Structural - Lane

Download as pdf or txt
Download as pdf or txt
You are on page 1of 37
At a glance
Powered by AI
The document discusses structural design parameters for a building including seismic, wind, gravity loads.

The seismic design category is B, occupancy category is III, mapped spectral accelerations are provided, design is based on equivalent lateral force procedure.

The basic wind speed is 100 mph, exposure category is C, design wind pressures for various building elements are provided.

C:\Proj\2011101_structural_kevinh.

rvt SYMBOLS LEGEND DEFERRED SUBMITTALS DESIGN CRITERIA STRUCTURAL DRAWING LIST
SYMBOL DESCRIPTION SYMBOL DESCRIPTION 1. GENERAL: 1. CODES AND STANDARDS: SHEET ADD
SYMBOL DESCRIPTION 1A. THE FOLLOWING PORTIONS OF THE STRUCTURAL DESIGN WILL NOT BE SUBMITTED AT THE 1A. GENERAL DESIGN NUMBER SHEET TITLE DD BP#1 BP#2 BP#3 005
MECH UNIT (XX.Xk = MECH TIME OF PERMIT APPLICATION. WHEN RECEIVED AND REVIEWED, THESE DEFERRED SUBMITTAL - INTERNATIONAL BUILDING CODE 2009
XXX'-XX" STEEL BEAM SHEAR STUD QUANTITY S-001 NOTES
ELEVATION CALLOUT UNIT OPERATING WEIGHT ITEMS SHALL BE SUBMITTED TO THE BUILDING OFFICIAL BY THE CONTRACTOR:
IN KIPS INCLUDING INERTIA - EXCAVATION SHORING 2. SEISMIC LOADS S-002 NOTES
XX.Xk XXk BEAM SIZE [XX] c=X" XXk
BASE) - METAL STAIRS - SEISMIC DESIGN CATEGORY = B S-003 QUALITY ASSURANCE
STEP (XXX'-XX") - OCCUPANCY CATEGORY = III
- CURTAIN WALL S-004 QUALITY ASSURANCE
EXTENT OF CONCRETE PAD SERVICE BM CAMBER (INCHES) - LIGHT GAGE METAL FRAMING - EARTHQUAKE IMPORTANCE FACTOR, Ie = 1.25
REACTION (KIPS) S-101 FIRST LEVEL FLOOR PLAN
EL OF T/STEEL - METAL RAILINGS - MAPPED SPECTRAL RESPONSE ACCELERATION, Ss= 0.212
SLOPE S-102 SECOND LEVEL FLOOR PLAN
CAST-IN-PLACE CONC - MAPPED SPECTRAL RESPONSE ACCELERATION, S1= 0.059
- DESIGN SPECTRAL RESPONSE COEFFICIENT, SDs = 0.170 S-103 THIRD LEVEL FLOOR PLAN
1 KEY NOTE
* BOTTOM FLANGE CONNECTION PER 20 / S-501 - DESIGN SPECTRAL RESPONSE COEFFICIENT, SD1 = 0.067
- SOIL SITE CLASS = C
S-104
S-105
FOURTH LEVEL FLOOR PLAN
PENTHOUSE FLOOR PLAN






SUBGRADE MOMENT CONNECTION - BASIC STRUCTURAL SYSTEM: BUILDING FRAME SYSTEM S-106 ROOF PLAN
- STRUCTURAL SEISMIC LATERAL SYSTEM: ORDINARY REINFORCED CONCRETE

FORM SAVER
AXIAL DRAG CONNECTION PHASED CONSTRUCTION NOTES SHEAR WALLS
- RESPONSE MODIFICATION FACTOR, R = 5
S-200
S-201
COLUMN SCHEDULE
PARTIAL PLANS


The Lane Center for
BRACING - SEISMIC RESPONSE COEFFICIENT, Cs= 0.033 S-202 PARTIAL PLANS Academic Health
1. GENERAL:
X DRAWING REVISION NUMBER DECK TYPE 1A. USE THE MOST CURRENT DRAWINGS IN PREPARATION OF SUBMITTALS. ALL SUBMITTALS
- SYSTEM OVERSTRENGTH FACTOR, OMEGA = 2.5 S-210 CORE WALL ELEVATIONS Sciences
- DESIGN BASE SHEAR EAST-WEST DIRECTION = 270 KIPS S-211 CORE WALL ELEVATIONS University of Colorado at
SYMBOL DESCRIPTION ABOVE DECK CONCRETE THICKNESS SHALL LIST DATE OF DRAWINGS USED TO PREPARE THE SUBMITTAL.
2VLIX.XXA - DESIGN BASE SHEAR NORTH-SOUTH DIRECTION = 270 KIPS Colorado Springs
CURRENT REVISION CLOUD TYPE S-212 CORE WALL ELEVATIONS
SOG CONCRETE SLAB ON GRADE XXX'-XX" - SEISMIC ANALYSIS PROCEDURE: EQUIVALENT LATERAL FORCE PROCEDURE 2011101.00
1B. BECAUSE THIS IS A PHASED CONSTRUCTION PROJECT, THE CONTRACTOR MUST ANTICIPATE S-213 STAIR PLANS AND SECTIONS
FW1 FOUNDATION WALLS DECK SPAN DIRECTION ADDITIONAL DRAWING REVISIONS AFTER EARLY BID PACKAGES HAVE BEEN ISSUED. THESE
3. WIND LOADS S-220 BUILDING ELEVATIONS
LOAD FOR SPECIALTY DESIGNER REVISIONS WILL INCREASE THE CONSTRUCTION COST. THE CONTRACTOR SHALL INCLUDE
T/SLAB AT SLAB-ON-DECK - OCCUPANCY CATEGORY = III S-221 BUILDING ELEVATIONS
THESE ANTICIPATED COSTS IN ANY BIDS OR PRICE GUARANTEES PROVIDED TO THE OWNER.
SLAB TYPE - WIND IMPORTANCE FACTOR, Iw = 1.15 S-300 TYP CONCRETE DETAILS Owner
WELDED-WIRE REINFORCEMENT SLAB THICKNESS - BASIC WIND SPEED = 100 MPH
S-310 TYP DRILLED PIER DETAILS Facilities Services
SOGXXA TYPE - EXPOSURE CATEGORY = C University of Colorado at Colorado Springs
SECTION OR - INTERNAL PRESSURE COEFFICIENT, GCpi = +/- 0.18 S-311 TYP FOUNDATION WALL DETAILS
XXX'-XX" T/SLAB
Campus Services Building, Rm 212
X DETAIL CUT S-312 FOUNDATION WALL DETAILS 1420 Austin Bluffs Parkway
Colorado Springs, CO 80918
XX DRILLED PIER DIAMETER IN INCHES 4. DESIGN WIND PRESSURE FOR COMPONENTS AND CLADDING AND ELEMENTS S-313 TYP GRADE BEAM DETAILS 719-255-3505
SHEET NUMBER PENETRATION INTO BEDROCK IN FEET DESIGNED BY THE CONTRACTOR S-314 TYP SOG DETAILS
DPXXA-XX - PRESSURES LISTED BELOW ARE BASED ON 10 SF EFFECTIVE WIND AREA. FINAL
ELEVATION CUT TYPE S-315 TYP STEEL TO CONCRETE CONNECTIONS
X XX'-X" CALCULATIONS TO BE COMPLETED BY CONTRACTOR Architect
- SEE WALL CORNER AND SPECIAL ROOF ZONES DIAGRAM S-316 STEEL TO CONCRETE CONNECTIONS AndersonMasonDale Architects, P.C.
XX PD-1 T/DRILLED PIER ELEVATION S-320 TYP CONCRETE SHEAR WALL DETAILS
SHEET NUMBER - TYPICAL WALL AREA INWARD PRESSURE = 33 PSF 3198 Speer Boulevard
Denver, CO, 80211
PIER DOWELS - TYPICAL WALL AREA OUTWARD PRESSURE = 33 PSF S-500A TYP STL BM CONNS 303-294-9448
- WALL CORNERS(OUTWARD) = 60 PSF S-500B TYP STL BM CONNS
X NEW GRID LINES - TYPICAL ROOF AREA (OUTWARD) = 48 PSF
- ROOF SPECIAL ZONES (EDGES) (OUTWARD) = 75 PSF
S-501 TYP STEEL DETAILS
Clinical Planning
- ROOF SPECIAL ZONES (CORNERS) (OUTWARD) = 101 PSF S-502 STEEL DETAILS
James W Nakai & Associates, PC
- PARAPETS (INWARD OR OUTWARD) = 123 PSF S-503 STEEL DETAILS 520 E Colorado Ave
- TYPICAL SOFFITS (UPWARD OR DOWNWARD) = 33 PSF Colorado Springs, CO 80903
S-530 TYP METAL DECK DETAILS 719-635-2142
- SOFFIT CORNER AREAS (DOWNWARD) - 60 PSF S-531 TYP METAL DECK DETAILS
S-540 TYP EXT WALL
5. LATERAL LOAD RESISTING SYSTEM DESCRIPTION: Civil
- METAL ROOF DECK AND COMPOSITE CONCRETE SLAB ON METAL DECK DIAPHRAMS S-541 TYP EXT WALL
TerraNova Engineering, Inc.
SPANNING BETWEEN ORDINARY REINFORCED CONCRETE SHEAR WALLS. CONCRETE 815 S 25th Street
SHEAR WALLS ARE SUPPORTED BY DRILLED PIERS. RELEASE NOTES: Colorado Springs, CO 80904
ABBREVIATIONS 719-635-6422

6. GRAVITY LOADS DD: DRAWINGS ARE RELEASED FOR DESIGN DEVELOPMENT AND GMP PRICING
/ Per EL Elevation MACH Machine (S) Salvaged
6A. SEE GRAVITY LOADS TABLE FOR SUPERIMPOSED DEAD LOAD AND LIVE LOADS USED Landscape
@ At ELEV Elevator MACH RM Machine Room S South IN DESIGN BP#1: DRAWINGS ARE RELEASED FOR EXTENTS OF OVEREXCAVATION BELOW SLABS ON
Lime Green Design, Inc
AB Anchor Bolt EMBED Embedded MAS Masonry SC Slip Critical GRADE ONLY 900 E. Louisiana Avenue, Suite 209
ACI American Concrete Institute EN Edge Nail MATL Material SCHED Schedule 6B. DRIFTING, SLIDING AND UNBALANCED SNOW Denver, CO 80210
- SEE 'DRIFTED SNOW LOADING DIAGRAM' ON S-004 BP#2: DRILLED PIERS, GRADE BEAMS, FOUNDATION WALLS, MAT SLABS, SLABS ON GRADE, 303-733-7558
ADDNL Additional ENGR Engineer MAX Maximum SECT Section
- GROUND SNOW LOAD = 20 PSF CAST IN PLACE SHEAR WALLS, ANCHOR BOLTS, EMBEDS AND SLABS ON METAL DECK ARE
AESS Architectural Exposed EOR Engineer-of-Record MBS Metal Building Supplier SIM Similar
- SNOW EXPOSURE FACTOR Ce = 1.0 RELEASED FOR PERMITTING AND BIDDING.
Structural Steel EQ Equal MCJ Masonry Control Joint SLH Short Leg Horizontal Structural
- SNOW LOAD IMPORTANCE FACTOR Is = 1.1
AFF Above Finished Floor EQ SP Equally Spaced MECH Mechanical SLRS Seismic Load Resisting - FLAT ROOF SNOW LOAD Pf= 30 PSF BP#3: RELEASED FOR CONSTRUCTION. Martin/Martin
12499 West Colfax Avenue
ALT Alternate EQUIP Equipment MEP Mech/Elect/Plumb System Lakewood, CO 80215
ALUM Aluminum ES Each Side MIN Minimum SLV Short Leg Vertical 7. FIRE RESISTANCE, CONDITIONS OF RESTRAINT: 303-431-6100

APA American Plywood SOG Slab on Grade 7A. FOR DETERMINING FIRE-RESISTANCE RATINGS PER IBC SECTION 703, FLOOR AND
EW Each Way MISC Miscellaneous
Association ROOF FRAMING SUPPORTING A COMPOSITE SLAB CAN BE ASSUMED TO BE
EXP Expansion ML Micro-Lam SP Space(s) Mechanical/Plumbing
RESTRAINED. ALL OTHER FRAMING AND CONSTRUCTION WALL BE ASSUMED TO BE
APPROX Approximate EXP ANCH Expansion Anchor MLS Masonry Lap Splice SP @ Space at Shaffer Baucom Engineering & Consulting
UNRESTRAINED.
ARCH Architect or Architectural EXT Exterior mm Millimeter SPECS Specifications 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
MNFR Manufacturer SPRT Support 303-986-8200
B/ or BO Bottom of SS Stainless Steel
WALL CORNER AND SPECIAL ROOF ZONES DIAGRAM
FAB Fabricate MO Masonry Opening
BAL Balance FD Footing Dowel MTL Metal STD Standard
INDICATES DIMENSIONS OF Electrical
BD Board FF Finished Floor STIFF Stiffener WALL CORNER ZONES, TYP Shaffer Baucom Engineering & Consulting
BF Braced Frame FIN Finish(ed) N North STL Steel 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
BG Backgouge FLG Flange N-S North-South STR Structural INDICATES CORNER 10'-0" 10'-0"

10'-0"
303-986-8200
BL Brick Ledge SW Shearwall ZONES AT ROOF
FLR Floor NIC Not in Contract
STEPS

10'-0"
BLDG Building FND Foundation NM Non-Metallic SYM Symmetrical Technology
BLKG Blocking FO Face of NO or # Number 10'-0" Rimrock Group
BM Beam FP Full Penetration or Fire NOM Nominal T Top 10807 New Allegiance Drive, Suite 400

10'-0"
Colorado Springs, CO 80921
BN Boundary Nail Proofing NS Non-Shrink or Near Side T&B Top and Bottom 719-533-1112
BOS Bottom of Steel FRAM Framing NTS Not To Scale T/ or T.O. Top of
BOT or B Bottom FS Far Side NWC Normal Weight Concrete THK Thick or Thickness
BRG Bearing Building Performance Engineer

10'-0"
FT Foot or Feet TL Total Load
Ambient Energy
BSMT Basement FTG Footing O.F. Outside Face TOC Top of Concrete 130 W 5th Ave
BTWN Between FV Field Verify OAE Or Approved Equivalent TOF Top of Footing Denver, CO 80204
303-278-1532
OC On Center TOM Top of Masonry

10'-0"
CC Center to Center 10'-0"
GA Gage or Gauge OD Outside Diameter TOP Topping

10'-0"
CF Cold Formed GALV Galvanized TOS Top of Steel Cost Estimating

10'-0"
OH Opposite Hand 10'-0" 10'-0"
CG Center of Gravity Parametrix, Inc.
GL Glu-lam OPNG Opening TOW Top of Wall
20'-0" 7186 South Highland Drive
CIP Cast-In-Place GR Grade or Grind OPP Opposite TRANS Transverse Salt Lake City, UT 84121
801-733-5900
CJ Control Joint GR BM Grade Beam OVS Oversized TWS Two-Way Slab INDICATES DIMENSIONS OF SPECIAL
CJP Complete Joint Penetration OWS One-Way Slab TYP Typical ROOF ZONES (EDGES), TYP
CL Centerline HAS or Headed Anchor Stud
CLG Ceiling HDAS PAF Power Actuated Fastener ULT Ultimate ZONES AT ROOF
CLR Clear HD Headed or Holdown PC Precast UNO Unless Noted Otherwise
CMU Concrete Masonry Unit HDAR Headed Anchor Rod PCA Portland Cement ZONES AT PH STEPPED ROOF
COL Column HDG Hot Dipped Galvanized Association VERT Vertical
INDICATES DIMENSIONS OF SPECIAL
CONC Concrete HK Hook PD Pier Dowel VIF Verify in Field ROOF ZONES (CORNERS), TYP
CONN Connection HORIZ Horizontal PEN Penetration
CONST Construction HT Height PERP Perpendicular W/ With
CONT Continue or Continuous HVAC Heating-Ventilating and A/C PL Plate (Steel) W/O Without GRAVITY LOADS TABLE
CONTR Contractor PLF Pounds Per Lineal Foot WD Width or Wood SUPERIMPOSED LIVE LOAD PARTITION POINT LOAD
COORD Coordinate I.F. Inside Face LOCATION DEAD LOAD (PSF) LIVE LOAD (PSF) REDUCTION LOAD (PSF) (LB)
PREFAB Prefabricated WF Wide Flange
CSJ Construction Joint ID Inside Diameter STAIRS AND 10 100 No -- 300
PRELIM Preliminary WP Working Point or Issue Date
EXITS
CTR(D) Center(ed) IN Inch PS Prestressed Waterproofing
TYPICAL FLOOR 10 100 Yes INCLUDED IN 2000 DESIGN DEVELOPMENT SEPTEMBER 12, 2012
INT Interior PSF Pounds Per Square Foot WT Weight
LL BP#2 NOVEMBER 16, 2012
d Penny IT Precast Inverted Tee Beam PSI Pounds Per Square Inch WWR Welded Wire Reinforcement BP#3 DECEMBER 21, 2012
TYPICAL FLOOR 25 100 Yes INCLUDED IN 2000
DAS Deformed Anchor Stud PT Point or Post-Tension or WxH Width x Height OVER LL RECORD DRAWINGS APRIL 18, 2014

DBL Double JST Joist Pretensioned MECHANICAL


DATE PRINTED: 4/18/2014 9:09:21 AM

DCW Demand Critical Weld JT Joint MECHANICAL 10 75 + EQUIP BUT No -- --


DFS Deferred Submittal QTY Quantity NOT LESS THAN
DIA or Diameter k Kip 150
DIAG Diagonal RAD or R Radius TERRACE 45 100 (INCLUDES No -- 2000
DIM Dimension L or LG Length RB Precast Rectangular Beam PLANTER LOAD)
DL Dead Load LB Precast L-Shaped Beam RC Reinforced Concrete ROOF AT 15 (INCLUDES 5 30 MIN UNIFORM No -- --
FOURTH LEVEL ROOFING LOAD) LOAD, SEE NOTE
DESIGNERS: KH/AM

DN Down LB(S) Pound(s) RE: or REF Refer to (Reference) 6B FOR SNOW


DO Ditto LCE Compression Embedment REINF Reinforce(ing)(d)(ment) LOADS
DP Drilled Pier or Deep LCS Compression Lap Splice REQD Required ROOF AT 15 (INCLUDES 5 30 MIN UNIFORM No -- --
DT Precast Double Tee LDH Hook Development Length REQT(S) Requirement(s) PENTHOUSE ROOFING LOAD) LOAD, SEE NOTE Project Number: 2011101.00
DTL(S) Detail(s) LL Live Load RET Return LEVEL 6B FOR SNOW
Drawn By: KH/AM
DWG(S) Drawing(s) LLH Long Leg Horizontal RO Rough Opening LOADS
DWL(S) Dowels(s) LLV Long Leg Vertical ROF Random Oriented Fiber PENTHOUSE 40 (INCLUDES 5 30 MIN UNIFORM No -- -- Reviewed By: KH
ROOF ROOFING LOAD LOAD, SEE NOTE PD
LOC(S) Location(s) or Locate Approved By:
AND 10 FUTURE 6B FOR SNOW
(E) or Existing LONG Longitudinal PHOTOVOLTAIC) LOADS
EXIST LSL Laminated Strand Lumber PERGOLA (LEVEL 10 30 MIN UNIFORM No -- --
PROJECT MANAGER: KH

E-W East-West LT Light 2 AND LEVEL 4) LOAD, SEE NOTE


MM JOB #: 23616.S.01

EA Each LTE Tension Embedment 6B FOR SNOW


EC Epoxy Coated LTS Tension Lap Splice Length LOADS NOTES
PRINCIPAL: PD

EE Each End LTWT Lightweight


EF Each Face LVL Level or Laminated Veneer
EOR: PD

EJ Expansion Joint Lumber


LWC Light Weight Concrete
S-001
C:\Proj\2011101_structural_kevinh.rvt GENERAL NOTES FOUNDATION NOTES STEEL NOTES
1. GENERAL: 1. DESIGN CRITERIA: 1. CONNECTIONS:
1A. ENGINEER: REFERENCES ON THE STRUCTURAL DRAWINGS TO ENGINEER MEAN THE 1A. THE GEOTECHNICAL REPORT PREPARED BY CTL THOMPSON, NUMBER CS178777-125, DATED DECEMBER 28, 2011, THE FINAL NOTICE LETTER, DATED 1A. PROVIDE CONNECTIONS AS SHOWN IN THE STEEL BEAM CONNECTION SCHEDULES AND STEEL MATERIAL TABLE
STRUCTURAL ENGINEER OF RECORD. OTHER ENTITIES ARE SPECIFICALLY NOTED AS SEPTEMBER 19, 2012, AND THE LETTER ADDRESSING WALL BACKFILL DATED OCTOBER 30, 2012 PROVIDED CRITERIA FOR THE FOUNDATION DESIGN FOR THE DETAILS HEREIN. REFER TO SPECIFICATION FOR ALTERNATIVES AND CONNECTIONS NOT SHOWN. STEEL ELEMENT ASTM/TYPE Fy (KSI) Fu (KSI) COMMENTS
CONTRACTORS ENGINEER, MECHANICAL ENGINEER, ETC. PROJECT. ANCHOR RODS F1554 GR 55 55 75 WELDABLE, HEAVY HEX HEADED
2. WELDING REQUIREMENTS:
1B. THESE NOTES SUPPLEMENT THE SPECIFICATIONS, WHICH SHALL BE REFERENCED FOR 2. DRILLED PIERS: BOLTS A325 OR F1852 -- 120 BOLTS ARE 3/4" UNO, USE
2A. WELDERS: HAVE IN POSSESSION CURRENT EVIDENCE OF PASSING THE APPROPRIATE A.W.S.
ADDITIONAL REQUIREMENTS. 2A. PIER CAPACITY CRITERIA: TENSION-CONTROLLED WHERE
QUALIFICATION TESTS.
- MAXIMUM END BEARING PRESSURE = 35 KSF POSSIBLE
1C. UNDERGROUND UTILITIES: LOCATE EXISTING UTILITIES AND NOTIFY ARCHITECT OF EXISTING - MAXIMUM SIDE SHEAR FOR LENGTH OF PENETRATION INTO BEDROCK FOR GRAVITY LOADS = 3.5 KSF 2B. MINIMUM WELDS: AISC SPECIFICATION, NOT LESS THAN 3/16 FILLET, CONTINUOUS UNLESS COLD-FORMED A1003 33 -- --
UTILITIES OR SUBGRADE CONDITIONS WHICH INTERFERE WITH WORK. - MAXIMUM SIDE SHEAR FOR LENGTH OF PENETRATION INTO BEDROCK FOR UPLIFT LOADS = 3.5 KSF OTHERWISE NOTED. STUDS/PLATE, 33 AND 43
- SIDE SHEAR FOR UPPER 5-0 OF PIER WAS NEGLECTED MIL
1D. STRUCTURAL ELEMENTS ARE CENTERED ON GRID LINES AND GRID LINE INTERSECTIONS - MINIMUM DEAD LOAD END BEARING PRESSURE MAINTAINED = 20 KSF 2C. WELD SIZES AND LENGTHS CALLED FOR ON THE DRAWINGS ARE THE NET EFFECTIVE COLD-FORMED A1003 50 -- --
UNLESS DIMENSIONED OTHERWISE. - WHERE MINIMUM DEAD LOAD PRESSURES WERE NOT OBTAINED, PIER LENGTHS WERE EXTENDED BEYOND THE MINIMUM PENETRATION REQUIRED. INCREASE WELD SIZE IF GAPS EXIST AT THE FAYING SURFACE. STUDS/PLATE, 54 MIL AND
USING SIDE SHEAR TO COMPENSATE FOR THE DEAD LOAD DEFICIT. BP HEAVIER
003
2. USE OF DRAWINGS: 2D. WELD SIZES SHALL BE AS SHOWN UNLESS A GREATER SIZE IS REQUIRED BY ANSI/AISC 360-05 COLD-FORMED TRACK, A1003 33 -- --
2A. DO NOT SCALE DRAWINGS. 3. FOUNDATION WALLS: TABLES J2.3 AND J2.4. ALL THICKNESSES The Lane Center for
3A. EQUIVALENT FLUID PRESSURES USED FOR WALL DESIGN:
2B. WHERE DISCREPANCIES OCCUR BETWEEN PLANS, DETAILS, GENERAL NOTES AND - AT REST CONDITION = 60 PCF
DAS A496 60 80 -- Academic Health
2E. ALL GROOVE WELDS SHALL BE COMPLETE PENETRATION UNLESS NOTED.
SPECIFICATIONS, THE MORE STRINGENT REQUIREMENTS SHALL GOVERN. DETAILS ON DRAWINGS - LATERAL PRESSURE DUE TO SURCHARGE = 100 PSF HAS A108 51 65 STUDS ARE 3/4" UNO Sciences
TAKE PRECEDENCE OVER GENERAL NOTES AND TYPICAL DETAILS. DETAILS NOTED TYPICAL 2F. FIELD WELDING SYMBOLS INDICATE SUGGESTED CONSTRUCTION PROCEDURES. OTHER SHAPES A36 36 58 -- University of Colorado at
APPLY TO ALL SIMILAR CONDITIONS. WHERE NO SPECIFIC DETAILS ARE SHOWN, CONSTRUCTION 3B. WALL DESIGN BASED ON ON-SITE OR IMPORTED SILTY TO CLAYEY SAND BACKFILL ADJACENT TO FOUNDATION WALLS. SEE GEOTECHNICAL REPORT FOR PIPE A53 GR B 35 60 -- Colorado Springs
SHALL CONFORM TO SIMILAR WORK ELSEWHERE ON THE PROJECT. REQUIREMENTS. 3. COMPOSITE GRAVITY FRAMING: PLATES A36 36 58 -- 2011101.00
3A. COMPOSITE BEAMS ARE DESIGNED ASSUMING STUDS ARE INSTALLED IN THE WEAK POSITION RECT HSS A500 GR B 46 58 --
3. TEMPORARY CONDITIONS: 4. SITE RETAINING WALLS: (Rp = 0.6). SEE TYPICAL METAL DECK DETAILS FOR PLACEMENT REQUIREMENTS.
3A. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. THE 4A. EQUIVALENT FLUID PRESSURES USED FOR WALL DESIGN: ROUND HSS A500 GR B 42 58 --
CONTRACTOR IS RESPONSIBLE FOR FURNISHING ALL TEMPORARY BRACING AND/OR SUPPORT - ACTIVE CONDITION = 45 PCF 3B. COMPOSITE GIRDERS ARE DESIGNED ASSUMING STUDS ARE WELDED THROUGH THE METAL WELDING ELECTRODES, E70 PER AWS Owner
THAT MAY BE REQUIRED AS THE RESULT OF THE CONTRACTORS CONSTRUCTION METHODS - PASSIVE CONDITION = 350 PCF DECK AND/OR METAL DECKING/SHEET STEEL COVERS MORE THAN HALF OF THE TOP FLANGE (Rp = THICKNESS OF THINNER
Facilities Services
AND/OR SEQUENCES. REFER TO LATERAL LOAD RESISTING SYSTEM DESCRIPTION IN DESIGN - LATERAL PRESSURE DUE TO SURCHARGE = 100 PSF 0.75). SEE TYPICAL METAL DECK DETAILS FOR PLACEMENT REQUIREMENTS. PART > 0.1 INCHES (12 GA) University of Colorado at Colorado Springs
CRITERIA FOR ADDITIONAL INFORMATION. - MAXIMUM FOOTING TOTAL LOAD SOIL BEARING PRESSURE = 2000 PSF WELDING ELECTRODES, E60 OR E70 -- -- PER AWS Campus Services Building, Rm 212
1420 Austin Bluffs Parkway
- ULTIMATE COEFFICIENT OF FRICTION USED IN DESIGN TO RESIST LATERAL LOADS = 0.40 4. CAMBER: THICKNESS OF THINNER Colorado Springs, CO 80918
3B. FOUNDATION WALLS MAY BE BACKFILLED PRIOR TO THE SLAB-ON-GRADE AND UPPER SLAB 4A. FABRICATE BEAMS SUCH THAT ROLLING OR FABRICATION INDUCED CAMBER IS UP AFTER PART 0.1 INCHES (12 GA) 719-255-3505
CONSTRUCTION. BACKFILL SHALL BE PLACED EVENLY ALONG LENGTH OF BUILDING UP TO THE 4B. WALL DESIGN BASED ON ON-SITE SILTY TO CLAYEY SAND BACKFILL ADJACENT TO SITE RETAINING WALLS. SEE GEOTECHNICAL REPORT FORE ERECTION. WF, WT A992 50 65 --
SPECIFIED GRADE. USE ONLY HAND OPERATED TOOLS FOR COMPACTION ADJACENT TO REQUIREMENTS.
FOUNDATION WALLS AND GRADE BEAMS. GRADE BEAMS SHALL BE BACKFILLED EVENLY ON 4B. CAMBER SHOWN IS BASED ON THE COMPUTED DEFLECTION OF THE BEAM DUE TO Architect
BOTH SIDES. HEAVY CONSTRUCTION EQUIPMENT SHALL NOT BE OPERATED WITHIN 10'-0" OF 5. VOID FORM: SELFWEIGHT OF CONCRETE PLACED. DESIGN IS BASED ON THE THEORETICAL CONCRETE AndersonMasonDale Architects, P.C.
FOUNDATION WALL UNTIL SOG AND SECOND LEVEL SLAB IS IN PLACE AND HAS REACHED THE 5A. ALL GRADE BEAMS, MATS, FOUNDATION WALLS, PILASTERS AND PIER CAPS SHALL BE CONSTRUCTED OVER A 4 INCH HIGH VOID. THICKNESS PLUS 1/2 THICKNESS FOR DECK LEVELING AND 1/2 THICKNESS FOR BEAM LEVELING. 3198 Speer Boulevard
BP Denver, CO, 80211
SPECIFIED 28-DAY COMPRESSIVE STRENGTH. 003 INCLUDE QUANTITY OF ADDED CONCRETE DUE TO DECK AND BEAM DEFLECTION IN BID. 303-294-9448

4. SUBMITTALS AND SUBSTITUTIONS: 4C. VALUE NOTED ON PLAN IS IN-PLACE CAMBER, AFTER ERECTION, PRIOR TO PLACING
4A. SUBMITTALS: REFER TO SPECIFICATIONS FOR DETAILED REQUIREMENTS. CONCRETE. ADJUST FABRICATION AS REQUIRED TO ACHIEVE CAMBER SPECIFIED WITHIN Clinical Planning
- IF THE CONTRACTOR REQUESTS A CHANGE FROM THE STRUCTURAL DRAWINGS, IT SHALL BE TOLERANCES. James W Nakai & Associates, PC
APPROVED BY THE ARCHITECT AND DESIGNED BY MARTIN/MARTIN, INC. PRIOR TO SUBMITTING 520 E Colorado Ave
SHOP DRAWINGS. VARIATION SHALL BE INDICATED ON THE SHOP DRAWINGS. CONTRACTOR 5. STRUCTURAL STEEL INSTALLATION: POST-INSTALLED ANCHOR TABLE Colorado Springs, CO 80903

SHALL COMPENSATE MARTIN/MARTIN, INC. FOR MAKING THE CHANGE.


- CONSTRUCTION DOCUMENTS SHALL NOT BE REPRODUCED FOR USE IN SUBMITTALS
CONCRETE NOTES 5A. ALL HIGH STRENGTH BOLTS USED IN COLUMN SPLICES, CONNECTIONS OF BEAMS AND
ANCHOR TYPE PRODUCT Fy (KSI) Fu (KSI) COMMENTS
719-635-2142

GIRDERS TO COLUMNS, AND WHERE NOTED ON THE DRAWINGS AS TYPE SC OR OTHER TYPE
- ALL SHOP DRAWINGS SHALL REFERENCE THE STRUCTURAL DRAWING NUMBER AND DETAIL FOLLOWED BY PT, SHALL BE TENSIONED TO THE VALUES OF TABLE J3.1 OF ANSI/AISC 360-05. ADHESIVE HILTI HY 150 MAX SD (*) -- -- SUBMIT CALCULATIONS Civil
1. GENERAL: (IN CONCRETE) FOR SUBSTITUTIONS
USED TO PREPARE THE SUBMITTAL OTHER HIGH-STRENGTH BOLTS MAY BE INSTALLED SNUG TIGHT AS DEFINED BY AISC. TerraNova Engineering, Inc.
1A. ALL WORK SHALL CONFORM WITH ACI 301, LATEST EDITION, UNLESS NOTED OTHERWISE IN
- SUBMIT A STATEMENT OF RESPONSIBILITY FOR CONSTRUCTION OF THE LATERAL LOAD CONCRETE MIX TABLE ADHESIVE ANCHOR RODS -- 36 58 THREADED ROD, 815 S 25th Street
DRAWINGS OR PROJECT SPECIFICATIONS. Colorado Springs, CO 80904
RESISTING SYSTEM IDENTIFIED IN THE DESIGN CRITERIA IN ACCORDANCE WITH IBC SECTION 1709 6. METAL DECK:

MAX W/C RATIO, INCLUDING FLY ASH


MIN MIN UNGREASED 719-635-6422

MAX AGGREGATE SIZE (IN), NOTE a


6A. SEE METAL DECK SCHEDULE FOR MATERIALS, PROFILE, AND CONNECTIONS TO STRUCTURE.

TOTAL AIR CONTENT (%), NOTE b


1B. DETAIL BARS IN ACCORDANCE WITH THE LATEST EDITIONS OF PUBLICATION SP-66: ACI

OTHER REQUIREMENTS, NOTE c


4B. SUBSTITUTIONS: ARCHITECTS APPROVAL SHALL BE SECURED FOR ALL SUBSTITUTIONS EXPANSION ANCHORS HILTI KWIK BOLT TZ -- -- SUBMIT CALCULATIONS
DETAILING MANUAL WITH ADDED REQUIREMENTS OF THE PROJECT SPECIFICATION AND ACI 318: (IN CONCRETE) FOR SUBSTITUTIONS
6B. DECK DESIGN IS IN ACCORDANCE WITH STEEL DECK INSTITUTE (SDI) PUBLICATION NO. 31 AND Landscape
BUILDING CODE REQUIREMENTS FOR STRUCTURAL CONCRETE.

28 DAY STRENGTH, f'c (KSI)


4C. NONCONFORMANCE: NOTIFY ARCHITECT OF CONDITIONS NOT CONSTRUCTED PER THE DIAPHRAGM DESIGN MANUAL, LATEST EDITIONS. SCREW ANCHORS HILTI HUS-EZ -- -- SUBMIT CALCULATIONS Lime Green Design, Inc
CONTRACT DOCUMENTS PRIOR TO PROCEEDING WITH CORRECTIVE WORK. SUBMIT PROPOSED 900 E. Louisiana Avenue, Suite 209
2. REINFORCING MATERIALS: FOR SUBSTITUTIONS
REPAIR TO THE ARCHITECT FOR ACCEPTANCE. CONTRACTOR SHALL COMPENSATE 6C. PLACE CONCRETE ON METAL DECK IN ACCORDANCE WITH SDI PUBLICATION NO. 31 TO LIMIT Denver, CO 80210

CONCRETE WEIGHT
2A. SEE REINFORCING MATERIALS TABLE 303-733-7558
MARTIN/MARTIN, INC. FOR DESIGNING THE REPAIR. CONSTRUCTION LOADS TO ALLOWABLE MAGNITUDES. * USE HILTI HIT RE 500 SD FOR EMBEDMENT GREATER THAN 12"

CONC MIX TYPE


3. REINFORCING FABRICATION:
5. OSHA STANDARDS: 6D. REINFORCE OPENINGS IN METAL ROOF DECK AND FLOOR DECK SUPPORTING CONCRETE FILL
3A. SPLICES: Structural
5A. THE STRUCTURE IS DESIGNED TO FUNCTION AS A UNIT UPON COMPLETION. NOTHING SHOWN IN ACCORDANCE WITH TYPICAL DECK OPENING DETAILS.
- NO SPLICING OF REINFORCEMENT PERMITTED EXCEPT AS NOTED ON DRAWINGS. MAKE BARS Martin/Martin
ON THE STRUCTURAL DRAWINGS SHALL BE CONSTRUED AS ELIMINATING THE NEED FOR THE 12499 West Colfax Avenue
CONTINUOUS AROUND CORNERS. WHERE PERMITTED, SPLICES MAY BE MADE BY CONTACT LAPS
CONTRACTOR TO COMPLY WITH ALL OSHA REQUIREMENTS. INTENDED USE 6E. INSTALL DECK OVER 4 SUPPORTS (3 SPAN CONTINUOUS) UNLESS NOTED OTHERWISE. DO NOT Lakewood, CO 80215
OR MECHANICAL CONNECTORS. 303-431-6100
INSTALL DECK AS SINGLE SPAN UNLESS SPECIFICALLY SHOWN ON DRAWINGS.
- SEE LAP SPLICE SCHEDULE FOR LAP LENGTHS. 1 DRILLED PIERS 4 NWC 0.50 1 -- DP
5B. THE CONTRACTOR SHALL ADD ALL NECESSARY BOLTS, ANCHOR BOLTS, PLATES, STIFFENER
PLATES, STABILIZER PLATES, BRIDGING, BRACING, BEARING SEATS, COLUMN SPLICES, ETC., AS 2 GRADE BMS, TIE BMS, 4 NWC 0.50 3/4 -- -- 6F. PROVIDE DECK ATTACHMENTS AS NOTED ON DRAWINGS.
3B. MISCELLANEOUS REINFORCING REQUIREMENTS: MAT SLABS, FND WALLS, Mechanical/Plumbing
WELL AS CLOSURES FOR OPENINGS. IN ADDITION, FIELD WELD ANYTHING THAT MAY BE
- PROVIDE ADDITIONAL BARS OR STIRRUPS REQUIRED TO SECURE REINFORCING IN PLACE WALLS Shaffer Baucom Engineering & Consulting
CONSIDERED A TRIP HAZARD, SUCH AS SHEAR STUDS, AFTER PROTECTIVE DECKING IS 6G. HANGERS: SEE TYPICAL METAL DECK DETAILS FOR ALLOWABLE HANGER LOADS AND
DURING CONCRETE PLACEMENT. 3 SLAB ON GRADE 3.5 NWC -- 1 NP SVT, MSS
7333 West Jefferson Avenue, Suite 230
INSTALLED. SPACING. METAL GAUGE CONVERSION Lakewood, CO 80235
- MAKE ALL REINFORCING BAR BENDS IN THE FABRICATORS SHOP UNLESS NOTED. 303-986-8200
- NO WELDING OF REINFORCING PERMITTED UNLESS NOTED ON DRAWINGS. WHERE 4 SLABS ON METAL DECK 3.5 NWC 0.50 3/4 NP SVT MINIMUM THICKNESS
5C. WASHERS OR RINGS MAY BE WELDED TO NON-AESS COLUMNS TO PROVIDE FOR SAFETY 7. STRUCTURAL COLD FORMED METAL FRAMING: GAUGE
PERMITTED, PERFORM WELDING IN ACCORDANCE WITH AWS D1.4, LATEST EDITION. 5 ALL CONC EXPOSED TO 5 NWC 0.40 3/4 6 MSS, MCI (MILS*)
CABLES. DO NOT PLACE HOLES IN COLUMNS WITHOUT APPROVAL OF THE STRUCTURAL WEATHER OR DEICERS: 7A. COLD FORMED METAL FRAMING IS A PERFORMANCE SPECIFIED ITEM DESIGNED BY THE
- PROVIDE ADDED REINFORCING TO TRIM ALL OPENINGS, NOTCHES, AND REENTRANT CORNERS 22 27 Electrical
ENGINEER. ADJUST LOCATIONS OR ADD COLUMN SPLICES AS NECESSARY TO COMPLY WITH SLABS ON GRADE, SITE CONTRACTOR. PROVIDE STUD DEPTH INDICATED ON THE DRAWINGS. DO NOT EXCEED MAXIMUM
AS NOTED IN TYPICAL DETAILS. BP
OSHA REQUIREMENTS. SUBMIT PROPOSED LOCATIONS. WALLS, MECHANICAL SPACING INDICATED. VARY FLANGE WIDTH, GAGE, YIELD STRENGTH, BRACING, STUD SPACING, 20 33 Shaffer Baucom Engineering & Consulting
- 003 7333 West Jefferson Avenue, Suite 230
YARD ETC. AS REQUIRED TO SATISFY PERFORMANCE CRITERIA IN THE CONTRACT DOCUMENTS. MINIMUM 18 43
3C. INCLUDE IN THE BID THE COST FOR THE MATERIAL, FABRICATION AND PLACING OF 1000 Lakewood, CO 80235
5D. WHERE THE STRUCTURAL DRAWINGS APPEAR TO CONFLICT WITH OSHA REQUIREMENTS, THE STUD GAGE SPECIFIED IS REQUIRED FOR ATTACHMENT OF OTHER MATERIALS TO STUDS. DO NOT 303-986-8200
LINEAR FEET OF #5 REINFORCING BARS AND 500 LINEAR FEET OF #8 REINFORCING BARS. THE 16 54
STRUCTURAL DRAWINGS REPRESENT FINAL CONDITIONS ONLY. THE CONTRACTOR SHALL ADD BASE BIDS ON MINIMUM GAGE OR MAXIMUM SPACING SPECIFIED.
REINFORCING WILL BE ADDED TO THE SHOP DRAWINGS AND IN FIELD OBSERVATION REPORTS BY 14 68
ALL ERECTION FRAMING NECESSARY TO COMPLY WITH OSHA.
THE ENGINEER AS ADDED PER GENERAL NOTES. AN UP-TO-DATE TOTAL OF LINEAR FEET Technology
7B. REFER TO DETAILS FOR MINIMUM CONNECTIONS AND OTHER REQUIREMENTS. DEVELOP 12 97
ADDED WILL BE MAINTAINED AND SUBSTANTIATED BY SHOP DRAWINGS AND FIELD OBSERVATION
6. CONSTRUCTION ENGINEERING: FORCES NOTED. DO NOT IMPOSE FORCES ON THE BUILDING STRUCTURE IN DIRECTIONS OR AT Rimrock Group
REPORTS. NOTES: 10807 New Allegiance Drive, Suite 400
6A. THE STRUCTURE DEFINED ON THE CONTRACT DOCUMENTS HAS BEEN DESIGNED ONLY FOR LOCATIONS OTHER THAN THAT SHOWN ON THE STRUCTURAL DRAWINGS. DO NOT IMPOSE FORCES Colorado Springs, CO 80921
LOADS ANTICIPATED ON THE STRUCTURE DURING ITS SERVICE LIFE. PROVIDE ALL REQUIRED LARGER THAN SPECIFIED. CONNECTIONS TO CONCRETE SHALL NOT USE PAFs TO RESIST TENSION * 1 MIL = 1/1000" 719-533-1112
4. STRUCTURAL CONCRETE MIX REQUIREMENTS:
ENGINEERING AND OTHER MEASURES TO ACHIEVE THE MEANS, METHODS, AND SEQUENCES OF LOADS.
4A. SEE CONCRETE MIX TABLE
WORK. SUCH ENGINEERING MAY INCLUDE, BUT IS NOT LIMITED TO: CONCRETE MIX TABLE NOTES:
- LAYOUT Building Performance Engineer
5. SLABS:
- DESIGN FOR FORMWORK PROPORTIONS OF MATERIALS IN CONCRETE MIX SHALL BE ESTABLISHED BY CONTRACTOR Ambient Energy
5A. VERIFY ALKALINITY OF CONCRETE SURFACE, SLAB VAPOR TRANSMISSION, AND SLAB
- DESIGN OF CONCRETE MIXES TO: 130 W 5th Ave
FLATNESS/LEVELNESS ARE COMPATIBLE WITH FLOORING SYSTEM AND ADHESIVES PRIOR TO Denver, CO 80204
- ERECTION PROCEDURES WHICH ADDRESS STABILITY OF THE FRAME DURING CONSTRUCTION - PROVIDE THE MINIMUM COMPRESSIVE STRENGTH AS INDICATED IN THE MIX TABLE. DO NOT
INSTALLING FLOORING. 303-278-1532
- WELD PROCEDURES EXCEED THE MAXIMUM WATER-CEMENT RATIO NOTED.
- DESIGN OF TEMPORARY BRACING OF WALLS FOR WIND, SEISMIC, OR SOIL LOADS - PROVIDE WORKABILITY AND CONSISTENCY TO PERMIT CONCRETE TO BE WORKED READILY
5B. TAKE PRECAUTIONS TO MINIMIZE SLAB CURLING. GRIND SLAB OR USE LEVELING COMPOUND
- SURVEYING TO VERIFY CONSTRUCTION TOLERANCES INTO FORMS AND AROUND REINFORCEMENT UNDER CONDITIONS OF PLACEMENT TO BE Cost Estimating
IF FLOOR FLATNESS AND LEVELNESS VALUES ARE NOT ACCEPTABLE TO THE ARCHITECT.
- EVALUATION OF TEMPORARY CONSTRUCTION LOADS ON STRUCTURE DUE TO EQUIPMENT EMPLOYED, WITHOUT SEGREGATION OR EXCESSIVE BLEEDING. CONTRACTOR SHALL SELECT Parametrix, Inc.
AND MATERIALS APPROPRIATE SLUMP. USE ADMIXTURES AS REQUIRED TO OBTAIN DESIRED RESULTS. 7186 South Highland Drive
6. NON-SHRINK GROUT:
- STRUCTURAL ENGINEERING TO RESIST ANY OTHER LOADS NOT IDENTIFIED ON DESIGN Salt Lake City, UT 84121
6A. CONFORM TO ASTM C1107, GRADES B, OR C. 801-733-5900
DRAWINGS USE TYPE I / II PORTLAND CEMENT UNLESS NOTED OTHERWISE. FOR CONCRETE MIXES USED
6B. ACHIEVE 8000 PSI COMPRESSIVE STRENGTH AT 28 DAYS. ON FLOORS MINIMUM CEMENTITIOUS CONTENT SHALL BE 540 POUNDS PER CUBIC YARD
7. COORDINATION:
7A. STRUCTURAL DRAWINGS ARE NOT STAND-ALONE DOCUMENTS AND ARE INTENDED TO BE FOR CONCRETE PLACED BY PUMPING PROVIDE CONCRETE MIX FLOWABILITY TO FACILITATE
7. PLACING REINFORCEMENT:
USED IN CONJUNCTION WITH CIVIL, ARCHITECTURAL, MECHANICAL, ELECTRICAL, AND DRAWINGS PUMPING. ENTRAINED AIR MAY BE USED TO FACILITATE PUMPING SUBJECT TO THE
7A. REINFORCEMENT PROTECTION:
FROM OTHER DISCIPLINES. THE CONTRACTOR SHALL COORDINATE ALL REQUIREMENTS OF THE PROVISIONS OF NOTE b BELOW.
- SEE CONCRETE COVER TABLE ON S-300
CONTRACT DOCUMENTS INTO SHOP DRAWINGS AND WORK.
- SEE ACI 318-08 7.5 FOR REINFORCEMENT PLACING TOLERANCES AND ACI 117 FOR
ADDITIONAL REQUIREMENTS a. FOR THE MAXIMUM COARSE AGGREGATE SIZE INDICATED, USE THE FOLLOWING
7B. COORDINATE DIMENSIONS OF ALL OPENINGS, BLOCKOUTS, DEPRESSIONS, ETC., WITH AGGREGATE SIZE NUMBERS PER ASTM C33:
ARCHITECTURAL DRAWINGS, DRAWINGS FROM OTHER DISCIPLINES, AND FIELD CONDITIONS 3/4: #67 AGGREGATE
7B. PROVIDE ACCESSORIES NECESSARY TO PROPERLY SUPPORT REINFORCING AND WELDED
PRIOR TO SHOP DRAWING SUBMITTAL. 1: #57 AGGREGATE
WIRE REINFORCING AT POSITIONS SHOWN ON PLANS. ALL REINFORCING, DOWELS, BOLTS, AND
EMBEDDED PLATES SHALL BE SET AND TIED IN PLACE BEFORE THE CONCRETE IS POURED.
7C. SEE ARCHITECTURAL PLANS FOR INTERIOR PARTITIONS. PARTITION FRAMING SHALL BE b. WHERE AIR CONTENT IS INDICATED IN THE MIX TABLE, PROVIDE AIR ENTRAINING
STABBING INTO PREVIOUSLY PLACED CONCRETE IS NOT PERMITTED.
CONNECTED TO THE PRIMARY STRUCTURE IN SUCH A WAY SO AS TO ALLOW FOR VERTICAL LIVE ADMIXTURE. TOTAL AIR CONTENT LIMITS INCLUDE BOTH ENTRAINED AND ENTRAPPED AIR +/-
LOAD DEFLECTIONS OF SPAN/360 OF THE FLOOR FRAMING. DO NOT MAKE RIGID VERTICAL AND 1 1/2%. NP IN COLUMN INDICATES ADDITION OF ENTRAINED AIR IS NOT PERMITTED EXCEPT
8. CONSTRUCTION/CONTROL JOINTS:
HORIZONTAL CONNECTIONS TO THE PRIMARY STRUCTURE IN THE PLANE OF THE PARTITION. WHERE CONTRACTOR CAN DEMONSTRATE THAT SLABS WITH ENTRAINED AIR WILL HAVE A
8A. SUBMIT DRAWINGS SHOWING CONSTRUCTION AND CONTROL JOINT LOCATIONS ALONG WITH Issue Date
THE SEQUENCE OF POURS. CONSTRUCTION JOINT LOCATIONS AND CASTING SEQUENCE SHALL FINISH ACCEPTABLE TO THE ARCHITECT WITHOUT BLISTERS. AIR CONTENT NOTED IS BASED
BE ARRANGED TO MINIMIZE THE EFFECTS OF ELASTIC AND LONG-TERM ON 3/4" AGGREGATE. IF 3/8 AGGREGATE IS USED, INCREASE AIR CONTENT BY 1 1/2%. DESIGN DEVELOPMENT SEPTEMBER 12, 2012
SHORTENING/SHRINKAGE. BP#2 NOVEMBER 16, 2012
BP c. ABBREVIATIONS FOR OTHER REQUIREMENTS AS FOLLOWS: BP#3 DECEMBER 21, 2012
8B. CONSTRUCTION JOINTS IN SLABS-ON-GRADE AND SLABS ON DECK SHALL BE LOCATED TO 003 RECORD DRAWINGS APRIL 18, 2014
ACCOMMODATE THE MAXIMUM LENGTH AND AREA THE CONTRACTOR CAN REASONABLY POUR, MSS = MAXIMUM SHRINKAGE STRAIN LIMITED, RE: SPECS.
DATE PRINTED: 4/18/2014 9:09:24 AM

FINISH, AND JOINT IN THE SAME DAY, BUT SHALL NOT EXCEED 150 FEET WITH A MAXIMUM AREA SVT = CONTRACTOR SHALL PROVIDE CONCRETE WITH REDUCED WATER OR WITH SPECIAL
OF 15,000 SQUARE FEET UNLESS APPROVED BY THE ENGINEER. DO NOT PLACE CONTROL JOINTS ADMIXTURES AS REQUIRED IN ORDER TO ACHIEVE THE SLAB VAPOR TRANSMISSION
IN SLABS ON METAL DECK. REQUIRED FOR THE SPECIFIED FLOORING MATERIALS
MCI = MAXIMUM CHLORIDE ION LIMITS 0.15 FOR CONCRETE EXPOSED TO CHLORIDES IN USE.
9. MEP AND OTHER OPENINGS AND EMBEDMENTS: DP = PROVIDE 5 1/2" MINIMUM SLUMP. FOR DRILLED PIERS CASED DURING CONSTRUCTION
9A. PROVIDE SLEEVES AT OPENINGS (SUCH AS THOSE REQUIRED FOR PLUMBING AND PROVIDE CONCRETE MIX WITH FLOWABILITY TO PREVENT ARCHING WHEN CASING IS
ELECTRICAL PENETRATIONS) BEFORE PLACING CONCRETE. REMOVE METAL DECK AT SLEEVES PULLED. ENTRAINED AIR MAY BE USED TO FACILITATE CASING REMOVAL.
DESIGNERS: KH/AM

AFTER CONCRETE HAS CURED. DO NOT CUT REINFORCING WHICH MAY CONFLICT. CORING OF
CONCRETE IS NOT PERMITTED.

