Relay Coordination
Relay Coordination
Relay Coordination
1
CONTENT
INTRODUCTION
STANDARDS OF RELAY COORDINATION
PROTECTION SYSTEM DESIGN
SIGNIFICANCE OF RELAY AND RELEASE
OVERCURRENT PROTECTION
BASICS OF CURRENT TRANSFORMER AND ITS CONNECTIONS
MEASURED AND DERIVED EARTH FAULT
RELAY TIMEING AND SETTING
LV, MV AND HV PROTECTION
DIFFERENCE BETWEEN ELCB AND RCCB
RELEASE AND RELAY
TRUE FAULT CURRENT
RELAY CASE STUDY
DIRECTIONAL RELAY
RINGMAIN RELAY
2
INTRODUCTION
Relay coordination is an important aspect in the protection system
design as coordination schemes must guarantee fast, selective, and reliable relay
operation to isolate the power system faulted sections. Thus, the relay coordination
problem is formulated, for a real time distribution system is simulated using ETAP .
when the fault is occurred the relay coordination is used to trip the function and
protect the device
A relay is switching device as it works to isolate or change the state of an
electric circuit (Circuit Breaker) from one state to another.
One end of Current transformer (C.T) is connected to a branch in power
network and another end are connected to relay. CT measures the current
in the network, and once the current varies above or below the acceptable
Relay works on the principle of electromagnetic induction. When the
electromagnet is applied with some current, it induces a magnetic field around it.
Above image shows working of the relay. A switch is used to apply DC current to
the load
Relay coordination study and analysis is performed to make sure that safety
operation of the system is functioning correctly and to avoid the nuisance
tripping, as protection is a major concern in any industry and they rely on
protective devices for the same.
3
Needs for relay coordination
It is used to protect the device from fault
Cost maintenance
It is also used for a human safety purpose
Protection system
Unit protection
Non unit protection
Unit protection (unit scheme)
Unit protection is used to protect the all parts in Transformer, Transmission
lines, Motor, Generator or Busbars
Transmission lines is used to protect the fault from the distance relay
Differential relay operates internal method only
Kirchhoff’s current law is used to sum of the incoming current is equal to
the sum of the outgoing current
Non unit protection (non unit scheme)
It is a backup protection device and it is also depending on the current only
and it is classified into two main protections
Time graded over current protection (DMT)
Current graded over current protection (IDMT)
DMT (Definite Minimum Time)
DMT (Definite Mean Time) Relay – It operates when current in the circuit
exceeds a set value & exceeded value of current remains in the circuit for a
4
period/duration set in the relay. Instantaneous rely – It operates
instantaneously/immediately when current in the circuit exceeds the set value/pick
up of the relay.
IDMT (Inverse Definite Minimum Time)
IDMT relay is inverse definite minimum time relay. It is one in which Time of
operation is inversely proportional to magnitude of fault current near pickup value
and becomes substantially constant slightly above the pickup value of the Relay.
Significances of relay and release
There are classified into
Low voltage circuit breaker (Connected to branch whose voltage is
less 1kV)
High voltage circuit breaker (Connected to branch whose voltage is
above 1kV)
Release is less than 1KVA and it is the Low voltage side
Relay is greater than 1KVA and it is the High voltage side
Objective of Electrical system Protection and Coordination
6
Low voltage circuit breaker
Characteristics
Depending on the time of the operation of relays they are categorized as
follows
TOC Time Over Current (OR) Inverse Definite Minimum Time (IDMT) [51]
7
Inverse definite minimum time (IDMT)overcurrent Relay is one in which the
operating time is approximately inversely proportional to the -up value and then
becomes constant above the pick-up value of the relay
IDMT (51)
Standards (Normal, Moderate inverse) [IEC/IEEE/ANSI]
Long inverse [IEC/IEEE/ANSI]
Very long inverse [IEC/IEEE/ANSI]
External inverse [IEC/IEEE/ANSI]
This relay is created by applying intentional time delay after cross in g pick up the
value of the current. A definite minimum time over current relay can be
adjusted to issue a trip out put a t an exact amount of time after it pickup. Thus, it
has a time setting adjustment and pickup adjustment.
8
DMT (50)
When the fault is occurred DMT is used to trip the device in 0-1sec when the
current is decreases or not decreases its tripping
Instantaneous [50I]
Formula
𝐾
Trip time (Top)t(G) = T × [ 𝐼 𝐴𝑐𝑡𝑢𝑎𝑙 + β]
[ ]−1
𝐼 𝑆𝑒𝑡
I actual = fault current(A)
I set = setting current as relay pickup current
T = TMS
Kr, β or C = Constant it will be subjected
Standards k α β IV SV
Standard inverse 0.14 0.02 0.01 10 1
9
Longtime inverse 120 1 0 5 1
Relay trip time calculation
Time dial or Time multiplier settings will be adjusted ed at graph based on the
curve positioning on plotted graph.
