1646 - Relay Coordination Table
1646 - Relay Coordination Table
1646 - Relay Coordination Table
S.B. KANG
Y.K. MIN
M.J. KIM
REV.
DATE
DESCRIPTION
BY
CHECKED
APPROVED
MESSRS.
CLASS
BV
DRAWING NO.
PROJECT NO.
Rev. 0
TABLE OF CONTENTS
PAGE
1. APPLICATION .......
3. CALCULATION CRITERIA ..
Page 2 of 90
Rev. 0
1. APPLICATION
1.1
The protective relay setting report, which apply selective system to clear only faulted feeder, is
applied to 6.6KV system of ship no. H1646-9 / S253-6 (8,200 TEU container vessel) for following
purpose.
1) The objective of protective scheme in power system is to minimize hazardous to personnel and
equipment while causing the least disruption of power service.
2) Coordination studies are required to select or verify the clearing characteristics of devices such as
fuses, circuit breakers and relays used in the protective scheme.
3) The studies are also needed to determine the protective device setting that will provide selective
fault isolation.
4) In a properly coordinated system, a fault results in interruption of only the minimum amount of
equipment necessary to isolate the faulted portion of the system. The power supply to load in the
reminder of the system is maintained.
5) The goal is to achieve an optimum balance between protective equipment and selective fault
isolation that is consistent with the operation requirements of the overall power system.
1.2
Thus,
to
tx
tm = ( 2
3
) 1,000 + 75 + 30 + 35
100
= 200ms
Page 3 of 90
Rev. 0
SWBD EQUIPMENT
CT / PT
APPLIED FEEDER
RATIO
6.6KV
MAIN
SWB
D
6.6KV
MAIN
SWBD
-1/2
500/5A
5P10/15VA
5P10/30VA
200/1.5mA (ZCT)
6.6
0.11
/
KV
3
3
(INCOMER SIDE)
TR : 1,600KVA, 6.6/0.44KV
IFLC = 140A, %Z = 5.85%
NO.1/2 STEP-DOWN TR
FEEDER
(P-MTR1-1, P-MTR2-1)
TR : 3,900KVA, 6.6/0.44KV
IFLC = 341.2A, %Z = 6.11%
0.11
0.19
/
KV
3
3
(BUS SIDE)
1.0CL/3P,
100/200VA
5P10/15VA
5P10/30VA
200/1.5mA (ZCT)
6.6
0.11
/
KV
3
3
(INCOMER SIDE)
6.6
3
NO. 1/2/3/4/5/6/7
REEFER TR FEEDER
(P-RTR1~7-1)
0.11
0.19
/
KV
3
3
(BUS SIDE)
6.6
0.11
/
KV
3
3
(INCOMER SIDE)
6.6
3
0.11
0.19
/
KV
3
3
(BUS SIDE)
200/5A
0.11
0.19
/
KV
3
3
(BUS SIDE)
1.0CL/3P
100/200VA
5P20/40VA
200/1.5mA (ZCT)
0.11
0.19
/
KV
3
3
(BUS SIDE)
50/5A
0.11
0.19
/
/
KV
3
3
(BUS SIDE)
350/5A
0.11
0.19
/
KV
3
3
(BUS SIDE)
HYUNDAI/
HIMAP-T
49, 46,
51LR, 50,
66, 67G,
PF : 100A
HYUNDAI/
HIMAP-M
49, 46,
51LR, 50,
66, 67G
HYUNDAI/
HIMAP-M
5P10/15VA
1.0CL/3P
100/200VA
5P10/15VA
200/1.5mA (ZCT)
6.6
3
50/51, 67G,
87T
1.0CL/3P
100/200VA
200/1.5mA (ZCT)
6.6
3
HYUNDAI/
HIMAP-FI
5P10/15VA
5P10/15VA
27, 50/51,
67G
1.0CL/3P
100/200VA
450/5A
6.6
3
25
DEIF/
CSQ-2M
&
DEIF /
FAS-113DG
1.0CL/100VA
200/1.5mA (ZCT)
6.6
3
MAKER/
MODEL
400/5A
APPLIED
PROTECTIVE
ACC. CL / VA
RELAY
1.0CL/3P
100/200VA
Page 4 of 90
Rev. 0
3. CALCULATION CRITERIA
3.1
Page 5 of 90
Rev. 0
Page 6 of 90
Rev. 0
Ig =
Rg +
1
R
+ j3wc
Where,
Ig
Eg
Rg
: Equivalent resistance, which transfer the current limit resistance(r) of the GPT
open delta winding to the neutral earth resistance of the GPT primary.
1
n2r (n : Voltage ratio of GPT)
9
: Capacitive reactance between phase and earth
R=
0.4 200VA
Where,
200VA : The rated burden of GPT
0.4 : Factor for fault duration
r 24 ohm,
Select, r = 25 ohm
c) Equivalent resistance, which transfer the current limit resistance(r) of the GPT open delta
winding to the neutral earth resistance of the GPT primary.
R=
=
1
9
n2r
6.6
/
3
0.19 2
) x 25
3
9
= 10,056 ohm
IgR =
10,000 +
1
1
10,056
= 0.19A
Page 7 of 90
Rev. 0
0.19A
1,000 = 1.4mA
Therefore, The limit setting of the directional overcurrent relay shall be selected to
1.0mA.
Definite delay time setting shall be selected to 0.2sec.
The phase angle setting shall be 60and the volt low limit setting shall be 20%.
3) 46 : Reverse phase relay
The limit value of the negative sequence current shall be set to trip at the less value
than the permissible negative sequence current (I2) and the permissible level of the
integrated quantity I2t (=K), which should be supplied by the generators manufacturer.
K and I2 of generator are normally applied as follows when the information is not
provided by generators manufacturer.
Generator
I2
K = I2t
Diesel generator
10% IFLC
40
Page 8 of 90
Rev. 0
7) 27 : Undervoltage relay
The undervoltage limit 1 shall be used for stand-by D/G start and blackout change
after voltage build up.
It shall be set at 90% of rated voltage and time delay set at 5 sec.
The undervoltage limit 2 for circuit breaker trip shall be set at 50% of rated voltage
and time delay set at 1.0sec in order to give all other relays an opportunity to operate.
8) 59 : Overvoltage relay
The overvoltage limit 1 for circuit breaker trip shall be used to provide a back-up for
overvoltage.
It shall be set at 110% of rated voltage and the time multiplier shall be set to trip
after 5.0 sec at 130% of rated voltage with IEC normal inverse curve.
The overvoltage limit 2 shall be used to function for stand-by D/G start and blackout
change after voltage build up at overvoltage caused by overspeed, excitation system
malfunction etc.
It shall be set to trip after 5.0 sec at 108% of rated voltage.
9) 25 : Synchronizing check relay
Synchronizing check relay shall be set as follows
y Max. phase angle
: 7deg
: 250mHz
: 100sec
: 2sec
: 10sec
Page 9 of 90
Rev. 0
1
of the synchronous reactance(Xd) of the generator
2
X' d
Xd
) and the circle offset shall be set to the generator transient reactance
.
(that is,
2
2
Time delay setting shall be 5 sec, which is the delayed time to be necessary to allow
Circle radius shall be set to
The overvoltage ground relay, which is used for detecting 6.6kV bus bar ground fault
and used to trip bus tie and generator circuit breaker, shall be set to 30% of relay rated
voltage, 10sec for bus tie circuit breaker and 12sec for generator circuit breaker.
Page 10 of 90
Rev. 0
1) 27 : Undervoltage relay
The setting of the undervoltage relay(27), which monitors the live voltage of busbar for closing permissive of distribution feeder CB and for abnormal trip of motor
feeder shall be selected to 80% of the rated voltage and the time setting selected to
2.0sec and shall be selected to 20% of the rated voltage and time setting selected to
1.0sec for dead bus checking.
The overvoltage ground relay, which is used for detecting of 6.6KV ground fault and
used to give an Alarm signal to AMS, shall be set to 15% of relay rated voltage, 1.3sec
(min. setting) at 1.3 times the setting with inverse curve.
Page 11 of 90
Rev. 0
y XP
y Fset
y U max
y TBC
Page 12 of 90
Rev. 0
Digital relay type HYUNDAI/HIMAP-FI device is provided for the reefer TR feeder
protection. This includes undervoltage relay (27), overcurrent relay (50/51), directional ground
relay (67G).
1) 27 : Undervoltage relay
The instantaneous overcurrent setting shall be selected to trip at 220% (that is,
slightly less than instantaneous setting of incomer/generator feeder) of a rated
current of one(1) smallest generator and provided with coordination margin of
at least 0.2sec with bus-tie circuit breaker.
Normal operating condition ;
For 6.6KV system earth fault current, refer to 67G of Para 3.1.1 (Incomer from
D/G of 6.6KV MAIN SWBD).
Current setting is selected to 1.0mA. Time shall be set at 0.2sec.
The phase angle setting shall be 60and the voltage setting shall be 20%.
Page 13 of 90
Rev. 0
For the step-down TR protection, digital relay type HYUNDAI/HIMAP-T device is provided
This includes overcurrent relay(50/51), directional ground relay(67G) & TR differential
relay(87T).
1) 50/51 : Overcurrent relay
The time overcurrent setting shall be selected to trip at 85% of a rated current
of one(1) biggest rated generator and provided with coordination margin of
0.2sec with overcurrent relay of the one(1) biggest generator.
Normal operating condition ;
The instantaneous overcurrent setting shall be selected to trip at 220% (that is,
slightly less than instantaneous setting of incomer/generator feeder) of a rated
current of one(1) smallest rated generator and provided with coordination
margin of at 0.2 sec with bus-tie circuit breaker.
Normal operating condition ;
For 6.6KV system earth fault current, refer to 67G of Para 3.1.1 (incomer from
D/G of 6.6KV MAIN SWBD). Current setting is selected to 1.0mA. Time shall be
set at 0.2sec.
This phase angle setting shall be 60and voltage setting shall be 20%.
Page 14 of 90
Rev. 0
3) 87 : TR differential relay
a)
Inst. ratio :
Inst. ratio setting, which is initiated regardless of the magnitude of the stabilizing
current if this setting value be exceeded, should be set to the larger value if 150%
and above of transformer inrush current and transformer through fault current.
b)
Differential ratio :
Differential ratio setting shall be chosen by the amount of differential current that
might be seen during normal operation condition.
Setting shall be selected to 25% as the relay protects no load tap changer
transformer.
c)
Bias ratio :
Bias ratio setting shall be selected to 20% as the differential ratio setting is 25%.
d)
e)
TR angle : Ddo
Zero comp
: disable
Page 15 of 90
Rev. 0
Digital relay type HYUNDAI/HIMAP-M device is provided for motor feeder protection.
This includes thermal overload relay (49), locked rotor relay (51LR), Negative sequence relay
(46), Start inhibit relay for motor (66), Directional ground relay (67G) & Instantaneous
overcurrent (50).
Setting curve of 6.6KV BOW THRUSTER MOTOR feeder shall be selected to laid below
overcurrent protection curve of incomer (from D/G) overcurrent curve for tripping and lockout
of bus tie CB under the condition of the three(3) [= one(1) big Gen. + two(2) small Gen.]
generators parallel operation.
1) 49 : Overload relay
a) Thermal current :
Thermal current shall be set at 100% of motor full load current
b) Cold thermal limit at 6
Cold thermal limit at 6 shall be laid below the cold curve of the motor, which is
informed from motor manufacturer
c) Hot thermal limit at 6
Hot thermal limit at 6 shall be laid below the characteristic of hot curve to limit
the thermal image value, which is informed from motor manufacturer, and shall be
set not to trip at motor starting.
d) tc/th : Ratio of cooling time constant to thermal time constant.