9B. REFER TO TYPICAL DETAILS FOR SPACING LIMITS ON SLEEVES AND FOR REQUIREMENTS FOR
EMBEDDED CONDUIT AND PIPE. EMBEDDED CONDUIT IS NOT PERMITTED IN SLABS ON METAL Project Number: 2011101.00
DECK.
Drawn By: KH/AM

Reviewed By: KH
REINFORCING MATERIAL TABLE
Approved By: PD
REINF ELEMENT ASTM Fy (KSI) Fu (KSI) COMMENTS
TYP REINFORCING A615 60 90 --
WELDED & FIELD BENT REINF A706 60 80 --
PROJECT MANAGER: KH

WELDED WIRE REINFORCING, SMOOTH A185 65 75 --


MM JOB #: 23616.S.01

NOTES
PRINCIPAL: PD
EOR: PD

S-002
C:\Proj\2011101_structural_kevinh.rvt
POST-INSTALLED ANCHORS/REINFORCING STEEL SPECIAL INSPECTIONS STRUCTURAL CONCRETE SPECIAL INSPECTIONS QUALITY ASSURANCE GENERAL NOTES
ITEM FREQUENCY STANDARD CRITERIA ITEM FREQUENCY STANDARD CRITERIA
EXPANSION ANCHORS, SLEEVE
STATEMENT OF STRUCTURAL SPECIAL INSPECTIONS AND TESTING
REINFORCING STEEL
ANCHORS, SCREW ANCHORS - DURING PLACEMENT P ACI 318 3.5,7.1-7.7 VERIFY GRADE, FINISH, SIZE, BAR QUANTITY, 1. GENERAL:
- PRIOR TO START OF WORK -- ICC-ES REPORT REVIEW CONTRACTOR'S INSTALLATION LOCATION, SPACING, COVER, HOOK LENGTHS, 1A. SCOPE OF WORK
PROCEDURE. SPLICE LENGTH, SPLICE LOCATIONS, BEND - THE OWNER WILL ENGAGE A QUALIFIED INSPECTION AND TESTING AGENCY(S) TO PERFORM SPECIAL
- PRIOR TO PLACEMENT OF 100%
DIAMETERS, COATING, SURFACE CONDITION, INSPECTIONS AND TESTING FOR ALL STRUCTURAL MEMBERS AND ASSEMBLIES AS NOTED HEREIN.
- PRIOR TO INSTALLATION OF EACH ICC-ES REPORT VERIFY TYPE, DIAMETER, LENGTH, FINISH, AND CONCRETE AND SUPPORT. - SPECIAL INSPECTIONS ARE IN ADDITION TO INSPECTIONS BY THE AUTHORITY HAVING JURISDICTION REQUIRED
ANCHOR ANCHOR BASE MATERIAL. VERIFY MAXIMUM IMPACT BY IBC 2009 SECTION 110.
WRENCH TORQUE RATING FOR SCREW - REFER TO THE SPECIFICATIONS FOR REPORTING AND PROCEDURAL REQUIREMENTS FOR QUALITY ASSURANCE
ANCHORS. - WELDING C AWS D1.4 VERIFY ASTM A706 REINFORCING STEEL.
AND QUALITY CONTROL.
- FIELD BENDING P ACI 301 3.3.2.8 -- - REFER TO ARCH/MECH/ELEC/CIVIL SPECIFICATIONS AND DRAWINGS FOR ADDITIONAL SPECIAL INSPECTION AND
- DURING INSTALLATION OF C ICC-ES REPORT CONTINUOUS INSPECTION REQUIRED
- COATED REINFORCING P ACI 301 3.2.1.2 -- TESTING THAT MAY BE REQUIRED.
ANCHOR REGARDLESS IF PERIODIC INSPECTION IS
PERMITTED BY ICC-ES REPORT. VERIFY HOLE - MECHANICAL CONNECTORS C ICC-ES REPORT -- - SPECIAL INSPECTIONS AND TESTING ARE APPLICABLE TO ALL REVISIONS AND/OR FUTURE WORK ADDED BY
AMENDMENTS TO THESE DOCUMENTS.
DIMENSIONS, HOLE CLEANING, ANCHOR The Lane Center for
EMBEDMENT, EDGE DISTANCES AND SPACING. BOLTS AND EMBEDMENTS 1B. DEFINITIONS Academic Health
- PRIOR TO PLACEMENT OF 100% -- VERIFY TYPE, FINISH, DIAMETER, LENGTH, - SPECIAL INSPECTOR: THE AGENCY ENGAGED BY THE OWNER AND APPROVED BY THE AUTHORITY HAVING
- AFTER INSTALLATION OF 100% VISUAL -- VERIFY NUMBER, EDGE DISTANCES, AND ANCHOR CONCRETE QUANTITY, EMBEDMENT LENGTH, SPACING AND JURISDICTION TO ACT AS THE DESIGNATED REPRESENTATIVE TO PERFORM INSPECTIONS.
Sciences
ATTACHED ASSEMBLY FLUSH WITH AND PERPENDICULAR TO THE EDGE DISTANCES. VERIFY USE OF PLACING - SPECIAL INSPECTION: INSPECTION PERFORMED BY THE SPECIAL INSPECTOR ACCORDING TO IBC 2009 SECTION University of Colorado at
RECEIVING SURFACE. TEMPLATE. 1704 TO ENSURE COMPLIANCE WITH APPROVED CONSTRUCTION DOCUMENTS AND REFERENCED STANDARDS. Colorado Springs
- (P) PERIODIC INSPECTION: THE PART-TIME OR INTERMITTENT OBSERVATION BY THE SPECIAL INSPECTOR OF 2011101.00
ADHESIVE ANCHORS,
- WELDING -- -- INSPECT PER THE STRUCTURAL STEEL TABLE WORK BEING PERFORMED. SPECIAL INSPECTOR SHALL BE PRESENT IN THE AREA WHERE THE WORK IS BEING
REINFORCING STEEL ANCHORED
INTO HARDENED CONCRETE CONCRETE PERFORMED. OBSERVATION OF ALL WORK (100% VISUAL) SHALL BE MADE AT THE COMPLETION OF THE WORK.
-- - (C) CONTINUOUS INSPECTION: THE FULL-TIME OBSERVATION BY THE SPECIAL INSPECTOR OF WORK BEING
- MIX DESIGN EACH VERIFY USE OF APPROVED DESIGN MIXTURE FOR Owner
- PRIOR TO START OF WORK -- ICC-ES REPORT REVIEW CONTRACTOR'S INSTALLATION PERFORMED. SPECIAL INSPECTOR SHALL BE PRESENT IN THE AREA WHERE THE WORK IS BEING PERFORMED.
TRUCK EACH TRUCK LOAD
PROCEDURE. OBSERVATION OF ALL WORK (100% VISUAL) SHALL BE MADE AT THE COMPLETION OF THE WORK. Facilities Services
- FORMWORK PRIOR TO P ACI 318 6.1.1 INSPECT FIRST POUR OF EACH TYPE (GRADE University of Colorado at Colorado Springs
- PRIOR TO INSTALLATION OF EACH ICC-ES REPORT VERIFY TYPE, DIAMETER, LENGTH, FINISH, AND PLACEMENT OF CONCRETE BEAM, MAT, WALLS, SLAB, SLAB-ON-DECK, ETC.) 1C. DEFICIENCIES IN WORK
Campus Services Building, Rm 212
1420 Austin Bluffs Parkway
ANCHOR ANCHOR BASE MATERIAL. - CORRECT DEFICIENCIES IN WORK THAT TESTS AND INSPECTIONS INDICATE DO NOT COMPLY WITH THE Colorado Springs, CO 80918
CONTRACT DOCUMENTS AND REFERENCED STANDARDS. 719-255-3505
- DURING INSTALLATION OF C ICC-ES REPORT CONTINUOUS INSPECTION REQUIRED - PLACEMENT OF CONCRETE C ACI 318 5.9-5.10 - ALL COST OF ADDITIONAL TESTING AND/OR INSPECTIONS FOR CORRECTIVE WORK SHALL BE BORNE BY THE
ANCHOR REGARDLESS IF PERIODIC INSPECTION IS ACI 318 5.11-5.13 CONTRACTOR.
- CURING P
PERMITTED BY ICC-ES REPORT. VERIFY HOLE Architect
DIMENSIONS, HOLE CLEANING, ANCHOR 2. SHOP FABRICATIONS: AndersonMasonDale Architects, P.C.
EMBEDMENT, EDGE DISTANCES AND SPACING. 3198 Speer Boulevard
2A. GENERAL Denver, CO, 80211
- PERFORM INSPECTIONS AND TESTING FOR ALL SHOP FABRICATED STRUCTURAL MEMBERS AND ASSEMBLIES AS 303-294-9448
- AFTER INSTALLATION OF 100% VISUAL -- VERIFY NUMBER, EDGE DISTANCES, AND ANCHOR NOTED HEREIN. SPECIAL INSPECTOR SHALL PERFORM SPECIAL INSPECTIONS AND TESTING UNLESS THE
ATTACHED ASSEMBLY FLUSH WITH AND PERPENDICULAR TO THE FABRICATOR IS REGISTERED AND APPROVED BY THE AUTHORITY HAVING JURISDICTION TO PERFORM SUCH WORK
RECEIVING SURFACE. STRUCTURAL CONCRETE TESTING WITHOUT SPECIAL INSPECTION OR FABRICATOR HAS A CURRENT ICC-ES EVALUATION REPORT. Clinical Planning
ITEM FREQUENCY STANDARD CRITERIA - SPECIAL INSPECTOR SHALL VERIFY THE FABRICATOR MAINTAINS AND FOLLOWS DETAILED SHOP FABRICATION James W Nakai & Associates, PC
- CURE TIME 100% VISUAL -- VERIFY FULL CURE TIME HAS ELAPSED PRIOR TO AND QUALITY CONTROL PROCEDURES, UNLESS FABRICATOR IS REGISTERED AND APPROVED.
520 E Colorado Ave
REINFORCING STEEL, BOLTS Colorado Springs, CO 80903
APPLICATION OF TORQUE OR LOAD TO ANCHOR. - AT THE COMPLETION OF FABRICATION, THE APPROVED FABRICATOR SHALL SUBMIT A CERTIFICATE OF
AND EMBEDMENTS 719-635-2142
COMPLIANCE TO THE AUTHORITY HAVING JURISDICTION ACCORDING TO IBC 2009 SECTION 1704.2.2.
- WELDING -- -- PER STRUCTURAL STEEL TESTING - APPROVED FABRICATORS MAY PERFORM TESTING NOTED HEREIN EXCEPT THAT NONDESTRUCTIVE TESTING
CONCRETE (NDT) SHALL ONLY BE PERFORMED BY PERSONNEL WITH QUALIFICATIONS THAT MEET OR EXCEED THE CRITERIA OF Civil
- COMPOSITE SAMPLE ASTM C172 OBTAIN AT POINT OF PLACEMENT. FOR DRILLED AWS D1.1 SUBCLAUSE 6.14.6 AND AMERICAN SOCIETY FOR NONDESTRUCTIVE TESTING (ASNT) SNT-TC-1A OR ASNT TerraNova Engineering, Inc.
815 S 25th Street
1. f'c < 5000 PSI 100 CY/MIX/DAY PIERS OBTAIN NEAR BEGINNING OF LOAD PRIOR CP-189. Colorado Springs, CO 80904
TO PLACEMENT IN SHAFT. ADJUST FREQUENCY 719-635-6422
AS REQUIRED TO PROVIDE MINIMUM 5 TOTAL 2B. SHOP FABRICATIONS INCLUDED
2. DRILLED PIERS EACH SHAFT - SHOP FABRICATED STRUCTURAL STEEL INCLUDING STAIRS AND RAILING ELEMENTS
TESTS PER MIX BUT NOT MORE THAN ONE
SAMPLE PER TRUCK LOAD. - SHOP FABRICATED COLD FORMED STEEL ELEMENTS Landscape
POST-INSTALLED ANCHORS/REINFORCING STEEL TESTING - SLUMP EACH ASTM C143 SPECIFIED SLUMP SHALL BE AS SUMBITTED IN
Lime Green Design, Inc
900 E. Louisiana Avenue, Suite 209
ITEM FREQUENCY STANDARD CRITERIA COMPOSITE THE MIX DESIGN 1 1/2". PERFORM ADDITIONAL Denver, CO 80210
SAMPLE TESTS WHEN CONCRETE CONSISTENCY 303-733-7558
EXPANSION ANCHORS, SLEEVE
APPEARS TO CHANGE.
ANCHORS, SCREW ANCHORS
- AIR CONTENT WHEN AIR EACH ASTM C231 PRESSURE --
SOILS SPECIAL INSPECTIONS Structural
- TORQUE TEST 100% -- TEST ANCHOR WITH CALIBRATED TORQUE ITEM FREQUENCY STANDARD CRITERIA
ENTRAINMENT IS SPECIFIED COMPOSITE METHOD Martin/Martin
WRENCH TO 100% OF THE INSTALLATION
TORQUE NOTED IN ICC-ES REPORT. ATTAIN SAMPLE SUBGRADE 12499 West Colfax Avenue
Lakewood, CO 80215
SPECIFIED TORQUE WITHIN 1/2 TURN OF THE - TEMPERATURE EACH ASTM C1064 REQUIRED WHEN AIR TEMPERATURE IS 40 F - EXCAVATION P -- VERIFY EXCAVATIONS ARE EXTENDED TO 303-431-6100
NUT. COMPOSITE AND BELOW OR 80F AND ABOVE. THE PROPER DEPTH AND HAVE REACHED
ADHESIVE ANCHORS, SAMPLE AND 60 THE PROPER BEARING MATERIAL
REINFORCING STEEL ANCHORED Mechanical/Plumbing
MINUTE
INTO HARDENED CONCRETE - BEARING MATERIAL P SOILS REPORT VERIFY BEARING MATERIAL IS ADEQUATE TO Shaffer Baucom Engineering & Consulting
INTERVALS
ACHIEVE THE DESIGN BEARING CAPACITY 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
- TENSION TEST FIRST 3 AND 1% ASTM E488 TEST THE INSTALLATION OF THE FIRST 3 OF EACH - COLD WEATHER CURING -- ASTM C1074 RECORD MAXIMUM AND MINIMUM CONCRETE 303-986-8200
CONTROLLED FILL
OF REMAINING STATIC TENSION TYPE, BASE MATERIAL, AND POSITION (DOWN, TEMPERATURE DURING CURING PERIOD, WHEN
HORIZONTAL, OVERHEAD). OBSERVE ASTM E488 DAILY AVERAGE AIR TEMPERATURE OF 40 F OR - PRIOR TO PLACEMENT P -- VERIFY SUBGRADE HAS BEEN PROPERLY
MINIMUM EDGE DISTANCES FOR DETERMINING BELOW IS EXPECTED FOR 3 SUCCESSIVE DAYS PREPARED Electrical
TEST LOCATIONS. SUBMIT PROPOSED TEST DURING CURING PERIOD. - PLACEMENT C -- VERIFY USE OF PROPER MATERIALS, DENSITIES, Shaffer Baucom Engineering & Consulting
LOCATIONS AND REQUESTS FOR REQUIRED - COMPRESSIVE STRENGTH EACH ASTM C31 (6x12 TEST ONE CYLINDER SPECIMEN AT 7 DAYS AND COMPACTION, AND LIFT THICKNESSES 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
TENSION TEST LOAD VALUES TO ENGINEER. COMPOSITE SPECIMENS) TWO CYLINDER SPECIMENS AT 28 DAYS. IF 303-986-8200
SAMPLE AND ASTM C39 DESIGN STRENGTH IS NOT ACHIEVED AT 28 SOILS SPECIAL INSPECTION NOTES:
DAYS, TEST REMAINING CYLINDER AT 56 DAYS. 1. SEE CIVIL DRAWINGS AND/OR SPECIFICATIONS FOR ADDITIONAL EARTHWORK AND UTILITY INSPECTION REQUIREMENTS.
ACCEPTANCE CRITERIA PER ACI 318. 2. SEE CIVIL DRAWINGS AND/OR SPECIFICATIONS FOR CLASSIFICATION AND TESTING REQUIREMENTS FOR COMPACTED FILL Technology
AND/OR CONTROLLED LOW-STRENGTH MATERIAL. Rimrock Group
MEASURE CONCRETE FLOOR -- ASTM E1155 PERFORM MEASUREMENTS WITHIN 48 HOURS
10807 New Allegiance Drive, Suite 400
FLATNESS (FF) AND FLOOR OF FINISHING OPERATIONS AND PRIOR TO Colorado Springs, CO 80921
LEVELNESS (FL) REMOVAL OF SHORES OR FORMS. MEASURE 719-533-1112
AREAS INDICATED IN THE SPECIFICATIONS. DRILLED PIER FOUNDATIONS SPECIAL INSPECTIONS
ITEM FREQUENCY STANDARD CRITERIA Building Performance Engineer
STRUCTURAL CONCRETE TESTING NOTES: DURING DRILLING Ambient Energy
1. NONDESTRUCTIVE TESTING MAY BE PERMITTED BY THE ARCHITECT, BUT WILL NOT BE USED AS SOLE BASIS FOR - DRILLING OPERATIONS C -- PROVIDE REPORT FOR EACH DRILLED PIER. 130 W 5th Ave
APPROVAL OR REJECTION OF DEFICIENT CONCRETE. Denver, CO 80204
303-278-1532
2. REPORTS OF COMPRESSIVE STRENGTH TESTS SHALL CONTAIN THE FOLLOWING INFORMATION: DATE OF CONCRETE
PLACEMENT, LOCATION OF CONCRETE BATCH IN WORK, DESIGN 28-DAY COMPRESSIVE STRENGTH, CONCRETE SUPPLIER - SHAFT PLACEMENT C -- VERIFY LOCATION, PLUMBNESS, AND
AND MIXTURE ID NUMBER, TIME OF BATCH AND PLACEMENT, AMBIENT AIR TEMPERATURE, SITE ADDED WATER AND DIAMETER.
Cost Estimating
ADMIXTURES, UNIT WEIGHT, AND AS REQUIRED BY ASTM C39. - BEARING MATERIAL C SOILS REPORT VERIFY BEARING MATERIAL IS ADEQUATE TO Parametrix, Inc.
ACHIEVE THE DESIGN BEARING CAPACITY. 7186 South Highland Drive
Salt Lake City, UT 84121
- DEPTH OF PENETRATION C -- VERIFY DEPTH OF PENETRATION INTO BEARING 801-733-5900
MATERIAL AND OVERALL LENGTH.
CONCRETE AND REINFORCING -- -- INSPECT PER THE STRUCTURAL CONCRETE
STEEL SPECIAL INSPECTIONS AND TESTING TABLES.
RECORD CONCRETE VOLUMES.

Issue Date

BP#2 NOVEMBER 16, 2012


BP#3 DECEMBER 21, 2012
RECORD DRAWINGS APRIL 18, 2014
DATE PRINTED: 4/18/2014 9:09:25 AM
DESIGNERS: KH/AM

Project Number: 2011101.00

Drawn By: KH/AM

Reviewed By: KH

Approved By: PD
PROJECT MANAGER: KH
MM JOB #: 23616.S.01

QUALITY ASSURANCE
PRINCIPAL: PD
EOR: PD

S-003
C:\Proj\2011101_structural_kevinh.rvt

STRUCTURAL METAL DECKING SPECIAL INSPECTIONS STRUCTURAL COLD FORMED STEEL SPECIAL INSPECTIONS STRUCTURAL STEEL SPECIAL INSPECTIONS
ITEM FREQUENCY STANDARD CRITERIA ITEM FREQUENCY STANDARD CRITERIA ITEM FREQUENCY STANDARD CRITERIA
METAL DECK FRAMING PRIOR TO START OF WORK
- METAL DECK P -- VERIFY TYPE, GAGE, AND LOCATION - MEMBERS AND CONNECTIONS P -- VERIFY TYPE, SIZE, LOCATION, SPACING - PRIOR TO FABRICATION OR -- -- VERIFY PLATES AND SHAPES CONFORM TO
- ATTACHMENT P -- VERIFY ATTACHMENT TYPE, SIZE, SPACING, - BRIDGING AND BLOCKING P -- VERIFY TYPE, LOCATION, AND ATTACHMENT ERECTION ASTM STANDARDS SPECIFIED, REVIEW
AND EDGE DISTANCES MANUFACTURER'S CERTIFIED MILL TEST
- FIELD CUTS AND NOTCHES P -- NO CUTS OR NOTCHES THROUGH SECTION REPORTS OR CERTIFICATE OF COMPLIANCE
- FIELD CUTS AND NOTCHES P -- VERIFY CUTS OR NOTCHES THROUGH SECTION FLANGES PERMITTED.
ARE REPAIRED. - SPLICING P -- NO SPLICING OF STRUCTURAL MEMBERS - PRIOR TO BOLTING -- AISC 360 / VERIFY BOLT ASSEMBLY CONFORMS TO ASTM
PERMITTED UNLESS SPECIFIED ON THE RCSC SPECIFICATION STANDARDS SPECIFIED, REVIEW CERTIFICATE OF
WELDED ATTACHMENTS COMPLIANCE, OBSERVE PRE-INSTALLATION
AWS D1.1/D1.3 CONSTRUCTION DOCUMENTS.
- PRIOR TO WELDING -- VERIFY FILLER MATERIALS, WELDING VERIFICATION TESTING OF PRETENSIONED
PROCEDURES, WELDER QUALIFICATIONS, AND - PUNCHOUTS P -- VERIFY SPACING REQUIREMENTS FROM FASTENER ASSEMBLIES, VERIFY APPROPRIATE
MANUFACTURER'S CERTIFICATE OF COMPLIANCE BEARINGS AND CONNECTIONS AND REINFORCING FAYING SURFACE CONDITION
IS USED WHERE REQUIRED - PRIOR TO WELDING -- AWS D1.1 / VERIFY MATERIALS, PROCEDURES, WELDER
The Lane Center for
- DURING WELDING P AWS D1.3 --
100% VISUAL AWS D1.3 VERIFY ALL SPECIFIED WELDS HAVE BEEN MADE.
AISC 360 QUALIFICATIONS, AND REVIEW CERTIFICATES Academic Health
- AFTER WELDING WELDED ATTACHMENTS OF COMPLIANCE Sciences
VERIFY SIZE, SPACING AND QUALITY. - PRIOR TO WELDING -- AWS D1.1/D1.3 VERIFY FILLER MATERIALS, WELDING
- CORROSION RESISTANCE P -- WELDED AREAS ARE TO BE TREATED WITH PROCEDURES, WELDER QUALIFICATIONS, AND FRAMING University of Colorado at
TREATMENT APPROVED TREATMENT TO MATCH CORROSION MANUFACTURER'S CERTIFICATE OF COMPLIANCE Colorado Springs
- DURING ERECTION P -- VERIFY INSTALLATION OF BRACING AND
RESISTANCE OF EFFECTED AREA STIFFENING, MEMBER LOCATIONS, AND 2011101.00
- DURING WELDING P AWS D1.3 --
CONNECTIONS. REPORT ANY OBSERVATION OF
SCREWED ATTACHMENTS - AFTER WELDING 100% VISUAL AWS D1.3 -- KINKS, BENDS, OR OTHER DAMAGE.
- FASTENER P -- VERIFY TYPE, DIAMETER, LENGTH, SPACING AND - CORROSION RESISTANCE P -- WELDED AREAS ARE TO BE TREATED WITH
EDGE DISTANCES TREATMENT APPROVED TREATMENT TO MATCH CORROSION DURING BOLTING Owner
RESISTANCE OF EFFECTED AREA Facilities Services
- SCREW PENETRATION P -- VERIFY MATERIALS HAVE BEEN DRAWN - SNUG-TIGHTENED JOINTS P AISC 360 / VERIFY CONNECTED MATERIALS HAVE BEEN University of Colorado at Colorado Springs
TOGETHER AND SCREWS ARE FULLY DRIVEN RCSC SPECIFICATION DRAWN TOGETHER AND PROPERLY SNUGGED. Campus Services Building, Rm 212
SCREWED ATTACHMENTS 1420 Austin Bluffs Parkway
WITH A MINIMUM PENETRATION OF 3 THREADS P AISC 360 / VERIFY PROPER USE OF PRETENSION METHOD,
- FASTENER P -- VERIFY TYPE, DIAMETER, LENGTH, SPACING AND - PRETENSIONED AND SLIP- Colorado Springs, CO 80918
THROUGH THE LAST MATERIAL JOINED. RCSC SPECIFICATION VERIFY CONNECTED MATERIALS HAVE BEEN 719-255-3505
EDGE DISTANCES CRITICAL JOINTS
DRAWN TOGETHER AND PROPERLY SNUGGED.
- DAMAGED SCREWS P -- NO POPPED SCREW HEADS OR STRIPPED SCREWS - SCREW PENETRATION P -- VERIFY MATERIALS HAVE BEEN DRAWN
ARE PERMITTED. ALL DAMAGED SCREWS SHALL TOGETHER AND SCREWS ARE FULLY DRIVEN - PRETENSIONED AND SLIP- C AISC 360 / VERIFY PROPER USE OF PRETENSION METHOD, Architect
BE REPLACED. WITH A MINIMUM PENETRATION OF 3 THREADS CRITICAL JOINTS USING RCSC SPECIFICATION VERIFY CONNECTED MATERIALS HAVE BEEN AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
THROUGH THE LAST MATERIAL JOINED. CALIBRATED WRENCH OR TURN- DRAWN TOGETHER AND PROPERLY SNUGGED. Denver, CO, 80211
OF-NUT METHOD WITHOUT VERIFY TIGHTNESS OF NUT FOR 10% OF BOLTS 303-294-9448
- DAMAGED SCREWS P -- NO POPPED SCREW HEADS OR STRIPPED SCREWS MATCHMARKING (2 MIN) AT EACH JOINT.
ARE PERMITTED. ALL DAMAGED SCREWS SHALL
BE REPLACED. DURING WELDING Clinical Planning
James W Nakai & Associates, PC
- COLD FORMED STEEL P ICC-ES REPORT VERIFY TYPE, NUMBER OF FASTENERS, AND - SINGLE PASS P AWS D1.1 -- 520 E Colorado Ave
ASSEMBLIES INSTALLATION IN CONFORMANCE WITH ICC-ES FILLET WELD < 5/16" Colorado Springs, CO 80903
719-635-2142
REPORT - SINGLE PASS FILLET WELD C AWS D1.1 --
> 5/16" AND MULTIPASS
POWER-ACTUATED FASTENERS Civil
FILLET WELD
- PRIOR TO INSTALLATION FIRST OF EACH ICC-ES REPORT VERIFY TYPE, DIAMETER, LENGTH, FINISH, AND TerraNova Engineering, Inc.
FASTENER TYPE BASE MATERIAL. - PARTIAL PENETRATION C AWS D1.1 -- 815 S 25th Street
AND BASE GROOVE WELD Colorado Springs, CO 80904
719-635-6422
MATERIAL
- COMPLETE PENETRATION C AWS D1.1 --
GROOVE WELD
- DURING INSTALLATION P ICC-ES REPORT -- Landscape
- AFTER INSTALLATION 100% VISUAL -- VERIFY MATERIALS HAVE BEEN DRAWN - SHEAR CONNECTOR, HEADED P AWS D1.1 VERIFY TYPE, SIZE, SPACING, AND LOCATIONS Lime Green Design, Inc
TOGETHER AND FASTENER HEAD STAND-OFF ANCHOR STUD (HAS) AND 900 E. Louisiana Avenue, Suite 209
IS ACCEPTABLE (FULLY DRIVEN). DEFORMED ANCHOR STUD (DAS) Denver, CO 80210
303-733-7558
AFTER WELDING
- SINGLE PASS 100% VISUAL AWS D1.1 -- Structural
FILLET WELD < 5/16" Martin/Martin
100% VISUAL AWS D1.1 ALSO VERIFY TYPE, SIZE, SPACING, AND 12499 West Colfax Avenue
- SHEAR CONNECTOR, HEADED Lakewood, CO 80215
ANCHOR STUD (HAS) AND LOCATIONS 303-431-6100
DEFORMED ANCHOR STUD (DAS)

Mechanical/Plumbing
STRUCTURAL STEEL INSPECTION NOTES:
DRIFTED SNOW LOAD DIAGRAM 1. IN TENSIONED JOINTS, WHEN SPLINES ARE NOT SHEARED OR INDICATOR WASHERS ARE NOT PROPERLY DEFORMED, THE
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
TESTING AGENCY SHALL DETERMINE THAT PROPER BOLT TENSION HAS BEEN ACHIEVED BY THE APPLICATION OF A Lakewood, CO 80235
303-986-8200
PROPERLY CALIBRATED TESTING TORQUE OR THE CONTRACTOR MAY REMOVE AND REPLACE ALL DEFICIENT BOLTS. ALL
COST OF ADDITIONAL INSPECTION SHALL BE BORNE BY THE CONTRACTOR.
Electrical
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200
STRUCTURAL STEEL TESTING
9 8 76.9 6 5.9 5 4.9 4 3.9 3 2.62.4 21.9 1.5 1 ITEM FREQUENCY STANDARD CRITERIA/REMARKS
Technology
WELDING
Rimrock Group
- FILLET WELD 10% ASTM E709 NOT REQUIRED FOR SHOP WELDS 10807 New Allegiance Drive, Suite 400
MAGNETIC PARTICLE PERFORMED BY AN APPROVED FABRICATOR Colorado Springs, CO 80921
719-533-1112
- PARTIAL PENETRATION 100% ULTRASONIC OR NOT REQUIRED FOR SHOP WELDS
GROOVE WELD RADIO GRAPHIC PERFORMED BY AN APPROVED FABRICATOR
Building Performance Engineer
- COMPLETE PENETRATION 100% ULTRASONIC OR --
Ambient Energy
GROOVE WELD RADIO GRAPHIC 130 W 5th Ave
Denver, CO 80204
A - SHEAR CONNECTOR, HEADED 1% BEND TEST, AWS D1.1 BEND TEST: PER AWS D1.1 BENT STUD (TORQUE
303-278-1532

ANCHOR STUD (HAS), DEFORMED 100% RING TEST SECTION 7 TEST FOR THREADED STUDS) ACCEPTANCE
D4 B.1 ANCHOR STUD (DAS), THREADED CRITERIA. Cost Estimating
A.6 B.2 STUDS RING TEST: STRIKE WITH HAMMER, IF THE STUD Parametrix, Inc.
RINGS, STUD IS ACCEPTABLE. IF STUD DOES NOT 7186 South Highland Drive
B.5 B RING, PERFORM AWS D1.1 BEND TEST. Salt Lake City, UT 84121
801-733-5900
FRAMING
B.4 B.8 - THERMAL CUTTING OF SHAPES 100% ASTM E709 MAGNETIC ANY CRACK REGARDLESS OF SIZE OR LOCATION
D4 AND PLATES EXCEEDING 2 PARTICLE SHALL CAUSE WELD TO BE REJECTED.
D3 C.1 INCHES THICK
D3
- SHAPES EXCEEDING 1 1/2 100% ASTM A898 (LEVEL 1 CRITERIA TO BE MET 6 INCHES ABOVE AND
C.3 C INCHES THICK SUBJECT TO CRITERIA) BELOW EACH WELD, OR SHALL BE CAUSE
D1 D1 THROUGH-THICKNESS WELD FOR REJECTION.
C.6 SHRINKAGE STRAINS
D4
- PLATES EXCEEDING 1 1/2 100% ASTM A435 ANY DISCONTINUITY CAUSING A TOTAL LOSS
INCHES THICK SUBJECT TO OF BACK REFLECTION THAT CANNOT BE
THROUGH-THICKNESS WELD CONTAINED WITHIN A CIRCLE 3 INCHES IN
D
D.1
SHRINKAGE STRAINS DIAMETER SHALL BE REJECTED.

- EMBEDDED PLATE ASSEMBLIES 100% ULTRASONIC TEST ALONG CENTERLINE OF PLATE WIDTH Issue Date
WITH PLATES EXCEEDING 3/4 AFTER STUD/REBAR SHOP WELDING.
E INCH BP#2 NOVEMBER 16, 2012
BP#3 DECEMBER 21, 2012
D2 D5 RECORD DRAWINGS APRIL 18, 2014
TYP AT PARAPETS STRUCTURAL STEEL TESTING NOTES:
1. THE WELDING INSPECTOR SHALL HAVE THE AUTHORITY TO REJECT WELDMENTS. SUCH REJECTION MAY BE BASED ON
DATE PRINTED: 4/18/2014 9:09:26 AM

VISUAL INSPECTION WHERE IN THE INSPECTOR'S OPINION THE WELDMENT WOULD NOT PASS A MORE DETAILED INVESTIGATION.
2. IF DEFICIENT WELDS ARE DISCOVERED, THE REMAINING UNINSPECTED WELDS SHALL RECEIVE SUCH ULTRASONIC OR
MAGNETIC PARTICLE TESTING AS MAY BE REQUIRED BY THE ARCHITECT AND ENGINEER. ALL COST OF ADDITIONAL TESTING
SHALL BE BORNE BY THE CONTRACTOR.
3. REPORTS OF WELD TESTS SHALL CONTAIN THE FOLLOWING INFORMATION: DESCRIPTION OF EACH WELD, IDENTIFYING
MARK OF THE RESPONSIBLE WELDER, CRITIQUE OF DEFECTS NOTED BY VISUAL INSPECTION OR TESTING, STATEMENT OF
ACCEPTABILITY PER AWS STANDARDS.
W
DESIGNERS: KH/AM

DRIFT P W S
BP Project Number: 2011101.00
D1 003 94 PSF 17'-3" 22 PSF
Drawn By: KH/AM
D2 69 PSF 11'-4" 22 PSF
P

Reviewed By: KH
D3 82 PSF 14'-6" 22 PSF
Approved By: PD
D4 50 PSF 6'-9" 22 PSF
S

D5 39 PSF 8'-0" 22 PSF


PROJECT MANAGER: KH
MM JOB #: 23616.S.01

WHERE DRIFT WIDTH EXCEEDS FACE OF BUILDING QUALITY ASSURANCE


PRINCIPAL: PD

ROOF WIDTH, DRIFT IS


TRUNCATED AT EDGE OF ROOF
EOR: PD

S-004
C:\Proj\2011101_structural_kevinh.rvt

9 8 7 6.9 6 5.9 5 4.9 4 3.9 3 2.6 2.4 2 1.9 1.5 1

1'-11" 9'-9" 27'-0" 4'-0" 23'-0" 2'-8" 24'-4" 1'-4" 25'-8" 3'-8" 23'-4" 10'-6" 16'-4" 3'-2" 13'-4" 13'-8"

20
The Lane Center for
DP48B-14' Academic Health
11" 99'-0" Sciences
PD-3A University of Colorado at

2'-6"
Colorado Springs
2011101.00
5" PIER CL
DP48B-14'

11'-2"

FW2

6" PIER CL
S-220 11
99'-0" DP48B-14'
S-312 Owner
2 PD-3B 99'-0"

2'-0"
1'-8"
Facilities Services
FW1 PD-5 University of Colorado at Colorado Springs
Campus Services Building, Rm 212
DP48B-14' 1420 Austin Bluffs Parkway
99'-0" A Colorado Springs, CO 80918
RFC 047

1'-0"
1'-0"
719-255-3505
PD-3A

4"
1'-0" 2" SOUTH OF GRID
10
1'-8" 1'-2" 12'-5" 7 1/2" 2'-2" 1'-8" 3" SIM 1'-0" 1'-8"
S-312 Architect
BP

FW1
FW1
003 AndersonMasonDale Architects, P.C.
2'-1 1/2"
3 19
6 6 DP30A-10' B.1 3198 Speer Boulevard

21'-0"
DP48A-14' BP 1'-2 1/2"
S-210 S-311 Denver, CO, 80211
RFC 016 1'-0"
003 S-320 S-320 12 99'-0"
DP54-14' 11" 11" 11"

3'-7"

2'-6"
99'-0" 303-294-9448

2'-9"

2'-6"
RFC 018
1'-1"
2'-9"

S-312
PD-3A 99'-0" ADD PD-5 ADD
B/ WALL STEP DP48B-14'

4'-10" 2'-6"
PD-3A DP54-14' DP48B-14'
005 005 DP48A-14' B.2

1'-1"
1'-1"
BP 10
T/CAP 95'-0" 91'-0" Clinical Planning
1'-8"

ADD
1'-3"

7'-4"
FW1 99'-0" DP48A-14' DP48A-14' 003
91'-0" 99'-0"

1'-0"
6'-3"
S-312

1'-0"
005

4'-10"

4'-10"
DP48A-14' PD-6 2'-3" James W Nakai & Associates, PC

1'-11"
9"
PD-3A 99'-0" 99'-0" PD-6 PD-3A
2'-8"

520 E Colorado Ave


99'-0" 11 SIM

2"
Colorado Springs, CO 80903
11
PD-3A PD-3A
PD-3A
FW1 S-312 B.5 B 719-635-2142

TYP UNO

3'-9"

1'-0"
ADD
S-314
FW1

FW2

FW2
1'-0" 005

2'-2"
12'-6" 8 1/2" 1'-8"

1'-8"
B/ WALL

8'-11"
EQ,TYP,
S-221 1 DP48A-14' 2

9'-7"
9'-9"

10"
1'-1"
BP Civil

2'-3"
BP 1'-8" 4" STEP RFC 049 FW1

2'-3"
99'-0" S-311

FW1
003 003

EQ
8 19 TerraNova Engineering, Inc.

