanking for the tested zone should remain on steadily.
elements.
5. Return to step 2 to test the next detector.
Figure 13—EOL Resistor Installation 2. Simultaneously press and release the SELECT and
TEST buttons. The Status display will change from
a “1” to an “8” indicating that the controller is in the
Count Test mode of operation.
6.1 15 95-8555
3. Press the SELECT button until the desired zone is 2. Inspect the viewing windows for contamination and
displayed on the ZONE indicator on the controller clean as necessary. (Refer to the “Maintenance”
front panel. section for complete information regarding cleaning
of the detector viewing windows.)
4. Press and hold the TEST button. The DETECTOR/
ZONE display indicates the counts per second 3. Check input power to the unit.
(cps) received from the detector. If the counts per
second exceeds 99, the FIRE LOGIC LEDs are 4. Check system and detector logs.
illuminated to indicate that the number shown on
the display must be multiplied by 10. The normal 5. Turn off the input power to the detector and check
reading for an oi test is 80 to 110 cps. For a live all wiring for continuity. Important: Disconnect
fire test, 270 - 330 cps will be generated. wiring at the detector before checking system
wiring for continuity.
A zero reading may indicate a dirty window, oi problem,
faulty detector, or defective wiring. 6. If all wiring checks out and cleaning of the oi plate/
window did not correct the fault condition, check for
Release the Test button, the ZONE and DETECTOR high levels of background IR radiation by covering
display should drop to a reading of 0 to 1 counts per the detector with the factory supplied cover or
second. aluminum foil. If the fault condition clears, extreme
background IR radiation is present. Re-adjust the
view of the detector away from the IR source or
FIRE ALARM TEST (Pulse Output to Fire Alarm Panel) relocate the detector.
1. Disable any extinguishing equipment that is
connected to the system. If none of these actions corrects the problem, return the
detector to the factory for repair.
2. Apply input power to the system.
NOTE
3. Initiate a live fire test or a Mag o i test. (See It is highly recommended that a complete spare
“Magnetic oi / Manual oi” under “Optical Integrity” be kept on hand for field replacement to ensure
in the “Description” section of this manual.) continuous protection.
WARNING
The sensor module (“front” half of the detector)
TROUBLESHOOTING contains no user serviceable components and
should never be tampered with.
WARNING
The sensor module (“front” half of the detector) To maintain maximum sensitivity and false alarm
contains no user serviceable components and resistance, the viewing windows of the X9800
should never be tampered with. must be kept relatively clean. Refer to the
following procedure for cleaning instructions.
1. Disable any extinguishing equipment that is
connected to the unit.
6.1 16 95-8555
CLEANING PROCEDURE LOOSEN TWO CAPTIVE SCREWS
CAUTION
Disable any extinguishing equipment that is
connected to the unit to prevent unwanted
actuation.
CLOCK BATTERY
The real time clock has a backup battery that will
operate the clock with no external power. Return the
device to the factory for battery replacement if needed.
NOTE
If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.
6.1 17 95-8555
FEATURES SPECIFICATIONS
• Responds to a fire in the presence of modulated OPERATING VOLTAGE—
blackbody radiation (i.e., heaters, ovens, turbines) 24 Vdc nominal (18 Vdc minimum, 30 Vdc maximum).
without false alarm Maximum ripple is 2 volts peak-to-peak.
• High speed capability — 30 milliseconds
or CSA compliance, the power source must
F
• Built-in data logging / event monitoring, up to 1500 utilize a SELV (Safety Extra Low Voltage) or Class
events (up to 1000 general, 500 alarms) 2 style power supply.
• Pulse output for compatibility with controller based
POWER CONSUMPTION—
systems
Without heater: 2.1 watts at 24 Vdc nominal;
• Microprocessor controlled heated optics for 3.5 watts at 24 Vdc in alarm.
increased resistance to moisture and ice 2.2 watts at 30 Vdc nominal;
• Automatic, manual, or magnetic oi testing 4.0 watts at 30 Vdc in alarm.
Heater only: 8 watts maximum.
• Easily replaceable oi plate Total power: 16.5 watts at 30 Vdc with EOL resistor
• Fire and fault relays installed and heater on maximum.