Constant tc/th shall be set by the information of motor manufacturer, if the
information is not provided,
tc
= 3 is selected
th
Instantaneous overcurrent shall be set high enough not to trip on the first inrush
current at 100% voltage.
Current = 1.2 1.6 Starting current
Where,
1.6 = D.C Offset
1.2 = Safety factor
Page 16 of 90
Rev. 0
a) Start current :
Start current shall be set equal to the actual starting current at rated voltage.
b) Start time :
Start time shall be set greater than the real starting time of the motor at rated
voltage for the direct on line starting and at reduced voltage for the auto TR starting.
c) Locked rotor current
Locked rotor current shall be set greater than motor rated current, but less than
motor starting current.
Therefore, locked rotor current shall be set at 300% of motor rated current for the
direct on line starting and at 200% of motor rated current for the auto TR starting
locked rotor current.
d) Locked rotor time
As the locked rotor time initiates after start time set, time shall be set at 2sec but
less than 80% of stall time on hot condition shown on manufacturers data sheet.
4) 46 : Negative sequence relay
Current setting shall be normally selected to 1.4 times the maximum permissible
continuous negative phase sequence current and time selected to 4sec to prevent
maloperation at motor starting.
Current = 1.4 Insc
Where,
Insc = The maximum permissive continuous negative sequence current
(5 15% IFLC)
Current = 1.4 10% IFLC = 14% IFLC,
For 6.6KV system earth fault current, refer to 67G of Para 3.1.1 (Incomer from
D/G of 6.6KV MAIN SWBD).
Current setting is selected to 1.0mA. Time shall be set at 0.2sec.
The phase angle setting shall be 60 and the voltage setting shall be 20%.
Page 17 of 90
Rev. 0
SWBD
FEEDER
RATING
POWER
FUSE
INTERSECT POINT
OF RELAY AND
FUSE
RATED BREAKING
CAPACITY
OF VCS
6.6KV
MAIN
SWBD-1/2
No. 1/2
MAIN L.O
PUMP
6.6KV
355KW
IFLC = 37.6A
IST =235A (DOL)
100A
Refer to
Protective Relay
coordination curve
3.2KA
6.6KV
MAIN
SWBD-1
BOW
THRUSTER
MOTOR
6.6KV
2,500KW
IFLC = 279.3A
IST =419A (50%)
250A2
Refer to
Protective Relay
coordination curve
3.2KA
The intersect point of relay and fuse curve shall be lower than the rated breaking capacity of VCS.
Page 18 of 90
Rev. 0
B.
C.
D.
Address
Applied relay
500/5A
Relay type
Manufacturer
D/G Data
Applied D/G
: P-DG-1/2
Rating
: 3,733.33KVA (2,800KW), PF : 0.75
Volt rating
: 6,600V
FLC
: 326.6A
Max. 3Ph Transient Contri. Fault Current : 2,599.8A
Steady State Fault Current : 979.8A
CT/PT Data
PT Ratio
: 6.6:3 / 0.11:3 KV (Incomer Side)
6.6:3 / 0.11:3 / 0.19:3 KV (Bus Side)
CT Ratio
: 500/5A
500/5A (Gen. Side)
ZCT Ratio
: 200/1.5mA
Relay setting table
Function
DG
200/1.5mA
27
59
81
40
50/51
87
32
46
47
67G
95i
64
500/5A
Setting Range
Setting Value
Remarks
0 9999A
326.6A
0201
0 65000V
6600V
0202
0 9999KW
2,800KW
0203
50/60HZ
60HZ
0204
0 9999A
500A
0205
0 65000V
6600V
0206
0 9999V
110V
0207
0 65000V
6600V
0208
0 9999V
110V
0209
0 65000V
Not Used
0210
0 9999V
Not Used
0211
0 65000V
6600V
0212
0 9999V
190V
0213
0 65000V
Not Used
0214
0 9999V
Not Used
0215
0 9999A
Fixed as 200/1.5mA
0216
0 9999A
in Program.
0217
0 9999A
Not Used
0218
0 9999A
Not Used
0219
0 9999A
500A
0220
0.01-9.99WPRIM/WSEC
1.0
0221
24Vdc -230Vac
110Vdc
0222
24Vdc -230Vac
110Vdc
0223
24Vdc -230Vac
110Vdc
Page 19 of 90
Address
Function
Rev. 0
Setting Range
Setting Value
Remarks
Undervoltage Relay
- Undervoltage 1.Limit
- Delay Time (Definite)
On / Off / CB On
0.0 ~ 99.9%
0.03 ~ 99.99sec
CB On
90%
5 sec
1103
1104
1105
1106
- Undervoltage 2. Limit
- Delay Time (Definite)
- Min. Start Voltage
- Min. Frequency
0.0 ~ 99.9%
0.03 ~ 99.99sec
0.0 ~ 99.9%
0.0 ~ 99.9HZ
50%
1 sec
30%
33HZ
Overvoltage Relay
- 1. Limit Value
On / Off / Reclose
1 ~ 999.9%
On
110%
1602
1603
0.01 ~ 10
Normal Inverse /
Definite
0.1
Normal Inverse
1604
1605
1606
- Reserved
- 2 Limit Value
- Delay Time (Definite)
1 ~ 999.9%
0.01 999.99sec
108%
5 sec
Frequency Relay
Overfreq. 1. Step Limit
- Delay Time (Definite)
Reserved
On / Off / CB On
100.0 199.9%
0.1 999.9sec
CB On
105%
5 sec
2004
2005
2006
100.0 199.9%
0.1 999.9sec
110%
3 sec
VCB trip
2007
2008
2009
0.1 99.9%
0.1 999.9sec
97.5%
5 sec
2010
2011
2012
0.1 99.9 %
0.1 999.9sec
0.1 99.9%
90%
10 sec
65%
VCB trip
On / Off
0.0-9999%
0.03-99.99sec
0.7 ~ 1.0 Rated Volt.
On / Off
2.5 ~ 300.0 ohm
2.5 ~ 300.0 ohm
0.1 ~ 10.0sec
On / Off
2.5 ~ 300.0 ohm
2.5 ~ 300.0 ohm
0.1 ~ 10.0sec
On
50%
2 sec
0.7 Rated Volt
On
23.8 ohm
2.4 ohm
5 sec
Off
Not Used
Not Used
Not Used
1/2 Xd
1/2 Xd
Page 20 of 90
Address
Function
Rev. 0
Setting Range
Setting Value
On / Off / Reclose
2.0 ~ 2999.9%
30 ~ 9999ms
On
250%
600ms
Remarks
Instantaneous Overcurrent
- 1. Limit
- Delay Time (Definite)
Reserved
1404
1405
1406
- 2. Limit
- Delay Tiem (Definite)
Reserved
2.0 ~ 2999.9%
30 ~ 9999ms
250%
400ms
B/T Trip
1407
1408
1409
- Rev. Limit
- Delay Time (Definte)
Reserved
2.0 ~ 2999.9%
30 ~ 9999ms
250%
50ms
1410
- Inrush Blocking
On / Off
On
On / Off / Reclose
2.0 ~ 2999.9%
0.03 ~ 10.00
On
105%
0.36
8 Curve Shapes(IDMT)
None, Def./Th, Def.,Curve
D-F
Very Inverse
None
Gen. CB Trip
1503
1504
- Curve Shape
- Reset Characteristic
1505
1506
- 1. Limit
- Delay Time (Definite)
2.0 ~ 2999.9%
0.1 ~ 999.9sec
100%
3 sec
1507
1508
1509
1510
1511
1512
1513
- 2. Limit
- Delay Time (Definite)
- 3. Limit
- Delay Time (Definite)
- Reset Charact. (Th)
- Volt. Restrain (51VR)
- Voltage Low Limit
2.0 ~ 2999.9%
0.1 ~ 999.9sec
2.0 ~ 2999.9%
0.1 ~ 999.9sec
0 ~ 99sec
On / Off
10 ~ 90%
Not Used
Not Used
Not Used
Not Used
0 sec
Off
Not Used
2104
2105
2106
2107
2108
2109
Reserved
Reserved
- Delay CT-Saturation
- Inrush Blocking
- Bias Limit
- Zero Compensation
On / Off
1.0 ~ 99.9%
0.03~ 999.99sec
None, Dy1, Dy5, Dy7,
Dy11, Yd1
On
20%
0.1 sec
None
0.1 ~ 9999.9sec
On / Off
0.1 ~ 999.9%
On / Off
0.1 sec
On
30%
Off
Page 21 of 90
Address
Function
Rev. 0
Setting Range
Setting Value
On / Off
0.1 ~ 99.9%
0.1 ~ 99.9sec
0.1 ~ 99.9%
0.1 ~ 99.9sec
0.1 ~ 199.9%
0.1 ~ 99.9sec
0.1 ~ 199.9%
0.1 ~ 99.9sec
On
10%
5 sec
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Remarks
Overload Relay
- 1. Limit Reverse Power
- Delay Time (Definite)
- 2. Limit Reverse Power
- Delay Time (Definite)
- 1. Limit Active Power
- Delay Time (Definite)
- 2. Limit Active Power
- Delay Time (Definite)
On / Off / Reclose
0.0 ~ 99.9%
0.01 ~ 99.99
Norm. Inverse / Definite
1.0 ~ 99.9%
0.0 ~ 99.9%
0 ~ 9999ms
0.0 ~ 99.9%
0 ~ 9999ms
On / Off
On
10%
2.0
Norm. Inverse
10%
Not Used
Not Used
Not Used
Not Used
Off
On / Off
1.0 ~ 199.9%
0.01 ~ 99.99sec
On
20%
2 sec
Event No.
0-30 Deg
0-2000mHZ
70.0-100.0%
100.0-130.0%
0.1-30%
70.0-100.0%
100.0-130.3%
0.1-999.9sec
0.1-999.9sec
0-9999ms
0.1-999.9sec
0.1-999.9sec
Event Reminder For
Output
Event Reminder For
Output
Event Reminder For
Output
Event Reminder For
Output
800
7 deg
250 mHZ
94%
106%
5%
95%
105%
100 sec
2 sec
500 ms
10 sec
2 sec
0.0-99.9%
0-9999(Event Number)
Up/Down/Both
0-1000ms
50%
1014
1015
1016
1017
1018
1019
1020
Both
100ms
Page 22 of 90
Address
Function
Rev. 0
Setting Range
Setting Value
On/Off
0.0-99.9%
Event Reminder for Output
Event Reminder for Output
On
10%
Remarks
With External
Black Out Signal
AC Direction (67GS)
- Limit Value (Igndx)
- Delay Time (Definite)
- Pick-Up Type (67GX)
On / Off
0 ~ 9999mA
0.1 ~ 999sec
Meas. Ignd1/Meas.
Ignd2/Meas. Ig1 & 2
On
1.0mA
0.2 sec
Meas. Ignd1
1814
1815
1816
0.1 ~ 999.9%
0 ~ 360
On/Off
20%
60
Off
On/Off
1.0 99.9%
1 99%
30 9999ms
0.03 99.99sec
On
0%
15%
100 ms
1 sec
2305
1 2999%
955%
Off
On / Off / Reclose
0.1-999.9%
0.1-999.9sec
On
30%
10 sec
1704
1705
1706
0.1-999.9%
0.1-999.9sec
30%
12 sec
Page 23 of 90
E.
Rev. 0
Calculation
1. ANSI 40
%Xd = 245% (3,733.33KVA Base)
Xd =
%Xd KV 2 10
=
KVA
245 6.6 2 10
3,733.33
= 28.58 ohm
CT RATIO
VT RATIO
100
= 1.0 28.58/2
60
= 23.8 ohm
Circle 1 radius
= 1.0 Xd/2
%Xd KV 2 10
KVA
1
2
1
2
Xd
2.88
24.7 6.6 2 10
3,733.33
= 2.88 ohm
CT RATIO
VT RATIO
100
60
= 2.4 ohm ..