11"
1'-4" DP CL DP48A-14'

FW1
PD-3A FW1 SEE 4 / S-210 1'-0" S-313 815 S 25th Street
S-312 ADD
2"

FOR FND MAT AND 99'-0" Colorado Springs, CO 80904


B.4 DP48B-16' 2 DP48B-16' DP DETAILS
005 2 S-221 719-635-6422
PD-3B 2'-3"
10"

96'-4"

1'-8"

1'-0"
S-312 96'-4" 1'-2" DP54-14' DP54-14' DP48B-14' SIM B.8
PD-3B DP48A-14' DP48A-14' DP48A-14' PIER DWLS

29'-1"
PD-3B B/WALL STEP 1'-2" PIER CL 1'-0"
1'-0"

8 TYP FND WALL 91'-0" Landscape

1'-10
99'-0" 99'-0" BP " 18
IN N-S WALL 9'-10

FW4
99'-0" 99'-0" 18 99'-0" DP48B-14'
S-314 CONST JT PD-6 003
S-311 Lime Green Design, Inc
BP PD-3A PD-3A

"
8'-0" PD-3B PD-3B S-311 PD-3B 1'-0" 3" 1'-1" 91'-0" 900 E. Louisiana Avenue, Suite 209
2'-4" 1'-2"
003
Denver, CO 80210
1'-0"

100'-0" PD-6 303-733-7558


12'-0" 9 SOG5A C.1
S-312
SOG4A FW2
10'-9"

DP24A-8'
2 2 1 DP48A-14' Structural
SOG5A T/BL = 99'-4" 96'-4"

14'-2
S-213
S-314 S-314 99'-0" Martin/Martin
PD-2 12499 West Colfax Avenue

"
2 PD-3A
Lakewood, CO 80215
T/BL = 103'-4" (2) THUS C.3 C 303-431-6100

8"
14 DP30A-18' DP30A-18' DP30A-18' DP30A-18' DP30A-18' DP30A-18' DP30A-18'
S-314 10 14
2'-3"
99'-0" 99'-0" 99'-0" 99'-0" 6 TYP DRILLED 99'-0" 99'-0" 99'-0" 12" SOG AT S-312
S-314 Mechanical/Plumbing
STAIR POSTS 9'-8"

1'-2 /2"
PD-1 PD-1 PD-1 PD-1 S-310 PIER PD-1 PD-1 PD-1

1'-10 '-11"
Shaffer Baucom Engineering & Consulting
PER 11 SIM
CL OF DP

T/BL = 99'-4"

1/2"
7333 West Jefferson Avenue, Suite 230
TYP DRILLED
22'-3"

12

1
5
S-314 Lakewood, CO 80235
S-310 PIER DOWELS
21'-7"

8"
C.6 303-986-8200
2 DP36A-10'
4 6" 9" 12
15 TYP BASE FW3
S-315

29'-7"
S-312 PLATE 96'-4" Electrical
DP48B-16' DP48B-16' S-314 TYP STEEL STAIR BY
5
T/BL = 99'-4" 7 96'-4" SEE COL SCHED ON PD-4B Shaffer Baucom Engineering & Consulting
96'-4" S-313 CONTRACTOR. SEE ARCH 15 BP
S-312 HSS 5x5x1/4 DOOR POST S-200 FOR COL SIZES (2) THUS
7333 West Jefferson Avenue, Suite 230
PD-3B PD-4B FOR STRINGER REQTS S-312 003 Lakewood, CO 80235
T/BL = 99'-4" SEE ARCH FOR LOC T/CAP = 99'-0"

18'-1
5"

303-986-8200
ADD
BASE PLATE: 12 TYP, UNO

07
005 10
S-315 DP24A-14' 16 TYP AT HSS8x4x1/2 TYP AT CW,

/8"
1'-6" TYP
DP24A-10' DP24A-14' DP24A-14' DP24A-14' DP24A-14' DP24A-14' DP24A-16' SEE DTL FOR BASE PL 11 S-314 Technology
11"

9 96'-4" 1'-6" TYP S-313 COLUMNS


10 96'-4" 96'-4" 96'-4" 96'-4" 96'-4" 96'-4" 96'-4" 1'-6" S-314 Rimrock Group
CONTRACTOR NOTE S-316 PD-2 10807 New Allegiance Drive, Suite 400
6 10 PD-2 BP
(2) LOCS S-314 PD-2 PD-2 PD-2 PD-2 PD-2 PD-2

8"
Colorado Springs, CO 80921

8"
DRILLED PIERS NOT 003
S-312 S-314 BP D 719-533-1112

2'-6"
ALIGNED IN E-W ASI 003
DIRECTION 027

7'-0"
10"
8"
6'-0" 5'-6" 7'-7" 2'-0" 10 8 TYP GR BM T/BL = 99'-4"
2 TYPICAL 2 GR BM AT
D.1 Building Performance Engineer
1'-1" 7" 2'-10" 1 S-314 S-313 CONST JT TYP AT GRID D BL S-313 AT BRICK LEDGE S-313 STOREFRONT
Ambient Energy
130 W 5th Ave
5'-2 1/2"

13'-7"
WP Denver, CO 80204
1 VESTIBULE 303-278-1532
7'-0" 17'-8" 2'-4" 6'-8" 18'-0" 2'-4" 6'-8" 18'-0" 2'-4" 6'-8" 18'-0" 2'-4" 6'-8" 18'-0" 2'-4" 6'-8" 18'-0" 2'-2" S-201 FOUNDATION
Cost Estimating
E Parametrix, Inc.
7186 South Highland Drive
DP30A-12' DP30A-12' DP30A-8' DP30A-8' DP30A-8' DP30A-8' DP30A-8' DP30A-10' Salt Lake City, UT 84121
7 TYP 801-733-5900
99'-0" 99'-0" 99'-0" 99'-0" 99'-0" 99'-0" 99'-0" 99'-0"
S-316 GRID E
PD-1 PD-1 PD-1 PD-1 PD-1 PD-1 PD-1 PD-1

S-220

Issue Date

DESIGN DEVELOPMENT SEPTEMBER 12, 2012


FIRST LEVEL FLOOR PLAN SITE / UTILITIES OCTOBER 29, 2012
1/8" = 1'-0" BP#2 NOVEMBER 16, 2012
TR UE NORTH 2' 4' 8' 16'
BP#3 DECEMBER 21, 2012
ADDENDUM 005 JANUARY 25, 2013
DATE PRINTED: 4/18/2014 9:09:27 AM

KEYNOTE LEGEND FOUNDATION NOTES


ASI 027
RECORD DRAWINGS
JUNE 13, 2013
APRIL 18, 2014

1 INDICATES AREA THAT SHALL BE OVER-EXCAVATED TO 1. SEE S0 SERIES SHEETS FOR GENERAL NOTES, SYMBOLS AND
9'-0" MINIMUM BELOW THE BOTTOM OF THE SLAB-ON- ABBREVIATIONS.
BP
003 GRADE. 9'-0" OVER-EXCAVATION SHALL EXTEND TO THE
OUTSIDE FACE OF THE FOUNDATION WALL/GRADE 2. SEE S3 SERIES SHEETS FOR TYPICAL CONCRETE DETAILS.
BEAM. BACKFILL OVER-EXCAVATION BELOW SLAB-ON-
DESIGNERS: KH/AM

GRADE WITH DENSELY COMPACTED GRANULAR FILL. 3. SEE S-314 FOR TYPICAL SLAB-ON-GRADE DETAILS.
SEE EARTHWORK SPEC.
4. SEE ARCHITECTURAL DRAWINGS FOR VAPOR RETARDER LOCATIONS.
2 STAIR FRAMING BY MTL STAIR MANUF. SIZE POSTS
CONTRACTOR SHALL INSTALL VAPOR RETARDER PER RECOMMENDATIONS OF
AND BASE PLATES TO FIT IN STUD WALL. BRACE STAIR Project Number: 2011101.00
PCA AND ACI 302.1R-04.
AS REQUIRED. BRACING, POSTS AND BASE PLATES
Drawn By: KH/AM
SHALL FIT WITHIN STUDWALLS, SEE ARCH. DO NOT
5. SEE ARCHITECTURAL AND MECHANICAL DRAWINGS FOR SLAB SLOPES,
CONNECT TO FND WALL. PROVIDE STRINGER W/ Reviewed By: KH
DEPRESSIONS, FILL, PADS, AND CURBS NOT SHOWN ON THE STRUCTURAL
FLANGE WIDTH SUFFICIENT FOR HANDRAIL
DRAWINGS. Approved By: PD
CONNECTION SHOWN BY ARCHITECT.
6. SEE S-310 FOR TYPICAL DRILLED PIER DETAILS.
PROJECT MANAGER: KH

7. SEE S-311&S-312 FOR TYPICAL FOUNDATION WALL DETAILS.


MM JOB #: 23616.S.01

8. SEE S-200 FOR COLUMN SCHEDULE. FIRST LEVEL FLOOR PLAN


PRINCIPAL: PD

9. SEE S-311 FOR FOUNDATION WALL SCHEDULE FOR FOUNDATION WALLS


NOTED THUS: "FWX"
EOR: PD

S-101
C:\Proj\2011101_structural_kevinh.rvt

9 8 7 6.9 6 5.9 5 4.9 4 3.9 3 2.6 2.4 2 1.9 1.5 1

9'-9" 27'-0" 4'-0" 23'-0" 2'-8" 24'-4" 1'-4" 25'-8" 3'-8" 23'-4" 10'-6" 16'-4" 3'-2" 13'-4" 13'-8"
2'-0" 1'-10"

20
The Lane Center for
Academic Health
Sciences
T/WALL = 114'-6" University of Colorado at
Colorado Springs
COL CL, (3) LOCS 2011101.00
1 AT GRID 2
BP 1" SOUTH
S-220 003
16 5
10 7
OF GRID
SIM Owner
2 S-313 S-313 T/BL = 115'-4"
S-313 S-311 Facilities Services

2'-0"
8"

8"
University of Colorado at Colorado Springs
T/ CAP = 115'-0" Campus Services Building, Rm 212
1420 Austin Bluffs Parkway
A

1'-0"
Colorado Springs, CO 80918
T/PILASTER = 115'-6 1/2" (4) LOCS

18k

14k

14k
15 ASI 719-255-3505
T/BL = 115'-4" DP30A-12' 001
5'-4" RFC 039 ASI S-311 1'-0" 8" T/BL = 115'-4"
008 112'-0" 1'-10"
ADD Architect
006 5 PD-2 1

W12x19 [20]

W12x19 [20]
16

W18x35 [18]
BP TYPE 304 STAINLESS STEEL SOG10A AndersonMasonDale Architects, P.C.
8 1/2" DP30A-12' S-313 S-311 B.1 3198 Speer Boulevard

21'-0"
003 ANCHOR RODS. (9) LOCS AT 116'-0"
114'-6" 18 17 8" 10 1'-0" 3 Denver, CO, 80211
GRID A.6&B. 3"

5'-4
T/ BL = 115'-4" RFC 045 S-311 T/WALL = 114'-6" S-312 S-313 9
S-201 303-294-9448
T/WALL = 114'-6" PD-1 15'-3" RFC 032
1'-5 1/2"

3/4"
TYP AT COUNTERFORTS ADD S-314
A.6 5 BP 005 EQ EQ EQ B.2 Clinical Planning
1'-0"

3" BP CL
SIM 003
8"

14k
14k
6'-5"

S-316 10 16 GRADE BEAM AT 2 BP


11'-6" 16 2 AT STOREFRONT James W Nakai & Associates, PC

2'-4"

1'-4"
CURTAINWALL

36k
1 B/GR BM = 112'-4"

1'-7"
S-312 003 8" 22k W18x35 [20] 26k 520 E Colorado Ave
T/WALL = 116'-0" S-313 S-313 S-311 S-313
Colorado Springs, CO 80903
B.5 B

W12x19 [10] 8k
6k
719-635-2142
1'-0"
2'-8"

10"
6k W12x19 [6]

6'-2"
1'-5"
ADD

2'-2"
1'-0" HSS4x4x1/4 SOG5.5 SIM 10

26k
1'-0"

10"
S-221 1

7 1/4"
RFC 136 18 006

10'-7"

W12x19 [6]
8" 3" Civil

W12x26 [6]

11'-7"

8k

6k
8 1/2" 2'-0" BP-1 ADD

W12x19 [6]
9 S-313 13
S-315
8'-4"

T/BL = 110'-8" T/CAP = 115'-0" 116'-0" 005 10" T/ PILASTER = 115'-0" TerraNova Engineering, Inc.

6k
RFC 083 RFC 040 S-314 ADD
S-314 ASI 815 S 25th Street
005 008
RFC 035&046 RFC 081 RFC 039 Colorado Springs, CO 80904

9'-10
2 S-221 719-635-6422
W12x26 [10] W21x44 [26]

8k

8k

6k
T/BL = 107'-4" USE W27 8k 10k 32k 26k TYP 304 STAINLESS STEEL
10k

14k

18k

18k

18k

"
BP

~
~
16k

16k

54k

16k

16k

68k

16k

16k

22k

16k

44k
T/BL = 107'-4" EMBED 8k ANCHOR RODS. (4) LOCS AT B.8

1'-2"
#3
5'-10"

16k

14k
W18x35 [26]
16

16k

29'-1"
T/ WALL = 109'-4" 13 W12x26 [10]
HSS6x6x3/8 AND 20
GRID 2.4. Landscape
W16x26 [6] HSS6x6x3/8 W16x26 [6] S-314 S-315
ANGLE CONT TYP TYP TOC= 108'-11"
S-531 8k Lime Green Design, Inc

W12x19 [10]

W12x19 [10]
W12x19 [10]
W12x19 [10]

W12x19 [10]

W18x35 [18]

W12x19 [10]

W21x44 [16]
W12x19 [3]

W12x26 [18]

HSS
W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]
2'-0"

W12x19 [12]

W12x26 [16]
REINF TO 900 E. Louisiana Avenue, Suite 209

W12x19 [12]
W12x19 [12]

W12x19 [12]
6k 6k

W24x55 [22]

W24x55 [22]
1'-6" 6k

9'-0"
W12x19 [6] Denver, CO 80210

2'-3"
W18x35 6k

GRID 2 14

5x3x
303-733-7558
RFC 024 6k S-531 ASI C.1
~

1/2
020

12'-0"

12'-0"
3 3 (2)#7 CTR
KICKER
10'-2"

PER 10 / S-503 S-501 S-501 IN SLAB 1 Structural


~ S-213 ADD
10k

GRID A-E

16k
TYP

16k
14k

16k

HSS
005 Martin/Martin

16k

18k
18k

40k

48k

18k

10k
T/ WALL = 109'-4" 2'-3"
18k

18k

16k

16k

16k

16k

16k

26k
6k

9'-0"
12499 West Colfax Avenue
14k W16x26 [8] 44k W21x50 [30] 44k 42k W21x50 [30] 42k 42k W21x50 [30] 42k 42k W21x50 [30] 42k 44k W21x50 [36] 48k 42k W24x55 [12,9,12] 42k

5x3x
* 14 C
Lakewood, CO 80215
C.3 303-431-6100

1/2
* OPEN
28k

28k

26k

26k

26k

26k

26k

26k

26k

26k

26k

26k
20k

22k

28k

26k

26k

26k

26k

14k
16k

S-312
17 TOC= 102'-0"
S-531 Mechanical/Plumbing

HSS
2VLI3.5A 1'-8"

9'-0"
2'-3"
W16x26 [4] Shaffer Baucom Engineering & Consulting

5x3x
116'-0" 7333 West Jefferson Avenue, Suite 230
6k 12k W21x44 [8]
Lakewood, CO 80235

1/2
10

12k W21x44 [12]12k


A 6k C.6 303-986-8200
W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"


W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"


RFC 054 HSS8x4x1/2 AT CW,
S-530
W16x31 [16]

0". (6) THUS FOR BASE


W24x55 [30]

W21x44 [30]

W21x44 [30]

W16x31 [16]
TYP T/ GIRT
PL SEE 14 / S-312

29'-7"
HSS
A ELEVATION = 114'-8" Electrical
AND 15 / S-312

5x3x
Shaffer Baucom Engineering & Consulting
A 18 7333 West Jefferson Avenue, Suite 230

18'-1
T/ WALL = 109'-4" W16x26 [4]

1/2
Lakewood, CO 80235
6k A
S-501
AT (4) LOCS MARKED 11 TYP AT 303-986-8200

0 7/8
CHANNEL TO ALIGN B 6k "A" COORD LOC W/ S-502 SOUTH CW

HSS
WITH PARITION. COORD

"
12k W21x44 [8] RFC 062 PARTITION SUPPLIER

5x3x
T/ WALL = 109'-4" LOC WITH SUPPLIER 12 Technology
B B 19 AT (5) LOCS MARKED
16k

22k

1/2
S-502 Rimrock Group
"B" COORD LOC W/ HSS5x3x1/2
20k

S-503
28k

26k

26k

26k

26k

14k
28k

28k

26k

26k

26k

26k

26k

26k

26k

26k

26k
10807 New Allegiance Drive, Suite 400

26k
18 W16x26 [8] 42k W21x44 [30] 42k 40k W21x44 [24] 40k 40k W21x44 [24] 40k 40k W21x44 [24] 40k 40k W21x44 [24] 40k B B PARTITION SUPPLIER Colorado Springs, CO 80921
S-503
* HSS5x3x1/2
D 719-533-1112
12k 40k W24x55 [12,9,12] 40k *
* HSS8x3x1/4 AESS ( 116' - 0" )
16k

16k

14k

14k

14k

14k

14k

14k

14k

14k

14k

14k
12k

12k

14k

14k

14k

14k

14k

14k
10k

D.1

7'-0"
ADD
10
005 Building Performance Engineer
2 VESTIBULE
W18x35 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W18x35 [10]
10k W12x19 [10]

W12x19 [10]

16k W12x19 [10]

W12x19 [10]

14k W12x19 [10]

W12x19 [10]

14k W12x19 [10]

W12x19 [10]

14k W12x19 [10]

W12x19 [10]

14k W12x19 [10]

W12x19 [10]

14k W12x19 [10]


S-540
W12x19 [8] S-201 ROOF Ambient Energy

16'-1"
130 W 5th Ave
5'-2 1/2" WP Denver, CO 80204
6k 6k 303-278-1532
12k

12k

14k

14k

14k

14k

14k

14k
W12x19 [6]

~
~
16k

14k

14k

14k

14k

14k
6k W24x55 [17,6,17] W24x55 [13,6,13] W24x55 [13,6,13] W24x55 [13,6,13] W24x55 [13,6,13] W24x55 [13,6,13] Cost Estimating
* * W18x35 [8]* * 28k 28k
* *
26k 26k
* *
26k 26k
* *
26k 26k
* *
26k 26k
* *
26k 26k
** E Parametrix, Inc.
10k 10k
8"

7186 South Highland Drive


Salt Lake City, UT 84121
(2)#5 TYP AT 4 TYP 7" 801-733-5900
PERIMETER OF SLAB. S-540
8" EXTEND 5'-0" PAST RE-
ENTRANT CORNERS
1

S-220

Issue Date

DESIGN DEVELOPMENT SEPTEMBER 12, 2012


SECOND LEVEL FLOOR PLAN SITE / UTILITIES OCTOBER 29, 2012
TR UE NORTH
1/8" = 1'-0" BP#2 NOVEMBER 16, 2012
2' 4' 8' 16'
BP#3 DECEMBER 21, 2012
ADDENDUM 005 JANUARY 25, 2013
DATE PRINTED: 4/18/2014 9:09:29 AM

KEYNOTE LEGEND STEEL FLOOR FRAMING PLAN NOTES


1. SEE S0 SERIES SHEETS FOR GENERAL NOTES, SYMBOLS AND
ADDENDUM 006
ASI 001
FEBRUARY 8, 2013
FEBRUARY 19, 2013
ASI 008 MARCH 7, 2013
1 INDICATES AREA THAT SHALL BE OVER-EXCAVATED TO ABBREVIATIONS. ASI 020 MAY 20, 2013
9'-0" MINIMUM BELOW THE BOTTOM OF THE SLAB-ON- RECORD DRAWINGS APRIL 18, 2014
GRADE. 9'-0" OVER-EXCAVATION SHALL EXTEND TO THE 2. SEE S5 SERIES SHEETS FOR TYPICAL STEEL DETAILS.
OUTSIDE FACE OF THE FOUNDATION WALL/GRADE
BEAM. BACKFILL OVER-EXCAVATION BELOW SLAB-ON- 3. SEE S200 FOR STEEL COLUMN SCHEDULE.
DESIGNERS: KH/AM

GRADE WITH DENSELY COMPACTED GRANULAR FILL.


SEE EARTHWORK SPEC. 4. SEE S-530 FOR TYPICAL METAL DECK DETAILS AND SCHEDULE.

5. SEE S-500A &S-500B FOR TYPICAL STEEL CONNECTION DETAILS AND


SCHEDULE Project Number: 2011101.00

6. SPACE BEAMS EQUALLY BETWEEN GRID LINES UNLESS DIMENSIONED Drawn By: KH/AM

OTHERWISE. Reviewed By: KH

7. TOP OF BEAM ELEVATION = BOTTOM OF METAL DECK UNLESS NOTED Approved By: PD

OTHERWISE ON PLAN.

8. SEE 17/S-530 FOR REQUIREMENTS AT MECHANICAL AND ELECTRICAL


PROJECT MANAGER: KH

EQUIPMENT.
MM JOB #: 23616.S.01

SECOND LEVEL FLOOR PLAN


PRINCIPAL: PD
EOR: PD

S-102
C:\Proj\2011101_structural_kevinh.rvt

9 8 7 6.9 6 5.9 5 4.9 4 3.9 3 2.6 2.4 2 1.9 1.5 1

9'-9" 27'-0" 4'-0" 23'-0" 2'-8" 24'-4" 1'-4" 25'-8" 3'-8" 23'-4" 10'-6" 16'-4" 3'-2" 13'-4" 13'-8"

20
The Lane Center for
Academic Health
Sciences
University of Colorado at
Colorado Springs
2
2011101.00
S-213

S-220
7"
1
1" SOUTH TO Owner
2 BP
S-316 HSS12x4x5/16
003 GIRT CL Facilities Services
SEE ARCH ADD University of Colorado at Colorado Springs
W18x35 [22] FOR ELEV Campus Services Building, Rm 212
10k W12x26 [8]10k

7"
005
18k 18k 1420 Austin Bluffs Parkway
HSS10x8x1/4 (137'-7") ABOVE A Colorado Springs, CO 80918

8k

22k
26k
10" 719-255-3505
(130'-2 1/2) AT L3

EQ
TYP 4

W12x19 [12]

W14x22 [22]
W14x22 [12] 4 Architect
S-540 16k 16k
3 S-201
AndersonMasonDale Architects, P.C.

W21x50 [24]
S-202
B.1

DOWN
3198 Speer Boulevard

2VLI3.5A

21'-0"
Denver, CO, 80211

EQ

5 1/2"

5'-4
TYP AT 303-294-9448
4'-1"

24k
4 STRUT #5@12"OC SLAB W14x22 [12] 32k W21x44 [24] 36k

3/4"
W12x19 [6] 8k
16k 16k
A.6 S-213 BP DWLS THIS LOC SHOP WELD STUB TO 5"
B.2

6k
DECK Clinical Planning

10k
003

14k
HSS PER 10/S-502 "
1'-10
6'-5"

(2)#5 CTR IN SLAB

W21x44
6'-3"
10
DIRECTION James W Nakai & Associates, PC
TYP AT

EQ
1'-7"
10
W12x26 [10] 6k CHANGE S-531 5" 520 E Colorado Ave

26k

6k
3 3/4"
S-502 EAST CW Colorado Springs, CO 80903

2'-10 1/4"
B.5 B

W12x19 [12]

14k W12x19 [12]


W18x40 [22]
(SEE ARCH FOR

W12x19 [8] 6k HSS8x4x1/2 HSS8x4x1/2 HSS8x4x1/2 18k 24k 6k 6k 719-635-2142


ELEVATION)

9
HSS6x6x1/4

6k W12x26 10k

6'-2"
W12x26 [4] 6k

24k
W12x19 [8]

8'-2" 10"
S-320

30k
1 ( 129'-3 1/2" ) ( 129'-3 1/2" ) ( 129'-3 1/2" ) ADD

2'-8 1/4"
S-221

26k
[3]

10'-1"
18

36k

6k
x19 Civil

11'-3"

10k
11'-7"
9 OPEN 006
HSS8x4x1/2 16 10" 12
20 SIM W/ RFC136 S-315 ADD ADD * W
6k

W12x19 [6]
8" S-502 14 ASI (129'-3 1/2") 1'-7" TerraNova Engineering, Inc.
005 S-315

W18
S-501 W21 EMBED 020 005 815 S 25th Street
TYPE A S-531
12k W14x2212k RFC 081 Colorado Springs, CO 80904

9'-10
6"

x35
W21x44 [32] W24x55 [48] W12x26 [14]

8k
8k W16x26 [14] 8k 18k 18k 20k 24k 10k 6k W14x22 [14] 2 S-221 719-635-6422
16k

6 1/4
14
*

14k

"
~
~

10k
14k

10k

14k

14k

14k

14k

16k

34k
8" 2'-10" 10k B.8

8"
W24x55 [12,0]
20k

7"
14k

16k

16k

16k

16k

12k

14k
S-531 7

16k
BP

"
W12x19 [6] ASI

29'-1"
]
6k
020 CONT TYP 20 003
2x26 [10 S-501 Landscape
1
W16x26 [8] W16x26 [8] TYP 10k W

W18x35 [30]
REINF TO

W12x19 [10]

W18x35 [28]
Lime Green Design, Inc

4'-6" PAST
FO WALL
S-531

W12x19 [10]

W18x35 [26]

W12x19 [10]

HSS
W18x35 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W16x26 [10]
W12x19 [10]
W12x19 [12]

W12x19 [12]

W12x19 [12]

W12x19 [10]

W12x19 [10]
900 E. Louisiana Avenue, Suite 209

W12x19 [10]
10k W18x35 [18]

GRID 2

17'-10 1/2"
6k 6k

W24x55 [12]

W24x62 [12]

W12x19 [10]

9'-0"
Denver, CO 80210
9

5x3x
303-733-7558
S-502 C.1
7 7
~ 7'-0"

1/2
ADD (2)#7 CTR TYP T/ GIRT
005 EQ EQ S-501 S-501
TYPE B ELEVATION =129'-4"
IN SLAB 4 Structural
~

22k
W12x19 [6] GRID A-E

22k

24k
14k
10k

HSS
S-540 Martin/Martin
14k

16k

12k

16k

28k
14k

6k
14k

14k

14k

14k

16k

16k

16k

16k

14k

18k

16k
8k

9'-0"
12499 West Colfax Avenue
W12x19 [8] 42k W21x50 [26] 42k 48k W24x55 [26] 48k 42k W21x50 [26] 42k 42k W21x50 [26] 42k 60k W24x55 [32] 48k 42k W21x50 [26] 42k

5x3x
* C
Lakewood, CO 80215
12k C.3 303-431-6100

1/2
*
14k

26k

26k

26k

26k

26k

26k

26k

26k

26k

26k

26k

26k

26k
20k

20k

26k

26k

26k

26k

14k
1'-8" OPEN
Mechanical/Plumbing

HSS
11 TYP AT
W16x26 [4]

9'-0"
Shaffer Baucom Engineering & Consulting
2VLI3.5A S-502 SOUTH CW

5x3x
6k 7333 West Jefferson Avenue, Suite 230
130'-8" Lakewood, CO 80235

1/2
C.6 303-986-8200
W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"


W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"


W24x55 [30]

W14x22 [16]

W16x31 [16]

HSS

29'-7"
Electrical

5x3x
Shaffer Baucom Engineering & Consulting

1/2
7333 West Jefferson Avenue, Suite 230

18'-1
Lakewood, CO 80235
303-986-8200

0 7/8
HSS
W16x26 [4]

"
6k 8 15

5x3x
S-502 S-502 Technology
HSS5x3x1/2 12

1/2
Rimrock Group
14k

20k
20k

26k

26k

26k

26k

26k

14k
S-502
26k

26k

26k

26k

26k

26k

26k

26k

26k

26k

26k

26k
10807 New Allegiance Drive, Suite 400
W12x19 [8] 40k W21x44 [24] 40k 40k W21x44 [24] 40k 40k W21x44 [24] 40k 40k W21x44 [24] 40k 40k W21x44 [24] 40k 40k W21x44 [24] 40k HSS8x6x3/8 HSS5x3x1/2 Colorado Springs, CO 80921
* D 719-533-1112
12k * ( 129' - 6 1/2" )
*
8k

14k

14k

14k

14k

14k

14k

14k

14k

14k

14k

14k

14k
12k

12k

14k

14k

14k

14k

14k

14k
D.1

7'-0"
W12x19 [4] HSS12x3x5/16 AESS
Building Performance Engineer
6k RFC 036 ( 130' - 2" )
W12x19 [10]

W12x19 [10]

14k W12x19 [10]

W12x19 [10]

14k W12x19 [10]

W12x19 [10]

14k W12x19 [10]

W12x19 [10]

14k W12x19 [10]

W12x19 [10]

14k W12x19 [10]

W12x19 [10]

14k W12x19 [10]


12k W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W18x35 [10]
12k W18x35 [10]

RFC 056 Ambient Energy

16'-1"
130 W 5th Ave
5'-2 1/2" WP Denver, CO 80204
W12x19 [8] 303-278-1532
6k 6k
8k

14k

14k

14k

14k

14k

14k
~
~
14k

14k

14k

14k

14k

14k
W24x55 [13,6,13] W24x55 [13,6,13] W24x55 [13,6,13] W24x55 [13,6,13] W24x55 [13,6,13] W24x55 [13,6,13] Cost Estimating
W18x35 [8] 26k 26k 26k 26k 26k 26k 26k 26k 26k 26k 26k 26k
**
8k
* * * * * * * * * * * * ** E Parametrix, Inc.
7186 South Highland Drive
8"

Salt Lake City, UT 84121


(2)#5 TYP AT 4 TYP 801-733-5900
PERIMETER OF SLAB. S-540
8" EXTEND 5'-0" PAST RE- 7"
ENTRANT CORNER
1

S-220

Issue Date

DESIGN DEVELOPMENT SEPTEMBER 12, 2012


THIRD LEVEL FLOOR PLAN BP#2 NOVEMBER 16, 2012
TR UE NORTH
1/8" = 1'-0" BP#3 DECEMBER 21, 2012
2' 4' 8' 16'
ADDENDUM 005 JANUARY 25, 2013
ADDENDUM 006 FEBRUARY 8, 2013
DATE PRINTED: 4/18/2014 9:09:30 AM

STEEL FLOOR FRAMING PLAN NOTES ASI 020 MAY 20, 2013
RECORD DRAWINGS APRIL 18, 2014
1. SEE S0 SERIES SHEETS FOR GENERAL NOTES, SYMBOLS AND
ABBREVIATIONS.

2. SEE S5 SERIES SHEETS FOR TYPICAL STEEL DETAILS.

3. SEE S200 FOR STEEL COLUMN SCHEDULE.


DESIGNERS: KH/AM

4. SEE S-530 FOR TYPICAL METAL DECK DETAILS AND SCHEDULE.

5. SEE S-500A &S-500B FOR TYPICAL STEEL CONNECTION DETAILS AND


SCHEDULE Project Number: 2011101.00

6. SPACE BEAMS EQUALLY BETWEEN GRID LINES UNLESS DIMENSIONED Drawn By: KH/AM

OTHERWISE. Reviewed By: KH

7. TOP OF BEAM ELEVATION = BOTTOM OF METAL DECK UNLESS NOTED Approved By: PD

OTHERWISE ON PLAN.

8. SEE 17/S-530 FOR REQUIREMENTS AT MECHANICAL AND ELECTRICAL


PROJECT MANAGER: KH

EQUIPMENT.
MM JOB #: 23616.S.01

THIRD LEVEL FLOOR PLAN


PRINCIPAL: PD
EOR: PD

S-103
C:\Proj\2011101_structural_kevinh.rvt

9 8 7 6.9 6 5.9 5 4.9 4 3.9 3 2.6 2.4 2 1.9 1.5 1

9'-9" 27'-0" 4'-0" 23'-0" 2'-8" 24'-4" 1'-4" 25'-8" 3'-8" 23'-4" 10'-6" 16'-4" 3'-2" 13'-4" 13'-8"

20
The Lane Center for
Academic Health
Sciences
University of Colorado at
Colorado Springs
2011101.00
2
7" S-213
S-220
BP 1
1" SOUTH TO Owner
2 003 HSS12x4x5/16
S-316 Facilities Services
SEE ARCH GIRT CL
University of Colorado at Colorado Springs
FOR ELEV

7"
W18x35 [22] Campus Services Building, Rm 212
* 18k 18k * *10k W18x35 [8] 10k *

( 144' - 10 1/2" ) BELOW


1420 Austin Bluffs Parkway
ADD A

(152' - 3") ABOVE


Colorado Springs, CO 80918

W12x19 [6]

W12x19 [6]

8k

22k
* 005 719-255-3505

26k

EQ

6k

6k

HSS10x8x1/4
W12x19 [12]

W14x22 [22]
10"
16k 16k Architect
ASI AndersonMasonDale Architects, P.C.

W21x50 [24]
001 W14x22 [12] B.1 3198 Speer Boulevard

2VLI3.5A

21'-0"
Denver, CO, 80211

EQ

5 1/2"
20 SIM W/ 303-294-9448
4'-1" W27 EMBED ADD

24k
TYP AT S-501
W21x44 [24]

W12x19 [6] 8k
16k W14x22 [12] 16k 32k 36k 005
BP STRUT B.2
#5@12"OC SLAB DECK Clinical Planning

6k

10k

14k
003

36k
DWLS THIS LOC 5" TYP

6'-3"
7
W21x44 [2] DIRECTION 10 James W Nakai & Associates, PC

1'-8 1/4"

EQ
1'-7"
(2)#5 CTR IN SLAB 6k * CHANGE S-502 520 E Colorado Ave

26k
S-531

9 ' -1 1 4/ "
6k
FOURTH LEVEL
ADD Colorado Springs, CO 80903
B.5 B

W12x19 [12]

W12x19 [12]
W18x40 [22] W18x35
(SEE ARCH FOR

005
* 18k 24k 719-635-2142
8" WEST WALL

W24x55 [24] W24x55 [24] W24x55 [30]


ELEVATION)
HSS6x6x1/4

32k 32k 26k 26k 32k 36k STRIP W36 FLANGE T&B

6k

24k
* * * * * *

6k W12x19 [4]
ONE SIDE TO MATCH

10"
ABOVE

S-221 1

22k

22k

22k

22k

22k

22k

22k

52k
18

1'-1"
Civil

22k

22k

22k

11'-7"
SLAB EDGE DIM

11'-3"
8" 16
S-315 10"

4'-6" PAST
FO WALL
20 SIM W/ ADD 16
S-315
TerraNova Engineering, Inc.
11'-6" 815 S 25th Street

14k
S-501 W21 EMBED RFC136 005 S-315 RFC 027
Colorado Springs, CO 80904
10k W12x26 [12]

8k
10k 2 S-221 719-635-6422
W14x22 [14] 16k
*
8k
12k

14k

14k

14k

16k

16k

34k
B.8

~
~
20k

W18x40 [30]
16k

W36x135 [36]
W18x35 [26]

16k
W16x26 [14]

W16x26 [14]

W16x26 [14]

W16x26 [14]

W16x26 [14]

W16x26 [14]

W16x26 [14]

W16x26 [14]
W16x26 [14]

W16x26 [14]

29'-1"
BP

8"
W12x19 [4] 20 003 Landscape
6k RFC 031
S-531 TYP Lime Green Design, Inc
W18x35 [10]

W12x19 [10]

W12x19 [10]
W14x22 [10]
W12x19 [10]

W12x19 [10]

W12x19 [10]

W16x26 [10]
W12x19 [10]
900 E. Louisiana Avenue, Suite 209

W12x19 [10]
10k W18x35 [18]

Denver, CO 80210
CONT TYP 303-733-7558
7'-5" 7'-5" 4'-9" 2'-8" SLAB REINF C.1
ADD
005
TO GRID 2 ~ (2)#7 CTR 19
IN SLAB S-531 Structural
W12x19 [4]
~

22k
14k

GRID A-E

20k
22k

22k

48k
22k

16k
8k

Martin/Martin

16k
12k

16k

6k
14k

14k

22k

22k

22k

22k

22k

22k

22k

18k

16k
12499 West Colfax Avenue
10k W16x26 [8] 42k W21x50 [36] 42k 50k W24x55 [36] 54k 60k W24x55 [36] 52k 64k W24x55 [36] 48k 56k W24x62 [36] 52k 42k W24x55 [26] 42k
* C
Lakewood, CO 80215

* 10k C.3 303-431-6100


20k
12k

26k

26k

26k

26k

26k

26k

26k

26k

26k

26k

26k

26k

58k
26k

26k

26k

26k

26k
20k

9
S-501
Mechanical/Plumbing
1
2VLI3.5A Shaffer Baucom Engineering & Consulting
W16x26 [4] S-202
TOC= 144'-1" 7333 West Jefferson Avenue, Suite 230
6k 145'-4" Lakewood, CO 80235
C.6 303-986-8200
W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"


W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W16x31 [16] c=3/4"

W36x135 [24]
W24x55 [30]

W16x31 [16]

W21x50 [30]

29'-7"
Electrical
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200
W16x26 [4]
6k
Technology
26k

26k

26k

26k

26k

26k

56k
26k

26k
Rimrock Group
12k

20k

26k

26k

26k
20k

26k

26k

26k

26k

26k

26k
10807 New Allegiance Drive, Suite 400
10k W16x26 [8] 36k W24x62 [16,6,16] 36k 36k W24x62 [16,6,16] 36k 36k W24x62 [16,6,16] 36k 36k W24x62 [16,6,16] 36k 36k W24x62 [16,6,16] 36k 36k W24x62 [16,6,16] 36k Colorado Springs, CO 80921
EXTERIOR WALL *
ABOVE 10k
D 719-533-1112
* *
6k

12k

12k

12k

12k

12k

12k

12k

12k

12k

12k

12k

12k
12k

12k

12k

12k

12k

12k

14k
10k

9
D.1
W12x19 [4] S-501 HSS8x3x1/4 AESS Building Performance Engineer
6k
W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]

W12x19 [10]
( 140' - 0" )
W18x35 [10]

10k W12x19 [10]

10k W12x19 [10]

10k W12x19 [10]

10k W12x19 [10]

10k W12x19 [10]

10k W12x19 [10]

12k W18x35 [10]


Ambient Energy

16'-1"
130 W 5th Ave
Denver, CO 80204
W12x19 [8] 303-278-1532
6k 6k
6k

~
~
10k

10k

10k

10k

10k

10k

10k

10k

10k

10k

10k

10k

10k
W21x44 [20] W21x44 [20] W21x44 [20] W21x44 [20] W21x44 [20] W21x44 [20] Cost Estimating
* *6k W18x35 [8] 18k 18k 18k 18k 18k 18k 18k 18k 18k 18k 18k 18k *
E
6k * * * * * * * * * * * * * Parametrix, Inc.
7186 South Highland Drive
8"

Salt Lake City, UT 84121


(2)#5 TYP AT 4 TYP 801-733-5900
PERIMETER OF SLAB. S-540
8" EXTEND 5'-0" PAST RE- 7"
ENTRANT CORNER
1

S-220

Issue Date

DESIGN DEVELOPMENT SEPTEMBER 12, 2012


FOURTH LEVEL FLOOR PLAN BP#2 NOVEMBER 16, 2012
TR UE NORTH
1/8" = 1'-0" BP#3 DECEMBER 21, 2012
2' 4' 8' 16'
ADDENDUM 005 JANUARY 25, 2013
ASI 001 FEBRUARY 19, 2013
DATE PRINTED: 4/18/2014 9:09:31 AM

STEEL FLOOR FRAMING PLAN NOTES RECORD DRAWINGS APRIL 18, 2014

1. SEE S0 SERIES SHEETS FOR GENERAL NOTES, SYMBOLS AND


ABBREVIATIONS.

2. SEE S5 SERIES SHEETS FOR TYPICAL STEEL DETAILS.

3. SEE S200 FOR STEEL COLUMN SCHEDULE.


DESIGNERS: KH/AM

4. SEE S-530 FOR TYPICAL METAL DECK DETAILS AND SCHEDULE.

5. SEE S-500A &S-500B FOR TYPICAL STEEL CONNECTION DETAILS AND


SCHEDULE Project Number: 2011101.00

6. SPACE BEAMS EQUALLY BETWEEN GRID LINES UNLESS DIMENSIONED Drawn By: KH/AM

OTHERWISE. Reviewed By: KH

7. TOP OF BEAM ELEVATION = BOTTOM OF METAL DECK UNLESS NOTED Approved By: PD

OTHERWISE ON PLAN.

8. SEE 17/S-530 FOR REQUIREMENTS AT MECHANICAL AND ELECTRICAL


PROJECT MANAGER: KH

EQUIPMENT.
MM JOB #: 23616.S.01

FOURTH LEVEL FLOOR PLAN


PRINCIPAL: PD
EOR: PD

S-104
C:\Proj\2011101_structural_kevinh.rvt

9 8 7 6.9 6 5.9 5 4.9 4 3.9 3 2.6 2.4 2 1.9 1.5 1

9'-9" 27'-0" 4'-0" 23'-0" 2'-8" 24'-4" 1'-4" 25'-8" 3'-8" 23'-4" 10'-6" 16'-4" 3'-2" 13'-4" 13'-8"

20
The Lane Center for
Academic Health
Sciences
University of Colorado at
Colorado Springs
2011101.00
5 FOR STAIR ROOF
S-201 FRAME BELOW
7" 1
Owner
BP
003
S-316 5"
Facilities Services
University of Colorado at Colorado Springs

7"
W24x55 Campus Services Building, Rm 212
6k 6k W18x35 6k
* * 6k * * 6k
* W18x35
* 6k A 1420 Austin Bluffs Parkway
Colorado Springs, CO 80918

8k

6k
6k

6k

6k

6k
10k
719-255-3505

W12x19

W12x19
*
* ADD
W18x35 W18x35

W18x35
005

W12x19

W12x26
Architect
PROVIDE DOUBLE ANGLE PROVIDE DOUBLE ANGLE AndersonMasonDale Architects, P.C.

8k W12x26
RFC 027 W12x19 6k CONNECTION TO HSS CONNECTION TO HSS 6k W12x19 6k
11
B.1

W18x35
3198 Speer Boulevard

21'-0"
W24x68
COL, BEND ANGLE LEGS COL, BEND ANGLE LEGS S-530 Denver, CO, 80211
3'-9" 2'-6" 6'-1" 6k W12x19 [4] 6k 6k W12x19 [4] 6k 303-294-9448

W18x35
TYP AS REQD AS REQD ADD *

6k

6k

6k
BP 14k 006 W21x44 12k
COORD EXACT SIZE/LOC OF 17 15 003 #5@12"OC SLAB C8x11.5 WITH 5'-8" B.2
12 RFC 033
OPNG WITH ROOF HATCH DWLS THIS LOC CONN PER 16 SIM Clinical Planning

6k

8k
S-315 S-503
1'-6" *

8k
W12x19
* S-530

14k
1'-5"

94k
(2)#5 CTR IN SLAB S-531 James W Nakai & Associates, PC

8k
62k 520 E Colorado Ave

8k
5 W24x62 [62] W27x84 [88] W21x50 [22] W18x35

6k
W27x84 [72] 56k 52k 52k 62k 66k 38k 40k Colorado Springs, CO 80903
S-316 B.5 B
6k

6k
719-635-2142
W12x19 [10]

W12x19 [10]

W12x19 [10]

34k
2'-6"
6k

34k

34k

34k

34k

34k

34k

34k

34k

34k

24k

24k

16k
34k

34k
BP 6k W12x26 [6] 6k

22k
15 ADD
003

11'-1"
16 005 14
Civil
2VLI3.5A S-503

5'-0" PAST
FO WALL
17
RFC 027 W18x35 10k TerraNova Engineering, Inc.
( 159'-7 1/2" ) 2VLI8A W12x26 [4] S-315 OPTION #1 S-320
815 S 25th Street
6k W12x19 [12] 6k
6k

6k

6k

S-530
160'-0" 18k W12x26 [6] 18k 6k 6k 6k 6k SIM Colorado Springs, CO 80904
719-635-6422

W18x35
ADD

W30x90
* 005
6k

W18x35 [18]
6k

RFC 063

W18x35 [22]
W18x35 [18]

W18x35 [18]

W18x35 [18]

W18x35 [18]

W18x35 [18]

W18x35 [18]

W18x35 [18]

W18x35 [18]

W18x35 [18]

W24x55
10k
W18x35 [18]

W18x35 [18]
18k

10k

16k
B.8

6k
12k

14k

W18x35 [0,6]
W18x35 [22]
BP

29'-1"
20 SIM W/ OPTION #1 16 6'-0" 003 Landscape
SIM RFC136 W18x35 10k
S-501 W21 EMBED S-315 18 18 RFC136 Lime Green Design, Inc

W18x35 [18]
W12x19 [10]
W18x35 [10]

W16x26 [10]

W16x26 [10]
W12x19 [10]

900 E. Louisiana Avenue, Suite 209


W18x35

S-315 S-315

W18x40
6k W12x19 6k

W12x19
Denver, CO 80210
17'-10"

303-733-7558
41.0k 41.0k BP C.1
W14x22

17
003
RFC 042 S-502
HSS6x6x1/4 SEE 4 / S-501 W18x35 10k Structural

6k
34k

34k

34k

34k

22k
FOR DRAG CONN
12k

10k

34k

24k
Martin/Martin
*
10k

34k

34k

34k

34k

34k

34k

34k

12k

14k

12k

14k
6k

14k
12499 West Colfax Avenue
6k

6k

8k

8k
26k W24x68 [0,4,9] 34k 48k W24x62 [62] 52k 76k W24x62 [62] 56k 76k W24x62 [62] 54k 64k 12k 12k
* C
Lakewood, CO 80215

* 50k W21x44 * C.3 303-431-6100

6k

6k
10k

10k

10k

10k

10k

10k

10k

10k

10k

10k
2

8k
6k
8k

15
10k

10k

10k

10k

6k
1'-8"

STRUCTURE
S-530 S-202
TYP AT 12 W24x94 [9,4,0] (3) LOCS
PENTHOUSE 6'-0" S-501
W18x35 10k Mechanical/Plumbing
6k W12x19 6k S-530

SLOPE
1'-0" 5'-10" 6'-6" PERIMETER 1'-3 1/2" Shaffer Baucom Engineering & Consulting

W18x40
7333 West Jefferson Avenue, Suite 230

18'-0"
8" Lakewood, CO 80235
RFC 042 INDICATES KICKER
C.6 303-986-8200

W18x40
6k BELOW, SEE DETAIL W18x35 10k
6k W12x19
W24x55

W18x35

W18x35

W18x35

W18x35

W18x35

W18x35

W18x35

W18x35

W18x35

W18x35

W18x35

W18x35

W18x40

W18x40

W18x35

W18x35

W24x55

29'-7"
Electrical
18
Shaffer Baucom Engineering & Consulting

6k
S-501 7333 West Jefferson Avenue, Suite 230

2'-0"
3NB 6k W18x35 6k W18x35 10k Lakewood, CO 80235
303-986-8200
6k W12x19 6k 8 12'-6"
TYP
S-530
COORD W/ PARTITION Technology
SUPPLIER AND ARCH * Rimrock Group

8k
W18x35 10k
8k

8k

8k

8k

6k
10807 New Allegiance Drive, Suite 400
8k

8k

8k

8k

8k

8k

8k

8k

8k

8k

8k

6k

6k
W24x55 W24x55 W24x55 W24x55 W24x55 W24x55
* *10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k 10k Colorado Springs, CO 80921
* * * * * * * * * * * D 719-533-1112
5"

T/STEEL AT GRID D= 158'-6 1/2"


D.1 Building Performance Engineer
Ambient Energy

16'-1"
130 W 5th Ave
5" 7" Denver, CO 80204
303-278-1532

Cost Estimating
E Parametrix, Inc.
7186 South Highland Drive
Salt Lake City, UT 84121
801-733-5900

Issue Date

DESIGN DEVELOPMENT SEPTEMBER 12, 2012


PENTHOUSE FLOOR PLAN BP#2 NOVEMBER 16, 2012
TR UE NORTH
1/8" = 1'-0" BP#3 DECEMBER 21, 2012
2' 4' 8' 16'
ADDENDUM 005 JANUARY 25, 2013
ADDENDUM 006 FEBRUARY 8, 2013
DATE PRINTED: 4/18/2014 9:09:32 AM

STEEL FLOOR FRAMING PLAN NOTES RECORD DRAWINGS APRIL 18, 2014

1. SEE S0 SERIES SHEETS FOR GENERAL NOTES, SYMBOLS AND


ABBREVIATIONS.

2. SEE S5 SERIES SHEETS FOR TYPICAL STEEL DETAILS.

3. SEE S200 FOR STEEL COLUMN SCHEDULE.


DESIGNERS: KH/AM

4. SEE S-530 FOR TYPICAL METAL DECK DETAILS AND SCHEDULE.

5. SEE S-500A &S-500B FOR TYPICAL STEEL CONNECTION DETAILS AND


SCHEDULE Project Number: 2011101.00

6. SPACE BEAMS EQUALLY BETWEEN GRID LINES UNLESS DIMENSIONED Drawn By: KH/AM

OTHERWISE. Reviewed By: KH

7. TOP OF BEAM ELEVATION = BOTTOM OF METAL DECK UNLESS NOTED Approved By: PD

OTHERWISE ON PLAN.

8. SEE 17/S-530 FOR REQUIREMENTS AT MECHANICAL AND ELECTRICAL


PROJECT MANAGER: KH

EQUIPMENT.
MM JOB #: 23616.S.01

PENTHOUSE FLOOR PLAN


PRINCIPAL: PD
EOR: PD

S-105
C:\Proj\2011101_structural_kevinh.rvt

9 8 7 6.9 6 5.9 5 4.9 4 3.9 3 2.6 2.4 2 1.9 1.5 1

9'-9" 27'-0" 4'-0" 23'-0" 2'-8" 24'-4" 1'-4" 25'-8" 3'-8" 23'-4" 10'-6" 16'-4" 3'-2" 13'-4" 13'-8"

20
The Lane Center for
Academic Health
Sciences
University of Colorado at
Colorado Springs
2011101.00

Owner
Facilities Services
University of Colorado at Colorado Springs
Campus Services Building, Rm 212
1420 Austin Bluffs Parkway
A Colorado Springs, CO 80918
719-255-3505

12'-0" Architect
(3) EQ SP 2'-4 3/8" AndersonMasonDale Architects, P.C.
B.1 3198 Speer Boulevard

21'-0"
Denver, CO, 80211
303-294-9448
REMOVABLE
RFC 061 ELEVATOR HOIST
5'-0"
1
T/STEEL @ GRID B = 176'-7 1/2" THRU PLATE CONN OH 8 B/DECK = 176'-4" BEAM BELOW BY B.2 Clinical Planning
S-316 SIM PER 20 / S-500A S-316 CONTRACTOR James W Nakai & Associates, PC
4'-7" BP 520 E Colorado Ave
6k W12x26 6k 16k W18x35 16k 16k W18x35 16k 16k W18x106 16k 6k W18x35 6k 003 Colorado Springs, CO 80903
B.5 B 719-635-2142

6k W12x19 6k

W16x26 10k
10k

10k

10k

10k

10k

10k

10k

10k

10k

10k

14k
STRUCTURE
W12x19

10'-0"
11 Civil

3NB
6k

SLOPE
ADD
16 S-530 005 16 OPTION #1, SIM TerraNova Engineering, Inc.
3NB ADD 815 S 25th Street
S-315 S-315

4"
ADD OPTION #1, SIM W18x35 W18x35 005
ADD
Colorado Springs, CO 80904
005 719-635-6422
005

10k
6k W18x35 6k
6k

6k
8 B.8

W16x26

W16x26

W16x26

W16x26

W16x26

W16x26

W16x26

W16x26

W18x35
W16x26

W16x26

29'-1"
11
S-316 RFC 061 Landscape
S-530 SEE 8 / S-501 Lime Green Design, Inc
SIM FOR CONN AT BM, 900 E. Louisiana Avenue, Suite 209
W12x26

W16x26
W12x19
TYP Denver, CO 80210
3NC 303-733-7558
C.1
HATCH INDICATES
3NC DECK Structural

10k

10k
Martin/Martin
10k

10k

10k

10k

10k

10k

10k

10k

10k

10k
6k

6k

12499 West Colfax Avenue


HSS6x6x1/4 24k W24x76 26k 22k W18x35 16k 32k W24x76 26k Lakewood, CO 80215
C.3 C 303-431-6100

8"
3'-4"
T/STEEL @ GRID C = 176'-0"
Mechanical/Plumbing
8" 3 1/2" Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
C.6 303-986-8200

29'-7"
Electrical
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

Technology
Rimrock Group
10807 New Allegiance Drive, Suite 400
Colorado Springs, CO 80921
D 719-533-1112

D.1

7'-0"
Building Performance Engineer
Ambient Energy

16'-1"
130 W 5th Ave
5'-2 1/2" WP Denver, CO 80204
303-278-1532

Cost Estimating
E Parametrix, Inc.
7186 South Highland Drive
Salt Lake City, UT 84121
801-733-5900

Issue Date

DESIGN DEVELOPMENT SEPTEMBER 12, 2012


ROOF PLAN BP#2 NOVEMBER 16, 2012
TR UE NORTH
BP#3 DECEMBER 21, 2012
2' 4' 8' 16' 1/8" = 1'-0"
ADDENDUM 005 JANUARY 25, 2013
RECORD DRAWINGS APRIL 18, 2014
DATE PRINTED: 4/18/2014 9:09:33 AM

STEEL FLOOR FRAMING PLAN NOTES


1. SEE S0 SERIES SHEETS FOR GENERAL NOTES, SYMBOLS AND
ABBREVIATIONS.

2. SEE S5 SERIES SHEETS FOR TYPICAL STEEL DETAILS.

3. SEE S200 FOR STEEL COLUMN SCHEDULE.


DESIGNERS: KH/AM

4. SEE S-530 FOR TYPICAL METAL DECK DETAILS AND SCHEDULE.

5. SEE S-500A &S-500B FOR TYPICAL STEEL CONNECTION DETAILS AND


SCHEDULE Project Number: 2011101.00

6. SPACE BEAMS EQUALLY BETWEEN GRID LINES UNLESS DIMENSIONED Drawn By: KH/AM

OTHERWISE. Reviewed By: KH

7. TOP OF BEAM ELEVATION = BOTTOM OF METAL DECK UNLESS NOTED Approved By: PD

OTHERWISE ON PLAN.

