Lab Report Shell &tube Heat Exchanger
Lab Report Shell &tube Heat Exchanger
Lab Report Shell &tube Heat Exchanger
ABSTRACT/SUMMARY
We have successfully conducted our experiment of Shell and Tube Heat Exchanger by
using Heat Exchanger Training Apparatus (Model; HE 158C). A heat exchanger is a device that
allows heat from a fluid (a liquid or a gas) to pass to a second fluid (another liquid or
gas) without the two fluids having to mix together or come into direct contact. In this
experiment, cold water enters the shell at room temperature while hot water enters the tubes in
the opposite direction. We then vary the hot water and cold water flow rates and record the inlet
and outlet temperatures of both the hot water and cold water streams at steady state. The flow of
hot and cold water is counter-current flow. Then the experiment is repeated with co-current shell
and tube heat exchanger which is parallel flow of hot and cold water. From the data calculated,
shows that counter current flow configuration of heat exchanger is more preferred for practical
application.
2. INTRODUCTION
Flowmeter
Contro
l panel
Pump
a) Flow measurement
FT1: Hot water flow rate (LPM)
FT2: Cold water flow rate (LPM)
b) Temperature Measurement
TT1: Hot water inlet temperature (C)
TT2: Hot water inlet temperature (C)
TT2: Hot water inlet temperature (C)
TT2: Hot water inlet temperature (C)
The function of shell is to transport cold water. The water will be inserted into the shell
inlet and go out from at the shell outlet whereas tube is used to transport hot water across the
tube. Front-end header is where water will enter the tubeside of the heat exchanger. Furthermore,
Rear-end header is where the water leaves the heat exchanger. Baffles are installed in order to
support the tubes and allow water to flow across the tubes. Besides, baffles also give a higher
transfer rate due to the increase of turbulence. The heat exchangers dimension is as follows:
Information about the Shell & Tube Heat Exchanger unit
3. OBJECTIVES
1) To study the working principle of the concentric heat exchanger operating by using co-
current flow and counter-current fluid flow.
2) Then, another purpose of this experiment is to demonstrate the effect of hot and cold
flow rate variations on the performance of the heat exchanger system.
4. THEORY
The main function of heat exchanger is to either remove heat from a hot fluid or to add
heat to the cold fluid. The direction of fluid motion inside the heat exchanger can normally
categorised as parallel flow, counter flow and cross flow. In this experiment, we study only
counter-current and co-current flow. For co-current flow, also known as co-current flow, both the
hot and cold fluids flow in the same direction. Both the fluids enter and exit the heat exchanger
on the same ends. For counter-current flow, both the hot and cold fluids flow in the opposite
direction. Both the fluids enter and exit the heat exchanger on the opposite ends. In this
experiment, we focused on the shell and tube heat exchanger.
Heat exchangers with only one phase (liquid or gas) on each side can be called one phase
or single-phase heat exchangers. Two-phase heat exchangers can be used to heat a
liquid to boil it into a gas (vapor), sometimes called boilers, or cool a vapor to condense it
into a liquid (called condensers), with the phase change usually occurring on the shell side.
One of the most common, conductive-convective, heat exchanger types is the concentric
tube heat exchanger. These exchangers are built of coaxial tubes placed the ones inside the
others.
When both the fluids enter from the same side and flow through the same direction
we have the parallel flow (concurrent flow), otherwise, if the fluids enter from opposite
sides and flow through the contrary direction we have the countercurrent flow. Usually the
countercurrent flow is more efficient from the heat transfer point of view. This type of heat
exchangers can also be built with the internal tube made with longitudinal fins which could
be placed either in its internal surface or in its external one or both. This configuration is
useful mainly if one of the fluids is a gas or a liquid with a very high viscosity and it's very
difficult to have a good thermal convection coefficient.
The heats are transfer between the two fluids by convection mode which is from
the hot fluid to the wall and also by conduction which is occur within the wall itself and
back to the convection which is from the wall to the cold fluid. This concentric tube heat
exchanger is the simplest one of heat exchanger between the other types of heat exchanger.
This type mainly used for small flow rates of fluid.
Figure 1 - Diagram of Parallel and Counter Flow Configurations
6. PROCEDURE
GENERAL START-UP PROCEDURE
1 A quick inspection is performed to make sure that the equipment is in proper working
condition
2 All the valves are closed initially except for V1 and V12.
3 Hot water tank is filled up via a water supply hose connected to V27 until it is full.
4 The cold-water tank is filled up by opening V28 and the valve is leaved opened for
continues water supply.
5 A drain horse is connected to the cold water drain point.
6 The main power is switch on. The heater is switch on for the hot water tank and the
temperature controller is set to 50oC.
7 The water temperature in the hot tank is allowed to reach the set-point.
1. The heater is switched off until the hot water temperature drops below 40oC.
2. Pump, P1 and pump, P2 are switched off.
3. The main power is switched off.
4. All the water in the process line is drained off. The water is retained in the hot and cold
water for the next laboratory session.
