I/A Series HARDWARE

Product Specifications

PSS 21H-2Z42 B4

FBM242, Externally Sourced, Discrete Output Interface Module

The FBM242 Discrete Output Interface Module contains 16 discrete output channels which are sourced
externally.

FEATURES

 Executes the Discrete I/O or Ladder Logic

Key features of the FBM242 modules are:

program, with the following configurable options:


Input Filter Time, Fail Safe Configuration, FailSafe Fall-Back, and Sustained or Momentary
Outputs
 Various Termination Assemblies (TAs) that
contain:

 Sixteen discrete outputs


 Supports discrete output signals at voltages of:

15 to 60 V dc
120 V ac/125 V dc
240 V ac
 Each input and output is galvanically isolated;

group isolated when used with external excitation


 Compact, rugged design suitable for enclosure in

Class G3 (harsh) environments

Current limiting devices


Fuses
Relay outputs with external power source,
fusing, and power distribution
Solid state outputs
Redundant power distribution

Foxboro

PSS 21H-2Z42 B4
Page 2

OVERVIEW

FIELDBUS COMMUNICATION

The FBM242 Discrete Output Interface Module


contains 16 discrete output channels, which are
sourced externally, rated up to 2 A at 60 V dc.
Associated termination assemblies (TAs) provide for
discrete outputs to loads of 2 A at 60 V dc, relay
outputs (120 V ac/125 V dc, or 240 V ac), or relay
outputs with power distribution and fusing. Each
output is fully isolated from other channels and
ground.

A Fieldbus Communications Module or a Control


Processor interfaces to the redundant 2 Mbps
module Fieldbus used by the FBMs. The FBM242
accepts communication from either path (A or B) of
the redundant 2 Mbps Fieldbus should one path
fail or be switched at the system level, the module
continues communication over the active path.

The module interfaces electrical output signals from a


control processor to the field devices. It executes a
digital I/O application program, with ladder logic
support, and provides a Fail-Safe Configuration
option for the outputs.

Field power for contacts or solid state switches is


current limited.

COMPACT DESIGN
The module has a compact design, with a rugged
extruded aluminum exterior for physical protection of
the circuits. Enclosures specially designed for
mounting the FBMs provide various levels of
environmental protection, up to harsh environments
(Class G3), per ISA Standard S71.04.

VISUAL INDICATORS
Light-emitting diodes (LEDs) incorporated into the
front of the module provide visual indication of the
module operational status, as well as the discrete
states of the individual output points.

EASY REMOVAL/REPLACEMENT
The module can be removed/replaced without
removing field device termination cabling, power, or
communication cabling.

SECURITY

MODULAR BASEPLATE MOUNTING


The module mounts on a DIN rail mounted Modular
baseplate, which accommodates up to four or eight
Fieldbus Modules. The Modular baseplate is either
DIN rail mounted or rack mounted, and includes
signal connectors for redundant Fieldbus, redundant
independent dc power, and termination cables.

TERMINATION ASSEMBLIES (TAs)


Field I/O signals connect to the FBM subsystem via
DIN rail mounted TAs. The TAs used with the
FBM242 are described in TERMINATION
ASSEMBLIES on page 8.

PSS 21H-2Z42 B4
Page 3

F U N C T I O N A L S P E C I F I C AT I O N S

Output Channels

Communication

Sixteen isolated channels.

Applied Voltage

Communicates with its associated FCM or FCP via


the redundant 2 Mbps module Fieldbus

15 to 60 V dc (maximum)

Power Requirements

Load Current
2.25 A (maximum) per channel

Load Current-In-Rush
8 A (maximum) for 20 ms per channel at 30C.
6.4 A (maximum) for 20 ms per channel at 70C.

On-State Voltage Drop


0.2 V (maximum) at 2.25 A

Off-State Leakage Current


0.1 mA (maximum)

Inductive Loads
Module output may require a protective diode or
metal oxide varistor (MOV) connected across the
inductive load.