• A tri-color LED on the detector faceplate indicates EOL resistor must be ceramic, wirewound type, rated
normal condition and notifies personnel of fire alarm 5 watts minimum, with actual power dissipation not to
or fault conditions exceed 2.5 watts.
TEMPERATURE RANGE—
Operating: –40°F to +167°F (–40°C to +75°C).
Storage: –67°F to +185°F (–55°C to +85°C).
Hazardous location ratings from -55°C to +75°C available
on flameproof model.
HUMIDITY RANGE—
0 to 95% relative humidity, can withstand 100%
condensing humidity for short periods of time.
CONE OF VISION—
The detector has a 90° cone of vision (horizontal) with
the highest sensitivity lying along the central axis.
See Figure 15.
RESPONSE TIME—
32 inch methane plume: < 10 seconds.
1 foot x 1 foot n-Heptane: < 15 seconds.
(See “Appendix A” for details.)
6.1 18 95-8555
100% REPRESENTS THE MAXIMUM DETECTION DISTANCE FOR A
GIVEN FIRE. THE SENSITIVITY INCREASES AS THE ANGLE OF
THREAD SIZE—
INCIDENCE DECREASES. Conduit connection: Four entries, 3/4 inch NPT or M25.
VIEWING ANGLE Conduit seal not required.
0°
15°
100
15° SHIPPING WEIGHT (Approximate)—
30° 90 30°
Aluminum: 7 pounds (3.2 kilograms).
Stainless Steel: 14.6 pounds (6.7 kilograms).
80
45° 45° Mounting Arm (AL): 6 pounds (2.75 kilograms).
70 Mounting Arm (SS): 14 pounds (6.4 kilograms).
60
50
WARRANTY PERIOD—
DETECTION
DISTANCE 3 years
(PERCENT) 40
30 CERTIFICATION—
20
FM ®
10
APPROVED
A1288
Appendix A - FM
ENCLOSURE MATERIAL— Appendix B - CSA
Copper-free aluminum (painted) or Stainless Steel (316/ Appendix C - ATEX
CF8M Cast). Appendix D - IECEx
VIBRATION—
Conformance per FM 3260: 2000, MIL-STD 810C (Curve AW).
DIMENSIONS—
See Figure 16.
WIRING—
Field wiring screw terminals are UL/CSA rated for up to
14 AWG wire, and are DIN/VDE rated for 2.5 mm2 wire.
Screw terminal required torque range is 3.5–4.4 in.-lbs.
(0.4-0.5 N·m).
Important: 18 Vdc minimum must be available at the
detector. For ambient temperatures below –10°C (14°F)
and above +60°C (140°F) use field wiring suitable for
both minimum and maximum ambient temperature.
4.7
(11.9)
10.2 4.8
B2223
(25.9) (12.2)
6.1 19 95-8555
REPLACEMENT PARTS ORDERING INFORMATION
The detector is not designed to be repaired in the field. If When ordering, please specify:
a problem should develop, refer to the “Troubleshooting” X9800 IR Flame Detector with Pulse Output
section. If it is determined that the problem is caused by Refer to the X9800 Model Matrix below for details
an electronic defect, the device must be returned to the
Q9033 Mounting Arm is required:
factory for repair.
