1646 - Relay Coordination Table

Download as pdf or txt
Download as pdf or txt
You are on page 1of 92

SHIP No.

H1646-9 / S253-6 (8,200 TEU CONTAINER VESSEL)

PROTECTIVE RELAY & PMS SETTING REPORT

09. Jun. 2005

Issued for approval

S.B. KANG

Y.K. MIN

M.J. KIM

REV.

DATE

DESCRIPTION

BY

CHECKED

APPROVED

MESSRS.

HYUNDAI HEAVY INDUSTRIES CO., LTD.


SHIP No. H1646-9 / S253-6
(8,200 TEU CONTAINER VESSEL)

CLASS

BV

DRAWING NO.

PROTECTIVE RELAY & PMS SETTING REPORT

PROJECT NO.

HYUNDAI HEAVY INDUSTRIES CO., LTD.


ELECTRO & ELECTRIC SYSTEMS

1,CHEON HA-DONG, DONG-KU, ULSAN, KOREA


FAX. (052) 230-8120 (DESIGN), 230-8300(A/S)
TEX. (052) 230-8141~6 (DESIGN), 230-8345~6(A/S)

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

TABLE OF CONTENTS
PAGE
1. APPLICATION .......

2. LIST OF PROTECTIVE RELAY AND CT/PT ......

3. CALCULATION CRITERIA ..

4. SETTING CALCULATION OF PROTECTIVE RELAY .......... 19

5. RELAY SETTING CHECK LIST .. 41

6. PMS SETTING CHECK LIST . 59

7. PROTECTIVE RELAY COORDINATION CURVE . 84

Page 2 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

1. APPLICATION
1.1

The protective relay setting report, which apply selective system to clear only faulted feeder, is
applied to 6.6KV system of ship no. H1646-9 / S253-6 (8,200 TEU container vessel) for following
purpose.
1) The objective of protective scheme in power system is to minimize hazardous to personnel and
equipment while causing the least disruption of power service.
2) Coordination studies are required to select or verify the clearing characteristics of devices such as
fuses, circuit breakers and relays used in the protective scheme.
3) The studies are also needed to determine the protective device setting that will provide selective
fault isolation.
4) In a properly coordinated system, a fault results in interruption of only the minimum amount of
equipment necessary to isolate the faulted portion of the system. The power supply to load in the
reminder of the system is maintained.
5) The goal is to achieve an optimum balance between protective equipment and selective fault
isolation that is consistent with the operation requirements of the overall power system.

1.2

Coordination time margin


Coordination time margin tm of the protective relay has been calculated as follows.
tm = 2 ter top + tcb + to + tx
Where,
ter : Relay timing error (Taken as 3%)
top : Maximum operating times of relay nearer to the fault (Taken as 1,000ms)
tcb : Circuit breaker interrupting time(s) (Taken as 75ms)

Thus,

to

: Relay overshoot time(s) (Taken as 30ms)

tx

: Safety margin (Taken as 35ms)

tm = ( 2

3
) 1,000 + 75 + 30 + 35
100

= 200ms

Page 3 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

2. LIST OF PROTECTIVE RELAY AND CT/PT


No

SWBD EQUIPMENT

CT / PT

APPLIED FEEDER
RATIO

6.6KV
MAIN
SWB
D

6.6KV
MAIN
SWBD
-1/2

INCOMER FROM D/G(MG)


(P-DG-1, -2)

500/5A

5P10/15VA

500/5A (GEN. SIDE)

5P10/30VA

200/1.5mA (ZCT)
6.6
0.11
/
KV
3
3
(INCOMER SIDE)

D/G : 6.6KV, 3,733.33KVA


PF = 0.75, IFLC=326.6A
6.6
3

INCOMER FROM D/G(AG)


(P-AG-1, -2, -3)

TR : 1,600KVA, 6.6/0.44KV
IFLC = 140A, %Z = 5.85%

NO.1/2 STEP-DOWN TR
FEEDER
(P-MTR1-1, P-MTR2-1)
TR : 3,900KVA, 6.6/0.44KV
IFLC = 341.2A, %Z = 6.11%

NO. 1/2 MAIN L.O PUMP


(P-LO1-1, P-LO2-1)
MOTOR :
DIRECT ON LINE
6.6kV, 355kW
IFLC = 37.6A
BOW THRUSTER MOTOR
(P-BT-1)
MOTOR :
6.6KV, 2,500KW,
AUTO TR STARTING (50%)
IFLC= 279.3A, Ts = 20 sec
IST = 419A (50%)

0.11
0.19
/
KV
3
3
(BUS SIDE)

1.0CL/3P,
100/200VA
5P10/15VA

400/5A (GEN. SIDE)

5P10/30VA

200/1.5mA (ZCT)
6.6
0.11
/
KV
3
3
(INCOMER SIDE)
6.6
3

NO. 1/2/3/4/5/6/7
REEFER TR FEEDER
(P-RTR1~7-1)

0.11
0.19
/
KV
3
3
(BUS SIDE)

6.6
0.11
/
KV
3
3
(INCOMER SIDE)
6.6
3

0.11
0.19
/
KV
3
3
(BUS SIDE)

200/5A

27, 59, 81, 40,


50/51, 87, 32, HYUNDAI/
46, 47, 25/25A, HIMAP-BCG
1.0CL/100VA
67G, 95i, 64
1.0CL/3P,
100/200VA

0.11
0.19
/
KV
3
3
(BUS SIDE)

1.0CL/3P
100/200VA

6,000/5A (TR 2nd)

5P20/40VA

200/1.5mA (ZCT)
0.11
0.19
/
KV
3
3
(BUS SIDE)

50/5A

0.11
0.19
/
/
KV
3
3
(BUS SIDE)

350/5A

0.11
0.19
/
KV
3
3
(BUS SIDE)

HYUNDAI/
HIMAP-T

49, 46,
51LR, 50,
66, 67G,
PF : 100A

HYUNDAI/
HIMAP-M

49, 46,
51LR, 50,
66, 67G

HYUNDAI/
HIMAP-M

5P10/15VA

1.0CL/3P
100/200VA
5P10/15VA

200/1.5mA (ZCT)
6.6
3

50/51, 67G,
87T
1.0CL/3P
100/200VA

200/1.5mA (ZCT)
6.6
3

HYUNDAI/
HIMAP-FI

5P10/15VA

5P10/15VA

27, 50/51,
67G

1.0CL/3P
100/200VA

450/5A

6.6
3

25

DEIF/
CSQ-2M
&
DEIF /
FAS-113DG

1.0CL/100VA

200/1.5mA (ZCT)
6.6
3

MAKER/
MODEL

27, 59, 81, 40,


50/51, 87, 32, HYUNDAI/
46, 47, 25/25A, HIMAP-BCG
1.0CL/100VA
67G, 95i, 64

400/5A

D/G : 6.6KV, 2,933.33KVA


PF = 0.75, IFLC=256.6A

INCOMER FROM D/G &


BUS TIE

APPLIED
PROTECTIVE
ACC. CL / VA
RELAY

1.0CL/3P
100/200VA

Page 4 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

3. CALCULATION CRITERIA
3.1

6.6KV MAIN SWBD


3.1.1 INCOMER FROM D/G
The digital relay type HYUNDAI/HIMAP-BCG device provides protection for the incomer
breaker which supplies the 6.6KV main SWBD with power from D/G. This includes
overcurrent relay (50/51), Directional ground relay (67G), Generator differential protection
relay (87), Reverse power relay (32), Negative sequence relay (46), Phase sequence voltage
relay (47), Under/over voltage relay (27/59), Frequency relay (81), Loss of excitation relay (40),
Synchronizing check relay (25/25A), Inrush blocking relay (95i) & Overvoltage ground
relay(64).
1) 50/51 : Overcurrent relay
a) 51 : Time overcurrent relay
Current Limit shall be set at 105% of generators full load current.
Time multiplier shall be set for the relay to activate 5sec at 200% of current
limit setting and 1.7min at 110% of generator full load current.
Curve shape shall be of IEC very inverse type.
b) 50 : Instantaneous overcurrent relay
Instantaneous overcurrent relay shall be used to trip generator circuit breaker,
bus-tie circuit breaker. And it is also used as directional overcurrent relay(67S)
monitoring only the phase fault between generator and circuit breaker, resulting
from fault current contribution by another generator(s) running in parallel.
Generator circuit breaker trip (1 Limit)
Current limit shall be set at 250% of generator full load current.
Time shall be set for the relay to activate 600 ms at the current limit setting.
Curve shape shall be of definite type.
Bus-tie circuit breaker trip (2 Limit)
Current limit shall be set at 250% of generator full load current.
Time shall be set for the relay to activate 400 ms at the current limit setting.
Curve shape shall be of definite type.
Directional protection (Rev. Limit)
Current limit shall be set at 250% of generator full load current.
Time shall be set for the relay to activate 50 ms at Rev. limit setting.
Curve shape shall be of definite type.

Page 5 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

2) 67G : Directional ground overcurrent relay.

Page 6 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

a) Earth fault current:


Eg

Ig =

Rg +

1
R

+ j3wc

Where,
Ig

: Earth fault current of neutral unearthed system

Eg

: System voltage (Phase Neutral)

Rg

: Earth fault resistance

: Equivalent resistance, which transfer the current limit resistance(r) of the GPT
open delta winding to the neutral earth resistance of the GPT primary.
1
n2r (n : Voltage ratio of GPT)
9
: Capacitive reactance between phase and earth
R=

b) Current limit resistance of the GPT open delta winding, r


190V
190V
)
3
r

0.4 200VA

Where,
200VA : The rated burden of GPT
0.4 : Factor for fault duration
r 24 ohm,
Select, r = 25 ohm

c) Equivalent resistance, which transfer the current limit resistance(r) of the GPT open delta
winding to the neutral earth resistance of the GPT primary.
R=
=

1
9

n2r

6.6
/
3

0.19 2
) x 25
3
9

= 10,056 ohm

d) Minimum earth fault current


The minimum earth fault current from only one(1) GPT neutral neglecting capacitive current,
but considered earth fault resistance (Rg = 10,000 ohm) :
When the earth fault occurs,
6,600
3

IgR =
10,000 +

1
1
10,056

= 0.19A

Page 7 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

e) Minimum earth fault current injected to protection relay


1.5
200

0.19A

1,000 = 1.4mA

Therefore, The limit setting of the directional overcurrent relay shall be selected to
1.0mA.
Definite delay time setting shall be selected to 0.2sec.
The phase angle setting shall be 60and the volt low limit setting shall be 20%.
3) 46 : Reverse phase relay
The limit value of the negative sequence current shall be set to trip at the less value
than the permissible negative sequence current (I2) and the permissible level of the
integrated quantity I2t (=K), which should be supplied by the generators manufacturer.
K and I2 of generator are normally applied as follows when the information is not
provided by generators manufacturer.

Generator

I2

K = I2t

Diesel generator

10% IFLC

40

4) 32 : Reverse power relay


The reverse power relay shall be set as below to protect prime mover from generator
motoring.
- For Diesel generator
10% of the rated output of generator.
- For Turbo generator
2% of the rated output of generator.
5 seconds time delay shall be needed to prevent malfunction by power swing
capability to occur in an instant generator synchronizing or system hunting.
5) 87 : Differential protection relay
Since the differential protection relay shall be set not to trip on the faults outside the
differential protection zone and by current transformer mismatch. The current limit
setting of definite differential protection shall be selected to 20% of generator rated
current and the bias limit to 30%.

Page 8 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

6) 47 : Phase sequence voltage relay


If the phase sequence turns to reversal rotating or one phase is missing, the relay
becomes active. The voltage limit setting and delay time setting shall be selected to
trip at 2sec to trip instantaneously if voltage is greater than 20% of the generator rated
voltage.

7) 27 : Undervoltage relay
The undervoltage limit 1 shall be used for stand-by D/G start and blackout change
after voltage build up.
It shall be set at 90% of rated voltage and time delay set at 5 sec.
The undervoltage limit 2 for circuit breaker trip shall be set at 50% of rated voltage
and time delay set at 1.0sec in order to give all other relays an opportunity to operate.
8) 59 : Overvoltage relay
The overvoltage limit 1 for circuit breaker trip shall be used to provide a back-up for
overvoltage.
It shall be set at 110% of rated voltage and the time multiplier shall be set to trip
after 5.0 sec at 130% of rated voltage with IEC normal inverse curve.
The overvoltage limit 2 shall be used to function for stand-by D/G start and blackout
change after voltage build up at overvoltage caused by overspeed, excitation system
malfunction etc.
It shall be set to trip after 5.0 sec at 108% of rated voltage.
9) 25 : Synchronizing check relay
Synchronizing check relay shall be set as follows
y Max. phase angle

: 7deg

y Max. frequency diff.

: 250mHz

y Frequency Set. break time : 2sec


y Frequency set pulse time

: 100sec

y Speed adj. push after 10sec : 500mS


y Voltage set. break time

: 2sec

y Voltage set. pulse time

: 10sec

Page 9 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

10) 81 : Frequency relay


Over speed capability of generator under no excitation condition is 1.2times the rated
speed for 120sec.
The overfrequency 1 step limit for stand-by D/G start and blackout after voltage built
up shall be set at 105% of rated frequency, 5sec.
The overfrequency 2 step limit for CB trip shall be set at 110% of rated voltage, 3 sec
to protect overfrequency (over speed), which is caused by governor system failure and
causes additional mechanical stress to the generator and prime mover system and may
cause excessive heating.
The underfrequency 1 step limit for stand by D/G start and parallel running after
voltage built up shall be set at 97.5% of rated frequency, 5sec.
The underfrequency 2 step limit for CB trip shall be set at 90% of rated frequency,
10sec to protect underfrequency, which is caused by a results of more demand than
power that the connected generator can meet, and cause overheating to the generator
due to high excitation.
However, the over/under frequency setting value shall be smaller/larger than
over/under frequency capability of generator and under frequency setting value shall
be smaller than the engine droop, normally 4%.
11) 40 : Loss of field relay
Loss of field relay detects loss of excitation by using an impedance element on
wye(Y) connected generator. When the impedance falls within the impedance circle for
the delay time specified, a trip will occur.

1
of the synchronous reactance(Xd) of the generator
2
X' d
Xd
) and the circle offset shall be set to the generator transient reactance
.
(that is,
2
2
Time delay setting shall be 5 sec, which is the delayed time to be necessary to allow
Circle radius shall be set to

the use of normal field forcing during system faults.


Reactive power limit setting shall be 50% with 2 sec delay and minimum operating
voltage is 70% of the rated voltage.
12) 64 : Overvoltage ground relay

The overvoltage ground relay, which is used for detecting 6.6kV bus bar ground fault
and used to trip bus tie and generator circuit breaker, shall be set to 30% of relay rated
voltage, 10sec for bus tie circuit breaker and 12sec for generator circuit breaker.

Page 10 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

3.1.2 GPT PANEL

Digital relay type HYUNDAI/HIMAP-FI device is provided in GPT panel.


This includes undervoltage relay (27) and overvoltage ground relay(64).

1) 27 : Undervoltage relay

The setting of the undervoltage relay(27), which monitors the live voltage of busbar for closing permissive of distribution feeder CB and for abnormal trip of motor
feeder shall be selected to 80% of the rated voltage and the time setting selected to
2.0sec and shall be selected to 20% of the rated voltage and time setting selected to
1.0sec for dead bus checking.

2) 64 : Overvoltage ground relay

The overvoltage ground relay, which is used for detecting of 6.6KV ground fault and
used to give an Alarm signal to AMS, shall be set to 15% of relay rated voltage, 1.3sec
(min. setting) at 1.3 times the setting with inverse curve.

Page 11 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

3.1.3 INCOMER FROM D/G & BUS TIE


3. 1. 3.1 Synchronizing check relay (DEIF/CSQ-2M)

Synchronizing check relay DEIF/CSQ-2M device is provided for manual synchronizing


incomer from D/G and 6.6KV main bus.
1) 25 : Synchronizing check relay

Synchronizing check relay shall be set as follows,


y : Phase difference = 7
y u : Voltage difference = 5%
y Td

: Sync. Relay delay = Not used ( Because TR is set.)

y TR : Length of sync, pulse = 0.7S


y TB

: Dead bus offset voltage = OFF

3. 1. 3. 2 Synchronizing check relay (DEIF/FAS-113DG)

Synchronizing check relay DEIF/FAS-113DG device is provided for auto synchronizing


Bus Tie from 6.6KV main bus-A and 6.6KV main bus-B.

1) 25 : Synchronizing check relay

Synchronizing check relay shall be set as follows,


y TN

: Control pulse length = 500ms

y XP

: Proportional band = 0.5 HZ

y Fset

: Slip frequency = 0.2 HZ

y U max

: Acceptable voltage differences = 5% of U BB

y TBC

: Breaker closure time = 70ms

Page 12 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

3.1.4 REEFER TR FEEDER

Digital relay type HYUNDAI/HIMAP-FI device is provided for the reefer TR feeder
protection. This includes undervoltage relay (27), overcurrent relay (50/51), directional ground
relay (67G).
1) 27 : Undervoltage relay

Undervoltage setting, which is used to trip switchboard feeder, shall be selected to


80% of the rated voltage and the time setting selected to 2.0sec.
2) 50/51 : Overcurrent relay

a) 51 : Time overcurrent relay


In case of one(1) generator running ;

The time overcurrent setting shall be selected to trip at 125% of transformer


rated current and provided with coordination margin of 0.2sec with
overcurrent relay of the one(1) smallest generator.
Normal operating condition ;

The time overcurrent setting shall be selected to trip at 125% of transformer


rated current. Time setting shall be selected to provide a coordination margin
of 0.2sec with overcurrent relay of the two(2) smallest generators under the
condition of the two(2) generators and above are in parallel operation.
b) 50 : Instantaneous overcurrent relay
In case of one(1) generator running ;

The instantaneous overcurrent setting shall be selected to trip at 220% (that is,
slightly less than instantaneous setting of incomer/generator feeder) of a rated
current of one(1) smallest generator and provided with coordination margin of
at least 0.2sec with bus-tie circuit breaker.
Normal operating condition ;

The instantaneous overcurrent setting shall be selected to trip at 220% of a


rated current of two(2) smallest generators and provided with coordination
margin of at least 0.2 sec with bus-tie circuit breaker.
3) 67G : Directional ground relay

For 6.6KV system earth fault current, refer to 67G of Para 3.1.1 (Incomer from
D/G of 6.6KV MAIN SWBD).
Current setting is selected to 1.0mA. Time shall be set at 0.2sec.
The phase angle setting shall be 60and the voltage setting shall be 20%.

