MDVT v140w Drn1 Cabin
MDVT v140w Drn1 Cabin
MDVT v140w Drn1 Cabin
Content
Part 1 General Information .................................................. 1
2. Nomenclature ....................................................................2
3. Features .............................................................................3
General Information 1
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
The DC Inverter Mini VRF Series has developed as a high-efficiency product that will appeal to broader
range of users. It is ideal for small offices, villas, apartment and shops.
Midea launched two models DC inverter mini VRF (10.5kW/14kW) especially for tropical application. It
supports piping length up to 100m and longer drop difference up to 30m, max. 8 indoor units can be
connected to one outdoor unit, making it perfect for commercial and residential application.
1. Outdoor Units Lineup
2. Nomenclature
MDVT-V105W/DRN1
Refrigerant
N1: R410A
Power Supply
R: 380-415V, 3Ph, 50Hz
DC Inverter
Outdoor Unit
Inverter System
Climate Type
Omit: T1
T: T3
Multi-Digital-Variable
2 General Information
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
3. Features
3.1 High efficiency DC inverter compressor
At the heart of our system is a highly intelligent inverter-driven compressor. This advanced technology
enables the output of the outdoor unit to be modulated by the cooling or heating demands of the zone that it
controls.
This advanced system ensures precise temperature regulation and highly efficient energy usage, making a
significant contribution to the limiting the impact on the environment.
decrease the air resistance, save more power and enhance heat
exchange performance.
Hydrophilic film fins and inner-threaded copper pipes optimize heat High efficiency inner-thread pipe,
enhance heat transfer.
exchange efficiency.
New grille
New fan
3.4 Quick warm-up & cool-down design and less temperature fluctuation
Utilizing the inverter compressor benefits,
the system can reach full load quickly and Temp.
Notn-inverter
better living environment.
Time
General Information 3
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
3.5 Wide operation temperature range
COOLING MODE
No matter in extremely cold winter when outdoor 10
C 54
C
PQE & XYE, just only one group of communication wire of PQE,
achieved both of communication for indoor & outdoor unit and
network.
P Q E X Y E X Y E Reversible communication, central controller can be connected
from indoor side or outdoor side as you wish.
P Q E P Q E P Q E P Q E
4 General Information
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
3.9 Auto address setting function
The addresses of indoor units can be set automatically by outdoor unit.
Wired controller and wireless controller can enquire and modify the address of each indoor unit.
Right side
Front side
Bottom side
General Information 5
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
4. Indoor Units Lineup
Model
4-way cassette Low static Medium static
1-way cassette 2-way cassette 4-waycassette
(compact) pressure duct pressure duct
Capacity
(100W)
18
22
28
36
45
56
71
80
90
100
112
125
140
Model
Wall mounted Wall mounted Wall mounted
High static pressure duct
Capacity S type C type R type
(100W)
18
22
28
36
45
56
71
80
90
100
112
125
140
Model
Ceiling & floor Floor standing (exposed) Floor standing (concealed) Console
Capacity
(100W)
18
22
28
36
45
56
71
80
90
100
112
125
140
Note: If ODU connect only one IDU, the capacity of IDU should be not more than ODU.
If ODU connect more than one IDU, the capacity of each IDU should be not more than 8kW for refrigerant uniform distribution.
Due to continuous improvement, specifications are subject to change without prior notice.
6 General Information
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
2. Dimensions........................................................................9
5. Capacity tables................................................................ 11
C
D
F
E
B
Size A B C D E F G
Model
900 1327 348 320 400 360 600
(10.5/14kW)
A
Installation dimensions
Single unit installation
(Wall or obstacle)
>300
Air inlet
>300 Maintain
channel
Air inlet >600
>2000
Air outlet
>300
>600
>2000
3. Piping diagram
Indoor heat-exchanger
EXV
Liquid accumulator
High pressure switch
Outdoor heat-exchanger
Oil separator
EXV
7. Sound levels
Outdoor unit
Microphone
1.2m
1.0m
MDVT-V105W/DRN1 52
MDVT-V140W/DRN1 52
Part 3 Installation
1. Precautions ......................................................................25
2. Accessories .....................................................................26
24 Installation
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
1. Precautions
Ensure that all Local, National and International regulations are satisfied.