–– Q9033A for aluminum detectors only
–– Q9033B for aluminum and stainless steel detectors
REPLACEMENT PARTS
Part Number Description ACCESSORIES
009208-002 oi Replacement kit for X52/X22/X98 (5 Reflector Plates)
with Inspector Connector and Monitor Part Number Description
007307-002 Replacement oi Reflector Plate for X52/X22/X98 000511-029 Converter RS485 to RS232
(requires Inspector Connector to calibrate) 103881-001 Converter RS485 to USB
007819-001 W6300B1002 Serial Inspector Connector
(Inspector Monitor software included)
W6300B1003 USB Inspector Connector
007819-002 (Inspector Monitor software included)
009207-001 Flame Inspector Monitor CD
103922-001 Model 475 HART Communicator
102740-002 Magnet
DEVICE REPAIR AND RETURN 008082-001 Magnet and Adapter for Extension Pole
007739-001 Magnet and Extension Pole
Prior to returning devices, contact the nearest local 007240-001 Q1116A1001, Air Shield (AL)
007818-001 Q1118A1001 Aluminum Air Shield/Flange Mount (AL)
Detector Electronics office so that a Return Material 007818-002 Q1118S1001 Stainless Steel Air Shield/Flange Mount (SS)
Identification (RMI) number can be assigned. A 009177-001 Q1120A1001 Paint Shield mounting ring (AL)
009199-001 Q1198A1001 Dual Air Shield/Flange Mount (X9800 only)/(AL)
written statement describing the malfunction must 006097-001 Q1201 Laser
accompany the returned device or component to 102871-001 Laser Battery, 3V Lithium (laser)
assist and expedite finding the root cause of the 007255-001 Q1201C1001 X-Series Laser Holder (AL/Plastic)
007338-001 Q2000A1001 X-Series Weather Shield (AL)
failure. Q9033B Stainless Steel Mounting Arm Assembly is for
007290-001 aluminum and stainless steel detectors
Pack the unit properly. Always use sufficient packing Q9033A Aluminum Mounting Arm Assembly is for aluminum
007290-002 detectors only
material. Where applicable, use an antistatic bag as 011385-001 Q9033 Collar Attachment
protection from electrostatic discharge. 101197-001 Stop Plug, 3/4” NPT, AL
101197-004 Stop Plug, 3/4” NPT, SS
101197-005 Stop Plug, M25, AL, IP66
NOTE 101197-003 Stop Plug, M25, SS, IP66
010816-001 Stop Plug, 20 Pack, 3/4”NPT, AL
Det-Tronics reserves the right to apply a service 010817-001 Stop Plug, 20 Pack, 3/4”NPT, SS
charge for repairing returned product damaged as 010818-001 Stop Plug, 20 Pack, M25, AL, IP66
a result of improper packaging. 010819-001 Stop Plug, 20 Pack, M25, SS, IP66
103363-001 14 mm Hex Wrench (Steel)
103406-001 Screwdriver
001680-001 Window cleaner (6 pack)
Return all equipment transportation prepaid to the factory 107427-040 O-ring - Rear Cover (Viton) - black or brown
in Minneapolis. 005003-001 1 oz grease for detectors (non-silicon)
104346-154 O-ring - Rear Cover (Fluorosilicone) - blue
012549-001 1 oz PTFE silicone free lubricant
NOTE
It is highly recommended that a complete spare
be kept on hand for field replacement to ensure
continuous protection.
6.1 20 95-8555
X9800 MODEL MATRIX
MODEL DESCRIPTION
X9800 Single Frequency IR Flame Detector
TYPE MATERIAL
A Aluminum
S Stainless Steel (316)
TYPE THREAD TYPE
4M 4 PORT, METRIC M25
4N 4 PORT, 3/4" NPT
TYPE OUTPUTS
15 Relay and Pulse
TYPE APPROVALS
W FM/CSA/ATEX/IECEx
TYPE CLASSIFICATION
1 Division/Zone Ex d e
2 Division/Zone Ex d
6.1 21 95-8555
APPENDIX A
FM APPROVAL AND PERFORMANCE REPORT
• Explosion-proof for Class I, Div. 1, Groups B, C, and D (T5) Hazardous (Classified) Locations per FM 3615.
• Dust-ignition proof for Class II/III, Div. 1, Groups E, F, and G (T5) Hazardous (Classified) Locations per FM 3615.
• Nonincendive for Class I, Div. 2, Groups A, B, C, and D (T3) Hazardous (Classified) Locations per FM 3611.
• Nonincendive for Class II, Div. 2, Groups F and G (T3) Hazardous (Classified) Locations per FM 3611.
• Enclosure rating NEMA Type 4X per NEMA 250.
• Ambient Temperature Limits: –40°F to +167°F (–40°C to +75°C).
• Automatic Fire Alarm Signaling Performance verified per FM 3260 (2000).
The following accessories are FM approved for use with the X9800 Flame Detector:
Part Number Description
102740-002 Magnet
007739-001 Magnet and Extension Pole
007290-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
007290-002 Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001 Q9033 Collar Attachment
The oi test procedure, as described in the “Magnetic oi / Manual oi” section of this instruction manual, is the approved
external optical test method for this detector to verify end-to-end detector function. This test replaces the function and
need of a traditional external test lamp.