Page 13 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

3.1.5 STEP-DOWN TR FEEDER

For the step-down TR protection, digital relay type HYUNDAI/HIMAP-T device is provided
This includes overcurrent relay(50/51), directional ground relay(67G) & TR differential
relay(87T).
1) 50/51 : Overcurrent relay

a) 51 : Time overcurrent relay


In case of one(1) generator running ;

The time overcurrent setting shall be selected to trip at 85% of a rated current
of one(1) biggest rated generator and provided with coordination margin of
0.2sec with overcurrent relay of the one(1) biggest generator.
Normal operating condition ;

The time overcurrent setting shall be selected to trip at 125% of transformer


rated current.
Time setting shall be selected to provide a coordination margin of 0.2 sec
with overcurrent relay of the two(2) smallest generators under the condition
of the two(2) generators and above are in parallel operation.
b) 50 : Instantaneous overcurrent relay
In case of one(1) generator running ;

The instantaneous overcurrent setting shall be selected to trip at 220% (that is,
slightly less than instantaneous setting of incomer/generator feeder) of a rated
current of one(1) smallest rated generator and provided with coordination
margin of at 0.2 sec with bus-tie circuit breaker.
Normal operating condition ;

The instantaneous overcurrent setting shall be selected to trip at 220% of a


rated current of two(2) smallest generators and provided with coordination
margin of at least 0.2 sec with bus-tie circuit breaker.
2) 67G : Directional ground relay

For 6.6KV system earth fault current, refer to 67G of Para 3.1.1 (incomer from
D/G of 6.6KV MAIN SWBD). Current setting is selected to 1.0mA. Time shall be
set at 0.2sec.
This phase angle setting shall be 60and voltage setting shall be 20%.

Page 14 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

3) 87 : TR differential relay

a)

Inst. ratio :
Inst. ratio setting, which is initiated regardless of the magnitude of the stabilizing
current if this setting value be exceeded, should be set to the larger value if 150%
and above of transformer inrush current and transformer through fault current.

b)

Differential ratio :
Differential ratio setting shall be chosen by the amount of differential current that
might be seen during normal operation condition.
Setting shall be selected to 25% as the relay protects no load tap changer
transformer.

c)

Bias ratio :
Bias ratio setting shall be selected to 20% as the differential ratio setting is 25%.

d)

2nd harmonic ratio :


2nd harmonic ratio : 15%

e)

TR angle : Ddo
Zero comp

: disable

Page 15 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

3.1.6 MOTOR FEEDER

Digital relay type HYUNDAI/HIMAP-M device is provided for motor feeder protection.
This includes thermal overload relay (49), locked rotor relay (51LR), Negative sequence relay
(46), Start inhibit relay for motor (66), Directional ground relay (67G) & Instantaneous
overcurrent (50).
Setting curve of 6.6KV BOW THRUSTER MOTOR feeder shall be selected to laid below
overcurrent protection curve of incomer (from D/G) overcurrent curve for tripping and lockout
of bus tie CB under the condition of the three(3) [= one(1) big Gen. + two(2) small Gen.]
generators parallel operation.
1) 49 : Overload relay

a) Thermal current :
Thermal current shall be set at 100% of motor full load current
b) Cold thermal limit at 6
Cold thermal limit at 6 shall be laid below the cold curve of the motor, which is
informed from motor manufacturer
c) Hot thermal limit at 6
Hot thermal limit at 6 shall be laid below the characteristic of hot curve to limit
the thermal image value, which is informed from motor manufacturer, and shall be
set not to trip at motor starting.
d) tc/th : Ratio of cooling time constant to thermal time constant.
Constant tc/th shall be set by the information of motor manufacturer, if the
information is not provided,

tc
= 3 is selected
th

2) 50 : Instantaneous overcurrent relay

Instantaneous overcurrent shall be set high enough not to trip on the first inrush
current at 100% voltage.
Current = 1.2 1.6 Starting current

Where,
1.6 = D.C Offset
1.2 = Safety factor
Page 16 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

3) 51LR : Locked rotor relay

a) Start current :
Start current shall be set equal to the actual starting current at rated voltage.
b) Start time :
Start time shall be set greater than the real starting time of the motor at rated
voltage for the direct on line starting and at reduced voltage for the auto TR starting.
c) Locked rotor current
Locked rotor current shall be set greater than motor rated current, but less than
motor starting current.
Therefore, locked rotor current shall be set at 300% of motor rated current for the
direct on line starting and at 200% of motor rated current for the auto TR starting
locked rotor current.
d) Locked rotor time
As the locked rotor time initiates after start time set, time shall be set at 2sec but
less than 80% of stall time on hot condition shown on manufacturers data sheet.
4) 46 : Negative sequence relay

Current setting shall be normally selected to 1.4 times the maximum permissible
continuous negative phase sequence current and time selected to 4sec to prevent
maloperation at motor starting.
Current = 1.4 Insc
Where,
Insc = The maximum permissive continuous negative sequence current
(5 15% IFLC)
Current = 1.4 10% IFLC = 14% IFLC,

Select 15% IFLC

5) 67G : Directional ground relay (67G)

For 6.6KV system earth fault current, refer to 67G of Para 3.1.1 (Incomer from
D/G of 6.6KV MAIN SWBD).
Current setting is selected to 1.0mA. Time shall be set at 0.2sec.
The phase angle setting shall be 60 and the voltage setting shall be 20%.

Page 17 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

6) 66 : Start inhibit relay for motor

All setting shall be selected by the information of motor manufacturer.


If the information is not provided, start inhibit relay shall be set as follows.
Allow time = 60min
Number of start = 3 (direct), 4 (auto TR)
Limit time = 15min
Thermal limit (d) = 80%
Selection of power fuse for motor protection on the vacuum combination contactor (VCS).
NO.

SWBD

FEEDER

RATING

POWER
FUSE

INTERSECT POINT
OF RELAY AND
FUSE

RATED BREAKING
CAPACITY
OF VCS

6.6KV
MAIN
SWBD-1/2

No. 1/2
MAIN L.O
PUMP

6.6KV
355KW
IFLC = 37.6A
IST =235A (DOL)

100A

Refer to
Protective Relay
coordination curve

3.2KA

6.6KV
MAIN
SWBD-1

BOW
THRUSTER
MOTOR

6.6KV
2,500KW
IFLC = 279.3A
IST =419A (50%)

250A2

Refer to
Protective Relay
coordination curve

3.2KA

The intersect point of relay and fuse curve shall be lower than the rated breaking capacity of VCS.

Page 18 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

4. SETTING CALCULATION OF PROTECTIVE RELAY


4.1 6.6KV MAIN SWBD-1/2
4.1.1 INCOMER FROM D/G (MG)
A.

B.

C.

D.
Address

Applied relay

: 27, 59, 81, 40, 50/51, 87, 32,


46, 47, 25/25A, 67G, 95i, 64
: HIMAP-BCG
: HYUNDAI

500/5A

Relay type
Manufacturer
D/G Data
Applied D/G
: P-DG-1/2
Rating
: 3,733.33KVA (2,800KW), PF : 0.75
Volt rating
: 6,600V
FLC
: 326.6A
Max. 3Ph Transient Contri. Fault Current : 2,599.8A
Steady State Fault Current : 979.8A
CT/PT Data
PT Ratio
: 6.6:3 / 0.11:3 KV (Incomer Side)
6.6:3 / 0.11:3 / 0.19:3 KV (Bus Side)
CT Ratio
: 500/5A
500/5A (Gen. Side)
ZCT Ratio
: 200/1.5mA
Relay setting table
Function

DG

200/1.5mA

27

59

81

40

50/51

87

32

46

47

67G

95i

64
500/5A

6.6kV MAIN SWBD No.1

Setting Range

Setting Value

Remarks

Nominal Ratio Value


0200

Nominal Rated Current

0 9999A

326.6A

0201

Nominal Rated Voltage

0 65000V

6600V

0202

Nominal Rated Active Power

0 9999KW

2,800KW

0203

Nominal Rated Frequency

50/60HZ

60HZ

0204

CT Feeder Primary Side

0 9999A

500A

0205

PT Feeder Primary Side

0 65000V

6600V

0206

PT Feeder Secondary Side

0 9999V

110V

0207

PT Bus1 Primary Side

0 65000V

6600V

0208

PT Bus1 Secondary Side

0 9999V

110V

0209

PT Bus2 Primary Side

0 65000V

Not Used

0210

PT Bus2 Secondary Side

0 9999V

Not Used

0211

PT Gnd1 Primary Side

0 65000V

6600V

0212

PT Gnd1 Secondary Side

0 9999V

190V

0213

PT Gnd2 Primary Side

0 65000V

Not Used

0214

PT Gnd2 Secondary Side

0 9999V

Not Used

0215

CT Gnd1 Primary Side

0 9999A

Fixed as 200/1.5mA

0216

CT Gnd1 Secondary Side

0 9999A

in Program.

0217

CT Gnd2 Primary Side

0 9999A

Not Used

0218

CT Gnd2 Secondary Side

0 9999A

Not Used

0219

CT Diff Primary Side

0 9999A

500A

0220

CT Diff Winding Ratio

0.01-9.99WPRIM/WSEC

1.0

0221

Uaux Nominal Input

24Vdc -230Vac

110Vdc

0222

Shunt #1 Nominal Input

24Vdc -230Vac

110Vdc

0223

Shunt #2 Nominal Input

24Vdc -230Vac

110Vdc

Page 19 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Address

Function

Rev. 0

Setting Range

Setting Value

Remarks

ANSI 27 Undervoltage Relay


1100
1101
1102

Undervoltage Relay
- Undervoltage 1.Limit
- Delay Time (Definite)

On / Off / CB On
0.0 ~ 99.9%
0.03 ~ 99.99sec

CB On
90%
5 sec

1103
1104
1105
1106

- Undervoltage 2. Limit
- Delay Time (Definite)
- Min. Start Voltage
- Min. Frequency

0.0 ~ 99.9%
0.03 ~ 99.99sec
0.0 ~ 99.9%
0.0 ~ 99.9HZ

50%
1 sec
30%
33HZ

Stand-by D/G start and


blackout change after
voltage build up
VCB trip

ANSI 59 Overvoltage Relay


1600
1601

Overvoltage Relay
- 1. Limit Value

On / Off / Reclose
1 ~ 999.9%

On
110%

1602
1603

- Time Multiplier (TMS)


- Curve Shape

0.01 ~ 10
Normal Inverse /
Definite

0.1
Normal Inverse

1604
1605
1606

- Reserved
- 2 Limit Value
- Delay Time (Definite)

1 ~ 999.9%
0.01 999.99sec

108%
5 sec

110% of Rated Voltage


VCB Trip : 5.0 sec at 130%
of Rated Voltage
Stand-by D/G start and
blackout change after
voltage built up

ANSI 81 Frequency Relay


2000
2001
2002
2003

Frequency Relay
Overfreq. 1. Step Limit
- Delay Time (Definite)
Reserved

On / Off / CB On
100.0 199.9%
0.1 999.9sec

CB On
105%
5 sec

2004
2005
2006

Overfreq. 2. Step Limit


- Delay Time (Definite)
Reserved

100.0 199.9%
0.1 999.9sec

110%
3 sec

VCB trip

2007
2008
2009

Underfreq. 1. Step Limit


- Delay Time (Definite)
Reserved

0.1 99.9%
0.1 999.9sec

97.5%
5 sec

Stand-by D/G start and


parallel running

2010
2011
2012

Underfreq. 2. Step Limit


- Delay Time (Definite)
Undervoltage Blocking

0.1 99.9 %
0.1 999.9sec
0.1 99.9%

90%
10 sec
65%

VCB trip

On / Off
0.0-9999%
0.03-99.99sec
0.7 ~ 1.0 Rated Volt.
On / Off
2.5 ~ 300.0 ohm
2.5 ~ 300.0 ohm
0.1 ~ 10.0sec
On / Off
2.5 ~ 300.0 ohm
2.5 ~ 300.0 ohm
0.1 ~ 10.0sec

On
50%
2 sec
0.7 Rated Volt
On
23.8 ohm
2.4 ohm
5 sec
Off
Not Used
Not Used
Not Used

Stand-by D/G start and


blackout change after
voltage built up

ANSI 40 Loss of Excitation Relay


1170
1171
1172
1173
1174
1175
1176
1177
1178
1179
1180
1181

Loss Of Excitation Relay


Reactive Power Limit
Delay Time (Definite)
Min. Voltage
Circle1
Circle 1 Radius
Circle 1 Off Set
Circle 1 Trip Delay
Circle 2
Circle 2 Diameter
Circle 2 Off Set
Circle 2 Trip Delay

1/2 Xd
1/2 Xd

Page 20 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Address

Function

Rev. 0

Setting Range

Setting Value

On / Off / Reclose
2.0 ~ 2999.9%
30 ~ 9999ms

On
250%
600ms

Remarks

ANSI 50 Instant. Overcurrent Relay


1400
1401
1402
1403

Instantaneous Overcurrent
- 1. Limit
- Delay Time (Definite)
Reserved

1404
1405
1406

- 2. Limit
- Delay Tiem (Definite)
Reserved

2.0 ~ 2999.9%
30 ~ 9999ms

250%
400ms

B/T Trip

1407
1408
1409

- Rev. Limit
- Delay Time (Definte)
Reserved

2.0 ~ 2999.9%
30 ~ 9999ms

250%
50ms

Used as ANSI 67S

1410

- Inrush Blocking

On / Off

On

On / Off / Reclose
2.0 ~ 2999.9%
0.03 ~ 10.00

On
105%
0.36

8 Curve Shapes(IDMT)
None, Def./Th, Def.,Curve
D-F

Very Inverse
None

Gen. CB Trip

ANSI 51 AC Time Overcurrent Relay


1500
1501
1502

Time Overcurrent Relay


- Limit
- Time Multiplier (TMS)

1503
1504

- Curve Shape
- Reset Characteristic

1505
1506

- 1. Limit
- Delay Time (Definite)

2.0 ~ 2999.9%
0.1 ~ 999.9sec

100%
3 sec

1507
1508
1509
1510
1511
1512
1513

- 2. Limit
- Delay Time (Definite)
- 3. Limit
- Delay Time (Definite)
- Reset Charact. (Th)
- Volt. Restrain (51VR)
- Voltage Low Limit

2.0 ~ 2999.9%
0.1 ~ 999.9sec
2.0 ~ 2999.9%
0.1 ~ 999.9sec
0 ~ 99sec
On / Off
10 ~ 90%

Not Used
Not Used
Not Used
Not Used
0 sec
Off
Not Used

105% IFLC (Gen)


5 sec at 200% Setting
(1.7min at 110% IFLC)
- VCB Trip

Alarm only before


Preferential Trip

ANSI 87 Differential Protective Relay


2100
2101
2102
2103

Diff. Protective Relay


- Diff. Limit
- Delay Time (Definite)
- Angle Compensation

2104
2105
2106
2107
2108
2109

Reserved
Reserved
- Delay CT-Saturation
- Inrush Blocking
- Bias Limit
- Zero Compensation

On / Off
1.0 ~ 99.9%
0.03~ 999.99sec
None, Dy1, Dy5, Dy7,
Dy11, Yd1

On
20%
0.1 sec
None

0.1 ~ 9999.9sec
On / Off
0.1 ~ 999.9%
On / Off

0.1 sec
On
30%
Off

Page 21 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Address

Function

Rev. 0

Setting Range

Setting Value

On / Off
0.1 ~ 99.9%
0.1 ~ 99.9sec
0.1 ~ 99.9%
0.1 ~ 99.9sec
0.1 ~ 199.9%
0.1 ~ 99.9sec
0.1 ~ 199.9%
0.1 ~ 99.9sec

On
10%
5 sec
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used

Remarks

ANSI 32 Reverse Power Relay


1130
1131
1132
1133
1134
1135
1136
1137
1138

Overload Relay
- 1. Limit Reverse Power
- Delay Time (Definite)
- 2. Limit Reverse Power
- Delay Time (Definite)
- 1. Limit Active Power
- Delay Time (Definite)
- 2. Limit Active Power
- Delay Time (Definite)

50% of Power Required to


Motor a Gen.

ANSI 46 Reverse Phase Relay (CT Line Monitoring)


1200
1201
1202
1203
1204
1205
1206
1207
1208
1209

Reverse Phase Relay


- Limit Value
- Time Multiplier (TMS)
- Curve Shape
- Min. Feeder Voltage
- 2. Limit
- Delay Time (Definite)
- 1. Limit.
- Delay Time (Definite)
- Volt. Restrain [51VR]

On / Off / Reclose
0.0 ~ 99.9%
0.01 ~ 99.99
Norm. Inverse / Definite
1.0 ~ 99.9%
0.0 ~ 99.9%
0 ~ 9999ms
0.0 ~ 99.9%
0 ~ 9999ms
On / Off

On
10%
2.0
Norm. Inverse
10%
Not Used
Not Used
Not Used
Not Used
Off

ANSI 47 Phase Sequence Voltage Relay (VT Line Monitoring)


1300
1301
1302

Phase Sequence Relay


- Limit Value
- Delay Time (Definite)

On / Off
1.0 ~ 199.9%
0.01 ~ 99.99sec

On
20%
2 sec

Event No.
0-30 Deg
0-2000mHZ
70.0-100.0%
100.0-130.0%
0.1-30%
70.0-100.0%
100.0-130.3%
0.1-999.9sec
0.1-999.9sec
0-9999ms
0.1-999.9sec
0.1-999.9sec
Event Reminder For
Output
Event Reminder For
Output
Event Reminder For
Output
Event Reminder For
Output

800
7 deg
250 mHZ
94%
106%
5%
95%
105%
100 sec
2 sec
500 ms
10 sec
2 sec

0.0-99.9%
0-9999(Event Number)
Up/Down/Both
0-1000ms

50%

ANSI 25/25A Synchronizing Relay


1000
1001
1002
1003
1004
1005
1006
1007
1008
1009
1010
1011
1012
1013

Sync. Unit 1 Active by


- Max Phase Angle
- Max Frequency Diff.
- Min Frequency
- Max Frequency
- Max Voltage Diff.
- Min Voltage
- Max Voltage
- Freq. Set. Pulse Time
- Freq. Set. Break Time
- Speed Push After 10s
- Volt. Set. Pulse Time
- Volt. Set. Break Time
- Freq. Higher Event

1014

- Freq. Lower Event

1015

- Volt. Higher Event

1016

- Volt. Lower Event

1017
1018
1019
1020

- Preset Analog Output


- Activate Preset By
- Closing Direction
- CB Closing Delay

Both
100ms

Page 22 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Address

Function

Rev. 0

Setting Range

Setting Value

On/Off
0.0-99.9%
Event Reminder for Output
Event Reminder for Output

On
10%

Remarks

ANSI 25/25A Synchronizing Relay


1021
1022
1023
1024

- Life/Dead Cond. Check


- Min Voltage Level
- CB Sync. On Event
- Abnormal Bus 1 Event

With External
Black Out Signal

ANSI 67GS/GD AC Direction Ground Overcurrent Relay


1810
1811
1812
1813

AC Direction (67GS)
- Limit Value (Igndx)
- Delay Time (Definite)
- Pick-Up Type (67GX)

On / Off
0 ~ 9999mA
0.1 ~ 999sec
Meas. Ignd1/Meas.
Ignd2/Meas. Ig1 & 2

On
1.0mA
0.2 sec
Meas. Ignd1

1814
1815
1816

- Volt. Low Limit (Vo)


- Phase Angle (+/-60)
- AC Direction (67GD)

0.1 ~ 999.9%
0 ~ 360
On/Off

20%
60
Off

ANSI 95i Inrush Blocking Relay


2300
2301
2302
2303
2304

Inrush Blocking Relay


Limit Of DC Portion
2. Harmonic Content
Te Extension Time
Tmax Blocking Time

On/Off
1.0 99.9%
1 99%
30 9999ms
0.03 99.99sec

On
0%
15%
100 ms
1 sec

2305

Imax Blocking Inrush

1 2999%

955%

Off

120% of max. Gen. thru.