8. SEE 17/S-530 FOR REQUIREMENTS AT MECHANICAL AND ELECTRICAL


PROJECT MANAGER: KH

EQUIPMENT.
MM JOB #: 23616.S.01

ROOF PLAN
PRINCIPAL: PD
EOR: PD

S-106
C:\Proj\2011101_structural_kevinh.rvt

ROOF LEVEL ROOF LEVEL


176'-0" 176'-0"

The Lane Center for


Academic Health
PENTHOUSE PENTHOUSE
LEVEL LEVEL Sciences
160'-0" 160'-0"
University of Colorado at
Colorado Springs
2011101.00

Owner

W10x49
W10x49

W10x33

W10x33
FOURTH FOURTH Facilities Services
LEVEL LEVEL University of Colorado at Colorado Springs
Campus Services Building, Rm 212
145'-4" 145'-4" 1420 Austin Bluffs Parkway

HSS14x0.625 AESS

HSS14x0.375 AESS
HSS8x8x5/16

HSS10x4x1/2 AESS
Colorado Springs, CO 80918

HSS14x0.625 AESS
719-255-3505

HSS14x0.375 AESS
W10x60

W10x60
Architect

W10x33
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
Denver, CO, 80211
303-294-9448
THIRD LEVEL THIRD LEVEL
130'-8" 130'-8"

HSS8.625x0.500 AESS
HSS14x0.375 AESS
Clinical Planning

HSS14x0.375 AESS
HSS14x0.375 AESS
HSS14x0.375 AESS

HSS2-1/2x2-1/2x1/4
HSS14x0.375 AESS

James W Nakai & Associates, PC


RFC 155

HSS6x6x1/4

520 E Colorado Ave

PBC8x5

HSS12x6x1/2
Colorado Springs, CO 80903
719-635-2142

W10x54

W10x60
W10x88

W10x54
W10x54
W10x88
SECOND SECOND Civil
LEVEL LEVEL
TerraNova Engineering, Inc.
116'-0" 116'-0" 815 S 25th Street
Colorado Springs, CO 80904

HSS14x0.250 AESS
719-635-6422

Landscape

HSS14x0.375

HSS6x6x3/8
Lime Green Design, Inc

AESS
900 E. Louisiana Avenue, Suite 209
Denver, CO 80210
303-733-7558

FIRST LEVEL FIRST LEVEL


100'-0" 100'-0" Structural
BP-7 BP-1 BP-7 BP-8 BP-4 BP-1 BP-3 BP-3 2 BP-3 BP-7 BP-3 BP-3 BP-2 BP-2 BP-1 BP-1 BP-3 BP-6 BP-1 BP-1 BP-8 BP-5 BP-3
BP-3 BP-6 BP-8 BP-3 Martin/Martin
12499 West Colfax Avenue
Column A.6-4, A.6-4.9, B(-2'-9 1/4")-4, B(-2'-9
B(10'-6")-2.4(2'-10 B(-1'-10 B.1-2.4(-2'-3"), D-2, D-3, D-4, D-5, E(3'-4 E-2, E-3, E-4, E-5, Lakewood, CO 80215
Locations A-2, B(6'-3")-2 A-2.6 A.6-5.9, A.6-6.9, B(-1'-10 3/8")-2 B(-1'-7")-3.9 B-4, B-6.9 1/4")-4.9, B(-2'-9 B-4.9, B-5.9 B.1(-1'-9")-2.4 B.8(-2'-3")-2.4 C-2, C-3, C-4, C-7 C-5, C-6 C-8 C-9 C.3(-2'-3")-2.4 D-1 D-1.5(-1'-4") D-9 D.1-1.5 D.1-1.9, D.1-2.4 E(2'-2 1/2")-1.5
7/8") 3/8")-2.4(-1'-2 3/8") B.2-2.4(-2'-3") D-6, D-7, D-8 1/2")-1.9(1'-11") E-6, E-7, E-8, E-9 303-431-6100
A-3.9 A.6-8(5'-4") 1/4")-5.9

Mechanical/Plumbing
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200
PREFABRICATED BUILDING COLUMN NOTES COLUMN SCHEDULE KEY

FOR COLUMNS MARKED 'PBC', PROVIDE PREFABRICATED BUILDING COLUMN Electrical


PER THE SPECIFICATIONWITH THE FOLLOWING PROPERTIES: Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
PBC8x5 303-986-8200
- CONCRETE FILLED PIPE = HSS6x3x1/4
- OUTER SHELL DIMENSIONS = 8"x5"
6
- ALLOWABLE SAFE LOAD >= 20 kips Technology
S-501
Rimrock Group
10807 New Allegiance Drive, Suite 400
Colorado Springs, CO 80921
719-533-1112

Building Performance Engineer


Ambient Energy
130 W 5th Ave
Denver, CO 80204
303-278-1532

15 TYP, Cost Estimating


S-315 UNO Parametrix, Inc.
7186 South Highland Drive
Salt Lake City, UT 84121
801-733-5900

Issue Date

BP#2 NOVEMBER 16, 2012


BP#3 DECEMBER 21, 2012
RECORD DRAWINGS APRIL 18, 2014
DATE PRINTED: 4/18/2014 9:09:34 AM
DESIGNERS: KH/AM

Project Number: 2011101.00

Drawn By: KH/AM

Reviewed By: KH

Approved By: PD
PROJECT MANAGER: KH
MM JOB #: 23616.S.01

COLUMN SCHEDULE
PRINCIPAL: PD
EOR: PD

S-200
C:\Proj\2011101_structural_kevinh.rvt

2 1.9 1.5 2.4 1


C.6

2 2.4
10'-9"

EXTEND GRADE BM REINF AT The Lane Center for


A INSIDE FACE TO FAR END OF HSS8x4x1/2 TYP AT CW,
18 Academic Health
PILASTER AND TERMINATE FOR BASE PL SEE
S-313
ASI WITH HOOK Sciences
008 15 / S-312
RFC 039 University of Colorado at
1'-6" HSS12x6x1/2 2'-3" Colorado Springs
TYPE 304 STAINLESS DP30A-10' BP-6 PER 1'-4" DP30A-10' T/GR BM = 99'-0"
2011101.00

10"
2 T/ PILASTER = 99'-0"

10'-6"
STEEL ANCHOR RODS 96'-4"
15 / S-315 96'-4"
12'-5" 1'-0 1/2" PD-2 PD-2 D
T/ PILASTER = 115'-4"

2'-6"
2'-4"

2'-3"

2'-3"
2 1/2" POST CL
3 1 DP24A-10' Owner

TO BM CL
RFC 039

1'-6"
SIM
S-213 S-503 112'-4"
13 D.1 Facilities Services
University of Colorado at Colorado Springs

7'-0"
10 S-313
S-314
PD-2 TYPE 304 STAINLESS STEEL Campus Services Building, Rm 212
HSS7x7x1/4 ABOVE 11 ANCHOR RODS. (3) LOCS AT 6 17 15
1420 Austin Bluffs Parkway
HSS4x4x1/4 C9x13.4 BELOW 1'-4" DP36A-10' Colorado Springs, CO 80918
S-313 VESTIBULE. S-316 S-313 10 S-312 719-255-3505
1'-1" 96'-4"
OH BASE PL PILASTER S-314

10"
5 PD-2

C9x13.4
TYP AT 5 ASI

BELOW
4

4'-4 1/2"
008 5 1'-10" Architect
BELOW

HSS TO S-503 BP
C9x13.4

3NB

S-503 S-503
SIM 003
HSS 2 AT STOREFRONT S-313 5'-8" 5'-2 1/2" WP AndersonMasonDale Architects, P.C.

13'-7"
10'-6"
3198 Speer Boulevard
HSS7x7x1/4 S-313
15 14 6 Denver, CO, 80211

8'-6"
13 SOG5.5 S-313 S-316 303-294-9448
HSS4x4x1/4 S-313
1'-9"

10"
S-314 PILASTER BASE PL
A Clinical Planning
HSS7x7x1/4

10'-3 1/2" 10"


B.1 James W Nakai & Associates, PC
HSS7x7x1/4

3'-4 1/2"
3 11 520 E Colorado Ave

3'-3"

2'-2 1/2"
1" 2" TO
S-503 S-313 B Colorado Springs, CO 80903

1'-10 3/8"

1'-10 3/8"
6'-11"

BP CL DP24A-10' 2 DP24A-10'
719-635-2142

96'-4" S-313 96'-4"


E

SEE ARCH
PD-4B PD-2 Civil
AT STOREFRONT TerraNova Engineering, Inc.
815 S 25th Street
BP
003 T/ PILASTER = 99'-0" Colorado Springs, CO 80904
3 1'-11" 719-635-6422
TYP AT VESTIBULE
S-503
10'-10 1/2" Landscape
Lime Green Design, Inc
900 E. Louisiana Avenue, Suite 209
Denver, CO 80210
303-733-7558

Structural
Martin/Martin
12499 West Colfax Avenue
Lakewood, CO 80215
303-431-6100

SOUTH EAST STAIR ROOF EAST VESTIBULE FLOOR PLAN WEST VESTIBULE FLOOR PLAN Mechanical/Plumbing

5 1/4" = 1'-0" 3 1/4" = 1'-0" 1 1/4" = 1'-0"


Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

Electrical
Shaffer Baucom Engineering & Consulting
2 1.9 1.5 2.4 1 7333 West Jefferson Avenue, Suite 230
C.6 Lakewood, CO 80235
303-986-8200

Technology
Rimrock Group
10807 New Allegiance Drive, Suite 400
Colorado Springs, CO 80921
719-533-1112

2 2.4 Building Performance Engineer


ADD Ambient Energy

HSS
005 130 W 5th Ave
10'-10 1/2" TYP T/ HSS5x3 Denver, CO 80204
8

5x3x
303-278-1532
GIRT TO COL

EDGE OF PLATE
S-502 ELEVATION = 114'-8"
A

1/2
SEE ARCH
HSS8x6x3/8 14 7 15 GIRT TO 12 Cost Estimating
1 SIM FOR S-502
3 4 ( 114'-10 1/2" ) S-502 S-502
S-502 POST Parametrix, Inc.
1'-11" S-502 EDGE PLATE S-502 7186 South Highland Drive
S-502 HSS8x8x3/8 Salt Lake City, UT 84121
( 110'-0" ) HSS5x3x1/2 HSS5x3x1/2 801-733-5900
D
HSS10x8x1/4 (125'-4")

2'-6"
HSS8x8x3/16 AESS HSS4x4x3/8 HSS8x4x3/8
( 110'-0" )
(125'-4")

1'-10"
5
SIM FOR ( 110' - 0" ) D.1
HSS8x8x1/2

7'-0"
S-502 EDGE PLATE 4
( 110' - 0" )
6'-0"

S-502 3'-2"
ASI
007

HSS8x8x3/8
5 EDGE OF PLATE

( 110' - 0" )
S-502 SEE ARCH

HSS8x4x3/8
( 110' - 0" )
HSS8x4x3/8 AESS

HSS8x8x3/8
3NB

( 110' - 0" )
9'-0 1/2"
(125'-4") 4 WP
TYP HSS 5'-2 1/2"

13'-7"
13
S-502 TO HSS
HSS8x8x3/16 AESS

S-502
3NB
1'-11" 10'-1"
(125'-4")
HSS6x6x1/4 (125'-4")

9'-0"

HSS8x8x1/2 Issue Date


7 TYP HSS TO 2 ( 110' - 0" ) BP#2 NOVEMBER 16, 2012

3'-4 1/2"
S-502 POST CONN
ADD
B.1 S-502 BP#3
ADDENDUM 005
DECEMBER 21, 2012
JANUARY 25, 2013

EDGE OF PLATE
005 17 ASI 007 MARCH 7, 2013
E

SEE ARCH
S-503 B 4 1 ASI 008 MARCH 7, 2013
DATE PRINTED: 4/18/2014 9:09:35 AM

RECORD DRAWINGS APRIL 18, 2014


2'-1"

S-502 S-502
3
HSS6x6x1/4 AESS
S-502
(125'-4")
B.2
DESIGNERS: KH/AM

Project Number: 2011101.00

Drawn By: KH/AM

Reviewed By: KH

Approved By: PD
PROJECT MANAGER: KH
MM JOB #: 23616.S.01

WEST VESTIBULE ROOF PLAN PARTIAL PLANS


EAST VESTIBULE ROOF PLAN
PRINCIPAL: PD

2
4 1/4" = 1'-0"
1/4" = 1'-0"
EOR: PD

S-201
C:\Proj\2011101_structural_kevinh.rvt

2 1.9 2.4 1.5 1 2 1.9 2.4 1.5 1


B.1 B.1

14k
B.2 B.2

1'-2"
B " B

1'-1 3/4"
1'-10
ADD
8" 005

4'-0"
W18x35
L8x4x3/4 LLV, AESS
B.5 6k W18x35 [10] 6k
6k B.5

7'-9"
17 SIM 18k
S-502 [12]
x35

18k
W18 The Lane Center for
HSS8x6x3/8 AESS FOR CONN, SEE 16 / S-503
8k Academic Health

EQ
HSS8x4x1/4 AESS
PL2 8k Sciences
AESS, GR 50 [12] University of Colorado at
18x35
W Colorado Springs

L8x4
HSS8x4x1/4 AESS T/STEEL = 154' 10 1/2"

EQ
8k

W18
HSS8x4x1/4 AESS
TYP FOR PERGOLA FRAMING B.8 B.8 2011101.00

x3/4
10k

29'-1"

29'-1"
(154'-10 1/2")

x35
ALL FRAMING AND CONNS

EQ
ARE AESS 1'-10" x35 [14]

[20]
LLV,
W18

AES
Owner
HSS8x4x1/4 AESS 10k Facilities Services

S
14k
University of Colorado at Colorado Springs
17 (3) LOCS 19 TYP 19 Campus Services Building, Rm 212

EQ
1420 Austin Bluffs Parkway
S-502 S-502
S-531
[16] Colorado Springs, CO 80918
18x35 12'-0
"
# C.1 W 6k C.1 719-255-3505

6k
# HSS8x6x3/8 AESS [9]
x50

W18
14k

20k
#
PROVIDE ALUMINUM W18 48k Architect
EXTRUSION CONNECTION 6k

x35
]

18k
PL2 THAT PROVIDES THERMAL 8x 35 [24 AndersonMasonDale Architects, P.C.

[5]
W1 3198 Speer Boulevard

6k
AESS, GR 50 RELIEF
6k W12x26 [8] 6k W12x19 [8] 6k Denver, CO, 80211
HSS8x4x1/4 AESS C C 303-294-9448

L8x4
AESS
6k
ASI 13 TYP T/ CURTAIN
20k

x3/4
9 6 012
20k S-503 WALL POST Clinical Planning
C.3 S-502 C.3

LLV,
S-501

W18
James W Nakai & Associates, PC

HSS8x4x1/4
(154'-10 1/2")
520 E Colorado Ave
]

AES
0 [12

x35
HSS8x4x1/4 AESS 5 Colorado Springs, CO 80903
8x
W1 719-635-2142

[22]
2VLI
TOC= 144'-1"

3.5A
TYP 20k Civil
20
TerraNova Engineering, Inc.
S-502 SLOPE STRUCTURE 16k
# HSS8x6x1/2 AESS . DOWN 1/4"/12" 815 S 25th Street

24k
Colorado Springs, CO 80904
# # C.6 52k 6 C.6 719-635-6422
PL2

10k
[14] TYP W18 TO COL

29'-7"

29'-7"
PROVIDE ALUMINUM S-503
AESS, GR 50 x50
EXTRUSION CONNECTION W18 Landscape
HSS8x4x1/4 AESS THAT PROVIDES THERMAL [28]
x50

AESS
W18 Lime Green Design, Inc

14k
RELIEF

L8x4
900 E. Louisiana Avenue, Suite 209
16k

(3) EQ SP
Denver, CO 80210

(154'-10 1/2")

x1LL
16 8k 303-733-7558

4'-5"
k 50 [10]
18x

V, AE
HSS8x4x1/4
22k 8k W

W18
HSS8x4x1/4 AESS
10k W1 Structural

SS

x35
8x3

9"
20
SIM 5[
16 6k 6k
Martin/Martin
PL2

[20]
]
5 [10
S-502 ALUMINUM EXTRUSION ] 12499 West Colfax Avenue

W18x35 [8]
[4]

12'-0 7/8"
AESS, GR 50 8x3 k
W1 ] 6 x19 Lakewood, CO 80215

2'-0"
SHALL NOT BE CONTINUOUS [10 12
8x35 W 303-431-6100

6k
AT SUPPORT 1
HSS8x6x1/2 AESS
8k 6k W

10k
ADD
W18x35 [10] 6k 6k W18x35 [10] 6k 18k Mechanical/Plumbing
005 6k
DO NOT CONNECT D D Shaffer Baucom Engineering & Consulting

6k W18x50 [2]
HSS BEAM TO COL

22k
7333 West Jefferson Avenue, Suite 230

8"
Lakewood, CO 80235
L8x4x3/4 LLV, AESS # L8x4x3/4 LLV, AESS D.1 9 303-986-8200

7'-0"

7'-0"
1'-10 1/2" S-501
16 D.1
HSS8x4x1/4 AESS S-502 1'-2" Electrical
HSS8x4x1/4 AESS 7 Shaffer Baucom Engineering & Consulting
S-503 7333 West Jefferson Avenue, Suite 230
5'-2 1/2" WP 13'-4" 13'-8" 5'-2 1/2" WP Lakewood, CO 80235
303-986-8200

Technology
Rimrock Group
10807 New Allegiance Drive, Suite 400
Colorado Springs, CO 80921
719-533-1112

Building Performance Engineer


Ambient Energy
130 W 5th Ave
Denver, CO 80204
303-278-1532

Cost Estimating
PENTHOUSE - PERGOLA FRAMING FOURTH LEVEL - TERRACE Parametrix, Inc.

2 3/16" = 1'-0" 1 3/16" = 1'-0"


7186 South Highland Drive
Salt Lake City, UT 84121
801-733-5900

Issue Date

T/STEEL = 125'-10" BP#3 DECEMBER 21, 2012


TYP FOR PERGOLA FRAMING ADDENDUM 005 JANUARY 25, 2013
ALL FRAMING AND CONNS ASI 012 MARCH 27, 2013
ARE AESS 7 6.9 6 5.9 5 4.9 4 RECORD DRAWINGS APRIL 18, 2014
DATE PRINTED: 4/18/2014 9:09:36 AM

11'-2" 3'-3" 4'-0" 7'-3" 11'-2" 4'-7" 7'-3" 11'-2" 5'-11" 7'-3" 11'-2" 7'-3"
L8x4x1/2 LLV, AESS

SEE ARCH NO CONNECTION


SEE ARCH

HSS8x4x1/4 AESS

HSS8x4x1/4 AESS

FOR END OF BETWEEN ANGLE. TYP


L8x4x1/2 LLV, AESS L8x4x1/2 LLV, AESS ANGLE L8x4x1/2 LLV, AESS L8x4x1/2 LLV, AESS
A.6
L8x4x1/2 LLV, AESS

L8x4x1/2 LLV, AESS

L8x4x1/2 LLV, AESS

L8x4x1/2 LLV, AESS

L8x4x1/2 LLV, AESS

L8x4x1/2 LLV, AESS


L8x4x1/2 LLV, AESS
19
HSS8x4x1/4 AESS

HSS8x4x1/4 AESS

HSS8x4x1/4 AESS

HSS8x4x1/4 AESS

HSS8x4x1/4 AESS
HSS8x4x1/4 AESS

SEE ARCH

S-502
DESIGNERS: KH/AM

L8x4x1/2 LLV, AESS TYP


TYP

B L8x4x1/2 LLV, AESS L8x4x1/2 LLV, AESS L8x4x1/2 LLV, AESS Project Number: 2011101.00

Drawn By: KH/AM


9
S-320 RFC 111 20 SIM 20 TYP NO CONNECTION Reviewed By: KH
S-502 ANGLE TO ANGLE S-502 HSS TO ANGLE BETWEEN ANGLE. TYP
Approved By: PD

ALUMINUM TRELLIS FRAMING


3
PROJECT MANAGER: KH

3/16" = 1'-0"
MM JOB #: 23616.S.01

PARTIAL PLANS
PRINCIPAL: PD
EOR: PD

S-202
C:\Proj\2011101_structural_kevinh.rvt

3 2.6
B.4 B A.6 9 8 7 6.9

11"

T/WALL, SEE ARCH TYPICAL The Lane Center for


Academic Health
Sciences

1'-0"
A ROOF LEVEL ROOF LEVEL University of Colorado at
Colorado Springs

2'-6" MIN
2011101.00

2'-0" MIN 3'-0" MIN


Owner
Facilities Services
University of Colorado at Colorado Springs
Campus Services Building, Rm 212
1420 Austin Bluffs Parkway
Colorado Springs, CO 80918
719-255-3505

Architect
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
Denver, CO, 80211
303-294-9448

1'-10" MIN

2'-6" MIN
3
16 TYP AT MAT FND 17
1
S-212
S-212 S-310 BP S-320 Clinical Planning
003 PENTHOUSE LEVEL PENTHOUSE LEVEL
James W Nakai & Associates, PC
160'-0" 160'-0" 520 E Colorado Ave
Colorado Springs, CO 80903

3'-1 1/2"
719-635-2142
1'-0"
MIN
1'-0" MIN
B SIM 4 Civil

7 1/2"
S-320 TerraNova Engineering, Inc.
#5@12"OC HORIZ, (4)#5 EQ SP VERT, CTR 815 S 25th Street
CTR IN WALL ABOVE Colorado Springs, CO 80904
IN WALL ABOVE 719-635-6422
FOURTH LEVEL FOURTH LEVEL
2'-6" 2'-0"

15 #5@12"OC VERT, CTR


11'-4 1/2"

20 S-320 IN WALL ABOVE Landscape


4 FROM PENTHOUSE FOURTH LEVEL Lime Green Design, Inc
13'-10 1/2"

13'-2 1/2"

6" MIN
19'-0"

S-310
S-212 TO ROOF LEVEL 900 E. Louisiana Avenue, Suite 209

8 ' -0 "
BP
003
#5@12"OC VERT, #5@12"OC HORIZ, Denver, CO 80210
303-733-7558
CTR IN WALL ABOVE 13 CTR IN WALL ABOVE

1'-6" MIN
FOURTH LEVEL S-320 FOURTH LEVEL
Structural
FOURTH LEVEL FOURTH LEVEL
Martin/Martin
145'-4" 145'-4" 12499 West Colfax Avenue
Lakewood, CO 80215
303-431-6100
FOR BRICK WEST WALL IS 8" THICK
10

2'-6" MIN
SUPPORT ABOVE FOURTH LEVEL
#5@18"OC EF VERT S-316
RFC 145 EMBED Mechanical/Plumbing
1'-1" 2 9" ABOVE THIRD LEVEL
Shaffer Baucom Engineering & Consulting
3'-7" S-212 3'-3" 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
#5@18"OC EF HORIZ 303-986-8200
ABOVE THIRD LEVEL

3 Electrical
S-320 Shaffer Baucom Engineering & Consulting
6" MIN 3 7333 West Jefferson Avenue, Suite 230
S-320 Lakewood, CO 80235
SOUTH CORE - PLAN 3
TYP 303-986-8200

2'-6" MIN
2
4

1'-6" MIN
S-320
1/4" = 1'-0" S-320
Technology
THIRD LEVEL THIRD LEVEL Rimrock Group
130'-8" 130'-8" 10807 New Allegiance Drive, Suite 400
Colorado Springs, CO 80921
719-533-1112
TYP WALL 4 (2) BARS AT 3" OC TO
#7@12"OC EF VERT INTERSECTION S-320 MATCH SIZE OF WALL
REINF AT OPENING Building Performance Engineer
1'-0" MIN EDGES, UNO Ambient Energy
5 130 W 5th Ave

LTS TYP
TYP Denver, CO 80204
9 8 7 6.9 S-320 3
#7@18"OC EF VERT, 303-278-1532
#5@12"OC EF HORIZ S-320 SECOND TO FOURTH
6" MIN
TYP AT 6
13'-2 1/2"

LEVEL
OPNGS, Cost Estimating
S-320 OH #5@18"OC EF HORIZ, Parametrix, Inc.
2 SIDES, T&B
SECOND TO FOURTH 7186 South Highland Drive
S-211 Salt Lake City, UT 84121

LTS, TYP
LEVEL 801-733-5900
A.6

2'-0" MIN
2
RFC 040 20 12 TYP
S-311 S-320
TYP S-320
SECOND LEVEL SECOND LEVEL
116'-0" 116'-0"

SEE 12 / S-320
FOR HORIZ REINF #7 EF ABOVE AND BELOW
B TYPICAL 16 AT OPNG, EXTEND LTS

8 ' -0 "
1'-0" MIN 1'-0" MIN
S-320 PAST EDGE OF OPNG

3 6" MIN
1
S-211
S-211 2

2'-0" MIN
#5@18"OC EF HORIZ, LTS PAST

PERP WALL

S-210
19 ADJACENT TO DOOR CONT HORIZ REINF Issue Date
S-311 BELOW FOURTH LTS PAST PERP WALL
LEVEL. TYPICAL 18'-6"

BP#2 NOVEMBER 16, 2012


9 FOR FND WALL BP#3 DECEMBER 21, 2012
#7@18"OC EF VERT CORNER REINF

9 ' -0 "

9 ' -0 "
S-311 RECORD DRAWINGS APRIL 18, 2014
BELOW FOURTH
2'-6" 3'-11" 3'-7 1/2"

B.4 LEVEL
DATE PRINTED: 4/18/2014 9:09:37 AM

FIRST LEVEL FIRST LEVEL


100'-0" 100'-0"
#5@12"OC EF HORIZ,
EA SIDE OF DOOR

#7@18"OC EF VERT
DESIGNERS: KH/AM

1
S-210
(4)#7 EQ SP EF VERT
BELOW FOURTH LEVEL
Project Number: 2011101.00

Drawn By: KH/AM

Reviewed By: KH
BP PD
BP Approved By:
003 RFC 017 003 RFC 017

NORTH CORE - PLAN NORTH CORE - SOUTH WALL ELEVATION NORTH CORE - WEST WALL ELEVATION
3 2 1
PROJECT MANAGER: KH

1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0"


MM JOB #: 23616.S.01

CORE WALL ELEVATIONS


PRINCIPAL: PD
EOR: PD

S-210
C:\Proj\2011101_structural_kevinh.rvt

B.4 A.6
6.9 7 8 9 B

T/WALL = SEE ARCH


TYPICAL
The Lane Center for
ROOF LEVEL ROOF LEVEL Academic Health
Sciences
University of Colorado at
Colorado Springs
2011101.00

Owner
A.6 B B.4 Facilities Services
University of Colorado at Colorado Springs
Campus Services Building, Rm 212
1420 Austin Bluffs Parkway
Colorado Springs, CO 80918
719-255-3505

Architect
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
Denver, CO, 80211
PENTHOUSE LEVEL PENTHOUSE LEVEL PENTHOUSE LEVEL 303-294-9448

160'-0" 160'-0" 160'-0"


3
3 Clinical Planning
S-320
S-320 James W Nakai & Associates, PC
6 520 E Colorado Ave
S-320 Colorado Springs, CO 80903
719-635-2142

5 6 (2) #7@ 3" OC EF, T&B Civil


S-316 LTS
S-320 TerraNova Engineering, Inc.
3 3 815 S 25th Street
(2) #7@3" OC S-316 LTS S-316 Colorado Springs, CO 80904
4
EF, T&B 719-635-6422
3 S-320
S-320 6 OH
S-320
Landscape
#5@18"OC EF VERT, TYP Lime Green Design, Inc
900 E. Louisiana Avenue, Suite 209
Denver, CO 80210
303-733-7558
FOURTH LEVEL FOURTH LEVEL FOURTH LEVEL
145'-4" 145'-4" 145'-4"
Structural
Martin/Martin
12499 West Colfax Avenue
Lakewood, CO 80215
303-431-6100

Mechanical/Plumbing
#5@18"OC EF VERT, TYP
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200
#5@18"OC EF HORIZ, TYP

Electrical
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
#5@18"OC EF HORIZ, TYP 303-986-8200
THIRD LEVEL THIRD LEVEL THIRD LEVEL
130'-8" 130'-8" 130'-8"
Technology
Rimrock Group
10807 New Allegiance Drive, Suite 400
(6)#7@12"OC EF VERT Colorado Springs, CO 80921
SECOND LEVEL TO 719-533-1112
6 3 9
THIRD LEVEL S-320 #5@18"OC EF HORIZ
S-320 S-320 ABOVE SECOND LEVEL
Building Performance Engineer
Ambient Energy
AT STRUT
TYP FULL 4 4 TYP FULL 130 W 5th Ave
(3)#7@12"OC EF VERT HEIGHT HEIGHT Denver, CO 80204
S-320 S-320 BP
CORNER REINF, SECOND BP
303-278-1532
003
LEVEL TO THIRD LEVEL 003

LTS, TYP
6
Cost Estimating
S-320

LTS, TYP
Parametrix, Inc.
LTS 20 7186 South Highland Drive
5 (6)#7@12"OC EF VERT S-311 Salt Lake City, UT 84121
S-316 ADD BARS AT FW1 801-733-5900
SECOND LEVEL SECOND LEVEL SECOND LEVEL
116'-0" 116'-0" 116'-0"

20
~ #6@12" OC EW ABOVE BRICK
LEDGE TO END OF WALL #7@10"OC EF VERT 18
S-311
~

S-312
(3)#7@12"OC EF VERT
BP
~ ADD BARS AT CORNER
OF FW 1 5'-8" #7@18"OC EF HORIZ
003

6
18 S-320
19
FW1 S-312
S-311
9 WALL INTERSECTION
FW1
S-311
SEE 2/S-311 FOR
FND WALL REINF
~ EXTEND FW1 OUTSIDE FACE
REINF BELOW BRICK LEDGE TO SEE 2 / S-311 FOR
Issue Date

END OF WALL FND WALL REINF BP#2 NOVEMBER 16, 2012


~

BP#3 DECEMBER 21, 2012

~ FIRST LEVEL FIRST LEVEL FIRST LEVEL


ADDENDUM 005
RECORD DRAWINGS
JANUARY 25, 2013
APRIL 18, 2014
100'-0" 100'-0" 100'-0"
DATE PRINTED: 4/18/2014 9:09:39 AM
DESIGNERS: KH/AM

Project Number: 2011101.00

Drawn By: KH/AM

Reviewed By: KH

BP ADD Approved By: PD


003 005

NORTH CORE - NORTH WALL ELEVATION NORTH CORE - EAST WALL ELEVATION NORTH CORE - CENTER WALL ELEVATION
PROJECT MANAGER: KH

3 2 1
MM JOB #: 23616.S.01

1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0"


CORE WALL ELEVATIONS
PRINCIPAL: PD
EOR: PD

S-211
C:\Proj\2011101_structural_kevinh.rvt

B 2.6 3 3 2.6 A B

T/POCKET = 175'-10 1/2" 16 OPTION #1 SIM


4 4
S-315 EACH SIDE
S-212 S-212

ROOF LEVEL ROOF LEVEL ROOF LEVEL ROOF LEVEL

1'-9"
The Lane Center for
B/EMBED = 176'-0" #5@12"OC EF VERT
Academic Health
B/POCKET = 174'-1 1/2"
7'-0 1/2"

Sciences
#5@18"OC EF HORIZ University of Colorado at
3 3 3 Colorado Springs
S-320 S-320 BP S-320 2011101.00
003
3
#5@18"OC EF VERT S-320 BP
003
11 SIM 6 Owner
ADD
S-320 S-320 005 Facilities Services
3'-0" MIN University of Colorado at Colorado Springs
Campus Services Building, Rm 212
3'-4 1/2"

1420 Austin Bluffs Parkway


Colorado Springs, CO 80918
#5@18"OC EF HORIZ #5@8" OC EF VERT 719-255-3505
14 11 FOURTH LEVEL TO ROOF
S-320 S-530
PENTHOUSE LEVEL PENTHOUSE LEVEL PENTHOUSE LEVEL PENTHOUSE LEVEL Architect
160'-0" 160'-0" 160'-0" 160'-0" AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
Denver, CO, 80211
303-294-9448

Clinical Planning
James W Nakai & Associates, PC
SOUTH CORE - SOUTH WALL AT PH 520 E Colorado Ave
4 1/4" = 1'-0"
S-212
Colorado Springs, CO 80903
719-635-2142

Civil
TerraNova Engineering, Inc.
815 S 25th Street
Colorado Springs, CO 80904
719-635-6422

Landscape
FOURTH LEVEL FOURTH LEVEL FOURTH LEVEL
Lime Green Design, Inc
145'-4" 145'-4" 145'-4" 900 E. Louisiana Avenue, Suite 209
Denver, CO 80210
1'-6' MIN 303-733-7558

1'-9 3/8" 1'-6 5/8"

Structural
Martin/Martin
12499 West Colfax Avenue
Lakewood, CO 80215
303-431-6100
2'-6" 3'-9"
#5@18"OC EF VERT MAX MIN 3
BP Mechanical/Plumbing
#5@18"OC EF VERT ABOVE THIRD LEVEL 003 S-320
ABOVE THIRD LEVEL Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200
SEE 8 / S-320 DETAIL
8 TYP ABOVE FOR HORIZ REINF, TYP
S-320 DOOR BP
003
Electrical
THIRD LEVEL THIRD LEVEL THIRD LEVEL
Shaffer Baucom Engineering & Consulting
130'-8" 130'-8" 130'-8" 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
17'-7"
303-986-8200

4 ' -8 "
#5@18"OC EF HORIZ,
Technology
10 ABOVE SECOND LEVEL,
Rimrock Group
S-320 10
ADJACENT TO DOOR. 10807 New Allegiance Drive, Suite 400
4 TYPICAL BP Colorado Springs, CO 80921
6
S-320 003
S-320 (4)#5 EF VERT, EQ SP AT 719-533-1112
S-320
JAMB, ABOVE SECOND LEVEL #5@18"OC EF VERT
11 TYP BTWN DOORS
S-320
Building Performance Engineer
#5@12"OC EF VERT, Ambient Energy
ABOVE SECOND LEVEL 130 W 5th Ave
7 4 Denver, CO 80204
TYP S-320 S-320 303-278-1532
2
BP
TYP AT 15 16
2
S-320 003 EDGE S-311 S-311 TYP
S-320
Cost Estimating
SECOND LEVEL SECOND LEVEL SECOND LEVEL
Parametrix, Inc.
116'-0" 116'-0" 116'-0" 7186 South Highland Drive
Salt Lake City, UT 84121
801-733-5900

11
S-311
SEE 2 / S-311 FOR #5@18"OC EF HORIZ,
FND WALL REINF FIRST TO SECOND LEVEL
3
FW1
S-320 6
S-320 3
S-320

#5@12"OC EF VERT
BELOW SECOND LEVEL
BP Issue Date
FIRST LEVEL FIRST LEVEL FIRST LEVEL 003
100'-0" 100'-0" 100'-0" BP#2 NOVEMBER 16, 2012
#5@18"OC EF HORIZ BP#3 DECEMBER 21, 2012
FULL HEIGHT #5@18"OC EF HORIZ 12 ADDENDUM 005 JANUARY 25, 2013
FULL HEIGHT

LTS, TYP
3 RECORD DRAWINGS APRIL 18, 2014
S-311
#5@12"OC EF VERT
S-320
DATE PRINTED: 4/18/2014 9:09:40 AM

BELOW THIRD LEVEL #5@12"OC EF VERT #5@9"OC EF HORIZ


BP BELOW THIRD LEVEL BELOW FIRST LEVEL
BP
003 003 BP
003
DESIGNERS: KH/AM

Project Number: 2011101.00

Drawn By: KH/AM

Reviewed By: KH

Approved By: PD
RFC 017

SOUTH CORE - EAST WALL ELEVTAION SOUTH CORE - WEST WALL ELEVATION SOUTH CORE - NORTH WALL ELEVATION
3 2 1
PROJECT MANAGER: KH

1/4" = 1'-0" 1/4" = 1'-0" 1/4" = 1'-0"


MM JOB #: 23616.S.01

CORE WALL ELEVATIONS


PRINCIPAL: PD
EOR: PD

S-212
C:\Proj\2011101_structural_kevinh.rvt

B.1 B.2 B.5 B.8 C.1 C.3 C.6


1'-11 1/4" 8'-0" 3'-7 1/2" 4'-6 1/4" 3'-9 3/8" 3'-5" 6'-10 1/2" 1'-3 1/4"
11 3/4" 10 1/4" 10 1/4" 11 1/8" 10 1/2" 10 1/4"
HSS4x4x1/4, (3) LOCS T/ CURB = 116'-10"
T/STEEL = 123'-1" 9 8
T/STEEL = 137'-9"
T/STEEL = 152'-5"
14 CONTINUOUS DOGLEG SECOND LEVEL
S-503 STRINGER BY CONTRACTOR 116'-0" The Lane Center for
HSS5x5x1/4
Academic Health

"
2'-4
14
T/LEDGE = 113'-8" Sciences
ATTACH CURTAINWALL S-312
MULLIONS AT HORIZ University of Colorado at

2'-3"
HSS ELEVATIONS ONLY. B Colorado Springs
TYP.

"
2011101.00

2'-4
T/ LEDGE = 103'-7" T/ LEDGE = 102'-8"
STRINGER SHALL DOWN T/ LEDGE = 108'-11"
CANTILEVER TO CORNER. 15
NO VERTICAL SUPPORT S-312

2'-3"
FROM POST STEEL STAIR BY ADDNL REINF REQD AT T/ LEDGE = 105'-7" Owner
STAIR LANDING FRAMING CONTRACTOR POST LOCS, SEE 14 / S-312 Facilities Services

"
2'-4
BY CONTRACTOR UP
1 1

University of Colorado at Colorado Springs


Campus Services Building, Rm 212
1420 Austin Bluffs Parkway
1

FIRST LEVEL Colorado Springs, CO 80918


HSS STAIR SUPPORT
100'-0" 719-255-3505
BEAM. SEE PLAN
T/ LEDGE = 99'-0"
B.4 Architect
CONNECT LANDING AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
FRAMING TO Denver, CO, 80211
CONCRETE WALL 303-294-9448

Clinical Planning
James W Nakai & Associates, PC
520 E Colorado Ave
Colorado Springs, CO 80903
ADD 719-635-2142
006

Civil
STAIR 3 PARTIAL PLAN SOUTH FOUNDATION WALL - INTERIOR ELEVATION
4 1/4" = 1'-0" 1 3/16" = 1'-0"
TerraNova Engineering, Inc.
815 S 25th Street
Colorado Springs, CO 80904
719-635-6422

Landscape
Lime Green Design, Inc
900 E. Louisiana Avenue, Suite 209
Denver, CO 80210
303-733-7558

Structural
Martin/Martin
12499 West Colfax Avenue
Lakewood, CO 80215
303-431-6100

A
Mechanical/Plumbing
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

PENTHOUSE LEVEL
160'-0" Electrical
T/STEEL= 157'-4" Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

Technology
Rimrock Group
10807 New Allegiance Drive, Suite 400
Colorado Springs, CO 80921
719-533-1112

Building Performance Engineer


13 Ambient Energy
S-501 130 W 5th Ave
Denver, CO 80204
2.6 2 303-278-1532

FOURTH LEVEL
145'-4" Cost Estimating
Parametrix, Inc.
7186 South Highland Drive
12 10 Salt Lake City, UT 84121
TYP AT KINK TYP
S-501 S-501 16 TYP 3 17 801-733-5900
S-501 S-213 S-501

HSS14x4x3/8
LANDING BY
SUPPLIER, W/ 3"
CONC ABOVE DECK

HSS14x4x3/8
HSS14x4x3/8
SIM
19 11 11
S-501
TYP S-501
S-501
HSS14x4x1/4
A
THIRD LEVEL
130'-8" 15
S-501 19
Issue Date
S-501
12 TYP AT BP#2 NOVEMBER 16, 2012
14 GA MIN TREAD
BP#3 DECEMBER 21, 2012
FORM W/ 3" CONC S-501 KINK

HSS14x4x1/4

HSS14x4x3/8
ADDENDUM 006 FEBRUARY 8, 2013
BY STAIR SUPPLIER RECORD DRAWINGS APRIL 18, 2014

HSS14x4x3/8

HSS14x4x1/4
DATE PRINTED: 4/18/2014 9:09:41 AM

14

DOWN
S-501
DESIGNERS: KH/AM

SECOND LEVEL
116'-0" 13 Project Number: 2011101.00
S-501
Drawn By: KH/AM

Reviewed By: KH

Approved By: PD
PROJECT MANAGER: KH

SOUTH EAST STAIR ELEVATION SOUTH EAST STAIR


MM JOB #: 23616.S.01

3 1/4" = 1'-0" 2 1/4" = 1'-0" STAIR PLANS AND SECTIONS


PRINCIPAL: PD
EOR: PD

S-213
C:\Proj\2011101_structural_kevinh.rvt

9 8 7 6 5 4 3 2 1.9 1.5 1
FOR
8
231 SIM 600S FRAMING BY ALT
S-540 BYND 237 CFS CONTRACTOR

EQ EQ EQ EQ EQ EQ
ROOF LEVEL
ADD TYP. EACH SIDE
238 006
9'-11 5/8"

236 OF OPENING

EQ EQ
EJ The Lane Center for
ADD
233 233
236 TYP.
233 Academic Health

8"
ML-1 ML-1
006
231
16 Sciences
S-540 University of Colorado at
238
Colorado Springs
2011101.00
1'-8" EJ EJ EJ EJ EJ EJ EJ 1'-8"
165' -4"
PENTHOUSE LEVEL
160'-0"
11 AT WALL W8 BRICK SUPPORT
S-540 BEYOND Owner

~
202 Facilities Services
RFC 145 University of Colorado at Colorado Springs
10 14 19 AT WALL 4'-3" 3'-0" 4'-3" 3'-1 1/8"
14 Campus Services Building, Rm 212
S-316 AC-1 S-540 S-540 BEYOND SIM 1420 Austin Bluffs Parkway
S-540 Colorado Springs, CO 80918
719-255-3505
1'-8" EJ EJ EJ EJ EJ EJ EJ EJ FOURTH LEVEL
145'-4"
176' -1"

TYP AT CORNERS
28'-9 3/4"

14 Architect
8 8 OH
S-541 AndersonMasonDale Architects, P.C.
S-503 S-503 3198 Speer Boulevard

~
Denver, CO, 80211
303-294-9448
202 14
AC-6 S-540
12 8 202OH SIM
SIM 8 Clinical Planning
EJ EJ EJ EJ EJ EJ EJ EJ S-503 S-503
S-503 James W Nakai & Associates, PC
THIRD LEVEL 520 E Colorado Ave
176' -1"

130'-8" Colorado Springs, CO 80903


BRICK RELIEF ANGLE 719-635-2142
TYP AT SOFFIT AND 7 ADD
WINDOW HEAD

~
S-540 005
SIM AT GIRT Civil
14 SIM TerraNova Engineering, Inc.
AC-6 S-540 SIM AT GIRT 11 815 S 25th Street
Colorado Springs, CO 80904
7 S-503
8 OH 719-635-6422
8
215 EJ EJ EJ EJ EJ EJ EJ EJ S-540
S-503
S-503 SECOND LEVEL
176' -1"

116'-0"
Landscape
Lime Green Design, Inc
SIM 900 E. Louisiana Avenue, Suite 209
Denver, CO 80210

~
303-733-7558

17 TYP AT
AS-2 AS-1 AS-1 AS-1 S-540
AS-1 STOREFRONT AS-1 AC-18 AC-16 Structural
Martin/Martin
12499 West Colfax Avenue
FIRST LEVEL Lakewood, CO 80215
AC-20 100'-0" 303-431-6100

99' - 4" 99' - 4" 99' - 4" 99' - 4" 99' - 4" 18 99' - 4" 18 99' - 4" 99' - 4"
244 219 TYP JAMB 800S WALL FRAMING BY CFS 230 219 219
228 229 234 239 S-540 S-540 228 229 Mechanical/Plumbing
CONTRACTOR, SPLICE AS
REQD. Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

BUILDING ELEVATION - WEST


1 1/8" = 1'-0"
Electrical
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

1.5 1.9 2 2.6 3 3.9 4 4.95 5.9 6 6.9 7 8 9 Technology


8 8 Rimrock Group
SIM AT CONC WALL
237 SIM 231 10807 New Allegiance Drive, Suite 400
S-540 S-540
BEYOND Colorado Springs, CO 80921
719-533-1112

EQ EQ EQ EQ EQ EQ 238 EQ EQ
ROOF LEVEL
Building Performance Engineer
Ambient Energy
TYP. 236 130 W 5th Ave
EJ Denver, CO 80204
ML-1 ML-1 303-278-1532
10 WALL 231 6 215
238
207 S-541 BEYOND S-541
8 Cost Estimating
ADD ABOVE STAIR, 11 S-541 Parametrix, Inc.
005 TYP 3 1'-8"
SIDES S-541 15'-0" 7186 South Highland Drive
EJ EJ EJ EJ EJ EJ EJ EJ
PENTHOUSE LEVEL Salt Lake City, UT 84121
SIM 14 12 36'-10 3/4"
12 160'-0" 801-733-5900
80'-6 1/8"

S-540 S-540 S-540 241


CJ

~
CJ CJ
ADD
005 3
14 14
14
TYP AT CORNER AC-10
BRICK RELIEF ANGLE
4 S-316
S-541 AT WINDOW HEAD
S-540 S-540 S-541
13'-4 7/8" 18'-8"

FOURTH LEVEL
219
12 12
145'-4"
80'-6 1/8"

S-540 S-540 241


CJ O.P.H.