2. ANSI 51
Limit = 105% .
13.5 TMS
(I/ I P )-1
I
IP
= 2,
t=5
TMS = 0.37 .
3. ANSI 32
1. Limit reverse power
1. Limit reverse power = 10% of rated output of GEN.
..
Delay time = 5 sec
4. ANSI 95i
Imax Blocking inrush =
1.2 2,599.8A
100
326.6A
= 955.2
Page 24 of 90
4.1.2
Rev. 0
Relay type
Manufacturer
B. D/G Data
Applied D/G
: P-AG-1/2/3
Rating
: 2,933.33KVA (2,200KW), PF : 0.75
Volt rating
: 6,600V
FLC
: 256.6A
Max. 3Ph Transient Contri. Fault Current : 1,976.89A
Steady State Fault Current : 769.8A
C. CT/PT Data
PT Ratio
: 6.6:3 / 0.11:3 KV (Incomer Side)
6.6:3 / 0.11:3 / 0.19:3 KV (Bus Side)
CT Ratio
: 400/5A
400/5A (Gen. Side)
ZCT Ratio
: 200/1.5mA
D. Relay setting table
Address
Function
400/5A
DG
200/1.5mA
27
59
81
40
50/51
87
32
46
47
67G
95i
64
400/5A
Setting Range
Setting Value
Remarks
0 9999A
256.6A
0201
0 65000V
6600V
0202
0 9999KW
2,200KW
0203
50/60HZ
60HZ
0204
0 9999A
400A
0205
0 65000V
6600V
0206
0 9999V
110V
0207
0 65000V
6600V
0208
0 9999V
110V
0209
0 65000V
Not Used
0210
0 9999V
Not Used
0211
0 65000V
6600V
0212
0 9999V
190V
0213
0 65000V
Not Used
0214
0 9999V
Not Used
0215
0 9999A
Fixed as 200/1.5mA
0216
0 9999A
in Program.
0217
0 9999A
Not Used
0218
0 9999A
Not Used
0219
0 9999A
400A
0220
0.01-9.99WPRIM/WSEC
1.0
0221
24Vdc -230Vac
110Vdc
0222
24Vdc -230Vac
110Vdc
0223
24Vdc -230Vac
110Vdc
Page 25 of 90
Address
Function
Rev. 0
Setting Range
Setting Value
Remarks
Undervoltage Relay
- Undervoltage 1.Limit
- Delay Time (Definite)
On / Off / CB On
0.0 ~ 99.9%
0.03 ~ 99.99sec
CB On
90%
5 sec
1103
1104
1105
1106
- Undervoltage 2. Limit
- Delay Time (Definite)
- Min. Start Voltage
- Min. Frequency
1.0 ~ 99.9%
0.03 ~ 99.99sec
1.0 ~ 99.9%
0.0 ~ 99.9HZ
50%
1 sec
30%
33HZ
Overvoltage Relay
- 1. Limit Value
On / Off / Reclose
1 ~ 999.9%
On
110%
1602
1603
0.01 ~ 10
Normal Inverse /
Definite
0.1
Normal Inverse
1604
1605
1606
- Reserved
- 2 Limit Value
- Delay Time (Definite)
1 ~ 999.9%
0.01 999.99sec
108%
5 sec
Frequency Relay
Overfreq. 1. Step Limit
- Delay Time (Definite)
Reserved
On / Off / CB On
100.0 199.9%
0.1 999.9sec
CB On
105%
5 sec
2004
2005
2006
100.0 199.9%
0.1 999.9sec
110%
3 sec
VCB trip
2007
2008
2009
0.1 99.9%
0.1 999.9sec
97.5%
5 sec
2010
2011
2012
0.1 99.9 %
0.1 999.9sec
0.1 99.9%
90%
10 sec
65%
VCB trip
On / Off
0.0-9999%
0.03-99.99sec
0.7 ~ 1.0 Rated Volt.
On / Off
2.5 ~ 300.0 ohm
2.5 ~ 300.0 ohm
0.1 ~ 10.0sec
On / Off
2.5 ~ 300.0 ohm
2.5 ~ 300.0 ohm
0.1 ~ 10.0sec
On
50%
2 sec
0.7 Rated Volt
On
24.2 ohm
2.4 ohm
5 sec
Off
Not Used
Not Used
Not Used
1/2 Xd
1/2 Xd
Page 26 of 90
Address
Function
Rev. 0
Setting Range
Setting Value
On / Off / Reclose
2.0 ~ 2999.9%
30 ~ 9999ms
On
250%
600ms
Remarks
Instantaneous Overcurrent
- 1. Limit
- Delay Time (Definite)
Reserved
1404
1405
1406
- 2. Limit
- Delay Tiem (Definite)
Reserved
2.0 ~ 2999.9%
30 ~ 9999ms
250%
400ms
B/T Trip
1407
1408
1409
- Rev. Limit
- Delay Time (Definte)
Reserved
2.0 ~ 2999.9%
30 ~ 9999ms
250%
50ms
1410
- Inrush Blocking
On / Off
On
On / Off / Reclose
2.0 ~ 2999.9%
0.03 ~ 10.00
On
105%
0.36
8 Curve Shapes(IDMT)
None, Def./Th, Def.,Curve
D-F
Very Inverse
None
Gen. CB Trip
1503
1504
- Curve Shape
- Reset Characteristic
1505
1506
- 1. Limit
- Delay Time (Definite)
2.0 ~ 2999.9%
0.1 ~ 999.9sec
100%
3 sec
1507
1508
1509
1510
1511
1512
1513
- 2. Limit
- Delay Time (Definite)
- 3. Limit
- Delay Time (Definite)
- Reset Charact. (Th)
- Volt. Restrain (51VR)
- Voltage Low Limit
2.0 ~ 2999.9%
0.1 ~ 999.9sec
2.0 ~ 2999.9%
0.1 ~ 999.9sec
0 ~ 99sec
On / Off
10 ~ 90%
Not Used
Not Used
Not Used
Not Used
0 sec
Off
Not Used
2104
2105
2106
2107
2108
2109
Reserved
Reserved
- Delay CT-Saturation
- Inrush Blocking
- Bias Limit
- Zero Compensation
On / Off
1.0 ~ 99.9%
0.03~ 999.99sec
None, Dy1, Dy5, Dy7,
Dy11, Yd1
On
20%
0.1 sec
None
0.1 ~ 9999.9sec
On / Off
0.1 ~ 999.9%
On / Off
0.1 sec
On
30%
Off
Page 27 of 90
Address
Function
Rev. 0
Setting Range
Setting Value
On / Off
0.1 ~ 99.9%
0.1 ~ 99.9sec
0.1 ~ 99.9%
0.1 ~ 99.9sec
0.1 ~ 199.9%
0.1 ~ 99.9sec
0.1 ~ 199.9%
0.1 ~ 99.9sec
On
10%
5 sec
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used
Remarks
Overload Relay
- 1. Limit Reverse Power
- Delay Time (Definite)
- 2. Limit Reverse Power
- Delay Time (Definite)
- 1. Limit Active Power
- Delay Time (Definite)
- 2. Limit Active Power
- Delay Time (Definite)
On / Off / Reclose
0.0 ~ 99.9%
0.01 ~ 99.99
Norm. Inverse / Definite
1.0 ~ 99.9%
0.0 ~ 99.9%
0 ~ 9999ms
0.0 ~ 99.9%
0 ~ 9999ms
On / Off
On
10%
2.0
Norm. Inverse
10%
Not Used
Not Used
Not Used
Not Used
Off
On / Off
1.0 ~ 199.9%
0.01 ~ 99.99sec
On
20%
2 sec
Event No.
0-30 Deg
0-2000mHZ
70.0-100.0%
100.0-130.0%
0.1-30%
70.0-100.0%
100.0-130.3%
0.1-999.9sec
0.1-999.9sec
0-9999ms
0.1-999.9sec
0.1-999.9sec
Event Reminder For
Output
Event Reminder For
Output
Event Reminder For
Output
Event Reminder For
Output
800
7 deg
250 mHZ
94%
106%
5%
95%
105%
100 sec
2 sec
500 ms
10 sec
2 sec
0.0-99.9%
0-9999(Event Number)
Up/Down/Both
0-1000ms
50%
1014
1015
1016
1017
1018
1019
1020
Both
100ms
Page 28 of 90
Address
Function
Rev. 0
Setting Range
Setting Value
On/Off
0.0-99.9%
Event Reminder for Output
Event Reminder for Output
On
10%
Remarks
With External
Black Out Signal
AC Direction (67GS)
- Limit Value (Igndx)
- Delay Time (Definite)
- Pick-Up Type (67GX)
On / Off
0 ~ 9999mA
0.1 ~ 999sec
Meas. Ignd1/Meas.
Ignd2/Meas. Ig1 & 2
On
1.0mA
0.2 sec
Meas. Ignd1
1814
1815
1816
0.1 ~ 999.9%
0 ~ 360
On/Off
20%
60
Off
On/Off
1.0 99.9%
1 99%
30 9999ms
0.03 99.99sec
On
0%
15%
100 ms
1 sec
2305
1 2999%
924%
Off
On / Off / Reclose
0.1-999.9%
0.1-999.9sec
On
30%
10 sec
1704
1705
1706
0.1-999.9%
0.1-999.9sec
30%
12 sec
Page 29 of 90
E.
Rev. 0
Calculation
1. ANSI 40
%Xd = 245% (2,933.33KVA Base)
Xd =
%Xd KV 2 10
=
KVA
245 6.6 2 10
2,933.33
= 36.4 ohm
CT RATIO
VT RATIO
80
= 1.0 36.4/2
60
= 24.266 ohm
Circle 1 radius
= 1.0 Xd/2
%Xd KV 2 10
KVA
1
2
1
2
Xd
3.74
25.2 6.6 2 10
2,933.33
= 3.74 ohm
CT RATIO
VT RATIO
80
60
= 2.492 ohm ..
2. ANSI 51
Limit = 105% .
13.5 TMS
(I/ I P )-1
I
IP
= 2,
t=5
TMS = 0.37 .
3. ANSI 32
1. Limit reverse power
1. Limit reverse power = 10% of rated output of GEN.
..
Delay time = 5 sec
4. ANSI 95i
1.2 1,976.57A
100
256.6A
= 924.3
Page 30 of 90
Rev. 0
: 27M, 27R, 64
Relay type
: HIMAP FI
Manufacturer
: HYUNDAI
GPT
CLR
B. GPT Data
GPT Ratio
27
64
Function
Setting Range
Setting Value
Remarks
0.5-1.0Vn
0.8Vn (88V)
Time (Definite)
0.1-10 sec
2 sec
0.2-0.5Vn
0.2Vn (22V)
Time (Definite)
0.1-10 sec
1 sec
0.1-0.5Vn
0.15Vn (28.5V)
Mode
Inverse, Instant
Inverse
Time
Page 31 of 90
4.1.4
Rev. 0
: 25
Relay type
: CSQ-2M
Manufacturer
: DEIF
GPT
B. PT Data
PT Ratio =
6.6
3
0.11
KV (Incomer side from D/G)
3
6.6
3
0.11
KV (Bus side)
3
CLR
25
Function
Setting Range
Setting Value
, Phase Difference
5-20, Step=1
U, Voltage Difference
1-10%, Step=1%
5%
0-1sec, Step=0.1s
Not Used
0-1sec Or , Step=0.1sec
0.7 sec
Remarks
Because TR is Set
Off
: 25
Relay type
: FAS-113DG
Manufacturer
: DEIF
Function
Setting Range
Setting Value
25 ~ 500 ms
500ms
0.25 ~ 2.5 HZ
0.5 HZ
0.1 ~ 0.5 HZ
0.2 HZ
Remarks
2 ~ 12% of UBB
5% of UBB
20 ~ 200 ms
70 ms
Page 32 of 90
Rev. 0
B. TR data
Rating
: 1,600KVA, 6.6KV/0.44KV, %Z = 5.85%
FLC
: 140A(TR 1st) / 2,099.5A(TR 2nd)
Max. TR Through fault current : 2,393A
C. CT/PT Data
PT Ratio
CT Ratio
ZCT Ratio
Function
27
67G
200/1.5mA
No.1/2/3/4/5/6/7
REEFER TR
6.6 / 0.44kV
1,600kVA
50/51
200/5A
Setting Range
Setting Value
Remarks
0.02-1.0 Vn
0.1-10 sec
0.8 Vn
2 sec
1 ~ 18 In
2.8 In
0.05 ~ 10 sec
0.2 sec
0.2 ~ 2.4 In
Inv.Very Inv., Extremely Inv.