6.1 22 95-8555
FM Approval Description and Performance Report – Continued
RESPONSE CHARACTERISTICS
Very High Sensitivity
Distance Typical Response Time
Fuel Size / Flow Rate TDSA Quick Fire
feet (m) (seconds)
n-Heptane 1 x 1 foot 85 (25.9) 15 On Off
Methane 32 inch plume 60 (18.3) 5 On Off
Propane Torch 2 (0.6) 0.04 On On
High Sensitivity
Distance Typical Response Time
Fuel Size / Flow Rate TDSA Quick Fire
feet (m) (seconds)
n-Heptane 1 x 1 foot 50 (15.2) 8 On Off
Methane 32 inch plume 35 (10.7) 3 On Off
Pyrodex 40 grams 10 (3) 0.1 On On
Black Powder 40 grams 10 (3) 0.04 On On
n-Heptane 1 x 1 foot 50 (15.2) 6 On On
Low Sensitivity
Distance Typical Response Time
Fuel Size / Flow Rate TDSA Quick Fire
feet (m) (seconds)
n-Heptane 1 x 1 foot 15 (4.6) 8 On Off
6.1 23 95-8555
FM Approval Description and Performance Report – Continued
FIELD OF VIEW
Very High Sensitivity, Quick Fire Off
Distance Horizontal Typical Horiz. Response Vertical Typical Vert. Response
Fuel Size
feet (m) (degrees) Time (seconds) (degrees) Time (seconds)
42.5 +45 12 +45 10
n-Heptane 1 x 1 foot
(13) –45 14 –30 16
30 +45 7 +45 6
Methane 32 inch plume
(9.1) –45 4 –30 4
6.1 24 95-8555
APPENDIX B
CSA APPROVAL
DIVISION CLASSIFICATION:
Infrared Flame Detector/Controller X9800 series, rated 18-30 Vdc, 2.1 Watts to 16.5 Watts.
Relay contacts rated 5 Amps @ 30 Vdc.
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 0-M91 – General requirements - Canadian Electrical Code. Part II
CAN/CSA-C22.2 No. 25-1966 – Enclosures for use in Class II Groups E, F & G Hazardous Locations.
CAN/CSA-C22.2 No. 30-M1986 – Explosion-Proof Enclosures for use in Class I Hazardous Locations.
CAN/CSA-C22.2 No. 94-M91 – Special Purpose Enclosures.
CAN/CSA-C22.2 No. 142-M1987 – Process Control Equipment.
CAN/CSA-C22.2 No. 213-M1987 – Nonincendive Electrical Equipment for use in Class I, Division 2 Hazardous Locations.
ZONE CLASSIFICATION:
CLASS 4818 04 - SIGNAL APPLIANCES - Systems - For Hazardous Locations
Ex db eb IIC T6...T5
T6 (Tamb = -50°C to +60°C)
T5 (Tamb = -50°C to +75°C)
Ex tb IIIC T95°C
(Tamb = -50°C to +75°C)
Seal required adjacent to enclosure
IP66/IP67
Ex db IIC T6...T5
T6 (Tamb = -55°C to +60°C)
T5 (Tamb = -55°C to +75°C)
Ex tb IIIC T95°C
(Tamb = -55°C to +75°C)
Seal required adjacent to enclosure
IP66/IP67
APPLICABLE REQUIREMENTS
CAN/CSA-C22.2 No. 60079-0: 2007 – Electrical apparatus for explosive atmospheres. Part 0: General requirements
CAN/CSA-C22.2 No. 60079-1: 2011 – Explosive atmospheres. Part 1: Equipment protection by flameproof enclosures “d”
CAN/CSA-C22.2 No. 60079-7: 2012 – Explosive atmospheres. Part 7: Equipment protection by increased safety “e”
CAN/CSA-C22.2 No. 60079-31: 2012 – Explosive atmospheres. Part 31: Equipment dust ignition protection by enclosure “t”
The following accessories are CSA approved for use with the X9800 Flame Detector:
Part Number Description
102740-002 Magnet
007739-001 Magnet and Extension Pole
007290-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
007290-002 Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001 Q9033 Collar Attachment
6.1 25 95-8555
APPENDIX C
ATEX APPROVAL
Compliance with:
EN 60079-0: 2012+A11:2013
EN 60079-1: 2014
EN 60079-7: 2007
EN 60079-31: 2009
EN 60529:1991+A1:2000+A2:2013
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are ATEX certified and accepts wiring specifications from
14-24 AWG or 2.5-0.2 mm2.
