CSQ 2M
CSQ 2M
CSQ 2M
DEIF A/S
DEIF A/S
Tel.:
(+45) 9614 9614
Frisenborgvej 33, DK-7800 Skive Fax:
(+45) 9614 9615
Denmark
E-mail: deif@deif.com
List of contents
1.
2.
3.
3.1
3.2
4.
4.1
5.
Wiring diagrams ...........................................................................................11
5.1
AC input connections .....................................................................................11
5.1.1 Connection diagram .......................................................................................11
6.
Commissioning ............................................................................................12
7.
8.
Dimensions...................................................................................................14
9.
Page 2 of 20
Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com
4189340218K (UK)
Display/reading
The unit measures the two inputs voltages: Generator (GEN) and busbar (BB),
respectively. The phase difference from GENs zero-crossing to BBs zero-crossing is
calculated by the processor and is shown on the LED circle, consisting of 36 red
LEDs.
The red LEDs are only lit one at a time and its position indicates the phase difference
between GEN and BB. The lit LED simulates the pointer tip of an analog pointer
instrument. If the LED is lit in the 12 oclock position, the phase difference is 0
degrees. In the 6 oclock position, 180 degrees etc. With 36 LEDs the resolution is 10
degrees.
The movement of the lit LEDs position indicates the frequency difference between
GEN and BB. If the indication is turning clockwise (too fast), the GEN frequency is too
high in proportion to the BB frequency. If the indication is turning counter-clockwise,
the proportion is inversed. The rate of the motion tells about the frequency difference.
The faster the rotation, the bigger the frequency difference, e.g. 1 rotation per second
= 1Hz. If the BB frequency is 50Hz and the rotation turns right, the GEN frequency will
be 51Hz in this example.
If the frequency difference between GEN and BB is becoming too big (>3Hz), the
circular motion stops and a LED will be lit at the too fast or too slow mark,
dependent on which direction the GEN frequency has to be adjusted to.
Normal synchronising
The unit automatically calculates the synchronising parameters to check if there is the
required space for the synchronising inside the preset phase window. These
calculations compare the frequency difference with tR and the size of the phase
window. When tR is set to , td can be set by the user and is then included in the
calculations instead of tR.
If the window is set symmetrically, both under-frequency synchronising and overfrequency synchronising is possible.
Under- or over-frequency synchronising
When the window is set asymmetrically the following functionality is possible:
If the window is set asymmetrically with a higher positive than negative
value, only synchronising with the generator input at lower frequency than the
busbar input is possible (under-frequency synchronising).
If the window is set asymmetrically with a lower positive than negative
value, only synchronising with the generator input at higher frequency than the
busbar input is possible (over-frequency synchronising).
Note:
This function is not active with tR set to .
Page 4 of 20
Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com
4189340218K (UK)
To get access to the settings, remove the front frame and the front foil.
The CSQ-2 can be operated in two different modes: "Normal mode" and "setting
mode". Normal mode is used to display measuring values, and setting mode is used
to view the settings or change them to the desired functionality.
Page 6 of 20
Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com
3.1 LEDs
The CSQ-2 has the following LEDs on the fronts showing different operating
information.
LEDs on primary front (normal mode):
LED
Colour
Function
Circle
Red
SYNC.
Green
OK
Yellow
The lit LED in the circle shows the phase difference between
GEN and BUSBAR
All preset sync. parameters are OK, and the output relay is
activated
The phase difference between GEN and BUSBAR is within
the preset window
The voltage difference between GEN and BUSBAR is outside
the preset range. UGEN is too high
The voltage difference between GEN and BUSBAR is outside
the preset range. UGEN is too low
UGEN
Red
TOO HIGH
UGEN
Red
TOO LOW
Colour
Function
Circle
Red
Parts of the circle are used as scales for the different settings
Yellow
td
Yellow
tR
Yellow
Yellow
Ubus
Yellow
4189340218K (UK)
3.2 Settings
MODE:
NORMAL
U max.
U min.
SET/VIEW
pos
SET/VIEW
NEG
SET/VIEW
tr
YES
tr =
NO
SET/VIEW
td
SET/ACTIVATE
DEAD-BUS
SAVE
automatically
NORMAL
Page 8 of 20
Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com
5% of UBB
0.5 sec.
