Honeywell Enraf WFI Service Manual
Honeywell Enraf WFI Service Manual
Honeywell Enraf WFI Service Manual
Table of Contents
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Opening of the Instrument . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Closing of the Instrument. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Tools . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-5
Working Environment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Hazardous Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Safe Zone . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Required Skills. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2-6
Table of Contents
ii
Table of Contents
iii
Table of Contents
9.3.7 Commissioning the HCI-1WL for GPU and FlexConn Communication . . . . 9-15
9.3.8 Using the SmartView with the OneWireless Communication Option. . . . . . 9-18
9.3.8.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-18
9.3.8.2 SmartView OneWireless Status Display . . . . . . . . . . . . . . . . . . . . . . . . . . . 9-18
9.3.9
9.3.9.1
9.3.9.2
9.3.9.3
iv
General
CHAPTER 1GENERAL
1.1 Target Group for this Service Manual
This Wireless Field Interface Service Manual is meant for service
engineers who are assigned to commission a Wireless Field Interface.
1.2 Structure of this Manual
Chapter Title
Contents Description
1 - GENERAL
2 - SAFETY
3 - SYSTEM ARCHITECTURE
4 - SERVICE TOOLS
5 - INSTALLATION
6 - CONFIGURATION
This chapter gives all information needed to configure the OneWireless infrastructure, the Wireless Field Interface devices, and the protocol
tunneling.
7 - FIRMWARE UPGRADE
8 - OPERATIONS
9 - COMMISSIONING
1-1
General
Honeywell Enraf
Delftechpark 39, 2628 XJ Delft
PO Box 812, 2600 AV Delft
The Netherlands
1-2
Safety
CHAPTER 2 SAFETY
2.1 General
The Wireless Field Interface (WFI) adds a wireless capability to the
existing servo or the radar gauge by supporting the GPU protocol which
is compliant with the ISA100 standards. It consists of multiple electronic
boards, an antenna cable, and a communication antenna. The WFI
communicates with the servo or the radar gauge through the Honeywell
Enraf field bus Bi-Phase Mark, processes the data, and forwards the
information wirelessly to the Wireless Device Manager (WDM) which is
compliant with the ISA100 standards. The complete network including
the WFI is based on the ISA100 wireless field device network.
For the accurate and safe servicing of the WFI, it is essential that all
personnel follow generally accepted safety procedures in addition to the
safety precautions specified in this manual.
2.2 Safety Conventions
2.2.1 Warnings
Description
Remark
General warning
2.2.2 Cautions
Description
General caution sign
2-1
Safety
See the safety instructions shipped with the device for installation,
commissioning, operation, and maintenance.
2.3.2 EC Declaration of Conformity (for EU)
tricity.
2-2
Safety
2-3
Safety
2.5 Labels
NOTE to FM label:
Ta = -40 C to +149 C
FIGURE 2-1
2-4
Safety
2-5
Safety
2.8 Electrical
2.8.1 IEC Safety Standards
The entire electrical installation must be in accordance with the Inter-
2.8.2 Grounding
WARNING! Make sure the housing of the device is properly
connected to the ground reference! Make sure that
the electrical resistance of the ground connection is
2-6
Safety
of
prescribed
by
local
Type of protection:
ATEX / IEC Ex / CSA / FM
Certificate numbers:
ATEX / IEC Ex [pending for OneWireless option]
Wireless Field Interface:
2-7
Safety
2-8
System Architecture
Experion PKS
ISA100
Wireless
BPM I/F
I/F
Entis Pro
CIU
WDM
FDAP
Wireless Field
Interface
Servo Gauge
FIGURE 3-1
ESF07-0026
3-1
System Architecture
XXX-YYY
specific name or function
3-2
System Architecture
NOVRAM
Temperature sensor
Jumpers
Microcontroller
with program memory
Power supply
FIGURE 3-2
ESF07-0021
3-3
System Architecture
Jumpers:
Function
Board-specific jumper
Board-specific jumper
Health LED
The Health LED (= LE1, the blue one) indicates the general health
status of the FlexConn module.
Health Status
Flashing Pattern
Good
Uncertain
Bad
2 function LEDs
3-4
System Architecture
3 voltage monitors
The output of these monitors is the voltage levels from three different
FlexConn PCB locations, are used for diagnostics purposes.
See FIGURE 3-3.
FIGURE 3-3
ESF07-0023
1 temperature sensor
For the operational PCB, this sensor acts as an input for environmentaltemperature diagnostics. The PCBs environmental temperature is used
as a measure for the temperature inside the WFI device.
3-5
System Architecture
3.3 Entities
Information exchange between the various FlexConn modules takes
place by means of the entities.
An entity represents a unique information association within the
FlexConn architecture. This information may consist of measuring data,
status data, commissioning parameters, diagnostics data, or
commands.