0.9 In
Very Inv
0.05 ~ 10tap
0.56 Tap
1 ~ 18 In
5.6 In
0.05 ~ 10 sec
0.2 sec
0.2 ~ 2.4 In
Inv.Very Inv., Extremely Inv.
0.05 ~ 10 Tap
Time
0.9 In
Very Inv
125% of IFLC(TR)
1.4 Tap
1 ~ 10mA
0.1 ~ 0.2V0
0.1 ~ 10 sec
45~ 75
1.0mA
0.2VO
0.2 sec
60
Page 33 of 90
Rev. 0
E. Calculation
Current =
Time
t=
13.5 Tap
(I/ I p )-1
I
Ip
560
180
= 3.11,
t=4
1.25 140
200
13.5 Tap
(I/ I p )-1
I
Ip
1,120 = 6.22,
180
t=4
2.2 (256.6+256.6)
200
Page 34 of 90
Rev. 0
87T
67G
200/1.5mA
No.1 / 2
6.6 / 0.44kV
3,900kVA
C. CT/PT Data
PT Ratio
CT Ratio
ZCT Ratio
6,000/5A
0.44KV SWBD
50/51
450/5A
TR Data
Rating
: 3,900KVA, 6.6/0.44KV, %Z = 6.11%
FLC
: 341.2A (TR 1st) / 5,117.4A (TR 2nd)
Max. TR Through fault current : 5,584A
Function
Setting Range
Setting Value
Remarks
1 ~ 10 mA
0.1 ~ 0.2 V0
0.1 ~ 10sec
45~ 75
1.0 mA
0.2VO
0.2 sec
60
Primary Current
Secondary Current
Inst. Ratio
0.2 ~ 1.2 In
0.2 ~ 1.2 In
500 ~ 1500%
0.75 In
0.85 In
1500%
Differential Ratio
Bias Ratio
2nd Harmonic Ratio
TR Angle
Zero Comp.
Time
20 ~ 50%
20 ~ 50%
10 ~ 30%
25%
20%
15%
Ddo
Disable
Below 50ms
Enable, Disable
Below 50ms
1 ~ 18 In
1.3 In
0.05 ~ 10 sec
0.2 sec
0.2 ~ 2.4 In
Inv. Very Inv., Extremely Inv
.
0.05 ~ 10 Tap
0.62 In
Very Inv
0.3 Tap
1 ~ 18In
2.5 In
0.05 ~ 10 sec
0.2 sec
0.2 ~ 2.4 In
Inv. Very Inv., Extremely Inv
.
0.05 ~ 10 Tap
0.95 In
Very Inv
0.4 Tap
Page 35 of 90
E.
Rev. 0
Calculation
Time
t=
13.5 Tap
(I/ I p )-1
I
Ip
585
279
= 2.54,
t=4
Current =
Current =
Time
t=
13.5 Tap
(I/ I p )-1
I
Ip
1,125 = 2.63,
427.5
t=4
1.5 5,584
450
Page 36 of 90
Rev. 0
C. CT/PT Data
PT Ratio
CT Ratio
ZCT Ratio
100A
50/5A
49
46
51LR
66
50
67G
200/1.5mA
M
355KW
No.1/2 MAIN L.O PUMP
Function
Setting Range
Setting Value
Remarks
0.1 ~ 1.2 In
0.5 ~ 180 sec
0.5 ~ 180 sec
0.1 ~ 10
0.76 In
6 sec
3.5 sec
3
0.1 ~ 0.5 In
0.1 ~ 10 sec
0.12 In
4 sec
Start Current
0.2 ~ 14.4 In
4.7 In
Start Time
Locked Rotor Current
Locked Rotor Time
1.0 ~ 60 sec
0.2 ~ 6.0 In
1.0 ~ 4.0 sec
1.5 sec
2.3 In
2 sec
0.2 ~18 In
8.5 In
0.2 sec
1 ~ 60 min
1~4
1 ~ 60 min
40 ~ 100 %
60 min
3
15 min
80 %
1 ~ 10 mA (Fixed)
0.1 ~ 0.2 V0
0.1 ~ 10.0 sec
45~ 75
1.0 mA
0.2VO
0.2 sec
60
Page 37 of 90
Rev. 0
E. Calculation
1. ANSI 49
Thermal current
1.0 x 36.6
= 0.752In .... Set thermal current = 0.76In
50
(Pick up primary current = 38A)
Thermal current =
2. ANSI 46
Current
0.15 x 37.6
= 0.112In Set current = 0.12In
50
(Pick up primary current = 6A)
Current =
3. ANSI 51LR
Start current
1.0 x 235A
= 4.7 . Set current = 4.7In
50
(Pick up primary current = 235A)
Start current =
4. ANSI 50
Current
1.6 x 1.2 x 235
= 9.024In Set current = 8.5In
50
(Pick up primary current = 425A)
(For coordination with power fuse)
Current =
Page 38 of 90
Rev. 0
Motor data
Applied motor
Rating
Volt rating
FLC
Starting current
Starting time
C. CT/PT Data
PT Ratio
CT Ratio
ZCT Ratio
350/5A
49
46
51LR
66
50
67G
= 419A
200/1.5mA
M
2,500kW
BOW THRUSTER MOTOR
Function
Setting Range
Setting Value
Remarks
0.1 ~ 1.2 In
0.5 ~ 180 sec
0.5 ~ 180 sec
0.1 ~ 10
0.8 In
1.6 sec
1.2 sec
3
100% of IFLC(Motor)
0.15 x IFLC(Motor)
0.1 ~ 0.5 In
0.12 In
Time
0.1 ~ 10 sec
4 sec
0.2 ~ 14.4 In
1.0 ~ 60 sec
0.2 ~ 6.0 In
1.0 ~ 4.0 sec
1.2 In
20 sec
1.6 In
2 sec
0.2 ~18 In
2.3 In
0.05 sec
200% of IFLC(Motor)
1 ~ 60 min
1~4
1 ~ 60 min
40 ~ 100 %
60 min
4
15 min
80 %
1 ~ 10 mA (Fixed)
0.1 ~ 0.2V0
0.1 ~ 10.0 sec
45~ 75
1.0 mA
0.2 VO
0.2 sec
60
Page 39 of 90
Rev. 0
E. Calculation
1. ANSI 49
Thermal current
1.0 279.3
= 0.798 In ... Set thermal current = 0.8 In
350
(Pick up primary current = 280A)
Thermal current =
2. ANSI 46
Current
0.15 279.3
= 0.12 In . Set current = 0.12 In
350
(Pick up primary current = 42A)
Current =
3. ANSI 51LR
Start current
1.0 419
= 1.197 In ... Set current = 1.2 In
350
(Pick up primary current = 420A)
Start current =
4. ANSI 50
Current
1.2 1.6 419
= 2.298 In .. Set current = 2.3 In
350
(Pick up primary current = 805A)
Current =
Page 40 of 90
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-1
P-DG-2
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
FUNCTION
* NOMINAL RATIO VALUES
0200. NOMINAL RATED - Current
0201.
- Voltage
0202.
- Active Power
0203.
- Frequency
0204. CT Feeder -primary side
0205. PT Feeder -primary side
0206.
-secondary side
0207. PT BUS1
-primary side
0208.
-secondary side
0209. PT BUS2
-primary side
0210.
-secondary side
0211. PT GND1
-primary side
0212.
-secondary side
0213. PT GND2
-primary side
0214.
-secondary side
0215. CT GND1
-primary side
0216.
-secondary side
0217. CT GND2
-primary side
0218.
-secondary side
0219. CT DIFF
-primary side
0220. Transformer winding ratio
0221. - Uaux nominal input
0222. - Shunt#1 nominal input
0223. - Shunt#2 nominal input
GEN.:
6.6kV
3,733.33KVA
PF=0.75
FLC=326.6A
SETTING RANGE
0 - 9999A
0 - 65000V
0 - 9999KW
50/60HZ
0 -9999A
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 9999A
0 - 9999A
0 - 9999A
0 - 9999A
0 - 9999A
0.01 - 9.99Wprim/Wsec
24Vdc - 230Vac
24Vdc - 230Vac
24Vdc - 230Vac
SET POINT
326.6A
6600V
2,800KW
60HZ
500A
6600V
110V
6600V
110V
NOT USED
NOT USED
6600V
190V
NOT USED
NOT USED
1
1
NOT USED
NOT USED
500A
1.0
110Vdc
110Vdc
110Vdc
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
CT :
500/5A
5P10/15VA
500/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)
0215/0216
EVENT
200/1.5mA fixed
in program.
1101/1102
(Undervolt. 1st)
27
ON / OFF / CB ON
0.0 - 99.9%
0.03 - 99.99SEC
0.0 - 99.9%
0.03 - 99.99SEC
0.0 - 99.9 %
0.0 - 99.9HZ
41 of 90
CB ON
90%
5 SEC
50%
1sec
30%
33HZ
stand-by DG
start and
blackout change
after build-up
1103/1104 :
(Undervoltage. 2nd)
VCB trip
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-1
P-DG-2
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
59
INCOMER
FROM D/G
GEN.:
6.6kV
3,733.33KVA
PF=0.75
FLC=326.6A
81
40
FUNCTION
SETTING RANGE
SET POINT
ON / OFF / RECLOSE
1 - 9999%
0.01 - 10
NORM. INVERSE/DEFINITE
ON
110%
0.1
NORM. INV.
1 - 9999%
0.01 - 999.99SEC
108%
5sec
ON / OFF / CB ON
100.0 - 199.9%
0.1 - 999.99SEC
CB ON
105%
5SEC
100.0 - 199.9%
0.1 - 999.99SEC
110%
3SEC
0.1 - 99.9%
0.1 - 999.99SEC
97.5%
5SEC
0.1 - 99.9%
0.1 - 999.9SEC
0.1 - 99.9%
90%
10SEC
65%
ON / OFF
0.0 - 9999%
0.03 - 99.99SEC
0.7 - 1.0 x RATED VOLTAGE
ON / OFF
2.5 - 300.0OHM
2.5 - 300.0OHM
0.1 - 10.0SEC
ON/OFF
2.5 - 300.0OHM
2.5 - 300.0OHM
0.1 - 10.0SEC
ON
50%
2 SEC
0.7 xRATED VOL
ON
23.8 OHM
2.4 OHM
5SEC
OFF
NOT USED
NOT USED
NOT USED
42 of 90
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
CT :
500/5A
5P10/15VA
500/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)
stand-by DG
start and parallel
running
2010/2011
(Underfreq. 2nd)
VCB trip
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-1
P-DG-2
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
50
INCOMER
FROM D/G
GEN.:
6.6kV
3,733.33KVA
PF=0.75
FLC=326.6A
51
FUNCTION
SETTING RANGE
SET POINT
1400. Instantaneous
1401. - 1.limit
1402. - delay time (definite)
1403. reserved
1404. - 2.limit
1405. - delay time (definite)
1406. reserved
1407. - rev. limit
1408. - delay time (definite)
1409. reserved
1410. - inrush blocking
ON / OFF / RECLOSE
2 - 2999.9%
30 - 9999ms
ON
250%
600ms
2.0 - 2999.9%
30 - 9999ms
250%
400ms
2.0 - 2999.9%
30 - 9999ms
250%
50ms
ON/OFF
ON
ON / OFF / RECLOSE
2.0 - 2999.9 %
0.03 - 10.00
8 CURVE SHAPES(IDMT)
NONE,DEF./TH,DEF.,CURVE D-F
2.0 - 2999.9%
0.1 - 999.9SEC
2.0 - 2999.9%
0.1 - 999.9SEC
2.9 - 2999.9%
0.1 - 999.9SEC
0 -99SEC
ON/OFF
10 -90%
ON
105%
0.36
VERY INV.