Read this PRECAUTIONS carefully before Installation.
The precautions described below include the important Items regarding safety.
Observe them without fail.
After the installation work, perform a trial operation to check for any problem.
Follow the Owners Manual to explain how to use and maintain the unit to the customer.
Turn off the main power supply switch (or breaker) before maintenance the unit.
Ask the customer that the Installation Manual and the Owners manual should be kept together.
Caution 1:
The characteristics of R410A refrigerant are; Hydrophilic, oxidizing membrane or oil, and its pressure is approx.1.6 times
higher than that of refrigerant R22.Accompanied with the new refrigerant, refrigerating oil has also been changed ,Therefore,
during installation work, be sure that water, dust, former refrigerant, or refrigerating oil does not enter the refrigerating cycle.
To prevent charging an incorrect refrigerant and refrigerating oil, the sizes of connecting sections of charging port of the main
unit and installation tools are charged from those for the conventional refrigerant.
Accordingly the exclusive tools are required for the new refrigerant (R410A):
For connecting pipes, use new and clean piping designed for R410A, and please care so that water or dust does not enter.
Moreover, do not use the existing piping because there are problems with pressure-resistance force and impurity in it.
Caution 2:
This unit must be connected to the main power supply by means of a switch with a contact separation of at least 3 mm. The
installation fuse must be used for the power supply line of this conditioner.
Caution 3:
Ask an authorized dealer or qualified installation professional to install/maintain the air conditioner. Inappropriate installation
may result in water leakage, electric shock or fire.
Turn off the main power supply switch or breaker before attempting any electrical work. Make sure all power switches are off.
Failure to do so may cause electric shock.
Connect the connecting cable correctly. If the connecting cable is connected in a wrong way, electric parts may be damaged.
When moving the air conditioner for the installation into another place, be very careful not to enter any gaseous matter other
than the specified refrigerant into the refrigeration cycle. If air or any other has is mixed in refrigerant, the gas pressure in the
refrigeration cycle becomes abnormally high and it may resultantly causes pipe burst and injuries on persons.
Do not modify this unit by removing any of the safety guards or by by-passing any of the safety inter lock switches. Exposure of
unit to water or other moisture before installation may cause a short circuit of electrical parts.
Do not store it in a wet basement or expose to rain or water. After unpacking the unit, examine it carefully if there are possible
damage.
Do not install in a place that might increase the vibration of the unit. To avoid personal injury (with sharp edges) be careful
when handling parts.
Perform installation work properly according to the Installation Manual. Inappropriate installation may result in water leakage,
electric shock or fire. When the air conditioner is installed in a small room, provide appropriate measures to ensure that the
concentration of refrigerant leakage occur in the room does not exceed the critical level. If refrigerant gas has leaked during
the installation work, ventilate the room immediately. If the leaked refrigerant gas comes in contact with fire, noxious gas may
generate. After the installation work, confirm that refrigerant gas doer not leak. If refrigerant gas leaks into the room and flows
near a fire source, such as a cooking range, noxious gas might generate.
Install the air conditioner securely in a location where the base can sustain the weight adequately. Perform the specified
installation work to guard against an earthquake. If the air conditioner is not installed appropriately, accidents may occur due to
the falling unit.
Electrical work must be performed by a qualified electrician in accordance with the Installation Manual. Make sure the air
conditioner uses an exclusive power supply. An insufficient power supply capacity or inappropriate installation may cause fire.
Use the specified cables for wiring connect the terminals securely fix. To prevent external forces applied to the terminals from
Installation 25
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
affecting the terminals. Be sure to provide grounding. Do not connect ground wires to gas pipes, water pipes, lightning rods or
ground wires for telephone cables. Conform to the regulations of the local electric company when wiring the power supply.