Output Channel Isolation


Each channel is galvanically isolated from all other
channels and earth (ground). The module withstands,
without damage, a potential of 600 V ac applied for
one minute between any channel and ground, or
between a given channel and any other channel.
CAUTION
This does not imply that these channels are
intended for permanent connection to
voltages of these levels. Exceeding the limits
for input voltages, as stated elsewhere in this
specification, violates electrical safety codes
and may expose users to electric shock.

INPUT VOLTAGE RANGE (REDUNDANT)


24 V dc +5%, -10%
CONSUMPTION (MAXIMUM)
3 W (maximum) at 24 V dc
HEAT DISSIPATION (MAXIMUM)
6.5 W (maximum) at 24 V dc (with all outputs at
1.5 A each)

Calibration Requirements
The module and termination assemblies require no
calibration.

PSS 21H-2Z42 B4
Page 4

F U N C T I O N A L S PE CI F I C AT I O N S ( C O N T I N U E D )

Regulatory Compliance
ELECTROMAGNETIC COMPATIBILITY (EMC)
European EMC Directive 89/336/EEC
Meets: EN 50081-2 Emission standard
EN 50082-2 Immunity standard
EN 61326 Annex A (Industrial Levels)
CISPR 11, Industrial Scientific and Medical
(ISM) Radio-frequency Equipment Electromagnetic Disturbance Characteristics
- Limits and Methods of Measurement
Meets: Class A Limits
IEC 61000-4-2 ESD Immunity
Contact 4 kV, air 8 kV
IEC 61000-4-3 Radiated Field Immunity
10 V/m at 80 to 1000 MHz
IEC 61000-4-4 Electrical Fast
Transient/Burst Immunity
2 kV on I/O, V dc power and communication
lines
IEC 61000-4-5 Surge Immunity
2kV on ac and dc power lines; 1kV on I/O
and communications lines
IEC 61000-4-6 Immunity to Conducted
Disturbances induced by Radio-frequency
Fields
10 V (rms) at 150 kHz to 80 MHz on I/O, V
dc power and communication lines
IEC 61000-4-8 Power Frequency Magnetic
Field Immunity
30 A/m at 50 and 60 Hz
PRODUCT SAFETY - TERMINATION
ASSEMBLIES WITH LOW VOLTAGE INPUTS
Underwriters Laboratories (UL) for U.S. and
Canada
UL/UL-C listed as suitable for use in
UL/UL-C listed Class I, Groups A-D;
Division 2; temperature code T4 enclosure
based systems. These modules are also UL
and UL-C listed as associated apparatus for
supplying non-incendive communication
circuits for Class I, Groups A-D hazardous
locations when connected to specified
I/A Series processor modules as described
in the I/A Series DIN Rail Mounted

Subsystem Users Guide (B0400FA).


Communications circuits also meet the
requirements for Class 2 as defined in Article
725 of the National Electrical Code (NFPA
No.70) and Section 16 of the Canadian
Electrical Code (CSA C22.1). Conditions for
use are as specified in the I/A Series DIN Rail
Mounted Subsystem Users Guide
(B0400FA).
European Low Voltage Directive 73/23/EEC
and Explosive Atmospheres (ATEX) directive
94/9/EC
CENELEC (DEMKO) certified as
EEx nA IIC T4 for use in CENELEC certified
Zone 2 enclosure certified as associated
apparatus for supplying non-incendive field
circuits for Zone 2, Group IIC, potentially
explosive atmospheres when connected to
specified I/A Series processor modules as
described in the I/A Series DIN Rail Mounted
Subsystem Users Guide (B0400FA). Also
see, Certifications for Termination
Assemblies on page 11.
PRODUCT SAFETY - TERMINATION
ASSEMBLIES WITH RELAY OUTPUTS OR
HIGH VOLTAGE INPUTS
Underwriters Laboratories (UL) for U.S. and
Canada
UL/UL-C listed as suitable for use in ordinary
locations and compliant with UL 3121, First
Edition, and Canadian Standard, C22.2
No.1010.1-92 when connected to specified
I/A Series processor modules as described
in the I/A Series DIN Rail Mounted
Subsystem Users Guide (B0400FA).
European Low Voltage Directive 73/23/EEC
Certified for use in ordinary locations and
compliant with IEC 61010 when connected
to specified I/A Series processor modules as
described in the I/A Series DIN Rail Mounted
Subsystem Users Guide (B0400FA)