In addition to the information exchange between FlexConn modules,
entities are used for data presentation on the SmartView display, and for
the communication between the Engauge service tool and the WFI.
The entities are represented by a textual description, for example,
Reset, Tank bottom, Health, or Baudrate.
The entities structure is related to the following:
General status information
The generic FlexConn part
The function-specific FlexConn part
3.3.1 Status Entities
The Health entity reflects the condition of the entire module, each
single module function, and the calculated or measured value of a
sensor function.
The Health entity structure is defined by the following items:
1. status
2. status category
3. status code
The status field gives high-level information about the following:
good
uncertain
bad
3-6
System Architecture
Status
Status Category
actual
manual
Good
last valid
stored
instrument
Uncertain
environment
general hardware fail
general firmware fail
general commissioning fail
general calibration fail
general operational fail
Bad
over range (data available!)
under range (data available!)
no data available
un-initialized
killed
The status code provides information about the specific reason why the
status is good, uncertain, or bad. This information is presented as an
information number and a textual description of this specific situation.
See the table below.
001 056 077 104 632 328 207 782 065 478 199 389 011 072
cal fail
sw fail
hw fail
instrument environment
over range
stored
under range
last
valid
no data
manual
Bad
killed
actual
Uncertain
un-init
Good
........................................................
3-7
System Architecture
FlexConn module
The firmware (software) version data is built according to the format
below:
A 1 0 0 0 0
internal preliminary
bug fixes
minor functionality
warning + measuring data related part
main functionality
hardware modifications
3-8
System Architecture
<
<
Smartviews easy-view display, five backlit keys and simple and intuitive
navigation facilitate process data and configuration of the WFI device.
Most FlexConn module settings can be configured using SmartView.
MENU
FIGURE 3-4
MAIN
<
>
SELECT
ESF07-0024
Select a specific function to access the specific entities for this function.
The specific entities are described in Chapter 9 - Commissioning.
3-9
System Architecture
FIGURE 3-5
3 - 10
ESF09-0001
System Architecture
Each board descriptor user interface starts with the tab page Status.
On this tab page the Health and Commissioning entities for the
complete module and the individual functions are available.
3.5.2 Generic Entities in Engauge
The Status tab page is always followed by the Generic tab page, on
which the general commands and diagnostics entities are available.
3.5.3 Board-specific Entities in Engauge
The Generic tab page is always followed by the Board specific tab
page, on which the board-specific entities are available. These entities
are specific for each individual FlexConn module type. The boardspecific entities are further described in Chapter 6 - Commissioning.
3.5.4 Specific Entities on Engauge
After the board-specific tab page, for each implemented function on the
concerned FlexConn module a specific tab page follows.
In case of complex functions, extra tab pages may exist, containing
those specific functions involved.
The specific entities are described in Chapter 9- Commissioning.
3.5.5 Function-generic Entities on Engauge
The function category generic entities are placed at the bottom of each
function tab page in Engauge.
For each category (sensor, digital I/O, communication, display), the
basic Engauge version contains only one entity:
Function identification.
With this entity, the user can change the function name, which then
becomes available on the SmartView Primary Value screen and in
Engauge.
3 - 11
System Architecture
3 - 12
Service Tools
The SmartView is the basic tool in which the user can communicate with
the WFI modules.
The open keyboard contacts may be dangerous in an explosionhazardous environment hence the SmartView is built up as a totally
shielded explosion-safe tool.
NOTE: SmartView is an optional tool. If you want to use
SmartView then you can use a SmartView board
(FIISMV) as an optional board. WFI has a provision
for an optional board.
4.1.2 SmartView Versions
FIGURE 2-1
ESF07-0027
4.1.3 Connections
4-1
Service Tools
<
<
MAIN
<
MENU
FIGURE 2-2
>
SELECT
ESF07-0024
Function
within menu ...
Commissioning
Commands
Extra information
Display contrast
Backlight
Identification
Display settings
Display Test
4-2
Commissioning
Display contrast
Increase contrast
Backlight
Display settings
Service Tools
Button
Function
within menu ...
Commissioning
Commands
Display contrast
Backlight
Display settings
Commissioning
Commands
Commissioning
Commands
Display settings
Identification
Commissioning
Commands
Display settings
Identification
Show menu
Decrease contrast
Increase contrast
4-3
Service Tools
Depending on the state of the menu process and the pressed button(s),
following screens can be displayed:
start-up
SmartView
Menu Structure
<
MAIN
<
PV
screen
password-protected
menu
value
edit
commissioning
board
list
function
list
entity
list
commands
board
list
function
list
command
list
extra
information
display
contrast
backlight
identification
display
settings
display test
primary
values (PV)
ESF07-0043
4-4
Service Tools
Black test
Blank test
Enraf logo + software version + tank ID
PV screen
<
<
By using the [menu] screen of the SmartView (see FIGURE 2-3) you can
view and/or modify settings, or you can send a specific command to a
sensor or a digital I/O board.