5. All the valves are closed.
7.RESULT
Sample Calculation :
Hot Water
3
Density 988.18 kg/ m
Viscosity 0.0005494 Pa.s
Thermal condition 0.6436 W/m.K
Heat Capacity 4175.00 J/kg.K
Cold Water
3
Density 995.67 kg/ m
Viscosity 0.0008007 Pa.s
Thermal condition 0.6155 W/m.K
Heat Capacity 0.0008007 Pa.s
= -3644.33 W
Heat transfer rate for cold water, Q
= mc Cp T
L 1 m3 1 min kg J
= 1 min x 1000 L x 60 s x 995.67 m3 x 4183 kg .C x (31.6-49.1) C
= -1214.76 W
Heat loss
= Qhot-Qcold
= -3644.33+1214.76
= -2429.57W
Efficiency
Qcold
x 100
= Qhot
=300%
=8.42C
3 Calculation of the tube and shell heat transfer coefficients by Kerns method :
a Heat transfer coefficient at tube side
i Cross Flow Area,A
di2
= 4
3.142 x 0.0077 5 2
= 4
2
= 0.0000472 m
ii Total cross Flow Area, At
= At x Nt
= 0.0000472 x 10
2
=0.000472 m
iii Mass velocity, Gt
mt
= At
0.1647
= 0.000472
2
= 349.13 kg/ m s
iv Linear velocity, ut
= p
349.13
= 988.18
= 0.3533 m/s
v Renolds Number, Re
x de
=
349.13 x 7.75 1
= 0.0005494 x 1000
= 4924.93
Value shows in range of turbulent flow
vi Prandtl No, Pr
x Cp
= k
0.0005494 x 4175
= 0.6436
= 3.56
vii Tube Side Coefficient, hi
jh P r 0.33 k
= di
0.33
0.004 x 4924.93 x 3.56 x 0.6436
= 0.00775
2
= 2570.36 W m K
8.3
= 995.67
= 0.0083 m/s
iv Equivalent diameter, de
1.1
= d 0 (pt2 - 0.917d02 )
1.1
= 9.53 [ 182 - 0.917 (9.53)2]
= 27.80 mm
v Reynolds number, Re
Gs x de
=
8.3 x 27.80 1
= 0.0008007 x 1000
= 288.17
Value shows in range of laminar flow
vi Prandtl No, Pr
x Cp
= k
0.0008007 x 4183
= 0.6155
= 5.44
vii Shell Side Coefficient, hs
jh P r 0.33 k
= de
2500 2570.3
2570.3
2570.3
2570.3
2570.3
2000
1865.89
Tube side
1500 1510.41
Heat Transfer Coefficient (W/m2K) Shell side
1132.73
1000
500
377.72
151.04
0
1 2 3 4 5
The experiment was carried out to study the working principle of parallel flow and
counter flow heat exchangers and also to investigate the effect of fluid temperature on counter
and parallel flow heat exchanger performance. There are two types of experiment which is
counter-current shell and tube heat exchanger and co-current shell and tube heat exchanger. The
different between these two experiments are the counter-current flow is when hot water and cold
water flow in opposite direction to each other while co-current flow is where hot and cold water
flow in the same direction and also known as parallel flow. For counter-current flow and co-
current flow, the experiment is run and all of the temperature and pressure data is recorded
From the data collected, the counter-current and co-current heat exchangers exit
temperature of the hot fluid is higher than the exit temperature of the cold fluid but due to the
equipment error during experiment is done, exit temperature becomes lower than temperature
inlet for parallel flow . This cause the experiment cannot be done practically. Instead of
equipment and human error, this may because of the heat loss to the surrounding that can reduce
the temperature itself and the flow rates which always easily change during the experiment may
also cause this problem. This shows that heat may not spontaneously transfer from a colder body
to a hotter body.
The increase in flow rate of one of the stream will results in an increase in the rate of heat
transfer. But from calculation, results show that the increase of flow rate, the lower the heat
transfer. This is contra to the theoretical result but due to big error from the unit and since the
unit does not function properly, we cannot able to avoid this mistake. Theoretically, the amount
of heat loss form the hot water should be equal to the heat gain by the cold water.
Based on the calculation done, it is found out that the values of LMTD, which is log
mean temperature difference for co-current flow is higher than the counter-current flow. But, the
overall heat transfer coefficient for counter-current flow is higher than the co-current flow. This
mean that counter current flow heat exchanger has a higher effectiveness rather than parallel
flow heat exchanger.
10 CONCLUSION
So, overall in conclusion, shell and tube heat exchanger follows the basic law of
Thermodynamics and fulfilled the study of Heat Transfer. In parallel (co-current) flow
configuration, the exit temperature of the hot fluid is always higher than the exit temperature of
the cold fluid. In countercurrent flow configuration, the exit temperature of the hot fluid is also
higher than the exit temperature of the cold fluid. But then, in the configuration of counter
current flow, the exit temperature of the cold fluid is higher than the exit temperature of the cold
fluid in co-curent configuration. So, this stand the statement that counter current flow heat
exchanger has a higher effectiveness than the parallel flow configuration. Besides, the
experiment shows that the flow rate of one of the stream is directly proportional to the rate of
heat transfer since the rate of heat transfer is increases as the flow rate of fluid increases.
Futhermore, the amount of heat loss form the hot water is not equal to the heat gain by the cold
water due to the heat loss to the surrounding. From the calculations done, the LMTD (log mean
temperature difference) for co-current flow is higher than the counter-current flow. In a nut shell,
counter current flow configuration of heat exchanger is more preferred for practical application.
One of the application of heat exchanger is oil cooler.
11 RECOMMENDATION
Based on the experiment, there are a few recommendations that can be suggested in order to
increasing the performance of the concentric heat exchanger and to avoid from the error while
recorded the data thus can affect the calculation outwards. Firstly, the most importance is to
make sure that the equipment is in good condition so that the flow of the experiment does not
disturbing by the inconstant data. Then, while conducting the experiment, make sure that the
time taken to collect the data is punctually followed. The relay of the time can affect the data
recorded. It is suggested that, the alert alarm system is placed so that it can be easier to record the
data on time. Then, while recording the data, make sure that the pressure and temperature is at
constant value because this can affect the calculation made.
12 REFERENCES
Yunus A.Cengel, 2006, Heat and Mass Transfer: A Practical Approach. Mc Graw Hill,, 3 rd
Edition
Christie John Geankoplis, Transport Process AND Separation (includes unit operations) ,
4thEdition
APPENDIX