PSS 21H-2Z42 B4
Page 5

E N V I R O N M E N TA L S P E C I F I C AT I O N S (1 )

Operating Conditions
TEMPERATURE
Module
-20 to +70C (-4 to +158F)
Termination Assembly
PVC
-20 to +50C (-4 to +122F)

PA
-20 to +70C (-4 to +158F)

RELATIVE HUMIDITY
5 to 95% (noncondensing
ALTITUDE
-300 to +3000 m (-1000 to +10 000 ft)

Storage Conditions
TEMPERATURE
-40 to +70C (-40 to +158F)
RELATIVE HUMIDITY
5 to 95% (noncondensing)
ALTITUDE
-300 to +12 000 m (-1000 to +40 000 ft)

Contamination
Suitable for use in Class G3 (Harsh) environments as
defined in ISA Standard S71.04, based on exposure
testing according to EIA Standard 364-65, Class III.

Vibration
7.5 m/s2 (5 to 500 Hz)

(1) The environment ranges can be extended by the type of enclosure containing the module. Refer to the Product Specification Sheet
(PSS) applicable to the enclosure that is to be used.

PSS 21H-2Z42 B4
Page 6

P H Y S I C A L S P E C I F I C AT I O N S

Mounting
MODULE
FBM242 mounts on a Modular Baseplate. The
baseplate can be mounted on a DIN rail
(horizontally or vertically), or horizontally on a
19-inch rack using a mounting kit. Refer to
PSS 21H-2W6 B4 for details.
TERMINATION ASSEMBLY
The TA mounts on a DIN rail and accommodates
multiple DIN rail styles including 32 mm (1.26 in)
and 35 mm 1.38 in)

Mass
MODULE
284 g (10 oz) approximate
TERMINATION ASSEMBLY
Compression
127 mm (5.02 in) 272 g (0.60 lb,
approximate)
148 mm (5.75 in) 285 g (0.65 lb,
approximate)
216 mm (8.51 in) 320 g (0.70 lb,
approximate)
Ring Lug
196 mm (7.78 in) 310 g (0.68 lb,
approximate
321mm (12.64 in) 600 g (1.6 lb,
approximate

Part Numbers
MODULE
P0916TA
TERMINATION ASSEMBLIES
Refer to FUNCTIONAL SPECIFICATIONS TERMINATION ASSEMBLIES on page 9

Dimensions - Module
HEIGHT
102 mm (4 in),114 mm (4.5 in) including mounting
lugs
WIDTH
45 mm (1.75 in)
DEPTH
104 mm (4.11 in)

Dimensions - Termination Assembly


COMPRESSION SCREW
Refer to page 13
RING LUG AND KNIFE SWITCH
Refer to page 15

Termination Cables
CABLE LENGTHS
Up to 30 m (98 ft)
CABLE MATERIALS
Polyurethane or Hypalon/XLP.
TERMINATION CABLE TYPE
Type 4 or type 4H - Refer to Table 1
CABLE CONNECTION
37-pin male D-subminiature

Construction - Termination Assembly


MATERIAL
Polypropylene (PVC), compression
Polyamide (PA), compression
PVC, ring lug
PVC, knife terminal
FAMILY GROUP COLOR
Dark blue - discrete
TERMINAL BLOCKS
Outputs- 2 tiers (switch and solid state), 3 tiers
(relay), 16 positions
Power Distribution - 2 tiers, 4 positions

PSS 21H-2Z42 B4
Page 7

P H Y S I C A L S PE CI F I C AT I O N S ( C O N T I N U E D )