NONE
100%
3 SEC
NOT USED
NOT USED
NOT USED
NOT USED
0 SEC
OFF
NOT USED
43 of 90
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
CT :
500/5A
5P10/15VA
500/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)
1505/1506
Alarm only
before
preferential trip
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-1
P-DG-2
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
87
INCOMER
FROM D/G
SETTING RANGE
SET POINT
ON / OFF
1.0 - 99.9%
0.03 - 999.99SEC
NONE,DY1,DY5,DY7,DY11,YD1,
ON
20%
0.1SEC
NONE
0.1 - 9999.9SEC
ON/OFF
0.1 - 999.9%
ON/OFF
0.1SEC
ON
30%
OFF
32
ON/OFF
0.1 - 99.9%
0.1 - 99.9SEC
0.1 - 99.9%
0.1 - 99.9SEC
0.1 - 199.9%
0.1 - 99.9SEC
0.1 - 199.9%
0.1 - 99.9SEC
ON
10%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
46
ON/OFF/RECLOSE
0.0 -99.9%
0.01 - 99.99
NORM. INV. /DEFINITE
1.0 - 99.9%
0.0 - 99.9%
0 - 9999ms
0.0 - 99.9%
0 - 9999ms
ON/OFF
ON
10%
2.0
NORM. INV.
10%
NOT USED
NOT USED
NOT USED
NOT USED
OFF
47
ON/OFF
1.0 - 199.9%
0.01 - 99.99SEC
ON
20%
2 SEC
GEN.:
6.6kV
3,733.33KVA
PF=0.75
FLC=326.6A
FUNCTION
44 of 90
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
CT :
500/5A
5P10/15VA
500/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)
1131/1132
50% of power
Required to
motor a Gen.
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-1
P-DG-2
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
25/25A
INCOMER
FROM D/G
GEN.:
6.6kV
3,733.33KVA
PF=0.75
FLC=326.6A
FUNCTION
1000. SYNC. UNIT 1 activ by
1001. - MAX phase angle
1002. - MAX frequency diff.
1003. - MIN frequency
1004. - MAX frequency
1005. - MAX voltage diff.
1006. - MIN voltage
1007. - MAX voltage
1008. - freq.set.pulse time
1009. - freq.set.break time
1010. - speed push after 10s
1011. - volt.set.pulse time
1012. - volt.set.break time
1013. - freq. higher event
1014. - freq. lower event
1015. - volt. higher event
1016. - volt. lower event
1017. - preset analog output
1018. - activate preset by
1019. - closing direction
1020. - CB closing delay
1021. - life/dead cond. check
1022. - min voltage level
1023. - CB sync. ON event
1024. - abnormal bus 1 event
SETTING RANGE
EVENT NO.
0 - 30 deg
0 - 2000mHZ
70.0 - 100.0%
100.0 - 130.0%
0.1 - 30%
70.0 - 100.0%
100.0 - 130.0%
0.1 - 999.9SEC
0.1 - 999.9SEC
0 - 9999ms
0.1 - 999.9SEC
0.1 - 999.9SEC
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
0.0 -99.9%
0 - 9999(EVENT NUMBER)
UP/DOWN/BOTH
0 -1000ms
ON/OFF
0.0 - 99.9%
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
45 of 90
SET POINT
800
7deg
250mHZ
94%
106%
5%
95%
105%
100SEC
2SEC
500ms
10SEC
2SEC
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
CT :
500/5A
5P10/15VA
500/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)
50%
BOTH
100ms
ON
10%
1021/1022
with External
Black out signal
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-1
P-DG-2
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
SETTING RANGE
SET POINT
ON
1.0mA
0.2SEC
MEAS. IGND1
ON/OFF
0 - 9999mA
0.1 - 999SEC
MEAS. IGND1/MEAS. IGND2/
MEAS.IGND1&2
IGND2/MEAS. IG1&2
0 - 360deg
ON/OFF
95I
ON/OFF
0.1 - 99.9%
1 - 99%
30 - 9999ms
0.03 - 99.99SEC
1 - 2999%
ON
0%
15%
100ms
1SEC
955%
64
ON/OFF/RECLOSE
0.1 - 999.9%
0.1 - 999.9SEC
ON
30%
10SEC
0.1 - 999.9%
0.1 - 999.9SEC
30%
12SEC
GEN.:
6.6kV
3,733.33KVA
PF=0.75
FLC=326.6A
FUNCTION
46 of 90
20%
60deg
OFF
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
CT :
500/5A
5P10/15VA
500/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)
1701/1702 :
Bus tie VCB trip
1704/1705 :
Own VCB trip
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-1
P-AG-2
P-AG-3
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
FUNCTION
* NOMINAL RATIO VALUES
0200. NOMINAL RATED - Current
0201.
- Voltage
0202.
- Active Power
0203.
- Frequency
0204. CT Feeder -primary side
0205. PT Feeder -primary side
0206.
-secondary side
0207. PT BUS1
-primary side
0208.
-secondary side
0209. PT BUS2
-primary side
0210.
-secondary side
0211. PT GND1
-primary side
0212.
-secondary side
0213. PT GND2
-primary side
0214.
-secondary side
0215. CT GND1
-primary side
0216.
-secondary side
0217. CT GND2
-primary side
0218.
-secondary side
0219. CT DIFF
-primary side
0220. Transformer winding ratio
0221. - Uaux nominal input
0222. - Shunt#1 nominal input
0223. - Shunt#2 nominal input
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
SETTING RANGE
0 - 9999A
0 - 65000V
0 - 9999KW
50/60HZ
0 -9999A
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 9999A
0 - 9999A
0 - 9999A
0 - 9999A
0 - 9999A
0.01 - 9.99Wprim/Wsec
24Vdc - 230Vac
24Vdc - 230Vac
24Vdc - 230Vac
SET POINT
256.6A
6600V
2,200KW
60HZ
400A
6600V
110V
6600V
110V
NOT USED
NOT USED
6600V
190V
NOT USED
NOT USED
1
1
NOT USED
NOT USED
400A
1.0
110Vdc
110Vdc
110Vdc
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
CT :
400/5A
5P10/15VA
400/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)
0215/0216
EVENT
200/1.5mA fixed
in program.
1101/1102
(Undervolt. 1st)
27
ON / OFF / CB ON
0.0 - 99.9%
0.03 - 99.99SEC
0.0 - 99.9%
0.03 - 99.99SEC
0.0 - 99.9 %
0.0 - 99.9HZ
47 of 90
CB ON
90%
5 SEC
50%
1sec
30%
33HZ
stand-by DG
start and
blackout change
after build-up
1103/1104 :
(Undervoltage. 2nd)
VCB trip
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-1
P-AG-2
P-AG-3
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
59
INCOMER
FROM D/G
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
81
40
FUNCTION
SETTING RANGE
SET POINT
ON / OFF / RECLOSE
1 - 9999%
0.01 - 10
NORM. INVERSE/DEFINITE
ON
110%
0.1
NORM. INV.
1 - 9999%
0.01 - 999.99SEC
108%
5sec
ON / OFF / CB ON
100.0 - 199.9%
0.1 - 999.99SEC
CB ON
105%
5SEC
100.0 - 199.9%
0.1 - 999.99SEC
110%
3SEC
0.1 - 99.9%
0.1 - 999.99SEC
97.5%
5SEC
0.1 - 99.9%
0.1 - 999.9SEC
0.1 - 99.9%
90%
10SEC
65%
ON / OFF
0.0 - 9999%
0.03 - 99.99SEC
0.7 - 1.0 x RATED VOLTAGE
ON / OFF
2.5 - 300.0OHM
2.5 - 300.0OHM
0.1 - 10.0SEC
ON/OFF
2.5 - 300.0OHM
2.5 - 300.0OHM
0.1 - 10.0SEC
ON
50%
2 SEC
0.7 xRATED VOL
ON
24.2 OHM
2.4 OHM
5SEC
OFF
NOT USED
NOT USED
NOT USED
48 of 90
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
CT :
400/5A
5P10/15VA
400/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)
stand-by DG
start and parallel
running
2010/2011
(Underfreq. 2nd)
VCB trip
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-1
P-AG-2
P-AG-3
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
50
INCOMER
FROM D/G
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
51
FUNCTION
SETTING RANGE
SET POINT
1400. Instantaneous
1401. - 1.limit
1402. - delay time (definite)
1403. reserved
1404. - 2.limit
1405. - delay time (definite)
1406. reserved
1407. - rev. limit
1408. - delay time (definite)
1409. reserved
1410. - inrush blocking
ON / OFF / RECLOSE
2 - 2999.9%
30 - 9999ms
ON
250%
600ms
2.0 - 2999.9%
30 - 9999ms
250%
400ms
2.0 - 2999.9%
30 - 9999ms
250%
50ms
ON/OFF
ON
ON / OFF / RECLOSE
2.0 - 2999.9 %
0.03 - 10.00
8 CURVE SHAPES(IDMT)
NONE,DEF./TH,DEF.,CURVE D-F
2.0 - 2999.9%
0.1 - 999.9SEC
2.0 - 2999.9%
0.1 - 999.9SEC
2.9 - 2999.9%
0.1 - 999.9SEC
0 -99SEC
ON/OFF
10 -90%
ON
105%
0.36
VERY INV.
NONE
100%
3 SEC
NOT USED
NOT USED
NOT USED
NOT USED
0 SEC
OFF
NOT USED
49 of 90
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
CT :
400/5A
5P10/15VA
400/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)
1505/1506
Alarm only
before
preferential trip
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-1
P-DG-2
P-DG-3
P-DG-4
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
87
INCOMER
FROM D/G
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
FUNCTION
SETTING RANGE
SET POINT
ON / OFF
1.0 - 99.9%
0.03 - 999.99SEC
NONE,DY1,DY5,DY7,DY11,YD1,
ON
20%
0.1SEC
NONE
0.1 - 9999.9SEC
ON/OFF
0.1 - 999.9%
ON/OFF
0.1SEC
ON
30%
OFF
32
ON/OFF
0.1 - 99.9%
0.1 - 99.9SEC
0.1 - 99.9%
0.1 - 99.9SEC
0.1 - 199.9%
0.1 - 99.9SEC
0.1 - 199.9%
0.1 - 99.9SEC
ON
10%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
46
ON/OFF/RECLOSE
0.0 -99.9%
0.01 - 99.99
NORM. INV. /DEFINITE
1.0 - 99.9%
0.0 - 99.9%
0 - 9999ms
0.0 - 99.9%
0 - 9999ms
ON/OFF
ON
10%
2.0
NORM. INV.
10%
NOT USED
NOT USED
NOT USED
NOT USED
OFF
47
ON/OFF
1.0 - 199.9%
0.01 - 99.99SEC
ON
20%
2 SEC
50 of 90
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
CT :
400/5A
5P10/15VA
400/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)
1131/1132
50% of power
Required to
motor a Gen.