MAIN
MENU
FIGURE 2-3
>
SELECT
ESF07-0030
Menu Item
<
Description
[menu]
Screen title.
[commissioning]
[commands]
[extra information]
[display contrast]
[backlight]
4-5
Service Tools
Menu Item
TABLE 6-1
Description
[identification]
[display settings]
[display test]
The [backlight] screen (see FIGURE 2-4) allows you to enable/disable the
backlight. The SmartView only turns the backlight ON if following
conditions are met:
[backlight] is enabled by the host
[backlight] is enabled by the user
<
<
MENU
FIGURE 2-4
4-6
MAIN
<
>
SELECT
ESF07-0031
Service Tools
The [extra information] mode can be configured to display either the [level &
temperature] screen or the [extra information] screen (see FIGURE 2-5). The
[extra information] screen displays information about a specific function.
The specific functions are described in chapter 9. The [level & temperature]
screen (see FIGURE 2-5) displays information about the measured
product level and temperature. In this menu mode, it is not possible to
change any settings.
MENU
<
>
SELECT
<
MAIN
<
<
<
MENU
M AI N
<
>
SELECT
ESF07- 0039/0012
FIGURE 2-5
The level & temperature screen (left) and the extra information screen (right)
4-7
Service Tools
<
<
The [display contrast] screen (see FIGURE 2-6) displays a horizontal scroll
bar. By moving the scroll bar, you can adjust the contrast. Moving to the
right immediately increases contrast, moving to the left decreases
contrast.
MAIN
<
MENU
FIGURE 2-6
>
SELECT
ESF07-0032
The [display settings] screen allows you to set the buttons time-outs. The
screen displays the following items:
Feature
Possible States
Default
ON/OFF
ON
ON/OFF
ON
4-8
Service Tools
MENU
FIGURE 2-7
<
>
SELECT
<
MAIN
<
<
<
software version
MENU
MAIN
<
>
SELECT
E S F0 7- 0 03 3 + 00 2 9
4-9
Service Tools
<
<
Once the password is entered correctly (only once for both menu
entries), you can change the values. 15 minutes after the last button is
pressed, the password needs to be re-entered.
MAIN
MENU
FIGURE 2-8
<
>
SELECT
ESF07-0040
<
<
MENU
FIGURE 2-9
MAIN
<
>
SELECT
ESF07-0034
The [function list] screen (see FIGURE 2-10) displays all available
4 - 10
Service Tools
<
<
MAIN
MENU
FIGURE 2-10
<
>
SELECT
ESF07-0045
<
<
MENU
FIGURE 2-11
MAIN
<
>
SELECT
ESF07-0036
The [function list] screen (see FIGURE 2-12) displays all configurable
entities of a function.
The actual entity value is also visible.
You can navigate through the board list by using the up or down
button. A function can be selected by simultaneously pressing the
4 - 11
Service Tools
<
<
left + right button. You can return to the [board list] screen by pressing
the left button.
MAIN
MENU
FIGURE 2-12
<
>
SELECT
ESF07-0046
<
<
(see FIGURE 2-13). You can navigate through the entity list by using
the up or down button. An entity can be selected by simultaneously
pressing the left + right button. You can return to the [function list]
screen by pressing the left button.
MENU
FIGURE 2-13
MAIN
<
>
SELECT
ESF07-0047
4 - 12
Service Tools
You can scroll along the characters by push and hold the up
button.
An entity modification is only executed on simultaneously
pressing the left + right button. After this, first a range check is
done. If the modification is accepted, you return back to the [value
edit] screen.
The cursor can be shifted to the right by pressing the right button.
You can return to the [entity list] screen by pressing the left button.
<
<
MAIN
MENU
FIGURE 2-14
<
>
SELECT
ESF07-0037
4 - 13
Service Tools
<
<
MAIN
MENU
FIGURE 2-15
<
>
SELECT
The [function list] screen appears and displays all configurable entities
<
<
MAIN
MENU
FIGURE 2-16
4 - 14
<
>
SELECT
ESF07-0046
Service Tools
<
<
button.
MENU
FIGURE 2-17
MAIN
<
>
SELECT
HCW-1WL board restarts and the security keys are erased. The WFI
device can then be provisioned through over-the-air provisioning.
4 - 15
Service Tools
4.2 Engauge
4.2.1 Connecting the Engauge Service Tool
FDAP
WDM
Engauge
FIGURE 2-18
ESF09-0010
4 - 16
Service Tools
FIGURE 2-19
ESF09-0001
4 - 17
Service Tools
Browse through the tab pages which reveals the same information/
parameter settings that can be found using the SmartView, although in
a more user friendly way.
However, some settings or commands can only be executed by
Engauge. For example, executing an Alarm simulation test is only
possible through Engauge.
