K3MA-L Temperature Meter: Ordering Information
K3MA-L Temperature Meter: Ordering Information
K3MA-L Temperature Meter: Ordering Information
K3MA-L
selection functions.
Easy confirmation of max/min display.
Short 80-mm depth (measured from edge of face
plate).
C
US
front panel.
Recognized to U.S. and Canadian requirements
Ordering Information
Input type
Platinum-resistance thermometer or
thermocouple
Supply voltage
Output
None
24 VAC/VDC
None
Model
K3MA-L 100-240VAC
K3MA-L-@
1
1. Input Type
L:
2. Output Type
None: No output
C:
3. Supply Voltage
100-240VAC: 100 to 240 VAC
24VAC/VDC: 24 VAC/VDC
K3MA-L
K3MA-L
Specifications
Ratings
K3MA-L 100-240VAC, K3MA-L-C 100-240VAC
Supply voltage
6 VA max.
Insulation resistance
Dielectric withstand voltage 2,000 VAC for 1 min between external terminal and case.
Insulation provided between inputs, outputs, and power supply.
Noise immunity
Vibration resistance
Shock resistance
150 m/s2 (100 m/s2 for relay contact outputs) 3 times each on 3 axes, 6 directions.
Ambient temperature
Operating:
Storage:
Ambient humidity
Ambient atmosphere
EMC
(EMI)
Emission Enclosure:
EN61326+A1
Industry
CISPR 11 Group 1 class A: CISRP16-1/-2
Emission AC Mains:
(EMS)
Immunity ESD:
Immunity RF-interference:
EN61000-4-4:
2 kV (power line)
Approx. 200 g
Input/Output Ratings
Relay Contact Output
Item
Rated load
10 mA at 5 VDC
Mechanical life
Electrical life
(at an ambient temperature of 20 C)
375 VA, 36 W
K3MA-L
K3MA-L
Measuring Ranges
Platinum-resistance Thermometer
Input
C
F
Range
Pt100
-200 to 850
-300 to 1500
Parameter
JPt100
-199.9 to 500.0
-199.9 to 900.0
-199.9 to 500.0
-199.9 to 900.0
0.0 to 100.0
0.0 to 210.0
0.0 to 100.0
0.0 to 210.0
Thermocouple
Input
C -200
Range
to
1300
F -300
Parameter
-20.0 -100
to
500.0
to
2300
0.0
to
900.0
-20.0 -200
to
850
to
400.0
to
1500
0.0
to
750
-100
-199.9
0
to
600
-100
-200
0
to
1700
100
to
1800
to
400.0
to
700
to
1300
199.9 300
to
to
700.0 2300
0
to
3000
0
to
3000
300
to
3200
to
700
199.9 0
to
to
700.0 1100
100
to
1500
-300
to
400
to
400.0
-199.9 -200
0
to
1700
to
400
-300
to
850
Characteristics
Thermocouple:
( 0.5% of indication value or 1 C, whichever greater) 1 digit max.
Platinum-resistance thermometer:
( 0.5% of indication value or 1 C, whichever greater) 1 digit max.
Input
Thermocouple: K, J, T, E, L, U, N, R, S, B
Platinum-resistance thermometer: JPt100, Pt100
Measurement method
Sampling period
500 ms
Sampling period (sampling times multiplied by number of averaging times if average processing
is selected.)
Display
Polarity display
Zero display
Input shift
Input shift equivalent to the setting value supported for all points within the sensor measurement
range.
Hold function
Hysteresis setting
Other functions
Output
1 s max.
Enclosure ratings
Memory protection
Note:
The indication accuracy of the K thermocouple at a temperature of 200 to 1300 C is 2 C 1 digit maximum.
The indication accuracy of the T and N thermocouples at a temperature of 100 C or less is 2 C 1 digit maximum.
The indicator accuracy of the U and L thermocouples at any temperature is 2 C 1 digit maximum.
The indication accuracy of the B thermocouple at a temperature of 400 C or less is unrestricted.
The indication accuracy of the R and S thermocouples at a temperature of 200 C or less is 3 C 1 digit maximum.