CJ CJ
15
S-541 8 8
AC-27 AC-29 AC-11 AC-9 Issue Date
S-540 S-540
THIRD LEVEL BP#3 DECEMBER 21, 2012
20 130'-8" ADDENDUM 005 JANUARY 25, 2013
S-540 RECORD DRAWINGS APRIL 18, 2014
13'-4 7/8"

18'-8"
DATE PRINTED: 4/18/2014 9:09:46 AM

EJ EJ

15'-8 3/8"

SECOND LEVEL
225 116'-0"
AC-22 234 17
219 AC-12
DESIGNERS: KH/AM

S-541 115' - 4" 115' - 4" 115' - 4"

Project Number: 2011101.00

Drawn By: KH/AM

FIRST LEVEL Reviewed By: KH


100'-0"
Approved By: PD
PROJECT MANAGER: KH
MM JOB #: 23616.S.01

BUILDING ELEVATIONS
PRINCIPAL: PD

BUILDING ELEVATION - EAST


EOR: PD

2 1/8" = 1'-0"
S-220
C:\Proj\2011101_structural_kevinh.rvt

E D.1 D C AT LADDER B A A A.6 B B.4 C D D.1 E


BEYOND
ADD 8
005 S-540

EJ ROOF LEVEL EJ ROOF LEVEL

The Lane Center for


SIM.
Academic Health
16
233 233 ADD
006 Sciences
AT PERGOLA 105 8 8 University of Colorado at
S-540 ADD 8 16
006 207 Colorado Springs
S-541 S-541 S-541 S-540
14 2011101.00
EJ EJ S-320 EJ EJ EJ EJ EJ
PENTHOUSE LEVEL PENTHOUSE LEVEL
12 12
56'-8"

160'-0" 12 223 160'-0"


S-540 S-540 OPH 11
S-540 Owner
W8 BRICK SUPPORT ADD
8 ADD 006 S-540
006 Facilities Services

~
202 CJ S-540 CJ 202 University of Colorado at Colorado Springs
SIM AT Campus Services Building, Rm 212
14 800S CFS WALL FRAMING BRICK RELIEF ANGLE, 3 14 14 1420 Austin Bluffs Parkway
14 19
ADD SIM GIRT
005 S-540 ADD AC-3 S-540 GRID A TO B SEE ARCH FOR 14 ADD
S-316
AC-2
S-540 S-540 S-540
Colorado Springs, CO 80918
006 14 005 719-255-3505
7 ELEVATION S-540
S-540 SIM AT GIRT
S-540 EJ EJ EJ EJ
FOURTH LEVEL 242 FOURTH LEVEL
242 Architect
12 145'-4" 145'-4"
58'-4"

12 12 14
12 12 AndersonMasonDale Architects, P.C.
S-540 SIM AT S-540 S-540 S-541 3198 Speer Boulevard
S-540 AC-26 S-540
GIRT 8 BRICK RELIEF ANGLE, SEE TYP AT CORNER Denver, CO, 80211
303-294-9448
~

CJ CJ S-540 ARCH FOR ELEVATION CJ CJ


202 202
14 14 14
14
AC-5
S-540 HSS GIRT, SEE PLAN 8 AC-8 AC-28 9 AS-9 S-540 AS-9 AC-28 9 AC-7 S-540 Clinical Planning
14 S-540 7 ADD
ADD SIM SIM AT GIRT FOR ELEVATION, TYP S-540 S-541 S-541 006 James W Nakai & Associates, PC
006 S-540 S-540 520 E Colorado Ave
8'-3 5/8" 16'-8 3/8"
THIRD LEVEL THIRD LEVEL Colorado Springs, CO 80903
130'-8" 12 130'-8" 719-635-2142
12 12
BRICK RELIEF S-540 BRICK RELIEF ANGLE TO
ANGLE AT WINDOW S-540 S-540
ALIGN WITH WINDOW Civil
HEAD AND SOFFIT
~

CJ CJ HEAD AND SOFFIT TYP TerraNova Engineering, Inc.


14 14 815 S 25th Street
14
AC-5 10
800S CFS WALL AC-7
Colorado Springs, CO 80904
S-540 AS-8 S-540 AS-8 S-540 719-635-6422
AC-15 AC-23 FRAMING ADD
006
ADD S-540
006 225
SECOND LEVEL SECOND LEVEL Landscape
116'-0" 115' - 4"
O.P.H. 116'-0"
12 12 Lime Green Design, Inc
225 11 11 20 AT DOOR 900 E. Louisiana Avenue, Suite 209
S-540 BEYOND S-540 S-540
234 S-540 S-540 Denver, CO 80210
115' - 4" 234 303-733-7558
CFS WALL
110' -FRAMING
8" FROM
~

TOP OF CONCRETE WALL TO


RELIEF ANGLE ABOVE 107' - 4" Structural

9'-4"
BYND
219 Martin/Martin
12499 West Colfax Avenue
103' - 4"
Lakewood, CO 80215
FIRST LEVEL FIRST LEVEL 303-431-6100
100'-0" 99' - 4" 100'-0"
AC-17 99' - 4"
TYPICAL CFS WALL TYPICAL 600S CFS Mechanical/Plumbing
234 234
FRAMING AT WINDOWS WALL FRAMING BTWN Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
WINDOWS Lakewood, CO 80235
303-986-8200
DO NOT CONNECT CFS WALL
FRAMING, SHEATHING OR RELIEF
ANGLE TO DOOR POSTS. RELIEF Electrical
ANGLE IS CONTINUOUS PAST Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
POSTS Lakewood, CO 80235
303-986-8200

BUILDING ELEVATION - NORTH


1 1/8" = 1'-0"
Technology
Rimrock Group
10807 New Allegiance Drive, Suite 400
Colorado Springs, CO 80921
719-533-1112

BUILDING ELEVATION - SOUTH


2 1/8" = 1'-0"
Building Performance Engineer
Ambient Energy
130 W 5th Ave
Denver, CO 80204
303-278-1532

Cost Estimating
Parametrix, Inc.
7186 South Highland Drive
Salt Lake City, UT 84121
801-733-5900

EXTERIOR WALL FRAMING SCHEDULE


FOR BIDDING
LOCATION STUD SIZE AND SPACING COMMENTS

METAL STUD BACKING BRICK AT 600S162-68 @ 16" OC 14/S-540 Issue Date


RIBBON WINDOWS - TYPICAL
BP#3 DECEMBER 21, 2012
METAL STUD BACKING BRICK AT 600S162-68 @ 12" OC 14/S-540 ADDENDUM 005 JANUARY 25, 2013
RIBBON WINDOWS - CORNER RECORD DRAWINGS APRIL 18, 2014

STUD BACKING FULL HEIGHT BRICK - 800S200-54 @ 16" OC


DATE PRINTED: 4/18/2014 9:09:51 AM

TYPICAL
STUD BACKING FULL HEIGHT BRICK - 800S200-68 @ 12" OC
CORNER
FULL HEIGHT STUD BACKING STUCCO - 800S162-43 @ 16" OC MECHANICAL PENTHOUSE
TYPICAL
FULL HEIGHT STUD BACKING STUCCO - 800S162-54 @ 16" OC
DESIGNERS: KH/AM

MECHANICAL PENTHOUSE
CORNER

NOTE: Project Number: 2011101.00


THE SIZES LISTED IN THIS TABLE MAY BE USED FOR BIDDING. FINAL DESIGN IS BY
THE CFSF CONTRACTOR. Drawn By: KH/AM

Reviewed By: KH

Approved By: PD
PROJECT MANAGER: KH
MM JOB #: 23616.S.01

BUILDING ELEVATIONS
PRINCIPAL: PD
EOR: PD

S-221
C:\Proj\2011101_structural_kevinh.rvt

CONCRETE COVER
LAP SPLICE AND DEVELOPMENT LENGTH SCHEDULE (INCHES)
CASE COVER (IN) F'c = 3,000 PSI THRU 3,500 PSI F'c = 4,000 PSI F'c = 5,000 PSI
CONCRETE PLACED AGAINST EARTH 3 BAR SIZE BAR SIZE COMP TENSION COMP TENSION COMP TENSION
CONCRETE PLACED IN FORMS, EXPOSED TO WEATHER OR EARTH 2 (IN-LB) (METRIC)
LTE LTE LTS LTS LTE LTE LTS LTS LTE LTE LTS LTS
LCE LCS LDH LCE LCS LDH LCE LCS LDH
CONCRETE PLACED ON VOID FORMS WITH MASONITE OR PLYWOOD COVERING 2 TOP OTHER TOP OTHER TOP OTHER TOP OTHER TOP OTHER TOP OTHER
SLABS, WALLS OR PILASTERS NOT EXPOSED TO EARTH OR WEATHER 1 #3 #10 8 12 6 21 16 28 21 8 12 6 18 14 24 18 8 12 6 17 13 22 17
The Lane Center for
#4 #13 11 15 8 28 22 37 28 9 15 7 25 19 32 25 9 15 6 22 17 29 22
#5 #16 14 19 10 36 27 46 36 12 19 8 31 24 40 31 11 19 7 28 21 36 28 Academic Health
#6 #19 16 23 12 43 33 56 43 14 23 10 37 28 48 37 14 23 9 33 25 43 33 Sciences
#7 #22 19 26 13 62 48 81 62 17 26 12 54 42 70 54 16 26 10 48 37 63 48 University of Colorado at
Colorado Springs
#8 #25 22 30 15 71 55 93 71 19 30 13 62 47 80 62 18 30 12 55 42 72 55
2011101.00
#9 #29 25 34 17 80 62 105 80 21 34 15 70 54 91 70 20 34 13 62 48 81 62
#10 #32 28 38 19 90 70 118 90 24 38 17 78 60 102 78 23 38 15 70 54 91 70
#11 #36 31 42 22 100 77 131 100 27 42 19 87 67 113 87 25 42 17 78 60 101 78
Owner
Facilities Services
GENERAL NOTES: University of Colorado at Colorado Springs
1. 'LCE' = COMPRESSION EMBEDMENT LENGTH, 'LCS' = COMPRESSION LAP SPLICE LENGTH, 'LTE' = TENSION EMBEDMENT LENGTH, Campus Services Building, Rm 212
4d 'LTS' = TENSION LAP SPLICE LENGTH, 'LDH' = HOOK DEVELOPMENT LENGTH 1420 Austin Bluffs Parkway
2 1/2" MIN Colorado Springs, CO 80918
2. 'TOP' BARS ARE HORIZONTAL BARS PLACED SUCH THAT MORE THAN 12 IN. OF FRESH CONCRETE IS CAST BELOW THE BAR 719-255-3505
D1 D1 3. ALL BARS THAT ARE NOT 'TOP' BARS ARE 'OTHER' BARS

d
4. UNLESS NOTED OTHERWISE, ALL HOOK BARS SHALL EXTEND TO THE FAR FACE (LESS 2" COVER)

~
~
Architect

12d
LAP SPLICE NOTES: AndersonMasonDale Architects, P.C.
1. ALL SPLICES SHALL BE WIRED IN CONTACT AND STACKED VERTICALLY 3198 Speer Boulevard
Denver, CO, 80211
90 HOOK 180 HOOK 2. ALL SPLICES ARE 'LTS' UNLESS NOTED OTHERWISE 303-294-9448
3. SMALLER BAR LAP LENGTH SHALL BE USED WHEN SPLICING DIFFERENT SIZED BARS
PRINCIPAL REINFORCING 4. LAP LENGTHS SPECIFICALLY DETAILED ON DRAWINGS SHALL GOVERN IN LIEU OF LAP LENGTHS SCHEDULED
6d 5. BUNDLED BAR SPLICES: Clinical Planning
4" MIN A. INDIVIDUAL BAR SPLICES WITHIN THE BUNDLE SHALL BE STAGGERED James W Nakai & Associates, PC
D2 D2 B. INCREASE LAP LENGTH 20% FOR A 3 BAR BUNDLE 520 E Colorado Ave
C. INCREASE LAP LENGTH 33% FOR A 4 BAR BUNDLE Colorado Springs, CO 80903
719-635-2142
6 6. IF A NOTE OR DETAIL CALLS FOR A BAR TO BE EMBEDDED Ld (DEVELOPMENT LENGTH) INTO CONCRETE, THIS LENGTH SHALL CORRESPOND TO A 'LTE' LAP

N
4" d
MI
d

6
d

~
1
~ ~

~
ADJUSTMENTS TO GIVEN LAP LENGTHS: Civil
1. IF REINFORCING IS SPECIFIED AS EPOXY COATED, INCREASE SCHEDULED LAP LENGTHS BY 50% TerraNova Engineering, Inc.
90 HOOK 135 HOOK MAX OFFSET BEND 2. IF LIGHTWEIGHT AGGREGATE IS SPECIFIED, INCREASE SCHEDULED LAP LENGTHS BY 30% 815 S 25th Street
#3-#5 #3-#8 3. SCHEDULED LAP LENGTHS ASSUME: Colorado Springs, CO 80904
STIRRUPS ONLY TIE OR STIRRUP A. CLEAR COVER IS GREATER THAN BAR DIAMETER, BUT NOT LESS THAN 3/4"
719-635-6422

B. CLEAR SPACING BETWEEN BARS IS GREATER THAN 2 BAR DIAMETERS


D1 D2 C. IF EITHER CONDITION A OR B IS NOT MET FOR A GIVEN BAR, INCREASE LENGTHS BY 50% Landscape
NOTES:
1. ALL BENDS SHALL BE MADE COLD #3 - #8 6d #3 - #5 4d 4. SPLICE LENGTHS NOTED BASED ON Fy = 60,000 PSI. FOR OTHER YIELD STRENGTHS, MULTIPLY SPLICE LENGTHS NOTED BY Fy/60,000 Lime Green Design, Inc
2. #14 & #18 BARS SHALL BE BEND TESTED #9 - #11 8d #6 - #8 6d 900 E. Louisiana Avenue, Suite 209
& LAB APPROVED PRIOR TO BENDING HOOK EMBEDMENT NOTES: Denver, CO 80210
#9 - #11 8d 1. SCHEDULED HOOK EMBEDMENT LENGTHS ASSUME: 303-733-7558

A. SIDE COVER IS 2 1/2 INCHES OR GREATER


B. COVER BEYOND IS 2 INCHES OR GREATER
Structural
2. IF REINFORCING IS SPECIFIED AS EPOXY COATED, INCREASE SCHEDULED LAP LENGTHS BY 20%
Martin/Martin
TYPICAL REINFORCING BENDS 3. IF LIGHTWEIGHT AGGREGATE IS SPECIFIED, INCREASE SCHEDULED LAP LENGTHS BY 30% 12499 West Colfax Avenue
4. IF SIDE COVER IS LESS THAN 2 1/2 INCHES, INCREASE LENGTHS BY 40% Lakewood, CO 80215
303-431-6100

Mechanical/Plumbing
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

10 NO SCALE REINFORCING DEVELOPMENT, PLACEMENT, AND BEND INFO


Electrical
LTS + 18", TYP Shaffer Baucom Engineering & Consulting
2" CLR TO REINF, 12" MAX W 7333 West Jefferson Avenue, Suite 230
D TYP EW Lakewood, CO 80235
3'-0" MAX

WHICHEVER IS SMALLER
303-986-8200
ADD 1/2 NUMBER OF BARS

MAX D=0.3T OR 2"


INTERRUPTED BY OPNG
PLUS 1, SPACE AT 3" OC Technology
Rimrock Group
10807 New Allegiance Drive, Suite 400
NOTE 2 Colorado Springs, CO 80921
719-533-1112

NOTE 1

12" FROM ALL


ALIGN PEN'S

EDGES, TYP
Building Performance Engineer
VERTICALLY
Ambient Energy

T
130 W 5th Ave

H, 3'-0" MAX
Denver, CO 80204
303-278-1532

D = OUTSIDE DIAMETER
Cost Estimating
3D (12" MIN)
B/WALL Parametrix, Inc.
CLEAR 7186 South Highland Drive
DETAIL SIMILAR Salt Lake City, UT 84121
NOTE: WHERE CLEAR DISTANCE BETWEEN SLEEVES CAN NOT BE NOTE 1 FOR CIRCULAR 801-733-5900

ACHIEVED AS SHOWN, STRUCTURAL ENGINEER OF RECORD SHALL BE OPENINGS


NOTIFIED. NOTES:
SCHEDULE 40 SLEEVES SHALL BE USED IN CRITICAL AREAS OF THE 1. GREATER OF 2xD AND 12", WHERE CLEAR DISTANCE IS NOT ACHIEVABLE, TREAT AREA
WALL AND SLABS AS DETERMINED BY STRUCTURAL ENGINEER OF AS SINGLE OPENING REINFORCED PER "TYPICAL OPENING" DETAIL
RECORD. 2. DO NOT CUT REBAR AT PENETRATIONS LOCS. REBAR MAY BE MOVED 8" MAX TO NOTES:
IN WALL OR SLAB CONDUITS GREATER THAN [0.2T] SHALL BE SUBMITTED ACCOMMODATE PENETRATIONS 1. DETAIL APPLIES UNLESS REINF IS SPECIFICALLY DETAILED ON THE DRAWINGS
FOR REVIEW
AT PIPING OR CONDUIT AT OPENINGS 12" OR LESS TYPICAL OPENING

11 NO SCALE TYP CIP SLAB OR WALL PENETRATIONS

. LESSER OF: Issue Date


1) LDH
2) FAR FACE OF CONC LESS 2" BP#2 NOVEMBER 16, 2012
BP#3 DECEMBER 21, 2012
RECORD DRAWINGS APRIL 18, 2014
DATE PRINTED: 4/18/2014 9:09:52 AM

8'-0" MAX UNSUPPORTED 2'-6" MIN BEARING


2" CLR, TOP

LENGTH ON SOIL
3/4" CHAMFER
3" CLR, BOT

8 AT CORNERS, SIDEWALK EJ
EE 1'-6 5/8"

S-300 TYP
SEE CIVIL FOR
ELEVATION AND SLOPE SIDEWALK SEE CIVIL
6"
DESIGNERS: KH/AM

AT BEAM OR WALL FACE

(7) #4 @10" OC REMOVE SOIL FOR SWAIL


DITCH AFTER CONCRETE HAS LTS LTS UNO Project Number: 2011101.00

#4 @18" OC REACHED 70% OF SPECIFIED Drawn By: KH/AM


28-DAY STRENGTH
Reviewed By: KH

Approved By: PD
PROPERLY COMPACTED ON SITE OR
NOTES:
IMPORTED SAND BACKFILL PER
1. ALL REBAR EPOXY COATED.
OCTOBER 30, 2012 CTL LETTER.
PROJECT MANAGER: KH

REVIEWED AND APPROVED BY


FORM SAVER
MM JOB #: 23616.S.01

OWNERS GEOTECHNICAL ENGINEER


TYP CONCRETE DETAILS
TYPICAL
PRINCIPAL: PD

BP
003
EOR: PD

12 NO SCALE PEDESTRIAN BRIDGE SECTION 8 NO SCALE PEDESTRIAN BRIDGE AT SIDEWALK 4 NO SCALE TYP FORMSAVER
S-300
C:\Proj\2011101_structural_kevinh.rvt

3" CLR SHAFT DIA


LTS + H

LTS DRILLED PIER SCHEDULE


REINFORCEMENT
TYPE SHAFT DIA VERTICAL TIES REMARKS
DP24A 24" (6)#7 #4@14"
DP30A 30" (6)#9 #4@18
DP36A 36" (8)#8 #4@16
DP48A 48" (20)#10 #5@6

3"
CL
DP48B 48" (14)#10 #4@10

R
VERT REINF, EQUALLY DP54 54" (22)#10 #5@8
VOID, SEE SPACED AROUND

H
FND NOTES PERIMETER The Lane Center for
Academic Health
Sciences
University of Colorado at
Colorado Springs
2011101.00
FORM TOP AS REQUIRED TO
PREVENT MUSHROOMING

6" UNO T/BEARING MATERIAL, SEE Owner


GEOTECHNICAL REPORT FOR Facilities Services
DESCRIPTION. ASSUME 6222.50' University of Colorado at Colorado Springs
FOR BID PURPOSES Campus Services Building, Rm 212
1420 Austin Bluffs Parkway
Colorado Springs, CO 80918
719-255-3505

9 NO SCALE TYP STEPPED GR BM/WALL AT PIER


Architect
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
Denver, CO, 80211

MINIMUM PENETRATION INTO BEARING MATERIAL. SEE PLAN.


#3 ALIGNMENT BARS OR OTHER 303-294-9448

MINIMUM LENGTH = 24'-0"


APPROVED ALIGNMENT DEVICES
AT 1/4 POINTS AROUND
Clinical Planning
PERIMETER AT TOP, BOT, AND
James W Nakai & Associates, PC
MID 520 E Colorado Ave
Colorado Springs, CO 80903
719-635-2142
ROUGHEN WHEN THE DRILLING
PROCEDURE RESULTS IN EXCESSIVE
REMOLDING AND CAKING OF THE Civil
3 1/2"
BEDROCK ON THE PIER WALLS AS TerraNova Engineering, Inc.
PIER DIAMETER 815 S 25th Street
DETERMINED BY THE GEOTECHNICAL Colorado Springs, CO 80904
ENGINEER PIER TIE REINFORCING PATTERN 719-635-6422

~
PENETRATION INTO

6"
4" HORZ LEG Landscape
BEARING MATERIAL

LTS
TIED TO TIE
IN FEET (SEE PLAN) Lime Green Design, Inc

6"
PIER VERTICAL 900 E. Louisiana Avenue, Suite 209
SPLICE BARS AT B/PIER IF DP30A-10 Denver, CO 80210

4"
REQUIRED FOR OVERRUN BARS 303-733-7558

TYPICAL ALIGNMENT BAR PLAN MARK


Structural
Martin/Martin
12499 West Colfax Avenue
Lakewood, CO 80215
303-431-6100

Mechanical/Plumbing
BP Shaffer Baucom Engineering & Consulting
003 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

6 NO SCALE TYP DRILLED PIER SCHEDULE


9" EQ EQ EQ Electrical
EQ SP 9"
Shaffer Baucom Engineering & Consulting
(8) #6 DOWELS

4" CLR

4" CLR
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235

3"
303-986-8200

Technology
Rimrock Group
10807 New Allegiance Drive, Suite 400
Colorado Springs, CO 80921
719-533-1112

VOID, SEE
B 4" CLR, TYP Building Performance Engineer
FND NOTES
Ambient Energy
130 W 5th Ave
SIM AT CORNER. PLACE Denver, CO 80204
B DWLS IN E/W WALL UNO 303-278-1532

LTS
3" CLR

9"
Cost Estimating

EQ SP
LTS + 2'-0"
Parametrix, Inc.
VOID, SEE 7186 South Highland Drive
COLUMN FND NOTES Salt Lake City, UT 84121
801-733-5900
REINFORCING INDICATES CAP CENTER PIER ON
VERT BARS COLUMN ABOVE UNO

4" CLR
PIER DOWELS
PD-4B 4" CLR FND WALL REINF
DOWELS AT WALL ON PIER
R

(12) #11 DOWELS

9"
CL

AT TYPE A PD-6
6"

(6)#11 DOWELS AT INDICATES PIER


TYPE B REINFORCING DOWELS AT MAT

EQ SP
C

TYP
W/ STD HOOK AT A
PROVIDE #4 DWL BOT
TIES, TYP @48"OC
A
C

9"
SEE PLAN INDICATES DP Issue Date
SEE ELEVATION FOR WALL REINF 1'-0" VERT REINF

3"
MATCH COLUMN B DESIGN DEVELOPMENT SEPTEMBER 12, 2012
LTS

REINFORCING PROVIDE #4 DWL TIES

2" CLR
WALL DWLS TO MATCH
LTS

BP#2 NOVEMBER 16, 2012


WALL REINF, TYP @48" OC IN WALL, TYP ANCHOR RODS BP#3 DECEMBER 21, 2012

3"
OR DOWELS

6" FROM
RECORD DRAWINGS APRIL 18, 2014

T/WALL
PIER CAP W/ #9@8" OC EW T&B
B
DATE PRINTED: 4/18/2014 9:09:54 AM

6" CLR, TYP


T.O.CAP VOID, SEE FND

9"
GRATING COVER. NOTES

9"
SEE ARCH S/2 MAX, TYP
VOID, SEE
EQ

5'-0" TO CSJ

MATCH SIZE & A FND NOTES

3" MAX TO
PIER BAR
SPACING OF T&B REINF
CONST JT
3 ' -7 7 8/ "
DESIGNERS: KH/AM

(3)#5 EF, TYP AT


LTS

EQ

PERIMETER OF MAT
A 3" CLR 3" CLR

Project Number: 2011101.00


6" MAX

3" MAX
EQ

FULL DEPTH CONST JT Drawn By: KH/AM


#5@9" AROUND
HOOK, TYP
SUMP PIT Reviewed By: KH
T.O.PIER Approved By: PD
(4) #4 TIES

4" VOID FORM,


PROJECT MANAGER: KH

SEE FND NOTES PD-5 PD-3 A&B PD-2 PD-1


MM JOB #: 23616.S.01

DOWELS AT FND WALL DOWELS AT WALL ON PIER DOWELS AT GRADE BEAM CAP DOWELS AT PIER TYP DRILLED PIER DETAILS
PILASTER SUPPORT STL COLUMN
PRINCIPAL: PD

BP BP
003 003
EOR: PD

20 NO SCALE SHEAR WALL MAT SUMP REINF 16 NO SCALE PIER CAP AT SHEAR WALL 12 NO SCALE PIER DOWELS
S-310
C:\Proj\2011101_structural_kevinh.rvt

LTS OR CONT, TYP FOUNDATION WALL SCHEDULE


OUTSIDE FACE (SOIL MARK HORIZ A HORIZ B VERT
SIDE)
FW1 #10@12" #10@18" #5@12"
FW1 27" #10@12" #10@18" #5@12"
13 BAR SIZE & SPACING FW2 #5@9" #5@12" #5@12"
DO NOT PLACE HARDSCAPE ON BACKFILL UNTIL BACKFILL SETTLEMENT S-314 TO MATCH HORIZ FW3 #7@12" #7@12" #7@12"
HAS OCCURRED. RE: GEOTECHNICAL ENGINEER FOR CRITERIA. REINF
FW4 #10@12" #10@18" #5@9"
2'-0" CLAY BACKFILL PER INSIDE FACES INSIDE FACES
OCTOBER 30, 2012 CTL LETTER SECOND LEVEL, ELEV = 116'-0"

CROSS WALL OR
COUNTERFORT
SEE PLAN
2 ' 0- "

HORIZ REINF SEE 10 / S-300


2" CLR 1" CLR
The Lane Center for
OUTSIDE FACE Academic Health
(SOIL SIDE) Sciences
OPEN CIRCLE INDICATES
VERTICAL REINF University of Colorado at
9
Colorado Springs
SOLID CIRCLE INDICATES ADDITIONAL
S-311
2011101.00
VERTICAL BARS, SIZE TO MATCH
SIM AT WALL VERT REINF
INTERSECTION
Owner
HORIZ B EF
Facilities Services
INSIDE FACES University of Colorado at Colorado Springs

4 ' -3 1 2/ "
PROPERLY COMPACTED ON SITE OR BP Campus Services Building, Rm 212
IMPORTED SAND BACKFILL BEHIND 003 1420 Austin Bluffs Parkway
Colorado Springs, CO 80918
FOUNDATION WALLS AND UNDER ALL SOME LOCS 719-255-3505
HARDSCAPE PER OCTOBER 30, 2012 CTL
LETTER 9 NO SCALE TYP GR BEAM/FND WALL REINF
Architect
AndersonMasonDale Architects, P.C.
ELEV = 106'-0" 3198 Speer Boulevard
Denver, CO, 80211
303-294-9448

Clinical Planning
FIRST LEVEL, ELEV = 100'-0"
SEE DECK SCHED FOR James W Nakai & Associates, PC
520 E Colorado Ave
MIN BRG LENGTH
SEE PLAN VERT EF Colorado Springs, CO 80903
719-635-2142

2" CLR
BEND DOWN FOLLOWING HORIZ A EF Civil
PLACEMENT OF DECK TerraNova Engineering, Inc.
815 S 25th Street

6 ' -2 3 4/ "
Colorado Springs, CO 80904
9'-0" OVEREXCAVATION T/BRICK LEDGE 719-635-6422

9 ' -0 "
AND COMPACTED
GRANULAR FILL EQ
DECK ORIENTATION Landscape
1 VARIES Lime Green Design, Inc
WALL MAY BE BACKFILLED
900 E. Louisiana Avenue, Suite 209
1.5 FULL HEIGHT PRIOR TO Denver, CO 80210
L3x3x1/4 CONT W/ CONSTRUCTING SOG AND 303-733-7558

TEMPORARY EXCAVATION 1/2"x4" HAS @24" SECOND LEVEL SLAB ON


SLOPE PER SOILS REPORT DECK
Structural
T/PIER Martin/Martin
12499 West Colfax Avenue

3" CLR
EQ EQ Lakewood, CO 80215
303-431-6100

AT BRICK LEDGE AT DECK BEARING Mechanical/Plumbing


BP
Shaffer Baucom Engineering & Consulting
003
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

18 NO SCALE TYP SOIL PREP SECTION 2 NO SCALE TYP FND WALL


Electrical

DRILLED PIER DOWELS


7 8" SPACING 6.9 3 3 Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
PER 16 303-986-8200
1'-0" NOTE 2 60'-0" MAX
S-310

3'-0" Technology
#7x @12 "OC HORIZ

3'-0"
Rimrock Group
#4x ASTM A706 DWLS @12", 10807 New Allegiance Drive, Suite 400
#9@12"OC VERT EF Colorado Springs, CO 80921

2" CLR
AT PERIMETER CONT WALL REINF LTS BEND DOWN, TYP 719-533-1112
PAST PERP WALL
16
LTS OR CONT 2" CLR 7
S-315
S-311 Building Performance Engineer
LTS

NOTE 2
LTS

60'-0" MAX
Ambient Energy
#4xCONT, TYP
SEE 9 / S-311 FOR FND 130 W 5th Ave
Denver, CO 80204
WALL CORNER REINF 303-278-1532
SECOND LEVEL CONT FND WALL REINF

2 ' -7 "
REQUIREMENTS

B Cost Estimating
Parametrix, Inc.
7186 South Highland Drive
Salt Lake City, UT 84121
B CONT VERT REINF 801-733-5900
LTS B
LTS PAST SECOND
LEVEL EQ EQ
LTS

NOTES:
CONT HORIZ FND 1. SUBMIT LOCATIONS OF CONST JTS FOR REVIEW PRIOR TO CONSTRUCTION
WALL REINF
1" CLR
DWLS TO MATCH SIZE TYPICAL 2. LOCATE CONST JTS AT LEAST 5'-0" FROM PILASTERS AND CORNERS. AT GR BEAMS,
AND SPACING OF SECOND JT SHALL BE IN MIDDLE THIRD OF SPAN
LEVEL WALL REINF
BP 1'-8"
003

CORE WALL TO FND WALL


19 NO SCALE PILASTER AT B/6.9 15 NO SCALE SLAB BEARING AT SOUTH CORE 11 NO SCALE
INTERSECTION 7 NO SCALE TYP T/FND WALL

1ST POUR 2ND POUR


3 1 1/2"
Issue Date

LTS DESIGN DEVELOPMENT SEPTEMBER 12, 2012


DOWELS TO MATCH SIZE AND
SPACING OF WALL ABOVE 3 BP#2 NOVEMBER 16, 2012

EQ
BP#3 DECEMBER 21, 2012
RECORD DRAWINGS APRIL 18, 2014

3'-0" VERT WALL

EQ
DATE PRINTED: 4/18/2014 9:09:56 AM

VERT REINF AT STEP SEE 9 / S-311 FOR FND REINF


3'-0"

#4x ASTM A706 DWLS @12", TO MATCH FND WALL INTERSECTION

EQ
WALL ABOVE REINF REQUIREMENTS

T
BEND DOWN, TYP

1 ' -6 "
#4x5'-0" @12",
FORMSAVER CONT KEY, TYP
2" CLR

CONT WALL REINF TO END

EQ
2 AT SECOND CTR ON CSJ
LTS

OF WALL STEP
S-313 LEVEL SOG SECOND LEVEL

EQ
DESIGNERS: KH/AM

HORIZ WALL
B T > 16" REINF
4 1/2"

1 1/2"
Project Number: 2011101.00
EDGES MAY BE
#4xCONT, TYP L3x3x1/4 CONT W/ ANGLED AT
LTS + 1'-0"

Drawn By: KH/AM

EQ EQ EQ
1/2x4" HAS @ 24" CONTR'S OPTION
A Reviewed By: KH
INTERMITTENT 1'-0"

T 8"
LONG KEYS @ 2'-0" OC Approved By: PD

#5@12"OC
SEE ELEVATION T 16" B
NOTES:
PROJECT MANAGER: KH

FOR REINF
1. CLEAN SURFACES AND REMOVE LAITANCE
MM JOB #: 23616.S.01

8" 1'-0" 2. WET SURFACE AND REMOVE STANDING WATER PRIOR TO PLACING CONCRETE
TYP FOUNDATION WALL DETAILS
PRINCIPAL: PD

BP
BP
003
003
A
EOR: PD

THRESHOLD AT SOUTH CORE FND


20 NO SCALE WALL TRANSITION 16 NO SCALE
WALL 12 NO SCALE WALL STEP AT SOUTH CORE 8 NO SCALE TYP WALL VERTICAL CONST JOINT
S-311
TYP PL WASHERS 1/2x2x2 2" 2"
C:\Proj\2011101_structural_kevinh.rvt 9/16

3" 2"
W/ STD HOLE 2" 1'-0" 6"
(5/16)
TYP 3'-0"
(5/16)

8"

2"
9/16

2"

4 1/2"
3"
WASHER WELD NOT

2" 3"
STEP B/WALL
TYP REQD BTWN PLATES T/ WALL
5/16 SEE PLAN
PL WASHER 1/2x2x2 1'-2" (5/16)
TYP T/ WALL
W/ STD HOLE (2) SIDES (5/16) 2

LTS
2" 2" SEE PLAN
SECTION A 3/16 TYP S-312
TYP
A 5/16

3"
(2) SIDES #5@12" OC EW

2"
2"
TYP 3/16 ABOVE BL
PL 3/8x5 ES
PL 3/8x5 ES, NOTCH
PL 1 1/2 W/ (8) 3/4" AT COL WELD
ANCHOR BOLTS IN PL 1 1/2 W/ (10) 3/4" 3"
SECTION A
1 5/16" HOLES ANCHOR BOLTS IN 1 5/16" The Lane Center for
HOLES 3" 2" #5@12" VERT EF, INSIDE

LTS
Academic Health
POST, SEE PLAN LAYER AS SHOWN
2" CLR, TYP Sciences
NOTCH PL CURTAINWALL SHALL BE EXTERIOR University of Colorado at
OVER WELD SUPPORTED ON CONCRETE STAIR #5@12" HORIZ EF, Colorado Springs
AT BASE OF WALL TYP #6 DOWELS AT 12" EF

3'-0"
OUTSIDE LAYER AS 2011101.00
PROVIDE 8" WIDE BLOCKOUT IN #5@10" VERT SHOWN
COUNTERFORT FOR GRADE #6x AT 12" OC
BEAM REINF TO EXTEND #5@12" HORIZ
THROUGH. CONTINUE ALL 7 7/8"
Owner
CONTERFORT REINF THROUGH Facilities Services
BLOCKOUT. GRADE BEAM BELOW, PROVIDE

2'-6" MAX
University of Colorado at Colorado Springs
3 5/8"

3" BP CORNER REINF PER 9/2-311 Campus Services Building, Rm 212

2 ' -3 "
ADD 003 1420 Austin Bluffs Parkway
005 Colorado Springs, CO 80918
A #5@12" VERT EF, INSIDE 719-255-3505
MECH YARD WALL CONN TO FND
17 NO SCALE EAST CW BP VARIES 9 NO SCALE
WALL
LAYER AS SHOWN

SEE 1 / S-213 Architect


CSJ AT AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
CONTR Denver, CO, 80211
OPTION 303-294-9448

2'-6"
NOTCH PLATE OVER WELD 6"
SEE PLAN #10@8" HORIZ EF,
6 OUTSIDE LAYER AS Clinical Planning
S-320 SHOWN
James W Nakai & Associates, PC

4'-6"
T/ BL 520 E Colorado Ave
#5@9" VERT TYP, (6) #5@4" SEE PLAN Colorado Springs, CO 80903
SEE 2 / S-311 FOR EF AT POST, CTR ON POST, 719-635-2142
FND WALL REINF SEE 1/S-213 FOR LOCATIONS

#5@8" CLOSED TIES Civil


(8) #10 VERT TerraNova Engineering, Inc.
815 S 25th Street
(2) #5, EF

OMIT TYP WALL VERT BARS


Colorado Springs, CO 80904
719-635-6422

OVER THIS LENGTH


(2) #10 T&B

3" CLR
SEE PLAN
Landscape
4" VOID FORM T/ PIER Lime Green Design, Inc
SEE FND NOTES 4" VOID FORM
SEE PLAN 900 E. Louisiana Avenue, Suite 209
SEE FND NOTES T/ PIER Denver, CO 80210
303-733-7558
SEE PLAN

SEE PLAN Structural


#4@20" TIE SETS Martin/Martin
W/ (2) TIES AT 3" 12499 West Colfax Avenue
OC AT TOP OF Lakewood, CO 80215
303-431-6100
PILASTER SEE PLAN
SEE ELEVATION FOR
CIP SHEAR WALL REINF SEE PLAN Mechanical/Plumbing
BP BP BP
BP Shaffer Baucom Engineering & Consulting
003 003 003
003 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
NORTH CORE COUNTERFORT AT 303-986-8200

18 NO SCALE
WALL 14 NO SCALE SOUTH FOUNDATION WALL SECTION 10 NO SCALE TYP EDGE PILASTER 6 NO SCALE MECH YARD FND WALL - WEST 2 NO SCALE MECH YARD FND WALL - EAST
PL WASHER 1/2x2x2 2" 2" Electrical
2" 1'-0" 6"
W/ STD HOLE BRICK LEDGE BELOW
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
2"

Lakewood, CO 80235
9/16
2"

303-986-8200
4 1/2"
3"

(5/16)
TYP OMIT TYP WALL VERT T/ WALL
(5/16) Technology
TYP BARS OVER THIS SEE PLAN
Rimrock Group
5/16 LENGTH
2'-10"

(2) SIDES (12) #10 VERT 10807 New Allegiance Drive, Suite 400
Colorado Springs, CO 80921

3"
TYP 3/16 (2) ADDNL #10 BARS T&B 719-533-1112
3"

PL 3/8x5 ES, NOTCH PL #4@20" TIE SETS W/


2"
2"

AT COL WELD (2) TIE SETS AT 3" Building Performance Engineer


DRILLED PIER DOWELS, 6
LTS
PL 1 1/2 W/ (10) 3/4" ANCHOR SECTION A OC AT TOP OF SEE 12 Ambient Energy
SEE PLAN

S-312
BOLTS IN 1 5/16" HOLES 3" PILASTER S-310
130 W 5th Ave
#5@12" HORIZ Denver, CO 80204

3 ' -0 "
303-278-1532
WASHER WELD NOT REQD
BTWN PLATES #5@10" VERT
#5@12" VERT EF, INSIDE Cost Estimating
2" CLR, TYP
LAYER AS SHOWN Parametrix, Inc.
7186 South Highland Drive
A Salt Lake City, UT 84121
3"
SEE 1 / S-213 801-733-5900
#10@8" HORIZ EF,
NOTCH PL OVER WELD CJ TYP WALL REINF U-BAR, MATCH SIZE AND OUTSIDE LAYER AS
SPACING OF HORIZ BARS SHOWN 6"
1'-6"

#4 CLOSED STIRRUPS
W/ (4) LEGS AT 6" 0.C.
(2) #5 EF SEE PLAN
T/ BL
(4) #7 T&B SEE PLAN

BP BP BP
003 003 003

15 NO SCALE SOUTH FOUNDATION WALL GR BM 11 NO SCALE TYP CORNER PILASTER 7 NO SCALE MECH YARD FND WALL PLAN - WEST

4 3.9 Issue Date


3" MAX

BP#2 NOVEMBER 16, 2012


SIM 10
S-314 BP#3 DECEMBER 21, 2012
AT THRESHOLD ADDENDUM 005 JANUARY 25, 2013
A.6 RECORD DRAWINGS APRIL 18, 2014
DATE PRINTED: 4/18/2014 9:09:58 AM

CONT GRADE BM
#7@12"OC VERT
HORIZ REINF

#5@18" OC EW, EF
#7@9"OC HORIZ
LTS

3" CLR
DESIGNERS: KH/AM

SEE PLAN

#4@12" TIES W/ (2)


TIES AT 3" OC AT 4" VOID FORM
TOP OF PILASTER SEE FND NOTES T/ PIER
CONT WALL SEE PLAN Project Number: 2011101.00
HORIZ REINF
Drawn By: KH/AM

B Reviewed By: KH
CONT HORIZ WALL SEE PLAN
(8) #6 VERT REINF TO FAR Approved By: PD

SEE PLAN FACE AND HOOK

9
PROJECT MANAGER: KH

S-311
SEE FOR TYP
MM JOB #: 23616.S.01

FND WALL CORNER


REINF FOUNDATION WALL DETAILS
PRINCIPAL: PD

BP ADD ADD
003 005 005
EOR: PD

16 NO SCALE PILASTER AT B/6.5 12 NO SCALE PILASTER AT B4 8 NO SCALE TYP ELEVATOR PIT ON GRADE 4 NO SCALE MECH YARD FND WALL - NORTH
S-312
2" CLR
C:\Proj\2011101_structural_kevinh.rvt #4xCONT, TYP
DP CL
3'-0"
1'-1" 1'-1"

3'-0"
#4x ASTM A706 DWLS @12",
(8) #7 BEND DOWN, TYP
#5xCONT AT TYP, CTR SKEW HOOKS AS REQD
IN STEM

SOG THK
TO MAINTAIN COVER

1'-1"
HOOK T&B BARS #4x @18" OC AT TYP AT SECOND LEVEL
FROM GR BM ADDNL STIRRUP T/BL = SEE PLAN
ES OF OPNG NO BRICK LEDGE .
DP CL AND STEM AT SIM SEE PLAN SEE PLAN
LTE LTE

D.1
#5@8" EW LOC OPNG WITHIN
#4@12" T/BL = SEE PLAN
THUS DP CL
LTS

MIDDLE THIRD OF

1'-1"
#5@12" OC VERT
3 3/8"

2" CLR TYP BEAM DEPTH


SEE PLAN SEE PLAN #5@9" OC HORIZ,

1'-6"

D
#5@8" SIDE CTR IN GR BM The Lane Center for

LTE MIN
THUS SLEEVED PEN SIZE
LTS

#5x @12" OC (1) #10 T&B Academic Health


3 3/8"

SHALL NOT EXCEED

2" CLR
D/6, SPACE #5@12" OC HORIZ Sciences
MULTIPLE PEN'S AT T/PIER University of Colorado at
3xDIA OC MIN Colorado Springs
(2) #10 T&B
ADDNL #6@12" (2 2011101.00
MIN) ABOVE AND 4" VOID FORM.
T/PIER SEE FND NOTES
1'-6" BELOW OPNG

BP
Owner
003 4" VOID FORM. TYPICAL - AT BRICK LEDGE Facilities Services
BP 1.5 SEE FND NOTES University of Colorado at Colorado Springs
Campus Services Building, Rm 212

2" CLR
003 #4xCONT, TYP 1420 Austin Bluffs Parkway
Colorado Springs, CO 80918
719-255-3505
TYP GRADE BEAM - SLEEVED
17 NO SCALE PILASTER AT SW VESTIBULE - 3 13 NO SCALE PILASTER AT SE VESTIBULE 9 NO SCALE 5 NO SCALE GRADE BEAM - 2
3'-0"

3'-0"
OPENING #4x ASTM A706
Architect
DWLS @12" BEND
SKEW (2) DOWN, TYP AndersonMasonDale Architects, P.C.

8"
STIRRUPS AT ALIGN FACE OF GR 3198 Speer Boulevard
FND WALL GRADE BEAM Denver, CO, 80211

LTS
END OF GR BM AND FACE OF #5@8" EW THUS

2 7/8"
303-294-9448
BM ALIGN PILASTER W/ PILASTER
FACE OF GR BM LTS LTS

LTS
#5@8" SIDE THUS AT SECOND LEVEL

2 7/8"
EXTEND TOP REINF Clinical Planning
(16)#7 VERTS
2" CLR

TO END OF CURB AT . James W Nakai & Associates, PC


HOOK GR SIM 520 E Colorado Ave
BM BARS Colorado Springs, CO 80903
#4 TIE SETS @12" MATCH SIZE AND 719-635-2142
NUMBER OF BM
TOP REINF
10"

Civil

1'-4"
TerraNova Engineering, Inc.
D 815 S 25th Street
Colorado Springs, CO 80904
1'-3 1/4"

719-635-6422
9 DP CL
ABOVE CAP MATCH SIZE AND
S-311
NUMBER OF BM
SIDE REINF Landscape
DP CL
Lime Green Design, Inc

1'-8"
900 E. Louisiana Avenue, Suite 209
Denver, CO 80210
MATCH SIZE AND
2'-1 1/4"

2" CLR 2" CLR TYP 7/8"

303-733-7558
NUMBER OF BM
BOT REINF
VOID FORM, SEE Structural
FND NOTES
HOOK ENDS OF (3) #4 SEE PLAN Martin/Martin
12499 West Colfax Avenue

1'-1"
GR BM BARS DP CL
1'-4" 6" 1'-2"
AT STOREFRONT/CURTAINWALL Lakewood, CO 80215
303-431-6100
4" 2'-1" 2'-5" 3"
LTE 3". NOTES:
E 8 Mechanical/Plumbing
DP CL 1. SEE FOR POUR LENGTH LIMITS AND CONTROL JOINT DETAILS.
BP
003
1 BP
003 1.5 ADD
005
BP
003
S-313 Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

18 NO SCALE PILASTER AT SW CORNER 14 NO SCALE PILASTER AT SW VESTIBULE - 1 10 NO SCALE TYP GRADE BEAM TO FND WALL - 1 2 NO SCALE TYP GRADE BEAM
Electrical
Shaffer Baucom Engineering & Consulting
GRADE BEAM 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200
DP DOWELS NOTE 2 60'-0" MAX
Technology
Rimrock Group
10807 New Allegiance Drive, Suite 400
HOOK ENDS OF MATCH SIZE AND Colorado Springs, CO 80921
GR BM BARS NUMBER OF BM 719-533-1112
TOP REINF

Building Performance Engineer


NOTE 2 Ambient Energy

60'-0" MAX
130 W 5th Ave
Denver, CO 80204
303-278-1532
MATCH SIZE AND
DP CL NUMBER OF BM B
SIDE REINF Cost Estimating
Parametrix, Inc.
7186 South Highland Drive
3"

Salt Lake City, UT 84121


MATCH SIZE AND 801-733-5900

HOOK ENDS NUMBER OF BM VOID FORM, SEE


OF GR BM BOT REINF FND NOTES
BARS
NOTES:
1. SUBMIT LOCATIONS OF CONST JTS FOR REVIEW PRIOR TO CONSTRUCTION
9 1/2" 6 1/2" 3". 3" 2. LOCATE CONST JTS AT LEAST 5'-0" FROM PILASTERS AND CORNERS. AT GR BEAMS,
JT SHALL BE IN MIDDLE THIRD OF SPAN

BP
DP CL
ADD 003 ADD
005 005
3"
19 NO SCALE PILASTER AT SE CORNER 15 NO SCALE PILASTER AT SW VESTIBULE - 2 11 NO SCALE TYP GRADE BEAM TO FND WALL - 2

1ST POUR 2ND POUR A


Issue Date
1 1/2"
DESIGN DEVELOPMENT SEPTEMBER 12, 2012
BP#2 NOVEMBER 16, 2012

EQ
BP#3 DECEMBER 21, 2012
ADDENDUM 005 JANUARY 25, 2013
A RECORD DRAWINGS APRIL 18, 2014

EQ
DATE PRINTED: 4/18/2014 9:10:00 AM

ADDNL STIRRUP ES

EQ
2" MAX, AS REQD

EQ
2" CLR TOP

T
CONTINUE GRADE BEAM

1 ' -6 "
REINF THRU CAP CONT KEY, TYP

EQ
T/CAP = SEE PLAN

EQ
LAP LTE
DESIGNERS: KH/AM

EQ
1 1/2" TYP

SEE PLAN

2" CLR SIDES T > 16"


#5@12" HORIZx E
W

ADDNL #5@12"
(2 MIN)
1 1/2"
EDGES MAY BE Project Number: 2011101.00
#5@12" T&B REINFx
ANGLED AT LTE LTE Drawn By: KH/AM

EQ EQ EQ
EW CONTR'S OPTION

EQ
LAP LTE

Reviewed By: KH
T&B REINF TO RUN

T 8"
THRU JOINT Approved By: PD
2" CLR BOT

UNINTERRUPTED
VOID FORM BELOW T 16"
CAP OUTSIDE NOTES:
PROJECT MANAGER: KH

PIER, SEE FND A 1. CLEAN SURFACES AND REMOVE LAITANCE


MM JOB #: 23616.S.01

NOTES 2. WET SURFACE AND REMOVE STANDING WATER PRIOR TO PLACING CONCRETE LOCATE IN MIDDLE
3" UNO TYP GRADE BEAM DETAILS
THIRD OF SPAN
PRINCIPAL: PD

A B
EOR: PD

16 NO SCALE TYP GRADE BEAM AT COLUMN 8 NO SCALE TYP GRADE BEAM CONST JT
S-313
C:\Proj\2011101_structural_kevinh.rvt SEE GENERAL
CONTROL JOINTS NOT PERMITTED NOTES FOR POUR
LENGTH AND AREA
LIMITS
T = 5 1/2": NONE
#4x12'-0" @12", T = 10": #4@12"OC EW TOP
2" 8'-0".
FORMSAVER TYP SLAB 2
~ 11

1" CLR
6
REINF S-314 CONTROL OR

2" CLR
CTR ON CSJ T = 5 1/2": #5@12" OC EW BOT S-314 S-314
CONSTRUCTION JT

~
T = 10": #6@12"OC EW BOT

3" CLR
7

T
S-314

1" CLR
10'-0" MAX EW
MAX ASPECT
PROVIDE TYP RATIO = 1:1.5
BAR SUPPORTS, TRIM REINF AT
SEE SPEC ALL OPNGS,
12
The Lane Center for

NOTE 1
S-314
#4xCONT NOTCHES, AND 4 Academic Health
RE-ENTRANT
CORNERS
S-314 Sciences
University of Colorado at
3'-0" CONT VAPOR
Colorado Springs
RETARDER, SEE ARCH PROVIDE JT EW AT 2011101.00

3'-0"
8
#4x AT 12" ALL RE-ENTRANT S-314
CORNERS 10
A706 AND FIELD BEND DOWN S-314
NOTES:
1. PREPARED/COMPACTED SUBGRADE, SEE EARTHWORK SPEC FOR REQUIREMENTS. SEE NOTES: Owner
PLAN FOR EXTENT AND DEPTH OF OVEREXCAVATION AND RECOMPACTION. 1. KEY PLAN ILLUSTRATES CONSTRUCTION CONCEPTS ONLY. SEE PLAN FOR ACTUAL DIMENSIONS AND ARRANGEMENT Facilities Services
University of Colorado at Colorado Springs
2. PROVIDE ADDITIONAL CONTROL JOINTS AT ABRUPT CHANGES IN THICKNESS AND LOCATIONS PRONE TO CRACKING. COORD LOCS WITH FLOOR FINISHES AND INTERIOR WALLS Campus Services Building, Rm 212
BP ADD BP
003 005 1420 Austin Bluffs Parkway
003
Colorado Springs, CO 80918
719-255-3505

13 NO SCALE SOG AT T/ WALL 9 NO SCALE TYP SOG - SECOND LEVEL 5 NO SCALE TYP SOG KEY PLAN
Architect
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
Denver, CO, 80211
303-294-9448
DIAMOND OR

SEE ARCH, MECH, AND ELEC


LTS + H ROUND

4"
TY MIN

MI
BLOCKOUT Clinical Planning

N
P
4"
CONST JOINT T = 4": WWR 6x6-W2.9xW2.9
2'-0" HOOK James W Nakai & Associates, PC
T = 5": #4@18" OC EW

H
90 520 E Colorado Ave
Colorado Springs, CO 80903
6" MIN CL COL

3" CLR TYP


719-635-2142

90

90
COLUMN

1 1/2" CLR
MATCH TOP REINF TOOLED JT AT BAR SUPPORTS,
ANCHOR RODS BY CJ OR EXPOSED AREAS COLUMN OR SEE SPEC Civil
EQUIP MNFR TOP REINFORCING CONST JT PILASTER
ISOLATION JT TerraNova Engineering, Inc.