Fault current

ANSI 64 Overvoltage Ground Relay


1700
1701
1702
1703

Ground Detector Relay


- Limit Value Ugnd1
- Delay Time (Definite)
Reserved

On / Off / Reclose
0.1-999.9%
0.1-999.9sec

On
30%
10 sec

Bus Tie VCB Trip


(57V)

1704
1705
1706

-Limit Value Ugnd2


-Delay Time (Definite)
Reserved

0.1-999.9%
0.1-999.9sec

30%
12 sec

Own VCB Trip


(57V)

Page 23 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

E.

Rev. 0

Calculation
1. ANSI 40
%Xd = 245% (3,733.33KVA Base)
Xd =

%Xd KV 2 10
=
KVA

245 6.6 2 10
3,733.33

= 28.58 ohm

CT RATIO
VT RATIO
100
= 1.0 28.58/2
60
= 23.8 ohm

Circle 1 radius

= 1.0 Xd/2

Set circle 1 radius = 23.8 ohm

%Xd = 24.7% (3,733.33KVA Base)


Xd =

%Xd KV 2 10
KVA

Circle 1 off set =


=

1
2
1
2

Xd
2.88

24.7 6.6 2 10
3,733.33

= 2.88 ohm

CT RATIO
VT RATIO
100
60

= 2.4 ohm ..

Set circle 1 off set = 2.4 ohm

Circle 1 trip delay = 5 sec

Set circle 1 trip delay = 5 sec

2. ANSI 51
Limit = 105% .

Set limit = 105%

(Pick up primary current = 342.93A)


TMS
t=

13.5 TMS
(I/ I P )-1

I
IP

= 2,

t=5

TMS = 0.37 .

Set TMS = 0.36

3. ANSI 32
1. Limit reverse power
1. Limit reverse power = 10% of rated output of GEN.
..
Delay time = 5 sec

4. ANSI 95i
Imax Blocking inrush =

Set 1 limit reverse power = 10%


Set delay time = 5 sec

1.2 2,599.8A
100
326.6A

= 955.2

Set Imax Blocking inrush = 955%

Page 24 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

4.1.2

Rev. 0

INCOMER FROM D/G (AG)


A. Applied relay

: 27, 59, 81, 40, 50/51, 87, 32,


46, 47, 25/25A, 67G, 95i, 64
: HIMAP-BCG
: HYUNDAI

Relay type
Manufacturer
B. D/G Data
Applied D/G
: P-AG-1/2/3
Rating
: 2,933.33KVA (2,200KW), PF : 0.75
Volt rating
: 6,600V
FLC
: 256.6A
Max. 3Ph Transient Contri. Fault Current : 1,976.89A
Steady State Fault Current : 769.8A
C. CT/PT Data
PT Ratio
: 6.6:3 / 0.11:3 KV (Incomer Side)
6.6:3 / 0.11:3 / 0.19:3 KV (Bus Side)
CT Ratio
: 400/5A
400/5A (Gen. Side)
ZCT Ratio
: 200/1.5mA
D. Relay setting table
Address

Function

400/5A

DG

200/1.5mA

27

59

81

40

50/51

87

32

46

47

67G

95i

64
400/5A

6.6kV MAIN SWBD No.2

Setting Range

Setting Value

Remarks

Nominal Ratio Value


0200

Nominal Rated Current

0 9999A

256.6A

0201

Nominal Rated Voltage

0 65000V

6600V

0202

Nominal Rated Active Power

0 9999KW

2,200KW

0203

Nominal Rated Frequency

50/60HZ

60HZ

0204

CT Feeder Primary Side

0 9999A

400A

0205

PT Feeder Primary Side

0 65000V

6600V

0206

PT Feeder Secondary Side

0 9999V

110V

0207

PT Bus1 Primary Side

0 65000V

6600V

0208

PT Bus1 Secondary Side

0 9999V

110V

0209

PT Bus2 Primary Side

0 65000V

Not Used

0210

PT Bus2 Secondary Side

0 9999V

Not Used

0211

PT Gnd1 Primary Side

0 65000V

6600V

0212

PT Gnd1 Secondary Side

0 9999V

190V

0213

PT Gnd2 Primary Side

0 65000V

Not Used

0214

PT Gnd2 Secondary Side

0 9999V

Not Used

0215

CT Gnd1 Primary Side

0 9999A

Fixed as 200/1.5mA

0216

CT Gnd1 Secondary Side

0 9999A

in Program.

0217

CT Gnd2 Primary Side

0 9999A

Not Used

0218

CT Gnd2 Secondary Side

0 9999A

Not Used

0219

CT Diff Primary Side

0 9999A

400A

0220

CT Diff Winding Ratio

0.01-9.99WPRIM/WSEC

1.0

0221

Uaux Nominal Input

24Vdc -230Vac

110Vdc

0222

Shunt #1 Nominal Input

24Vdc -230Vac

110Vdc

0223

Shunt #2 Nominal Input

24Vdc -230Vac

110Vdc

Page 25 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Address

Function

Rev. 0

Setting Range

Setting Value

Remarks

ANSI 27 Undervoltage Relay


1100
1101
1102

Undervoltage Relay
- Undervoltage 1.Limit
- Delay Time (Definite)

On / Off / CB On
0.0 ~ 99.9%
0.03 ~ 99.99sec

CB On
90%
5 sec

1103
1104
1105
1106

- Undervoltage 2. Limit
- Delay Time (Definite)
- Min. Start Voltage
- Min. Frequency

1.0 ~ 99.9%
0.03 ~ 99.99sec
1.0 ~ 99.9%
0.0 ~ 99.9HZ

50%
1 sec
30%
33HZ

Stand-by D/G start and


blackout change after
voltage build up
VCB trip

ANSI 59 Overvoltage Relay


1600
1601

Overvoltage Relay
- 1. Limit Value

On / Off / Reclose
1 ~ 999.9%

On
110%

1602
1603

- Time Multiplier (TMS)


- Curve Shape

0.01 ~ 10
Normal Inverse /
Definite

0.1
Normal Inverse

1604
1605
1606

- Reserved
- 2 Limit Value
- Delay Time (Definite)

1 ~ 999.9%
0.01 999.99sec

108%
5 sec

110% of Rated Voltage


VCB Trip : 5.0 sec at 130%
of Rated Voltage
Stand-by D/G start and
blackout change after
voltage built up

ANSI 81 Frequency Relay


2000
2001
2002
2003

Frequency Relay
Overfreq. 1. Step Limit
- Delay Time (Definite)
Reserved

On / Off / CB On
100.0 199.9%
0.1 999.9sec

CB On
105%
5 sec

2004
2005
2006

Overfreq. 2. Step Limit


- Delay Time (Definite)
Reserved

100.0 199.9%
0.1 999.9sec

110%
3 sec

VCB trip

2007
2008
2009

Underfreq. 1. Step Limit


- Delay Time (Definite)
Reserved

0.1 99.9%
0.1 999.9sec

97.5%
5 sec

Stand-by D/G start and


parallel running

2010
2011
2012

Underfreq. 2. Step Limit


- Delay Time (Definite)
Undervoltage Blocking

0.1 99.9 %
0.1 999.9sec
0.1 99.9%

90%
10 sec
65%

VCB trip

On / Off
0.0-9999%
0.03-99.99sec
0.7 ~ 1.0 Rated Volt.
On / Off
2.5 ~ 300.0 ohm
2.5 ~ 300.0 ohm
0.1 ~ 10.0sec
On / Off
2.5 ~ 300.0 ohm
2.5 ~ 300.0 ohm
0.1 ~ 10.0sec

On
50%
2 sec
0.7 Rated Volt
On
24.2 ohm
2.4 ohm
5 sec
Off
Not Used
Not Used
Not Used

Stand-by D/G start and


blackout change after
voltage built up

ANSI 40 Loss of Excitation Relay


1170
1171
1172
1173
1174
1175
1176
1177
1178
1179
1180
1181

Loss Of Excitation Relay


Reactive Power Limit
Delay Time (Definite)
Min. Voltage
Circle1
Circle 1 Radius
Circle 1 Off Set
Circle 1 Trip Delay
Circle 2
Circle 2 Diameter
Circle 2 Off Set
Circle 2 Trip Delay

1/2 Xd
1/2 Xd

Page 26 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Address

Function

Rev. 0

Setting Range

Setting Value

On / Off / Reclose
2.0 ~ 2999.9%
30 ~ 9999ms

On
250%
600ms

Remarks

ANSI 50 Instant. Overcurrent Relay


1400
1401
1402
1403

Instantaneous Overcurrent
- 1. Limit
- Delay Time (Definite)
Reserved

1404
1405
1406

- 2. Limit
- Delay Tiem (Definite)
Reserved

2.0 ~ 2999.9%
30 ~ 9999ms

250%
400ms

B/T Trip

1407
1408
1409

- Rev. Limit
- Delay Time (Definte)
Reserved

2.0 ~ 2999.9%
30 ~ 9999ms

250%
50ms

Used as ANSI 67S

1410

- Inrush Blocking

On / Off

On

On / Off / Reclose
2.0 ~ 2999.9%
0.03 ~ 10.00

On
105%
0.36

8 Curve Shapes(IDMT)
None, Def./Th, Def.,Curve
D-F

Very Inverse
None

Gen. CB Trip

ANSI 51 AC Time Overcurrent Relay


1500
1501
1502

Time Overcurrent Relay


- Limit
- Time Multiplier (TMS)

1503
1504

- Curve Shape
- Reset Characteristic

1505
1506

- 1. Limit
- Delay Time (Definite)

2.0 ~ 2999.9%
0.1 ~ 999.9sec

100%
3 sec

1507
1508
1509
1510
1511
1512
1513

- 2. Limit
- Delay Time (Definite)
- 3. Limit
- Delay Time (Definite)
- Reset Charact. (Th)
- Volt. Restrain (51VR)
- Voltage Low Limit

2.0 ~ 2999.9%
0.1 ~ 999.9sec
2.0 ~ 2999.9%
0.1 ~ 999.9sec
0 ~ 99sec
On / Off
10 ~ 90%

Not Used
Not Used
Not Used
Not Used
0 sec
Off
Not Used

105% IFLC (Gen)


5 sec at 200% Setting
(1.7min at 110% IFLC)
- VCB Trip

Alarm only before


Preferential Trip

ANSI 87 Differential Protective Relay


2100
2101
2102
2103

Diff. Protective Relay


- Diff. Limit
- Delay Time (Definite)
- Angle Compensation

2104
2105
2106
2107
2108
2109

Reserved
Reserved
- Delay CT-Saturation
- Inrush Blocking
- Bias Limit
- Zero Compensation

On / Off
1.0 ~ 99.9%
0.03~ 999.99sec
None, Dy1, Dy5, Dy7,
Dy11, Yd1

On
20%
0.1 sec
None

0.1 ~ 9999.9sec
On / Off
0.1 ~ 999.9%
On / Off

0.1 sec
On
30%
Off

Page 27 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Address

Function

Rev. 0

Setting Range

Setting Value

On / Off
0.1 ~ 99.9%
0.1 ~ 99.9sec
0.1 ~ 99.9%
0.1 ~ 99.9sec
0.1 ~ 199.9%
0.1 ~ 99.9sec
0.1 ~ 199.9%
0.1 ~ 99.9sec

On
10%
5 sec
Not Used
Not Used
Not Used
Not Used
Not Used
Not Used

Remarks

ANSI 32 Reverse Power Relay


1130
1131
1132
1133
1134
1135
1136
1137
1138

Overload Relay
- 1. Limit Reverse Power
- Delay Time (Definite)
- 2. Limit Reverse Power
- Delay Time (Definite)
- 1. Limit Active Power
- Delay Time (Definite)
- 2. Limit Active Power
- Delay Time (Definite)

50% of Power Required to


Motor a Gen.

ANSI 46 Reverse Phase Relay (CT Line Monitoring)


1200
1201
1202
1203
1204
1205
1206
1207
1208
1209

Reverse Phase Relay


- Limit Value
- Time Multiplier (TMS)
- Curve Shape
- Min. Feeder Voltage
- 2. Limit
- Delay Time (Definite)
- 1. Limit.
- Delay Time (Definite)
- Volt. Restrain [51VR]

On / Off / Reclose
0.0 ~ 99.9%
0.01 ~ 99.99
Norm. Inverse / Definite
1.0 ~ 99.9%
0.0 ~ 99.9%
0 ~ 9999ms
0.0 ~ 99.9%
0 ~ 9999ms
On / Off

On
10%
2.0
Norm. Inverse
10%
Not Used
Not Used
Not Used
Not Used
Off

ANSI 47 Phase Sequence Voltage Relay (VT Line Monitoring)


1300
1301
1302

Phase Sequence Relay


- Limit Value
- Delay Time (Definite)

On / Off
1.0 ~ 199.9%
0.01 ~ 99.99sec

On
20%
2 sec

Event No.
0-30 Deg
0-2000mHZ
70.0-100.0%
100.0-130.0%
0.1-30%
70.0-100.0%
100.0-130.3%
0.1-999.9sec
0.1-999.9sec
0-9999ms
0.1-999.9sec
0.1-999.9sec
Event Reminder For
Output
Event Reminder For
Output
Event Reminder For
Output
Event Reminder For
Output

800
7 deg
250 mHZ
94%
106%
5%
95%
105%
100 sec
2 sec
500 ms
10 sec
2 sec

0.0-99.9%
0-9999(Event Number)
Up/Down/Both
0-1000ms

50%

ANSI 25/25A Synchronizing Relay


1000
1001
1002
1003
1004
1005
1006
1007
1008
1009
1010
1011
1012
1013

Sync. Unit 1 Active by


- Max Phase Angle
- Max Frequency Diff.
- Min Frequency
- Max Frequency
- Max Voltage Diff.
- Min Voltage
- Max Voltage
- Freq. Set. Pulse Time
- Freq. Set. Break Time
- Speed Push After 10s
- Volt. Set. Pulse Time
- Volt. Set. Break Time
- Freq. Higher Event

1014

- Freq. Lower Event

1015

- Volt. Higher Event

1016

- Volt. Lower Event

1017
1018
1019
1020

- Preset Analog Output


- Activate Preset By
- Closing Direction
- CB Closing Delay

Both
100ms

Page 28 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Address

Function

Rev. 0

Setting Range

Setting Value

On/Off
0.0-99.9%
Event Reminder for Output
Event Reminder for Output

On
10%

Remarks

ANSI 25/25A Synchronizing Relay


1021
1022
1023
1024

- Life/Dead Cond. Check


- Min Voltage Level
- CB Sync. On Event
- Abnormal Bus 1 Event

With External
Black Out Signal

ANSI 67GS/GD AC Direction Ground Overcurrent Relay


1810
1811
1812
1813

AC Direction (67GS)
- Limit Value (Igndx)
- Delay Time (Definite)
- Pick-Up Type (67GX)

On / Off
0 ~ 9999mA
0.1 ~ 999sec
Meas. Ignd1/Meas.
Ignd2/Meas. Ig1 & 2

On
1.0mA
0.2 sec
Meas. Ignd1

1814
1815
1816

- Volt. Low Limit (Vo)


- Phase Angle (+/-60)
- AC Direction (67GD)

0.1 ~ 999.9%
0 ~ 360
On/Off

20%
60
Off

ANSI 95i Inrush Blocking Relay


2300
2301
2302
2303
2304

Inrush Blocking Relay


Limit Of DC Portion
2. Harmonic Content
Te Extension Time
Tmax Blocking Time

On/Off
1.0 99.9%
1 99%
30 9999ms
0.03 99.99sec

On
0%
15%
100 ms
1 sec

2305

Imax Blocking Inrush

1 2999%

924%

Off

120% of max. Gen. thru.


Fault current

ANSI 64 Overvoltage Ground Relay


1700
1701
1702
1703

Ground Detector Relay


- Limit Value Ugnd1
- Delay Time (Definite)
Reserved

On / Off / Reclose
0.1-999.9%
0.1-999.9sec

On
30%
10 sec

Bus Tie VCB Trip


(57V)

1704
1705
1706

-Limit Value Ugnd2


-Delay Time (Definite)
Reserved

0.1-999.9%
0.1-999.9sec

30%
12 sec

Own VCB Trip


(57V)

Page 29 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

E.

Rev. 0

Calculation
1. ANSI 40
%Xd = 245% (2,933.33KVA Base)
Xd =

%Xd KV 2 10
=
KVA

245 6.6 2 10
2,933.33

= 36.4 ohm

CT RATIO
VT RATIO
80
= 1.0 36.4/2
60
= 24.266 ohm

Circle 1 radius

= 1.0 Xd/2

Set circle 1 radius = 24.2 ohm

%Xd = 25.2% (2,933.33KVA Base)


Xd =

%Xd KV 2 10
KVA

Circle 1 off set =


=

1
2
1
2

Xd
3.74

25.2 6.6 2 10
2,933.33

= 3.74 ohm

CT RATIO
VT RATIO
80
60

= 2.492 ohm ..

Set circle 1 off set = 2.4 ohm

Circle 1 trip delay = 5 sec

Set circle 1 trip delay = 5 sec

2. ANSI 51
Limit = 105% .

Set limit = 105%

(Pick up primary current = 269.43A)


TMS
t=

13.5 TMS
(I/ I P )-1

I
IP

= 2,

t=5

TMS = 0.37 .