Inappropriate grounding may cause electric shock Do not install the air conditioner in a location subject to a risk of exposure to
a combustible gas. If a combustible gas leaks, and stays around the unit, a fire may occur.
2. Accessories
Please check whether the following fittings are of full scope. If there are some spare fittings, please restore
them carefully.
1. Outdoor unit
1
installation manual
4.Outflow connecting
1
tube
Strong Strong
wind wind
26 Installation
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
3.2 Installation space (units: mm)
Since the gravity center of the unit is not at its physical center, so please be careful when lifting it with a
sling.
Never hold the inlet of the outdoor unit to prevent it from deforming.
Do not touch the fan with hands or other objects.
Do not lean it more than 45, and do not lay it sidelong.
Make concrete foundation according to the specifications of the outdoor units.
Fasten the feet of this unit with bolts firmly to prevent it from collapsing in case of earthquake or strong
wind.
>60cm
Fix with bolt
Air inlet
>300 Maintain
channel
Air inlet >600
>2000
Air outlet
>300
>600
>2000
All the pictures in this manual are for explanation purpose only. They may be slightly different from the air
conditioner you purchased (depend on model).The actual shape shall prevail.
Installation 27
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
3.3 Water Outlet
Four condensed water outlets on the chassis for selection display as the follow figure:
Outlet for power and connecting pipes
While installing the outdoor unit, pay attention to the installation place and the drainage pattern; if its
installed at the alpine zone, the frozen condensed water will block up the water outlet, please pull out the
rubber stopper of the reserve water outlet. If that still fails to satisfy for the water draining, please knock open
the other two water outlets, and keep the water can drain in time. Pay attention to the knock the reserve
water outlet from outside to inside, and it will be beyond repair after knocking open, please pay attention to
the installation place, lest cause the inconvenience. Please do the moth proofing for the knocked out hole, to
avoid the pest processing into and destroy the components.
4. Piping installation
4.1 Piping connection
Offering four directions to connect pipes and wirings for meet a variety installation request.
Fat pipe
Right side pipe connection: please remove the L-shape metal plate, otherwise cannot wiring.
Back side pipe connection: Please wipe off the piping support rubber blanket beside the inner outlet pipe
cover of the machine while back side getting out pipes.
Bottom side pipe connection: the knock out should from inside to outside, and then piping and wiring through
this.
Pay attention to the piping the fat connecting pipe should out from the largest hole, otherwise the pipes will
be rubbed. Please do the moth proofing for the knocked out hole, to avoid the pest processing into and
destroy the components.
4.2 Allowable length and level difference of refrigerant pipe
Permitted value Piping
Total Pipe Length(Actual) 100m L1+L2+L3+L4+L5+a+b+c+d+e+f
45 (10.5kW)
Actual Length L1+L2+L3+L4+L5+f(The first connect
Maximum 60m (14kW)
method) or L1+L3+L5+f(The second
Piping(L) Equivalent 50 (10.5kW)
Pipe Length connect method)
Length 70m (14kW)
Pipe Length (from the first branch to the L2+L3+L4+L5+f(The first connect method)
20m
furthest IDU) or L3+L5+f(The second connect method)
Pipe Length(IDU to the nearest branch) 15m a,b,c,d,e
Level difference Outdoor Unit up 30m
Level
between IDU~ODU Indoor Unit Down 20m
difference
Level difference between IDU~IDU 8m
Note: When the total equivalent piping length of liquid + gas side is 90m, it must increase the size of air side main pipe.
Besides, according to the distance of refrigerant pipe and the over matched state of indoor unit, when the capacity is
decreasing it still can increase the gas side main pipe size.
