HVCB Timing Application
HVCB Timing Application
HVCB Timing Application
testing guide
FAQ................................................................ 37
Index.............................................................. 48
References..................................................... 50
Distribution substation
CB Closed position Opening of the main Opening of the arcing CB in open position
Current flows through the contacts contacts The arc is quenched; the lower
main contacts The moving part goes down The current keeps flowing chamber reaches its minimum
thus separating the main due to the arc generated volume and its maximum
contacts. There is no arc between the fixed and moving pressure level, kept by the valve
striking as the current keeps contacts. The gas can not leak locked by the supersonic wave.
flowing from the upper from the nozzle as the hole is As the self-generated pressure
terminal to the moving parts blocked by the fixed contact of the dead volume decreases,
through the arcing contacts. or from the inside of the due to the outflow of the gas
moving contact because of through the moving contact,
During the downstroke, the
the arc clogging effect. the valve re-opens. From
moving part exerts a pressure
now on, a new jet of fresh
on the gas housed in the
gas flows in and makes the
lower chamber; the pressure
temperature of the contacts
increase generated in the
fall. At the same time, the
lower chamber opens the
gas flows through the nozzle,
connection valve of the upper
free from the fixed arcing
chamber. The compressed
contact. The cleaning of
gas flows from the lower
the arcing chamber by means
to the upper chamber thus
of fresh gas makes the device
equalising the pressures.
suitable for another reclosing
and the interruption up to the
maximum breaking capacity.
Resistor contacts
PIR
Preinsertion resistor (PIR) contacts are mainly used at
higher voltages (362 kV and above). The main purpose of
PIR contacts is to limit the transients on the network when
reconnecting lines with no load. They are only used during
close and are connected in parallel with the main contacts.
The PIR contacts close about 8-12 ms before main con-
tacts.
The pre-insertion resistor provides inrush limiting by the
momentary insertion of a resistive device into the circuit
before full energizing.
HV circuit breakers
Electrical power transmission networks are protected and
controlled by high-voltage circuit breakers. The definition
of high voltage varies but in power transmission context it
is usually said to be voltage over 72kV. High-voltage break-
72 kV Distribution circuit breaker Primary distribution vacuum circuit-breaker (15 kV) with
integrated sensors and protection control unit.
Dead-tank
The distinguishing feature of dead-tank technology is that
the interrupter chamber is accommodated in an earthed
metal housing. With this design the SF6 gas filling the tank
insulates the high voltage live parts of the contact assembly
from the housing. Outdoor bushings connect the inter-
rupter chamber with the high-voltage terminals.
This construction means an increased risk of internal earth
fault or short circuit within the tank and the risk cannot be Live tank circuit breaker
neglected. To handle those situations the bushings on both
sides of the tank are normally equipped with current trans-
former further connected to protective relays.
The dead tank circuit breaker has an advantage in case of
earth-quakes.
Low voltage CB
Low voltage circuit breakers types are common in domestic,
commercial and industrial applications up to 1000 V AC.
A Molded Case Circuit Breaker (MCCB) can be rated up to
2500 A. They are thermal or thermal-magnetic operated.
These CBs are often installed in draw-out enclosures that
allow removal and interchange without dismantling the
switchgear. Some large MCCBs are remotely operated by
electrical motors, often part of an automatic transfer switch
Dead tank circuit breaker
system for standby power.
Circuit Breaker testing guide Main types of CB 13
CB technologies
Circuit breakers can mainly be divided into three groups rent and voltage transformers, and supplementary modules.
depending on medium that encloses (insulates) the breaker The major advantage with a GIS installation is the reduc-
contacts. In one group, it is air or other gas, in the second tion of space required compared to the air-insulated substa-
vacuum and in the third oil. tions. The maintenance and test interval for circuit breakers
installed in a GIS is also longer compared to AIS.