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-1
P-AG-2
P-AG-3
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
25/25A
INCOMER
FROM D/G
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
FUNCTION
1000. SYNC. UNIT 1 activ by
1001. - MAX phase angle
1002. - MAX frequency diff.
1003. - MIN frequency
1004. - MAX frequency
1005. - MAX voltage diff.
1006. - MIN voltage
1007. - MAX voltage
1008. - freq.set.pulse time
1009. - freq.set.break time
1010. - speed push after 10s
1011. - volt.set.pulse time
1012. - volt.set.break time
1013. - freq. higher event
1014. - freq. lower event
1015. - volt. higher event
1016. - volt. lower event
1017. - preset analog output
1018. - activate preset by
1019. - closing direction
1020. - CB closing delay
1021. - life/dead cond. check
1022. - min voltage level
1023. - CB sync. ON event
1024. - abnormal bus 1 event
SETTING RANGE
EVENT NO.
0 - 30 deg
0 - 2000mHZ
70.0 - 100.0%
100.0 - 130.0%
0.1 - 30%
70.0 - 100.0%
100.0 - 130.0%
0.1 - 999.9SEC
0.1 - 999.9SEC
0 - 9999ms
0.1 - 999.9SEC
0.1 - 999.9SEC
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
0.0 -99.9%
0 - 9999(EVENT NUMBER)
UP/DOWN/BOTH
0 -1000ms
ON/OFF
0.0 - 99.9%
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
51 of 90
SET POINT
800
7deg
250mHZ
94%
106%
5%
95%
105%
100SEC
2SEC
500ms
10SEC
2SEC
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
CT :
400/5A
5P10/15VA
400/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)
50%
BOTH
100ms
ON
10%
1021/1022
with External
Black out signal
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-1
P-AG-2
P-AG-3
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
SETTING RANGE
SET POINT
ON
1.0mA
0.2SEC
MEAS. IGND1
ON/OFF
0 - 9999mA
0.1 - 999SEC
MEAS. IGND1/MEAS. IGND2/
MEAS.IGND1&2
IGND2/MEAS. IG1&2
0 - 360deg
ON/OFF
95I
ON/OFF
0.1 - 99.9%
1 - 99%
30 - 9999ms
0.03 - 99.99SEC
1 - 2999%
ON
0%
15%
100ms
1SEC
924%
64
ON/OFF/RECLOSE
0.1 - 999.9%
0.1 - 999.9SEC
ON
30%
10SEC
0.1 - 999.9%
0.1 - 999.9SEC
30%
12SEC
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
FUNCTION
52 of 90
20%
60deg
OFF
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
CT :
400/5A
5P10/15VA
400/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)
1701/1702 :
Bus tie VCB trip
1704/1705 :
Own VCB trip
PANEL/
FEEDER NO
REV. 0
RELAY
TYPE
ANSI
CODE
HYUNDAI/
HIMAP-FI
27M
FUNCTION
SETTING RANGE
SET POINT
VOLTAGE
0.5 - 1.0Vn
0.8Vn (88V)
TIME (DEFINITE)
0.1 - 10SEC
2SEC
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
REMARKS
GPT :
6 .6
0 . 11
0 . 19
KV
3
1.0CL/3P, 100/200VA
(BUS SIDE)
27R
64
VOLTAGE
0.2 - 0.5Vn
0.2Vn (22V)
TIME (DEFINITE)
0.1 - 10SEC
1SEC
VOLTAGE
0.1 - 0.5Vn
0.15Vn (28.5V)
MODE
INVERSE, INSTANT
INVERSE
TIME
53 of 90
PANEL/
FEEDER NO
REV. 0
RELAY
TYPE
ANSI
CODE
DEIF/
CSQ-2M
25
FUNCTION
, PHASE DIFFERENCE
u, VOLTAGE DIFFERENCE
Td, SYNC. RELAY DELAY
TR, LENGTH OF SYNC. PULSE
TB, DEAD BUS OFFSET VOLTAGE
SETTING RANGE
5-20, STEP=1
1-10%, STEP=1%
0-1SEC, STEP=0.1S
0-1SEC OR , STEP=0.1S
SET POINT
7
5%
NOT USED
0.7 SEC
OFF
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
REMARKS
PT :
6 .6
0 .11
KV
1.0CL, 100VA
(INCOMER SIDE
FROM D/G)
6 .6
0 .11
KV
1.0CL/3P, 100/200VA
(BUS SIDE)
DEIF/
FAS-113DG
25
25 ~ 500 ms
2.5 ~ 2.5 HZ
0.1 ~ 0.5 HZ
2 ~ 12% OF UBB
20 ~ 200 ms
54 of 90
500ms
0.5 HZ
0.2 HZ
5% OF UBB
70 ms
PANEL/
FEEDER NO
RELAY
TYPE
ANSI
CODE
P-RTR1-1
P-RTR2-1
P-RTR3-1
P-RTR4-1
P-RTR5-1
P-RTR6-1
P-RTR7-1
HYUNDAI/
HIMAP-FI
27
REV. 0
FUNCTION
VOLTAGE
TIME (DEFINITE)
SETTING RANGE
0.02 - 1.0Vn
0.1 - 10SEC
SET POINT
SET VALUE
(PRIM. CT)
MEASUR.
TRANSFORMER
GPT :
0.8Vn
2SEC
6 .6
0 . 11
REMARKS
0 . 19
KV
3
1.0CL/3P, 100/200VA
(BUS SIDE)
50
CURRENT
TIME
1 ~ 18In
0.05 ~ 10 SEC
2.8 In
0.2 SEC
560A
CT :
200/5A, 5P10/15VA
1. In = 5A
2. NOTE 1
ZCT :
200/1,5mA
51
CURRENT
MODE
TIME
0.2 ~ 2.4 In
INV.VERY INV., EXTREMELY INV.
0.05 ~ 10TAP
0.9 In
VERY INV
0.56 TAP
50
CURRENT
TIME
1 ~ 18In
0.05 ~ 10 SEC
5.6 In
0.2 SEC
51
CURRENT
MODE
TIME
0.2 ~ 2.4 In
INV.VERY INV., EXTREMELY INV.
0.05 ~ 10TAP
0.9 In
VERY INV
1.4 TAP
67G
CURRENT
VOLTAGE
TIME
ANGLE
1 ~ 10mA
0.1 ~ 0.2VO
0.1 ~ 10SEC
45~ 75
1.0mA
0.2VO
0.2 SEC
60
180A
1,120A
1. In = 5A
2. NOTE 2
180A
NOTE
1. IN CASE OF ONE(1) GENERATOR RUNNING
2. NORMAL OPERATING CONDITION
55 of 90
REV. 0
PANEL/
FEEDER NO
RELAY
TYPE
ANSI
CODE
P-MTR1-1
P-MTR2-1
HYUNDAI/
HIMAP-T
50
No.1/2
STEP-DOWN TR
(6.6/0.44KV)
3,800KVA
%Z = 6.11%
FUNCTION
CURRENT
TIME
SETTING RANGE
1 ~ 18In
0.05 ~ 10 SEC
SET POINT
1.3 In
0.2 SEC
SET VALUE
(PRIM. CT)
585A
MEASUR.
TRANSFORMER
GPT :
6 .6
0 . 11
0 . 19
KV
3
REMARKS
1. In = 5A
2. NOTE 1
1.0CL/3P, 100/200VA
(BUS SIDE)
51
CURRENT
MODE
TIME
0.2 ~ 2.4 In
INV.VERY INV., EXTREMELY INV.
0.05 ~ 10TAP
0.62 In
VERY INV
0.3 TAP
50
CURRENT
TIME
1 ~ 18In
0.05 ~ 10 SEC
2.5 In
0.2 SEC
1,125A
CT :
450/5A (1'st), 5P10/15VA
6,000/5A (2'nd), 5P20/40VA
51
CURRENT
MODE
TIME
0.2 ~ 2.4 In
INV.VERY INV., EXTREMELY INV.
0.05 ~ 10TAP
0.95 In
VERY INV
0.4 TAP
427.5A
ZCT :
200/1,5mA
67G
CURRENT
VOLTAGE
TIME
ANGLE
1 ~ 10mA
0.1 ~ 0.2VO
0.1 ~ 10SEC
45~ 75
1.0mA
0.2VO
0.2 SEC
60
87T
PRIMARY CURRENT
SECONDARY CURRENT
INST. RATIO
DIFFERENTIAL RATIO
BIAS RATIO
2ND HARMONIC RATIO
TR ANGLE
ZERO COMP.
TIME
0.2 ~ 1.2In
0.2 ~ 1.2In
500 ~ 1500%
20 ~ 50%
20 ~ 50%
10 ~ 30%
0.75 In
0.85 In
1500%
25%
20%
15%
Ddo
DISABLE
BELOW 50mS
ENABLE, DISABLE
BELOW 50mS
279A
1. In = 5A
2. NOTE 2
NOTE
1. IN CASE OF ONE(1) GENERATOR RUNNING
2. NORMAL OPERATING CONDITION
56 of 90
PANEL/
FEEDER NO
RELAY
TYPE
P-L01-1
P-L02-1
HYUNDAI/
HIMAP-M
ANSI
CODE
49
MOTOR FEEDER
No.1/2
MAIN L.O PUMP
MOTOR :
6.6KV
355KW
FLC = 37.6A
46
51LR
REV. 0
FUNCTION
SETTING RANGE
SET VALUE
(PRIM. CT)
THERMAL CURRENT
COLD LIMIT
HOT LIMIT
c/h
0.1 ~ 1.2In
0.5 ~ 180SEC
0.5 ~ 180SEC
0.1 ~ 10
0.76 In
6 SEC
3.5 SEC
3
38A
CURRENT
TIME
0.1 ~ 0.5In
0.1 ~ 10SEC
0.12 In
4 SEC
6A
START CURRENT
START TIME
LOCKED ROTOR CURRENT
LOCKED ROTOR TIME
0.2 ~ 14.4In
1.0 ~ 60SEC
0.2 ~ 6.0In
1.0 ~ 4.0SEC
4.7 In
1.5 SEC
2.3 In
2 SEC
235A
425A
50
CURRENT
TIME
0.2 ~18In
BELOW 0.2SEC
8.5 In
0.2 SEC
66
ALLOW TIME
NUMBER OF START
LIMIT TIME
THERMAL LIMIT (d)
1 ~ 60MIN
1~4
1 ~ 60MIN
40 ~ 100%
60 MIN
3
15 MIN
80 %
67G
CURRENT
VOLTAGE
TIME
ANGLE
1 ~ 10mA (FIXED)
0.1 ~ 0.2VO
0.1 ~ 10.0SEC
45~ 75
1.0mA
0.2VO
0.2 SEC
60
PF
SET POINT
MEASUR.
