Location via proxy:   [ UP ]  
[Report a bug]   [Manage cookies]                

Siemens 3vu1300 1mm00

Download as pdf or txt
Download as pdf or txt
You are on page 1of 5

Motor Protection Circuit Breakers

3VU13 and 3VU16

3VU13/3VU16 is suitable for use in fuseless motor feeders upto 11KW/22KW (25A/63A) respectively. 3VU
motor protection circuit breakers are used for protection of motor against overload, single phasing and
short-circuit faults.

Applications
Motor Protection
Circuit breakers type 3VU13 & 3VU16 offer overload, short
circuit and phase loss protection for 3 phase motors upto 11kW
and 22 kW respectively. The breaker has a toggle switch for
ease of operation and can be offered with auxiliary contacts,
trip indicating contacts, U/V or Shunt release. High breaking
capacity of 100kA is available in 3VU13 upto 6A and in 3VU16
upto 25A.

Distribution Feeder Protection


Standard version of 3VU13 and 3VU16 has adjustable O/L and
fixed S/C release. Main application is for disconnection and 3VU13/16
protection of the distribution feeders, upto 25A and 63A
respectively. A large number of overlapping ranges are
available for offering closer protection to various loads. Standard

Transformer protection 3VU motor protection circuit breakers confirm to IS/IEC 60947-1,
IS/IEC 60947-2, IS/IEC 60947-4-1, DIN VDE 0660
A separate 3VU13 range can be offered to protect the primary
side of the transformers. The range is available upto 20A. To
take care of the inrush current due to transformer switching, Range
the S/C release is set at 19 times the rated current unlike 12
times of the rated current available in standard range. 3VU13: 0.16 - 25A

Fuse Monitoring 3VU16: 10 - 63A


3VU1340-1MS00 is offered for Fuse Monitoring application.
This device is connected in parallel to the fuses. In case one of Benefits and features
the fuses blows, the rated current will flow through the
corresponding phase of this MPCB. MPCB, through its auxiliary
contacts, provides a tripping signal to the contactor and thus High performance
the motor will be switched off. Hence, the motor will be Instantaneous Tripping
protected from single phasing. (Refer page 51 for connection 3VU circuit breakers operate on the Current Limiting
diagram) Principle.

Current Limiting Principle


In case of short-circuit condition motor protection circuit
breaker trips before the short-circuit current reaches the
prospective peak. Hence, for circuit breaker to be current
limiting it must interrupt the short-circuit current in half cycle
or less as shown below.

Fuse Monitoring MPCB - 3VU1340-1MS00

45
Current Limiting is achieved in 3VU as follows 3VU13 Circuit - breakers with 1NO+1NC auxiliary contacts for
In case of a short circuit, the contacts are opened electro- line-side protection of transformers with high inrush current
dynamically by the short circuit current. The instantaneous
Rated Overload Shortcircuit Type Std.
overcurrent release, through the switching mechanism, trips all Current release release pkg.
the three poles of the breaker. A large arc voltage is quickly In range setting (nos.)
built up in the arc chamber limiting the short circuit current. A A A
Thus ensures faster fault clearing. 0.6 0.4-0.6 12 3VU1340-1TE00
o
Ambient temperature compensation upto 55 C hence no 1 0.6-1 15 3VU1340-1TF00
o
deration required upto 55 C. 1.6 1-1.6 29 3VU1340-1TG00

2.4 1.6-2.4 48 3VU1340-1TH00


Safety
4 2.4-4 72 3VU1340-1TJ00 1
Trip Free Mechanism
6 4-6 120 3VU1340-1TK00
The breakers have a trip-free mechanism. Even by holding the
toggle, tripping operation can not be stopped or blocked once 10 6-10 190 3VU1340-1TL00
it is started. Thus ensure positive opening in the event of fault. 16 10-16 300 3VU1340-1TM00

Positive ON/OFF indication through toggle switch 20 14-20 300 3VU1340-1TN00

Compact and space saving

User friendliness and safety Fuse monitoring motor protection circuit - breakers with
1NO+1NC auxiliary contacts
SIGUT connection technique ensures ease of wiring (can
obviate use of lug) Rated Overload Shortcircuit Type Std.
Current release release pkg.
Fingers touch proof terminals ensures operator safety In range setting (nos.)
A A A
Separate trip indication on short circuit and overload fault
using alarm contact 0.2 0.2 1.2 3VU1340-1MS00 1

Flexibility
Can be used as a main and EMERGENCY STOP switch. 3VU16 Circuit - breakers with 1NO+1NC auxiliary contacts for
motor and plant protection
Identical accessories reduce stock levels
Rated Overload Shortcircuit Type$ Recommended Std.
Current release release 415V Motor pkg.
Selection and ordering data In range setting Rating in (nos.)
A A A Kw/HP (DOL)
3VU13 Circuit - breakers with 1NO+1NC auxiliary contacts for 10 6-10 120 3VU1640-1ML00 4/5.4
motor and plant protection
16 10-16 190 3VU1640-1MM00 7.5/10
$
Rated Overload Shortcircuit Type Recommended Std.
25 16-25 300 3VU1640-1MN00 11/15 1
Current release release 415V Motor pkg.
In range setting Rating in (nos.) 32 22-32 380 3VU1640-1MP00 15/20
A A A Kw/HP (DOL)
40 28-40 480 3VU1640-1MQ00 18.5/25
0.16 0.1 - 0.16 1.9 3VU1340-1MB00
52 36-52 600 3VU1640-1MR00 22/30
0.24 0.16 - 0.24 2.9 3VU1340-IMC00