4.2.3 Device Scanning
FIGURE 2-20
4 - 18
Service Tools
FIGURE 2-21
ESF09-0002
4 - 19
Service Tools
FIGURE 2-22
4 - 20
ESF09-0003
Service Tools
FIGURE 2-23
ESF09-0004
4 - 21
Service Tools
4 - 22
Installation
CHAPTER 5 INSTALLATION
Before starting with commissioning activities, first make sure all
5-1
Installation
Communication
antenna
Lightning
arrestor
FIGURE 5-1
5-2
Configuration -
CHAPTER 6 CONFIGURATION
The following topics describe how to configure the OneWireless
infrastructure, the Wireless Field Interface devices, and the protocol
tunneling.
2-1
After installing the WDM, you need to configure the WDM to enable it to
function in the OneWireless Network. The First Time Configuration
Wizard guides you through the initial configuration of the WDM. The
First Time Configuration Wizard appears ONLY when you log on to
the OneWireless user interface for the first time or after the WDM is
deleted (returning to factory defaults).
Considerations
The following are some of the network configuration rules that you must
follow while configuring the network properties.
2. On the Welcome page of the First Time Configuration Wizard, click Next.
2-2
4. On the Wireless Device Manager Settings page, type the WDM Tag
Name and the Description.
The Tag Name is the unique name that is used to identify the WDM. It can be
up to 16 characters long and must begin with an alphabetic character. Do not
use special characters in the Tag Name; underscore is the only acceptable
character. After completing the initial configuration, you cannot change the
WDM name. The Description can be up to 255 characters long.
5. If you need to configure redundant WDM, then under Redundancy Configuration, configure the following:
a) Select Enable redundancy for this Wireless Device Manager check box.
b) Click the Redundancy Role, as required. You can select either Primary
or Secondary option depending on the redundancy role.
c) In the Partner PCN IP Address box, type the IP address of the partner
WDM.
2-3
9. Click Next.
The Network Settings page appears.
10. Under Field Device Network (FDN), configure the network settings for the
wireless field device network as follows.
2-4
11. Under Process Control Network (PCN), configure the process control network
settings as follows.
Process
2-5
14. If you are selecting NTP server, enter the NTP Server IP Address and click
Next. The Administrator Information page appears.
15. Type the user name and password in the Administrator Name, New
Password, and Confirm Password fields.
The default user name configured for the WDM is administrator. You
can change the default user name in the First Time Configuration
Wizard, if required. However, you cannot change the user name after
completing the initial configuration.
The password must contain at least one character and can contain up
to 32 characters. It should not start or end with a space and must not
contain single quote ().
2-6
17. Verify the WDM settings, correct errors if any, and then click Finish.
If there are any errors in the configuration information that you have
provided, then the system does not allow you to click Finish.
2-7
Devices in the OneWireless Network can be provisioned using over-theair provisioning method. WDM provisions the access points. The access
points that are enabled to function as provisioning devices can provision
the field devices. To enable over-the-air provisioning capability, you
must enable this feature in the user interface.
Any access point that is in the factory default state, when connected to
the OneWireless Network can join the network as an unprovisioned
device. In this state, the WDM contains only the basic details about the
device such as the Tag Name, EUI64, and Radio Revision. Also, there
is no active data communication between the WDM and the device in
the unprovisioned state. You can accept or reject an unprovisioned
device using the user interface. If accepted, the WDM sends the
provisioning data to the device and the device transitions to provisioning
state. A device with new security data sends a join request to the WDM.
To provision the access points using over-the-air provisioning method
1. On the Selection Panel, select the WDM.
2. On the Property Panel, expand System Manager.
2-8
4. Click Apply.
The unprovisioned access points start appearing in the Selection Panel.
You can filter the device list to view only the unprovisioned access points in
the network.
5. On the ribbon bar, in the Filter group, click Device Status > Un-Provisioned.
7. Select the required access point in the Selection Panel or the map view and
then click Accept on the ribbon bar.
2-9
NOTE: You can select multiple access points using the Selection
Panel or the map view. Use SHIFT+click to select multiple
items in a successive list. Use CTRL+click to select multiple
items not in succession. It is recommended that you select
The Accept Over the Air Devices dialog box appears. The dialog box
displays all the unprovisioned access points that you have selected for
enabling over-the-air provisioning.
8. Click Accept.
The Progress column displays the status as In Progress, Provisioning, and then Completed when complete. Do not close the
dialog box when over-the-air provisioning is initiated for devices.
9. Click Close.
The Accept Over the Air Devices dialog box closes.
WARNING! R220 Wireless Field Interface devices can only be provisioned
using the over-the-air provisioning method.
2 - 10
2 - 11
interface, so that the device can rejoin through a different access point for provisioning.