10
OFF
4. Terminal list
4.1 Overview of the terminals
Terminal
no.
1
2
Signal
symbol
R (L1)
S (L2)
Signal name
3
4
SYNC.
SYNC.
Relay output
Relay output
5
6
R (L1)
S (L2)
Generator voltage
Generator voltage
Busbar voltage
Busbar voltage
+ open collector
- open collector
Marine version
Page 10 of 20 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com
5. Wiring diagrams
5.1 AC input connections
When ordering the CSQ-2, the correct range of voltage inputs must be specified. They
must be connected as shown below.
Note 1:
When the CSQ-2 is applied to emit a ready to sync. signal (tR is set to ), and it is
not directly controlling closing of the breaker, it is necessary to connect the CSQ-2
immediately before the ready signal is required, as the CSQ-2 disables check of the
voltage difference (U) when the internal synchronising relay is activated.
4189340218K (UK)
6. Commissioning
Before commissioning:
Warning:
7. Technical data
Accuracy:
2 (electrical degrees)
Resolution:
10 (36 LEDs)
Settings, range:
:
U:
tR :
td :
Ubus offset:
520 in 1 steps or
1040 in 2 steps
110% in 1% steps
01 sec. in 0.1 sec. steps or
01 sec. in 0.1 sec. steps
Off or 4 levels of noise suppression
(dead bus)
No limit
Busbar input:
Load: 2k/V
Generator input:
Frequency range:
4070Hz (supply)
Relay contact:
1 SPST-NO-contact
Life mechanical:
2 x 10
Life electrical:
1 x 10 (nominal value)
8A, 250V AC
8A, 24V DC
3A, 250V AC
3A, 24V DC
7
5
Page 12 of 20 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com
Temperature:
-1055C (nominal)
-2570C (operating)
-4070C (storage)
Temperature drift:
Set-points:
Max. 0.2% of full scale per 10C
Galvanic separation:
Climate:
HSE, to DIN40040
EMC:
Connections:
Materials:
Protection:
Type approval:
Dimensions:
Panel cut-out:
91 x 91 1 mm
Weight:
< 0.35 kg
4189340218K (UK)
8. Dimensions
All dimensions in mm
9. Order specifications
Input voltage and type must be specified when ordering the CSQ-2.
Order specification for the CSQ-2 consists of the following:
CSQ-2 - UN - type
where UN and type are as follows:
Code
UN
Function
Input voltage
Options
115V: (100127V AC input range)
230V: (220240V AC input range)
415V: (380...415V AC input range)
Type
Here the phase window is adjusted, in which synchronising can take place. The
adjustment starts from 5 and the window can open symmetrically or asymmetrically
around this value.
The regulating range is -20...-5 and 5...20, in 1 steps or
-40...-10 and 10...40, in 2 steps.
tR
Here the length of the pulse for the synchronising relay is adjusted.
The regulating range is 0...1 sec. in steps of 0.1 sec. or .
This function makes it possible to adjust the synchronising pulse according to the
external breakers demands (closing time).
For special purposes it is also possible to adjust tR to (infinite). This setting will (after
td has expired) provide a synchronising pulse as long as the following conditions are
met:
td
Here the time is adjusted, in which the phase difference must be inside the preset
synchronising window to allow SYNC. The regulating range is 0...1 sec. in steps of 0.1
sec.
td is only activated if tR is set to .
4189340218K (UK)
Dead bus
The possibility of closing the circuit breaker even though the busbar voltage is
missing. There is an extra adjustment, UBUS, where the level of dead busbar can be
set. This facility makes dead bus synchronising possible, even though there is noise
on the busbar. The regulating range is off or 10...40% of UN in steps of 10%.
Setting
OFF
10
20
30
40
Please notice that this setting is a coarse step regulation for suppression of possible
noise on the busbar. The scale 10-20-30-40 should therefore be considered more as
a 4 level noise suppression than as an accurate measuring setting.
Example:
The example is based on a 100V busbar system.