Air / Gas
ACB
Air / Gas
Air blast
SF6
Air circuit breakers (ACB)
ACBs can be used both as circuit breakers of low voltage
Vacuum
electrical distribution systems and for protection of electri-
Oil cal equipment in facilities and industries.
Bulk oil A common breaking principle is to use the magnetic field,
Minimum oil created by the current through the ACB, to force the arc to-
The SF6 insulated circuit breakers are more or less the only wards insulating lamells. As the arc goes further in between
installed type within transmission networks today, mainly the lamells eventually the distance to maintain the arc is
due to its relative high total rating and characteristic in exceeded and it is extinguished.
relation to its price. However, with new improvements
with vacuum breaker design they are also becoming more Air blast
common at the lower voltage ranges of the transmission The air blast circuit breakers came into use in the 1930s
networks. Today they can handle voltages up to 252 kV and became be the common circuit breaker on high voltage
but are still very expensive. The vacuum breakers are more and very high voltage applications. The robust designs were
commonly installed at system voltage levels of 70 kV and reliable and robust but noisy. Many breaks are needed for
below. Both the SF6 and vacuum circuit breakers are very high voltages and they are commonly found with opening
common in todays distribution networks. resistors.
Substations are often built as air-insulated switchgear (AIS), Air is compressed in a reservoir up to 14 bar. The contacts
using open air as insulating medium between the different are opened by air blast produced by opening a valve. The
phases and devices. compressed air is released and directed towards the arc at
high velocity. The air blast cools the arc and sweeps the arc-
Gas-insulated switchgears (GIS) are designed and assem-
ing products away. This increases the dielectric strength of
bled by a combination of standardized function modules
the medium between contacts and prevents re-establishing
such as circuit breakers, disconnectors, earth-switches, cur-
the arc. The arc is extinguished and the current is inter-
rupted. The short arcing time, compared with oil CB, gives
low impact on the main contacts.
Vacuum circuit breaker cut-away MCCB (Moulded Case Circuit Breaker) is one example of ACB
500 A / 600 V
Vacuum
Vacuum breakers are used up to 70 kV. Because there is no
gas to ionize to form the arc, the insulating gap is smaller
than an in other circuit breakers. An arc does form from
the vaporized contact material. The insulation distance
in a vacuum breaker is about 11-17 mm between plates.
Normally there is one break per phase but there can be two
interrupters in series.
Examples of bulk oil circuit breakers
1
2
4 5
6
New design
8
7
Motor
On command, the required operations are executed ac-
cording to the stored contact travel program and the motor
Hydraulics is controlled to move the circuit breaker primary contacts
accordingly. Energy charging, buffering, release and trans-
mission are essentially electrical and as such the mechanical
system is reduced to a minimum of moving parts.
Thermal / Magnetic
Current flowing through the circuit heats the bimetal cur-
rent sensor, causing it to bend, this releases the armature
Disc spring
and a spring forces the contacts to open. The load current
also flows through a coil which creates a magnetic field
that will trip the armature faster than the bimetal strip can
respond when very large currents flow.
Main results
70% of Major Failures (MF) were of mechanical origin
19% of MF were of electrical origin concerning the
auxiliary and control circuits
11% of MF were of electrical origin concerning the main
circuit
48% of MF were classified as Does not open or close on
command
CB year of
The operating mechanism was the part of the circuit manufacture
breaker responsible for the highest number of failures (37%
of MF).
Rated voltages 63-800 kV
Mechanism type Failures per 100 cb-years
Major failures Minor failures
Hydraulic 0.31 2.89
Pneumatic 0.27 0.80
Spring 0.27 0.40
Different types of operating mechanism have about the same major
failure rate.
Most of the minor failures of operating mechanisms are
either hydraulic oil or air leakages. The relationship between
18 Failure modes Circuit Breaker testing guide
Major failures segmented by failing sub-component Maintenance aspects
The average interval between scheduled overhaul is 8.3
years. This could in many cases be extended.