5. Select the required Wireless Field Interface device in the Selection Panel or
the map view and then click Accept on the ribbon bar.
NOTE: You can select multiple access points using the Selection
Panel or the map view. Use SHIFT+click to select multiple
items in a successive list. Use CTRL+click to select multiple
items not in succession. It is recommended that you
the required device and click Reject in the ribbon bar. The
Reject Over the Air Devices dialog box displays.
Click Reject.
The Progress column displays the status as In Progress, and then
Completed, when complete.
Click Close.
The Reject Over the Air Devices dialog box closes.
6. Click Accept.
The Progress column displays the status as In Progress, Provisioning, and then Completed, when complete. Do not close the
dialog box when over-the-air provisioning is initiated for devices.
7. Click Close.
The Accept Over the Air Devices dialog box closes.
All the field devices that you have selected for over-the-air provisioning are
provisioned.
NOTE: By default, the selected Wireless Field Interface devices
are provisioned and joined as line powered routers. Select
Device Management > Routing Assignment > Routing
Disabled to disable the routing field devices to function as
line powered routers.
6.1.2.1 Removing the provisioning key from Wireless Field Interface gauge
2 - 12
2. On the display, scroll to the commands item using the MENU buttons.
3. Press the LEFT ARROW and RIGHT ARROW (SELECT push buttons) simultaneously. You are prompted to enter the password. The default password for
SmartView is AAAAAA.
4. Use the MENU push buttons to enter the password and then press the
SELECT push buttons. The list of commands appears.
5. Scroll to select the CAN-1WL FlexConn board name and then press the
SELECT push buttons.
6. Scroll to select board and then press the SELECT push buttons.
7. Scroll to select Restore Default then press the SELECT push buttons. The provisioning key on the Wireless Field Interface gauge is now removed.
2 - 13
A Device Description (DD) file is usually a zip file that is available on the
disk supplied in the Honeywell Process Solutions website. It contains
information about the device type, commands that are supported by the
device, and other device-specific data. A DD file for a particular field
device is used to describe the device and to intderpret messages and
the device status.
NOTE: WFI requires two separate DD files one that must be
uploaded into One Wireless Device Manager and the
other for Experion.
WARNING! To ensure consistency in the channel names, load the DD
files before the device joins the network.
2.
3.
4.
5.
After joining the network for the first time, a field device capable of
operating as a router and an I/O device initializes its routing assignment
based on the current default routing policy. It is possible to override the
default routing policy by configuring routing assignment for field
devices. Configuring device routing assignment results in restarting the
device with a new role.
Considerations
2 - 14
Routing
Points, FDAP access points, and FDAP routers have the Join
Assignment permanently set to Join Enabled.
Non-routing field devices have the Join Assignment permanently
set to Join Disabled.
Routing field devices have the default Join Assignment set to
Follow System Manager Policy.
By default, the selected Wireless Field Interface devices are provisioned
and joined as line powered routers. Select Device Management > Routing
Assignment > Routing Disabled to disable the routing field devices to
function as line powered routers.
5. Click Apply.
6.2.3 Configuring Wireless Field Interface device channels
6.2.3.1 Configure Mode and Scale
To configure Scale
1. On the Selection Panel, select the Wireless Field Interface device channel.
2. On the Property Panel, expand Process Variable to view the following
read-only parameters in the OneWireless user interface.
WARNING! The configuration of the engineering units should be
performed using the Engauge tool only. The parameter values
of the sensor cards get reflected in the OneWireless user
interface as read-only parameters.
2 - 15
EU
3. Click Apply.
NOTE: After applying the changes, the newly configured values
appear under the Scale panel.
To configure Mode
1.
2.
3.
4.
4. Click Apply.
6.2.3.3 Remove channels from publication groups
2 - 16
4. Click Apply.
6.2.4 Enabling a Wireless Field Interface device in OneWireless Network
6.2.4.1 Enable ENRAF Ethernet / UDP interface on the OneWireless user interface
2 - 17
4. Under the Ethernet/UDP Interface Options, the UDP port number of the
port on which the WDM is connected is displayed.
5. Click Apply.
6.2.4.2 Monitor performance of ENRAF interface
2 - 18
The publication data for input and output field devices can be configured
using the Input Publication panel in the Property Panel. Depending on
the device type, a field device can have an Input Publication panel. This
is determined by the DD file for the field device.
The Input Publication panel contains the following configuration options.
Contract
2 - 19
2 - 20
The gauge has a unique GPU address. If the gauge does not have
one, then add a new GPU address.
Configure the Baud rate of BPM and set it to 2400
854 intermediate
877 (as an indicator)
Connect the WFI after you have added the GPU address of the gauge
and after configuring the gauge baud rate. WFI automatically scans for
GPU address of the connected gauge and so there is no necessity to
manually configure the WFI GPU address.
NOTE: WFI can suppport only one gauge at a time.