Set TMS = 0.36

3. ANSI 32
1. Limit reverse power
1. Limit reverse power = 10% of rated output of GEN.
..
Delay time = 5 sec

Set 1 limit reverse power = 10%


Set delay time = 5 sec

4. ANSI 95i

1.2 1,976.57A
100
256.6A
= 924.3

Imax Blocking inrush =

Set Imax Blocking inrush = 924%

Page 30 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

4.1.3 NO.1/2 BUS GPT PANEL


A. Applied relay

6.6kV MAIN SWBD No.1 / 2

: 27M, 27R, 64

Relay type

: HIMAP FI

Manufacturer

: HYUNDAI

GPT
CLR

B. GPT Data

GPT Ratio

: 6.6:3 / 0.11:3 / 0.19:3 KV

27
64

C. Relay setting table


Address

Function

Setting Range

Setting Value

Remarks

ANSI 27 Undervoltage Relay (27M)


Voltage

0.5-1.0Vn

0.8Vn (88V)

Time (Definite)

0.1-10 sec

2 sec

For 6.6KV Motor Stop

ANSI 27 Undervoltage Relay (27R)


Voltage

0.2-0.5Vn

0.2Vn (22V)

Time (Definite)

0.1-10 sec

1 sec

For Dead Bus Checking

ANSI 64 Overvoltage Ground Relay


Voltage

0.1-0.5Vn

0.15Vn (28.5V)

Mode

Inverse, Instant

Inverse

Time

Below 50ms (Inst.)


0.05-10tap (Inverse)

0.05 (Min. Setting)

For Remote Alarm

1.3 sec at 1.3 Setting (28.5V)

Page 31 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

4.1.4

Rev. 0

INCOMER FROM D/G & BUS TIE

1) SYNCHRONIZING CHECK RELAY (DEIF/CSQ-2M)


A. Applied relay

: 25

Relay type

: CSQ-2M

Manufacturer

: DEIF

6.6kV MAIN SWBD No.1 / 2

GPT

B. PT Data

PT Ratio =

6.6
3

0.11
KV (Incomer side from D/G)
3

6.6
3

0.11
KV (Bus side)
3

CLR

25

C. Relay setting table


Address

Function

Setting Range

Setting Value

, Phase Difference

5-20, Step=1

U, Voltage Difference

1-10%, Step=1%

5%

Td, Sync. Relay Delay

0-1sec, Step=0.1s

Not Used

0-1sec Or , Step=0.1sec

0.7 sec

Remarks

ANSI 25 Synchronizing Check Relay

TR, Length of Sync. Pulse

Because TR is Set

Off

TB, Dead Bus Offset Voltage

2) SYNCHRONIZING CHECK RELAY (DEIF/FAS-113DG)


A. Applied relay

: 25

Relay type

: FAS-113DG

Manufacturer

: DEIF

B. Relay setting table


Address

Function

Setting Range

Setting Value

25 ~ 500 ms

500ms

0.25 ~ 2.5 HZ

0.5 HZ

0.1 ~ 0.5 HZ

0.2 HZ

Remarks

ANSI 25 Synchronizing Check Relay


TN, Control Pulse Length
XP, Proportional Band
FSET, Slip Frequency
UMAX, Acceptable Volt. Diff

TBC, Breaker Closure Time

2 ~ 12% of UBB

5% of UBB

20 ~ 200 ms

70 ms

Page 32 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

4.1.5 NO.1/2/3/4/5/6/7 6.6KV REEFER TR FEEDER


A. Applied relay
: 27, 50/51, 67G
Relay type
: HIMAP-FI
Manufacturer
: HYUNDAI

6.6kV MAIN SWBD No.1/2

B. TR data
Rating
: 1,600KVA, 6.6KV/0.44KV, %Z = 5.85%
FLC
: 140A(TR 1st) / 2,099.5A(TR 2nd)
Max. TR Through fault current : 2,393A
C. CT/PT Data
PT Ratio
CT Ratio
ZCT Ratio

Function

27

67G
200/1.5mA

No.1/2/3/4/5/6/7
REEFER TR
6.6 / 0.44kV
1,600kVA

: 6.6:3 / 0.11:3 / 0.19:3 KV (Bus side)


: 200/5A
: 200/1.5mA
0.44KV SWBD

D. Relay setting table


Address

50/51

200/5A

Setting Range

Setting Value

Remarks

ANSI 27 Undervoltage Relay (27M)


Volatage
Time(Definite)

0.02-1.0 Vn
0.1-10 sec

0.8 Vn
2 sec

ANSI 50 Instant. Overcurrent Relay (In Case of One(1) Generator Running)


Current
Time

1 ~ 18 In

2.8 In

0.05 ~ 10 sec

0.2 sec

220% of IFLC (Gen.)

ANSI 51 Time Overcurrent Relay (In Case of One(1) Generator Running)


Current
Mode
Time

0.2 ~ 2.4 In
Inv.Very Inv., Extremely Inv.

0.9 In
Very Inv

0.05 ~ 10tap

0.56 Tap

125% of IFLC (TR)

ANSI 50 Instant. Overcurrent Relay (Normal Operating Condition)


Current
Time

1 ~ 18 In

5.6 In

0.05 ~ 10 sec

0.2 sec

220% of IFLC (2 Gen.)

ANSI 51 Time Overcurrent Relay (Normal Operating Condition)


Current
Mode

0.2 ~ 2.4 In
Inv.Very Inv., Extremely Inv.
0.05 ~ 10 Tap

Time

0.9 In
Very Inv

125% of IFLC(TR)

1.4 Tap

ANSI 67G Directional Ground Overcurrent Relay


Current
Voltage
Time
Angle

1 ~ 10mA
0.1 ~ 0.2V0
0.1 ~ 10 sec
45~ 75

1.0mA
0.2VO
0.2 sec
60

Page 33 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

E. Calculation

1. ANSI 51 (In case of one(1) generator running)


Current
1.25 140
= 0.875In ......... Set current = 0.9 In
200
(Pick up primary current = 180A)

Current =
Time
t=

13.5 Tap
(I/ I p )-1

I
Ip

560
180

= 3.11,

t=4

Tap =0.625 ..... Set tap = 0.56


2. ANSI 50 (In case of one(1) generator running)
Current
2.2 256.6
= 2.82In ... Set current = 2.8 In
200
(Pick up primary current = 560A)
Current =

Time = 0.2 sec .. Set time = 0.2sec


3. ANSI 51 (Normal operating condition)
Current
Current

1.25 140
200

= 0.875In . Set current = 0.9 In

(Pick up primary current = 180A)


Time
t=

13.5 Tap
(I/ I p )-1

I
Ip

1,120 = 6.22,
180

t=4

Tap =1.54 .... Set tap = 1.4


4. ANSI 50 (Normal operating condition)
Current
Current

2.2 (256.6+256.6)
200

=5.64In Set current = 5.6 In

(Pick up primary current = 1,120A)


Time = 0.2 sec .. Set time = 0.2sec

Page 34 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

4.1.6 NO.1/2 STEP-DOWN TR FEEDER


A. Applied relay
: 50/51, 67G, 87T
Relay type
: HIMAP-T
Manufacturer
: HYUNDAI
B.

6.6kV MAIN SWBD No.1/2

87T

67G
200/1.5mA
No.1 / 2
6.6 / 0.44kV
3,900kVA

C. CT/PT Data
PT Ratio
CT Ratio
ZCT Ratio

: 6.6:3 / 0.11:3 / 0.19:3 KV (Bus side)


: 450/5A(TR 1st) / 6,000/5A (TR 2nd)
: 200/1.5mA

6,000/5A

0.44KV SWBD

D. Relay setting table


Address

50/51

450/5A

TR Data
Rating
: 3,900KVA, 6.6/0.44KV, %Z = 6.11%
FLC
: 341.2A (TR 1st) / 5,117.4A (TR 2nd)
Max. TR Through fault current : 5,584A

Function

Setting Range

Setting Value

Remarks

ANSI 67G Directional Ground Overcurrent Relay


Current
Voltage
Time
Angle

1 ~ 10 mA
0.1 ~ 0.2 V0
0.1 ~ 10sec
45~ 75

1.0 mA
0.2VO
0.2 sec
60

Primary Current
Secondary Current
Inst. Ratio

0.2 ~ 1.2 In
0.2 ~ 1.2 In
500 ~ 1500%

0.75 In
0.85 In
1500%

Differential Ratio
Bias Ratio
2nd Harmonic Ratio
TR Angle
Zero Comp.
Time

20 ~ 50%
20 ~ 50%
10 ~ 30%

25%
20%
15%
Ddo
Disable
Below 50ms

ANSI 87T Differential Relay

Enable, Disable
Below 50ms

Max. Differential Ratio


(If diff. ratio is higher than this
setting value, That condition is
the same as the condition at this
setting value)

ANSI 50 Instant. Overcurrent Relay (In Case of One(1) Generator Running)


Current
Time

1 ~ 18 In

1.3 In

0.05 ~ 10 sec

0.2 sec

220% of IFLC (Gen.)

ANSI 51 Time Overcurrent Relay (In Case of One(1) Generator Running)


Current
Mode
Time

0.2 ~ 2.4 In
Inv. Very Inv., Extremely Inv
.
0.05 ~ 10 Tap

0.62 In
Very Inv

85% OF IFLC (Gen.)

0.3 Tap

ANSI 50 Instant. Overcurrent Relay (Normal Operating Condition)


Current
Time

1 ~ 18In

2.5 In

0.05 ~ 10 sec

0.2 sec

220% of IFLC (2 Gen.)

ANSI 51 Time Overcurrent Relay (Normal Operating Condition)


Current
Mode
Time

0.2 ~ 2.4 In
Inv. Very Inv., Extremely Inv
.
0.05 ~ 10 Tap

0.95 In
Very Inv

125% of IFLC (TR)

0.4 Tap

Page 35 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

E.

Rev. 0

Calculation

1. ANSI 51 (In case of one(1) generator running)


Current
0.85 326.6
= 0.62 In ...... Set current = 0.62 In
450
(Pick up primary current = 279A)
Current =

Time
t=

13.5 Tap
(I/ I p )-1

I
Ip

585
279

= 2.54,

t=4

Tap = 0.32 Set tap = 0.3


2. ANSI 50 (In case of one(1) generator running)
Current
2.2 256.6
= 1.254 In Set current = 1.3 In
450
(Pick up primary current = 585A)

Current =

Time = 0.2 sec .... Set time = 0.2 sec


3. ANSI 51 (Normal operating condition)
Current
1.25 341.2
= 0.947 In Set current = 0.95 In
450
(Pick up primary current = 427.5A)

Current =

Time
t=

13.5 Tap
(I/ I p )-1

I
Ip

1,125 = 2.63,
427.5

t=4

Tap = 0.483 . Set tap = 0.4

4. ANSI 50 (Normal operating condition)


Current
2.2 (256.6 + 256.6)
= 2.5 In Set current = 2.5 In
450
(Pick up primary current = 1,125A)
Current =

Time = 0.2sec .. Set time = 0.2 sec


5. ANSI 87T
Inst. Ratio
Inst. Ratio =

1.5 5,584
450

100= 1,861% Set current = 1,500% (Max.)

Page 36 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

4.1.7 MOTOR FEEDER (NO.1/2 MAIN L.O PUMP)


A. Applied relay
: 49, 46, 51LR, 50, 66, 67G
Relay type
: HIMAP-M
Manufacturer : HYUNDAI
Power fuse
: 100A (Maker : SIBA)
B. Motor data
Applied motor
Rating
Volt rating
FLC
Starting current
Starting time

: No.1/2 MAIN L.O PUMP


: 355KW
: 6.6KV
: 37.6A
: 235A (Direct on line)
: 1.5 SEC

C. CT/PT Data
PT Ratio
CT Ratio
ZCT Ratio

: 6.6:3 / 0.11:3/0.19:3 KV (Bus side)


: 50/5A
: 200/1.5mA

6.6kV MAIN SWBD No.1/2

100A

50/5A

49

46

51LR

66

50

67G

200/1.5mA

M
355KW
No.1/2 MAIN L.O PUMP

D. Relay setting table


Address

Function

Setting Range

Setting Value

Remarks

0.1 ~ 1.2 In
0.5 ~ 180 sec
0.5 ~ 180 sec
0.1 ~ 10

0.76 In
6 sec
3.5 sec
3

100% of IFLC (Motor)

0.1 ~ 0.5 In
0.1 ~ 10 sec

0.12 In
4 sec

0.15 x IFLC (Motor)

Start Current

0.2 ~ 14.4 In

4.7 In

100% of Starting Current

Start Time
Locked Rotor Current
Locked Rotor Time

1.0 ~ 60 sec
0.2 ~ 6.0 In
1.0 ~ 4.0 sec

1.5 sec
2.3 In
2 sec

300% of IFLC (Motor)

0.2 ~18 In

8.5 In

1.6 1.2 of Starting Current

Below 0.2 sec

0.2 sec

ANSI 49 Thermal Overload Relay


Thermal Current
Cold Limit
Hot Limit
c/h
ANSI 46 Negative Sequence Relay
Current
Time
ANSI 51LR Locked Rotor Relay

ANSI 50 Instantaneous Relay


Current
Time

ANSI 66 Start Inhibit for Motors Relay


Allow Time
Number of Start
Limit Time
Thermal Limit (d)

1 ~ 60 min
1~4
1 ~ 60 min
40 ~ 100 %

60 min
3
15 min
80 %

ANSI 67G Directional Ground Overcurrent Relay


Current
Voltage
Time
Angle

1 ~ 10 mA (Fixed)
0.1 ~ 0.2 V0
0.1 ~ 10.0 sec
45~ 75

1.0 mA
0.2VO
0.2 sec
60

Page 37 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

E. Calculation

1. ANSI 49
Thermal current
1.0 x 36.6
= 0.752In .... Set thermal current = 0.76In
50
(Pick up primary current = 38A)

Thermal current =

2. ANSI 46
Current
0.15 x 37.6
= 0.112In Set current = 0.12In
50
(Pick up primary current = 6A)

Current =

3. ANSI 51LR
Start current
1.0 x 235A
= 4.7 . Set current = 4.7In
50
(Pick up primary current = 235A)
Start current =

Locked rotor current


3.0 x 37.6
50
(Pick up primary current = 115A)
Locked rotor current =

= 2.256In .. Set current = 2.3In

4. ANSI 50
Current
1.6 x 1.2 x 235
= 9.024In Set current = 8.5In
50
(Pick up primary current = 425A)
(For coordination with power fuse)
Current =

Time .. Time = 0.2sec

Page 38 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

4.1.8 MOTOR FEEDER (BOW THRUSTER MOTOR)


A. Applied relay
: 49, 46, 51LR, 50, 66, 67G
Relay type
: HIMAP-M
Manufacturer
: HYUNDAI
B.

Motor data
Applied motor
Rating
Volt rating
FLC

Starting current
Starting time
C. CT/PT Data
PT Ratio
CT Ratio
ZCT Ratio

6.6kV MAIN SWBD No.1

: BOW THRUSTER MOTOR


: 2,500KW
: 6.6KV
: 279.3A
: 279.3 600% (50% Tap)
: 20 SEC (at 50% Tap)

350/5A

49

46

51LR

66

50

67G

= 419A
200/1.5mA

: 6.6:3 / 0.11:3 / 0.19:3 KV (Bus side)


: 350/5A
: 200/1.5mA

M
2,500kW
BOW THRUSTER MOTOR

D. Relay setting table


Address

Function

Setting Range

Setting Value

Remarks

ANSI 49 Thermal Overload Relay


Thermal Current
Cold Limit
Hot Limit
c/h

0.1 ~ 1.2 In
0.5 ~ 180 sec
0.5 ~ 180 sec
0.1 ~ 10

0.8 In
1.6 sec
1.2 sec
3

100% of IFLC(Motor)

0.15 x IFLC(Motor)

ANSI 46 Negative Sequence Relay


Current

0.1 ~ 0.5 In

0.12 In

Time

0.1 ~ 10 sec

4 sec

ANSI 51LR Locked Rotor Relay


Start Current
Start Time
Locked Rotor Current
Locked Rotor Time

0.2 ~ 14.4 In
1.0 ~ 60 sec
0.2 ~ 6.0 In
1.0 ~ 4.0 sec

1.2 In
20 sec
1.6 In
2 sec

100% of Starting Current

0.2 ~18 In

2.3 In

1.6 1.2 of Starting Current

Below 0.2 sec

0.05 sec

200% of IFLC(Motor)

ANSI 50 Instantaneous Relay


Current
Time

ANSI 66 Start Inhibit For Motors Relay


Allow Time
Number of Start
Limit Time
Thermal Limit (d)

1 ~ 60 min
1~4
1 ~ 60 min
40 ~ 100 %

60 min
4
15 min
80 %

ANSI 67G Directional Ground Overcurrent Relay


Current
Voltage
Time
Angle

1 ~ 10 mA (Fixed)
0.1 ~ 0.2V0
0.1 ~ 10.0 sec
45~ 75

1.0 mA
0.2 VO
0.2 sec
60

Page 39 of 90

H1646-9 / S253-6 8,200 TEU CONTAINER VESSEL


PROTECTIVE RELAY & PMS SETTING REPORT

Rev. 0

E. Calculation

1. ANSI 49
Thermal current
1.0 279.3
= 0.798 In ... Set thermal current = 0.8 In
350
(Pick up primary current = 280A)

Thermal current =

2. ANSI 46
Current
0.15 279.3
= 0.12 In . Set current = 0.12 In
350
(Pick up primary current = 42A)

Current =

3. ANSI 51LR
Start current
1.0 419
= 1.197 In ... Set current = 1.2 In
350
(Pick up primary current = 420A)
Start current =

Locked rotor current


2 279.3
350
(Pick up primary current = 560A)
Locked rotor current =

= 1.596 In ... Set current = 1.6 In

4. ANSI 50
Current
1.2 1.6 419
= 2.298 In .. Set current = 2.3 In
350
(Pick up primary current = 805A)
Current =

Time .. Time = 0.05 sec

Page 40 of 90

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.1 INCOMER FROM D/G (MG)
ITEM
INCOMER
FROM D/G

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-1
P-DG-2

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

FUNCTION
* NOMINAL RATIO VALUES
0200. NOMINAL RATED - Current
0201.
- Voltage
0202.
- Active Power
0203.
- Frequency
0204. CT Feeder -primary side
0205. PT Feeder -primary side
0206.
-secondary side
0207. PT BUS1
-primary side
0208.
-secondary side
0209. PT BUS2
-primary side
0210.
-secondary side
0211. PT GND1
-primary side
0212.
-secondary side
0213. PT GND2
-primary side
0214.
-secondary side
0215. CT GND1
-primary side
0216.
-secondary side
0217. CT GND2
-primary side
0218.
-secondary side
0219. CT DIFF
-primary side
0220. Transformer winding ratio
0221. - Uaux nominal input
0222. - Shunt#1 nominal input
0223. - Shunt#2 nominal input

GEN.:
6.6kV
3,733.33KVA
PF=0.75
FLC=326.6A

SETTING RANGE
0 - 9999A
0 - 65000V
0 - 9999KW
50/60HZ
0 -9999A
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 9999A
0 - 9999A
0 - 9999A
0 - 9999A
0 - 9999A
0.01 - 9.99Wprim/Wsec
24Vdc - 230Vac
24Vdc - 230Vac
24Vdc - 230Vac

SET POINT
326.6A
6600V
2,800KW
60HZ
500A
6600V
110V
6600V
110V
NOT USED
NOT USED
6600V
190V
NOT USED
NOT USED
1
1
NOT USED
NOT USED
500A
1.0
110Vdc
110Vdc
110Vdc

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER

09. Jun. 2005


REMARKS

CT :
500/5A
5P10/15VA
500/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)

0215/0216
EVENT
200/1.5mA fixed
in program.