The number of failures caused by incorrect maintenance
has decreased compared to the first enquiry (85% decrease
for major failures, 26% for minor failures), but there is still
room for improvement
About a quarter of the failures are caused by inadequate
instructions and incorrect erection, operation and mainte-
nance.
The three important issues for breaker maintenance are:
Lubrication
CB year of
Contact adjustment
manufacture
Neglect or lack of maintenance
Briefly, the most important thing for breaker maintenance
The operating mechanism remains the most unreliable part
is grease. All breakers use grease as lubricant, and grease
of the breaker.
tends to dry out over time due to the heat produced in the
Does not close/open on command and Locked in open breaker parts carrying the load.
or closed position remain the most frequently occurring
failure modes. Conclusions
The overall circuit breaker major failure rate appears to be The results from the latest survey is preliminar and the final
substantially lower than in the previous survey. report is soon going to be released. However, one can see
that the reliability surveys show positive trends; the HV
Mechanical aspects circuit breakers are getting better.
A large part of the major failures have mechanical origin. The reliability surveys have:
The operating mechanism and the electrical control and
auxiliary circuits are the components responsible for the Helped users to choose optimal equipment and
majority of both major and minor failures. maintenance procedures
The dominant major failure modes are Does not open or Helped manufacturers to improve their products
close on commandand Locked in open or closed posi- Contributed to improvement of international standards
tion. These modes add up to almost 70% of the major
failures.
Generator circuit breaker failure A distribution circuit breaker pole totally damaged by explosion.
Testing guide
Type of CB Vacuum Oil Minimum Oil SF6 Air-blast GIS
Voltage levels
(kV) 1 36 Any 6 145 145 400 6 40 72 245 >245 6 40 40 130 >130 Any
Application
Timing x x x x x x x x x x (x)1)
Motion (x)2) x x x x x x (x)3) (x)3) (x)3) x
Coil current x x x x x x x (x)2) (x)2) (x)2) x
DRM n/a (x)2) (x)2) (x)2) x x x (x)2) (x)2) (x)2) (x)6)
SRM x x x x x x x x x x (x)1)
Vibration (x)2) (x)2) (x)2) x (x)2) x x (x)2) (x)2) (x)2) x
DCM (x)2) x x x x x x x x x (x)1)
Motor current x x (x)4) (x)4) (x)4) (x)4) (x)4) n/a n/a n/a (x)4)
Min. voltage to operate CB x x x x x x x x x x x
Minimum voltage x x x x x x x x x x x
Station voltage x x x x x x x x x x x
Gas density n/a n/a n/a x x x n/a n/a n/a n/a
Voltage integrity x n/a n/a n/a n/a n/a n/a n/a n/a n/a n/a
Air pressure/flow n/a n/a n/a n/a n/a n/a n/a x x x n/a
PIR contacts n/a x (x)5) (x)5) (x)5) (x)5) (x)5) (x)5) (x)5) (x)5) (x)5)
Grading capacitors n/a n/a n/a (x)5) (x)5) (x)5) (x)5) (x)5) (x)5) (x)5) (x)5)
Legend
x Applicable
(x)1) If accessible
(x)2) Possible
(x)3) Optional if disconnector knife/contact is included in CB design.
(x)4) Motor current is only applicable on spring drives.
Applicability and presence of grading capacitors as well as PIR contacts are depending on network design and
(x)5) not related to CB design.
(x)6 If accessible and if not vacuum CB
n/a Not applicable
Comments
Motor current There are three different types of operating mechanisms; Spring, hydraulic and pneumatic. Motor current is
only applicable on spring drives.
PIR contacts Applicability and presence of grading capacitors as well as PIR contacts are depending on network design and
Grading capacitors not related to CB design. Usually not used in distribution networks.
Oil CBs Well defined travel trace and transducer attachment points. At higher voltages serial contacts per phase but
those cannot be accessed, thus only timed as single contacts per phase. If PIR contact those are often sliding
contacts in the main tank. No separation possible. Has to be timed as parallel contacts. PIR values can be down
to 10 . Coil current traces are essential. Always single operation mechanism if single tank design.