T
A 815 S 25th Street
Colorado Springs, CO 80904
A 719-635-6422

1'-0"
PLAN AT COLUMN PLAN AT PILASTER

NOTE 1
7 CONTR OPTION A706 AND FIELD BEND DOWN CONT VAPOR Landscape
FIRST POUR
S-314 3'-0"

3" CLR
RETARDER, SEE ARCH Lime Green Design, Inc
7 COLUMN FACE 900 E. Louisiana Avenue, Suite 209

3'-0"
2" #4x @12" TOP S-314 Denver, CO 80210
A 7 TYPICAL SLAB-ON-GRADE SECTION 303-733-7558
#4@12" T&B EW S-314

8"
3" CLR Structural
#4x4'-0@12", EC,
Martin/Martin
CTR EQ

2" CLR
12499 West Colfax Avenue
SECTION AT COLUMN CONCRETE ENCASEMENT Lakewood, CO 80215
(1) #4xCONT 303-431-6100
TO COVER COL BASE,
NOTES:
TYPICAL A TYP
1. PREPARED/COMPACTED SUBGRADE, SEE EARTHWORK SPEC FOR REQUIREMENTS.
SEE PLAN FOR EXTENT AND DEPTH OF OVEREXCAVATION AND RECOMPACTION. Mechanical/Plumbing
BP BP BP Shaffer Baucom Engineering & Consulting
003 003 003 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
TYP SOG BLOCKOUT AT 303-986-8200
14 NO SCALE TYP SOG ISOLATED EQUIP PAD 10 NO SCALE TYP SOG EXT THRESHOLD 6 NO SCALE
COLUMN/PILASTER 2 NO SCALE TYP SOG
Electrical
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

Technology
Rimrock Group
1 1/2" 10807 New Allegiance Drive, Suite 400
STAIR STRINGER AND EDGES MAY BE Colorado Springs, CO 80921
CONN TO SOG BY STAIR ANGLED AT 719-533-1112

EQ EQ EQ
MNFR CONTR'S OPTION

T
ELASTOMERIC JT

8"
Building Performance Engineer
SEALANT WHERE Ambient Energy
REQD (SEE ARCH) 130 W 5th Ave
Denver, CO 80204
NOTES: 303-278-1532
1. CLEAN SURFACES AND REMOVE LAITANCE
2. WET SURFACE AND REMOVE STANDING WATER PRIOR TO PLACING CONCRETE
Cost Estimating

1'-0" MIN
Parametrix, Inc.
1/4" PREFORMED JT A 7186 South Highland Drive
Salt Lake City, UT 84121
FILLER OVER FULL SLAB 801-733-5900
DEPTH, FILLER SHALL
(3) #4xCONT NOT PROTRUDE ABOVE
SLAB
2'-0" 2'-0"

3" CLR
#4x @24"
2'-0" (MIN), EXTEND
THICKENED ZONE 1'-0" AT T 6" AT T < 6"
BEYOND STRINGERS
1ST POUR 2ND POUR
#4 ES CONT
6"
SLAB REINF LAP (2) MESH
11 NO SCALE TYP SOG BELOW METAL STAIR 7 NO SCALE TYP SOG ISOLATION JOINT A PANELS OR LTS

T
T
Issue Date

DESIGN DEVELOPMENT SEPTEMBER 12, 2012


RE-ENTRANT CORNER: 1 BP#2 NOVEMBER 16, 2012

2" MIN
DIAG BARS 2 BP#3 DECEMBER 21, 2012
1" CLR ADDENDUM 005 JANUARY 25, 2013
VARIES
1" CLR

RECORD DRAWINGS APRIL 18, 2014


DATE PRINTED: 4/18/2014 9:10:01 AM

WWR 6x6-W2.9xW2.9
CONSTRUCTION JOINT CONT VAPOR

2'-0" TYP
(2) #4 TYP
2" CLR

NOTE 1 RETARDER,
1/8" . SEE ARCH
EXTEND REINF
12" THRU JT
#3x @16" W/(4) #4xCONT
TYPICAL
DESIGNERS: KH/AM

1 1/4" AT T = 5"
12"

1" AT T = 4"
Project Number: 2011101.00

ADHESIVE ANCHOR Drawn By: KH/AM


CONTROL JOINT
Reviewed By: KH
NOTES:
1. PROVIDE TOOLED JT OR SAW CUT AS SOON AS THE CONC HAS HARDENED SUFFICIENTLY Approved By: PD
OPENING
3"

TO PERMIT CUTTING WITHOUT CHIPPING, SPALLING, OR TEARING (BUT NOT MORE THAN 12
NOTES: HOURS AFTER CASTING)
POST-INSTALLED REBAR OPTION 1. DETAIL APPLIES FOR ALL OPNGS IN SOG'S AND SLABS ON METAL DECK
PROJECT MANAGER: KH

2. REINF NOT REQUIRED AT OPNGS SMALLER THAN 10"x10"


MM JOB #: 23616.S.01

3. SEE OTHER DTLS FOR REINF AT OPNGS IN CONC WALLS, CONC STR SLABS, AND METAL
DECK SLABS TYP SOG DETAILS
PRINCIPAL: PD

BP BP
003 003
EOR: PD

12 NO SCALE TYP SOG EQUIP PAD 8 NO SCALE TYP TRIM REINF 4 NO SCALE TYP SOG JOINTS
S-314
C:\Proj\2011101_structural_kevinh.rvt 1 1/2" 1" 2" 5" 5" 2" AT WALL END 8

AT PILASTER
4 7 AT SKEWED 1 1/2" EMBED & BEAM CL T/CONC S-315 TYP EMBEDDED PL SCHED**
S-315 S-315 CONNS A DO NOT WELD CAPACITY (KIPS)* D L TOTAL
BEAM

1'-0" MIN
13/16"x2 3/4" SLOTTED HOLE ACROSS TOP WHERE 10 (IN) (IN) # HAS
6" STUDS 8" STUDS
IN L, STD HOLE IN BM OF ANGLE EDGE OF

2"
LESS S-315
#6x2'-4", EMBED T/PL = T/BM, TYP C8, W8 10 10 12 6 4
CONC
SUPPLIER TO TIE IN
PLACE CENTERED ON C10, W10 10 10 12 6 4
3
AT TOP
PLATE, WELDING NOT TYP BASE PLATE SCHEDULE CORNER C12, W12 25 25 12 8 4
PL 3/4

EQ
PERMITTED S-315
EDGES

1 1/2" T&B
BASE PLATE PLATE PLATE 3/4" RETURN W14 33 33 14 9 6
PLATE THICKNESS WIDTH LENGTH 3/4" HAS, TYP, SEE TOP, FULL W16 39 39 16 10 6
2'-0" MIN
MARK T (IN) B (IN) N (IN) SCHEDULE FOR LENGTH RETURN 5/16

EQ
L6x6x1/2 x CONT

D
L
AND TOTAL # BOT W18 40 50 18 12 6
BP1 1 12 12
L6x3 1/2x3/8, (2) PT 2 W21 46 56 21 14 8
BP2 1 1/2 13 13 BOLTS, CENTER S-315

EQ
VERTICALLY ON BM W24 46 64 24 16 10 The Lane Center for
WHERE
BP3 1 17 17 3 SIDES, LESS W27 50 68 27 18 12 Academic Health
3/16
5/16 NOTE 1 W30 55 73 30 18 14
3/16 BP4 3/4 10 10 Sciences
TRIM FLG T&B, ONE SIDE

2"

2'-0" MIN
AT BOT W33 55 74 33 20 14 University of Colorado at
BP5 1/2 16 9 ONLY, AS REQD FOR FIELD 6 WHERE 6
CORNER Colorado Springs
PL3/8x8x8 W/(2) 1/2" WELDING CLEARANCES EMBED ELEVATION S-315 LESS S-315 W36 58 77 36 20 16
B/CONC EDGES 2011101.00
HAS (BOT) AND (2) #4 BP6 3/4 13 13 BEAM ELEVATION * SERVICE LEVEL (ASD)
(A706) (TOP) @ 4'-0" A
OC MAX AND 1'-0" BP7 1 16 16 NOTES: ** EMBEDDED PLATE TYPE IS BASED ON BEAM DEPTH. IF
FROM END 1. COMPLETE ALL WELDS PRIOR TO INSTALLING DECK OR USING BEAM TO SUPPORT ANY CONSTRUCTION MATERIALS PLAN REACTION IS GREATER THAN SCHEDULED CAPACITY,
MINIMUM CONCRETE EDGE DISTANCES AT WALLS Owner
BP8 1 1/2 22 22 SEE 6 / S-316 REQUEST CUSTOM CONNECTION FROM ENGINEER
11
2. SEE FOR WELDING OF REBAR TO EMBED PLATES WHEN REQUIRED. DAS MAY BE SUBSTITUTED FOR REBAR. NOTES: 6" LONG STUDS SHALL BE USED AT 8" THICK WALLS. Facilities Services
S-315 University of Colorado at Colorado Springs
Campus Services Building, Rm 212
ADD
1420 Austin Bluffs Parkway
005
Colorado Springs, CO 80918
N 719-255-3505

17 NO SCALE STUD SUPPORT AT PH WALL 5/16 9 NO SCALE TYP BM EMBED PL CONN & SCHEDULE

2" TYP
Architect
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
HSS OR PIPE COLUMN Denver, CO, 80211
303-294-9448

B
REPLACE ALL

0" TO 1'-0"
HAS W/ #6 (A706)
Clinical Planning

LTS
(5/16) #6x2'-4", EMBED 5"
8" TO 2'-0" James W Nakai & Associates, PC
1 1/2"

SUPPLIER TO TIE IN 520 E Colorado Ave

4 MAX
1 1/2"
PLACE CENTERED ON Colorado Springs, CO 80903
719-635-2142
PLATE, WELDING NOT 1 1/2" #6 T & B (A706)
REMOVE ERECTION BOLT
PERMITTED
FROM CONN ANGLE ON FAR 4 MAX
SIDE Civil
W8-W18: (3) #6

5"
PL1/2x6x6 REPLACE TOP (2) TerraNova Engineering, Inc.
W21-W36: (3) #8

T
HAS w/ (2) #6 (A706) ADDNL #6 FOR W27 & ABOVE 815 S 25th Street

1'-0"
A706 Colorado Springs, CO 80904
719-635-6422

RET BOT
5/16
Landscape
Lime Green Design, Inc
900 E. Louisiana Avenue, Suite 209
Denver, CO 80210
1'-0"

AT HSS OR PIPE COL 303-733-7558


LESSER OF:
LTS
1) LDH
20 2) FAR FACE OF EDGE OF CONCRETE Structural
FOR ADDNL INFO CONC LESS 2" Martin/Martin
S-315

4" TO 2'-0"
12499 West Colfax Avenue
N Lakewood, CO 80215
B/CONCRETE 303-431-6100
NOTE 3
5/16 SINGLE SIDED BACK-TO-BACK
3/4" ANCHOR RODS, Mechanical/Plumbing
UNO Shaffer Baucom Engineering & Consulting
RFC136 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235

B
PL WASHER 5/16x2x2 W/
18 NO SCALE DRAG BEAM CONN W/ SIDE PLATE STD HOLE 10 NO SCALE TYP BM EMBED NEAR T/WALL 6 NO SCALE TYP BM EMBED NEAR B/WALL 2 NO SCALE TYP BM EMBED NEAR EDGE OF WALL
303-986-8200
4" TYP

9" Electrical
PL3/4x9x12 W/ (4) 5/8" THREADED RODS
IN OVS HOLES, AT INSIDE FACE OF WALL. 1 5/16" HOLES IN 2 1/2" TYP
Shaffer Baucom Engineering & Consulting
BASE PLATE 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
PL3/16x2x2 WASHER, TYP A 303-986-8200
PROJECTION
ABOVE NUT
1 1/2" TYP

2" MIN

PL3/8x4 1/2x8 CTR ON HSS, ES


Technology
5/16 A
1'-0"

TYP Rimrock Group


5/16 FOR HAS AND 10 10807 New Allegiance Drive, Suite 400
Colorado Springs, CO 80921
HOOKED BARS S-315 719-533-1112
(2) SIDES
3/16 TYP
(E) L BENT PL 3/8xL ~
L
1 1/2" NS GROUT
T

4 1/2" 4 1/2" (E) STOP WELD (2) D


1'-6" MIN

OPTIONAL LEVELING Building Performance Engineer


BAR DIA'S BEAM WEB
NUTS Ambient Energy
AT WEST WALL FROM BEND

6"
130 W 5th Ave
DOUBLE NUT OR Denver, CO 80204
HEADED ANCHOR ROD 303-278-1532
BAR SIZE E L BAR SIZE D
PL3/8x9x12 ON OUTSIDE FACE OF SHAFT.
#3 3/16 2 #3 1/4 3 1/2"
Cost Estimating
7/8" HAMMER DRILLED HOLE. LOCATE TYPICAL #4 1/4 2 1/2 #4 5/16 Parametrix, Inc.
WALL REINF PRIOR TO DRILLING. DO #5 5/16 3 #5 3/8
7186 South Highland Drive
Salt Lake City, UT 84121
NOT CUT OR DAMAGE REINF. REPAIR 801-733-5900
SPALLED CONCRETE PER SPEC. NOTES: #6 3/8 3 1/2 #6 7/16
1. SEE COLUMN SCHEDULE OR PLAN FOR BASE PLATE MARK #7 7/16 4 #7 1/2 FOR HORIZ
2 1/8"

2
2. PLATE SIZE MAY BE INCREASED AT HSS COL TO PROVIDE BOLT CLEARANCE #8 1/2 4 1/2 #8 9/16
1 1/4" MAX PROJECTION AT EAST WALL.
.

S-315 BARS
3. ALL AROUND WELD MAY BE USED IN LIEU OF THE WELD SHOWN
1" 1/2"

CHIP OUT CONCRETE 1" MAX, AS


8"

REQUIRED, RECESS PLATE AND GROUT. NOTES:


NOTES: 1. REQUEST CONN FROM ENGINEER IF > 45
1. ALL WELDED REBAR SHALL BE A706

BP (3) SIDES BP ADD


RFC 064 003 005
003 5/16 TYP
TYP BM EMBED NEAR TOP-EDGE OF
19 NO SCALE STRUT TO WALL CONN 15 NO SCALE TYP COL BASE PLATE - GRAVITY 11 NO SCALE TYP REBAR WELD SCHEDULE 7 NO SCALE TYP BM EMBED AT SKEWED BM 3 NO SCALE
WALL
1 1/2" 1" A PL1/2x7x5 SHORT DIM EQ EQ EQ
1 1/2" PERP TO BM Issue Date
4
3/16 4 BP#2 NOVEMBER 16, 2012
1 1/2"

3 SIDES S-300
5/16 3/16 4 BP#3 DECEMBER 21, 2012
ADDENDUM 005 JANUARY 25, 2013
PL 1 1/4 WITH
2" MIN TO

SEE 9 / S-315 FOR ANGLE ASI 001 FEBRUARY 19, 2013


OPNG

(8)#9 A706
AND SHEAR CONN REQTS RECORD DRAWINGS APRIL 18, 2014
DATE PRINTED: 4/18/2014 9:10:03 AM

3'-0" .
1'-0"

EXTEND REBAR 3-SIDES #5x @18"


LTE TOP INTO 5/16 TYP
WALL L4x3x1/4xCONT (LLV) #6 (A706), MATCH HAS
EMBED PL 3/8x8x8 W/ 3" 3" LAYOUT AND TOTAL
5/16 (4) 3/8"x6" HDAS @ 2 SIDES
TYP 1/4 NUMBER SHOWN IN BM

LTE
5/16
2"

4'-0" OC MAX WITHIN EMBED SCHEDULE


4 1/2"

1'-0" OF END
DESIGNERS: KH/AM

4"

OPTION #1 - EMBED PLATE


7" 5/16 PL 1/2 W/ (2) ANCHOR
TYP 5/8" HILTI KWIK BOLT
PL1/2x7x7 RODS, INSTALL
TZ (4" EMBED) @ 2'-0"
ANCHOR RODS AWAY
3" 3" 3" 3" OC. PLACE FIRST Project Number: 2011101.00
1 3/4"

E70XX
1/2" TYP

FROM DOOR
3"

5/8 EMBED & BEAM CL ANCHOR 6" (MIN), 1'-0" Drawn By: KH/AM
(MAX), AWAY FROM
3"

EDGE OF OPNG FOR WALLS BETWEEN 8" AND Reviewed By: KH


3'-0" . 15
FOR ADDNL INFO 14" THICK, PLATE WIDTH TO
EQ

5/16 S-315 MATCH WALL THICKNESS. FOR Approved By: PD


#5x @18"
5/16 4
6" MIN TO

WALLS THICKER THAN 14",


OPNG
2'-0"
EQ

L4x3x1/4xCONT (LLV) W/ PLATE WIDTH = 14"


11/16"x2 1/2" HORIZ SLOTS
PROJECT MANAGER: KH

IN VERT LEG
MM JOB #: 23616.S.01

EQ

5/16
4 OPTION #2 - POST-INSTALLED ANCHORS TYP STEEL TO CONCRETE
5/16
3"
PRINCIPAL: PD

ASI BP ADD CONNECTIONS


BP
003 001
A 003 005
EOR: PD

20 NO SCALE TYP DRAG BM CONN 16 NO SCALE TYP MTL DECK SLAB TO CONC WALL 12 NO SCALE OVERHEAD DOOR POST BASE PLATE 8 NO SCALE TYP BM EMBED AT END OF WALL 4 NO SCALE TYP BM EMBED AT PILASTER
S-315
C:\Proj\2011101_structural_kevinh.rvt

2"
WASHER TO BM CL
PL (2) SIDES 3/16

5"
SEE 9 / S-315 FOR BM
POST TO PL CONN TO EMBED, TYP
5/16

1" CLR

3 1/2" AT SIM
WASHER PL 1/4x1 1/2" T/SOG = 100'-0" PL3/4x14x21 W/(6)#6 A706 TYP,
(HDG) W/ STD HOLES PL3/4x14x27 W/(10)#6 A706 AT W24
THUS:
PL3/4x7x0'-10" (HDG) 2" 10" 2"
W/ (4) 1" HOLES T/GRADE BEAM = 99'-4"

1 1/2"

2"
1" NS GROUT TOUCH UP FIELD WELDED
AREAS WITH ZINC RICH
PRIMER
The Lane Center for

EQ
(4) 5/8" ADHESIVE
ANCHORS (HDG). EMBED Academic Health
12" WITH HILTI HY-150 Sciences
MAX-SD IN HAMMER University of Colorado at

2" TYP
DRILLED HOLE. DO NOT

EQ
Colorado Springs
CUT OR DAMAGE 1 1/2" TYP 5/16
2011101.00
EXISTING GRADE BEAM EMBED PL 1/2 W/ (4)
REINFORCING. PULL 3/4"x6" HAS THUS:

1"
TEST (1) ANCHOR TO 3

5"
8" 4"
KIP TENSION LOAD.
Owner
NOTES SEE 2 / S-315 FOR HORIZ BARS Facilities Services
8" University of Colorado at Colorado Springs
- SEE 6/A-405 FOR ADDITIONAL INFORMATION
4"

SEE 11 / S-315 FOR WELD REQTS Campus Services Building, Rm 212


ASI BP BP ASI
027 003 1420 Austin Bluffs Parkway
003 001 Colorado Springs, CO 80918
719-255-3505

9 NO SCALE GATE POST BASE 5 NO SCALE NE WINDOW SUPPORT 1 NO SCALE END OF WALL EMBED
Architect
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
Denver, CO, 80211
303-294-9448
3/8
SEE ARCH PL WASHER 3/8x3x3 W/ Clinical Planning
STD HOLE James W Nakai & Associates, PC
A 520 E Colorado Ave
FOR CJ 9 Colorado Springs, CO 80903
719-635-2142
REQTS S-540 BASE PL 1 1/2 W/ (8)
1" ANCHOR BOLTS
AND 1 3/4" HOLES Civil
BENT PL 3/8 W/ 6" TerraNova Engineering, Inc.
VERT LEG (HDG), 14 815 S 25th Street

2"
2'-4"
Colorado Springs, CO 80904
RE: 3 / S-316 S-313 719-635-6422

9"
SEE ARCH
Landscape
Lime Green Design, Inc
1/4"x1 1/2" HDG

4"
900 E. Louisiana Avenue, Suite 209

9"
PL WASHER Denver, CO 80210
303-733-7558
1/2"x4" EMBED STAINLESS

2"
STEEL EXP ANCHOR AT 12" FOR ADDNL 15
OC, 3" EA SIDE OF SPLICES, INFO S-315 Structural
(2) SIDES Martin/Martin
6" FROM END OF WALL
3/16 TYP 12499 West Colfax Avenue
Lakewood, CO 80215
HORIZ LSL HOLE 2" 9" 9" 2" 303-431-6100
AT BENT PL

Mechanical/Plumbing
BP ASI SECTION A Shaffer Baucom Engineering & Consulting
RFC 0145 003 001
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

10 NO SCALE POST INSTALLED BRICK SUPPORT 6 NO SCALE ROUND HSS BASE PL


Electrical
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200
ELASTOMERIC JOINT
SEALANT
5" Technology
SEE ARCH
Rimrock Group

2 1/2" MIN
PL1/2x8x10 W/ (4) 10807 New Allegiance Drive, Suite 400
PL 1/2x10x10 WITH (4) 3/4"

4" MIN
1/2"x4 1/2" EMBED 1" Colorado Springs, CO 80921
SCREW ANCHORS IN x 5" EMBED HAS. 1'-6" OC 719-533-1112
SEE LANDSCAPE AND 1'-0" MAX FROM ENDS
1" HOLES

2" TYP
Building Performance Engineer

3" TYP
WASHER PL1/4x1 1/2x 1 1/2

1/2"
3/16 Ambient Energy
WITH STD HOLE TYP T/PIER 130 W 5th Ave
Denver, CO 80204

6"
1'-3" MIN 9 303-278-1532
FOR CJ REQTS

4"
S-540
#4 x . SEE ARCH
14 Cost Estimating

1" MAX
S-503 Parametrix, Inc.
1"
(4) #4 ADHESIVE 7186 South Highland Drive

2" TYP
(2) SIDES, Salt Lake City, UT 84121
TYP 3/16 ANCHORS. (1) ES 801-733-5900
OF BASE PLATE
BENT PL 3/8 W/ 6"
CHIP OUT CONC AND GRIND VERT LEG (HDG)
SURFACE SMOOTH TO
RECESS PLATE BOTTOM OF CONCRETE IN
SOME LOCS, ALIGN B/PL
NOTES: WITH B/CONC
AESS PAINT SYSTEM SHALL BE INSTALLED ON COLUMN AND BASE PLATE PRIOR
TO ENCASING IN CONCRETE
RFC 0145 RFC 037

11 NO SCALE POST CONN AT STAIR LANDING - 2 7 NO SCALE COL BASE AT GRID E 3 NO SCALE BRICK SUPPORT AT CONCRETE

Issue Date
20
FOR EMBED
S-315
BP#3 DECEMBER 21, 2012
ADDENDUM 006 FEBRUARY 8, 2013
EXTEND ROOFING MEMBRANE ASI 001 FEBRUARY 19, 2013
ABOVE T/EMBED. SEE ARCH ASI 027 JUNE 13, 2013
RECORD DRAWINGS APRIL 18, 2014
DATE PRINTED: 4/18/2014 9:10:04 AM

RET TOP
5/16
PL TO
PL1/2x4x1'-3 FL 5/16 3
PL TO
T/INSULATION = SEE ARCH 5/16 8 FL
PL TO 5/16
EMBED 5/16
DESIGNERS: KH/AM

5"
T/STEEL = SEE PLAN

B/EMBED = 176'-2 Project Number: 2011101.00

Drawn By: KH/AM

1'-1"
Reviewed By: KH

FOR ADDNL CONN Approved By: PD


REQTS, SEE 9 / S-315
PROJECT MANAGER: KH
MM JOB #: 23616.S.01

STEEL TO CONCRETE
PRINCIPAL: PD

5/16 CONNECTIONS
RFC 061 .
EOR: PD

8 NO SCALE PENTHOUSE DRAG CONN


S-316
C:\Proj\2011101_structural_kevinh.rvt LTS + 18", TYP
W
16
B.4 3'-0" MAX
AT SOMD
S-315 B.4 ADD 1/2 NUMBER OF BARS
INTERRUPTED BY OPNG
ANGLE PER PLAN PLUS 1, SPACE AT 3" OC
PL1/2x6 W/ (2) BOLTS IN STD

FOR PLACING CONDUIT


ACCEPTABLE ZONE
HOLES. SEE ARCH FOR 1'-0" MIN C-C
HORIZ DIM MAX OD OF
CONDUIT IS 1 1/4"
3'-0"
#4(A706)x @12"OC PROVIDE U-BARS
AT OPNG EDGES,

LTS

4"
TO MATCH SIZE

H, 3'-0" MAX
#4xCONT AND SPACING OF
#5@12"OC VERT TYP WALL REINF
PL3/8 TO MATCH
ANGLE SIZE The Lane Center for

4"
.

Academic Health
HORIZ BARS TO 3/16 DETAIL SIMILAR 1'-0" MIN
TYP
3/16 5/16 FOR CIRCULAR FROM END Sciences

LTS
MATCH TYP WALL 5/16 University of Colorado at
REINF OPENINGS
SEE ELEV FOR Colorado Springs
WALL REINF 2011101.00
WALL REINF
(2) #5@3" OC T&B
NOTES:
1. DETAIL APPLIES UNLESS REINF IS SPECIFICALLY DETAILED ON THE DRAWINGS
Owner

2"
PL1/2x8x10 W/(4) Facilities Services
2" 4" 2" 1/2"x6" HAS TYPICAL OPENING CONDUIT IN WALL University of Colorado at Colorado Springs
Campus Services Building, Rm 212
BP BP
1420 Austin Bluffs Parkway
003 003
Colorado Springs, CO 80918
719-255-3505

17 NO SCALE LINK BM AT 8" WALL 13 NO SCALE CIP SHEAR WALL STEP 9 NO SCALE PERGOLA EMBED TO WALL 5 NO SCALE TYP CIP SHEAR WALL - PENETRATIONS
Architect
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
1" CLR Denver, CO, 80211
303-294-9448

2.6 Clinical Planning


PL WASHER 1/4x 2 1/2x 2 1/2
W/ STD HOLE #5 TIES @8" OC James W Nakai & Associates, PC
HORIZ REINF 520 E Colorado Ave
Colorado Springs, CO 80903

LTS
719-635-2142
(2) 3/4" ADHESIVE
ANCHOR RODS WITH 5" TRIM REINF LTS CONST JT LOCS
PENTHOUSE LEVEL
EMBED AT EACH ANGLE. 160'-0" WHERE SHOWN, SHALL NOT CONFLICT Civil

3"
FINGER TIGHTEN NUT, SEE CIP SHEAR WITH EMBEDDED

3"
TerraNova Engineering, Inc.
BACK OFF 1/4 TURN AND WALL ELEVATIONS PLATES, SUBMIT 815 S 25th Street
JOINT LOCATIONS Colorado Springs, CO 80904
DAMAGE THREADS.

3"
719-635-6422
FOR REVIEW

3 SIDES Landscape
1/4 SEE ELEVATION FOR Lime Green Design, Inc
REINF VERT REINF 900 E. Louisiana Avenue, Suite 209
Denver, CO 80210
2" MIN U-BAR SIZE & SPACING 303-733-7558
L6x6x3/8x1'-0" W/ (2) 1 1/2" LONG CLR, TYP TO MATCH HORIZ REINF
VERT SLOTTED HOLES IN VERT
LEG AT 8" SPACING. LOCATE Structural
ANGLE AT 1'-6" FROM END OF Martin/Martin
12499 West Colfax Avenue
WALL AND AT 4'-0" MAX SPACING Lakewood, CO 80215
303-431-6100

Mechanical/Plumbing
BP BP Shaffer Baucom Engineering & Consulting
003 003 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
DIAPHRAGM CONN AT PENTHOUSE 303-986-8200

14 NO SCALE
SOUTH WALL 10 NO SCALE SECTION AT OPNG IN CORE WALL 6 NO SCALE TYP CIP SHEAR WALL - END 2 NO SCALE TYP CIP SHEAR WALL - CONST JT
Electrical
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

U-BAR SIZE & SPACING


TO MATCH HORIZ REINF Technology
OF WALL B
Rimrock Group
WALL B 10807 New Allegiance Drive, Suite 400
#5@9"OC HORIZ U-BAR SIZE & SPACING WALL B Colorado Springs, CO 80921
TO MATCH HORIZ REINF 719-533-1112

U BAR SIZE AND


SEE ELEV FOR
SPACING TO MATCH
VERT REINF, TYP Building Performance Engineer
HORIZ REINF OF WALL B
LTS

Ambient Energy
WALL A TRIM REINF 130 W 5th Ave
Denver, CO 80204
CORNER BAR TO WHERE SHOWN, 303-278-1532

LTS
SEE ELEV FOR SEE CIP SHEAR
MATCH SIZE AND
VERT REINF WALL ELEVATIONS
SPACING OF HORIZ

3"
REINF OF WALL A 3" Cost Estimating

LTS TYP
Parametrix, Inc.
7186 South Highland Drive
LTS Salt Lake City, UT 84121
U-BAR SIZE & SPACING TO 801-733-5900

2" MIN MATCH HORIZ REINF OF


LTS WALL A
CLR, TYP
WALL A

BP
BP
003
003

15 NO SCALE CIP SHEAR WALL CORNER 11 NO SCALE TYP CIP SHEAR WALL - PIER AT DOOR 7 NO SCALE TYP CIP SHEAR WALL - END 2 3 NO SCALE TYP CIP SHEAR WALL - CORNER

3'-0"
3'-0"

1 1/2" LEDGE Issue Date


#4x (A706) @12",
FIELD BEND #4x6'-0" @18"OC 3'-0" BP#2 NOVEMBER 16, 2012
#4@12" OC x 4'-0" #4(A706)x @12"OC BP#3 DECEMBER 21, 2012
#4xOPNG WIDTH
CENTERED ON JOINT ADDENDUM 005 JANUARY 25, 2013
#4xCONT ADDENDUM 006 FEBRUARY 8, 2013
STAIR LANDING
RECORD DRAWINGS APRIL 18, 2014
SLAB BY SUPPLIER
DATE PRINTED: 4/18/2014 9:10:06 AM

U-BAR SIZE & SPACING TO


SEE ELEV FOR REINF MATCH HORIZ REINF OF
BELOW OPNG WALL A
#5@12"OC EF HORIZ
#5@9"OC EF HORIZ

LTS
SEE ELEV FOR
HORIZ REINF TYP L2x2x3/16 CONT W/
DESIGNERS: KH/AM

1/2"x3" HAS @ 24"

LTS
#5@12"OC EF VERT

3"
LTS

Project Number: 2011101.00


#5@9"OC STIRRUPS

LTS
#5@12"OC
Drawn By: KH/AM
(2)#7@3"OC EF T&B Reviewed By: KH
SEE 12 / S-320 INSIDE STIRRUPS, CONT WALL A
AND ELEV FOR REINF (2)#7@3"OC EF T&B FULL LENGTH OF WALL Approved By: PD

INSIDE STIRRUPS, CONT


FULL LENGTH OF WALL
PROJECT MANAGER: KH
MM JOB #: 23616.S.01

TYP CONCRETE SHEAR WALL


PRINCIPAL: PD

BP ADD DETAILS
003 005
EOR: PD

TYP CIP SHEAR WALL - LINK BEAM TYP CIP SHEAR WALL -
16 NO SCALE CIP SHEAR WALL BM AT OPNG 12 NO SCALE TYP CIP SHEAR WALL - LINK BM 8 NO SCALE
SECTION AT FLOOR OPNG 4 NO SCALE
INTERSECTION S-320
C:\Proj\2011101_structural_kevinh.rvt

BEAM REACTION
EXTENDED SINGLE PL CONNECTIONS

XXk

XXk
G 6" G 10"
# BOLT BEAM CAPACITY C MAX CAPACITY C MAX XXk XXk BEAM SIZE XXk
ROWS SIZES (KIPS) TOP T & B (KIPS) TOP T & B
FABRICATOR MAY SELECT SINGLE PLATE,

XXk

XXk
2 W8-W12 12 6" 6" 8 10" 10"
SINGLE ANGLE, DOUBLE ANGLE, OR END
3 W10-W18 22 6" 6" 15 10" 10" PLATE CONNECTION THAT PROVIDES

1 1/2" MIN
3" MAX 1 1/2" MIN
4 W16-W24 37 8" 6" 25 10" 10" REACTION NOTED ON PLAN
5 W18-W30 53 10" 6" 37 12" 10"
6 W21-W40 73 11" 8" 52 14" 10" XXk XXk 20
FOR SINGLE PLATE CONN SCHEDULE
S-500A
5/16 7 W24-W44 95 13" 9" 68 16" 12" SUPPORT, SEE DTLS
45 < 60
(3/8) 8 W30-W44 118 16" 11" 86 16" 15"

BEAM SIZE
18
FOR SINGLE ANGLE CONN SCHEDULE
22 < 45, BEVEL 9 W33-W44 142 16" 14" 106 16" 16" S-500B
The Lane Center for


90
5/16
END OF PL AT FACE
Academic Health

3" MIN
3/8 20

TYP
OF SUPPORT C FOR DOUBLE ANGLE & END PLATE
2 COLUMNS OF BOLTS S-500B
5/16 G 3"
XXk XXk CONN SCHEDULE Sciences
14 < 22 COPE BEAM WHERE REQD. University of Colorado at

1 1/2" MIN
1/2 SEE SCHED FOR MAXIMUM 1 1/2" 1 1/2" NOTES:
PL 3/8: Colorado Springs
5/16 COPES AND NOTES 2 & 3 FOR 1. REFER TO STEEL NOTES FOR MATERIAL GRADES OF


7 < 14 5 BOLTS, STANDARD OR HORIZ AT BM 2011101.00
7/16 ADDITIONAL REQMTS. CONNECTION MATERIAL BOLTS & WELDS.
SHORT SLOTS MAY BE USED SPLICE

3" TYP
STD HOLES IN BEAM 2. ALL REACTIONS NOTED ON PLAN AND IN SCHEDULES AND

1 1/2"
5/16 5/16 6 BOLTS, HORIZ SHORT SLOTS

XXk
0 < 7 STD OR SSL IN PLATE 5/16
3 DETAILS ARE SERVICE LEVEL.
3/8 REQUIRED S-500B 3. REACTION APPLIES TO BOTH ENDS OF BEAM WHERE
COLUMN WEB/ FLANGE XXk Owner
ONLY ONE REACTION IS GIVEN.
A OR BEAM WEB Facilities Services
6. 6k MINIMUM REACTION SHALL BE ASSUMED WHERE NO
PL 1/2 XXk University of Colorado at Colorado Springs
SEE PLAN REACTION OR OTHER REQUIREMENTS ARE PROVIDED. Campus Services Building, Rm 212
1420 Austin Bluffs Parkway
# BOLT ROWS (4 SHOWN)

1 1/2"
Colorado Springs, CO 80918
719-255-3505

G 5 NO SCALE TYP BEAM SINGLE PLATE 1 NO SCALE TYP BEAM CONNECTIONS


Architect
AndersonMasonDale Architects, P.C.
COPE LENGTH, SEE SCHED 3198 Speer Boulevard
Denver, CO, 80211
303-294-9448

3" 1 1/2"
D
NOTE:

TYP

d/2 MIN
THE GEOMETRY SHOWN IS THE BASIS FOR Clinical Planning

TOP
COPE
DEPT
D

d
NGTH
20 CALCULATIONS OF LIMIT STATES INVOLVING James W Nakai & Associates, PC
G ALL HOLES IN E LE 520 E Colorado Ave
COP SCHED

H
S-500A COPED BEAMS. ALL EDGE DISTANCE

1 1/2"
A BEAMS ARE Colorado Springs, CO 80903
10
A SECTION: SECTION: DIMENSIONS SHOWN ARE MINIMUMS. SEE 719-635-2142

1 1/2"
STANDARD
S-500A TH
PL3/8x4x6 AT TOP FLANGE, BEAM SLOPING DOWN BEAM SLOPING UP HOLES LENG
PE
CO SCHED
REQUIRED ONLY WHERE NO 1 1/2" TOP & BOTTOM COPE Civil
G 1/2" RADIUS SEE
DECK IS PRESENT AT
.

TYP COPE 1 1/2" TerraNova Engineering, Inc.

k + 1 1/2"
CONNECTION AND BEAM COPE LENGTH USE 'TOP COPED' 815 S 25th Street

3" TYP

1 1/2"
COPE 'C' EXCEEDS 'G' ~ VALUES IN TABLE Colorado Springs, CO 80904

~
SEE SCHED 719-635-6422

BOTT
COPE
DEPT
1 1/2"

OM
G

1 1/2"
3 SIDES Landscape
~

d/2 MIN

H
ALL HOLES IN

TOP TH
Lime Green Design, Inc
ALL HOLES IN

DEP
BEAMS ARE 900 E. Louisiana Avenue, Suite 209

d w/ WEB EXT PL
PLAN: SKEWED BEAM SLOPING

COPE
BEAMS ARE
.

STANDARD HOLES Denver, CO 80210

TYP
d

3"
UP OR DOWN

d/2 MIN
303-733-7558

1 1/2"
X STANDARD HOLES
30 MA SECTION:

1 1/2"
FOR SKEW ANGLES 55, BEAM TO COLUMN 1 1/2"
USE G=6" Structural
FOR SKEW ANGLES 60,
NOTES: 1 1/2"
E LENGTH
1. SERVICE LEVEL (ASD) IN KIPS. COP SCHED Martin/Martin
USE G=10" SEE 12499 West Colfax Avenue

k + 1 1/2"

1 1/2"
2. WHERE NO DECK IS PRESENT AT CONNECTION, AND BEAM COPE 'C' EXCEEDS 'G', BRACE COPE LENGTH Lakewood, CO 80215
TOP FLANGE OF BEAM TO GIRDER. PROVIDE PL3/8x4x6 ON TOP FLANGE. WELD 4 SIDES. SEE SCHED TH 303-431-6100
AT SKEW 60 3. AT COLUMNS, BEAM COPE 'C' SHALL NOT EXCEED 'G'.
3
PE LENG

BOTT
AT SKEW 30 S-500A CO SCHED
4. MINIMUM BEAM WEB THICKNESS SHALL BE 0.23".

COPE
SEE

DEPT
TOP COPE ONLY BOTTOM COPE ONLY TOP & BOTTOM COPE - SLOPED Mechanical/Plumbing

OM
H
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
TYP BEAM EXTENDED SINGLE PL 303-986-8200

18 NO SCALE TYP BEAM SKEWED CONN 10 NO SCALE


CONN 6 NO SCALE TYP BEAM COPE GEOMETRY
Electrical
Shaffer Baucom Engineering & Consulting
T INDICATES TOP TB INDICATES TOP
COPE ONLY AND BOTTOM COPE
3/4" A325 SINGLE PLATE CONNECTION SCHEDULE - MAX REACTION (KIPS) - SERVICE LEVEL 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

COPE CONDITION UNCOPED COPE LENGTH 4" COPE LENGTH 5 1/4" COPE LENGTH 6 1/8" COPE LENGTH 8"
Technology
# OF BOLTS 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9
Rimrock Group
COPE TYPE T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB 10807 New Allegiance Drive, Suite 400
BEAM SIZES Colorado Springs, CO 80921
1.5 x d 719-533-1112
W8 10-15 & C8 16 12 6 10 6# 8 6# 6 6#
CONNECTION, SEE
18-28 16 16 9 14 7 12 6 9 6# SCHEDULES.
USE T&B COPE VALUES Building Performance Engineer
31 & UP 16 16 11 16 8 16 7 14 6
ROUND HSS RECT HSS Ambient Energy
W10 12-19 & C10 16 28 14 7 24 17 11 6# 22 13 9 6# 19 11 7 6# 14 9 130 W 5th Ave
OR PIPE W MIN WALL THK Denver, CO 80204
22-30 16 28 16 9 28 21 16 7 28 16 13 6 27 14 10 6# 21 11 303-278-1532
3" 3/16"

d
D MIN WALL THK
33-45 16 16 11 16 9 16 7 14 6 4" 3/16"
<=13" 3/16"
49 & UP 16 16 13 16 10 16 9 16 7 5" 3/16" Cost Estimating
13"<
1/4" Parametrix, Inc.
W12 14-22 & C12 16 28 15 7 26 17 11 6 23 12 10 6# 20 10 8 6# 14 7 <=17" 6" 3/16" 7186 South Highland Drive
G ADD WEB EXTENSION PL Salt Lake City, UT 84121
26-35 16 28 16 9 28 20 16 7 28 15 14 6 28 13 11 6# 21 9 17"< 7" 1/4" CJP AT WHERE AVAILABLE BEAM 801-733-5900
5/16"
<=22" 8" 1/4" STRIPPED DEPTH IS INSUFFICIENT FOR
40 & UP 16 28 16 11 28 26 16 9 28 20 16 7 28 17 15 6 28 13
9" 5/16" FLANGES CONNECTION DEPTH. PL THK
WHERE WALL G
W14 22-26 28 28 20 28 15 26 13 20 9 AND GRADE TO MATCH BM
THICKNESS < MIN, 10" 5/16"
30-38 28 28 24 28 18 28 16 25 12 1/2" WEB
PROVIDE THRU PLATE 12" 3/8"
AS SHOWN 5/16
43 & UP 28 28 27 28 21 28 18 28 14 14" 1/2"
5/16
W16 26-31 28 41 28 22 41 39 28 17 41 30 28 14 41 24 22 10 35 17 16" 1/2"
36-57 28 41 28 26 41 41 28 20 41 36 28 17 41 31 28 13 41 22 WHERE WALL
THICKNESS < MIN,
67 & UP 28 41 28 28 41 41 28 27 41 41 28 24 41 41 28 18 41 33 PROVIDE THRU PLATE
W18 35-46 28 41 54 28 26 41 41 54 54 28 21 41 37 54 54 28 18 41 32 54 50 27 14 41 23 54 39 AS SHOWN
50-71 28 41 54 28 28 41 41 54 54 28 24 41 41 54 54 28 21 41 38 54 54 28 16 41 29 54 46 3 NO SCALE TYP BEAM WEB EXTENSION
76 & UP 28 41 54 28 28 41 41 54 54 28 28 41 41 54 54 28 25 41 41 54 54 28 20 41 35 54 54
W21 44-57 41 54 66 41 41 54 54 66 66 41 41 54 54 66 66 41 37 54 54 66 66 41 29 54 44 66 66 Issue Date
. 1/4" 1 1/2" dc = LARGER OF TOP OR BOTTOM COPE
62-93 41 54 66 41 41 54 54 66 66 41 41 54 54 66 66 41 41 54 54 66 66 41 33 54 52 66 66 BP#3 DECEMBER 21, 2012
101 & UP 41 54 66 41 41 54 54 66 66 41 41 54 54 66 66 41 41 54 54 66 66 41 41 54 54 66 66 RECORD DRAWINGS APRIL 18, 2014

W24 55-62 41 54 66 78 41 41 54 54 66 66 78 78 41 41 54 54 66 66 78 78 41 41 54 54 66 66 78 78 41 33 54 52 66 66 78 78

dc
68 & UP 41 54 66 78 41 41 54 54 66 66 78 78 41 41 54 54 66 66 78 78 41 41 54 54 66 66 78 78 41 35 54 54 66 66 78 78 3/16
DATE PRINTED: 4/18/2014 9:10:09 AM

1/4"
W27 - W44 54 66 78 90 103 54 54 66 66 78 78 90 90 103 103 54 54 66 66 78 78 90 90 103 103 54 54 66 66 78 78 90 90 103 103 54 54 66 66 78 78 90 90 103 103
PL 3/8

dc
NOTES: RECT OR ROUND
4 5
1. # INDICATES WEB REINFORCEMENT REQD TO ACHIEVE NOTED CAPACITY. SEE S-500A HSS COLUMN OR
S-500A
3" MAX PIPE

~
MIN NOMINAL FLANGE WIDTH:

W
18
8"

2. FOR SKEWED BEAM CONNECTIONS SEE TOP & BOTTOM COPE


S-500A 6 1/2" FOR W8 COLS
5 10 8" FOR W10 THRU W14 COLS 1/2" 1 1/2" 5/16 T&B PL TO
DESIGNERS: KH/AM

COPED AT TOP FLG ONLY COPED T&B S-500A 5/16 1/2" S-500A 5/16 COL
NOTE: DETAIL APPLIES ONLY WHERE
. .