Field Termination Connections


COMPRESSION - ACCEPTED WIRING SIZES
Solid/Stranded/AWG
0.2 to 4 mm2/0.2 to 2.5 mm2/24 to 12 AWG
Stranded with Ferrules
0.2 to 2.5 mm2 with or without plastic collar
RING-LUG - ACCEPTED WIRING SIZES
#6 size connectors (0.375 in (9.5 mm))
0.5 to 4 mm2/22 AWG to 12 AWG

Termination Assembly Switching Relays


ELECTRICAL SERVICE LIFE
100,000 operations at rated resistive load
5,000,000 operations at no load.
5 A RELAY
Type
Single-Pole, Double-Throw, Normally Open
(SPDT_NO)
Switching Current
5 A at up to 120 V ac (see GENERAL
PURPOSE PLUG-IN RELAY TERMINATION
ASSEMBLY SPECIFICATIONS on page 16)

PSS 21H-2Z42 B4
Page 8

TERMINATION ASSEMBLIES
General Description
Field I/O signals connect to the FBM subsystem via
DIN rail mounted termination assemblies (TAs).
Multiple types of TAs are available with FBMs to
provide I/O signal connections, signal conditioning,
optical isolation from signal surges, external power
connections, and/or fusing for protection of the FBM
and/or field device as required by the particular FBM.
Since these features are built into the termination
assemblies (where required), in most applications
there is no need for additional termination equipment
for field circuit functions such as circuit protection or
signal conditioning (including fusing and power
distribution).
The DIN rail mounted termination assemblies
connect to the FBM subsystem baseplate by means
of removable termination cables. The cables are
available in a variety of lengths, up to 30 meters
(98 feet), allowing the termination assemblies to be
mounted in either the enclosure or in an adjacent
enclosure. Refer to FUNCTIONAL SPECIFICATIONS
- TERMINATION ASSEMBLIES on page 9 for
termination cable part numbers and specifications.

Discrete Outputs
Termination assemblies with discrete outputs support
sixteen 2-wire discrete output signals at passive low
voltages of less than 60 V dc and active high voltage
levels of 120 V ac or 240 V ac. Active termination
assemblies support output signal conditioning for
FBMs. To condition signals, these termination
assemblies provide fuse protection, relays, solid-state
devices, and terminal blocks to connect externally
supplied optional power distribution.
Low Voltage Discrete Outputs
The low voltage outputs (less than 60 V dc) use
passive termination assemblies. These assemblies
are available with and without output protection

(fusing). Termination assemblies with protection have


individual user serviceable fuses that are designed to
limit the output current to 2 A. Sixteen vertically
mounted, one per channel, 3.15 A sand filled fuses
(temperature derated) allow a maximum of 2 A
current per output channel. Termination assemblies
without fusing (unprotected) are intended for use by
Foxboro engineers or customers who are using
interposing relays or fuse terminal blocks between
the termination assembly and the field devices.
Power for the low voltage outputs can be supplied by
the FBM +24 V dc auxiliary power supply (internally
(FBM) sourced) or by a field voltage source (externally
sourced).
High Voltage Discrete Outputs
The high voltage output (120 V ac or 240 V ac)
termination assemblies use plug-in SPDT (Form C)
electromechanical relays and solid-state switches.
The plug-in sockets allow field replacement of
individual relays. The relays and associated sockets
are located under the component covers of the
termination assemblies.The termination assemblys
switched outputs use unsealed, general purpose
relays.These assemblies are capable of providing
mixed voltage and are designed to provide signal
segregation by locating the low voltage inputs an the
opposite side of the terminal assembly from the
outputs. A solid-state output module is optionally
available. High voltage discrete outputs are always
externally sourced power.
The output termination assemblies come in either
output or output with power distribution (usersupplied via terminals on the termination assembly).
In both configurations, when the FBM output is on,
the relay coil is energized and the relay contact is
switched from normally closed (NC) position to the
normally open (NO) position. The FBM +24 V dc
auxiliary power supply is used to energize the relay
coil.

