ABB is a leader in power and automation technologies that enable utility and industry customers to improve their performance while lowering environmental impact.
The ABB Group of companies operates in around 100 countries and employs about
150,000 people.
ABB offers a wide range of high-voltage products up to 1200 kV that help enhance
the reliability, efficiency and quality of power in transmission and distribution grids,
power plants and industries while enhancing eco-efficiency. The wide product range
is complemented by a comprehensive service offering.
ABB is the global leader in high-voltage GIS (gas-insulated switchgear) technology
with more than 23,000 bays installed around the world. In 2009, ABB commissioned a GIS rated to handle more than one million volts (1200 kV), with a transmission capability of 6900 megawatts, reaching new heights in terms of global voltage
levels. We pioneered high-voltage GIS in the mid-1960s and with the introduction
of the new 145 kV we complete the innovative switchgear portfolio comprising a
uniform design and operation philosophy. We continue to drive technology and innovation within the full range of advanced GIS for voltages from 72.5 kV to 1200 kV.
Table of contents
Applications
Benefits
Technology
The circuit-breaker
Operating principles
The disconnector
10
10
11
12
12
Surge arresters
12
13
Transformer connections
13
Cable terminations
13
SF6-air bushings
13
14
14
14
16
17
17
Manufacturing phase
17
Use phase
17
17
Technical data
18
ABB holds a distinguished record of innovations in GIS technology and our latest
ELK-04 series for 145 kV is designed to reduce complexity and life cycle costs.
Applications
Benefits
Modular, compact design
The integrated local control cubicle as well as the drive cubicle is located at the
front of the switchgear. Easy access is granted for manual operation of all equipment.
Gas density information can be displayed on the integrated local control cubicle using combined density sensors/monitors. All instrument transformers are wired to the
integrated local control cubicle.
A service catwalk between the integrated local control cubicle and the bay gives
convenient access to viewports and gas filling points.
GIS from ABB are built on 50 years of pioneering research and development and
experience delivering over 23,000 switchgear bays in over 100 countries. Our
switchgears are crafted using standardized and modular components that enable
the construction of common layouts and bus schemes.
Technology
GIS from ABB
The circuit-breaker
The horizontal circuit-breaker module provides optimal performance and low maintenance. ELK-04 C circuit-breakers are equipped with Auto-pufferTM interrupters,
i.e. self-blast interrupters with one unit per pole. They require minimum maintenance
and only a low amount of operational energy. The optimized and compact layout
minimizes the volume of SF6 insulating gas by 70 percent compared to its predecessor. The circuit-breaker fits to all layouts and is used in other ABB GIS applications as well as for live tank and dead tank circuit-breakers.
The entire operating mechanism is located outside the SF6 gas compartments. The
torsion springs generate less vibration than traditional compression type springs
and a robust charging motor provides recharging of the closing spring in less than
15 seconds. A damping device reduces mechanical stress to a minimum.
In the normal service position of the circuit-breaker the contacts are closed and
the opening and closing springs are charged. In this position the circuit-breaker is
always ready to perform an opening operation or a complete auto-reclosing
(O 0.3 s CO). To open the circuit-breaker, the opening latch (1) is released and
the opening spring (A) is activated. The shaft rotation is converted into a linear
movement to open the breaker. The motion of the contact system is retarded by a
damping device (B).
Operating principles
Releasing the closing latch (2) cause the closing springs (C) to pull the main operating lever (4) to the closed position. At the same time the opening spring (A) is
charged. At the end of the stroke the opening latch (1) engages and locks the main
operating lever (4) connected to the circuit-breaker in closed position.
After reaching the closed position, the closing spring (C) is charged by a motor (5)
turning the charging gear wheel (6) while the cam support (3) is locked by the closing latch (2). The closing spring can be charged by means of a hand crank if the
auxiliary power supply or control circuit fails.
5
OFF
ON
ON
OFF
The disconnector
The disconnectors provide a safe insulating gap to isolate sections with different
potential, for example busbar disconnectors, which isolate a feeder.
The operating mechanism of the disconnector and earthing switch is mounted in
the drive cubicle at the front of the bay and contains all the components needed for
operation and is wired to the integrated local control cubicle next to it. Hand-crank
access and position indicators are features conveniently located in the drive cabinet
and are easy accessible.