1/2" AT ORTHOGONAL CONNS, 1/2" 5/16 TYPICAL . 1/4" 1 1/2" dc


1/2" MAX INDICATED IN CONNECTION SCHEDULES
6 1 1/2" MAX AT SKEWED CONNS
S-500A 5/16
T/2 MIN
A Project Number: 2011101.00
W8, W10, W12 & W14 5/16
COLUMNS ONLY Drawn By: KH/AM

dc
5/16 5/16
TYP
T/2 MIN

T/2 MIN

T/2 MIN

5/16 5/16 Reviewed By: KH

1 1/2"
1/4"
~
3/16 Approved By: PD
T/2 MIN

k1 PL 3/8
SLOT WALL

.
3/8"
5/16 OF HSS COL

1 1/2"

k
PROJECT MANAGER: KH

5/16
THRU PLATE OPTION
MM JOB #: 23616.S.01

PL 1 T&B TYP, BLOCK FLANGE AS SINGLE COPE


AT EXTENDED 10 5
PL 1 1/2 T&B AT W12 & W14 PL 3/8 1/2" 1 1/2" REQ'D TO WELD TYP STL BM CONNS
PL CONN S-500A S-500A
PRINCIPAL: PD

TYP COLS w/ 8" FLANGES A


BEAM TO GIRDER BEAM TO COLUMN FLANGE BEAM TO COLUMN WEB - OPTION 1 BEAM TO COLUMN WEB - OPTION 2 BEAM TO HSS COL
EOR: PD

20 NO SCALE TYP BEAM SINGLE PLATE CONNECTION SCHEDULE 4 NO SCALE TYP BEAM WEB REINF
S-500A
C:\Proj\2011101_structural_kevinh.rvt

AT DOUBLE ANGLE
3" MAX AT SINGLE
BOLT GAUGE SHALL

ANGLE, NO LIMIT
T INDICATES TOP TB INDICATES NOT EXCEED DEPTH
COPE ONLY TOP AND 3/4" A325 SINGLE ANGLE CONNECTION SCHEDULE - MAX REACTION (KIPS) - SERVICE LEVEL 3" MAX
OF PLATE
BOTTOM COPE 1 1/4" MIN
EQ EQ
COPE CONDITION UNCOPED COPE LENGTH 4" COPE LENGTH 5 1/4" COPE LENGTH 6 1/8" COPE LENGTH 8" AT DBL ANGLES
# OF BOLTS 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9
COPE TYPE T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB
BEAM SIZES
BEAM WEB
W8 10-15 & C8 10 10 6 10 6# 8 6# 6 6#

1 1/4"
MIN

1 1/4"

1 1/4"
18-28 10 10 9 10 7 10 6 9 6#

MIN

MIN
31 & UP 10 10 10 10 8 10 7 10 6
W10 12-19 & C10 10 20 10 7 20 17 10 6# 20 13 9 6# 19 11 7 6# 14 9 3/8" ANGLE PL 3/8

BOLTS MAY BE
22-30 10 20 10 9 20 20 10 7 20 16 10 6 20 14 10 6# 20 11 THICKNESS

STAGGERED
OR ALIGNED
3" MIN, TYP,
33-45 10 10 10 10 9 10 7 10 6 The Lane Center for

3" MIN
TYP
49 & UP 10 10 10 10 10 10 9 10 7 Academic Health
W12 14-22 & C12 10 20 10 7 20 17 10 6 20 12 10 6# 20 10 8 6# 14 7 Sciences
University of Colorado at
26-35 10 20 10 9 20 20 10 7 20 15 10 6 20 13 10 6# 20 9 Colorado Springs
40 & UP 10 20 10 10 20 20 10 9 20 20 10 7 20 17 10 6 20 13 2011101.00

1 1/4"

1 1/4"
MIN

MIN
STANDARD OR HORIZ
W14 22-26 20 20 20 20 15 20 13 20 9 SHORT SLOTTED
30-38 20 20 20 20 18 20 16 20 12 HOLES MAY BE
USED, TYP Owner
43 & UP 20 20 20 20 20 20 18 20 14
Facilities Services
W16 26-31 20 33 20 20 33 33 20 17 33 30 20 14 33 24 20 10 33 17 ANGLE END PLATE University of Colorado at Colorado Springs
Campus Services Building, Rm 212
36-57 20 33 20 20 33 33 20 20 33 33 20 17 33 31 20 13 33 22 1420 Austin Bluffs Parkway
Colorado Springs, CO 80918
67 & UP 20 33 20 20 33 33 20 20 33 33 20 20 33 33 20 18 33 33 719-255-3505

W18 35-46 20 33 46 20 20 33 33 46 46 20 20 33 33 46 46 20 18 33 32 46 46 20 14 33 23 46 39 1 NO SCALE TYP BEAM ANGLES/END PLATE


Architect
50-71 20 33 46 20 20 33 33 46 46 20 20 33 33 46 46 20 20 33 33 46 46 20 16 33 29 46 46
AndersonMasonDale Architects, P.C.
76 & UP 20 33 46 20 20 33 33 46 46 20 20 33 33 46 46 20 20 33 33 46 46 20 20 33 33 46 46 3198 Speer Boulevard
Denver, CO, 80211
W21 44-57 33 46 59 33 33 46 46 59 59 33 33 46 46 59 59 33 33 46 46 59 59 33 29 46 44 59 59 303-294-9448
62 & UP 33 46 59 33 33 46 46 59 59 33 33 46 46 59 59 33 33 46 46 59 59 33 33 46 46 59 59
W24 TO W44 33 46 59 72 84 97 33 33 46 46 59 59 72 72 84 84 97 97 33 33 46 46 59 59 72 72 84 84 97 97 33 33 46 46 59 59 72 72 84 84 97 97 33 33 46 46 59 59 72 72 84 84 97 97 Clinical Planning
James W Nakai & Associates, PC
NOTES: FOR SHARED HOLES WHERE WEB tw<0.41", TOTAL CONNECTION 520 E Colorado Ave
4
1. # INDICATES WEB REINFORCEMENT REQD TO ACHIEVE NOTED CAPACITY. SEE S-500A CAPACITY(SUM OF REACTIONS FROM BOTH SIDES) IS LIMITED TO Colorado Springs, CO 80903
719-635-2142
VALUES IN THE TABLE BELOW. USE THE LESSER VALUE FROM THIS 1/2" RADIUS TYP
BOLTS STAGGERED .
BOLTS ALIGNED
.
BOLTS STAGGERED .
BOLTS ALIGNED
.
TABLE AND THE CONNECTION SCHEDULE.
1/2". 1/2" MAX NP=NOT PERMITTED Civil

0.24" tw < 0.30"


0.30" tw < 0.35"
0.35" tw < 0.41"
6 tw TerraNova Engineering, Inc.
SINGLE ANGLE

# OF BOLTS
S-500A 815 S 25th Street
CONN Colorado Springs, CO 80904
719-635-6422

Landscape
2 NP NP NP
T/2 MIN

T/2 MIN

Lime Green Design, Inc


A A 3 12 15 17 900 E. Louisiana Avenue, Suite 209
4 19 24 28 "UNCOPED" VALUES MAY Denver, CO 80210
303-733-7558
5 27 34 39 BE USED WHEN
5/8" RET 6 34 43 50
3 SIDES, FLANGES ARE BLOCKED
TOP FULL 7 42 53 62
5/16 5/16 TYP OR STRIPPED ONE SIDE Structural
RET BOT 8 49 62 72 TO PASS T DIMENSION Martin/Martin
9 57 71 83 OF COLUMN 12499 West Colfax Avenue
BOLTED BEAM / BOLTED SUPPORT BOLTED BEAM / WELDED SUPPORT WELDED BEAM / BOLTED SUPPORT BOLTED BEAM/BOLTED SUPPORT Lakewood, CO 80215
1
2 1 SHARED HOLES 303-431-6100
S-500B
S-500B S-500B
A
Mechanical/Plumbing
AT COLUMN AT GIRDER Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

18 NO SCALE TYP BEAM SINGLE ANGLE CONNECTION SCHEDULE 2 NO SCALE TYP BEAM FLANGE BLOCK
Electrical
Shaffer Baucom Engineering & Consulting
SHOP WELDED/FIELD BOLTED CONN SHOP & FIELD BOLTED CONN 7333 West Jefferson Avenue, Suite 230
. .

Lakewood, CO 80235
T INDICATES TOP TB INDICATES 303-986-8200
COPE ONLY TOP AND 3/4" A325 DOUBLE ANGLE AND END PLATE CONNECTION SCHEDULE - MAX REACTION (KIPS) - SERVICE LEVEL 1
BOTTOM COPE
COLUMN WEB OR S-500B
Technology
COPE CONDITION UNCOPED COPE LENGTH 4" COPE LENGTH 5 1/4" COPE LENGTH 6 1/8" COPE LENGTH 8" FLANGE 1/2"
Rimrock Group
10807 New Allegiance Drive, Suite 400
# OF BOLTS 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 2 3 4 5 6 7 8 9 DOUBLE ANGLE END PLATE Colorado Springs, CO 80921
COPE TYPE T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB T TB 719-533-1112
BEAM SIZES DOUBLE ANGLE OR A
W8 10-15 19 12 6 10 6# 8 6# 6 6# END PLATE

T/2 MIN
Building Performance Engineer
18-28 26 18 9 14 7 12 6 9 6# A Ambient Energy
130 W 5th Ave
31 & UP 33 26 11 20 8 18 7 14 6 Denver, CO 80204
303-278-1532
W10 12-19 22 33 14 7 26 17 11 6# 22 13 9 6# 19 11 7 6# 14 9
A
22-30 28 42 20 9 33 21 16 7 32 16 13 6 27 14 10 6# 21 11
Cost Estimating
33-45 33 26 11 21 9 18 7 14 6
Parametrix, Inc.
49 & UP 39 32 13 25 10 22 9 17 7 7186 South Highland Drive

T/2 MIN, BASED ON T


OF SIMILAR BEAM
Salt Lake City, UT 84121
W12 14-22 23 35 15 7 27 17 11 6 23 12 10 6# 20 10 8 6# 14 7 801-733-5900
2
26-35 26 40 20 9 31 20 16 7 31 15 14 6 28 13 11 6# 21 9 S-500B
40 & UP 34 51 28 11 40 26 23 9 40 20 20 7 38 17 15 6 30 13 FOR ANGLE/END 1
WHERE WEB tw<0.41", TOTAL CONNECTION DETAIL CONN TO PERMIT PLATE SIZE & S-500B 1" MAX
W14 22-26 40 31 20 30 15 26 13 20 9
CAPACITY (SUM OF REACTIONS FROM BOTH SAFE ERECTION OF BM EA DETAIL
30-38 47 37 24 37 18 32 16 25 12 SIDES) IS LIMITED AS FOLLOWS: SIDE WHERE BOLTS ARE
SEE SCHEDULE 20
43 & UP 53 42 27 42 21 40 18 31 14 0.35" tw < 0.41", 20.5k x # OF SHARED BOLTS SHARED, IN ACCORDANCE
FOR CAPACITY S-500B
0.30" tw < 0.35", 17.6k x # OF SHARED BOLTS WITH ALL OSHA STANDARDS,
W16 26-31 43 58 34 22 44 39 33 17 44 30 29 14 44 24 22 10 35 17 0.23" tw < 0.30", 13.7k x # OF SHARED BOLTS TYP AND WELDING
36-57 51 69 40 26 52 47 40 20 52 36 35 17 52 31 28 13 45 22 tw 0.23", 9.9k x # OF SHARED BOLTS

67 & UP 69 92 54 35 70 63 54 27 70 49 54 24 70 42 42 18 69 33
W18 35-46 52 70 87 41 26 53 47 66 62 41 21 53 37 66 58 35 18 53 32 66 50 27 14 45 23 66 39
TYPICAL AT COLUMN/GIRDER 3 NO SCALE TYP BEAM DBL ANGLE SPLICE
50-71 62 83 103 49 31 63 56 78 73 49 24 63 44 78 69 44 21 63 38 78 60 34 16 56 29 78 46
5/16
76 & UP 71 95 119 58 38 76 67 93 88 58 29 76 53 93 82 58 25 76 46 93 72 45 20 74 35 93 56 45 < 60 Issue Date
(3/8)
W21 44-57 81 102 122 62 55 77 72 91 87 62 43 77 68 91 87 62 37 77 59 91 85 52 29 77 44 91 66 22 < 45, BEVEL BP#3 DECEMBER 21, 2012
SHOP WELDED/FIELD BOLTED CONN SHOP & FIELD BOLTED CONN 5/16 RECORD DRAWINGS APRIL 18, 2014
62-93 93 117 140 71 63 88 82 104 99 71 49 88 78 104 99 71 43 88 67 104 97 64 33 88 52 104 76
. .

END OF BM WEB AT
3/8
END PLATE
101 & UP 95 119 143 89 79 110 103 131 124 89 62 110 97 131 124 89 54 110 84 131 122 89 42 110 66 131 95 1
1/2" 1/2" MAX 5/16
W24 55-62 92 115 138 161 70 63 87 81 103 98 120 114 70 49 87 77 103 98 120 114 70 42 87 66 103 96 120 114 62 33 87 52 103 73 120 102 S-500B 14 < 22
DATE PRINTED: 4/18/2014 9:10:13 AM

1/2
68-103 95 119 143 166 74 66 91 85 108 103 126 120 74 51 91 81 108 103 126 120 74 45 91 70 108 101 126 120 69 35 91 54 108 78 126 107 5/16


7 < 14
104 & UP 95 119 143 166 89 79 110 103 131 124 151 145 89 62 110 97 131 124 151 145 89 54 110 84 131 122 151 145 88 42 110 66 131 95 151 129 7/16
W27 84-129 119 143 166 101 95 120 114 139 133 101 89 120 114 139 133 101 77 120 112 139 133 101 60 120 87 139 119 5/16
A 0 < 7
3/8
146 & UP 119 143 166 119 119 143 143 166 166 119 118 143 143 166 166 119 102 143 143 166 166 119 79 143 115 166 156
5/16

T/2 MIN
W30 90-148 119 143 166 190 103 97 123 116 142 136 162 155 103 91 123 116 142 136 162 155 103 79 123 114 142 136 162 155 103 62 123 89 142 121 162 155 0 =
DESIGNERS: KH/AM

5/16
173 & UP 119 143 166 190 119 119 143 143 166 166 190 190 119 119 143 143 166 166 190 190 119 111 143 143 166 166 190 190 119 86 143 124 166 166 190 190 END PLATE
W33 118-152 143 166 190 214 143 136 166 159 189 182 212 205 143 136 166 159 189 182 212 205 143 134 166 159 189 182 212 205 143 104 166 142 189 182 212 205
169 & UP 143 166 190 214 143 143 166 166 190 190 214 214 143 143 166 166 190 190 214 214 143 143 166 166 190 190 214 214 143 127 166 166 190 190 214 214 3 SIDES, Project Number: 2011101.00

W36 135-160 143 166 190 214 143 143 166 166 190 190 214 214 143 143 166 166 190 190 214 214 143 143 166 166 190 190 214 214 143 114 166 155 190 190 214 214 DOUBLE ANGLE OR TYP 5/16 Drawn By: KH/AM
END PLATE
170 & UP 143 166 190 214 143 143 166 166 190 190 214 214 143 143 166 166 190 190 214 214 143 143 166 166 190 190 214 214 143 129 166 166 190 190 214 214 Reviewed By: KH

W40 149-215 143 166 190 214 143 143 166 166 190 190 214 214 143 143 166 166 190 190 214 214 143 143 166 166 190 190 214 214 143 119 166 163 190 190 214 214 Approved By: PD

235 & UP 143 166 190 214 143 143 166 166 190 190 214 214 143 143 166 166 190 190 214 214 143 143 166 166 190 190 214 214 143 142 166 166 190 190 214 214
W44 ALL 166 190 214 166 166 190 190 214 214 166 166 190 190 214 214 166 166 190 190 214 214 166 166 190 190 214 214 6
PROJECT MANAGER: KH

S-500A
NOTES:
MM JOB #: 23616.S.01

1. # INDICATES WEB REINFORCEMENT REQD TO ACHIEVE NOTED CAPACITY. SEE


4 ANGLES - BOLTED BEAM / BOLTED SUPPORT ANGLES - WELDED BEAM / BOLTED SUPPORT
S-500A TYP STL BM CONNS
PRINCIPAL: PD

COPED BEAM CONDITION AT GIRDER A


EOR: PD

20 NO SCALE TYP BEAM DOUBLE ANGLE AND END PLATE CONNECTION SCHEDULE
S-500B
C:\Proj\2011101_structural_kevinh.rvt
1 1/2" T = THK OF THINNER FLG
NOTE 1
5/16

4"
AT GIRDER PROVIDE END PL
1/4
CONN PER 20 / S-500B MIN WEB CONNECTION
LANDING BY 1/4 2" MIN
W/ MAX NUMBER OF BOLTS (1) C7x12.25 FOR W10

4"
SUPPLIER G
AND 1" PL THICKNESS SHIM AS REQD
OPTIONAL LIFTING
SEE ARCH 1/2" DAS @ 8"OC, HOLE IN CHANNEL
PL WASHER 5/16x2x2
EXTEND 3'-0" PAST W/ STD HOLES

2"
BM CL
STAIR A MIN (2) BOLT ROWS SHARED PJP EA

6"
3 1/2"
2 1/2"

1" CLR
TREAD BY BY END PL CONNECTIONS FLG, SEE

2"
L3x3x1/4 CONT
SUPPLIER 3 SIDES TABLE (E)

3/16 2-12
PJP EFFECTIVE The Lane Center for

2"
3/16 2-12
AT W12 PROVIDE END PL WELD SIZE
TYP AT Academic Health

6"
LANDING SUPPORT BENT PL3/8 x CONN PER 20 / S-500B STUD TO PL 7/16 T E
HEADER BTWN CONT W/ MAX NUMBER OF BOLTS Sciences
STRINGERS BY STAIR AND 1" PL THICKNESS PL 1 1/2x1'-3x1'-3 W/ FINISH PER T 3/4" 1/4 University of Colorado at
SUPPLIER OVS HOLES AISC Colorado Springs

2"
3/16 2-12 CAP PL 1/4 1" END PL,
2-12 MAX WIDTH 7" 3/4" < T 1 1/2" 5/16 2011101.00
3/16
PL 1 1/2x1'-3x1'-3 W/ (4) 1 1/2" < T 2 1/4" 3/8
3/4 THREADED STUDS
.

BOLTS THRU
Owner
BOTH END PLATES NOTES: Facilities Services
5/16 1. (2) CHANNELS REQD FOR COLS OVER 30'-0" LONG OR OVER 100 LB/FT University of Colorado at Colorado Springs
2. STD HOLES IN COL, STD OR OVS HOLES IN CHANNEL Campus Services Building, Rm 212
A 1420 Austin Bluffs Parkway
Colorado Springs, CO 80918
NOTES: FIELD WELDED OPTION 719-255-3505
1. ALL AROUND WELD MAY BE USED IN LIEU OF WELD SHOWN
17 NO SCALE SOUTH EAST STAIR DETAIL 5 13 NO SCALE SOUTH EAST STAIR DETAIL 1 9 NO SCALE BALCONY DRAG CONN AT WF COL TO HSS COL
Architect
AndersonMasonDale Architects, P.C.
5 1/2" AT NOM 8" FLG 3198 Speer Boulevard
7" AT NOM 10" FLG Denver, CO, 80211
3" AT W10 303-294-9448
EA END 3/16 1 1/2 PL3/8x6x6 3 SIDES 1 1/4" 1 1/4" 1 1/4" 1 1/4"
TYP 3/16 1 1/2 3/16
G
CJP, Clinical Planning
GRIND James W Nakai & Associates, PC
SHIM AS REQ'D, 520 E Colorado Ave
0" MIN, 3/4" MAX FLUSH SHIMS MAY BE Colorado Springs, CO 80903
719-635-2142

NS GROUT

1 1/2"
3 /4 "MAX
NS GROUT LOOSE, SHOP
1 1/2" WELDED, OR
L4x4x1/4 BRACE 3/16
@4'-0" OC EXTENDED AND
3/16 Civil
SHOP BOLTED, TYP

EQ

1 1/2"
1 3/4"
TerraNova Engineering, Inc.

2@3"
815 S 25th Street
PL 3/8x5x10 A OPTIONAL LIFTING

1 3/4"
Colorado Springs, CO 80904
HOLE 719-635-6422
1" MAX
7 /8"

PL 1/2 EA FLG
3/16 A Landscape
3/16 Lime Green Design, Inc

2@3"
G

1 1/2"
900 E. Louisiana Avenue, Suite 209
Denver, CO 80210
CAP PL 1/4 3 SIDES, ALT 303-733-7558
COORD W/ TO BOLTING 5/16
PARTITION PL 3/8
4"

1 1/2"
SUPPLIER BASE PL3/8x6 Structural
Martin/Martin
12499 West Colfax Avenue
C8x11.5xCONT W/ HOLES L4x4x1/4 PARALLEL W/ PARTITION 3 SIDES, ALT Lakewood, CO 80215
NOTES: 5/16 TO BOLTING 303-431-6100
FOR ROD ATTACHMENT OF AT EA END, SLOPE UP AND CONN
1 1/2" TYP 1. STD HOLES IN COL STD AND CONN PLATES
PARTITION HEAD TO TOP OF ADJACENT HANGER (2) 3/8"x2 1/2" EMBED
SCREW ANCHORS AT SAME SERIES WF COL - FIELD BOLTED OPTION Mechanical/Plumbing
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

18 NO SCALE TYP SPRT FOR PARTITION 14 NO SCALE SOUTH EAST STAIR DETAIL 2 10 NO SCALE SOUTH EAST STAIR CORNER 6 NO SCALE TYP COL SPLICE
Electrical
Shaffer Baucom Engineering & Consulting
3" 7333 West Jefferson Avenue, Suite 230

1/4 5/16 2-6 Lakewood, CO 80235


303-986-8200
11
10
TYP S-501 S-501 3"
Technology
1 1/2" TYP PL 3/8 Rimrock Group
8 3 1/2" 10807 New Allegiance Drive, Suite 400
SIM AT BEAM CONN AT HSS, Colorado Springs, CO 80921
S-501
5/16 TYP 1" MIN 719-533-1112

DECK SUPPORT

k
STIFF PL 3/8 ES Building Performance Engineer
AT HSS COL A
3 SIDES Ambient Energy
1/4 .

5/16 130 W 5th Ave


L4x4x3/8x3" 1/4
Denver, CO 80204
TYP 303-278-1532
1/4
3 SIDES
3/16
CAP PL 3/4 W/ (4) Cost Estimating
BOLTS (2) BOLTS Parametrix, Inc.
AT TYP AT SIM 1/4 7186 South Highland Drive
AT WF, 1/4 Salt Lake City, UT 84121
A 801-733-5900
TYP 5/16
(3/16) 3
(3/16) 3 AT SIM 1 1/2" MIN
L4x4x3/8x6"
WF OR HSS COL, 1/2" 3"
ORIENTATON VARIES STIFFENER

k
WELD TO EA 3/8" STIFF PL, ALIGN PL 3/8 ES
LEG, TYP 3/16 W/ HSS WALLS 12
TYPICAL AT BEAM END
S-501
8
3 SIDES AT BM CONN
1/4 S-501
AT WF COL

19 NO SCALE SOUTH EAST STAIR BM TO COL 15 NO SCALE SOUTH EAST STAIR DETAIL 3 11 NO SCALE SOUTH EAST STAIR HEADER 7 NO SCALE TYP BM OVER COLUMN 3 NO SCALE TYP COL TRANSFER

20A 9
S-500A S-315 Issue Date

2"
BP#3 DECEMBER 21, 2012
5/16 RECORD DRAWINGS APRIL 18, 2014
5/16 1" MAX 3" 1 3/4"
HORIZ
REACTION
PL WASHER ONLY
DATE PRINTED: 4/18/2014 9:10:15 AM

AT ROUND CUT
PLATE TO MATCH LSL HOLES IN BM FLG CLASS 'A' SC
5/16 PL 1/2
PARALLEL TO BEAM BOLTS, TYP
.

5/16
CONN TO HSS
MAXIMUM # OF BOLTS

1 1/2"
CJP, GRIND
1 1/2"

BY CURTAIN
MIN

2" PL3/8 W/ (2) BOLTS SHOWN IN STL CONN

3" TYP
WALL MNFR. FLUSH
BEAM TO COLUMN FLG/HSS/EMBED IN STD HOLES SCHED
DESIGNERS: KH/AM

LEVEL 3-4 LANDING


10 STRIP FLG ONE SIDE
S-500A OR COPE
Project Number: 2011101.00
HORIZ AND PL 3/8
5/16 3 SIDES VERT Drawn By: KH/AM
5/16 TYP REACTION

k
AT SIM 5/16 Reviewed By: KH
5/16
Approved By: PD

1 1/2"
EXTEND PLATE TO
KINK UP OR DOWN BOT FLANGE AT SIM
.

e
PROJECT MANAGER: KH

3/8
MM JOB #: 23616.S.01

CONN TO HSS BY CURTAIN WALL 3/8


1 1/2" MIN MNFR. DESIGN CONN TO MULION TYP STEEL DETAILS
IN PL TYP
PRINCIPAL: PD

LEVEL 2-3 LANDING FOR ECCENTRICITY 'e'. NO


BEAM TO COLUMN WEB MOMENT PERMITTED TO HSS
EOR: PD

20 NO SCALE BM FLANGE CONN 16 NO SCALE SOUTH EAST STAIR DETAIL 4 12 NO SCALE SOUTH EAST STAIR STRINGER 8 NO SCALE TYP FULL HEIGHT SHEAR CONN 4 NO SCALE TYP BM DRAG CONN THRU COL
S-501
3'-6" 8
C:\Proj\2011101_structural_kevinh.rvt 3 SIDES SEE ARCH, 1'-10" MAX
1'-10"

S-501 1/4
BM CL
L4x4x1/2x0'-7 SEE ARCH
FITTED STIFF 5"
PL 3/8 ES 2" MAX BENT PL 3/8xCONT
3 SIDES 2 SIDES
1" MAX 1/4 BENT PL 3/8xCONT (3/16) 2-12
TYP 5/16
5/16 3/16 2-12

1'-0"
L5x3 1/2x3/8x0'-6 (1/4)
3/16 2-12
W/ (2) BOLTS ES 2-12
3/16

1/2"
OF HSS STRIP VERT

1'-0"
LEG AT BOLT
3 SIDES L4x4x1/2x0'-7
TYP 1/4 1 1/4" TYP COPE GIRT 2 1/4"
HSS8x4x1/4 AT COL RECESSED CAP PL 1/4,
TYPE A 1/4
SEAL WELD ALL
1/4 AROUND

5"
.

1"

1"
1/2" 5/16
PL2x7 1/2, AESS,
5/16 5 5/16
GR 50
1" 5/16 5 5/16
The Lane Center for
5/16
PLATE TO Academic Health

1"
18 5/16 5/16
TUBE CONN S-502
Sciences
University of Colorado at
5/16 Colorado Springs
PL3/8x6 5/16 PL1/2x3x6
2011101.00

PL1/2x3x6
SEAL Owner
WELD
1/4 ES Facilities Services
T&B 1/4 University of Colorado at Colorado Springs
3/8 AT SIM ADD
NOTE: AESS STEEL. SEE SPEC Campus Services Building, Rm 212
RFC 026 FOR AESS TOLERANCE LIMITS.
005 TYPE B 1420 Austin Bluffs Parkway
Colorado Springs, CO 80918
719-255-3505

17 NO SCALE PERGOLA SUPPORT HANGER 13 NO SCALE VESTIBULE DECK EDGE AT PARAPET 9 NO SCALE GIRT TO WF CONN 5 NO SCALE VESTIBULE DECK EDGE 1 NO SCALE VESITBULE BM COL CONN
Architect
1/16" MAX

AndersonMasonDale Architects, P.C.


1/2" MAX
GAP ES

1/4" 3198 Speer Boulevard


RECESSED END PL1/2x1x7 1/2 AT Denver, CO, 80211
PL 1/4 ES LOCS NOTED 303-294-9448

THUS: #
L4x4x1/2x6, EA SIDE
Clinical Planning

DIVISION 9 FRAMING D (5/16)


10" MAX 5/16
5/16
3 SIDES
James W Nakai & Associates, PC
520 E Colorado Ave
PL3/16x7x8 AT SEE ARCH G AX
Colorado Springs, CO 80903

LOCS NOTED 4" M 719-635-2142


1/4"

. THUS: #

20
Civil
TerraNova Engineering, Inc.
815 S 25th Street
AT LOCS NOTED: # Colorado Springs, CO 80904
PL 3/16 TO PL 1/2 719-635-6422
3/16
3/4" RET T&B (5/16)

8"
AT LOCS NOTED: # 1/4 L4x4x1/2x8, EA SIDE (5/16)
Landscape
PL 1/2 TO PL 2 1/4 Lime Green Design, Inc
. 900 E. Louisiana Avenue, Suite 209
FULL RET AT END 5/16 Denver, CO 80210
TYP T&B 1/4 12 303-733-7558

(5/16)
3 1/2" RET (5/16) Structural
(3) SIDES 3 SIDES T&B 5/16
Martin/Martin
FITTED PL TO HSS 1/4 5/16 12499 West Colfax Avenue
10 5/16 Lakewood, CO 80215
PL 1/2x9 W/ (3) BOLT ROWS PER: 303-431-6100
S-500A
1/4

FILL RECESSED AREA WITH WELD NOTE: STEEL IS AESS. SEE Mechanical/Plumbing
ASI
MATERIAL AND GRIND SMOOTH. SPEC FOR REQTS. ASI Shaffer Baucom Engineering & Consulting
012 TYP T&B RFC 059 012 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
SKEWED CONNECTION AT LEVEL 4 303-986-8200

18 NO SCALE PERGOLA BEAM TO PLATE CONN 14 NO SCALE SECTION AT VESITBULE ENTRY 10 NO SCALE CURTAIN WALL GIRT CONN - EAST 6 NO SCALE
TERRACE 2 NO SCALE HSS BM CONN AT COL
Electrical
RECESSED CAP PL 1/4 AESS, Shaffer Baucom Engineering & Consulting
SEAL WELD ALL AROUND 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200
PL3/8x6x10 AESS

PL3/8x8x10 AESS
5"

Technology
Rimrock Group

2 1/2" CLR
PL3/8x1 5/8x8 AESS 10807 New Allegiance Drive, Suite 400
L4x4x3/8x4 TOP 3 SIDES Colorado Springs, CO 80921
3"

5/16 SECTION A 719-533-1112


5/16 A
2"

5/16 L4x4x3/8x9 BOT


L4x4x1/2x4 TOP
PL WASHER 1/4x3", TYP 5/16 SEAL Building Performance Engineer
Ambient Energy
130 W 5th Ave
3 SIDES 1/2" MAX Denver, CO 80204
2" 1/4
(1) BOLT IN HORIZ LEG, (5/16) 3 SIDES 303-278-1532
3/16

5"
(2) BOLTS IN VERT LEG ANGLE IS (5/16)
TYP CONTINUOUS AT A
Cost Estimating
AT CONN MARKED THUS: # SOME LOCS L4x4x1/2x6 BOT
1/2" MAX Parametrix, Inc.
PROVIDE LSL HOLES IN PL, 7186 South Highland Drive
FINGER TIGHTEN, BACK OFF (5/16) Salt Lake City, UT 84121
801-733-5900
NUT 1/4" TURN AND DAMAGE (5/16)
1/2"

THREADS, STD HOLES IN CL HSS GIRT = CL HSS8x4 VERT L4x4x1/2x4


ANGLE (1/4)
(1/4) 5/16
3"

5/16
2"

1/4 T&B
STD HOLES IN 3/16 2
1 1/2"
PLATE AND ANGLE 1/4 3 3 SIDES
AT TYP 1/4 NOTE: STEEL IS AESS. SEE
SPEC FOR REQTS.
SECTION A
RFC 102&111

19 NO SCALE PERGOLA ANGLE TO POST CONN 15 NO SCALE GIRT TO HSS POST CONN 11 NO SCALE CURTAIN WALL GIRT CONN - SOUTH 7 NO SCALE VESTIBULE BM TO POST CONN 3 NO SCALE VESTIBULE BM MITERED CORNER

L4x4x1/2x6, EA SIDE Issue Date

BP#3 DECEMBER 21, 2012


ES ADDENDUM 005 JANUARY 25, 2013
SEAL WELD T&B 5/16 A ASI 012 MARCH 27, 2013
L4x4x3/8x4 TOP RECORD DRAWINGS APRIL 18, 2014
DATE PRINTED: 4/18/2014 9:10:16 AM

1/4 3
1/4 3

HSS TO ANGLE HSS TO HSS 3 SIDES 3 SIDES


1/4 7/16 7/16 1/2" MAX 5/16
1/4
1/2" 3 1/2" TYPICAL
DESIGNERS: KH/AM

3 SIDES
1/4

PL6x4x3/8 ES, AESS WP AT COL CL


3"

L4x4x1/2x4, EA SIDE Project Number: 2011101.00

Drawn By: KH/AM


3"

L4x4x3/8
Reviewed By: KH
BEVEL END OF
3"

PLATE AT FACE 5/16 Approved By: PD


OF SUPPORT 3/8 PL3/8x6x6 FITTED PL 3/8
3 SIDES 1/4
7/16
3 SIDES
PROJECT MANAGER: KH

5/16 PL3/8x6 ES W/ (2) BOLTS 1/4


3 SIDES
MM JOB #: 23616.S.01

IN 3" SLOTTED HOLES. 1/4 1/2" MAX 3 SIDES


STD HOLES IN HSS. 1/4
SECTION A STEEL DETAILS
HSS TO COLUMN NOTE: STEEL IS AESS. SEE
PRINCIPAL: PD

SPEC FOR REQTS. RFC 036 AT HSS 4x4


EOR: PD

20 NO SCALE PERGOLA BEAM CONN 16 NO SCALE POST SUPPORT 12 NO SCALE GIRT CONN AT ROUND HSS 8 NO SCALE GIRT CONN TO WF COL 4 NO SCALE HSS BM CONN
S-502
C:\Proj\2011101_structural_kevinh.rvt

A 1/4
1/4

1" CLR
5 FOR ADDNL
S-500A PLATE REQTS A
PL1/4 ES W/
(2) BOLTS PL 3/8x6x1'-1" ES W/ 157'-4"

1 1/2"
3" VERT SLOTTED
(5) SC BOLTS MIN
HOLES.

1 1/2"
ALIGN

3"
2 1/2"
(2) 3/4" BOLTS, 3/16 3-12
HAND TIGHTEN 3/16 3-12 3/16
BACK OFF NUT AND ALIGN
2

3"
DAMAGE THREADS The Lane Center for

1 1/2"
1/2"
S-503
1/4 W24x55 3/16 3
TYP EA END
1/4 3'-0" Academic Health

1 1/2"
3/16 3

EQ
B/STEEL = 155'-1"
2"
Sciences
PL1/4 ES W/ 6" 6" University of Colorado at
(2) BOLTS Colorado Springs
3"

EQ
2011101.00
1'-1 1/2"
2 1/2" SECTION A
L6x4x3/8x2'-6" LLV W/ 3" VERT
SLOTTED HOLES AT POST, EA
SIDE OF POST Owner
Facilities Services
University of Colorado at Colorado Springs
ADD Campus Services Building, Rm 212
005 1420 Austin Bluffs Parkway
Colorado Springs, CO 80918
719-255-3505

17 NO SCALE VESTIBULE BEAM TO POST CONN 13 NO SCALE TOP OF CURTAIN WALL CONN 5 NO SCALE SOUTH EAST STAIR 5 1 NO SCALE SOUTH EAST STAIR - ROOF 1
Architect
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard

L6x3 1/2x3/8x0'-6 W/
. Denver, CO, 80211
303-294-9448
6"
11 AT LEVEL 3.5 (2) BOTS EA LEG HSS14
S-316 AND 4.5 LANDING
TYP PL1/2x8x8 W/ 5/16 3/16 Clinical Planning
1/4 (4) 3/4x6" HAS James W Nakai & Associates, PC
5/16
520 E Colorado Ave
2 1/2" MIN Colorado Springs, CO 80903
1 1/8" MIN (3) SIDES
5/16
719-635-2142
EW, TYP
1 1/2" W18
5/16 BOLTED OPTION Civil
TYP
5/16 A A TerraNova Engineering, Inc.
815 S 25th Street
3" 2"

Colorado Springs, CO 80904

1 1/2"

3"
L 719-635-6422

2" TYP
(3/16) TYP AT

3"
1 1/2"

(3/16) HSS Landscape


L4x4x3/8 x6"

3"
3/16 W/(2) BOLTS, TYP Lime Green Design, Inc
TYP 900 E. Louisiana Avenue, Suite 209

1 1/2"
3/16 Denver, CO 80210

3"
PL3/8 ES OF POST W/ (2) 3/16 303-733-7558
CONTRACTOR MAY USE
BOLTS. STD HOLES IN
1" 1" ANY COMBINATION OF

k
PLATE, VERT LSL PL 3/8x6x0'-6 TYP
. A WELDING OR BOLTING
HOLES IN POST TYP 3" Structural
SHOWN
1/4 Martin/Martin

1"
3/16 1 1/2 KICKER: 1 1/2" 1 1/2" 12499 West Colfax Avenue
TYP FOR L8'-0": L3x3x1/4 Lakewood, CO 80215
L3x3x1/4 T&B 3/16 1 1/2 303-431-6100
FOR 8'-0"<L12'-0": L4x4x1/4 PL 1/2x14x1'-3 W/ A
(10) 3/4" BOLTS
Mechanical/Plumbing
ADD ADD RFC 145 Shaffer Baucom Engineering & Consulting
005 006 RFC 098 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200

18 NO SCALE OVERHEAD DOOR TOP CONN 14 NO SCALE POST CONN AT STAIR LANDING 10 NO SCALE TYP KICKER 6 1 1/2" = 1'-0" W18 TO HSS CONN 2 NO SCALE SOUTH EAST STAIR - ROOF 2
Electrical

D D.1 8
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
S-501 303-986-8200

L4x4x1/4x2'-4" LONG W/ HSS14 W12 ABOVE HSS, SEE


(3) 1/2" HILTI KWIK PENTHOUSE PLAN
Technology
BOLT TZ WITH 3 1/2" 5/16 Rimrock Group
10 1/2" EA PL
EMBEDMENT. INSTALL 5/16 10807 New Allegiance Drive, Suite 400
(1) ANCHOR IN THE FULL HT STIFF PL ES Colorado Springs, CO 80921
MAX 1/4 719-533-1112
CENTER OF EA BOT 1'-2"
W18 1/4
1" MAX

NO VERTICAL SUPPORT AT 1/4


FLUTE TYP
SIM. PROVIDE VERTICAL 1/4
SLOTTED HOLES IN 1 1/2" 3 1/2" 1 1/2" Building Performance Engineer
SUNSHADE VERT Ambient Energy
WT6x9.5 ALIGN WEB WITH
3/16

2" 3 1/2" 3 1/2" 2"


130 W 5th Ave
BM ABOVE. PL3/8x4 FAR
1 1/2"

5/16 Denver, CO 80204


3/16 PL3/8x10x7 W/ 3" VERT 3/16
5/16 SIDE, ALIGN WITH WT 303-278-1532
SLOTTED HOLES. 3/16
ALIGN BOLTS IN HOLE 157'-4"
PER DIMS BELOW Cost Estimating
3"
2"
1"

WELDED PL3/8 (AESS) EACH Parametrix, Inc.


CONNECTION AT SIDE OF SUNSHADE 7186 South Highland Drive
9"

1 1/2"

PERP CHANNEL VERT, CONTR COORD Salt Lake City, UT 84121


801-733-5900
LOC WITH SUNSHADE
2" 3"
(2)L6x4x3/8 W/ (2) SUPPLIER

1"
3 SIDES 3" AT
BOLTS IN STD HOLES TYP HSS8X3 PL 3/4x11, W/
3/16 SUNSHADE AND HSS END
1 1/2" STD HOLES 3/16
MATERIAL TYP
EA FLANGE CAP PL 3/8 PL WASHER 1/4x3", TYP 3/16
3/16 SEPARATION BY
SUPPLIER
3/16 PL 1/2x11x1'-3 W/ VERT LSL HOLES
NOTES: AND (6) 3/4" BOLTS. FINGER
SEE 18 / S-501 FOR ADDNL INFO TIGHTEN, BACK OFF NUT 1/4 TURN
ADD ADD
RFC 062 005 AND DAMAGE THREADS
005

19 NO SCALE SPRT FOR PARTITION AT DECK 15 NO SCALE T/COL TO GIRDER AT PENTHOUSE 11 1 1/2" = 1'-0" SUNSHADE TO HSS 8x3 7 1 1/2" = 1'-0" HSS COL CONN AT D/1.9 3 NO SCALE SOUTH EAST STAIR - ROOF 3

Issue Date
NOTE 1
NOTE 4 BP#3 DECEMBER 21, 2012
NOTE 2

ADDENDUM 005 JANUARY 25, 2013

NO WELDING . ADDENDUM 006


RECORD DRAWINGS
FEBRUARY 8, 2013
APRIL 18, 2014

PERMITTED AT 2" 3" 1 1/2"


DATE PRINTED: 4/18/2014 9:10:18 AM

THIS LOCATION NO VERTICAL RXN FROM (3/16)


SUNSHADE ABOVE. (3/16)
NOTE 3 5/16 PROVIDE VERTICAL EA PL
5/16
CJP T&B 5/16 SLOTTED HOLES IN
CONTR OPTION TO TYP SUNSHADE VERT
5/16 SHOP WELD STUB 3/16 3 SIDES
3/16 TYP
1/2" CLR
DESIGNERS: KH/AM

AT CORNER OR TEE JOINT


NOTE 2

1 1/2"

NOTE 3
SHEAR CONN, SEE Project Number: 2011101.00
STEEL CONN
3"

PL3/8 (AESS) EACH HSS8x3 W/ CAP PL 1/4


SCHED HSS12x3 W/ CAP PL 1/4 AT SIM
Drawn By: KH/AM
NOTE 4 SIDE OF SUNSHADE
VERT, CONTR COORD 3/16
NOTE 1 HSS12X3 Reviewed By: KH
1 1/2"

9
LOC WITH SUNSHADE PL1/2x6x7 ES 3/16
S-503 Approved By: PD
SUPPLIER PL 1/2x6x12 ES AT SIM
NOTES: AT BUTT JOINT SUNSHADE AND HSS14 COL
1. GREATER OF 1.5 x WEB THICKNESS OR 1 1/2"
PROJECT MANAGER: KH

MATERIAL
2. GREATER OF 1.0 x WEB THICKNESS OR 1", NEED NOT EXCEED 2" 10 1/2" SEPARATION BY
MM JOB #: 23616.S.01

3. MIN RADIUS = 3/8" SUPPLIER


4. BACKING MAY REMAIN IN PLACE UNO. MAX STEEL DETAILS
PRINCIPAL: PD

ADD
005
EOR: PD

TYP WF CJP WELD ACCESS AND


9 NO SCALE
BACKING 16 NO SCALE TYP MOMENT CONN 12 1 1/2" = 1'-0" SUNSHADE TO HSS 12x3 8 1 1/2" = 1'-0" TYP HSS GIRT TO COL 4 NO SCALE SOUTH EAST STAIR - ROOF 4
S-503
VARIES, 6" MAX
#4xCONT, TYP 4" THRU 6" 4" THRU 6"
C:\Proj\2011101_structural_kevinh.rvt #4x @12"

1 1/2" MIN
2" MAX
AT
THREADED #4x @12" ADHESIVE
WWR (NOTE 3)
ROD 5/16 ANCHOR, TYP METAL DECK SLAB SCHEDULE
A A #4@12" EW (3 EW MIN) DECK CONCRETE CONCRETE MIN DECK
PL3/8x3 CONT W/ 1/2"
HAS @ 12" (NOTE 4), CONC ADDNL CONC TOTAL MAX MIN DECK GAGE, 2 DECK CONN DECK
#4xCONT TYP TOC DEPTH ABOVE (SECOND POUR) THK CONC TYPE (SEE SHEAR STUD UNSHORED GAGE, SPAN OR MAX DECK TYPE (SEE DIAPHRAGM
LOCATE PL BELOW
ALL SIDES SLAB MARK TYPE (IN) DECK (IN) (IN) (IN) GEN NOTES) LENGTH (IN) SLAB REINF CLEAR SPAN 1-SPAN MORE CANTILEVER SCHED) SHEAR (PLF) REMARKS
WWF (NOTE 3), TYP
2VLI3.5A 2 VL 2 3 1/2 -- 5 1/2 TYPE 4 4 6x6-W2.1xW2.1 WWR 8'-9" 16 20 2'-6" A -- --
STD HOOK, TYP 2VLI8A 2 VL 2 3 1/2 4 1/2 10 TYPE 4 4 6x6-W2.1xW2.1 WWR (1ST POUR) 8'-9" 16 18 - A -- --
STUD RAIL TYPICAL POST-INSTALLED
TYPICAL #4@12"EW (2ND POUR)
OPTION REBAR OPTION
3NB 3N 3 -- -- -- -- -- -- 8'-9" -- 18 - B 677 --
SKEW HOOK 3NC 3N 3 -- -- -- -- -- -- 4'-0" -- 16 - C 1900 --
GREATER GREATER
AS REQ'D TO
THAN 6" THAN 6"

3"
WWR (NOTE 3) PROVIDE
#4x @12" CLR COVER
(2) #4xCONT, NOTES: The Lane Center for

3" TYP
TYP A 1. SEE SPECIFICATIONS FOR FLOOR FINISH & FLATNESS REQUIREMENTS
2. INSTALL DECK OVER 4 SUPPORTS (3 SPAN CONTINUOUS) WHERE POSSIBLE
Academic Health
3. COMPOSITE DECK DESIGN IS SIZED BASED UPON THE FOLLOWING MAXIMUM CONDITIONS: DECK CONNECTION SCHEDULE Sciences
POST INSTALLED REBAR OPTION a. WET WEIGHT OF CONC = 145 PSF NORMAL WEIGHT University of Colorado at
b. DECK DEFLECTION = 3/4" PERP SUPPORT MEMBERS PARALLEL SUPPORT MEMBERS SIDELAPS Colorado Springs
TYPE
c. AVERAGE SLAB THICKNESS INCREASED BY 1/2" FOR LEVELING CONNECTION PATTERN CONNECTION PATTERN CONNECTION PATTERN 2011101.00
STUD RAIL TYPICAL POST-INSTALLED d. CONST LIVE LOAD = 20 PSF. IF CONST LIVE LOAD WILL EXCEED 20 PSF, THEN CONTR SHALL DESIGN
OPTION REBAR OPTION DECK FOR INCREASED LOADING A 3/4" PUDDLE WELDS 36/4 3/4" PUDDLE WELDS 12" OC #10 SCREW 3'-0" OC
NOTES:
1. SEE MECH/ELEC DRAWINGS FOR SIZE, THICKNESS, AND LOCATIONS. 4. DECK TYPE 'VLJ' MAY BE SUBSTITUTED FOR DECK TYPE 'VLI'
B 5/8" PUDDLE WELDS 24/4 5/8" PUDDLE WELDS 12" OC #10 SCREW 10 / SPAN
2. EQUIP BASE SHALL NOT BE PLACED MONOLITHICALLY WITH SLAB/CURB WITHOUT WRITTEN 5. SCHEDULED STUD LENGTH IS NET-IN-PLACE LENGTH OF HDAS Owner
APPROVAL OF ENGINEER. 6. SUBMIT SHOP DRAWINGS INDICATING STUD LAYOUT (NO. OF STUDS/RIB) AND PLACEMENT ALONG BEAM C 3/4" PUDDLE WELDS 24/4 3/4" PUDDLE WELDS 12" OC WELDED 8 / SPAN Facilities Services
3. WWR TO MATCH THAT OF SLAB OR 6x6-W2.9xW2.9 WHERE SLAB WWR NOT IDENTIFIED. 7. NO TEMPORARY SHORING OF STEEL DECK PERMITTED WITHOUT PRIOR ACCEPTANCE OF THE ENGINEER University of Colorado at Colorado Springs
4. F1554 GR55 WELDABLE THREADED ROD WITH NUT MAY BE USED AS AN ALTERNATE TO HAS. 8. HANGERS WITH A 50 POUND MAXIMUM LOAD MAY BE PLACED AT 4'-0" MINIMUM SPACING EACH WAY. Campus Services Building, Rm 212
1420 Austin Bluffs Parkway
Colorado Springs, CO 80918
719-255-3505