The flame detector model X9800IR shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure “d” for use with the
terminal compartment in type of explosion protection flameproof enclosure “d,” or in type of explosion protection
increased safety “e” for use with the terminal compartment in type of explosion protection increased safety “e.” They
shall be IP66/IP67 rated, suitable for the conditions of use, and correctly installed.
The metal housing for the Infrared (IR) flame detector type X9800 must be electrically connected to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
6.1 26 95-8555
NOTE
Operational performance verified from –40°C to +75°C.
NOTE
An optional third party addressable module can only be used within the Ex d flameproof model unless the
addressable module is component certified as Ex e for use within the Ex d e increased safety model.
NOTE
Refer to the “EOL Resistors” section for installation details. All cable entry devices and blanking elements
shall be certified to “E-generation” or “ATEX” standards, in type of explosion protection increased safety “e” or
flameproof enclosure “d” (as applicable), suitable for the conditions of use and correctly installed. They shall
maintain the degree of ingress protection IP66/IP67 for the apparatus. Unused conduit entries shall be closed
with suitable blanking elements.
NOTE
For ATEX installations, the X9800 detector housing must be electrically connected to earth ground.
The following accessories are ATEX approved for use with the X9800 Flame Detector:
Part Number Description
007290-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
007290-002 Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001 Q9033 Collar Attachment
6.1 27 95-8555
APPENDIX D
IECEx APPROVAL
CERTIFICATE OF CONFORMITY
IECEx ULD 06.0018X
Ex db eb IIC T6...T5 Ex db IIC T6...T5
Ex tb IIIC T80°C Ex tb IIIC T80°C
T6 (Tamb = –50°C to +60°C) or T6 (Tamb = –55°C to +60°C)
T5 (Tamb = –50°C to +75°C) T5 (Tamb = –55°C to +75°C)
IP66/IP67. IP66/IP67.
Compliance with:
IEC 60079-0: 2011, Ed. 6
IEC 60079-1: 2014, Ed. 7
IEC 60079-7: 2006, Ed. 4
IEC 60079-31: 2008, Ed. 1
IEC 60529: 2013, Ed. 2.2
INSTALLATION INSTRUCTIONS
The field wiring connections in the terminal compartment are suitable certified and accepts wiring specifications from
14-24 AWG or 2.5-0.2 mm2.
The flame detector model X9800IR shall be installed according to the instructions given by the manufacturer.
The cable entry devices shall be certified in type of explosion protection flameproof enclosure “d” for use with the
terminal compartment in type of explosion protection flameproof enclosure “d,” or in type of explosion protection
increased safety “e” for use with the terminal compartment in type of explosion protection increased safety “e.” They
shall be IP66/IP67 rated, suitable for the conditions of use and correctly installed.
The metal housing for the Infrared (IR) flame detector type X9800 must be electrically connected to earth ground.
For ambient temperatures below –10°C and above +60°C use field wiring suitable for both minimum and maximum
ambient temperature.
The following accessories are IECEx approved for use with the X9800 Flame Detector:
Part Number Description
007290-001 Q9033B Stainless Steel Mounting Arm Assembly is for aluminum and stainless steel detectors
007290-002 Q9033A Aluminum Mounting Arm Assembly is for aluminum detectors only
011385-001 Q9033 Collar Attachment
6.1 28 95-8555
95-8555
FlexSonic ® Acoustic X3301 Multispectrum PointWatch Eclipse ® IR FlexVu ® Universal Display Eagle Quantum Premier ®
Leak Detector IR Flame Detector Combustible Gas Detector with GT3000 Toxic Gas Detector Safety System
Corporate Office Phone: 952.946.6491 All trademarks are the property of their respective owners.
6901 West 110th Street Toll-free: 800.765.3473 © 2016 Detector Electronics Corporation. All rights reserved.
Minneapolis, MN 55438 USA Fax: 952.829.8750 Det-Tronics manufacturing system is certified to ISO 9001—
www.det-tronics.com det-tronics@det-tronics.com the world’s most recognized quality management standard.