0.4 0.24-0.4 4.8 3VU1340-1MD00


0.6 0.4-0.6 7.2 3VU1340-1ME00 3VU16 Circuit - breakers for plant protection
1 0.6-1 12 3VU1340-1MF00 0.25/0.33 $
Rated Overload Shortcircuit Type Std.
1.6 1-1.6 19 3VU1340-1MG00 0.37/0.5 Current release release pkg.
In range setting (nos.)
2.4 1.6-2.4 29 3VU1340-1MH00 0.75/1
A A A
3.2 2-3.2 38 3VU1340-1NH00 1.1/1.5
63 45-63 600 3VU1640-1LS00 1
4 2.4-4 48 3VU1340-1MJ00 1.5/2 1 $
The 3VU13 and 3VU16 circuit breakers are also available without auxiliary
5 3.2-5 60 3VU1340-1NJ00 2.2/3 contacts. To order the same, the 8th place of the type number is to be replaced
6 4-6 72 3VU1340-1MK00 3/4 with the digit 0.

8 5-8 96 3VU1340-1NK00 3.7/5

10 6-10 120 3VU1340-1ML00 4/5.4

13 8-13 156 3VU1340-1NL00 5.5/7.5


16 10-16 190 3VU1340-1MM00 7.5/10

20 14-20 240 3VU1340-1MN00 9.3/12.5


25 18-25 300 3VU1340-1MP00 11/15

46
Technical Data
According to DIN VDE 0660; IS/IEC 60947-1; IS/IEC 60947-2; IS/IEC 60947-4-1

Type 3VU13 3VU16

Number of poles 3 3
Max. rated current In
motor protection A 25 52
distribution A 25 63
Permissible ambient temperature
at full rated current C -20 ... +55
in storage C -50 ... +80

Rated operational voltage Ue V 690


Rated frequency Hz 50/60

Rated insulation voltage Ui V 750


Rated impulse withstand voltage Uimp kV 6

Utilization category
to IS/IEC 60947-2 (motor starter protection) A
to IS/IEC 60947-4-1 (motor starters) AC-3
Mechanical endurance Operating cycles
up to 25 A 1/h 100,000 100,000
25 A upwards 1/h 30,000
Number of operating cycles/h (on load) 1/h 25 25

Degree of protection
with open terminals/with conductors connected IP00/IP20

Temperature compensation to IS/IEC 60947-4-1 Yes

Phase failure sensitivity to IS/IEC 60947-4-1 Yes


Auxiliary contact for 3VU13 and 3VU16

Rated operational voltage Ue AC V 230 400 500


Rated operational current Ie A 3 1.5 1.2

Utilization category AC-15

Rated operational voltage Ue DC L/R 200 ms DC V 24 60 220


Rated operational current Ie A 2.3 0.7 0.3

Utilization category DC-13

Wattloss Per Breaker


Current Watt Current Watt
rating rating
0.6 5 2.4 8
4 6 6 7
6 7 25 14
25 9 63 23

Cross-section for main conductors


2
Solid or stranded mm 2 x (1 ... 6) 1 x 1.5 ... 2 x 16
or 1 x 25 + 1 x 10
2
Finely stranded with end sleeve mm 2 x (1 ... 4) 1 x 1.5 ... 2 x 10
or 1 x 16 + 1 x 10
Cross-sections for auxiliary and control connecting leads
2
Solid or stranded mm 1 x 0.5 ... 2 x 2.5
2
Finely stranded with end sleeve mm 1 x 0.5 ... 2 x 2.5

47
Technical data for accessories:

3VU13 3VU16
Undervoltage Release

Consumption During Pick-up VA/W 10/6

Consumption During Running VA/W 4.7/2


Dropout V 0.7 to 0.35 X Ue

Pickup V 85 to 110% of Ue
Max Operating Time ms 20

Shunt Release

Consumption VA/W 10/6


Max Continuous Rating Sec 5

Pickup V 0.7 to 1.1 X Ue


Current Limiter for 3VU13

Rated current In 56 Amps

Rated Voltage Ue 500 V, 50 / 60 Hz.


2
Power Connection mm 2 x (1 to 6)

Mounting
on DIN Rail in any position.

Table 1 3VU13/3VU16 breaking capacity at 415V

3VU13

Rated current A 0.16-1 1.6 2.4 3.2-4 5-6 8-10 13-16 20-25

Rated Short circuit breaking capacity @ 415V


Icu kA 100 100 100 100 100 10(50) 6(50) 6(50)

Ics kA 100 100 100 100 100 10(50) 6(50) 6(50)

Maximun back up fuse (gL/gG)


Diazed A * * * * * 80 80 80

NH A * * * * * 80 80 80
( ) Values in bracket are with current limiter; * Fuse not required

For 3VU13 breakers of ratings 8A & above, in place of fuses, the Current Limiter can be used to increase the S/C breaking capacity.

Rated Breaking Capacity DC; t = 15ms


1 Contact 2 Contacts 3 Contacts
in series in series 10 kA
110-150V 220-300V 330-450V

3VU16

Rated current A 1.6-2.4 4 6 10 16 25 32-63


Rated Short circuit breaking capacity @ 415V

Icu kA 100 100 100 100 100 100 35

Ics kA 100 100 100 100 100 50 17


Maximun back up fuse (gL/gG); * Fuse not required

Diazed A * * * * * * -
NH A * * * * * * 200

Rated Breaking Capacity DC; t = 15ms, upon enquiry

48
Characteristic Curves

Times set current Short circuit current Ik (effective)


Time current characteristics of 3VU13 Cut off characteristics of 3VU1300-0MK00

Times set current Short circuit current Ik (effective)


Time current characteristics of 3VU16 Cut off characteristics of 3VU1600-0MN00

49

You might also like