PSS 21H-2Z42 B4
Page 9

Termination assemblies with power distribution have


a dedicated terminal block which provides a
connection to externally supplied power and
distributed internally on the termination assembly to
each of the output channels. The line or positive side
of the supply is fused; the neutral or negative side of
the supply is connected to the field.
F U N C T I O N A L S P E C I F I C AT I O N S - T E R M I N AT I O N A S S E M B L I E S
TA Part Number(b)
FBM
Type

Output Signal(a)

PVC

PA

TA
TA
Term. Cable Certification
Type(e)
Type(c) Type(d)

FBM242 16 channel, switch (protected - fused)


15 to 60 V dc (externally sourced) at 2 A
maximum
Channel isolation provided by FBM242

P0916JY
P0916RJ

C
RL

4, 4H

1,2

FBM242 16 channel, switch (unprotected - no


fuses)
15 to 60 V dc (externally sourced) at 2 A
maximum
Channel isolation provided by FBM242

P0917XX

4, 4H

1,2

FBM242 16 channel, switch (protected - fused)


P0917HX
15 to 60 V dc (externally sourced) at 2 A
maximum with power distribution
Current is limited to 12A maximum for
each group of 8 channels simultaneously
Group isolation provided by termination
assembly

4, 4H

1,4

P0923LH(f)
FBM242 16 channel, switch (each channel is
protected - fused)
Redundant power
15 to 60 V dc (externally sourced) at 12 A
maximum with power distribution
Group isolation provided by termination
assembly

4, 4H

1,4

FBM242 16 channel, switch (externally sourced)


P0923LL
SPDT (Form C) Relays with LED indicators
<30 V dc at 5 A maximum,
Up to 250 V ac at 5 A maximum
Channel isolation provided by termination
assembly relays

PSS 21H-2Z42 B4
Page 10

F U N C T I O N A L S P E C I F I C AT I O N S - T ER M I NAT I O N A SS EM BL I E S ( C O N T I N U E D )
TA Part Number(b)
FBM
Type

Output Signal(a)

PVC

PA

TA
TA
Term. Cable Certification
Type(e)
Type(c) Type(d)

P0916NG P0916YY
FBM242 16 channel, switch (externally sourced)
SPDT (Form C) Relays
P0916RK
<30 V dc at 5 A maximum,
Up to 250 V ac at 5 A maximum
Channel Isolation provided by termination
assembly relays

C
RL

FBM242 16 channel, switch (externally sourced)


with power distribution
SPDT (Form C) Relays
<30 V dc at 5 A maximum
Up to 250 V ac at 5 A maximum
Total current is limited to 12 A maximum
for each group of 8 channels
simultaneously
Group isolation provided by termination
assembly

C
RL

P0926DV
FBM242 16 channel, switch (externally sourced)
SPDT (Form C) Relays
125 V ac/125V dc at 2 A maximum
Channel isolation provided by termination
assembly relays

Knife (g)

FBM242 16 channel, switch (externally sourced)


P0926BE
Solid State Switch 125 V ac/125V dc at 2
A maximum
Channel isolation provided by FBM242

Knife (g)

P0916JZ
P0916RL

P0916YZ

(a) Maximum current is limited to12 A per 8 channels. Output inductive load limits based on current of 2 A. Inductance limit increases by
a factor of 4, for each factor of 2 reduction in current. For an inductive load above stated limits, a snubber diode is required for a dc
inductive load or a MOV (metal oxide varistor) is required for an ac inductive load. Diode current rating must be equal to the maximum
load current and voltage rating equal to 1.3X maximum supply voltage. MOV must be rated for 120 V ac use and current rating must
be equal to maximum load current.
(b) PVC is polyvinyl chloride rated from -20 to +50C (-4 to 122F); PA is polyamide rated from -20 to +70C (-4 to +158F).
(c) C = TA with compression terminals, RL = TA with ring lug terminals. Knife has compression terminals.
(d) See to Table 2 and Table 3 for cable part numbers.
(e) See to Table 1 Termination Assembly certification definitions.
(f) The ON volt drop for an FBM242 across the Oring diode is typically: 0.498V @ 12A; 0.520V @16 A. The typical voltage drop to a
channel output is 0.6V at 1.65A per channel.
(g) This is knife disconnect construction. Knives and test sockets provided for circuit validation only. Knife disconnects are not rated for
interrupting loads. Power must be removed before disconnecting circuit.