1101/1102
(Undervolt. 1st)

27

RELAY SETTING CHECK LIST.xls

1100. Undervoltage relay


1101. - Undervoltage 1.limit
1102. - Delay time (definite)
1103. - Undervoltage 2.limit
1104. - Delay time (definite)
1105. - Minimum startvoltage
1106. - Minimum frequency

ON / OFF / CB ON
0.0 - 99.9%
0.03 - 99.99SEC
0.0 - 99.9%
0.03 - 99.99SEC
0.0 - 99.9 %
0.0 - 99.9HZ

41 of 90

CB ON
90%
5 SEC
50%
1sec
30%
33HZ

stand-by DG
start and
blackout change
after build-up
1103/1104 :
(Undervoltage. 2nd)

VCB trip

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.1 INCOMER FROM D/G (MG)
ITEM

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-1
P-DG-2

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE
59

INCOMER
FROM D/G
GEN.:
6.6kV
3,733.33KVA
PF=0.75
FLC=326.6A

81

40

RELAY SETTING CHECK LIST.xls

FUNCTION

SETTING RANGE

SET POINT

1600. Overvoltage relay


1601. - 1. Limit value
1602. - Time multiplier(TMS)
1603. - Curve shape
1604.
reserved
1605. - 2. Limit value
1606. - Delay time(definite)

ON / OFF / RECLOSE
1 - 9999%
0.01 - 10
NORM. INVERSE/DEFINITE

ON
110%
0.1
NORM. INV.

1 - 9999%
0.01 - 999.99SEC

108%
5sec

2000. Frequency relay


2001. Overfreq. 1.Step limit
2002. - Delay time(definite)c
2003.
reserved
2004. Overfreq. 2.Step limit
2005. - Delay time(definite)c
2006.
reserved
2007. Underfreq.1.Step limit
2008. - Delay time(definite)c
2009.
reserved
2010. Underfreq.2.Step limit
2011. - Delay time(definite)
2012. Undervoltage blocking

ON / OFF / CB ON
100.0 - 199.9%
0.1 - 999.99SEC

CB ON
105%
5SEC

100.0 - 199.9%
0.1 - 999.99SEC

110%
3SEC

0.1 - 99.9%
0.1 - 999.99SEC

97.5%
5SEC

0.1 - 99.9%
0.1 - 999.9SEC
0.1 - 99.9%

90%
10SEC
65%

1170.Loss of excitation relay


1171. reactive power limit
1172. delay time(definite)
1173. min. voltage
1174. Circle 1
1175.
- radius
1176.
- offset
1177.
- delay
1178. Circle 2
1179.
- diameter
1180.
- offset
1181.
- delay

ON / OFF
0.0 - 9999%
0.03 - 99.99SEC
0.7 - 1.0 x RATED VOLTAGE
ON / OFF
2.5 - 300.0OHM
2.5 - 300.0OHM
0.1 - 10.0SEC
ON/OFF
2.5 - 300.0OHM
2.5 - 300.0OHM
0.1 - 10.0SEC

ON
50%
2 SEC
0.7 xRATED VOL
ON
23.8 OHM
2.4 OHM
5SEC
OFF
NOT USED
NOT USED
NOT USED

42 of 90

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER
CT :
500/5A
5P10/15VA
500/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)

09. Jun. 2005


REMARKS
1601/1602
(Overvolt. 1st)
VCB trip
1605/1606
(Overvolt. 2nd)
stand-by DG
start and
blackout change
after voltgae
build-up.
2001/2002
(Overfreq. 1st)
stand-by DG
start and
blackout change
after voltgae
build-up.
2004/2005
(Overfreq. 2nd)
VCB trip
2007/2008
(Underfreq. 1st)

stand-by DG
start and parallel
running
2010/2011
(Underfreq. 2nd)

VCB trip

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.1 INCOMER FROM D/G (MG)
ITEM

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-1
P-DG-2

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE
50

INCOMER
FROM D/G
GEN.:
6.6kV
3,733.33KVA
PF=0.75
FLC=326.6A

51

RELAY SETTING CHECK LIST.xls

FUNCTION

SETTING RANGE

SET POINT

1400. Instantaneous
1401. - 1.limit
1402. - delay time (definite)
1403. reserved
1404. - 2.limit
1405. - delay time (definite)
1406. reserved
1407. - rev. limit
1408. - delay time (definite)
1409. reserved
1410. - inrush blocking

ON / OFF / RECLOSE
2 - 2999.9%
30 - 9999ms

ON
250%
600ms

2.0 - 2999.9%
30 - 9999ms

250%
400ms

2.0 - 2999.9%
30 - 9999ms

250%
50ms

ON/OFF

ON

1500. Time overcurrent relay


1501. - Limit
1502. - Time multiplier(TMS)
1503. - Curve shape
1504. - Reset characteristic
1505. - 1.limit
1506. - Delay time(definite)c
1507. - 2.limit
1508. - Delay time(definite)
1509. - 3.limit
1510. - Delay time(definite)
1511. - Reset character (Th)
1512. - Volt. restain[51VR]
1513.
- Volt low limit

ON / OFF / RECLOSE
2.0 - 2999.9 %
0.03 - 10.00
8 CURVE SHAPES(IDMT)
NONE,DEF./TH,DEF.,CURVE D-F
2.0 - 2999.9%
0.1 - 999.9SEC
2.0 - 2999.9%
0.1 - 999.9SEC
2.9 - 2999.9%
0.1 - 999.9SEC
0 -99SEC
ON/OFF
10 -90%

ON
105%
0.36
VERY INV.
NONE
100%
3 SEC
NOT USED
NOT USED
NOT USED
NOT USED
0 SEC
OFF
NOT USED

43 of 90

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER
CT :
500/5A
5P10/15VA
500/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)

09. Jun. 2005


REMARKS
1401/1402
GEN CB trip
1404/1405
B/T trip
1407/1408
GEN CB trip
(same as 67S)

GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)

1505/1506
Alarm only
before
preferential trip

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.1 INCOMER FROM D/G (MG)
ITEM

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-1
P-DG-2

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE
87

INCOMER
FROM D/G

SETTING RANGE

SET POINT

2100. Diff. protective relay


2101. - Diff. limit
2102. - Delay time(definite)
2103. - Angle compensation
2104. - reserved
2105. - reserved
2106. - Delay CT-saturation
2107. - Inrush blocking
2108. - Bias limit
2109. - Zero compensation

ON / OFF
1.0 - 99.9%
0.03 - 999.99SEC
NONE,DY1,DY5,DY7,DY11,YD1,

ON
20%
0.1SEC
NONE

0.1 - 9999.9SEC
ON/OFF
0.1 - 999.9%
ON/OFF

0.1SEC
ON
30%
OFF

32

1130. Overload relay


1131. - 1.limit reverse power
1132. - delay time (definite)
1133. - 2.limit reverse power
1134. - delay time (definite)
1135. - 1.limit active power
1136. - delay time (definite)
1137. - 2.limit active power
1138. - delay time (definite)

ON/OFF
0.1 - 99.9%
0.1 - 99.9SEC
0.1 - 99.9%
0.1 - 99.9SEC
0.1 - 199.9%
0.1 - 99.9SEC
0.1 - 199.9%
0.1 - 99.9SEC

ON
10%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED

46

1200. Reverse phase relay


1201. - Limit value
1202. - Time multiplier(TMS)
1203. - Curve shape
1204. - Min. feeder voltage
1205. - 1.limit
1206. - Delay time(definite)
1207. - 2.limit
1208. - Delay time(definite)
1209. - Volt. restrain[51VR]

ON/OFF/RECLOSE
0.0 -99.9%
0.01 - 99.99
NORM. INV. /DEFINITE
1.0 - 99.9%
0.0 - 99.9%
0 - 9999ms
0.0 - 99.9%
0 - 9999ms
ON/OFF

ON
10%
2.0
NORM. INV.
10%
NOT USED
NOT USED
NOT USED
NOT USED
OFF

47

1300. Phase sequence relay


1301. - Limit value
1302. - Delay time(definite)

ON/OFF
1.0 - 199.9%
0.01 - 99.99SEC

ON
20%
2 SEC

GEN.:
6.6kV
3,733.33KVA
PF=0.75
FLC=326.6A

RELAY SETTING CHECK LIST.xls

FUNCTION

44 of 90

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER

09. Jun. 2005


REMARKS

CT :
500/5A
5P10/15VA
500/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)

1131/1132
50% of power
Required to
motor a Gen.

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.1 INCOMER FROM D/G (MG)
ITEM

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-1
P-DG-2

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE
25/25A

INCOMER
FROM D/G
GEN.:
6.6kV
3,733.33KVA
PF=0.75
FLC=326.6A

RELAY SETTING CHECK LIST.xls

FUNCTION
1000. SYNC. UNIT 1 activ by
1001. - MAX phase angle
1002. - MAX frequency diff.
1003. - MIN frequency
1004. - MAX frequency
1005. - MAX voltage diff.
1006. - MIN voltage
1007. - MAX voltage
1008. - freq.set.pulse time
1009. - freq.set.break time
1010. - speed push after 10s
1011. - volt.set.pulse time
1012. - volt.set.break time
1013. - freq. higher event
1014. - freq. lower event
1015. - volt. higher event
1016. - volt. lower event
1017. - preset analog output
1018. - activate preset by
1019. - closing direction
1020. - CB closing delay
1021. - life/dead cond. check
1022. - min voltage level
1023. - CB sync. ON event
1024. - abnormal bus 1 event

SETTING RANGE
EVENT NO.
0 - 30 deg
0 - 2000mHZ
70.0 - 100.0%
100.0 - 130.0%
0.1 - 30%
70.0 - 100.0%
100.0 - 130.0%
0.1 - 999.9SEC
0.1 - 999.9SEC
0 - 9999ms
0.1 - 999.9SEC
0.1 - 999.9SEC
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
0.0 -99.9%
0 - 9999(EVENT NUMBER)
UP/DOWN/BOTH
0 -1000ms
ON/OFF
0.0 - 99.9%
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT

45 of 90

SET POINT
800
7deg
250mHZ
94%
106%
5%
95%
105%
100SEC
2SEC
500ms
10SEC
2SEC

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER

09. Jun. 2005


REMARKS

CT :
500/5A
5P10/15VA
500/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)

50%
BOTH
100ms
ON
10%

1021/1022
with External
Black out signal

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.1 INCOMER FROM D/G (MG)
ITEM
INCOMER
FROM D/G

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-1
P-DG-2

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

67GS/GD 1810. AC direction. [67GS]


1811. - Limit value [Ignd1]
1812. - Delay Time (definite)
1813. - Pickup type (67Gx)

SETTING RANGE

SET POINT
ON
1.0mA
0.2SEC
MEAS. IGND1

1814. - Volt. low limit(Vo1)


1815. - Phase angle [+/-60]
1816. AC directional [67GD]

ON/OFF
0 - 9999mA
0.1 - 999SEC
MEAS. IGND1/MEAS. IGND2/
MEAS.IGND1&2
IGND2/MEAS. IG1&2
0 - 360deg
ON/OFF

95I

2300. Inrush blocking relay


2301. - limit of DC-portion
2302. - 2. harmonic content
2303. - Te extension time
2304. - Tmax blocking time
2305. - Imax blocking inrush

ON/OFF
0.1 - 99.9%
1 - 99%
30 - 9999ms
0.03 - 99.99SEC
1 - 2999%

ON
0%
15%
100ms
1SEC
955%

64

1700. GROUND DETECTOR RELAY


1701. - LIMIT VALUE UGND1
1702. - DELAY TIME (DFINITE)
1703. RESERVED
1704. - LIMIT VALUE UGND2
1705. - DELAY TIME (DEFINITE)
1706. RESERVED

ON/OFF/RECLOSE
0.1 - 999.9%
0.1 - 999.9SEC

ON
30%
10SEC

0.1 - 999.9%
0.1 - 999.9SEC

30%
12SEC

GEN.:
6.6kV
3,733.33KVA
PF=0.75
FLC=326.6A

RELAY SETTING CHECK LIST.xls

FUNCTION

46 of 90

20%
60deg
OFF

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER

09. Jun. 2005


REMARKS

CT :
500/5A
5P10/15VA
500/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)

1701/1702 :
Bus tie VCB trip
1704/1705 :
Own VCB trip

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.2 INCOMER FROM D/G (AG)
ITEM
INCOMER
FROM D/G

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-1
P-AG-2
P-AG-3

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

FUNCTION
* NOMINAL RATIO VALUES
0200. NOMINAL RATED - Current
0201.
- Voltage
0202.
- Active Power
0203.
- Frequency
0204. CT Feeder -primary side
0205. PT Feeder -primary side
0206.
-secondary side
0207. PT BUS1
-primary side
0208.
-secondary side
0209. PT BUS2
-primary side
0210.
-secondary side
0211. PT GND1
-primary side
0212.
-secondary side
0213. PT GND2
-primary side
0214.
-secondary side
0215. CT GND1
-primary side
0216.
-secondary side
0217. CT GND2
-primary side
0218.
-secondary side
0219. CT DIFF
-primary side
0220. Transformer winding ratio
0221. - Uaux nominal input
0222. - Shunt#1 nominal input
0223. - Shunt#2 nominal input

GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

SETTING RANGE
0 - 9999A
0 - 65000V
0 - 9999KW
50/60HZ
0 -9999A
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 65000V
0 - 9999V
0 - 9999A
0 - 9999A
0 - 9999A
0 - 9999A
0 - 9999A
0.01 - 9.99Wprim/Wsec
24Vdc - 230Vac
24Vdc - 230Vac
24Vdc - 230Vac

SET POINT
256.6A
6600V
2,200KW
60HZ
400A
6600V
110V
6600V
110V
NOT USED
NOT USED
6600V
190V
NOT USED
NOT USED
1
1
NOT USED
NOT USED
400A
1.0
110Vdc
110Vdc
110Vdc

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER

09. Jun. 2005


REMARKS

CT :
400/5A
5P10/15VA
400/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)

0215/0216
EVENT
200/1.5mA fixed
in program.

1101/1102
(Undervolt. 1st)

27

02 Relay Setting check List.xls

1100. Undervoltage relay


1101. - Undervoltage 1.limit
1102. - Delay time (definite)
1103. - Undervoltage 2.limit
1104. - Delay time (definite)
1105. - Minimum startvoltage
1106. - Minimum frequency

ON / OFF / CB ON
0.0 - 99.9%
0.03 - 99.99SEC
0.0 - 99.9%
0.03 - 99.99SEC
0.0 - 99.9 %
0.0 - 99.9HZ

47 of 90

CB ON
90%
5 SEC
50%
1sec
30%
33HZ

stand-by DG
start and
blackout change
after build-up
1103/1104 :
(Undervoltage. 2nd)

VCB trip

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.2 INCOMER FROM D/G (AG)
ITEM

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-1
P-AG-2
P-AG-3

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE
59

INCOMER
FROM D/G
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

81

40

02 Relay Setting check List.xls

FUNCTION

SETTING RANGE

SET POINT

1600. Overvoltage relay


1601. - 1. Limit value
1602. - Time multiplier(TMS)
1603. - Curve shape
1604.
reserved
1605. - 2. Limit value
1606. - Delay time(definite)

ON / OFF / RECLOSE
1 - 9999%
0.01 - 10
NORM. INVERSE/DEFINITE

ON
110%
0.1
NORM. INV.

1 - 9999%
0.01 - 999.99SEC

108%
5sec

2000. Frequency relay


2001. Overfreq. 1.Step limit
2002. - Delay time(definite)c
2003.
reserved
2004. Overfreq. 2.Step limit
2005. - Delay time(definite)c
2006.
reserved
2007. Underfreq.1.Step limit
2008. - Delay time(definite)c
2009.
reserved
2010. Underfreq.2.Step limit
2011. - Delay time(definite)
2012. Undervoltage blocking

ON / OFF / CB ON
100.0 - 199.9%
0.1 - 999.99SEC

CB ON
105%
5SEC

100.0 - 199.9%
0.1 - 999.99SEC

110%
3SEC

0.1 - 99.9%
0.1 - 999.99SEC

97.5%
5SEC

0.1 - 99.9%
0.1 - 999.9SEC
0.1 - 99.9%

90%
10SEC
65%

1170.Loss of excitation relay


1171. reactive power limit
1172. delay time(definite)
1173. min. voltage
1174. Circle 1
1175.
- radius
1176.
- offset
1177.
- delay
1178. Circle 2
1179.
- diameter
1180.
- offset
1181.
- delay

ON / OFF
0.0 - 9999%
0.03 - 99.99SEC
0.7 - 1.0 x RATED VOLTAGE
ON / OFF
2.5 - 300.0OHM
2.5 - 300.0OHM
0.1 - 10.0SEC
ON/OFF
2.5 - 300.0OHM
2.5 - 300.0OHM
0.1 - 10.0SEC

ON
50%
2 SEC
0.7 xRATED VOL
ON
24.2 OHM
2.4 OHM
5SEC
OFF
NOT USED
NOT USED
NOT USED

48 of 90

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER
CT :
400/5A
5P10/15VA
400/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)

09. Jun. 2005


REMARKS
1601/1602
(Overvolt. 1st)
VCB trip
1605/1606
(Overvolt. 2nd)
stand-by DG
start and
blackout change
after voltgae
build-up.
2001/2002
(Overfreq. 1st)
stand-by DG
start and
blackout change
after voltgae
build-up.
2004/2005
(Overfreq. 2nd)
VCB trip
2007/2008
(Underfreq. 1st)

stand-by DG
start and parallel
running
2010/2011
(Underfreq. 2nd)

VCB trip

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.2 INCOMER FROM D/G (AG)
ITEM

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-1
P-AG-2
P-AG-3

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE
50

INCOMER
FROM D/G
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

51

02 Relay Setting check List.xls

FUNCTION

SETTING RANGE

SET POINT

1400. Instantaneous
1401. - 1.limit
1402. - delay time (definite)
1403. reserved
1404. - 2.limit
1405. - delay time (definite)
1406. reserved
1407. - rev. limit
1408. - delay time (definite)
1409. reserved
1410. - inrush blocking

ON / OFF / RECLOSE
2 - 2999.9%
30 - 9999ms

ON
250%
600ms

2.0 - 2999.9%
30 - 9999ms

250%
400ms

2.0 - 2999.9%
30 - 9999ms

250%
50ms

ON/OFF

ON

1500. Time overcurrent relay


1501. - Limit
1502. - Time multiplier(TMS)
1503. - Curve shape
1504. - Reset characteristic
1505. - 1.limit
1506. - Delay time(definite)c
1507. - 2.limit
1508. - Delay time(definite)
1509. - 3.limit
1510. - Delay time(definite)
1511. - Reset character (Th)
1512. - Volt. restain[51VR]
1513.
- Volt low limit