2 - 21
2 - 22
To access the field device data, you need to configure the Enraf
interface from the OneWireless user interface.
Prerequisites
Ensure the following:
2 - 23
5. Click Apply.
6.4.3 Configure ENRAF Ethernet/UDP interface
2 - 24
2 - 25
2 - 26
Prerequisites
Ensure that the speed/duplex setting for the switch port to which the
WDM is connected is set to Auto.
To upgrade the WDM firmware
1. On the Selection Panel, select the WDM.
2. On the ribbon bar, in the Upgrade group, click Application. The
WDM Update dialog box appears.
3-1
The WDM Update dialog box displays the upload status. Once
complete, the Firmware File box displays the uploaded firmware file
4. Click Update.
The firmware upgrade starts and once complete, the user interface displays
a message indicating the result of firmware upgrade operation.
WARNING! At times, the update may take longer than expected
and the result of the upgrade may not be displayed.
Instead, a Page not available error may appear. In
such cases, wait for a minute and then redirect the
browser to https:// <ipaddress>/restartzfs.html for
viewing the result. Do not remove or reboot the WDM
during the upgrade process. After the WDM upgrade
from R210 to R220 is complete, the WDM reboots
automatically.
3-2
3-3
The Firmware Upgrade Status dialog box now displays the status
of the upgrade appears. Closing the dialog box allows the upgrade
operation to run in the background. The upgrade status is displayed
in the status bar. Click the firmware upgrade status box to open the
dialog box again. If multiple users are simultaneously upgrading
different device firmware, all the users can view the progress of all
the device upgrades.
5. Close the Firmware Upgrade Status dialog box.
6. Verify the upgraded version of the firmware is as follows:
a) On the Selection Panel of the OneWireless user interface, select
the field device.
b) On the Property Panel, expand Device Manager Summary.
c) Under Identification group, review the firmware version
displayed in the Sensor Revision field.
3-4
Radio firmware
1. On the Selection Panel of the OneWireless user interface, select the
field device.
You can select multiple devices of the same type using the Selection
Panel or the map view. Use SHIFT +click to select multiple items in a
successive list. Use CTRL+click to select multiple items not in
succession.
2. On the ribbon bar, in the Upgrade group, click Radio.
3-5
in the status bar. Click the firmware upgrade status box to open the
dialog box again. If multiple users are simultaneously upgrading
different device firmware, all the users can view the progress of all
the device upgrades.
5. Close the Firmware Upgrade Status dialog box.
6. Verify the upgraded version of the firmware is as follows:
a) On the Selection Panel of the OneWireless user interface, select
the field device.
b) On the Property Panel, expand Device Manager Summary.
c) Under Identification group, review the firmware version
displayed in the Sensor Revision field.
7.4 Upgrading the FDAP/access point firmware
Download the latest OneWireless installation package from the
Honeywell Process Solutions website.
To upgrade the FDAP/access point firmware
1. On the Selection Panel, select the FDAP/access point.
You can select multiple devices using the Selection Panel or the map
view. Use SHIFT+click to select multiple items in a successive list.
Use CTRL+click to select multiple items not in succession.
2. On the ribbon bar, in the Upgrade group, click Radio. The Radio
Firmware Upgrade dialog box appears.
3. In the Available Firmware Files list, select the required firmware
upgrade file.
By default, the firmware upgrade file appears in the list. If the file is
not available in the list, perform the following steps to open the
firmware file.
a) Click Add to browse to the directory location of the firmware upgrade file.
b) Click Open.
4. Click Upgrade.
The Firmware Upgrade Status dialog box appears. The Progress
column displays the progress of the upgrade.
NOTE: To abort any firmware upgrade operation, click the
Abort Upgrade icon adjacent to the upgrade
status.
3-6
Considerations
Following are some of the considerations for upgrading the device
firmware.
3-7
b) Click Open.
5. Click Start.
The upgrade status is displayed in the status bar.
6. Close the FlexConn Firmware Update Engauge dialog box.
7. Enter the Time Out value in the Engauge tool as 9999 ms.
3-8
Operations -
CHAPTER 8 OPERATIONS
The following topic describes how to read the WFI field device
information from SmartView.
4-1
8.1 Reading the Wireless Field Interface field device information from SmartView
To read the Wireless Field Interface field device information from
SmartVie.
1. On SmartView, press the UP ARROW and DOWN ARROW simultaneously (MENU push buttons) to view the menu items on the display.
2. On the display, scroll to the commands item using the MENU
buttons.
3. Press the LEFT ARROW and RIGHT ARROW (SELECT push
buttons) simultaneously. You are prompted to enter the password.
The default password for SmartView is AAAAAA.
4. Use the MENU push buttons to enter the password and then press
the SELECT push buttons. The list of commands appears.
5. Scroll to select the CAN-1WL FlexConn board name and then press
the SELECT push buttons.