Disconnector
Busbar disconnector
8 GIS ELK-04 C, 145 kV | ABB
Earthing switches connect isolated sections of the switchgear to the earth potential
to protect personnel during maintenance and assembly work.
Feeder terminals are often equipped with fast-acting (or make-proof) earthing
switches. These devices are able to earth induced currents on overhead lines, discharge larger capacitances such as cables, and provide safety when the opposite
end of a line is not properly de-energized. The fast-acting earthing switch includes a
spring operated mechanism, which is either charged by a motor or by a hand crank.
Similar to disconnectors, the operating mechanism of the maintenance earthing
switch is located in the drive cubicle at the front of the bay. Hand-crank access,
position indicators and mechanical interlocking, are features conveniently located in
the drive cubicle and are easy accessible from the operators corridor. The operating mechanism of the fast-acting earthing switch is located at the equipment itself
and controlled via the control cubicle.
Our maintenance-free voltage and current transformers provide highly reliable metering, control, and protection functions. Used for system protection, our powerful
transformers offer years of trouble-free service even for heavy-duty applications.
The three-pole inductive voltage transformers are connected to the switchgear with
a standardized connecting flange and a partition insulator. The primary winding is
coiled on top of the core and the secondary windings. The latter are connected to
the terminals in the external terminal box through a gas-tight multiple bushing.
Voltage transformer
10 GIS ELK-04 C, 145 kV | ABB
The single-pole inductive current transformers are attached to the same housing
where the maintenance earthing switch is located. They are located outside the gas
compartment eliminating the need for a gas-tight feed to the secondary terminals.
The current transformer can be placed on the feeder side and on the busbar side
and may contain multiple cores for metering and protection within a single cast
resin case. Current transformer parameters such as burden, ratio, accuracy class
and transient performance are set to meet specific project requirements. Multi-ratio
transformers provide different ratios selectable by taps.
Current transformer
ABB | GIS ELK-04 C, 145 kV 11
We have versatile terminal and connecting elements that enable the switchgear to
be customized to fit your project requirements. We offer connecting elements in various shapes and sizes including phase rotation modules, different angular modules
and straight sections.
The busbar module of ELK-04 C covers a universal expansion joint to absorb heat
expansion and vibrations during operation. During site installation, the expansion
element ensures that neighboring bays can be connected easily.
Surge arresters
Surge arresters are fully-enclosed metal components that limit switching and lightning over voltages. For stable and reliable operations, the ELK-04 C is equipped
with gapless gas-insulated metal-oxide surge arresters. Ratings and discharge
classes are tailored to your project specific requirements.
L-element
12 GIS ELK-04 C, 145 kV | ABB
T-element
X-element
Transformer connections
Our supply can include cable connections of the plug-in type with dry-type or
fluid-filled terminations. The interfaces conform to IEC standards. A removable link
disconnects and isolates the GIS from the cable during high-voltage test for convenience and ease of operations.
Cable terminations
Our lightweight SF 6-air bushings are available in two variants in the standard version, with composite insulators and silicon sheds or with classical porcelain insulators. Creepage distance, length, and shape depend on the project-specific environmental requirements. We provide SF6-air bushings that are maintenance-free with
self-cleaning silicon sheds.
SF6-air bushings
Cable connection
SF6-air bushing
ABB | GIS ELK-04 C, 145 kV 13
The local control cubicle (LCC) includes all required functions for the control and
supervision of the GIS bay. The LCC is usually integrated with the bay and located
on top of the drive cubicle. LCCs can also be delivered as stand alone units not
integrated with the bay. As an integral part of the ELK-04 C, the LCC is wired, factory-tested and shipped together with the bay as one transport unit. This reduces
installation and commissioning time to a minimum and eliminates errors during site
installation. Connections from the LCCs prepared terminal blocks to dedicated
protection cubicles, control systems, power supply, and inter-bay wiring are the only
installation work done on site.
Our LCCs can either be of the Smart Grid Enabled type or the conventional type
with Mimic. Our advanced Relion family of protection and control-IEDs as well as
the conventional Mimic solution ensures the safe and economical operation of the
switchgear.
Our broad range of control and protection systems includes IEC 61850 compliant products that provide open, future-proof and flexible system architecture. Our
advanced local control cubicles enable monitoring and remote diagnostic functions
ensuring high availability and fast access to precise information from anywhere in
the system, speeding up responses and reducing outage time. Depending on the
project requirements, we can also deliver standalone LCCs with all customary control and protection devices.