ON / OFF / RECLOSE
2.0 - 2999.9 %
0.03 - 10.00
8 CURVE SHAPES(IDMT)
NONE,DEF./TH,DEF.,CURVE D-F
2.0 - 2999.9%
0.1 - 999.9SEC
2.0 - 2999.9%
0.1 - 999.9SEC
2.9 - 2999.9%
0.1 - 999.9SEC
0 -99SEC
ON/OFF
10 -90%

ON
105%
0.36
VERY INV.
NONE
100%
3 SEC
NOT USED
NOT USED
NOT USED
NOT USED
0 SEC
OFF
NOT USED

49 of 90

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER
CT :
400/5A
5P10/15VA
400/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)

09. Jun. 2005


REMARKS
1401/1402
GEN CB trip
1404/1405
B/T trip
1407/1408
GEN CB trip
(same as 67S)

GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)

1505/1506
Alarm only
before
preferential trip

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.2 INCOMER FROM D/G (AG)
ITEM

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-1
P-DG-2
P-DG-3
P-DG-4

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE
87

INCOMER
FROM D/G
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

02 Relay Setting check List.xls

FUNCTION

SETTING RANGE

SET POINT

2100. Diff. protective relay


2101. - Diff. limit
2102. - Delay time(definite)
2103. - Angle compensation
2104. - reserved
2105. - reserved
2106. - Delay CT-saturation
2107. - Inrush blocking
2108. - Bias limit
2109. - Zero compensation

ON / OFF
1.0 - 99.9%
0.03 - 999.99SEC
NONE,DY1,DY5,DY7,DY11,YD1,

ON
20%
0.1SEC
NONE

0.1 - 9999.9SEC
ON/OFF
0.1 - 999.9%
ON/OFF

0.1SEC
ON
30%
OFF

32

1130. Overload relay


1131. - 1.limit reverse power
1132. - delay time (definite)
1133. - 2.limit reverse power
1134. - delay time (definite)
1135. - 1.limit active power
1136. - delay time (definite)
1137. - 2.limit active power
1138. - delay time (definite)

ON/OFF
0.1 - 99.9%
0.1 - 99.9SEC
0.1 - 99.9%
0.1 - 99.9SEC
0.1 - 199.9%
0.1 - 99.9SEC
0.1 - 199.9%
0.1 - 99.9SEC

ON
10%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED
NOT USED

46

1200. Reverse phase relay


1201. - Limit value
1202. - Time multiplier(TMS)
1203. - Curve shape
1204. - Min. feeder voltage
1205. - 1.limit
1206. - Delay time(definite)
1207. - 2.limit
1208. - Delay time(definite)
1209. - Volt. restrain[51VR]

ON/OFF/RECLOSE
0.0 -99.9%
0.01 - 99.99
NORM. INV. /DEFINITE
1.0 - 99.9%
0.0 - 99.9%
0 - 9999ms
0.0 - 99.9%
0 - 9999ms
ON/OFF

ON
10%
2.0
NORM. INV.
10%
NOT USED
NOT USED
NOT USED
NOT USED
OFF

47

1300. Phase sequence relay


1301. - Limit value
1302. - Delay time(definite)

ON/OFF
1.0 - 199.9%
0.01 - 99.99SEC

ON
20%
2 SEC

50 of 90

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER

09. Jun. 2005


REMARKS

CT :
400/5A
5P10/15VA
400/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)

1131/1132
50% of power
Required to
motor a Gen.

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.2 INCOMER FROM D/G (AG)
ITEM

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-1
P-AG-2
P-AG-3

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE
25/25A

INCOMER
FROM D/G
GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

02 Relay Setting check List.xls

FUNCTION
1000. SYNC. UNIT 1 activ by
1001. - MAX phase angle
1002. - MAX frequency diff.
1003. - MIN frequency
1004. - MAX frequency
1005. - MAX voltage diff.
1006. - MIN voltage
1007. - MAX voltage
1008. - freq.set.pulse time
1009. - freq.set.break time
1010. - speed push after 10s
1011. - volt.set.pulse time
1012. - volt.set.break time
1013. - freq. higher event
1014. - freq. lower event
1015. - volt. higher event
1016. - volt. lower event
1017. - preset analog output
1018. - activate preset by
1019. - closing direction
1020. - CB closing delay
1021. - life/dead cond. check
1022. - min voltage level
1023. - CB sync. ON event
1024. - abnormal bus 1 event

SETTING RANGE
EVENT NO.
0 - 30 deg
0 - 2000mHZ
70.0 - 100.0%
100.0 - 130.0%
0.1 - 30%
70.0 - 100.0%
100.0 - 130.0%
0.1 - 999.9SEC
0.1 - 999.9SEC
0 - 9999ms
0.1 - 999.9SEC
0.1 - 999.9SEC
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT
0.0 -99.9%
0 - 9999(EVENT NUMBER)
UP/DOWN/BOTH
0 -1000ms
ON/OFF
0.0 - 99.9%
EVENT REMINDER FOR OUTPUT
EVENT REMINDER FOR OUTPUT

51 of 90

SET POINT
800
7deg
250mHZ
94%
106%
5%
95%
105%
100SEC
2SEC
500ms
10SEC
2SEC

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER

09. Jun. 2005


REMARKS

CT :
400/5A
5P10/15VA
400/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)

50%
BOTH
100ms
ON
10%

1021/1022
with External
Black out signal

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.2 INCOMER FROM D/G (AG)
ITEM
INCOMER
FROM D/G

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-1
P-AG-2
P-AG-3

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

67GS/GD 1810. AC direction. [67GS]


1811. - Limit value [Ignd1]
1812. - Delay Time (definite)
1813. - Pickup type (67Gx)

SETTING RANGE

SET POINT
ON
1.0mA
0.2SEC
MEAS. IGND1

1814. - Volt. low limit(Vo1)


1815. - Phase angle [+/-60]
1816. AC directional [67GD]

ON/OFF
0 - 9999mA
0.1 - 999SEC
MEAS. IGND1/MEAS. IGND2/
MEAS.IGND1&2
IGND2/MEAS. IG1&2
0 - 360deg
ON/OFF

95I

2300. Inrush blocking relay


2301. - limit of DC-portion
2302. - 2. harmonic content
2303. - Te extension time
2304. - Tmax blocking time
2305. - Imax blocking inrush

ON/OFF
0.1 - 99.9%
1 - 99%
30 - 9999ms
0.03 - 99.99SEC
1 - 2999%

ON
0%
15%
100ms
1SEC
924%

64

1700. GROUND DETECTOR RELAY


1701. - LIMIT VALUE UGND1
1702. - DELAY TIME (DFINITE)
1703. RESERVED
1704. - LIMIT VALUE UGND2
1705. - DELAY TIME (DEFINITE)
1706. RESERVED

ON/OFF/RECLOSE
0.1 - 999.9%
0.1 - 999.9SEC

ON
30%
10SEC

0.1 - 999.9%
0.1 - 999.9SEC

30%
12SEC

GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

02 Relay Setting check List.xls

FUNCTION

52 of 90

20%
60deg
OFF

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER

09. Jun. 2005


REMARKS

CT :
400/5A
5P10/15VA
400/5A
5P10/30VA
(GEN. SIDE)
PT:
6.6RT(3)/0.11RT(3) KV
1.0CL/100VA
(INCOMER SIDE)
GPT:
6.6RT(3)/0.11RT(3)/0.19(3)KV
1.0CL/3P,100/200VA
(BUS SIDE)

1701/1702 :
Bus tie VCB trip
1704/1705 :
Own VCB trip

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.3 NO.1/2 BUS GPT PANEL
ITEM
NO.1/2 BUS
GPT PANEL

PANEL/
FEEDER NO

REV. 0

RELAY
TYPE

ANSI
CODE

HYUNDAI/
HIMAP-FI

27M

FUNCTION

SETTING RANGE

SET POINT

VOLTAGE

0.5 - 1.0Vn

0.8Vn (88V)

TIME (DEFINITE)

0.1 - 10SEC

2SEC

SET VALUE
(PRIM. CT)

09. Jun. 2005

MEASUR.
TRANSFORMER

REMARKS

GPT :

6 .6

0 . 11

0 . 19
KV
3

1.0CL/3P, 100/200VA
(BUS SIDE)

27R

64

RELAY SETTING CHECK LIST.xls

VOLTAGE

0.2 - 0.5Vn

0.2Vn (22V)

TIME (DEFINITE)

0.1 - 10SEC

1SEC

VOLTAGE

0.1 - 0.5Vn

0.15Vn (28.5V)

MODE

INVERSE, INSTANT

INVERSE

TIME

BELOW 50mS (INST.)


0.05 - 10TAP (INVERSE)

0.05 (MIN. SETTING)

53 of 90

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.4 INCOMER FROM D/G & BUS TIE
ITEM
INCOMER
FROM D/G &
BUS TIE

PANEL/
FEEDER NO

REV. 0

RELAY
TYPE

ANSI
CODE

DEIF/
CSQ-2M

25

FUNCTION
, PHASE DIFFERENCE
u, VOLTAGE DIFFERENCE
Td, SYNC. RELAY DELAY
TR, LENGTH OF SYNC. PULSE
TB, DEAD BUS OFFSET VOLTAGE

SETTING RANGE
5-20, STEP=1
1-10%, STEP=1%
0-1SEC, STEP=0.1S
0-1SEC OR , STEP=0.1S

SET POINT
7
5%
NOT USED
0.7 SEC
OFF

SET VALUE
(PRIM. CT)

09. Jun. 2005

MEASUR.
TRANSFORMER

REMARKS

PT :

6 .6

0 .11

KV

1.0CL, 100VA
(INCOMER SIDE
FROM D/G)

6 .6

0 .11

KV

1.0CL/3P, 100/200VA
(BUS SIDE)

DEIF/
FAS-113DG

RELAY SETTING CHECK LIST.xls

25

TN, CONTROL PULSE LENGH


XP, PROPORTIONAL BAND
fSET, SLIP FREQUENCY
UMAX, ACCEPTABLE VOLT. DIFF
TBC, BREAKER CLOSURE TIME

25 ~ 500 ms
2.5 ~ 2.5 HZ
0.1 ~ 0.5 HZ
2 ~ 12% OF UBB
20 ~ 200 ms

54 of 90

500ms
0.5 HZ
0.2 HZ
5% OF UBB
70 ms

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.5 No.1/2/3/4/5/6/7 REEFER TR FEEDER
ITEM
REEFER TR
FEEDER
No.1/2/3/4/5/6/7
REEFER TR
(6.6/0.44KV)
1,600KVA
%Z = 5.85%

PANEL/
FEEDER NO

RELAY
TYPE

ANSI
CODE

P-RTR1-1
P-RTR2-1
P-RTR3-1
P-RTR4-1
P-RTR5-1
P-RTR6-1
P-RTR7-1

HYUNDAI/
HIMAP-FI

27

REV. 0
FUNCTION
VOLTAGE
TIME (DEFINITE)

SETTING RANGE
0.02 - 1.0Vn
0.1 - 10SEC

SET POINT

SET VALUE
(PRIM. CT)

MEASUR.
TRANSFORMER
GPT :

0.8Vn
2SEC

09. Jun. 2005

6 .6

0 . 11

REMARKS

0 . 19
KV
3

1.0CL/3P, 100/200VA
(BUS SIDE)

50

CURRENT
TIME

1 ~ 18In
0.05 ~ 10 SEC

2.8 In
0.2 SEC

560A

CT :
200/5A, 5P10/15VA

1. In = 5A
2. NOTE 1

ZCT :
200/1,5mA
51

CURRENT
MODE
TIME

0.2 ~ 2.4 In
INV.VERY INV., EXTREMELY INV.
0.05 ~ 10TAP

0.9 In
VERY INV
0.56 TAP

50

CURRENT
TIME

1 ~ 18In
0.05 ~ 10 SEC

5.6 In
0.2 SEC

51

CURRENT
MODE
TIME

0.2 ~ 2.4 In
INV.VERY INV., EXTREMELY INV.
0.05 ~ 10TAP

0.9 In
VERY INV
1.4 TAP

67G

CURRENT
VOLTAGE
TIME
ANGLE

1 ~ 10mA
0.1 ~ 0.2VO
0.1 ~ 10SEC
45~ 75

1.0mA
0.2VO
0.2 SEC
60

180A

1,120A

1. In = 5A
2. NOTE 2

180A

NOTE
1. IN CASE OF ONE(1) GENERATOR RUNNING
2. NORMAL OPERATING CONDITION

RELAY SETTING CHECK LIST.xls

55 of 90

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.6 No.1/2 STEP-DOWN TR FEEDER
ITEM
STEP-DOWN TR
FEEDER

REV. 0

PANEL/
FEEDER NO

RELAY
TYPE

ANSI
CODE

P-MTR1-1
P-MTR2-1

HYUNDAI/
HIMAP-T

50

No.1/2
STEP-DOWN TR
(6.6/0.44KV)
3,800KVA
%Z = 6.11%

FUNCTION
CURRENT
TIME

SETTING RANGE
1 ~ 18In
0.05 ~ 10 SEC

SET POINT
1.3 In
0.2 SEC

SET VALUE
(PRIM. CT)
585A

09. Jun. 2005

MEASUR.
TRANSFORMER
GPT :

6 .6

0 . 11

0 . 19
KV
3

REMARKS
1. In = 5A
2. NOTE 1

1.0CL/3P, 100/200VA
(BUS SIDE)
51

CURRENT
MODE
TIME

0.2 ~ 2.4 In
INV.VERY INV., EXTREMELY INV.
0.05 ~ 10TAP

0.62 In
VERY INV
0.3 TAP

50

CURRENT
TIME

1 ~ 18In
0.05 ~ 10 SEC

2.5 In
0.2 SEC

1,125A

CT :
450/5A (1'st), 5P10/15VA
6,000/5A (2'nd), 5P20/40VA

51

CURRENT
MODE
TIME

0.2 ~ 2.4 In
INV.VERY INV., EXTREMELY INV.
0.05 ~ 10TAP

0.95 In
VERY INV
0.4 TAP

427.5A

ZCT :
200/1,5mA

67G

CURRENT
VOLTAGE
TIME
ANGLE

1 ~ 10mA
0.1 ~ 0.2VO
0.1 ~ 10SEC
45~ 75

1.0mA
0.2VO
0.2 SEC
60

87T

PRIMARY CURRENT
SECONDARY CURRENT
INST. RATIO
DIFFERENTIAL RATIO
BIAS RATIO
2ND HARMONIC RATIO
TR ANGLE
ZERO COMP.
TIME

0.2 ~ 1.2In
0.2 ~ 1.2In
500 ~ 1500%
20 ~ 50%
20 ~ 50%
10 ~ 30%

0.75 In
0.85 In
1500%
25%
20%
15%
Ddo
DISABLE
BELOW 50mS

ENABLE, DISABLE
BELOW 50mS

279A

1. In = 5A
2. NOTE 2

NOTE
1. IN CASE OF ONE(1) GENERATOR RUNNING
2. NORMAL OPERATING CONDITION

RELAY SETTING CHECK LIST.xls

56 of 90

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.7 MOTOR FEEDER (No.1/2 MAIN L.O PUMP)
ITEM

PANEL/
FEEDER NO

RELAY
TYPE

P-L01-1
P-L02-1

HYUNDAI/
HIMAP-M

ANSI
CODE
49

MOTOR FEEDER
No.1/2
MAIN L.O PUMP
MOTOR :
6.6KV
355KW
FLC = 37.6A

46

51LR

REV. 0
FUNCTION

SETTING RANGE

SET VALUE
(PRIM. CT)

THERMAL CURRENT
COLD LIMIT
HOT LIMIT
c/h

0.1 ~ 1.2In
0.5 ~ 180SEC
0.5 ~ 180SEC
0.1 ~ 10

0.76 In
6 SEC
3.5 SEC
3

38A

CURRENT
TIME

0.1 ~ 0.5In
0.1 ~ 10SEC

0.12 In
4 SEC

6A

START CURRENT
START TIME
LOCKED ROTOR CURRENT
LOCKED ROTOR TIME

0.2 ~ 14.4In
1.0 ~ 60SEC
0.2 ~ 6.0In
1.0 ~ 4.0SEC

4.7 In
1.5 SEC
2.3 In
2 SEC

235A

425A

50

CURRENT
TIME

0.2 ~18In
BELOW 0.2SEC

8.5 In
0.2 SEC

66

ALLOW TIME
NUMBER OF START
LIMIT TIME
THERMAL LIMIT (d)

1 ~ 60MIN
1~4
1 ~ 60MIN
40 ~ 100%

60 MIN
3
15 MIN
80 %

67G

CURRENT
VOLTAGE
TIME
ANGLE

1 ~ 10mA (FIXED)
0.1 ~ 0.2VO
0.1 ~ 10.0SEC
45~ 75

1.0mA
0.2VO
0.2 SEC
60

PF

RELAY SETTING CHECK LIST.xls

SET POINT

09. Jun. 2005

MEASUR.
TRANSFORMER
GPT :

6 .6

0 . 11

REMARKS

0 . 19
KV
3

1.0CL/3P, 100/200VA
(BUS SIDE)

CT :
50/5A (PRI.), 5P10/15VA

115A
ZCT :
200/1,5mA

100A

57 of 90

SHIP No. H1646-9 / S253-6

5. RELAY SETTING CHECK LIST


5.1 6.6KV MAIN SWBD-1/2
5.1.8 MOTOR FEEDER (BOW THRUSTER MOTOR)
ITEM

PANEL/
FEEDER NO

RELAY
TYPE

P-BT-1

HYUNDAI/
HIMAP-M

ANSI
CODE
49

MOTOR FEEDER
BOW THRUSTER
MOTOR :
6.6KV
2,500KW
FLC = 279.3A

46

51LR

RELAY SETTING CHECK LIST.xls

REV. 0
FUNCTION

SETTING RANGE

SET POINT

SET VALUE
(PRIM. CT)

THERMAL CURRENT
COLD LIMIT
HOT LIMIT
c/h

0.1 ~ 1.2In
0.5 ~ 180SEC
0.5 ~ 180SEC
0.1 ~ 10

0.8 In
1.6 SEC
1.2 SEC
3

280A

CURRENT
TIME

0.1 ~ 0.5In
0.1 ~ 10SEC

0.12 In
4 SEC

42A

START CURRENT
START TIME
LOCKED ROTOR CURRENT
LOCKED ROTOR TIME

0.2 ~ 14.4In
1.0 ~ 60SEC
0.2 ~ 6.0In
1.0 ~ 4.0SEC

1.2 In
20 SEC
1.6 In
2 SEC

420A

805A

50

CURRENT
TIME

0.2 ~18 In
BELOW 0.2SEC

2.3 In
0.05 SEC

66

ALLOW TIME
NUMBER OF START
LIMIT TIME
THERMAL LIMIT (d)

1 ~ 60MIN
1~4
1 ~ 60MIN
40 ~ 100%

60 MIN
4
15 MIN
80 %

67G

CURRENT
VOLTAGE
TIME
ANGLE

1 ~ 10mA (FIXED)
0.1 ~ 0.2V0
0.1 ~ 10.0SEC
45~ 75

1.0mA
0.2VO
0.2 SEC
60

58 of 90

09. Jun. 2005

MEASUR.
TRANSFORMER
GPT :

6 .6

0 . 11

REMARKS

0 . 19
KV
3

1.0CL/3P, 100/200VA
(BUS SIDE)

CT :
350/5A (PRI.), 5P10/15VA

560A
ZCT :
200/1,5mA

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.1 INCOMER FROM D/G (P-DG-1)

ITEM
INCOMER
FROM D/G
(P-DG-1)

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-1

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

GENERAL
PARAMETER

GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A

POWER
MANAGEMENT

PMS SETTING CHECK LIST.xls

FUNCTION

SETTING RANGE

SET POINT

0180. Generator - number


0181.
- priority
0182. Net selectors - 1.event
0183.
- 2.event
0184. Automatic mode
0185. Start release
0186. Start next diesel
0187. Remote start
0188. Remote stop
0189. Load balance after start
0190. Mains parallel operation
0191. Manual mode type

1
1

0900. P.M.
- switch by event
0901.
- characteristic
0902. START - check limits
0903.
- 1.load limit
0904.
- delay
0905.
- 2.load limit
0906.
- delay
0907.
- low frequency
0908.
- delay
0909.
- high current
0910.
- delay
0911. STOP - with priority
0912.
- block by event ;
0913.
- remaining load
0914.
- remaining current
0915.
- delay

0
ON->OFF
SINGLE
90%
15SEC
0
0
0HZ
0SEC
100%
5SEC
LOW
0
70%
0
300SEC

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

505
896
830
801
0
0
0
MANUAL 2

59 of 90

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.1 INCOMER FROM D/G (P-DG-1)

ITEM
INCOMER
FROM D/G
(1G-001)

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-1

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

LOAD
SHARING

SETTING RANGE

SET POINT

0925. SYM. - switch by event


0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point
0935.
- analog input
0936.
- range minimum
0937.
- range maximum
0938.
- next attempt
0939. Allowed load difference
0940.
- delay

0
ON -> OFF
5SEC
4SEC
3%

0945.
- switch by event
0946.
- characteristic
0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point

0
ON -> OFF
60HZ
60HZ
30SEC
80SEC
0.5%

VOLTAGE
REGULATOR

0958.
0959.