Minimum Oil CBs Coil currents are essential, as well as operating
1 contact / phase, single operating mechanism.
6 145 kV mechanism damping dash-pots. Travel is essential and
Minimum Oil CBs 2-6 contacts / phase. 400 kV always separate (3) it is usually relatively easy to find documentation on
145 400 kV operating mechanisms. transducer attachment points etc.
With only one side grounded the capacitive coupled current can
reach values high enough to be harmful or lethal for humans.
According to the IEC standard it is the closing/opening of the arcing contact that counts as the breakers operation time, not the main contact.
Examples showing the problems finding threshold setting:
Threshold > 3 m Continuously closed
2 m < Threshold < 3 m Correct closing time (to set the threshold within these limits is a bit of a lottery)
50 < Threshold < 2 m Incorrect closing time (e.g. 1000 in the diagram)
Threshold < 50 Continuously open
Closed
Contact closure
Position
Stroke
Arcing zone
Open
Time
Circuit breaker operating mechanism with rotary motion Motion diagram and timing graphs for a close-open operation
transducer and accelerometer (for vibration measurement).
Movement starts
Motion curve
Resistance curve
Slight increase in resistance when the
contacts start to slide
DRM is a reliable method to estimate the length/wear of the arcing contact. The SDRM202 provides high current and the TM1800 gives an
accurate measurement with very good resolution. Besides, it is possible to use DualGround testing.
Current
When you apply a voltage across a coil, the current curve
first shows a straight transition whose rate of rise depends
on the coils electrical characteristic and the supply voltage.
When the coil armature (which actuates the latch on the
operating mechanisms energy package) starts to move, the
1 Trip coil energized 6 Proportional to DC coil
resistance electrical relationship changes and the coil current drops.
2-5 Armature travel
3-4 Armature operates trip 7 Auxiliary contact opens The peak value of the first, lower current peak is related
latch 8 Current decay to the fully saturated coil current (max current), and this
4-5 Armature completes its relationship gives an indication of the spread to the lowest
travel tripping voltage. If the coil were to reach its maximum
5 Armature hits stop
current before the armature and latch start to move, the
Example of coil current on circuit breaker breaker would not be tripped. It is important to note, how-
ever, that the relationship between the two current peaks
When a trip coil is first energized [1], current flows through varies, particularly with temperature. This also applies to the
its windings. The magnetic lines of force in the coil magne- lowest tripping voltage.
tize the iron core of the armature, in effect inducing a force
Coil currents can be measured on a routine basis to detect
in the armature. The current flowing through the trip coil
potential mechanical and/or electrical problems in actuating
increases to the point where the force exerted on the arma-
coils well in advance of their emergence as actual faults.
ture is sufficient to overcome forces, combined gravitational
and friction, which may be exerted, pulling [2] it through Voltage
the trip coil core. In some cases it is also of interest to measure DC voltage
The magnitude of the initial current [1-2] is proportional sagging during coil operation. The voltage to the coil will
to the energy required to move the armature from its initial vary during operation. This change will influence the coil
rest position. The movement of the iron core through the current, the armature release time and finally the contact
trip coil generates an electromagnetic force in the coil that timing.
in turn has an effect on the current flowing through it. The
SELECTION GUIDE
Measurement entity Circuit breaker EGIL TM1700 TM1800
configuration Model / Config Model Modules / Configuration
Main contact 1 break / phase EGIL Basic All TM1700 1 Timing M/R
timing 2 break / phase All TM1700 1 Timing M/R
4 break / phase All TM1700 4) 2 - 7 Timing M/R
Main and PIR 1 break / phase EGIL Basic All TM1700 1 Timing M/R
contact timing 2 break / phase All TM1700 1 Timing M/R
4 break / phase All TM1700 4) 2 -7 Timing M/R
Coil current 1 operating mech. EGIL Basic All TM1700 1 Control
3 operating mech. TM1720/50/60 2 Control or 1 Control + 1 Analog + 3 ext. current clamps
Motion 1 operating mech. EGIL Motion All TM1700 5) 1 Analog or 1 Digital
EGIL SDRM
3 operating mech.