TRANSFORMER
GPT :
6 .6
0 . 11
REMARKS
0 . 19
KV
3
1.0CL/3P, 100/200VA
(BUS SIDE)
CT :
50/5A (PRI.), 5P10/15VA
115A
ZCT :
200/1,5mA
100A
57 of 90
PANEL/
FEEDER NO
RELAY
TYPE
P-BT-1
HYUNDAI/
HIMAP-M
ANSI
CODE
49
MOTOR FEEDER
BOW THRUSTER
MOTOR :
6.6KV
2,500KW
FLC = 279.3A
46
51LR
REV. 0
FUNCTION
SETTING RANGE
SET POINT
SET VALUE
(PRIM. CT)
THERMAL CURRENT
COLD LIMIT
HOT LIMIT
c/h
0.1 ~ 1.2In
0.5 ~ 180SEC
0.5 ~ 180SEC
0.1 ~ 10
0.8 In
1.6 SEC
1.2 SEC
3
280A
CURRENT
TIME
0.1 ~ 0.5In
0.1 ~ 10SEC
0.12 In
4 SEC
42A
START CURRENT
START TIME
LOCKED ROTOR CURRENT
LOCKED ROTOR TIME
0.2 ~ 14.4In
1.0 ~ 60SEC
0.2 ~ 6.0In
1.0 ~ 4.0SEC
1.2 In
20 SEC
1.6 In
2 SEC
420A
805A
50
CURRENT
TIME
0.2 ~18 In
BELOW 0.2SEC
2.3 In
0.05 SEC
66
ALLOW TIME
NUMBER OF START
LIMIT TIME
THERMAL LIMIT (d)
1 ~ 60MIN
1~4
1 ~ 60MIN
40 ~ 100%
60 MIN
4
15 MIN
80 %
67G
CURRENT
VOLTAGE
TIME
ANGLE
1 ~ 10mA (FIXED)
0.1 ~ 0.2V0
0.1 ~ 10.0SEC
45~ 75
1.0mA
0.2VO
0.2 SEC
60
58 of 90
MEASUR.
TRANSFORMER
GPT :
6 .6
0 . 11
REMARKS
0 . 19
KV
3
1.0CL/3P, 100/200VA
(BUS SIDE)
CT :
350/5A (PRI.), 5P10/15VA
560A
ZCT :
200/1,5mA
ITEM
INCOMER
FROM D/G
(P-DG-1)
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-1
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
GENERAL
PARAMETER
GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A
POWER
MANAGEMENT
FUNCTION
SETTING RANGE
SET POINT
1
1
0900. P.M.
- switch by event
0901.
- characteristic
0902. START - check limits
0903.
- 1.load limit
0904.
- delay
0905.
- 2.load limit
0906.
- delay
0907.
- low frequency
0908.
- delay
0909.
- high current
0910.
- delay
0911. STOP - with priority
0912.
- block by event ;
0913.
- remaining load
0914.
- remaining current
0915.
- delay
0
ON->OFF
SINGLE
90%
15SEC
0
0
0HZ
0SEC
100%
5SEC
LOW
0
70%
0
300SEC
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
505
896
830
801
0
0
0
MANUAL 2
59 of 90
ITEM
INCOMER
FROM D/G
(1G-001)
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-1
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
LOAD
SHARING
SETTING RANGE
SET POINT
0
ON -> OFF
5SEC
4SEC
3%
0945.
- switch by event
0946.
- characteristic
0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point
0
ON -> OFF
60HZ
60HZ
30SEC
80SEC
0.5%
VOLTAGE
REGULATOR
0958.
0959.
0
OFF -> ON
POWER
FACTOR
CONTROLLER
BIG
CONSUMER
REQUEST
(BCR)
0970.
- switch by event
0977. ASYM. - switch by event
0
0
838
0
0
0
GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A
FREQUENCY
CONTROLLER
FUNCTION
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
0
OFF->ON
80
NONE
20%
90%
600SEC
0
0
66HZ
54HZ
- switch by event
- characteristic
60 of 90
ITEM
INCOMER
FROM D/G
(P-DG-1)
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-1
HYUNDAI/
HIMAP-BCG
GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A
REV. 0
ANSI
CODE
FUNCTION
SETTING RANGE
SET POINT
BLACKOUT
533
DOUBLE
20%
1SEC
NEXT
OFF
0
DIESEL
CONTROL
ON
1800RPM
20%
85%
120%
NONE
OFF
0
10%
110%
90%
0
0
10SEC
DIESEL
STARTING
PHASE
0
0
1
NO
NO
10SEC
10SEC
40SEC
85%
2SEC
60SEC
NO
61 of 90
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
ITEM
INCOMER
FROM D/G
(P-DG-1)
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-1
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
DIESEL
STOPPING
PHASE
GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A
FUNCTION
SETTING RANGE
SET POINT
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
YES
120SEC
836
10%
20SEC
60SEC
NO
30SEC
5SEC
0670/0671
- PT1
PREFERENTIA
L TRIP LIMITS
BUS
ABNORMAL
100%
5SEC
105%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
57HZ
5SEC
110%
1SEC
0682.ABNORMAL BUS-overfreq.
0683.
- underfrequency
0684.
- overvoltage
0685.
- undervoltage
0686.
- delay
0687. PREF.TRIP -check limits
63HZ
57HZ
105%
95%
5SEC
OFF
62 of 90
0672/0673
- PT2
0678/0679
PT1- 95% 5SEC
PT2- 95% 10SEC
0680/0681
HIGH ACTIVE
POWER:
ST-BY gen. start
and
parallel running
ITEM
INCOMER
FROM D/G
(P-DG-1)
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-1
HYUNDAI/
HIMAP-BCG
GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A
REV. 0
ANSI
CODE
ADDITIONAL
LIMITS
FUNCTION
SETTING RANGE
0280. OVERSPEED
- limit
0281.
- delay
0282. OVERVOLTAGE - limit
0283.
- delay
0284. OVERCURRENT - limit
0285.
- delay
0286. OVERLOAD (OWN) - limit
0287.
- delay
0288. OVERLOAD (NET) - limit
0289.
- delay
0290. PF CAP. LOW - limit
0291.
- delay
0292. PF IND. LOW - limit
0293.
- delay
0294. REVERSE POWER - limit
0295.
- delay
0296. REACT.POWER IND.- limit
0297.
- delay c
0298. NETLOAD excl.OWN- limit %
0299.
- delay
SET POINT
0
0
95%
0.1SEC
0
0
75%
0.1SEC
75%
0.1SEC
0
0
0
0
0
0
0
0
90%
0.1SEC
63 of 90
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
0282:
Voltage Build-up
for synchronizing
ITEM
INCOMER
FROM D/G
(P-DG-2)
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-2
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
GENERAL
PARAMETER
GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A
POWER
MANAGEMENT
FUNCTION
SETTING RANGE
SET POINT
2
2
0900. P.M.
- switch by event
0901.
- characteristic
0902. START - check limits
0903.
- 1.load limit
0904.
- delay
0905.
- 2.load limit
0906.
- delay
0907.
- low frequency
0908.
- delay
0909.
- high current
0910.
- delay
0911. STOP - with priority
0912.
- block by event ;
0913.
- remaining load
0914.
- remaining current
0915.
- delay
0
ON->OFF
SINGLE
90%
15SEC
0
0
0HZ
0SEC
100%
5SEC
LOW
0
70%
0
300SEC
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
505
896
830
801
0
0
0
MANUAL 2
64 of 90
ITEM
INCOMER
FROM D/G
(P-DG-2)
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-2
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
LOAD
SHARING
SETTING RANGE
SET POINT
0
ON -> OFF
5SEC
4SEC
3%
0945.
- switch by event
0946.
- characteristic
0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point
0
ON -> OFF
60HZ
60HZ
30SEC
80SEC
0.5%
VOLTAGE
REGULATOR
0958.
0959.
0
OFF -> ON
POWER
FACTOR
CONTROLLER
BIG
CONSUMER
REQUEST
(BCR)
0970.
- switch by event
0977. ASYM. - switch by event
0
0
0
0
0
0
GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A
FREQUENCY
CONTROLLER
FUNCTION
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
0
OFF->ON
80
NONE
20%
90%
600SEC
0
0
66HZ
54HZ
- switch by event
- characteristic
65 of 90
ITEM
INCOMER
FROM D/G
(P-DG-2)
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-2
HYUNDAI/
HIMAP-BCG
GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A
REV. 0
ANSI
CODE
FUNCTION
SETTING RANGE
SET POINT
BLACKOUT
533
DOUBLE
20%
1SEC
NEXT
OFF
0
DIESEL
CONTROL
ON
1800RPM
20%
85%
120%
NONE
OFF
0
10%
110%
90%
0
0
10SEC
DIESEL
STARTING
PHASE
0
0
1
NO
NO
10SEC
10SEC
40SEC
85%
2SEC
60SEC
NO
66 of 90
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
ITEM
INCOMER
FROM D/G
(P-DG-2)
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-2
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
DIESEL
STOPPING
PHASE
GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.5A
FUNCTION
SETTING RANGE
SET POINT
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
YES
120SEC
836
10%
20SEC
60SEC
NO
30SEC
5SEC
0670/0671
- PT1
PREFERENTIA
L TRIP LIMITS
BUS
ABNORMAL
100%
5SEC
105%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
57HZ
5SEC
110%
1SEC
0682.ABNORMAL BUS-overfreq.
0683.
- underfrequency
0684.
- overvoltage
0685.
- undervoltage
0686.
- delay
0687. PREF.TRIP -check limits
63HZ
57HZ
105%
95%
5SEC
OFF
67 of 90
0672/0673
- PT2
0678/0679
PT1- 95% 5SEC
PT2- 95% 10SEC
0680/0681
HIGH ACTIVE
POWER:
ST-BY gen. start
and
parallel running
ITEM
INCOMER
FROM D/G
(P-DG-2)
PANEL/
FEEDER NO
RELAY
TYPE
P-DG-2
HYUNDAI/
HIMAP-BCG
GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A
REV. 0
ANSI
CODE
ADDITIONAL
LIMITS
FUNCTION
SETTING RANGE
0280. OVERSPEED
- limit
0281.
- delay
0282. OVERVOLTAGE - limit
0283.
- delay
0284. OVERCURRENT - limit
0285.
- delay
0286. OVERLOAD (OWN) - limit
0287.
- delay
0288. OVERLOAD (NET) - limit
0289.
- delay
0290. PF CAP. LOW - limit
0291.
- delay
0292. PF IND. LOW - limit
0293.
- delay
0294. REVERSE POWER - limit
0295.
- delay
0296. REACT.POWER IND.- limit
0297.
- delay c
0298. NETLOAD excl.OWN- limit %
0299.
- delay
SET POINT
0
0
95%
0.1SEC
0
0
75%
0.1SEC
75%
0.1SEC
0
0
0
0
0
0
0
0
90%
0.1SEC
68 of 90
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
0282:
Voltage Build-up
for synchronizing
ITEM
INCOMER
FROM D/G
(P-AG-1)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-1
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
GENERAL
PARAMETER
GEN.:
6.6kV
2,933.33kVA
PF=0.75
FLC=256.6A
POWER
MANAGEMENT
FUNCTION
SETTING RANGE
SET POINT
3
3
0900. P.M.
- switch by event
0901.
- characteristic
0902. START - check limits
0903.
- 1.load limit
0904.
- delay
0905.
- 2.load limit
0906.
- delay
0907.
- low frequency
0908.
- delay
0909.
- high current
0910.
- delay
0911. STOP - with priority
0912.
- block by event ;
0913.
- remaining load
0914.
- remaining current
0915.
- delay
0
ON->OFF
SINGLE
90%
15SEC
0
0
0HZ
0SEC
100%
5SEC
LOW
0
70%
0
300SEC
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
505
896
830
801
0
0
0
MANUAL 2
69 of 90
ITEM
INCOMER
FROM D/G
(P-AG-1)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-1
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
LOAD
SHARING
SETTING RANGE
SET POINT
0
ON -> OFF
5SEC
4SEC
3%
0945.
- switch by event
0946.
- characteristic
0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point
0
ON -> OFF
60HZ
60HZ
30SEC
80SEC
0.5%
VOLTAGE
REGULATOR
0958.
0959.
0
OFF -> ON
POWER
FACTOR
CONTROLLER
BIG
CONSUMER
REQUEST
(BCR)
0970.