0
OFF -> ON

POWER
FACTOR
CONTROLLER
BIG
CONSUMER
REQUEST
(BCR)

0970.
- switch by event
0977. ASYM. - switch by event

0
0

0984. REQUEST 1 by event


0988. REQUEST 2 by event
0992. REQUEST 3 by event
0996. REQUEST 4 by event

838
0
0
0

GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A

FREQUENCY
CONTROLLER

PMS SETTING CHECK LIST.xls

FUNCTION

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

0
OFF->ON
80
NONE
20%
90%
600SEC
0
0

66HZ
54HZ

- switch by event
- characteristic

60 of 90

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.1 INCOMER FROM D/G (P-DG-1)

ITEM
INCOMER
FROM D/G
(P-DG-1)

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-1

HYUNDAI/
HIMAP-BCG

GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A

PMS SETTING CHECK LIST.xls

REV. 0
ANSI
CODE

FUNCTION

SETTING RANGE

SET POINT

BLACKOUT

0230. START - by event


0231.
- mains monitor
0232.
- bus 1 voltage
0233.
- delay
0234.
- diesel
0235. STOP - after blackout
0236.
- delay

533
DOUBLE
20%
1SEC
NEXT
OFF
0

DIESEL
CONTROL

0260. Diesel control


0261. SPEED
- nominal
0262.
- ignition
0263.
- running up
0264.
- overspeed
0265. TACHO
- input
0266. PICKUP
- input
0267.
- impuls / rev.
0268. LIMITS
- n max. diff.
0269.
- n high limit %
0270.
- n low limit
0271. PRELUBRICATE - pulsetime
0272.
- breaktime
0273. Alarmblocking delay

ON
1800RPM
20%
85%
120%
NONE
OFF
0
10%
110%
90%
0
0
10SEC

DIESEL
STARTING
PHASE

0630. PREGLOWING - max time


0631.
- shorten by
0632. START VALVE - max trials
0633.
- fuel valve
0634.
- at RPM=0
0635.
- max time
0636.
- BREAKTIME
0637. RUNNING UP - max time *
0638.
- min volt.
0639. READY TO TAKE LOAD time
0640. SYNCHRONIZING max time * c
0641. Start next after 1.trial

0
0
1
NO
NO
10SEC
10SEC
40SEC
85%
2SEC
60SEC
NO

61 of 90

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.1 INCOMER FROM D/G (P-DG-1)

ITEM
INCOMER
FROM D/G
(P-DG-1)

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-1

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

DIESEL
STOPPING
PHASE

GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A

FUNCTION

SETTING RANGE

0650. Stop abort if last gen.


0651. ALARM PRIO.2 - max time
0652. LOAD REDUCT. - by event
0653.
- loadlimit
0654.
- max time
0655.
- CB OFF
0656. COOLING DOWN - time
0657.
- if prio.2
0658. RUNNING DOWN - max time
0659. FIXED DELAY - time
0660. Stop valve event
0661. Emergency stop event

SET POINT

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

YES
120SEC
836
10%
20SEC
60SEC
NO
30SEC
5SEC

0670/0671
- PT1
PREFERENTIA
L TRIP LIMITS

BUS
ABNORMAL

PMS SETTING CHECK LIST.xls

0670. HIGH CURRENT - 1. limit


0671.
- delay
0672.
- 2. limit
0673.
- delay
0674.
- 3. limit
0675.
- delay
0676.
- 4. limit
0677.
- delay c
0678. LOW FREQUENCY - limit
0679.
- delay
0680.HIGH LOAD
- limit
0681.
- delay

100%
5SEC
105%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
57HZ
5SEC
110%
1SEC

0682.ABNORMAL BUS-overfreq.
0683.
- underfrequency
0684.
- overvoltage
0685.
- undervoltage
0686.
- delay
0687. PREF.TRIP -check limits

63HZ
57HZ
105%
95%
5SEC
OFF

62 of 90

0672/0673
- PT2
0678/0679
PT1- 95% 5SEC
PT2- 95% 10SEC
0680/0681
HIGH ACTIVE
POWER:
ST-BY gen. start
and
parallel running

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.1 INCOMER FROM D/G (P-DG-1)

ITEM
INCOMER
FROM D/G
(P-DG-1)

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-1

HYUNDAI/
HIMAP-BCG

GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A

PMS SETTING CHECK LIST.xls

REV. 0
ANSI
CODE

ADDITIONAL
LIMITS

FUNCTION

SETTING RANGE

0280. OVERSPEED
- limit
0281.
- delay
0282. OVERVOLTAGE - limit
0283.
- delay
0284. OVERCURRENT - limit
0285.
- delay
0286. OVERLOAD (OWN) - limit
0287.
- delay
0288. OVERLOAD (NET) - limit
0289.
- delay
0290. PF CAP. LOW - limit
0291.
- delay
0292. PF IND. LOW - limit
0293.
- delay
0294. REVERSE POWER - limit
0295.
- delay
0296. REACT.POWER IND.- limit
0297.
- delay c
0298. NETLOAD excl.OWN- limit %
0299.
- delay

SET POINT
0
0
95%
0.1SEC
0
0
75%
0.1SEC
75%
0.1SEC
0
0
0
0
0
0
0
0
90%
0.1SEC

63 of 90

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

0282:
Voltage Build-up
for synchronizing

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.2 INCOMER FROM D/G (P-DG-2)

ITEM
INCOMER
FROM D/G
(P-DG-2)

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-2

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

GENERAL
PARAMETER

GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A

POWER
MANAGEMENT

PMS SETTING CHECK LIST.xls

FUNCTION

SETTING RANGE

SET POINT

0180. Generator - number


0181.
- priority
0182. Net selectors - 1.event
0183.
- 2.event
0184. Automatic mode
0185. Start release
0186. Start next diesel
0187. Remote start
0188. Remote stop
0189. Load balance after start
0190. Mains parallel operation
0191. Manual mode type

2
2

0900. P.M.
- switch by event
0901.
- characteristic
0902. START - check limits
0903.
- 1.load limit
0904.
- delay
0905.
- 2.load limit
0906.
- delay
0907.
- low frequency
0908.
- delay
0909.
- high current
0910.
- delay
0911. STOP - with priority
0912.
- block by event ;
0913.
- remaining load
0914.
- remaining current
0915.
- delay

0
ON->OFF
SINGLE
90%
15SEC
0
0
0HZ
0SEC
100%
5SEC
LOW
0
70%
0
300SEC

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

505
896
830
801
0
0
0
MANUAL 2

64 of 90

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.2 INCOMER FROM D/G (P-DG-2)

ITEM
INCOMER
FROM D/G
(P-DG-2)

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-2

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

LOAD
SHARING

SETTING RANGE

SET POINT

0925. SYM. - switch by event


0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point
0935.
- analog input
0936.
- range minimum
0937.
- range maximum
0938.
- next attempt
0939. Allowed load difference
0940.
- delay

0
ON -> OFF
5SEC
4SEC
3%

0945.
- switch by event
0946.
- characteristic
0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point

0
ON -> OFF
60HZ
60HZ
30SEC
80SEC
0.5%

VOLTAGE
REGULATOR

0958.
0959.

0
OFF -> ON

POWER
FACTOR
CONTROLLER
BIG
CONSUMER
REQUEST
(BCR)

0970.
- switch by event
0977. ASYM. - switch by event

0
0

0984. REQUEST 1 by event


0988. REQUEST 2 by event
0992. REQUEST 3 by event
0996. REQUEST 4 by event

0
0
0
0

GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A

FREQUENCY
CONTROLLER

PMS SETTING CHECK LIST.xls

FUNCTION

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

0
OFF->ON
80
NONE
20%
90%
600SEC
0
0

66HZ
54HZ

- switch by event
- characteristic

65 of 90

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.2 INCOMER FROM D/G (P-DG-2)

ITEM
INCOMER
FROM D/G
(P-DG-2)

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-2

HYUNDAI/
HIMAP-BCG

GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A

PMS SETTING CHECK LIST.xls

REV. 0
ANSI
CODE

FUNCTION

SETTING RANGE

SET POINT

BLACKOUT

0230. START - by event


0231.
- mains monitor
0232.
- bus 1 voltage
0233.
- delay
0234.
- diesel
0235. STOP - after blackout
0236.
- delay

533
DOUBLE
20%
1SEC
NEXT
OFF
0

DIESEL
CONTROL

0260. Diesel control


0261. SPEED
- nominal
0262.
- ignition
0263.
- running up
0264.
- overspeed
0265. TACHO
- input
0266. PICKUP
- input
0267.
- impuls / rev.
0268. LIMITS
- n max. diff.
0269.
- n high limit %
0270.
- n low limit
0271. PRELUBRICATE - pulsetime
0272.
- breaktime
0273. Alarmblocking delay

ON
1800RPM
20%
85%
120%
NONE
OFF
0
10%
110%
90%
0
0
10SEC

DIESEL
STARTING
PHASE

0630. PREGLOWING - max time


0631.
- shorten by
0632. START VALVE - max trials
0633.
- fuel valve
0634.
- at RPM=0
0635.
- max time
0636.
- BREAKTIME
0637. RUNNING UP - max time *
0638.
- min volt.
0639. READY TO TAKE LOAD time
0640. SYNCHRONIZING max time * c
0641. Start next after 1.trial

0
0
1
NO
NO
10SEC
10SEC
40SEC
85%
2SEC
60SEC
NO

66 of 90

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.2 INCOMER FROM D/G (P-DG-2)

ITEM
INCOMER
FROM D/G
(P-DG-2)

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-2

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

DIESEL
STOPPING
PHASE

GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.5A

FUNCTION

SETTING RANGE

0650. Stop abort if last gen.


0651. ALARM PRIO.2 - max time
0652. LOAD REDUCT. - by event
0653.
- loadlimit
0654.
- max time
0655.
- CB OFF
0656. COOLING DOWN - time
0657.
- if prio.2
0658. RUNNING DOWN - max time
0659. FIXED DELAY - time
0660. Stop valve event
0661. Emergency stop event

SET POINT

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

YES
120SEC
836
10%
20SEC
60SEC
NO
30SEC
5SEC

0670/0671
- PT1
PREFERENTIA
L TRIP LIMITS

BUS
ABNORMAL

PMS SETTING CHECK LIST.xls

0670. HIGH CURRENT - 1. limit


0671.
- delay
0672.
- 2. limit
0673.
- delay
0674.
- 3. limit
0675.
- delay
0676.
- 4. limit
0677.
- delay c
0678. LOW FREQUENCY - limit
0679.
- delay
0680.HIGH LOAD
- limit
0681.
- delay

100%
5SEC
105%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
57HZ
5SEC
110%
1SEC

0682.ABNORMAL BUS-overfreq.
0683.
- underfrequency
0684.
- overvoltage
0685.
- undervoltage
0686.
- delay
0687. PREF.TRIP -check limits

63HZ
57HZ
105%
95%
5SEC
OFF

67 of 90

0672/0673
- PT2
0678/0679
PT1- 95% 5SEC
PT2- 95% 10SEC
0680/0681
HIGH ACTIVE
POWER:
ST-BY gen. start
and
parallel running

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.2 INCOMER FROM D/G (P-DG-2)

ITEM
INCOMER
FROM D/G
(P-DG-2)

PANEL/
FEEDER NO

RELAY
TYPE

P-DG-2

HYUNDAI/
HIMAP-BCG

GEN.:
6.6kV
3,733.33kVA
PF=0.75
FLC=326.6A

PMS SETTING CHECK LIST.xls

REV. 0
ANSI
CODE

ADDITIONAL
LIMITS

FUNCTION

SETTING RANGE

0280. OVERSPEED
- limit
0281.
- delay
0282. OVERVOLTAGE - limit
0283.
- delay
0284. OVERCURRENT - limit
0285.
- delay
0286. OVERLOAD (OWN) - limit
0287.
- delay
0288. OVERLOAD (NET) - limit
0289.
- delay
0290. PF CAP. LOW - limit
0291.
- delay
0292. PF IND. LOW - limit
0293.
- delay
0294. REVERSE POWER - limit
0295.
- delay
0296. REACT.POWER IND.- limit
0297.
- delay c
0298. NETLOAD excl.OWN- limit %
0299.
- delay

SET POINT
0
0
95%
0.1SEC
0
0
75%
0.1SEC
75%
0.1SEC
0
0
0
0
0
0
0
0
90%
0.1SEC

68 of 90

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

0282:
Voltage Build-up
for synchronizing

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.3 INCOMER FROM D/G (P-AG-1)

ITEM
INCOMER
FROM D/G
(P-AG-1)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-1

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

GENERAL
PARAMETER

GEN.:
6.6kV
2,933.33kVA
PF=0.75
FLC=256.6A

POWER
MANAGEMENT

PMS SETTING CHECK LIST.xls

FUNCTION

SETTING RANGE

SET POINT

0180. Generator - number


0181.
- priority
0182. Net selectors - 1.event
0183.
- 2.event
0184. Automatic mode
0185. Start release
0186. Start next diesel
0187. Remote start
0188. Remote stop
0189. Load balance after start
0190. Mains parallel operation
0191. Manual mode type

3
3

0900. P.M.
- switch by event
0901.
- characteristic
0902. START - check limits
0903.
- 1.load limit
0904.
- delay
0905.
- 2.load limit
0906.
- delay
0907.
- low frequency
0908.
- delay
0909.
- high current
0910.
- delay
0911. STOP - with priority
0912.
- block by event ;
0913.
- remaining load
0914.
- remaining current
0915.
- delay

0
ON->OFF
SINGLE
90%
15SEC
0
0
0HZ
0SEC
100%
5SEC
LOW
0
70%
0
300SEC

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

505
896
830
801
0
0
0
MANUAL 2

69 of 90

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.3 INCOMER FROM D/G (P-AG-1)

ITEM
INCOMER
FROM D/G
(P-AG-1)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-1

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

LOAD
SHARING

SETTING RANGE

SET POINT

0925. SYM. - switch by event


0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point
0935.
- analog input
0936.
- range minimum
0937.
- range maximum
0938.
- next attempt
0939. Allowed load difference
0940.
- delay

0
ON -> OFF
5SEC
4SEC
3%

0945.
- switch by event
0946.
- characteristic
0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point

0
ON -> OFF
60HZ
60HZ
30SEC
80SEC
0.5%

VOLTAGE
REGULATOR

0958.
0959.

