Negative Power Factor
Negative Power Factor
Dinesh Chhajer
Megger
Dallas, Tx
dinesh.chhajer@megger.com
Abstract: Power Factor (PF) testing has been a very critical to make correct decisions when it comes to
common insulation diagnostic test and is frequently estimating an assets remaining healthy life.
used to evaluate the insulation condition of electrical Electrical insulation has been a very common reason
equipment. This paper focuses on some unknown and
for most of the electrical equipment failures. A lot of
not so popular facts that get overlooked easily. PF
time and effort have been put forward to diagnose
testing has been standardized at 10 kV and readings are
trended over a period of time at that voltage level or
and better estimate the condition of insulation as it
with values equivalent to 10 kV. Is PF a function of ages. Deterioration of insulation is dependent upon
voltage? Why is only 10 kV the standard value? various factors like ageing, mechanical stress,
Excitation current measurements taken at lower voltage thermal and chemical stress, over loading and
levels are normalized to 10 kV using a linear V/I varying environmental conditions. Dielectric strength
relationship, whereas excitation or magnetization curve of insulation can be assessed by various off-line and
exhibits a non-linear relation. PF testing of low- online testing techniques.
capacitance specimens, at times, will reflect negative PF
values. How can PF readings be negative? PF values of Power Factor (PF) test is a traditional and reliable
all insulation materials vary with temperature. Use of way of estimating the condition of insulation of
average temperature correction factor tables for
electrical equipment such as power transformers,
specimens subjected to different loading, ageing
circuit breakers, generators, cables and other
acceleration and stresses only gives an approximate
value and not accurate temperature compensation for electrical assets. PF values, trended periodically, can
PF values. help in detecting problems like contamination, high
moisture content and the presence of voids in
This paper is intended to explain these unusual PF specimen insulation. Excitation current tests, along
testing facts which include PF as a function of voltage, with PF tests performed on power transformers, can
negative PF values, non-linearity in excitation current
help in detecting turn to turn insulation failure.
measurements, use of average temperature correction
factor values and some other PF facts that are often Diagnostic tests, along with best testing practices as
overlooked.
per internationally accepted standards, provide
Keywords- Power factor (PF), excitation current, valuable information that can prevent unplanned and
temperature correction, dielectric frequency response unexpected failure of the insulation system.
(DFR) Maintaining good quality of insulation helps in
preventing failures and outages that jeopardize the
I. INTRODUCTION reliability of the overall electrical system operation.
Extending the life of substation assets result in less
With an increasing failure rate of substation electrical outages, higher reliability, system stability and a
equipment, utilities and large industry are faced with substantial financial benefit.
a challenge to focus on preventive and predictive
maintenance to ensure the power systems integrity II. Power Factor vs. Voltage
and stability. Precise and accurate measurements are
PF tests are usually performed at 10 kV or the Test instruments with very high noise suppression
readings are obtained as 10 kV equivalent. The capability are required for measurements in high
appropriate voltage level at which to perform the voltage substations where electrical noise and
power factor tests is a frequently debated topic. In interference level can be as high as 15 mA. Since,
todays world, the available instrumentation and signal current is very low when performing AC
measurement techniques provide flexibility in insulation test, a SNR of 1:20 can be expected in
performing the same PF test with a variable test worst case scenarios.
voltage. With the test instruments available, PF can
be performed at any voltage ranging from 27 V to 12 With the new developments in testing technologies,
kV. What test voltage is good enough for accurate we can expect to see testing being performed at lower
and reliable measurements? The answer resides in voltages with better filtering and noise rejection
what kind of specimen is being tested and under what capabilities. Additionally, we can expect the size of
conditions it is being tested. the portable test sets to reduce further in coming
years.
Most of the power transformers have oil-paper type
insulating systems. This type of insulation exhibits a III. Negative Power Factor Values
flat response (no change) when PF is measured as a
function of test voltage. On the other hand motors For an ideal insulation, the value of PF should be
and generators typically have dry or solid type zero. For all practical purposes, any specimen
insulation that exhibits PF values as a function of test exhibiting a value close to zero is considered to have
voltages. Its value increases with the increase in test a good quality of insulation. PF test sets always try to
voltage due to the presence of voids. Almost all solid measure one single capacitor. If it is not just a
insulation materials have voids present in it. The capacitor, the results look strange. This should give
number of voids present will vary based upon the an indication to the user about the characteristics of
geometry, age, construction and design of the the specimen. When performing tests on bushings,
insulation system. PF is a measure of losses taking three winding transformers or inter-phase insulation
place in the insulation system. The amount of of rotating machinery, the PF values will sometimes
increase in PF value as a function of voltage turn out to be negative. What does that mean? PF is a
corresponds to the degree of ionization taking place measure of the amount of watts loss taking place in
in voids. the insulation. Negative PF corresponds to watts
generation as opposed to watts loss. Obviously,
One of the reason industry has standardized on 10 kV insulation cannot generate it, which proves that
as a typical test voltage is for immunization against negative PF values are not real.
electrostatic interference. Power transformers
operating in high voltage substations are subjected to
a lot of electrical noise and interference around the Specimen
nominal frequency. A HV test signal provides better
signal to noise ratio (SNR) for precise and accurate
measurements. Table 1 below shows a SNR ratio of
1:2 in 765 kV substation on a UST (Ungrounded
Specimen Test) measurement.