The Desired Cases Are Two, graph shall not be over lapped and need to maintain
some gradings
IEC time multiplier setting (TMS). IEEE time dial (TD). In some relay s and
literature, a TDM (Time Dial Multiplier) is used, instead of a TD (Time Dial).
Formula
TDM = TD/7
Basics of current transformer and its connections
Phase current transformer Circuit breaker current transformer
Connection configuration
10
Neutral current measured - with CBCT
Traditional Time(200ms)
Relay Sensing time:20ms
Breaker opening time:40ms
CT saturation, settingerror:20ms Safety factor/Margin:100ms
CT1 The time interval is changing with respsct to the country where the project is
executed and plants complex network
11
12
1.1 × FLA
Long inverse =
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
1.3 × LRC
Instantaneous =
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
13
Transformer parallel LV relay settings
14
Calculation
1.1 ×𝐹𝐿𝐴
Long current is 1.1 times =
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
1.3 ×𝐿𝑅𝐶 %
Instantaneous is 1.3 times =
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
Measured earth fault can be defined as where the R, Y, B phase are not
calculated equal measuring ampere is calculated from the relay known as the
Measured fault relay
Derived earth fault can be defined as the where the R, Y, B phase are equal
measured the same ampere are calculated from the relay known as Derived earth
fault
15
Relay sensing time is – 20ms (milli seconds)
Breaker opening time is – 40ms
CT saturation, settings error – 20ms
Safety factor margin – 100ms
So total margin is 200ms and 250ms is provided by a series relay line
LV protections are
Switch
Fuse
Disconnector
MCB – Miniature Circuit Breaker
MCCB – Molded Case Circuit Breaker
ACB – Air Circuit Breaker
ELCB – Earth Leak Circuit Breaker
RCB – Residual Circuit Breaker
RCCB – Residual Current Circuit Breaker
16
Type Z 2 to 3 times full load Greater than 0.01 secs
current
Type B
Type B, C and D are used for overcurrent protection of cables standards is IEC/EC
60898.1
Type C
Application: Include small transformer, Lightning pilot device, Control Circuit and
Coils residential, Commercial and Industrial
Type Z
D curve device are suitable for application where high levels of inrush current like
motor, transformer, and power supply
Type K
Suitable for inductive grid motor loads with high inrush current
17
Type Z
Very low value to short circuit highly sensitive device such as semiconductor
devices
ELCB RCCB
18
Leakage current should flow through It does not required earthing for current
earthing flow
No longer available and its advised you Widely used in present system
replace them if you find one
On the basis of their application, circuit breakers can be categorized into low
voltage circuit breakers, medium voltage circuit breakers, and high voltage
circuit breakers. Low voltage circuit breakers would include MCCB, ACB, MCB,
and RCCB. Medium voltage circuit breakers would include VCB, SF6, OCB, and
ABCB.
MCCB
A molded case circuit breaker (MCCB) is a type of electrical protection device
that is used to protect the electrical circuit from excessive current, which can cause
overload or short circuit.
It provides a overcurrent and short circuit protection up to 1600A and 3200A and it
is act as mechanical function
MCB
Miniature Circuit Breaker is a device that ensures safety and prevents electrical
hazards in the appliances or devices. MCB is an automatic switch. A circuit
breaker is an electrical safety device designed to protect an electrical circuit from
damage caused by an overcurrent or short circuit.
19
ACB
Air circuit breaker is a circuit breaker for the purpose of protecting low voltage
circuit, mainly for energizing and cutting off high current. It is used as the
master of a factory and building, and as a main circuit breaker of a ship, and it is
possible to attach various accessories according to the purpose.
20
Release
21
In the true fault current calculated by using the fault occurred in HV buses and run
the short circuit analysis and the true fault current is obtained
This is identifying the method of the true fault current is determined
22
1.1 × FLA
Long inverse =
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
1.3 × LRC
Instantaneous =
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
23
1.1 × FLA
Long inverse =
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
1.3 × LRC
Instantaneous =
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
24
Rings main relay
25
1.1 × FLA
Long inverse =
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
1.3 × LRC
Instantaneous =
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
The graph has been plotted between the relay and load is determined as
26
Relay settings
Input settings
Output settings
27
Relay modelling
28
1.1 × FLA
Long inverse =
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
1.3 × LRC
Instantaneous =
𝐶𝑇 𝑟𝑎𝑡𝑖𝑜
Directional Earth Fault (DEF) is used to differentiate between different fault types
to ensure that co-ordination between protection devices such as distribution circuit
breakers and reclosers is maintained. This principle is referred to as “Selectivity”
in protection engineering.
29
30