- switch by event
0977. ASYM. - switch by event
0
0
0
0
0
0
GEN.:
6.6kV
2,933.33kVA
PF=0.75
FLC=256.6A
FREQUENCY
CONTROLLER
FUNCTION
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
0
OFF->ON
80
NONE
20%
90%
600SEC
0
0
66HZ
54HZ
- switch by event
- characteristic
70 of 90
ITEM
INCOMER
FROM D/G
(P-AG-1)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-1
HYUNDAI/
HIMAP-BCG
GEN.:
6.6kV
2,933.33kVA
PF=0.75
FLC=256.6A
REV. 0
ANSI
CODE
FUNCTION
SETTING RANGE
SET POINT
BLACKOUT
533
DOUBLE
20%
1SEC
NEXT
OFF
0
DIESEL
CONTROL
ON
1800RPM
20%
85%
120%
NONE
OFF
0
10%
110%
90%
0
0
10SEC
DIESEL
STARTING
PHASE
0
0
1
NO
NO
10SEC
10SEC
40SEC
85%
2SEC
60SEC
NO
71 of 90
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
ITEM
INCOMER
FROM D/G
(P-AG-1)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-1
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
DIESEL
STOPPING
PHASE
GEN.:
6.6kV
2,933.33kVA
PF=0.75
FLC=256.6A
FUNCTION
SETTING RANGE
SET POINT
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
YES
120SEC
836
10%
20SEC
60SEC
NO
30SEC
5SEC
0670/0671
- PT1
PREFERENTIA
L TRIP LIMITS
BUS
ABNORMAL
100%
5SEC
105%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
57HZ
5SEC
110%
1SEC
0682.ABNORMAL BUS-overfreq.
0683.
- underfrequency
0684.
- overvoltage
0685.
- undervoltage
0686.
- delay
0687. PREF.TRIP -check limits
63HZ
57HZ
105%
95%
5SEC
OFF
72 of 90
0672/0673
- PT2
0678/0679
PT1- 95% 5SEC
PT2- 95% 10SEC
0680/0681
HIGH ACTIVE
POWER:
ST-BY gen. start
and
parallel running
ITEM
INCOMER
FROM D/G
(P-AG-1)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-1
HYUNDAI/
HIMAP-BCG
GEN.:
6.6kV
2,933.33kVA
PF=0.75
FLC=256.6A
REV. 0
ANSI
CODE
ADDITIONAL
LIMITS
FUNCTION
SETTING RANGE
0280. OVERSPEED
- limit
0281.
- delay
0282. OVERVOLTAGE - limit
0283.
- delay
0284. OVERCURRENT - limit
0285.
- delay
0286. OVERLOAD (OWN) - limit
0287.
- delay
0288. OVERLOAD (NET) - limit
0289.
- delay
0290. PF CAP. LOW - limit
0291.
- delay
0292. PF IND. LOW - limit
0293.
- delay
0294. REVERSE POWER - limit
0295.
- delay
0296. REACT.POWER IND.- limit
0297.
- delay c
0298. NETLOAD excl.OWN- limit %
0299.
- delay
SET POINT
0
0
95%
0.1SEC
0
0
75%
0.1SEC
75%
0.1SEC
0
0
0
0
0
0
0
0
90%
0.1SEC
73 of 90
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
0282:
Voltage Build-up
for synchronizing
ITEM
INCOMER
FROM D/G
(P-AG-2)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-2
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
GENERAL
PARAMETER
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
POWER
MANAGEMENT
FUNCTION
SETTING RANGE
SET POINT
4
4
0900. P.M.
- switch by event
0901.
- characteristic
0902. START - check limits
0903.
- 1.load limit
0904.
- delay
0905.
- 2.load limit
0906.
- delay
0907.
- low frequency
0908.
- delay
0909.
- high current
0910.
- delay
0911. STOP - with priority
0912.
- block by event ;
0913.
- remaining load
0914.
- remaining current
0915.
- delay
0
ON->OFF
SINGLE
90%
15SEC
0
0
0HZ
0SEC
100%
5SEC
LOW
0
70%
0
300SEC
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
505
896
830
801
0
0
0
MANUAL 2
74 of 90
ITEM
INCOMER
FROM D/G
(P-AG-2)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-2
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
LOAD
SHARING
SETTING RANGE
SET POINT
0
ON -> OFF
5SEC
4SEC
3%
0945.
- switch by event
0946.
- characteristic
0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point
0
ON -> OFF
60HZ
60HZ
30SEC
80SEC
0.5%
VOLTAGE
REGULATOR
0958.
0959.
0
OFF -> ON
POWER
FACTOR
CONTROLLER
BIG
CONSUMER
REQUEST
(BCR)
0970.
- switch by event
0977. ASYM. - switch by event
0
0
0
0
0
0
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
FREQUENCY
CONTROLLER
FUNCTION
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
0
OFF->ON
80
NONE
20%
90%
600SEC
0
0
66HZ
54HZ
- switch by event
- characteristic
75 of 90
ITEM
INCOMER
FROM D/G
(P-AG-2)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-2
HYUNDAI/
HIMAP-BCG
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
REV. 0
ANSI
CODE
FUNCTION
SETTING RANGE
SET POINT
BLACKOUT
533
DOUBLE
20%
1SEC
NEXT
OFF
0
DIESEL
CONTROL
ON
1800RPM
20%
85%
120%
NONE
OFF
0
10%
110%
90%
0
0
10SEC
DIESEL
STARTING
PHASE
0
0
1
NO
NO
10SEC
10SEC
40SEC
85%
2SEC
60SEC
NO
76 of 90
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
ITEM
INCOMER
FROM D/G
(P-AG-2)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-2
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
DIESEL
STOPPING
PHASE
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
FUNCTION
SETTING RANGE
SET POINT
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
YES
120SEC
836
10%
20SEC
60SEC
NO
30SEC
5SEC
0670/0671
- PT1
PREFERENTIA
L TRIP LIMITS
BUS
ABNORMAL
100%
5SEC
105%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
57HZ
5SEC
110%
1SEC
0682.ABNORMAL BUS-overfreq.
0683.
- underfrequency
0684.
- overvoltage
0685.
- undervoltage
0686.
- delay
0687. PREF.TRIP -check limits
63HZ
57HZ
105%
95%
5SEC
OFF
77 of 90
0672/0673
- PT2
0678/0679
PT1- 95% 5SEC
PT2- 95% 10SEC
0680/0681
HIGH ACTIVE
POWER:
ST-BY gen. start
and
parallel running
ITEM
INCOMER
FROM D/G
(P-AG-2)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-2
HYUNDAI/
HIMAP-BCG
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
REV. 0
ANSI
CODE
ADDITIONAL
LIMITS
FUNCTION
SETTING RANGE
0280. OVERSPEED
- limit
0281.
- delay
0282. OVERVOLTAGE - limit
0283.
- delay
0284. OVERCURRENT - limit
0285.
- delay
0286. OVERLOAD (OWN) - limit
0287.
- delay
0288. OVERLOAD (NET) - limit
0289.
- delay
0290. PF CAP. LOW - limit
0291.
- delay
0292. PF IND. LOW - limit
0293.
- delay
0294. REVERSE POWER - limit
0295.
- delay
0296. REACT.POWER IND.- limit
0297.
- delay c
0298. NETLOAD excl.OWN- limit %
0299.
- delay
SET POINT
0
0
95%
0.1SEC
0
0
75%
0.1SEC
75%
0.1SEC
0
0
0
0
0
0
0
0
90%
0.1SEC
78 of 90
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
0282:
Voltage Build-up
for synchronizing
ITEM
INCOMER
FROM D/G
(P-AG-3)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-3
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
GENERAL
PARAMETER
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
POWER
MANAGEMENT
FUNCTION
SETTING RANGE
SET POINT
5
5
0900. P.M.
- switch by event
0901.
- characteristic
0902. START - check limits
0903.
- 1.load limit
0904.
- delay
0905.
- 2.load limit
0906.
- delay
0907.
- low frequency
0908.
- delay
0909.
- high current
0910.
- delay
0911. STOP - with priority
0912.
- block by event ;
0913.
- remaining load
0914.
- remaining current
0915.
- delay
0
ON->OFF
SINGLE
90%
15SEC
0
0
0HZ
0SEC
100%
5SEC
LOW
0
70%
0
300SEC
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
505
896
830
801
0
0
0
MANUAL 2
79 of 90
ITEM
INCOMER
FROM D/G
(P-AG-3)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-3
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
LOAD
SHARING
SETTING RANGE
SET POINT
0
ON -> OFF
5SEC
4SEC
3%
0945.
- switch by event
0946.
- characteristic
0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point
0
ON -> OFF
60HZ
60HZ
30SEC
80SEC
0.5%
VOLTAGE
REGULATOR
0958.
0959.
0
OFF -> ON
POWER
FACTOR
CONTROLLER
BIG
CONSUMER
REQUEST
(BCR)
0970.
- switch by event
0977. ASYM. - switch by event
0
0
0
0
0
0
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
FREQUENCY
CONTROLLER
FUNCTION
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
0
OFF->ON
80
NONE
20%
90%
600SEC
0
0
66HZ
54HZ
- switch by event
- characteristic
80 of 90
REV. 0
81 of 90
ITEM
INCOMER
FROM D/G
(P-AG-3)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-3
HYUNDAI/
HIMAP-BCG
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
REV. 0
ANSI
CODE
FUNCTION
SETTING RANGE
SET POINT
BLACKOUT
533
DOUBLE
20%
1SEC
NEXT
OFF
0
DIESEL
CONTROL
ON
1800RPM
20%
85%
120%
NONE
OFF
0
10%
110%
90%
0
0
10SEC
DIESEL
STARTING
PHASE
0
0
1
NO
NO
10SEC
10SEC
40SEC
85%
2SEC
60SEC
NO
82 of 90
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
REV. 0
83 of 90
ITEM
INCOMER
FROM D/G
(P-AG-3)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-3
HYUNDAI/
HIMAP-BCG
REV. 0
ANSI
CODE
DIESEL
STOPPING
PHASE
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
FUNCTION
SETTING RANGE
SET POINT
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
YES
120SEC
836
10%
20SEC
60SEC
NO
30SEC
5SEC
0670/0671
- PT1
PREFERENTIA
L TRIP LIMITS
BUS
ABNORMAL
100%
5SEC
105%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
57HZ
5SEC
110%
1SEC
0682.ABNORMAL BUS-overfreq.
0683.
- underfrequency
0684.
- overvoltage
0685.
- undervoltage
0686.
- delay
0687. PREF.TRIP -check limits
63HZ
57HZ
105%
95%
5SEC
OFF
84 of 90
0672/0673
- PT2
0678/0679
PT1- 95% 5SEC
PT2- 95% 10SEC
0680/0681
HIGH ACTIVE
POWER:
ST-BY gen. start
and
parallel running
ITEM
INCOMER
FROM D/G
(P-AG-3)
PANEL/
FEEDER NO
RELAY
TYPE
P-AG-3
HYUNDAI/
HIMAP-BCG
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A
REV. 0
ANSI
CODE
ADDITIONAL
LIMITS
FUNCTION
SETTING RANGE
SET POINT
0
0
95%
0.1SEC
0
0
75%
0.1SEC
75%
0.1SEC
0
0
0
0
0
0
0
0
90%
0.1SEC
0280. OVERSPEED
- limit
0281.
- delay
0282. OVERVOLTAGE - limit
0283.
- delay
0284. OVERCURRENT - limit
0285.
- delay
0286. OVERLOAD (OWN) - limit
0287.
- delay
0288. OVERLOAD (NET) - limit
0289.
- delay
0290. PF CAP. LOW - limit
0291.
- delay
0292. PF IND. LOW - limit
0293.
- delay
0294. REVERSE POWER - limit
0295.
- delay
0296. REACT.POWER IND.- limit
0297.
- delay c
0298. NETLOAD excl.OWN- limit %
0299.
- delay
85 of 90
SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER
REMARKS
0282:
Voltage Build-up
for synchronizing