28 Installation
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
The first connect method
Outdoor unit
a
L1
A
bwtween IDU-IDU
L2
Level difference
Pipe Length (from the first branch to the furthest IDU)
L3 L4 L5
B C D E
b c d e f
Indoor Unit
Outdoor unit
a N2
B
L3
L4 c N3
The first line Branch Pipe D N4
C d
L5
E f
e N5 N6
Indoor unit
L5 f
L4 E
L3 D e
L1 L2 B C
A c d
a b
Installation 29
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
The second connect method
Outdoor Unit(Take Model 14kW for example)
N1
(28)
a
L1 L2 intdoor Units
B
A b N2
(28) N3
L3 (28)
L4 c
The first line pipe branch D N4
C (28)
d
L5
e
E
f
N5 N6
(28) (22)
30 Installation
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
Table 3: Main pipes selection (L1)
When the equivalent length of all liquid and air When the equivalent length of all liquid and air
Total capacity of
pipes < 90m pipes 90m
outdoor units
air side liquid side The first line air side liquid side The first line
(kW)
(mm) (mm) branch pipe (mm) (mm) branch pipe
A16 15.9 9.5 FQZHN-01C 19.1 9.5 FQZHN-01C
16A23 19.1 9.5 FQZHN-01C 22.2 9.5 FQZHN-02C
Note: Main pipe L1 can be selected form table 2 and table 3, the larger size should be finally selected.
The straight distance between copper pipe turning and the contiguous branch pipe is at least 0.5m;
The straight distance between the contiguous branch pipes is at least 0.5m;
The straight distance which the branch pipes connected to the indoor unit is at least 0.5m;
Table4: Outdoor unit pipe connection
Piping side Outdoor unit pipe connection (mm)
MODEL Gas Side Liquid Side
10.5kW 15.9 9.5
14kW 15.9 9.5
Installation 31
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
When the outdoor unit connects 1 indoor unit:
Liquid Side Piping Diameter Refrigerant to be Added Perimeter Piping
6.4 0.023kg
9.5 0.060kg
12.7 0.120kg
15.9 0.180kg
19.1 0.270kg
22.2 0.380kg
Note: Additional refrigerant volume of divergent pipe is 0.1kg per item (Consider the liquid side of divergent pipe only)
4.8 Leak detection
Use soap water or leak detector to check every joint whether leak or not.
Note: A is low pressure side stop valve.
B is high pressure side stop valve.
C and D is connecting pipes interface of indoor and outdoor units.
Check point of outdoor unit D C
B
A
Check point of indoor unit
5. Electrical wiring
32 Installation
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
Cautions:
Please select power source for indoor unit and outdoor unit respectively
The power supply has specified branch circuit with leakage protector and manual switch.
The outdoor unit model which corresponding to different outdoor unit power supply should refer to the nameplate.
(Please set all the indoor unit power of one system into the same branch circuit.)
Please put the connective wire system between indoor unit and outdoor unit with the refrigerant system together.
Use 3-core shielded wire as indoor unit and outdoor unit signal wire.
The installation should comply with local electric standard.
Power wiring should be engaged by specialized electrician.
5.1 Outdoor unit wiring
Power specifications
Power Source 380-415V 3Ph~ 50Hz
Capacity(kW) 10.5 14
Power Wiring Size Wire size must comply with local codes
Circuit Breaker (A) 25 25
Indoor unit/Outdoor unit
3-core shielded wire
Signal wire (mm2)
3X0.75
(Weak electric signal)
Cautions:
Equipment complying with IEC 61000-3-12.A disconnection device having an air gap contact separation in all active
conductors should be incorporated in the fixed wiring according to the National Wiring Regulation.
5.2 Indoor unit wiring
Power specifications
Capacity(kW) 2.2~8
Phase 1-Phase
Installation 33
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
Cautions: Indoor/Outdoor unit signal wire is low voltage circuit. Do not let it touch the high voltage power wire and put it to
gather with power cord in the same wire distribution pipe.
Indoor unit power supply wiring
Indoor Power Supply
Circuit Breaker
Manual swtich
Wire Distribution Box
Indoor Unit
Fig. 5-6
Cautions:
1. Refrigerant piping system, indoor unit-indoor unit connection signal wires and indoor unit-outdoor unit connection signal
wire are in the same system.