6. Scroll to select board and then press the SELECT push buttons.
7. Scroll to select Read Dev Param then press the SELECT push
buttons.
8. On the display, scroll to the commissioning item using the MENU
buttons.
9. Scroll to select the CAN-1WL FlexConn board name and then press
the SELECT push buttons.
The details available on the SmartView are as below:
Value
4-2
Board Serial No
300001
Network Address
Device revision
HCW-1WL Build
Tx Power Level
Radio Mode
FHSS
SD Card Status
No Key
Key Tx Status
FAIL
Radio Diag1
SP1
Radio Diag2
WDT
Device Diag1
ELE
Device Diag2
WDT
Comm .OK
854
Commissioning
CHAPTER 9 COMMISSIONING
9.1 General
9.1.1 Introduction
6-1
Commissioning
9.2 FCM-BPM
9.2.1 Introduction
isolation transformer
FIGURE 9-1
F4A07-0005
6-2
Commissioning
Name
Value Range
Default Value
Explanation
[Baudrate]
<1200>
<2400>
<4800>
<2400>
Communication speed
[BPM sensitivity]
<1..8>
<8>
[Identification]
<-------->
Name of a tank or
instrument
<0..99>
<0>
[FlexConn instrument
address]
<0..1899>
<0>
[Level units]
<meters>
<inches>
<feet>
<fractions>
<meters>
<TANK1234>
6-3
Commissioning
Name
Value Range
Default Value
Explanation
[Temperature units]
<celsius>
<fahrenheit>
<celsius>
[Pressure units]
<pascal>
<kilo pascal>
<psi small> (2 digits before
<pascal>
separator)
[Density units]
<kilogram m3>
<degrees API>
<pounds ft3>
<kilogram m3>
[Decimal separator]
<point>
<comma>
<point>
[Level type]
<innage>
<ullage>
<innage>
[Password]
<......> 6 characters
<ENRAF2>
[Function identification]
<......> 13 characters
<BPM-slave>
NOTE: Ensure that you configure the Baud rate of BPM and
set it to 2400.
* Check/set all the before listed entities, make sure of the following:
the [Board Commissioned] and the [BPM slave Commissioned] entities are
<True>;
the [Board Health] and the [BPM slave Health] entities are <GOOD>.
6-4
Commissioning
Radio Module
FIGURE 9-2
ESF09-0011
board).
By using a protocol tunnel through the OneWireless network:
Through the Enraf FlexConn protocol.
Through the Enraf GPU protocol.
6-5
Commissioning
6-6
Commissioning
6-7
Commissioning
3. Click Apply.
6-8
Commissioning
See section
Ambient temp
9.3.5.2.5
Product pressure
Vapour pressure
Vapour temperature
Water level
6-9
Commissioning
The Field Device Summary panel displays the general details of the
field device.
Parameter
Description
Tag Name
Description
Default Map
Using this dropdown you can select the map under which this device is placed.
Based on the plant topology, users can create multiple site maps and place the
devices under these maps.
6 - 10
Commissioning
Parameter
Description
Channels
6 - 11
Commissioning
The publication data for input field devices can be configured using the
Input Publication panel.
Parameter
Description
Contact Status
Rate
State Limit
Defines the maximum number of stale input values that can be received before the
input status is set to Bad. It is recommended that for 1 second publication period, the
stale limit should be set to 15 seconds. For all other publication periods (5 seconds, 10
seconds, 30 seconds, and 1 minute), the stale limit should be set to 5.
Destination
Channel
6 - 12
Commissioning
Example
Configurable Transducer block 1 could be programmed to represent
the radar level from the CAN-XBAND. Then the PV of this tranducer
block represents the PV of the radar level function, the Innage value.
The SV of this transducer block represents the SV of the radar level
function, the Ullage level.
The current firmware version does have some limitations on what can
be programmed in these transducer blocks.
Configurable Transducer block 1 can only represent Levels. This is
Supported Units
Meters (m)
Millimeters (mm)
Inches (in)
Feet (ft)
6 - 13
Commissioning
Name
Explanation
Value Range
Default
[Board ID]
<0...255>
<0>
[Board Instance]
<0...7>
<0>
[Function Instance]
<0...15>
<0>
[Unit Type]
<0...5>
<0>
units of data:
0 = no unit
1 = level
2 = current
6 - 14
Commissioning
data.
Configurable Transducer block 4 can be used for any of the data
types mentioned above.
The Secondary Variable (SV) of the configurable function block is
automatically assigned to the Secondary Value of the FlexConn board
function that is linked to the Primary Variable (PV) as described before.
Example
To link a configurable transducer block to the Radar Level of
the TII-XR, the following settings need to be configured:
[Board ID] = 5
[Board instance] = 0
[Function instance] = 1
[Unit type] = 1
9.3.7 Commissioning the HCI-1WL for GPU and FlexConn Communication
6 - 15
Commissioning
Name
Value Range
Default Value
Explanation
[Identification]
<-------->
Name of a tank or
instrument.