K3MA-L
K3MA-L
Nomenclature
2. Operation indicators
Max
Min
1. Main indicator
SV
3. Level indicator
MAX/MIN
LEVEL
MODE
SHIFT
UP
4. MAX/MIN key
8. Up key
5. Level key
7. Shift key
6. Mode key
Name
Functions
1. Main indicator
2. Opera- 1
tion indi- SV
cators
Max
Min
3. Level indicator
Displays the current level that the K3MA-L is in. (See below for details.)
4. MAX/MIN Key
Used to display the MAX and MIN values when a measurement value is being displayed.
5. Level Key
6. Mode Key
7. Shift Key
Used to enable a set value to be changed. When changing a set value, this key is used to move along the digits.
8. Up Key
Used to change a set value. Used to set or clear a forced-zero function when a measurement value is being displayed.
Level indicator
Level
Protect
Not lit
Operation
.
!
Adjustment
Initial setting
Advanced-function setting
K3MA-L
K3MA-L
Operation
Main Functions
Setting
$)/
Note:
Input type
Platinum-resistance
thermometer
Meaning
-200 to 850C
-199.9 to 500.0C
0.0 to 100.0C
-199.9 to 500.0C
0.0 to 100.0C
-200 to 1300C
-20.0 to 500.0C
-100 to 850C
-20.0 to 400.0C
-200 to 400C
-199.9 to 400.0C
0 to 600C
-100 to 850C
-200 to 400C
-199.9 to 400.0C
-200 to 1300C
0 to 1700C
0 to 1700C
100 to 1800C
Pt100
JPt100
Thermocouple
K
J
T
E
L
U
N
R
S
B
-300 to 1500F
-1999 to 900.0F
0.0 to 210.0F
-199.9 to 900.0F
0.0 to 210.0F
-300 to 2300F
0.0 to 900.0F
-100 to 1500F
0.0 to 750.0F
-300 to 700F
-199.9 to 700.0F
0 to 1100F
-100 to 1500F
-300 to 700F
-199.9 to 700.0F
-300 to 2300F
0 to 3000F
0 to 3000F
300 to 3200F
0
Setting
!
Meaning
Display in C.
Display in F.
Setting
Meaning
#$
'*
#$'*
OUT1 value
Measurement
value
ON
Output
OFF
OUT1 upper-limit
value
Measurement
value
Hysteresis
Measurement
value
OUT1 value
Hysteresis
Hysteresis
OUT1 lower-limit
value
ON
ON
Output
Hysteresis
Output
OFF
OFF
K3MA-L
K3MA-L
Input shift equivalent to the setting value supported for all points
within the sensor measurement range.
The color of the value displayed can be set to either red or green.
For comparative output models, the display color can be set to
change from green to red, or from red to green, according to the
status of the comparison criterion.
Parameter
$).
Setting
to
Red
258.9
Temperature
OUT1 value
Green
Before shift
192.0
After shift
Temperature input
shift value
Input
Parameter Initialization
This function returns all of the parameters to their initial values.
Parameter
$)$/
Setting
*!!
*)
Meaning
Move-to-Protect-Level Time
The time required to shift to the protect level can be set as
desired.
---
MAX/MIN Display
Current value
Average Processing
Average processing stabilizes displayed values to minimize flicker
by averaging the fluctuating input signals. Average processing
can be performed for the measurement values in either of four
steps (OFF, 2 times, 4 times, or 8 times).
MAX/MIN
MAX/MIN
LEVEL
MODE
SHIFT
UP
MAX value
Max
MAX/MIN
MAX/MIN
LEVEL
MODE
SHIFT
UP
MIN value
Min
Set value
Hysteresis
Measurement value
ON
Output
OFF
MAX/MIN
MAX/MIN
LEVEL
MODE
SHIFT
UP
K3MA-L
K3MA-L
External Connections
Terminal Arrangement
A1
Power
supply
Output
terminals
A2
Models with
comparative
output
E1
E2
E3
E4
Input
terminals
E5
E6
E4
For thermocouple
input
Terminal No.