Auxiliary contact 1 operating mech. EGIL Basic TM1710 1) 1 Control 1) or 1 Timing AUX
timing TM1720/50/60
3 operating mech. TM1720/50/60 2 Control 1) or 1 Control + 1 Timing AUX
3 aux / phase TM1720/50/60 1 Control 1) and 1 Timing AUX or 2 timing aux
SRM 3) Any EGIL SDRM All TM1700 1 Timing M/R + 1 Analog
DRM 3) Any EGIL SDRM 1 Timing M/R + 1 Analog + 1 Digital 2)
1)
52a/b timing only
2)
If digital motion transducer
3)
SDRM201/202 accessory required
4)
Phase by phase and max 6 breaks / phase
5)
With 6 digital transducers or option with 3 analog channels.
Circuit breaker operation is very powerful and vibrations To minimize the error caused by the test instrument the
can cause clamps to lose connection with object dur- calibration intervals recommended by the manufacturer
ing measurement. This can cause odd results and false should be obeyed.
bounces caused by the bad connection.
When using incremental transducers avoid long cables; the
signal can be damped.
Generally, keep cables short and when needed twist them to
avoid induction from magnetic fields.
Keep different types of test cables away from each other.
Make sure to use the right cable intended for the specific
measurement.
Some cables have grounded screens to reduce disturbances.
These shall be used for measurements of analog entities
whereas unshielded cables is to be used for contact timing.
At DualGround testing with DCM the test cables shall not
be moved after tuning the circuit. If the position of the
cables are changed a new tuning has to be performed when
the circuit breaker is in closed position.
Timing measurements
Close Open Damping Charging Possible cause of failure condition
Time Time Time Motor
Faster/ Normal Normal Normal Change in characteristic of the closing system. Latching system is binding.
Slower
Faster Normal Normal Normal Spring charging system used for closing is defective.
CB operating system
Tested parameter Result
Coil current Varies with coil resistance and control voltage
Control voltage Increased voltage drop indicates increased resistance of the coil supply cables.
Must be measured in order to obtain traceability of coil current measurements and
timing measurements
Coil resistance A change could indicate a burned coil or a short circuit between winding turns.
Can be calculated from control voltage and peak current
Armature stop time Increased time indicates increased mechanical resistance in latch system or coil armature
Armature start current Increased current indicates increased mechanical resistance in coil armature
Gives an indication of the lowest operation voltage (coil pick up).
Max motor current Varies with winding resistance, supply voltage and applied force.
Start current not considered.
Motor voltage Increased voltage drop indicates increased resistance in the motor supply cables
Spring charge motor start time Closing time of auxiliary contact for the spring charge motor
Spring charge motor stop time Increased time shows e.g. higher mechanical friction
What kind of motion transducer should I use Follow the CB manufacturers recommendations
for a circuit breaker?
The general recommendation is to use rotary transducer
attach and to attach it to a rotating point in mechanism.
For live tank breakers you generally use a rotary transducer
but for dead tank breakers and bulk oil circuit breakers you
generally use a linear transducer.
Where should I attach the motion transducer? Follow the CB manufacturers recommendations
If the above is missing you should choose a point in which
the motion of the moving contact, as close as possible, is
reflected. This point could have a linear or a rotary movement
and it could be located in the operating mechanism or in a
gear case close to the breaker pole
Why should I test the CB with both sides When the CB is grounded just in one side, the opposite side
grounded? will become ungrounded when the CB is opened. This will
expose the test engineer to danger caused by capacitive
coupled currents, lightning or unintentional energizing of the
test object.