Figure 3: Vector diagram with different magnitude of Figure 4: Typical magnetization curve of a power
current INET and purely resistive loss current Is transformer
When dealing with specimens that are highly When performing excitation current measurements
inductive, such as power transformers, voltage and on delta windings, it is very important to ground the
current do not exhibit a linear correlation as shown in third leg of the delta configuration in order to obtain
Fig 4. correct readings as shown in Fig 5.
The relationship between V & I is dependent on core Since the excitation current is a UST test, grounding
characteristics and the material used. As applied the third leg eliminates the current flowing in the
voltage is increased, inductance of the transformer other two windings from the measurement circuit.
will change and therefore the excitation current will Pending the inductance and resistance of each
change too. Since, change of inductance is not linear winding, if third leg is not grounded, the results
with respect to voltage; change in current is also non- would be approximately 30 to 50% higher than true
linear. Assuming a linear relation to determine 10 kV readings as shown in Table 3.
equivalent excitation values would only give the
approximate values. It is very important to perform Table 3: Excitation current test performed on delta
tests at the same voltage if excitation current winding with and without third leg grounded
historical data need to be trended and compared with
present values. Test performed at 2 kV and then
corrected to 10 kV may not be comparable to test
performed at 10 kV as shown in Table 2. The ability
to trend and compare data is critical when trying to
find out problems associated with turn to turn A transformer with magnetized core can cause
insulation. erroneous readings in excitation current
measurements. The core may have residual
Table 2: Excitation current test performed at magnetism as a result of heavy fault seen by a
different voltages on a single phase Transformer transformer or because of application of DC
current/voltage to it. Presence of residual magnetism
would result in higher excitation current values than
normal. IEEE 62-1995 section 6.1.3.4 states that If a
significant change in the test results is observed, the
only known reliable method of excluding the effect of
residual magnetism is to demagnetize the transformer
core. It is recommended that the dc measurements of
the winding resistance be performed after the
exciting current tests.
V. Temperature Correction
Factors for PF readings
PF values are highly dependent on temperature. IEEE
C57.12.90 section 10.10.4 Note 3 (b) states that
Experience has shown that the variation in power
factor with temperature is substantial and erratic so
Figure 5: Excitation current measurement on a Delta that no single correction curve will fit all
winding with third leg grounded cases.Correction factor tables have traditionally
been used to bring all the recorded data to a common in the second half of the life cycle. In this second
base of 20 C. half, correction factors would be larger because of the
increased effect of temperature on condition of the
It is imperative to only compare a specimens PF insulation. Using average temperature correction
values that are either taken at a similar temperature or values can lead to incorrect trending of results and
corrected to the same temperature accurately. inaccurate estimation of the remaining healthy life of
Different specimens behave differently to the effects the object.
of change in temperature on PF values. Additionally,
the same specimen will become more temperature IEEE Std. 62-1995 states that Testing at
dependant as it ages, Ref [3]. temperatures below freezing should be avoided, since
this could significantly affect the measurement.
Each specimen is unique in its construction, design Among the primary reasons for performing this test is
and ratings. They are each subjected to different the capability of detecting moisture in insulation. The
kinds of stresses, loading and different environmental electrical characteristics of ice and water are quite
conditions. A transformer, with 20 years of service different and it is much more difficult to detect the
operating at 100% of its capacity in weather presence of ice than it is to detect water; sometimes it
conditions of 45 C would have a totally different is impossible. Measuring PF at too high or too low
level of stress on insulation than another transformer of temperature conditions can introduce error in PF
with 10 years of service running at 75% of its measurements. IEEE recommends performing the PF
capacity in an environmental condition of 30 C. tests at or near 20 C and repeated periodically for
Figure 6 below shows four transformers with varying correct trending.
degree of temperature dependence based upon their
age, rating and moisture level, Ref [3]. However, in reality its not always practical to cool
down or heat up the transformer or any other test
specimen to 20 C for the purpose of performing
these measurements.
VII. References
[1] IEEE Standard Test Code for Liquid-Immersed
Distribution, Power, and Regulating Transformers
and Guide for Short-Circuit Testing, IEEE
C57.12.90-2006
[2] IEEE Guide for Diagnostic Field Testing of
Electric Power Apparatus; Part 1: Oil Filled Power
Transformers, Regulators, and Reactors, IEEE 62-
1995
[3] P. Werelius, M Ohlen, Dielectric Frequency
Response and Temperature Dependence of Power
Factor, Electrical Insulation (ISEI), Conference
Record of the 2010 IEEE International Symposium
[4] D Chhajer, Power Factor Tip up Test
Techniques & Concerns, paper presented at NETA
2010
[5] Doble manual Power Factor Testing of electric
power apparatus insulation with Doble type M
instruments, Doble engineering company, 2002
[6] Megger, Instruction manual for Delta 2000- 10
kV automated insulation test set Rev. B 2001
[7] P. Werelius, thesis Development and
Application of High Voltage Dielectric Spectroscopy
for Diagnosis of Medium Voltage XLPE Cables
[8] Megger, Application guide for power factor
testing of power & distribution transformers