PSS 21H-2Z42 B4
Page 11

Table 1. Certifications for Termination Assemblies


Type

Certification

Type 1

TAs are UL/UL-C listed as suitable for use in Class I; Groups A-D; Division 2 temperature code
T4 hazardous locations. They are CENELEC (DEMKO) certified EEx nA IIC T4 for use in Zone 2
potentially explosive atmospheres.

Type 2

TAs are UL/UL-C listed as associated apparatus for supplying non-incendive field circuits Class
I; Groups A-D; Division 2 hazardous locations when connected to specified DIN rail mounted
FBMs and field circuits meeting entity parameter constraints specified in DIN Rail Mounted
Subsystem Users Guide (B0400FA). They are also CENELEC (DEMKO) certified as associated
apparatus for supplying field circuits for Group IIC, Zone 2 potentially explosive atmospheres.
Field circuits are also Class 2 limited energy (60 V dc, 30 V ac, 100 VA or less) if customersupplied equipment meets Class 2

Type 4

All field circuits are Class 2 limited energy (60 V dc, 30 V ac, 100 VA or less) if customer-supplied
equipment meets Class 2 limits.

Type 5

The TA and its field circuitry are for use in only ordinary (non-hazardous) locations.

Table 2. P/PVC Cable Types and Part Numbers


Length
m (ft)

Type 4,
26 AWG(b)

0.5 (1.6)

Type 4H,
22 AWG(a)(b)

Length
m (ft)

Type 4,
26 AWG(b)

Type 4H,
22 AWG(a)(b)

P0916FG

10.0 (32.8)

P0916FL

P0916GE

1.0 (3.2)

P0916FH

15.0 (49.2)

P0916FM

P0916GF

2.0 (6.6)

P0931RQ

20.0 (65.6)

P0916FN

P0916GG

3.0 (9.8)

P0916FJ

25.0 (82.0)

P0916FP

P0916GH

5.0 (16.4)

P0916FK

30.0 (98.4)

P0916FQ

P0916GJ

(a) Type 4H cables are used to reduce voltage drop in long (greater than 5 m (15 ft)) cable run applications.
(b) Type 4 and Type 4H cables are not interchangeable.
P/PVC is polyurethane outer jacket and semi-rigid PVC primary conductor insulation. Temperature range; -20 to +80C
(-4 to +176F)

PSS 21H-2Z42 B4
Page 12

Table 3. Hypalon/XLPE Cable Types and Part Numbers


Length
m (ft)

Type 4,
26 AWG(b)

0.5 (1.6)

Type 4H,
22 AWG(a)(b)

Length
m (ft)

Type 4,
26 AWG(b)

Type 4H,
22 AWG(a)(b)

P0916WD

10.0 (32.8)

P0916WH

P0916WN

1.0 (3.2)

P0916WE

15.0 (49.2)

P0916WJ

P0916WP

2.0 (6.6)

P0931RU

20.0 (65.6)

P0916WK

P0916WQ

3.0 (9.8)

P0916WF

25.0 (82.0)

P0916WL

P0916WR

5.0 (16.4)

P0916WG

30.0 (98.4)

P0916WM

P0916WS

(a) Type 4H cables are used to reduce voltage drop in long (greater than 5 m (15 ft)) cable run applications.
(b) Type 4 and Type 4H cables are not interchangeable.
H/XLPE is Hypalon outer jacket and XLPE (cross-linked polyethylene) primary conductor insulation. Temperature range;
-40 to +90C (-40 to +194F).