0
OFF -> ON

POWER
FACTOR
CONTROLLER
BIG
CONSUMER
REQUEST
(BCR)

0970.
- switch by event
0977. ASYM. - switch by event

0
0

0984. REQUEST 1 by event


0988. REQUEST 2 by event
0992. REQUEST 3 by event
0996. REQUEST 4 by event

0
0
0
0

GEN.:
6.6kV
2,933.33kVA
PF=0.75
FLC=256.6A

FREQUENCY
CONTROLLER

PMS SETTING CHECK LIST.xls

FUNCTION

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

0
OFF->ON
80
NONE
20%
90%
600SEC
0
0

66HZ
54HZ

- switch by event
- characteristic

70 of 90

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.3 INCOMER FROM D/G (P-AG-1)

ITEM
INCOMER
FROM D/G
(P-AG-1)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-1

HYUNDAI/
HIMAP-BCG

GEN.:
6.6kV
2,933.33kVA
PF=0.75
FLC=256.6A

PMS SETTING CHECK LIST.xls

REV. 0
ANSI
CODE

FUNCTION

SETTING RANGE

SET POINT

BLACKOUT

0230. START - by event


0231.
- mains monitor
0232.
- bus 1 voltage
0233.
- delay
0234.
- diesel
0235. STOP - after blackout
0236.
- delay

533
DOUBLE
20%
1SEC
NEXT
OFF
0

DIESEL
CONTROL

0260. Diesel control


0261. SPEED
- nominal
0262.
- ignition
0263.
- running up
0264.
- overspeed
0265. TACHO
- input
0266. PICKUP
- input
0267.
- impuls / rev.
0268. LIMITS
- n max. diff.
0269.
- n high limit %
0270.
- n low limit
0271. PRELUBRICATE - pulsetime
0272.
- breaktime
0273. Alarmblocking delay

ON
1800RPM
20%
85%
120%
NONE
OFF
0
10%
110%
90%
0
0
10SEC

DIESEL
STARTING
PHASE

0630. PREGLOWING - max time


0631.
- shorten by
0632. START VALVE - max trials
0633.
- fuel valve
0634.
- at RPM=0
0635.
- max time
0636.
- BREAKTIME
0637. RUNNING UP - max time *
0638.
- min volt.
0639. READY TO TAKE LOAD time
0640. SYNCHRONIZING max time * c
0641. Start next after 1.trial

0
0
1
NO
NO
10SEC
10SEC
40SEC
85%
2SEC
60SEC
NO

71 of 90

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.3 INCOMER FROM D/G (P-AG-1)

ITEM
INCOMER
FROM D/G
(P-AG-1)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-1

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

DIESEL
STOPPING
PHASE

GEN.:
6.6kV
2,933.33kVA
PF=0.75
FLC=256.6A

FUNCTION

SETTING RANGE

0650. Stop abort if last gen.


0651. ALARM PRIO.2 - max time
0652. LOAD REDUCT. - by event
0653.
- loadlimit
0654.
- max time
0655.
- CB OFF
0656. COOLING DOWN - time
0657.
- if prio.2
0658. RUNNING DOWN - max time
0659. FIXED DELAY - time
0660. Stop valve event
0661. Emergency stop event

SET POINT

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

YES
120SEC
836
10%
20SEC
60SEC
NO
30SEC
5SEC

0670/0671
- PT1
PREFERENTIA
L TRIP LIMITS

BUS
ABNORMAL

PMS SETTING CHECK LIST.xls

0670. HIGH CURRENT - 1. limit


0671.
- delay
0672.
- 2. limit
0673.
- delay
0674.
- 3. limit
0675.
- delay
0676.
- 4. limit
0677.
- delay c
0678. LOW FREQUENCY - limit
0679.
- delay
0680.HIGH LOAD
- limit
0681.
- delay

100%
5SEC
105%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
57HZ
5SEC
110%
1SEC

0682.ABNORMAL BUS-overfreq.
0683.
- underfrequency
0684.
- overvoltage
0685.
- undervoltage
0686.
- delay
0687. PREF.TRIP -check limits

63HZ
57HZ
105%
95%
5SEC
OFF

72 of 90

0672/0673
- PT2
0678/0679
PT1- 95% 5SEC
PT2- 95% 10SEC
0680/0681
HIGH ACTIVE
POWER:
ST-BY gen. start
and
parallel running

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.3 INCOMER FROM D/G (P-AG-1)

ITEM
INCOMER
FROM D/G
(P-AG-1)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-1

HYUNDAI/
HIMAP-BCG

GEN.:
6.6kV
2,933.33kVA
PF=0.75
FLC=256.6A

PMS SETTING CHECK LIST.xls

REV. 0
ANSI
CODE

ADDITIONAL
LIMITS

FUNCTION

SETTING RANGE

0280. OVERSPEED
- limit
0281.
- delay
0282. OVERVOLTAGE - limit
0283.
- delay
0284. OVERCURRENT - limit
0285.
- delay
0286. OVERLOAD (OWN) - limit
0287.
- delay
0288. OVERLOAD (NET) - limit
0289.
- delay
0290. PF CAP. LOW - limit
0291.
- delay
0292. PF IND. LOW - limit
0293.
- delay
0294. REVERSE POWER - limit
0295.
- delay
0296. REACT.POWER IND.- limit
0297.
- delay c
0298. NETLOAD excl.OWN- limit %
0299.
- delay

SET POINT
0
0
95%
0.1SEC
0
0
75%
0.1SEC
75%
0.1SEC
0
0
0
0
0
0
0
0
90%
0.1SEC

73 of 90

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

0282:
Voltage Build-up
for synchronizing

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.4 INCOMER FROM D/G (P-AG-2)

ITEM
INCOMER
FROM D/G
(P-AG-2)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-2

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

GENERAL
PARAMETER

GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

POWER
MANAGEMENT

PMS SETTING CHECK LIST.xls

FUNCTION

SETTING RANGE

SET POINT

0180. Generator - number


0181.
- priority
0182. Net selectors - 1.event
0183.
- 2.event
0184. Automatic mode
0185. Start release
0186. Start next diesel
0187. Remote start
0188. Remote stop
0189. Load balance after start
0190. Mains parallel operation
0191. Manual mode type

4
4

0900. P.M.
- switch by event
0901.
- characteristic
0902. START - check limits
0903.
- 1.load limit
0904.
- delay
0905.
- 2.load limit
0906.
- delay
0907.
- low frequency
0908.
- delay
0909.
- high current
0910.
- delay
0911. STOP - with priority
0912.
- block by event ;
0913.
- remaining load
0914.
- remaining current
0915.
- delay

0
ON->OFF
SINGLE
90%
15SEC
0
0
0HZ
0SEC
100%
5SEC
LOW
0
70%
0
300SEC

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

505
896
830
801
0
0
0
MANUAL 2

74 of 90

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.4 INCOMER FROM D/G (P-AG-2)

ITEM
INCOMER
FROM D/G
(P-AG-2)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-2

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

LOAD
SHARING

SETTING RANGE

SET POINT

0925. SYM. - switch by event


0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point
0935.
- analog input
0936.
- range minimum
0937.
- range maximum
0938.
- next attempt
0939. Allowed load difference
0940.
- delay

0
ON -> OFF
5SEC
4SEC
3%

0945.
- switch by event
0946.
- characteristic
0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point

0
ON -> OFF
60HZ
60HZ
30SEC
80SEC
0.5%

VOLTAGE
REGULATOR

0958.
0959.

0
OFF -> ON

POWER
FACTOR
CONTROLLER
BIG
CONSUMER
REQUEST
(BCR)

0970.
- switch by event
0977. ASYM. - switch by event

0
0

0984. REQUEST 1 by event


0988. REQUEST 2 by event
0992. REQUEST 3 by event
0996. REQUEST 4 by event

0
0
0
0

GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

FREQUENCY
CONTROLLER

PMS SETTING CHECK LIST.xls

FUNCTION

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

0
OFF->ON
80
NONE
20%
90%
600SEC
0
0

66HZ
54HZ

- switch by event
- characteristic

75 of 90

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.4 INCOMER FROM D/G (P-AG-2)

ITEM
INCOMER
FROM D/G
(P-AG-2)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-2

HYUNDAI/
HIMAP-BCG

GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

PMS SETTING CHECK LIST.xls

REV. 0
ANSI
CODE

FUNCTION

SETTING RANGE

SET POINT

BLACKOUT

0230. START - by event


0231.
- mains monitor
0232.
- bus 1 voltage
0233.
- delay
0234.
- diesel
0235. STOP - after blackout
0236.
- delay

533
DOUBLE
20%
1SEC
NEXT
OFF
0

DIESEL
CONTROL

0260. Diesel control


0261. SPEED
- nominal
0262.
- ignition
0263.
- running up
0264.
- overspeed
0265. TACHO
- input
0266. PICKUP
- input
0267.
- impuls / rev.
0268. LIMITS
- n max. diff.
0269.
- n high limit %
0270.
- n low limit
0271. PRELUBRICATE - pulsetime
0272.
- breaktime
0273. Alarmblocking delay

ON
1800RPM
20%
85%
120%
NONE
OFF
0
10%
110%
90%
0
0
10SEC

DIESEL
STARTING
PHASE

0630. PREGLOWING - max time


0631.
- shorten by
0632. START VALVE - max trials
0633.
- fuel valve
0634.
- at RPM=0
0635.
- max time
0636.
- BREAKTIME
0637. RUNNING UP - max time *
0638.
- min volt.
0639. READY TO TAKE LOAD time
0640. SYNCHRONIZING max time * c
0641. Start next after 1.trial

0
0
1
NO
NO
10SEC
10SEC
40SEC
85%
2SEC
60SEC
NO

76 of 90

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.4 INCOMER FROM D/G (P-AG-2)

ITEM
INCOMER
FROM D/G
(P-AG-2)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-2

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

DIESEL
STOPPING
PHASE

GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

FUNCTION

SETTING RANGE

0650. Stop abort if last gen.


0651. ALARM PRIO.2 - max time
0652. LOAD REDUCT. - by event
0653.
- loadlimit
0654.
- max time
0655.
- CB OFF
0656. COOLING DOWN - time
0657.
- if prio.2
0658. RUNNING DOWN - max time
0659. FIXED DELAY - time
0660. Stop valve event
0661. Emergency stop event

SET POINT

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

YES
120SEC
836
10%
20SEC
60SEC
NO
30SEC
5SEC

0670/0671
- PT1
PREFERENTIA
L TRIP LIMITS

BUS
ABNORMAL

PMS SETTING CHECK LIST.xls

0670. HIGH CURRENT - 1. limit


0671.
- delay
0672.
- 2. limit
0673.
- delay
0674.
- 3. limit
0675.
- delay
0676.
- 4. limit
0677.
- delay c
0678. LOW FREQUENCY - limit
0679.
- delay
0680.HIGH LOAD
- limit
0681.
- delay

100%
5SEC
105%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
57HZ
5SEC
110%
1SEC

0682.ABNORMAL BUS-overfreq.
0683.
- underfrequency
0684.
- overvoltage
0685.
- undervoltage
0686.
- delay
0687. PREF.TRIP -check limits

63HZ
57HZ
105%
95%
5SEC
OFF

77 of 90

0672/0673
- PT2
0678/0679
PT1- 95% 5SEC
PT2- 95% 10SEC
0680/0681
HIGH ACTIVE
POWER:
ST-BY gen. start
and
parallel running

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.4 INCOMER FROM D/G (P-AG-2)

ITEM
INCOMER
FROM D/G
(P-AG-2)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-2

HYUNDAI/
HIMAP-BCG

GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

PMS SETTING CHECK LIST.xls

REV. 0
ANSI
CODE

ADDITIONAL
LIMITS

FUNCTION

SETTING RANGE

0280. OVERSPEED
- limit
0281.
- delay
0282. OVERVOLTAGE - limit
0283.
- delay
0284. OVERCURRENT - limit
0285.
- delay
0286. OVERLOAD (OWN) - limit
0287.
- delay
0288. OVERLOAD (NET) - limit
0289.
- delay
0290. PF CAP. LOW - limit
0291.
- delay
0292. PF IND. LOW - limit
0293.
- delay
0294. REVERSE POWER - limit
0295.
- delay
0296. REACT.POWER IND.- limit
0297.
- delay c
0298. NETLOAD excl.OWN- limit %
0299.
- delay

SET POINT
0
0
95%
0.1SEC
0
0
75%
0.1SEC
75%
0.1SEC
0
0
0
0
0
0
0
0
90%
0.1SEC

78 of 90

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

0282:
Voltage Build-up
for synchronizing

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.5 INCOMER FROM D/G (P-AG-3)

ITEM
INCOMER
FROM D/G
(P-AG-3)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-3

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

GENERAL
PARAMETER

GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

POWER
MANAGEMENT

PMS SETTING CHECK LIST.xls

FUNCTION

SETTING RANGE

SET POINT

0180. Generator - number


0181.
- priority
0182. Net selectors - 1.event
0183.
- 2.event
0184. Automatic mode
0185. Start release
0186. Start next diesel
0187. Remote start
0188. Remote stop
0189. Load balance after start
0190. Mains parallel operation
0191. Manual mode type

5
5

0900. P.M.
- switch by event
0901.
- characteristic
0902. START - check limits
0903.
- 1.load limit
0904.
- delay
0905.
- 2.load limit
0906.
- delay
0907.
- low frequency
0908.
- delay
0909.
- high current
0910.
- delay
0911. STOP - with priority
0912.
- block by event ;
0913.
- remaining load
0914.
- remaining current
0915.
- delay

0
ON->OFF
SINGLE
90%
15SEC
0
0
0HZ
0SEC
100%
5SEC
LOW
0
70%
0
300SEC

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

505
896
830
801
0
0
0
MANUAL 2

79 of 90

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.5 INCOMER FROM D/G (P-AG-3)

ITEM
INCOMER
FROM D/G
(P-AG-3)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-3

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

LOAD
SHARING

SETTING RANGE

SET POINT

0925. SYM. - switch by event


0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point
0935.
- analog input
0936.
- range minimum
0937.
- range maximum
0938.
- next attempt
0939. Allowed load difference
0940.
- delay

0
ON -> OFF
5SEC
4SEC
3%

0945.
- switch by event
0946.
- characteristic
0926.
- characteristic
0927.
- break time
0928.
- pulse time
0929.
- deadband
0930.
- higher event
0931.
- lower event
0932. ASYM. - switch by event
0933.
- characteristic
0934.
- set point

0
ON -> OFF
60HZ
60HZ
30SEC
80SEC
0.5%

VOLTAGE
REGULATOR

0958.
0959.

0
OFF -> ON

POWER
FACTOR
CONTROLLER
BIG
CONSUMER
REQUEST
(BCR)

0970.
- switch by event
0977. ASYM. - switch by event

0
0

0984. REQUEST 1 by event


0988. REQUEST 2 by event
0992. REQUEST 3 by event
0996. REQUEST 4 by event

0
0
0
0

GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

FREQUENCY
CONTROLLER

PMS SETTING CHECK LIST.xls

FUNCTION

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

0
OFF->ON
80
NONE
20%
90%
600SEC
0
0

66HZ
54HZ

- switch by event
- characteristic

80 of 90

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.5 INCOMER FROM D/G (P-AG-3)

PMS SETTING CHECK LIST.xls

REV. 0

81 of 90

09. Jun. 2005

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.5 INCOMER FROM D/G (P-AG-3)

ITEM
INCOMER
FROM D/G
(P-AG-3)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-3

HYUNDAI/
HIMAP-BCG

GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

PMS SETTING CHECK LIST.xls

REV. 0
ANSI
CODE

FUNCTION

SETTING RANGE

SET POINT

BLACKOUT

0230. START - by event


0231.
- mains monitor
0232.
- bus 1 voltage
0233.
- delay
0234.
- diesel
0235. STOP - after blackout
0236.
- delay

533
DOUBLE
20%
1SEC
NEXT
OFF
0

DIESEL
CONTROL

0260. Diesel control


0261. SPEED
- nominal
0262.
- ignition
0263.
- running up
0264.
- overspeed
0265. TACHO
- input
0266. PICKUP
- input
0267.
- impuls / rev.
0268. LIMITS
- n max. diff.
0269.
- n high limit %
0270.
- n low limit
0271. PRELUBRICATE - pulsetime
0272.
- breaktime
0273. Alarmblocking delay

ON
1800RPM
20%
85%
120%
NONE
OFF
0
10%
110%
90%
0
0
10SEC

DIESEL
STARTING
PHASE

0630. PREGLOWING - max time


0631.
- shorten by
0632. START VALVE - max trials
0633.
- fuel valve
0634.
- at RPM=0
0635.
- max time
0636.
- BREAKTIME
0637. RUNNING UP - max time *
0638.
- min volt.
0639. READY TO TAKE LOAD time
0640. SYNCHRONIZING max time * c
0641. Start next after 1.trial

0
0
1
NO
NO
10SEC
10SEC
40SEC
85%
2SEC
60SEC
NO

82 of 90

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.5 INCOMER FROM D/G (P-AG-3)

PMS SETTING CHECK LIST.xls

REV. 0

83 of 90

09. Jun. 2005

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.5 INCOMER FROM D/G (P-AG-3)

ITEM
INCOMER
FROM D/G
(P-AG-3)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-3

HYUNDAI/
HIMAP-BCG

REV. 0
ANSI
CODE

DIESEL
STOPPING
PHASE

GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

FUNCTION

SETTING RANGE

SET POINT

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

YES
120SEC
836
10%
20SEC

0650. Stop abort if last gen.


0651. ALARM PRIO.2 - max time
0652. LOAD REDUCT. - by event
0653.
- loadlimit
0654.
- max time
0655.
- CB OFF
0656. COOLING DOWN - time
0657.
- if prio.2
0658. RUNNING DOWN - max time
0659. FIXED DELAY - time
0660. Stop valve event
0661. Emergency stop event

60SEC
NO
30SEC
5SEC

0670/0671
- PT1
PREFERENTIA
L TRIP LIMITS

BUS
ABNORMAL

PMS SETTING CHECK LIST.xls

0670. HIGH CURRENT - 1. limit


0671.
- delay
0672.
- 2. limit
0673.
- delay
0674.
- 3. limit
0675.
- delay
0676.
- 4. limit
0677.
- delay c
0678. LOW FREQUENCY - limit
0679.
- delay
0680.HIGH LOAD
- limit
0681.
- delay

100%
5SEC
105%
5SEC
NOT USED
NOT USED
NOT USED
NOT USED
57HZ
5SEC
110%
1SEC

0682.ABNORMAL BUS-overfreq.
0683.
- underfrequency
0684.
- overvoltage
0685.
- undervoltage
0686.
- delay
0687. PREF.TRIP -check limits

63HZ
57HZ
105%
95%
5SEC
OFF

84 of 90

0672/0673
- PT2
0678/0679
PT1- 95% 5SEC
PT2- 95% 10SEC
0680/0681
HIGH ACTIVE
POWER:
ST-BY gen. start
and
parallel running

SHIP No. H1646-9 / S253-6

6. PMS SETTING CHECK LIST


6.1 6.6KV MAIN SWBD-1/2
6.1.5 INCOMER FROM D/G (P-AG-3)

ITEM
INCOMER
FROM D/G
(P-AG-3)

PANEL/
FEEDER NO

RELAY
TYPE

P-AG-3

HYUNDAI/
HIMAP-BCG

GEN.:
6.6kV
2,933.33KVA
PF=0.75
FLC=256.6A

PMS SETTING CHECK LIST.xls

REV. 0
ANSI
CODE

ADDITIONAL
LIMITS

FUNCTION

SETTING RANGE

SET POINT
0
0
95%
0.1SEC
0
0
75%
0.1SEC
75%
0.1SEC
0
0
0
0
0
0
0
0
90%
0.1SEC

0280. OVERSPEED
- limit
0281.
- delay
0282. OVERVOLTAGE - limit
0283.
- delay
0284. OVERCURRENT - limit
0285.
- delay
0286. OVERLOAD (OWN) - limit
0287.
- delay
0288. OVERLOAD (NET) - limit
0289.
- delay
0290. PF CAP. LOW - limit
0291.
- delay
0292. PF IND. LOW - limit
0293.
- delay
0294. REVERSE POWER - limit
0295.
- delay
0296. REACT.POWER IND.- limit
0297.
- delay c
0298. NETLOAD excl.OWN- limit %
0299.
- delay

85 of 90

SET VALUE
MEASUR.
(PRIM. CT) TRANSFORMER

09. Jun. 2005

REMARKS

0282:
Voltage Build-up
for synchronizing

SHIP No. H1646-9 / S253-6