3. Low and Low low level switches shall be used in the DM water storage tank. Low
level switch shall be utilized for low level alarm in local control panel. Low low
level switch shall be used for tripping running pump as well as indication in local
control panel. The low low level switch shall also be used for start-up interlock of
forwarding pumps.
5. In addition to above alarms, there shall also be status indicating lamps for pump
status indication in the panel.
6. No remote operation for the pumps shall be envisaged. A common alarm for
system trouble will be routed to DCS.