PSS 21H-2Z42 B4
Page 13

DIMENSIONS NOMINAL

Compression Termination Assemblies


P0917XX, P0916JY

[125]
4.93

[127] (a)
5.02

[80] [72] (b)


3.13 2.83

P0917HX

[125]
4.93

[146] (a)
5.75

[80][72] (b)
3.13 2.83

P0916JZ, P0916YZ

[125]
4.93

[216] (a)
8.51

[80] [74] (b)


3.13 2.93

P0916NG, P0916YY, P0923LL1


[125]
4.93

[216] (a)
8.51

[80] [72] (b)


3.13 2.83

(a) Overall width for determining DIN rail loading.


(b) Height above DIN rail (add to DIN rail height for total).
1Dimensions

shown are for the PVC versions. All dimensions for this polyamide termination assembly are smaller.

PSS 21H-2Z42 B4
Page 14

DI M E N S I O N S N O M I N A L ( C O N T I N U E D )

Compression Termination Assemblies (Continued)


P0923LH




 D

 
  E

Ring Lug and Knife Switch Termination Assemblies


P0916RJ
[125]
4.93

[198] (a)
7.78

[72] (b)
2.83
[80]
3.13

P0916RL

[125]
4.93

[321] (a)
12.64

[74] (b)
[80]
2.93
3.13

P0916RK
[125]
4.93

[80][72] (b)
3.13 2.83

(a) Overall width for determining DIN rail loading.


(b) Height above DIN rail (add to DIN rail height for total).

[321] (a)
12.64

PSS 21H-2Z42 B4
Page 15

DI M E N S I O N S N O M I N A L ( C O N T I N U E D )

Ring Lug and Knife Switch Termination Assemblies (Continued)

P0926BE
[125]
4.93

[80]
3.13

[321] (a)
12.64

[72] (b)
2.83

P0926DV
125
4.93

72
80 2.83
3.14

(a) Overall width for determining DIN rail loading.


(b) Height above DIN rail (add to DIN rail height for total).

373
14.67

PSS 21H-2Z42 B4
Page 16

G E N E R A L P U R P O S E P L U G - I N R E L AY T ER M I N AT I O N A SS EM B LY S P E C I F I C AT I O N S

Description

Minimum Permissible Load

SPDT, plug-in, field replaceable

100 mA, 5 V dc

Rated Load

Contact Material

dc RESISTIVE
5 A at 30 V dc
dc INDUCTIVE (L/R = 7 MS)
5 A at 30 V dc
ac RESISTIVE
5 A at 240 V ac
ac INDUCTIVE (P.F. = 0.4)
5 A at 240 V ac

Carry Current

AgCdO

Contact Resistance
30 m maximum

Life Expectancy
MECHANICAL
20 X 106 operations minimum
ELECTRICAL
100 X103 (at rated load)

Response Time

5A

Maximum Operating Voltage


240 V ac, 30 V dc

Maximum Operating Current


5A

Maximum Switching Capacity


1200 VA, 150 W

OPERATE
15 ms maximum
RELEASE
ac
10 ms maximum
dc
5 ms maximum

R E L AT E D P R O D U C T S P E C I FI C AT I O N S H E E T S ( P S S )
PSS Number

Description

PSS 21H-2W1 B3

DIN Rail Mounted FBM Subsystem Overview

PSS 21H-2W2 B3

DIN Rail Mounted FBM Equipment, Agency Certification

PSS 21S-3B2 B3

Control Processor 270 (CP270) Integrated Control Software

IPS Corporate Headquarters


5601 Granite Parkway Suite 1000
Plano, TX 75024
United States of America
www.ips.invensys.com
Foxboro Global Client Support
Inside U.S.: 1-866-746-6477
Outside U.S.: 1-508-549-2424 or
contact your local Foxboro
representative.
Facsimile: 1-508-549-4999

Invensys, Foxboro, and I/A Series are trademarks of


Invensys plc, its subsidiaries, and affiliates.
All other brand names may be trademarks of their
respective owners.

Copyright 1999-2009 Invensys Systems, Inc.