100, 101, 200 and 201 - Datasheet
100, 101, 200 and 201 - Datasheet
100, 101, 200 and 201 - Datasheet
Main applications
l Extrusion lines
l Presses for rubber
l Presses
l Test equipment
l Food processing plant
l Pharmaceutical and chemical
industries
l Industrial ovens
l Wood working machines
GENERAL
The 100, 101, 200 and 201 are microprocessor based panel meter and alarm
units that use SMT for the board assembly that also reduces the size.
Any of the most common types of temperature probe, d.c. and potentiometer
inputs may be used and they are selected
simply using the faceplate keys.
The user interface consists of a red LED
display and 3 keys for setting the alarm
points and the instrument configuration.
A single key is used to display all the
intervention setpoints.
The active alarm outputs are indicated by
LEDs.
The operational software provides various
programming levels for the instruments.
These can be protected using entry
codes, while still being easy to use.
The first levels enable the alarm points
and relative hysteresis values to be entered.
At a higher level, it is possible to configure the type of input, the function of each
alarm, the protection levels, the offset for
the input signal and the beginning and
end of scale for linear inputs.
Main features
l Thermocouple, resistance thermometer,
d.c., potentiometer inputs completely
configurable from keypad
l Settable Offset function for input signal
l Tare reset function
l Up to 4 configurable alarm points
l Alarm memory selectable from keypad
TECHNICAL DATA
INPUTS
Accuracy 0,5% f.s. 1 digit
Sampling time 120msec
Tc - Thermocouple
for 100 and 200 instruments
J (Fe-CuNi) 0...800C / 32...999F
K (NiCr-Ni) 0...999C / 32...999F
S (Pt10 Rh-Pt) 0...999C / 32...999F
T (Cu-CuNi) -100...400C / -148...752F
for 101 and 201 instruments
J (Fe-CuNi) 0...800C / 32...1472F
K (NiCr-Ni) 0...1300C / 32...2372F
S (Pt10 Rh-Pt) 0...1600C / 32...2912F
T (Cu-CuNi) -100...400C / -148...752F
Selected from front panel keys.
Ambient temperature compensation error
is better than 0,1C for every 1C variation.
Messages for over or under range input,
incorrect connection and open circuit
probe.
RTD 2/3-wires
for 100 and 200 instruments
Pt100 -199...400C / -199...752F
Pt100 -19,9...99,9C / -19,9...99,9F
for 101 and 201 instruments
Pt100 -199...400C / -199...752F
Pt100 -199,9...400,0C / -199,9...752,0F
DC - Linear
0...50mV / 0...10V Ri 1M
0...20mA / 4...20mA Ri=500
(Ri=2,5 for transmitter with external supply).
(For 100 and 101 instruments only
0...50mV).
Potentiometer (only for 200 and 201)
1...20K, Ri 10M
Digital (only for 200 and 201)
Free voltage contact for input with selectable function by faceplate key.
5Vdc, 0,5mA max.
OUTPUTS
Relay
2 alarm outputs (Out 1, Out 2) with rated
at 5A/250Vac at cosj = 1
(3,5A at cosj = 0,4).
(Mod. 200 and 201) 2 alarm outputs (Out
3, Out 4) with rated at 3A/250Vac at
cosj = 1 (3,5A at cosj = 0,4).
(Out 3 and Out 4 can be only displayed
on mod.100).
Spark suppression on the NO contact.
Logic (only for 200 and 201)
Relay are simultaneously available for
Out 1.
22Vdc, Rout = 470 (20mA, max. 12V).
POWER SUPPLY
100...240Vac 10%
11...27Vac/dc 10%
50/60Hz; 6VA max.
Protection by internal fuse not serviceable
by the user.
TRANSMITTER SUPPLY
(only for 200 and 201)
Alternative to Out 3 and Out 4 outputs.
20Vdc 15%; 30mA max.
AMBIENTAL CONDITION
Working temperature range: 0...50C
Storage temperature range: -20...70C
Humidity: 20...85%Ur non condensing
ALARMS
- 4 alarm points that may be set as absolute, deviation or symmetrical deviation
around the previous absolute setpoint
and as high or low alarms.
- The alarm points may be set anywhere
in the configured scale.
- Hysteresis adjustment:
-999...3000 (-99.9...300,0) mod. 101 and 201
-199...999 (-19.9...99.9) mod. 100 and 200
WEIGHT
300g (100 and 101), 400g (200 and 201)
FACEPLATE DESCRIPTION
C
B
B
E
E
A
C
B
D
IP54 faceplate protection (IP65 available)
108
59
48
115
96
70
48
48
70
70
44,5
45
92
45
100
100
10
10
CONNECTION DIAGRAM
NC
OUT1
(MAIN)
OUT2
(AL)
C
NO
PWR
SUPPLY
TC
Pt100
3-wires
PTC
Pt100 2-wires
OUT1
(D2)
NC
OUT1
C
NO
NC
OUT2
PWR
SUPPLY
NO
NTC/PTC
Pt100
LIN INP
Idc (20mA) Pt100 2-wires 3-wires
TC
C
NO
GND
OUT4
OUT3
NC
LIN INP
Vdc
RST
Pot
TRANSMITTER
SUPPLY
ORDER CODE
MODEL
mod. 100
100
mod. 101
101
mod. 200
200
mod. 201
201
100
200
101
201
100
200
101
201
only displayed
0R*
0R*
2 alarms
2R
2R
4 alarms
4R
100
200
101
201
INPUT
ALARM OUTPUTS
POWER SUPPLY
11...27Vac/dc
100...240Vac/dc
1*
1*
GEFRAN spa reserves the right to make any kind of design or functional modification at any moment without prior notice
- EN 50082-2 (immunity in industrial environment) - EN 50081-1 (emission in residential environment) - EN 61010-1 (safety)