2. When power cord is parallel with signal wire, please put them into separate wire distribution pipes, and leave a proper
distance. (Reference distance: It is 300mm when current capacity of power cord is less than 10A, or 500mm when 50A).
6. Running test
Operate according to "gist for test running" on the electric control box cover.
Cautions:
Test running cannot start until the outdoor unit has been connected to the power for 12hr.
Test running cannot start until all the valves are affirmed open.
Never make the forced running. (Or the protector sits back, danger will occur.)
7. Precautions on refrigerant leakage
This air conditioner (A/C) adopts innocuous and nonflammable refrigerant. The locating room of the A/C
should big enough that any refrigerant leakage is unable to reach critical thickness. So certain essential
action can be taken on time.
Critical thickness------the Maximum thickness of Freon without any harm to person.
Refrigerant critical thickness: 0.44[kg/m] for R410A.
Confirm the critical thickness through follow steps, and take necessary actions.
1. Calculate the sum of the charge volume (A[kg]) Total Refrigerant volume of 10HP=factory refrigerant
volume + super addition
2. Calculate the indoor cubage (B[m]) (as the minimum cubage.
3. Calculate the refrigerant thickness
34 Installation
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
A[kg]
critical thickness
B[m3]
Counter measure against over high thickness
1. Install mechanical ventilator to reduce the refrigerant thickness under critical level. (Ventilate regularly)
2. Install leak alarm facility related to mechanical ventilator if you cannot regularly ventilate.
Outdoor unit
Indoor unit
Indoor unit
A. Ventilation
(Leak hunting siren should be installed in peristome
places easily keep refrigerant)
Fig. 7-1
Note: Please press constraint cool button to carry out refrigerant recycling process. Keep the low pressure above 0.2MPa;
otherwise compressor may be burnt out.
Installation 35
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
Part 4 Troubleshooting
1. Check table ......................................................................37
3. Troubleshooting ..............................................................38
36 Troubleshooting
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
1. Check table
No. Content Note
0 Running normally
1 Running mode 0: standby; 1: fan; 2: cooling; 3: heating; 4: forced cooling
2 Fan speed 0: closed; 1: low fan speed; 2: high fan speed
3 Total capacity of indoor unit Capacity requirements
4 Revised capacity of outdoor unit Capacity requirements
5 Pipe temperature of T3 sensor Actual value
6 Pipe temperature of T4 sensor Actual value
7 Discharge temperature of T5 sensor Actual value (if the temperature is over 100, it will display the
first two numbers.
8 Radiator surface temperature Actual value
9 EXV opening Actual value=display valve8
10 Current value Actual value
11 Voltage AD value Actual value
12 Average T2 temperature Actual value
13 Total quantity of indoor units Actual value
14 Quantity of running indoor units Actual value
15 The last error or protection code Display 00 if it has no error or protection
16 --
Troubleshooting 37
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
2. Outdoor unit error
Display Error or protection
E0 EEPROM error
E2 Communication error between ODU~IDU
E3 Communication error between main control chip and driver chip
E4 T3/T4 sensor error
E5 Voltage protection
E9 Low ambient temperature protection
(If operate the unit in cooling mode when the ambient temperate is lower than 10, it will
display E9 protection)
P0 Radiator high temperature protection
P1 High pressure protection
Low pressure protection
P2
Power supply phase sequence error
P3 Current protection of compressor
P4 Discharge temperature protection
P5 High temperature T3 protection of condenser
P6 IPM module protection
P7 High temperature T2 protection of evaporator
3. Troubleshooting
3.1 E0 (EFPROM error)
E0
EFPROM error
No
Change PCB
38 Troubleshooting
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
3.2 E2 (Communication error between ODU~IDU)
E2
Communication error
between ODU~IDU
No
No
No
No
Change PCB
Troubleshooting 39
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
3.3 E3 (Communication error between main control chip and driver chip)
E3
Communication error between
main control chip and drive chip
No
No
No
No
No
40 Troubleshooting
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
3.4 E4 (Error of T3/T4 sensor)
E4
Error of T3/T4 sensor
No
Yes
The wire of the sensor is broken Reconnect the wire
No
Yes
Sensor connect to wrong port Reconnect the sensor
No
Change PCB
E5
Voltage protection
No
No
No
Change PCB
Troubleshooting 41
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
3.6 P1 (High pressure protection)
P1
High pressure protection
No
No
No
No
System is blocked. This may be caused by Check the system and get
Yes
blocked valve, pressed tube, closed blocked rid of the block, and make
valve, etc. the loop smooth.