Ethernet switch
Monitoring PC
Digital monitoring, measurement, control, protection and communication based on IEC 61850
ABB | GIS ELK-04 C, 145 kV 15
The ELK-04 C is factory assembled and fully tested as one bay with the local control cubicle in a manufacturing facility using an advanced flow production system
that adheres to ABB internal quality and manufacturing excellence procedures. All
bays are produced and tested in controlled conditions under the strict supervision
of ABBs engineers and GIS experts.
ABB believes that innovation is a key to ABBs competitive advantage and it has
consistently invested in research and development to become a market leader. The
ELK-04 C is based on pioneering GIS technology since the 1960s and installation in
around 100 countries. It complies with or exceeds the latest international standards
(IEC/ANSI) and has been type tested in independent laboratories.
We are committed to giving you products of the highest quality that is why we strive
to produce only products that comply with or exceed the latest international standards (IEC/ANSI). In addition, our products have been type tested in independent
laboratories. Our certified design and manufacturing processes guarantee the highest quality of our products.
Our GIS bays are fully assembled and tested in the factory with standardized,
automated and reliable procedures. After routine testing, shipping units are packed
in accordance with the freight carriers requirements, the duration of transportation,
the dispatch route and site storage requirements.
Pre-tested, wired and SF6 pre-filled bays reduce the installation work significantly.
Bays are coupled using standard tools and gas handling is minimized. Site testing
according to IEC/ANSI standards and ABB quality assurance procedures include
leakage checks on flanges, instrument transformer, control and monitoring functions, resistance measurements and a high-voltage test. Site installation can be
carried out by ABB or by personnel from your own company under the guidance
of a certified ABB supervisor. ABB offers training courses for every aspect of GIS
installation, operation and maintenance.
ABBs metal-enclosed gas-insulated switchgear requires minimal maintenance in
service. Under normal operational conditions, more than 50 years smooth operation is assured with periodic visual checks. ABB Service provides competent 24/7
worldwide support in case of failures.
For ABB, sustainability is about balancing economic success, environmental stewardship and social progress to benefit all our stakeholders.
Sustainability considerations cover how we design and manufacture products, what
we offer customers, how we engage suppliers, how we assess risks and opportunities, and how we behave in the communities where we operate and towards one
another, while striving to ensure the health, safety and security of our employees,
contractors and others affected by our activities. In line with our business practices,
we publish environmental product declarations for each product we manufacture.
The life cycle of the ELK-04 C is separated into three phases: manufacture, use and
disposal. The manufacture scenario includes materials used, transport of components and SF6 gas leakage rates. The usage scenario includes transport of products
to customers as well as SF6 gas leakage rates and energy losses assuming a 50year life time. The disposal phase refers to SF6 gas leakage rates and the energy for
making recycled metals reusable.
Manufacturing phase
Use phase
2250
2500
Technical data
ELK-04 C, 145 kV
800
4800
ELK-04 C, 145 kV
Product ID
Rated voltage
kV
145
kV
275
kV
315
kV
650
kV
750
Rated frequency
Hz
50/60
3150
kA
kA
Installation
Rated filling pressure / minimum functional pressure (abs. at 20 C)
2GHV010550M0001
40
3
108
Indoor/outdoor
MPa
0.68/0.60
Circuit-breaker
Rated short-circuit breaking current, 50/60 Hz
kA
40
kA
108
1.3/1.5
Drive type
spring
ms
26 ... 35
ms
45 ... 55
Reclosing time
ms
< 300
O-0.3s-CO-3min-CO
class
M2
class
C2
mA
500
A/V
1600/30
kA
kV
kV
class
108
6
100
6
5
E1
ABB AG
High Voltage Products
Brown Boveri Strasse 30
63457 Hanau-Grossauheim / Germany
Phone: +49 621 381-3000
Fax:
+49 621 381-2645
www.abb.com/highvoltage
Note:
We reserve the right to make technical changes or
modify the contents of this document without prior
notice. With regard to purchase orders, the agreed
particulars shall prevail. ABB Ltd does not accept any
responsibility whatsoever for potential errors or possible
lack of information in this document.
We reserve all rights in this document and in the
subject matter and illustrations contained therein. Any
reproduction, disclosure to third parties or utilization of
its content in whole or parts is forbidden without prior
written consent of ABB Ltd.
Copyright 2014 ABB
All rights reserved
Contact us