<0..99>
<0>
[GPU Caching]
<caching off>
<GPU B record>
<GPU C record>
<GPU D record>
<GPU L record>
<GPU M record>
<caching off>
By switching on caching,
the system performance
can be greatly improved.
Switching caching on for a
record means that the
OneWireless network
automatically keeps an upto-date copy of this record
in the internal cache of the
gateway. This copy is
refreshed each second.
Any request for this record
is NOT sent to the
instrument but is directly
answered from the cache.
Note: Do not use this
setting for W&M approved
systems.
<0..1899>
<0>
[Level units]
<meters>
<inches>
<feet>
<fractions>
<meters>
[Temperature units]
<celsius>
<fahrenheit>
<celsius>
6 - 16
Commissioning
Name
Value Range
Default Value
Explanation
[Pressure units]
<pascal>
<kilo pascal>
<psi small> (2 digits before
separator)
<psi large> (3 digits before
separator)
<pascal>
[Density units]
<kilogram m3>
<degrees API>
<pounds ft3>
<kilogram m3>
[Decimal separator]
<point>
<comma>
<point>
[Level type]
<innage>
<ullage>
<innage>
[Password]
<......> 6 characters
<ENRAF2>
[Function identification]
<......> 13 characters
<GPU-slave>
<GOOD>.
6 - 17
Commissioning
<
<
MENU
M AIN
<
>
SELECT
Parameter
Description
PRSSI
SRSSI
Secondary RSSI = Signal strength indicator for the redundant wireless connection
Connection status
SD Status
simultaneously.
6 - 18
Commissioning
The signal strength is shown in dBm. Below -80 to -85 dBm no reliable
connection is possible.
When there is no redundant wireless connection the secondary RSSI
does not show a relevant value.
Connection status
Description
NO KEY:
MACCONN
SECCONN
CONNECT
DISCOVR
NOTCONN
SECURNG
NOREDUN
BAD KEY
SD Status
Description
SDOK
NOSD
6 - 19
Commissioning
Additionally, there are 3 commands that can be given to the radio board
on the HCI-1WL module.
9.3.9.2 Commands
* Select [Read device information], to read the static information from the
radio board.
After executing this command, the static information from the radio
board is read from the radio board and made available in diagnostic
entities. See 9.3.9.3.
* Select
After executing this command, the dynamic information from the radio
board is read from the radio board and made available in diagnostic
entities. See 9.3.9.3.
* Select
SD Card Status
Display Text
Description
SDOK
NOSD
Connection Status
Display Text
Description
NO KEY:
MACCONN
SECCONN
CONNECT
DISCOVR
NOTCONN
SECURNG
6 - 20
Commissioning
Display Text
Description
NOREDUN
BAD KEY
Description
TX power level
PRSSI
SRSSI
Secondary RSSI = Signal strength indicator for the redundant wireless connection.
Additional Items
Parameter
Description
Radio diagnostic
No explanation.
These diagnostic information items are only relevant if requested by the factory.
Radio software
build number
Radio Network
address
Radio
communication
channel
Wireless Network
ID
Radio mode
Radio IEEE Address
6 - 21
Commissioning
Remote
Cable length
3m
Remote
Cable length
10 m
Area
Antenna
Type
Integrated
Europe
4 dBi
10
10
12
8.5 dBi
14 dBi
Not possible
All types
20
6 - 22
Commissioning
6 - 23
Commissioning
<
<
MENU
FIGURE 9-3
MA IN
<
>
SELECT
F4A07-0013
At request from SmartView, the FII-SMV board prepares data sets for it.
The requests from SmartView depend on the actual screen at the time.
The communication between the FII-SMV and SmartView uses an own
protocol on an RS-485 physical layer.
The SmartView display can be delivered as a portable device.
The FII-SMV board continuously scans all addresses, and only the one
with the lowest address are served.
For example, if a stand-alone SmartView (address 3) and an integrated
SmartView (address 2) are connected, the stand-alone SmartView
(address 3) are served as soon as the integrated SmartView (address
2) is closed (set to idle).
6 - 24
Commissioning
Name
Value Range
Default Value
Explanation
[Decimal separator]
<point>
<comma>
<point>
<enable>
<disable>
<enable>
[Identification]
<-------->
Name of a tank or
instrument. This string is
visible within a [PV screen].
[Password]
<......> 6 characters
<ENRAF2>
[Function identification]
<......> 13 characters
<SmartView mst>
<level temperature>
<Info Switch>
<Info Switch>
<01......XX> 2 digits
<01>
<00......XX> 2 digits
<00>
<01......XX> 2 digits
<01>
<TANK1234>
6 - 25