17 NO SCALE TYP CONC EQUIPMENT BASE


EDGE OF MTL DECK
SHEET, TYP Architect
NOTES: METAL DECK PROPERTIES AndersonMasonDale Architects, P.C.
3198 Speer Boulevard

DECK DEPTH (IN)


C 1. FOR EQUIP WEIGHTS LESS THAN MINIMUM DECK DECK CLOSURES AS

S NEG (IN^3/FT)
S POS (IN^3/FT)
Denver, CO, 80211

DECK FY (KSI)
BEARINGS (IN)

DECK USAGE
200 LBS CURB MAY BE SUPPORTED REQUIRED 303-294-9448
~ ~

DECK GAGE
A
ON ROOF DECK

EXTERIOR
I (IN^4/FT)

INTERIOR
2. FOR EQUIP WITH CURB LOADS
LESS THAN 50 PLF USE DETAIL C DECK PERP SUPPORT 36" COVERAGE Clinical Planning
MC, TYP 3. FOR EQUIP WITH CURB LOADS TYPE BELOW James W Nakai & Associates, PC

B D LESS THAN 100 PLF PROVIDE DOUBLE 2VL 2 20 50 COMPOSITE 0.406 0.341 0.346 2 4 36/7 PATTERN: 520 E Colorado Ave
X.Xk 1.5 (B, F, A, VL) DECK Colorado Springs, CO 80903
LAYER OF DECK AND DETAIL C. 2VL 2 18 50 COMPOSITE 0.558 0.495 0.504 2 4 PARALLEL 719-635-2142
EXTEND DOUBLE DECK 1'-0" MIN EACH SUPPORT 36/4 PATTERN:
2VL 2 16 40 COMPOSITE 0.704 0.653 0.653 2 4

DECK SPAN
SIDE OF CURB AND 2" MIN PAST BELOW
BMS OR JOISTS ADJACENT SUPPORT MEMBER 1.5B 1 1/2 22 33 ROOF 0.155 0.186 0.192 2 4 Civil
24" COVERAGE
BELOW
~ DECK SPAN
~ 4. FOR EQUIP WITH CURB LOADS 1.5B 1 1/2 20 33 ROOF 0.201 0.234 0.247 2 4 PARALLEL 3N DECK 24/4 PATTERN: TerraNova Engineering, Inc.
815 S 25th Street
PLAN GREATER THAN 100 PLF USE DETAILS 1.5B 1 1/2 18 33 ROOF 0.289 0.318 0.327 2 4 SUPPORT CONN SIDELAP Colorado Springs, CO 80904
A AND B 3N 3 22 33 ROOF 0.770 0.382 0.433 2 4 CONNS 719-635-6422
3N 3 20 33 ROOF 0.960 0.501 0.552 2 4 PERP SUPPORT 36" COVERAGE
100 PLF TO 250 PLF MAX 3N 3 18 33 ROOF 1.330 0.688 0.749 2 4 CONN, EACH 2VLI DECK 36/4 PATTERN: Landscape
MECH CURB SHEET AT
COMPOSITE Lime Green Design, Inc
3/16 3 900 E. Louisiana Avenue, Suite 209
MC6x12 AT 1 1/2" ROOF TYP INDICATES CONNECTION
3/16 3 Denver, CO 80210
DECK, MC8x21.4 AT 3" NOTES: LAP ENDS OF LOCATION, TYP 303-733-7558
ROOF DECK 1. COMPOSITE METAL DECK SPECIFIED IS MANUFACTURED BY VULCRAFT. ALTERNATE ROOF AND
COMPOSITE METAL DECK MAY BE SUPPLIED PROVIDED MINIMUM DECK PROPERTIES ARE FORM DECK
SHEETS 2" UNO, Structural
SATISFIED AND THE RATIO OF THE RIB WIDTH MEASURED AT MID HEIGHT OF DECK TO RIB
HEIGHT IS NO LESS THAN 1.5. BUTT ENDS OF Martin/Martin
SUPPORTING BM 12499 West Colfax Avenue
COMPOSITE Lakewood, CO 80215
OR JOIST DECK SHEETS 303-431-6100

CURB PERPENDICULAR TO SUPPORT TYP DECK CONNECTIONS TYP FASTENER LAYOUT AT PERP SUPPORT
A Mechanical/Plumbing
Shaffer Baucom Engineering & Consulting
100 PLF TO 250 PLF MAX 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
MECH CURB
10
303-986-8200
2" MIN
NO SCALE METAL DECK SLAB SCHEDULE
MC6x12 AT 1 1/2"
ROOF DECK, MC8x21.4 Electrical
AT 3" ROOF DECK,
10'-0" MAX, Shaffer Baucom Engineering & Consulting

4'-0" MAX,
SPACE @ 4'-0 OC MAX 7333 West Jefferson Avenue, Suite 230

TYP
TYP Lakewood, CO 80235

SUPPORTING BEAM OR JOIST AT SIM, PROVIDE 1 1/2"x4" STL BM OR JOIST ~ ~ 303-986-8200

NOTCH @24"OC
INDIVIDUAL OPNG OR
GROUP OF SMALLER Technology
CURB PARALLEL TO SUPPORT
B OPNGS Rimrock Group
10807 New Allegiance Drive, Suite 400

50 PLF MAX
DECK DIRECTION
VARIES ~ ~ Colorado Springs, CO 80921
719-533-1112
MECH CURB C6x13 AT 'B' DECK
MC8X21.4 AT 'N' DECK, L4x4x5/16, 4 SIDES OF
PLACE OVER HIGH PLAN VIEW OPNGS PLAN VIEW
L3x3x1/4, FIELD CUT Building Performance Engineer
PL 16 GAx12xCONT
FLUTE NEAREST OPNG AS REQUIRED Ambient Energy
W/(2) ROWS OF #10 2" MIN BRG AT BEAM 130 W 5th Ave
SCREWS @12" AT BEAM, EXTEND AT JOIST, EXTEND Denver, CO 80204
L3x3x1/4 CONT W/ AT JOIST, EXTEND 303-278-1532
CHANNEL TO CL, MIN ANGLE LEG TO EDGE
1/2x4" HAS @ 24", CHANNEL TO EDGE 3/16
TYP TYP
3/16
SMALL MECHANICAL EQUIPMENT - DECK PARALLEL AT EA Cost Estimating
C CHANNEL COPE LEG EE Parametrix, Inc.
TOE, TYP 3/16 7186 South Highland Drive
50 PLF MAX Salt Lake City, UT 84121
MECH CURB ANGLE TO TYP 801-733-5900
3/16 1/4" MAX
CHANNEL,
TYP 3/16
PL 16 GAx12xCONT SECTION SECTION
W/(2) ROWS OF #10
SCREWS @12" ALTERNATE FRAME OPTION TYPICAL FRAME OPTION

AT OPENINGS LARGER THAN 13"


SMALL MECHANICAL EQUIPMENT - DECK PERPENDICULAR
D

TYP MTL DECK TO T/CONC WALL -


15 NO SCALE TYP MECH SUPPORT ON ROOF DECK 11 NO SCALE
CONT CLR DIM IN ANY DIRECTION: CLR DIM IN ANY DIRECTION: ADJACENT OPNG
18", NO REINFORCEMENT REQUIRED 24", PROVIDE REINF PLATE AS SHOWN
SEE PLAN < 18", TREAT GROUP AS INDIVIDUAL < 24", TREAT GROUP AS INDIVIDUAL Issue Date
OPNG W/ EXTENTS AS SHOWN, OPNG W/ EXTENTS AS SHOWN, PROVIDE
PROVIDE REINF PLATE OR FRAME ADJACENT OPNG FRAME DESIGN DEVELOPMENT SEPTEMBER 12, 2012
BP#2 NOVEMBER 16, 2012
FORMED EDGE BP#3 DECEMBER 21, 2012
RECORD DRAWINGS APRIL 18, 2014

EXTENTS OF GROUP
DATE PRINTED: 4/18/2014 9:10:21 AM

13" MAX
INDIVIDUAL OPNG

EW
EXTEND ROOF OR GROUP OF
1'-1
3/ 4"

OF GROUP
EXTENTS
DECK TO BEAM SMALLER OPNGS

1 0"
ROOF DECK OPNG:
COORD SIZE AND
AT DECK PARALLEL LOC WITH MEP AND
ARCH, TYP PL 16GA (MIN)
DESIGNERS: KH/AM

ABOVE OR

6" MAX
BELOW DECK

EW
SEE PLAN
#4xCONT AT EA
#10 TEK SCREWS

6" MIN,
DECK FLUTE Project Number: 2011101.00

TYP
AT PLATE EDGES,
FORMED EDGE (2) PER FLUTE Drawn By: KH/AM
PERP TO DECK
6" MAX Reviewed By: KH
AND AT CORNERS
EXTENTS
PD
2" CLR

Approved By:
OF GROUP
EXTENTS OF GROUP
PROJECT MANAGER: KH

FROM TOP OF AT OPENINGS UP TO 6" AT OPENINGS LARGER THAN 6" UP TO 13"


MM JOB #: 23616.S.01

FIRST POUR
NOTES: TYP METAL DECK DETAILS
AT DECK PARALLEL
PRINCIPAL: PD

1. FRAMES WILL SUPPORT THE WEIGHT OF A 500 LB MECH UNIT


EOR: PD

12 NO SCALE DECK TRANSITION 8 NO SCALE TYP METAL DECK ROOF OPENINGS


S-530
CASE 1: # STUDS < # RIBS/2
C:\Proj\2011101_structural_kevinh.rvt STEP 1 = ONE STUD EVERY THIRD RIB
MTL POUR STOP THICKNESS STEP 2 = 1/2 OF REMAINING STUDS AT EACH END OF BEAM, PLACE IN
EVERY OTHER EMPTY RIB STARTING FROM THE BEAM END BEAM FLANGE LIMITATIONS
OVERHANG 8 3/4" bf
TOTAL SLAB

BEAM CL
3" MAX STEP 2: 7 1/4" < bf < 8 3/4"
DEPTH 3" 6" 9" 12"

.
LTS 36" MAXIMUM 5 3/4" < bf

SINGLE ROW SPACING


#4x @12" STEP 1: 5" < bf 5 3/4"

SEE NOTE 1
5 1/2" 16 GA 14 GA 12 GA 3/16"

4" MIN
.

.
4" bf

1" CLR,
TYP
#4xCONT

DECK SPAN
SKEW HOOK

bf
MTL POUR STOP BY AS REQ'D 1 3/8" MIN
TO PROVIDE 3"

.
DECK MNFR TO BEAM CL 4" 3" MI
M N

3" MIN
1 3/8"

3" MIN
SLAB REINF, SEE CLR COVER 2" MIN

MIN
IN

.
1 3/8"
3"
1 1/2-6

MUTLIPLE ROW SPACING


SUPPORT WET

MIN

4 1/2"
MIN

MI
CASE 2: # STUDS < # RIBS

MIN
N
METAL DECK SLAB A

MI
1 3/8" MIN

N
WEIGHT OF CONC SEE NOTE 1, TYP

DECK SPAN
SCHED STEP 1 = ONE STUD EVERY OTHER RIB

3"
(14 GAGE MIN) STEP 2 = 1/2 OF REMAINING STUDS AT EACH END OF BEAM, PLACE IN
A 1 STUD/RIB 2 STUDS/RIB 3 STUDS/RIB The Lane Center for

N
1 3/8" MIN

MI
. . . .

EMPTY RIBS STARTING FROM THE BEAM END DECK


Academic Health

3"
4 1/2"
MTL POUR STOP, STEP 2: STIFFENER

MIN
SEE TABLE Sciences

.
MAX DECK CANTILEVER 1 3/8" MIN
PER METAL DECK STEP 1: STUDS MAY BE 3" MIN University of Colorado at
10

.
SLAB SCHEDULE, SEE INSTALLED Colorado Springs

1" MIN
S-530 OVERHANG

TYP
EITHER SIDE OF D

4 1/2"
2011101.00

MIN
SPACE STUDS
DECK STIFFENER UNIFORMLY OVER
OVERHANG UP TO 12" (STRONG OR LENGTH OR BTWN
WEAK POSITION) 3" MIN
AT DECK PERPENDICULAR 1 3/8" MIN SUPPORTED
1 3/8" MIN Owner
AT DECK PARALLEL MEMBERS
BEAM CL Facilities Services
University of Colorado at Colorado Springs
CASE 3: # RIBS < # STUDS < 2x # RIBS Campus Services Building, Rm 212
STEP 1 = ONE STUD EVERY RIB STUD PLACEMENT AT DECK PERPENDICULAR STUD PLACEMENT AT DECK PARALLEL 1420 Austin Bluffs Parkway
STEP 2 = 1/2 OF REMAINING STUDS AT EACH END OF BEAM, PLACE Colorado Springs, CO 80918
719-255-3505
ONE IN EACH RIB STARTING FROM THE BEAM END C
17 NO SCALE TYP INT SLAB EDGE STEP 2:
B

.
Architect
AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
Denver, CO, 80211
STEP 1: ~ 50 STUDS SPACED OVER FULL
~ 303-294-9448

.
LENGTH OF BEAM
PARALLEL SUPPORT
SEE DECK PERP BEAM [50]
CONNECTION PER Clinical Planning

~
CONDITION FOR
CONNECTION
STUD LAYOUT B James W Nakai & Associates, PC

EQ SPACED
GUARDRAIL POST, #4x5'-0" @1'-6" TOP SCHEDULE

26 STUDS
520 E Colorado Ave
SEE ARCH 3/16 AT DECK Colorado Springs, CO 80903
AT GIRDER OR
TRANSITION
DIRECTION CHANGE
SIDELAP
CONNECTION PER ~ 719-635-2142

COVER
BEAM CL

1" MIN
PL3/8x3xCONT CONNECTION
1/4 2-12 CASE 4: # STUDS > 2x # RIBS 1" MIN C
SCHEDULE Civil

~
STEP 1 = TWO STUDS EVERY RIB

GIRDER [26,8,26]
TerraNova Engineering, Inc.
STEP 2 = 1/2 OF REMAINING STUDS AT EACH END OF BEAM, PLACE

1" CLR

EQ SPACED

DECK SPAN
815 S 25th Street
# OF STUDS ARE

3 7/8"

8 STUDS
1" MIN
ONE IN EACH RIB STARTING FROM THE BEAM END Colorado Springs, CO 80904

CLR
INDICATED THUS 719-635-6422
STEP 2:
ON FRAMING PLAN

.
1 3/8"
MIN DECK Landscape

~
SEE MTL CLOSURES CONSIDER NON- Lime Green Design, Inc
DECK BY DECK

EQ SPACED
PL3/16x2x4 7/8. INSTALL AFTER STEP 1: ORTHOGONAL 900 E. Louisiana Avenue, Suite 209

26 STUDS
3/16

.
SUPPLIER Denver, CO 80210
SLAB EDGE BENT PL HAS SCHED FOR BEAMS TO BE "DECK 303-733-7558
BEEN WELDED TO BEAM. 20 STUD PERPENDICULAR"

~
ALIGN 1 1/2" FROM CL OF EA FOR SLAB EDGE LENGTH FOR STUD LAYOUT
S-531 A
RAILING POST. NOT TYP STUD, DECK, AND WWR INFO Structural

~
REQUIRED AT RAILING Martin/Martin
CORNERS A 12499 West Colfax Avenue
NOTES: Lakewood, CO 80215
BEAM CL 303-431-6100
1. PROVIDE STUDS AT 24" MAX WHERE NUMBER OF STUDS IS NOT INDICATED

STUD LAYOUT AT DECK PERPENDICULAR Mechanical/Plumbing


ASI Shaffer Baucom Engineering & Consulting
020 D 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
303-986-8200
14 NO SCALE SLAB EDGE AT RAILING TYPE A 10 NO SCALE TYP SHEAR STUD LAYOUT
Electrical
1' MAX TO EDGE 3x DIA OF LARGER 10"

DECK SPAN
Shaffer Baucom Engineering & Consulting

1" MIN 1'-2"x1'-2" OF FLASHING SLEEVE, TYP MAX OFFSET > 3" OFFSET < 3"
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
(IF REQD) 303-986-8200
DRAIN BODY OR DECK MAX OPNG

EXTEND BARS
ES OF 2" TYP ANGLE TO
NOTE 5 3/16

2'-0" TYP
CLOSURE 1/8 1 CHANNEL COL FLG,
#5 T&B ES
TYP 3/16 Technology

1/2" MAX
1/8 1 AT EACH
DRAIN FLASHING HIGH FLUTE

10" SQ MAX
Rimrock Group
(IF REQD) 10807 New Allegiance Drive, Suite 400

10" OR

3"
3'-0" Colorado Springs, CO 80921
(2) #5@3"

P X,
1 1/2" MIN

#4xCONT, TYP #4x @12" 719-533-1112

2"

TY MA
CTR ES FOR
14

/2"
3'-0" EDGE

21
A S-541

2"

3" MAX
C4x5.4x4'-0 ES OF PL Building Performance Engineer
3/4"x6" OPNG DECK SPAN

1/2" MAX
Ambient Energy
CUT 2 VERT
HDAS @12" 130 W 5th Ave
2" TYP

RIBS MAX Denver, CO 80204


303-278-1532
3"

NOTES:
1. DECK MAY BE CUT PRIOR TO SLAB POUR
2. IF DRAIN FLASHING EMBED IN SLAB IS REQUIRED, FLASHING SHALL NOTE 4 PLAN Cost Estimating
NOT EXTEND OVER THE TOP OF COMPOSITE BEAMS Parametrix, Inc.
3. PROVIDE BACK UP BARS IF REQD FOR DECK WELDING (2) 1/2"x6 HDAS 7186 South Highland Drive

#4@12"OC CLOSURE ANGLE TYP Salt Lake City, UT 84121


CONT BAR, SEE 3/16 801-733-5900
xCONT AT STEP, AT FLOOR DRAIN
EXTERIOR EOS PROVIDE 16 GA MIN
CTR IN SLAB L4x4x5/16xCONT, L3x3x1/4 TYP, SUPPORT
DETAILS SHEET METAL AS
BTWN BEAMS ONLY REQD WHEN
NOTES: BENT PL TO REQUIRED
3/16 2-12 UNSUPPORTED DECK AREA
1. PLACE SLEEVE ON DECK PRIOR TO CONCRETE PLACEMENT ANGLE AND EXCEEDS 3"
3/16 2-12
2" CLR, TYP' 2. DO NOT CUT METAL DECK UNTIL CONC HAS REACHED DESIGN STRENGTH COL 3/16
2'-0" TYP 3. 2" SLEEVES DO NOT REQUIRE TRIM STEEL (6" MIN SPACING) CONDITION #1
4. MULTIPLE OPENINGS PERP TO DECK SPAN CLOSER THAN MIN SPACING SHALL BE
L3x3x1/4
CONSIDERED A SINGLE OPENING AND REINFORCED PER 'TYPICAL OPENING' DETAIL.
5. PROVIDE REINFORCING BETWEEN MULTIPLE OPENINGS PARALLEL TO DECK SPAN SECTION
L3x3x1/4 DECK SPAN
(2) #4 TYP AT OPENINGS 10" OR LESS
AT PERIMETER COLUMN
19 NO SCALE TYP SLAB STEP - DECK PARALLEL
10'-0" MAX
PROVIDE 16 GA MIN
~ ~ SHEET METAL TO FILL Issue Date
3/16 COL CAVITY AS REQD
TYP CONST JT
3/16 1 1/2" TYP ~ ~ ~ 1'-1 1/8" MIN, DESIGN DEVELOPMENT SEPTEMBER 12, 2012
6'-0" MAX

PARALLEL 3/16
TO BEAMS TYP TYP BP#2 NOVEMBER 16, 2012
STEEL BEAM 3/16 BP#3 DECEMBER 21, 2012
OR CONC WALL BEAM CONDITION #2 ASI 020 MAY 20, 2013

~
RECORD DRAWINGS APRIL 18, 2014
DATE PRINTED: 4/18/2014 9:10:22 AM

C8x11.5 TYP

EQ
SEE PLAN 3/16
1'-0" MAX TYP
LTS 3/16
~

~
B
~ GIRDER
A ~ MTL POUR STOP
BY DECK MNFR
. .

DECK SPAN

EQ
1/2" DAS @ 12" 2" MIN BRG
3/16 1 1/2-6 BEAM PROVIDE 16 GA MIN
PLAN VIEW
~

~
SHEET METAL TO FILL
COL CAVITY AS REQD
1" CLR

DUCT SUPPORT #4x4'-0"@12" CTR IN SLAB


GIRDER

GIRDER
3/16
DESIGNERS: KH/AM

BY CONTR

.
OFFSET HDAS L3x3x1/4x9 W/ (2) OVER DECK
3/16

.
ON FLG IF REQD 3/4"x6 1/2" EMBED L3x3x1/4
EXP ANCHORS

3" MIN,
BEAM

TYP
#4xCONT
~

~
1/4 Project Number: 2011101.00

EQ CONDITION #3 Drawn By: KH/AM


3000 LB POINT LOAD EDGE OF L8x4x3/4x8 LLV, CONST JT
6"

OR 500 PLF MAX SLAB HOOK BARS IF NOT POSSIBLE CNTR CHANNEL PARALLEL Reviewed By: KH
3 SIDES SEE GENERAL NOTES FOR POUR AT INTERIOR COLUMN
TO ACHIEVE 2'-0" EXTENSION WEB ON ANGLE PL 3/8 3/16 TO GIRDERS
BENT PL 3/8 BEYOND EDGE OF OPNG LENGTH AND AREA LIMITS Approved By: PD
NOTES:
~

~
1. DECK OPNGS REQUIRE STIFFENERS OR FRAMING. SEE DECK OPNG DETAILS CONN OPTIONS TO STEEL TO CONCRETE BEAM
5'-0" . NOTES:
2. CENTER BARS IN SLAB ABOVE METAL DECK
PROJECT MANAGER: KH

1. CONTRACTOR MAY DESIGN ALTERNATE METHODS OF DECK SUPPORT.


NOTES: ~ ~ ~ DECK SUPPORTS SHALL BE ABLE TO SUPPORT THE DECK AS A FORM WITH
MM JOB #: 23616.S.01

TRIM REINFORCING AT OPENINGS LARGER THAN 10" 1. NO SAW CUT JOINTS IN ELEVATED SLAB ON METAL DECK UNO THE WET WEIGHT OF THE CONCRETE AND ALL CONSTRUCTION LOADS
TYP METAL DECK DETAILS
PRINCIPAL: PD

A B
EOR: PD

20 NO SCALE TYP MECH SHAFT OPENING 16 NO SCALE TYP METAL DECK SLAB OPENINGS 8 NO SCALE TYP SLAB CONST JOINT LOCATIONS 4 NO SCALE TYP MTL DECK SUPPORT AT COL
S-531
DESIGN CRITERIA FOR PERFORMANCE SPECIFIED COLD FORMED STEEL FRAMING (CFSF)
C:\Proj\2011101_structural_kevinh.rvt HOLD BACK WEB COLD FORMED METAL FRAMING USED FOR EXTERIOR CLADDING SUPPORT IS A PERFORMANCE
STIFFENER TO AVOID 1/8 1 MEMBER DEPTH: SPECIFIED SYSTEM DESIGNED AND PROVIDED BY THE CONTRACTOR (CFSF CONTRACTOR). REFER TO
RET TOP MEMBER DEPTHS ARE GIVEN
INTERFERENCE 1/8 4 SPECIFICATIONS FOR PROFESSIONAL ENGINEERING AND SUBMITTAL REQUIREMENTS. CONTRACTOR
W/ANGLE WELD IN 1/100 INCHES SHALL DESIGN ALL MEMBERS AND CONNECTIONS FORMING A COMPLETE SYSTEM FOR THE DEAD,
CONCENTRATED RXN FROM 3/8" TOUCH UP FIELD WELDED AREA (EXAMPLE: 6" = 600 x 1/100")
SEE ARCH WITH ZINCH RICH PAINT AFTER SNOW AND WIND FORCES INDICATED IN THE DESIGN CRITERIA SECTION. IN ADDITION TO THOSE FORCES
WINDOW MULLION ABOVE WEB STIFFENER IS A STUD
AT SOME LOCS, INCLUDE WELDING STYLE: THE FOLLOWING CONSTRAINTS SHALL BE MET:
SEGMENT W/LENGTH = 1. FRAMING MEMBERS WILL BE THE DEPTH NOTED ON WALL SECTION ON THE ARCHITECTURAL
RIGID CONN TO SLAB DEAD, WIND AND SNOW 1" TYP SEE PLAN THE FOUR ALPHA CHARACTERS UTILIZED
STUD DEPTH -3/8". FASTEN DRAWINGS.
ABOVE BY CFS BY THE DESIGNATOR SYSTEM ARE:

4" MIN
LOAD ON SUNSHADE, TYP. W/(4) #10 TEK SCREWS
CONTRACTOR S = STUD OR JOIST SECTIONS
BENT PL 3/8 1" T = TRACK SECTIONS 2. MINIMUM STUD THICKNESS BASED ON THE ATTACHMENT OF CLADDING MATERIAL IS GIVEN IN THE
600S SOFFIT HANGER (HDG) U = CHANNEL SECTIONS FOLLOWING TABLE:
SEE ARCH
FULL AVAILABLE
LENGTH, 4" MIN
600 S 162 - 54 F = FURRING CHANNEL SECTIONS
MATERIAL ATTACHED TO STUDS MIN. MIL THICKNESS MAX. STUD SPACING
(EXAMPLE: STUD OR JOIST SECTION = S)
A WELDED BRICK LEDGE 68 16" OC
600S WALL FRAMING MATERIAL THICKNESS: BRICK BACKUP 43 16" OC
RIGID CONN FROM METAL PANELS 54 16" OC
BY CFS CONTRACTOR MATERIAL THICKNESSES ARE GIVEN IN
SOFFIT TO HANGER ALL OTHERS 33 16" OC
1/1000 INCHES
BY CFS CONTR 1"
(EXAMPLE: 54 MILS = 0.054", 1 MIL = 1/1000")
The Lane Center for
7 SEE ARCH
S-540
COLD FORMED STEEL TRACK THICKNESSES SHALL BE EQUAL TO OR GREATER THAN THE WALL STUDS Academic Health
ILLUSTRATION OF WELD FLANGE WIDTH: ATTACHED TO IT.
4 4" MAX FLANGE WIDTHS ARE GIVEN IN 1/100 INCHES Sciences
S-540 (EXAMPLE: 1 5/8" = 1.625" = 162 x 1/100") DO NOT BASE BIDS ON THE ABOVE MINIMUM THICKNESSES. VARY THICKNESS, FLANGE WIDTH, YIELD University of Colorado at
STRESS, AND SPACING AS REQUIRED TO SATISFY PERFORMANCE CRITERIA. SEE S-221 FOR SIZES FOR Colorado Springs
DO NOT ATTACH SOFFIT TYPICAL ANNOTATION BIDDING 2011101.00
FRAMING TO STOREFRONT
HEADER 3. FRAMING MEMBERS WILL DELIVER FORCES TO THE STRUCTURAL FRAME AT THE LOCATIONS,
DIRECTIONS, AND MAGNITUDES NOTED IN THE DETAILS. VARIATIONS PROPOSED BY THE
RXN FROM STOREFRONT CENTER ON VENEER CONTRACTOR/CFSF ENGINEER TO ACCOMMODATE PREFABRICATION AND ALTERNATE SCHEMES WILL Owner
MULLIONS, BELOW DESIGN JOINTS, SEE ARCH FOR BRICK LEDGE BE SUBJECT TO THE EOR'S REVIEW AND APPROVAL. CONTRACTOR SHALL COMPENSATE M/M FOR THIS Facilities Services
800S HEADER TO SPAN JAMB LOCS 1/4" MAX ANGLE REVIEW. University of Colorado at Colorado Springs
TO JAMB COLD FORMED STL 3" MIN EDGE DISTANCE Campus Services Building, Rm 212
A 1420 Austin Bluffs Parkway
HORIZ STUD SUPPORT RFC 127 4" MIN FASTENER SPACING 4. LOADS: Colorado Springs, CO 80918
-WIND LOADS GIVEN IN THESE DOCUMENTS ARE BASED ON A COMPONENT AND CLADDING TRIBUTARY 719-255-3505
EXTERIOR WALL AT LEVEL 1 BY CFS CONTRACTOR. PAF
17 NO SCALE
STOREFRONT
MAX DEFORMATION
UNDER DESIGN LOADS
9 NO SCALE TYP CF WEB STIFFENER AT BL AREA OF 10 SQUARE FEET. REDUCTION IN LOADS BASED ON TRIBUTARY AREA ARE ALLOWED AS
PERMITTED IN THE GOVERNING BUILDING CODE.
-CFSF ENGINEER IS RESPONSIBLE FOR CALCULATING CUMULATIVE FORCES AT WINDOW JAMBS AND Architect

1/3 SLAB THK


SHALL NOT EXCEED

P MAX =
1/32" DUE TO ALL KNURLED SHANK MULLIONS FROM DISTRIBUTED LOADS PROVIDED IN THESE DOCUMENTS'. COORDINATE MULLION AND AndersonMasonDale Architects, P.C.
3198 Speer Boulevard
SOURCES JAMB LOCATIONS WITH THE GENERAL CONTRACTOR. Denver, CO, 80211
FASTENERS ARE TO BE -CFSF CONTRACTOR SHALL ACCOUNT FOR ANY ECCENTRICITY AT CONNECTIONS OF WINDOW HEADER 303-294-9448
DRIVEN THROUGH THE TRACK OR SILL PLATE WHICH COULD CAUSE ECCENTRIC LOADS ON COLD FORMED METAL FRAMING.
BRICK VENEER THICKNESS OF STEEL
5. DEFLECTION CRITERIA Clinical Planning
RIGID CONN TO SLAB IN STEEL IN CONCRETE -MAX HORIZONTAL DEFLECTION: James W Nakai & Associates, PC
10 METAL PANEL AT SIM.
ABOVE BY CFS S-540 FOR STUDS SUPPORTING METAL PANELS = SPAN/240 520 E Colorado Ave
CONNECT METAL Colorado Springs, CO 80903
CONTRACTOR BRIDGE PL CONN TO MTL TYPICAL CF-P POWDER ACTUATED FASTENER (PAF) FOR STUDS SUPPORTING MASONRY VENEER = SPAN/600
PANEL TO EACH 719-635-2142
DECK DESIGNED BY CFSF EQ EQ FOR STUDS SUPPORTING STUCCO AND PLASTER = SPAN/360
600S SOFFIT HANGER STUD.
CONTRACTOR FOR STUDS SUPPORTING OTHER = SPAN/240
-MAX VERTICAL DEFLECTION: Civil
NO BRICK RELIEF ANGLE FOR EXTERIOR SOFFIT STUDS SUPPORTING STUCCO OR PLASTER = SPAN/360 TerraNova Engineering, Inc.
OR MULLION REACTION -PER IBC TABLE 1604.3 FOOTNOTE F, WIND LOAD IS PERMITTED TO BE TAKEN AS 0.7 TIMES THE 815 S 25th Street
AT SIM Colorado Springs, CO 80904

d (MIN) TO EDGE OF
COLD-FORMED STL
COMPONENT AND CLADDING LOADS FOR THE PURPOSE OF DETERMINING DEFLECTION LIMITS EXCEPT 719-635-6422
RIGID CONN FROM
9 AT COLDFORMED STEEL FRAMING SUPPORTING MASONRY VENEER.
SOFFIT TO HANGER
S-540 - MAX VERTICAL LIVE LOAD DEFLECTION LIMITS USED IN DESIGN OF STRUCTURAL MEMBERS AT
BY CFS CONTR
VERTICAL SLIP CONNECTIONS: Landscape
SEE ARCH BRIDGE PL AND TEK SCREW SIZE d PERIMETER BEAMS AT STUD INFILL FRAMING= 3/8 Lime Green Design, Inc
STUD TO TRACK PERIMETER BEAMS AT STUD BY-PASS FRAMING= 3/4 900 E. Louisiana Avenue, Suite 209
#6, #8 1/2" INTERIOR FRAMING = SPAN/ 360 Denver, CO 80210
CONN BY CFSF TEK SCREWS 303-733-7558
CONCENTRATED RXN FROM CONTRACTOR
800S WALL FRAMING #10 5/8"
WINDOW MULLION BELOW AT 6. ADDITIONAL CRITERIA FOR CFSF.
SOME LOCS. INCLUDE LATERAL #12 3/4" -PROVIDE DOUBLE JAMB STUDS MIN AT ALL OPENINGS. Structural
LOADS FROM WINDOW AND EDGE OF ATTACHED -PROVIDE 1 ROW AT MID-HT (MIN) HORIZONTAL STUD BRIDGING.
A Martin/Martin
DEAD, SNOW AND WIND LOADS COLD-FORMED STL -PROVIDE 1 STUD EA SIDE OF MASONRY CONTROL JOINTS RE: ARCH FOR LOCATIONS 12499 West Colfax Avenue
JAMB PACK AND ON SUNSHADE. d (MIN) BTWN FASTENERS
7. WINDOW MULLIONS APPLY CONCENTRATED LOADS TO STUD WALLS SUPPORTING WINDOWS. DESIGN Lakewood, CO 80215
CONNS BY CFS d (MIN) TO EDGE OF FOR THE EFFECT OF CONCENTRATED LOADS. DESIGN FOR EFFECTS OF ECCENTRICCITY OF 303-431-6100
9 1/2"

CONTR SOFFIT FRAMING AND RIGID DECK PERPENDICULAR TO WALL DECK PARALLEL TO WALL COLD-FORMED STL CONNECTION SHOWN IN THE WINDOW SHOP DRAWINGS.
CONNECTION TO WALL FRAMING
8. ALL CFSF CONNS TRANSFERRING FORCE SHALL BE TIGHT, WITH MINIMAL DEFORMATION AND PLAY. Mechanical/Plumbing
BY CFS CONTRACTOR AT SOME
STOREFRONT JAMB RE: SPECS FOR REQUIREMENTS.
A LOCS TYPICAL CF-P TEK SCREW SPACING Shaffer Baucom Engineering & Consulting
9. AT CFSF SUPPORTING METAL PANEL, METAL PANEL SHALL BE CONNECTED AT EVERY WALL STUD. 7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
TYP CF METAL STUD DEFLECT TRACK 303-986-8200

18 NO SCALE EXTERIOR WALL AT LEVEL 1 BRICK 14 NO SCALE EXTERIOR WALL AT STRIP WINDOW 10 NO SCALE
AT MTL DECK SLAB 6 NO SCALE TYP COLD FORMED WALL FRAMING INFO
SEE ARCH Electrical
Shaffer Baucom Engineering & Consulting
CONCENTRATED RXN FROM 1" TYP SEE PLAN 7333 West Jefferson Avenue, Suite 230
WINDOW ABOVE. Lakewood, CO 80235
SEE ARCH 303-986-8200

SEE ARCH
Technology
1 1/2"1" Rimrock Group
10807 New Allegiance Drive, Suite 400
600S WALL FRAMING Colorado Springs, CO 80921
SIM FOR 719-533-1112
14
STUDS BTWN S-540 3/16
CHANNELS RIGID CONN BY
2" MIN 3/16 CFSF CONTRACTOR
VENEER Building Performance Engineer
PL3/16x 'T' - 1" SEE PLAN Ambient Energy
L6x6x3/8xCONT 130 W 5th Ave
3/16 2-12 3" MAX
Denver, CO 80204
PL3/16x4, CTR ON 2-12 PAF SIZE &
FIXED CONNECTION 3/16 303-278-1532

T
ANGLE LEG SPACING BY CFSF 3 SIDES
(TSN MIDWALL OR CONTRACTOR 1/8 1/2" DAS x 3'-0" 3/16 2-12

12" MAX
12" MAX
SIMILAR) BY CFS @ 12" OC
CONTRACTOR Cost Estimating
3 SIDES
3/16 Parametrix, Inc.
7186 South Highland Drive
3/16 Salt Lake City, UT 84121

1" CLR
3/16 801-733-5900
1 1/2" 1" AT MASONRY VENEER AT ALL OTHER FINISHES
6 BENT PL 5/16xCONT
S-540
3/16 2
3/16 2 NOTES:
- CONNECTIONS SHOWN ARE TYPICAL EACH STUD 2" MIN SLAB REINF, SEE METAL
BRICK VENEER DECK SLAB SCHED
1" DECK ORIENTATION
ADD VARIES
005 3/16 2 RFC 120 TYPICAL SLAB EDGE
L3x3x3/16 AT EACH 3/16 2
EXTERIOR WALL BELOW STRIP TYP CF RIGID CLIP CONN AT STL
19 NO SCALE
WINDOW
CHANNEL, EXTEND
1" MIN PAST BEAM
WEB
11 NO SCALE TYP CF BOTTOM TRACK TO CONC 7 NO SCALE
FRAMING
C6x8.2 @ 6'-0" OC AND 2" MIN DECK ORIENTATION Issue Date
2'-0" MAX FROM JOINTS. L6x6x3/8xCONT
3/16 2-12 VARIES
INSTALL AT CFSF 2-12
3/16 DESIGN DEVELOPMENT SEPTEMBER 12, 2012
TOLERANCES BP#3 DECEMBER 21, 2012
3 5/8" MAX A EXTEND TYP SHEAR ADDENDUM 005 JANUARY 25, 2013
1/2" 3/16 CONN FROM STL RECORD DRAWINGS APRIL 18, 2014
3/16 CONN SCHED TO
DATE PRINTED: 4/18/2014 9:10:24 AM

STRUCTURAL WALL W8x24 AESS. INSTALL VERT SLIP EXTENTS OF GIRDER


SYSTEM AT CFSF TOLERANCES. 3 SIDES CONN, TYP AS SHOWN, PROVIDE
3/16 9
EA STUD MAXIMUM # OF
VENEER TIES SEE ARCH S-540 NO KICKER OR FULL DEPTH
BEAM CONN REQD. DO NOT BOLTS
PL3/16x4, CTR ON 1 1/2" 1" W8 SHALL BE
VERTICAL LEG OF CONNECT STUDS TO BEAM
ANGLE TIGHT TO BACK BEAM WEB CONTINUOUS AT
8" MAX

AT ROOF DECK
OF VENEER CONNECT WINDOW TO CORNER STRIP FLG ONE SIDE

T&B
DESIGNERS: KH/AM

CFS FRAMING, DO NOT OR COPE

k
" M AX

ATTACH TO W8
1/2 /4" M
AX

AT PERPENDICULAR FRAMING
1

1/4" MIN 1/4" MAX 4 FOR SLAB


1/2" MAX 1/2" MAX VERT SLIP S-540 EDGE INFO Project Number: 2011101.00
VERT SLIP CONN CONN, TYP
VENEER LOOSE LINTEL SCHEDULE EA STUD Drawn By: KH/AM

OPENING LENGTH, L LINTEL BEARING EE REMARKS Reviewed By: KH

Approved By: PD
L 6'-0" L3 1/2x3 1/2x1/4 4" -
6'-0" < L 8'-0" L5x3 1/2x1/4 6" LLV
TYPICAL AT PERGOLA AT CORNER NO KICKER OR FULL DEPTH
8'-0" < L 10'-0" L6x3 1/2x5/16 6" LLV
PROJECT MANAGER: KH

ADD
MAX MIS-ALIGNMENT = 1/8". BEAM CONN REQD. DO NOT
MM JOB #: 23616.S.01

10'-0" < L 12'-0" L6x3 1/2x1/2 6" LLV RFC 057 TYP HORIZ AND VERT DUE TO
005 CONNECT STUDS TO BEAM
NOTE: ALL SOURCES. TYP EXT WALL
PRINCIPAL: PD

ALIGN WITH ALL MASONRY CONTROL JOINTS, 30'-0" MAX RFC 057 AT SLAB ON METAL DECK FLOOR
A
EOR: PD

TYP CF BYPASS VERT DEFLECTION


20 NO SCALE TYP MAS VENEER LOOSE LINTEL 16 NO SCALE EXTERIOR WALL AT STRIP WINDOW - 2 12 NO SCALE TYP CF STUD TO STUD SLIP CONN 8 NO SCALE
CONN AT FLR 4 NO SCALE TYP EXTERIOR SLAB EDGE
S-540
C:\Proj\2011101_structural_kevinh.rvt ECC
A 4
FOR SLAB EDGE
S-540
DEAD LOAD (DL)

SOFFIT FRAMING, DO NOT


ATTACH TO WALL STUDS WIND LOAD 800S WALL FRAMING BY
CFS CONTRACTOR
CURTAINWALL CONN BY
CURTAINWALL
SUPPLIER. DESIGN SEE ARCH
CONN TO MULLION FOR
MOMENT = DL*ECC

VERTICAL AND HORIZ 11


RXN AT SLAB EDGE SECTION S-540
The Lane Center for
VERT SLIP CONN 8
BY CFS CONTR S-540
ONLY
7
Academic Health
4
S-540 S-540 Sciences
PROVIDE TWO SIDED University of Colorado at
BRICK VENEER CONNECTION TO Colorado Springs
MULLION BEAM BEYOND 2011101.00
800S WALL FRAMING BY
CFS CONTRACTOR
600S WALL FRAMING BY
CFS CONTRACTOR Owner
Facilities Services
University of Colorado at Colorado Springs
Campus Services Building, Rm 212
PLAN BRICK VENEER 1420 Austin Bluffs Parkway
Colorado Springs, CO 80918
719-255-3505

17 NO SCALE STAIR 2 SOFFIT 9 NO SCALE EXTERIOR SLAB EDGE AT CW


HANGER/KICKER Architect
CONNECTION AND AndersonMasonDale Architects, P.C.
FASTENERS BY CFS 3198 Speer Boulevard
CONTRACTOR. INSTALL Denver, CO, 80211
1 303-294-9448
PL3/8x8, ALIGN TOP OF PER MNFR'S
PLATE WITH TOP OF SLAB, 800 S CFS WALL RECOMMENTATIONS. 1
AT LOCS WITH HORIZ STUD FRAMING BY CFS Clinical Planning
SUPPORT AT BOT FLANGE CONTRACTOR
James W Nakai & Associates, PC
OF BEAM, PROVIDE PLATE 9 520 E Colorado Ave
TO ALIGN WITH BEAM BOT S-540 Colorado Springs, CO 80903
BRICK VENEER 719-635-2142
FLANGE
CONNECT CFS FRAMING TO
Civil
PLATE AND FLANGE AS INDICATED 8
IN ADJACENT WALL FRAMING S-541
SEE ARCH TerraNova Engineering, Inc.
VERT SLIP CONN BY 815 S 25th Street
DETAILS. Colorado Springs, CO 80904
3/16 CFS CONTRACTOR 719-635-6422

CONCENTRATED RXN FROM


SEE ARCH FOR ELEV WINDOW MULLION BELOW Landscape
Lime Green Design, Inc
900 E. Louisiana Avenue, Suite 209
362 S CFS WALL

1/2"
Denver, CO 80210
FRAMING BY CFS 303-733-7558
CONTRACTOR
Structural
Martin/Martin
12499 West Colfax Avenue
Lakewood, CO 80215
303-431-6100

HSS 7x7, SEE PLAN


Mechanical/Plumbing
Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
CF STUDS AT CORNER AND EDGE 303-986-8200

14 NO SCALE
COLUMNS 10 NO SCALE STAIR 2 EXTERIOR WALL HEAD 6 NO SCALE EXTERIOR WALL AT EAST CURTAINWALL - 1
Electrical
2 1/2" Shaffer Baucom Engineering & Consulting
7333 West Jefferson Avenue, Suite 230
Lakewood, CO 80235
SEE ARCH 303-986-8200

600S WALL FRAMING BY


CFS CONTRACTOR 1" TYP SEE PLAN Technology
5/16 Rimrock Group
5/16 10807 New Allegiance Drive, Suite 400
Colorado Springs, CO 80921
METAL PANEL 719-533-1112
SEE ARCH

Building Performance Engineer


Ambient Energy
800S WALL FRAMING 130 W 5th Ave
RIGID CONN BY 7
BY CFS CONTRACTOR Denver, CO 80204
CFS CONTR S-540 303-278-1532

7 Cost Estimating
PL3/8x8 S-540 4 Parametrix, Inc.
CURTAINWALL CONN TO S-540 7186 South Highland Drive
L6x6x3/8xCONT Salt Lake City, UT 84121
RELIEF ANGLE IS 3/16 2-12 SLAB EDGE BY SUPPLIER
HORIZ STUD SUPPORT BY 801-733-5900
CONTINUOUS CFS CONTRACTOR 3/16 2-12

CONCENTRATED RXN FROM


WINDOW MULLION BELOW AT
SOME LOCS. INCLUDE LATERAL
LOADS FROM WINDOW AND
DEAD, SNOW AND WIND LOADS GRAVITY/LATERAL
ON SUNSHADE. HORIZ STUD SUPPORT CONN TO SLAB EDGE
BY CFS CONTRACTOR. BY CFS CONTR
MAX DEFORMATION

15 NO SCALE CORNER AT STAIR 2 11 NO SCALE STAIR 2 EXTERIOR WALL HEAD - 2


UNDER DESIGN LOADS
SHALL NOT EXCEED
1/32" DUE TO ALL
HORIZ STUD
SUPPORT BY CFS
SOURCES CONTRACTOR
4 Issue Date
FOR BM CONN
S-540
BRICK VENEER METAL PANEL. CONN
TO EACH STUD BP#3 DECEMBER 21, 2012
ADDENDUM 005 JANUARY 25, 2013
RECORD DRAWINGS APRIL 18, 2014
800S WALL FRAMING BY
CFS CONTRACTOR
DATE PRINTED: 4/18/2014 9:10:25 AM

12 AT METAL HEADER BY CFS CONTR TO


S-540 STUDS BELOW DISTRIBUTE MULLION RXN
DESIGNERS: KH/AM

TO (3) STUDS MINIMUM


9
SEE ARCH S-540 SEE ARCH

Project Number: 2011101.00


CONCENTRATED RXN FROM CONCENTRATED
WINDOW MULLION BELOW AT RXN FROM Drawn By: KH/AM

SOME LOCS. INCLUDE LATERAL CURTAINWALL


Reviewed By: KH
LOADS FROM WINDOW AND MULLION BELOW
Approved By: PD
DEAD, SNOW AND WIND LOADS
ON SUNSHADE.
PROJECT MANAGER: KH
MM JOB #: 23616.S.01

TYP EXT WALL


PRINCIPAL: PD

ADD
005
EOR: PD

EXTERIOR WALL AT EAST


8 NO SCALE TYP CF SPANDREL AT ROOF 4 NO SCALE
CURTAINWALL - 2 S-541

You might also like