National, international and local standards and regulations
states that all metallic parts in a substation should be
connected to ground.
How do a get conversion tables for my circuit - Contact manufacturer of your circuit breaker
breaker?
- Find out the geometric transfer function between the point
of transducer attachment and the moving contact and create
your own table.
- Make a reference measurement with one transducer
attached on the moving contact and one in the desired
transducer attachment point. From the result of the reference
measurement a table can be created.
I dont have data from manufacturer on my - Make a reference measurement (footprint) of the CB when
circuit breaker. How can I analyze my object? it is new and use this to compare with for the succeeding
tests.
- Use default settings for speed calculation points
- Compare results with other circuit breakers of the same type
EGIL
EGIL is designed specifically for medium-voltage break-
ers having one main contact per phase. Main contacts and
parallel contacts having pre-insertion resistors are recorded
and displayed simultaneously. Coil currents and two auxil-
iary contacts are also measured as standard. EGIL can be
equipped with an analog channel e.g. for motion measure-
ment and a USB port for communication with the CABA
computer program. EGIL with the SDRM option together
with the SDRM accessory enables static and dynamic resis-
tance measurements.
VIDAR
VIDAR tests vacuum in circuit breaker chambers using DC
voltage. When AC is used, the capacitive component of
the current flowing through the chamber must be tested.
With DC, this is eliminated. The resistive component of the
leakage current is very small compared with the capacitive
component, because of the high dielectric strength of the
chamber. The DC flashover voltage is equal to the peak AC
voltage. Testing can be completed in a few minutes
Auxiliary equipment
B10E
Supplies power conveniently to breaker coils and spring-
charging motors. Since this power is unaffected by load and
virtually ripple-free, its ideal for minimum trip-voltage tests.
SDRM202
The SDRM202 is an accessory for TM1800, TM1700 and
EGIL with SDRM option.
The SDRM202 is intended to use for both static and dynam-
ic resistance measurements (SRM and DRM) on high voltage
circuit breakers or other low resistive devices. Used together
with TM1800, TM1700 or EGIL the current and also the
voltage-drop across the circuit breaker contacts are measured.
The measuring unit can thus calculate the resistance as a
function of time.
MOM2
The ruggedness and lightweight, 1 kg (2.2 lbs), makes
MOM2 a handheld instrument very suitable for field work,
such as in substations.
MOM2 test system is designed to serve a number of appli-
cations. The most common are contact resistance measure-
ments of low-, medium- and high-voltage breakers and also
at bus-bar joints, and other high current links.
With MOM2 it is possible to make measurements accord-
ing to the DualGround method. This means that the test
object will be grounded on both sides throughout the test
giving a safer, faster and easier workflow.
MOM200A and MOM600A
MOM200A is designed to check and measure contact
resistances in high-voltage circuit breakers, disconnecting
switches (isolators) and bus-bar joints. The MOM200A is
an excellent choice when 200 amperes or less are needed
for measurement. The MOM600A is suitable when there is
a need for higher currents.
INGVAR
This powerful test system is designed for primary injection
testing of protective relay equipment and circuit breakers.
The system consists of a control unit and a current unit.
The two parts are portable, and INGVAR can be quickly
assembled and connected.
R
Reactor breaker ............................................. 11
References .................................................... 50
Resistor contacts ........................................... 10
S
Safety ............................................................ 22
Sampling frequency ....................................... 35
SDRM202 ...................................................... 39
SF6 ................................................................ 15
SF6 leakage .................................................. 31
Solutions to reduce the arc .............................. 9
Speed ............................................................ 27
Spring loaded ................................................ 17
SRM ............................................................... 27
Standards ........................................................ 7
Static resistance measurement ..................... 27
Switch disconnector ...................................... 12
Synchronized functionality ............................. 10
Synchronized switching ................................. 28
T
Temperature .................................................. 34
Test equipment .............................................. 33
Testing guide ................................................. 21
Test methods ................................................. 25
Price: 30