No
No
No
Change PCB
42 Troubleshooting
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
3.7 P2 (Low pressure protection)
P2
Low pressure protection
No
No
No
No
No
No
No
Change PCB
Troubleshooting 43
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
3.8 P2 (Phase sequence errors of power supply)
P2
Phase sequence errors of power supply
No
No
Yes
Power line is loose Fasten the power line
No
The power is over normal Yes Stop the units, and check
range or it has phase lack the power supply.
No
44 Troubleshooting
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
3.9 P3 (Compressor current protect)
P3
Compressor current protect
No
Yes
ODU load is excess Adjust IDU load or add ODU
No
System is blocked. This may be caused by Check the system and get
Yes
blocked valve, pressed tube, closed blocked rid of the block, and make
valve, etc. the loop smooth.
No
No
No
Compressor power lines are short circuit or Yes Check the compressor power
the ports are loose lines and fasten the ports
No
Measure the compressor
Yes terminal resistance. Normally
Compressor is disabled
they are 2-5 to each other
and infinite to earth
No
No
Yes
PCB is disabled Change PCB
Troubleshooting 45
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
3.10 P4 (Discharge temperature protection)
Unit will stop when discharge temperature is over 115C, and restart when discharge temperature is below
90C.
P4
Discharge temperature protection
No
No
No
No
No
Yes
PCB is disabled Change PCB
46 Troubleshooting
MCAC-VTSM-2013-01 R410A Tropical DC Inverter Mini VRF 50Hz
3.11 P5/P7
P5: High temperature T3 protection of condenser.
Unit will stop when condenser temperature is over 62C lasting 3 seconds, and restart when condenser
temperature is below 52C.
P7: High temperature T7 protection of evaporator.
Unit will stop when average evaporator temperature is over 63C lasting 50 seconds, and restart when
temperature is below 50C.
P5/P7
Sensor is disabled or the port is Yes Fasten the port or replace the
loose sensor
No
Yes
ODU load is excess Adjust IDU load or add ODU
No
No
System is blocked. This may be caused by Check the system and get
Yes
blocked valve, pressed tube, closed blocked rid of the block, and make
valve, etc. the loop smooth.
No
No
No
Yes
PCB is disabled Change PCB
Troubleshooting 47
R410A Tropical DC Inverter Mini VRF 50Hz MCAC-VTSM-2013-01
2.12 P6 (IPM module protection)
P6
IPM module protection
Check whether the voltage Check whether the power Adjust the power supply to
No No
between P-N of IPM module is supply is 380-415V, 3Ph, normal range
483~586V 50Hz
Yes
Yes
Check whether the
Check whether the wires Reconnect the power supply wire is No Reconnect the
No
between PCB and OPM is wires connect correctly and wires
fasten fasten
Yes
Yes
Check whether the E
No Reconnect the
Check whether the box wire is connect
Reconnect the correctly and fasten wires
compressor wire is No
connect correctly and compressor wires
Yes
fasten
Check whether the
Yes rectifier bridge wire is No
Change the
connect correctly and
rectifier bridge
fasten
Change IPM module
Yes
and check whether the System is OK
Yes
system is OK
Check whether the
connect wire of reactor
No Change
is normal. If the wire is No
connecting
broken, the
wire
Change compressor resistance value of
Yes
and check whether the System is OK two ports is
system is OK
Yes
Yes
48 Troubleshooting