A1 -
A2
E4 - E6 -
E5
E1 , E2 -
E3
Name
E5
E6
A
B
B
For platinumresistance
thermometer input
Description
Operation power
Outputs
K3MA-L
K3MA-L
Block Diagram
Input
Key
Input
Microcomputer
EEPROM
Output circuit
5V
12 V
Display
Contact
output (See
note.)
K3MA-L
K3MA-L
Levels
Level refers to a grouping of parameters. The following table lists the operations that are possible in each of the levels, and the diagram
tells how to move between levels. There are some parameters that are not displayed for certain models.
Level name
Function
Measurement
Protect
Setting lockouts.
Continue
Operation
Continue
Adjustment
Continue
Initial setting
Stopped
Advanced-function setting
Setting average processing, display color settings, and other ad- Stopped
vanced function parameters.
Power ON
Adjustment level
Operation level
+
Time set
by user
Less than 1 s
(See note.)
Protect level
1 s min.
1 s min.
+
1 s min.
- 123.4
Password "169"
1 s min.
Advanced-function
setting level
Note:
K3MA-L
K3MA-L
Parameters
Power ON
Press Level Key
for less than 1 s.
Adjustment level
Operation level
Press Level Key
for less than 1 s.
Current value
MODE
OUT1
value
OUT1
upper-limit
value
OUT1
lower-limit
value
MODE
MODE
MODE
10
K3MA-L
K3MA-L
Press Level
Key
for
more than 3 s.
MODE
Enter
password
"169"
Temperature unit
Temperature
unit
Average
processing
MODE
MODE
Models
with the
comparative output
function
Parameter
initialization
OUT1 type
MODE
Upper Limit
Lower Limit
Upper/Lower
Limits
MODE
Move to
advancedfunction
setting level
Models
with the
comparative output
function
OUT1
Hysteresis
MODE
MODE
Display
color
change
Password: -169
/ /
Unit: times
OUT1 hysteresis
OUT1 type
Green (red)
Green
Red (green)
MODE
Red
Display
auto-return
time
Unit: s
MODE
Move-toprotectlevel time
Unit: s
MODE
Settings displayed in reversed colors are initial settings.
11
K3MA-L
K3MA-L
Press
Level Key +
Operation Level
Protect level
Press
Level Key +
Mode Key
Operation/adjustment
lockouts
/ /
/ /
MODE
MODE
MODE
Operation/Adjustment Lockouts
Initial Settings
Setting
*+/
Operation level
Process value
display
Set value
display
Allowed
Allowed
Allowed
Allowed
Allowed
Prohibited
Allowed
Prohibited
Prohibited
Initial setting is 0.
This cannot be displayed on models not equipped with the comparative output function.
$+/
Setting
Shift to initial
setting level
Power ON
Moving to
adjustment
level
Shift to
advancedfunction
setting level
Allowed
Allowed
Allowed
Prohibited
Prohibited
Prohibited
1/+/
Setting
*!!
*)
Allowed
Prohibited
Measurement starts.
12
K3MA-L
K3MA-L
Setting Example
Initial Settings
E52-PR Thermocouple
Industrial furnace
Max
Min
SV
MAX/MIN
LEVEL
MODE
SHIFT
UP
K3MA-L-C AC100-240V
Application Examples
PID control
E5EN
K3MA-L
Generator motor
K3MA-L
Industrial furnace
Alarm output
Molding equipment
K3MA-L
Alarm output
13
K3MA-L
K3MA-L
Dimensions
Finger protective
cover (provided)
101.2
91
Main indicator
character size
Panel cut-out
120 min.
14.2 mm
A
85
7.6 mm
97
75 min.
12
92+0.5
0
45 +0.5
0
1.3
80
96
44.8
48
MAX/MIN
LEVEL
MODE
SHIFT
UP
Shape
Model
K32-49SC
Hard Cover
K32-49HC
Installation
1. Insert the K3MA-L into the panel cut-out hole.
2. For a waterproof installation, insert the rubber gasket onto
the body of the K3MA-L.
Wiring Precautions
Wiring
5.8 mm max.
3. Fit the adaptor into the grooves on the left and right sides of
the rear case, then push it until it contacts the panel to
secure the K3MA-L.
The unit markings are not attached to the K3MA-L. Select the desired markings from the provided sheet.
Note:
14
For scales and gauges, use the unit markings that are
specified by the relevant laws or regulations.
K3MA-L
K3MA-L
Precautions
!Caution
Do not touch the terminals while the power is being supplied.
Doing so may result in electric shock.
!Caution
Do not disassemble the product or touch the internal components of the product while the power is being supplied. Doing
so may result in electric shock.
!Caution
Do not allow pieces of metal or wire clippings to enter the product. Doing so may result in electric shock, fire, or malfunction.
!Caution
Perform correct settings for the product according to the control
application. Failure to do so may cause unexpected operation,
resulting in damage to the product or injury.
!Caution
Take safety measures, such as installing a separate monitoring
system, to ensure safety even if the product fails. Product failure may prevent comparative outputs from being generated,
resulting in serious accidents.
Observe the following precautions to ensure safety.
1. Maintain the power supply voltage within the range specified in the specifications.
2. Maintain the load within the ratings specified in the specifications.
3. Check each terminal for correct number and polarity before
connecting it. Incorrect or reverse connections may damage or burn out internal components in the product.
4. Tighten the terminal screws securely. The recommended
tightening torque is 0.43 to 0.58 Nm. Loose screws may
cause fire or malfunction.
5. Do not connect anything to unused terminals.
6. Provide a switch or circuit breaker so that operators can
easily turn OFF the power supply when necessary. Also
provide appropriate indications of such devices.
7. Do not attempt to disassemble, repair, or modify the product.
8. Do not use the product where flammable or combustible
gases are present.
Application
General Precautions
1. Do not use the product in the following locations:
Locations subject to direct radiant heat from heating
equipment.
Locations subject to exposure to water, oil, or chemicals.
Locations subject to direct sunlight.
Locations subject to dust or corrosive gases (particularly,
sulfuric gas or ammonia gas).
Locations subject to severe changes in temperature.
Locations subject to icing or condensation.
Locations subject to shock or vibration.
2. Do not block heat dissipation around the product, i.e., provide sufficient space for heat dissipation.
3. Ensure that the rated voltage is reached within two seconds
after the power is turned ON.
Temperature Meter
+ TemperaSignal
input
ture Meter
Power
supply
input
Surge absorber
When using a noise filter for the power supply, check for the voltage and current and install it as close as possible to the Temperature Meter.
Do not install the product near radios, television sets, or wireless
devices. Doing so may cause reception interference.
Increasing Service Life
Do not use the product in locations where the temperature or humidity exceeds the ratings or where condensation may occur.
When installing the product in a panel, be sure that the temperature around the product (not the temperature around the panel)
does not exceed the ratings. The product service life depends on
the ambient temperature. The higher the ambient temperature,
the shorter the service life. To extend the product service life,
lower the temperature inside the Temperature Meter.
Use and store the product within the temperature and humidity
ranges given in the specifications. When gang-mounting Temperature Meters or arranging them vertically, heat generated by
the Temperature Meters will cause the internal temperature to
rise, reducing the service life. In such cases, consider forced
cooling methods, such as using a fan to circulate air around the
Temperature Meters. Do not, however, allow only the terminals
to be cooled. Doing so will increase measurement error.
The life of the output relays are greatly affected by the switching
capacity and switching conditions. Use these relays within their
rated load and electrical life. The contacts may fuse or burn if
they are used past their electrical life.
15
K3MA-L
K3MA-L
Troubleshooting
When an error occurs, error details will be displayed on the main indicator. Confirm the error from the main indicator and take the appropriate countermeasures.
Level display
Main indicator
Not lit
Error contents
RAM memory error
Countermeasures
Repair is necessary.
Consult your OMRON sales representative.
Flashes . --
Not lit
Input error
Flashes
Not lit
Flashes
Not lit
Use the adjustment level to review the temperature input correction value.
Use the adjustment level to review the temperature input correction value.