The dead bus setting is chosen to 10. When the generator voltage is higher than 70V,
the CSQ-2 is activated, see note 1 below. When the dead bus function is activated,
the CSQ-2 will check the busbar voltage. If this is below 1525V, the CSQ-2 will send
a closing signal to the breaker. In some cases where long wires (busbars) are
connected to the CSQ-2, humming or noise picked up by the dead busbar can result
in a higher input voltage than 25V. To avoid that, adjust the setting for dead bus to 20
and try again. If the humming is very high, a setting of 30 or 40 can be necessary to
prevent humming (noise) to interfere with the dead bus function. If the dead bus
function is activated and the setting is 10, and the humming is higher than 1525V
but below 30V, the CSQ-2 will only activate the U LED indicating that the generator
voltage is too high. If the humming is higher than 30V, the CSQ-2 will start to indicate
the frequency and phase relationship by activating the LED circle. No sync. pulse will
be transmitted because the U voltage LED will still be active, indicating that the
voltage difference is too high. During commissioning this must be observed to make
sure that the dead bus noise suppressor is set correctly. After the breaker has been
closed, the sync. relay will stay on until the timer tR expires (01 sec). When tR
expires, the 12 oclock position and the OK LED will be illuminated. If infinite sync.
relay pulse is chosen, the sync. pulse will stay on also after the breaker is closed, this
is indicated by all 3 LEDs in 12 oclock position being lit.
Note 1:
The CSQ-2 is power supplied from the generator input, the busbar input is only for
measuring.
Page 16 of 20 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com
Commissioning
Normally tR is adjusted so it equals the circuit breakers closing time and -/+ to
max. allowed synchronising error.
Please notice that the CSQ-2 calculates space for tR (breaker closing time) within the
chosen window at the actual f (slip frequency). Therefore the max. synchronising
error will never exceed the chosen window.
Calculation example
The breaker closing time is 200mS, and tR is chosen to 200mS. The phase window is
set symmetrically to 10 (electrical degrees). Then the max. f can be calculated
using the following formula:
f =
(-) + (+)
360 x tR
f =
10 + 10
= 0.278Hz
360 x 0.2
4189340218K (UK)
Calculation of the actual synchronising error not to be mistaken for the max.
synchronising error which is solely determined by the chosen window
The next examples apply to situations where tR is set in the range 0.1...1 sec.
Example:
With a slip frequency (f) of 0.1Hz the phase changes with a rate of 36/sec. If is
set to 10 and tR is set to 0.2 sec. = breaker closing time, the actual synchronising
error can be calculated.
The moment the phase is within the set phase window (), the relay of the CSQ-2 is
activated on condition that there is space for the chosen tR, in this case 0.2 sec. If f is
too big, it will cause lack of space for the chosen tR time within the chosen window.
Example 1:
With a phase change of 36/sec. the phase will change 7.2 during the 0.2 sec. This
means that we can now calculate the phase displacement at the exact moment when
the breaker closes. is set to -10 and +10. The CSQ-2 relay will be activated -10
before top (12 oclock position), and after 7.2 the breaker closes which means that
the breaker closes 10 - 7.2 = 2.8 before top, that is an actual synchronising error of
-2.8. Applying the formula on page 17, the max. f with the shown settings can be
calculated to be 0.277Hz.
Example 2:
If we assume that the slip frequency in the actual case is 0.2Hz, the phase changes
with a rate of 72/sec. With a phase change of 72/sec. the phase will change 14.4
during the 0.2 sec. which gives a synchronising error of 10 - 14.4 = -4.4. The
negative result means that the breaker closed 4.4 after top, that is an actual
synchronising error of +4.4.
Example 3:
The same as examples 1 and 2, but with a slip frequency of 0.3Hz = 108/sec. At tR =
0.2 sec. the phase will change 21.6. As the window is set to 10, the CSQ-2 will
calculate that there is no longer space for a tR pulse of 0.2 sec., and therefore no relay
pulse is emitted.
General formula for the above-mentioned:
Actual synchronising error = (-) - 360 x f x breaker closing time (tR).
Alternatively at negative slip frequency:
Actual synchronising error = (+) - 360 x f x breaker closing time (tR).
If the result is negative, the synchronising will take place after top (0) provided that
there is space for tR within the window.
If you want to avoid synchronising after top, is set asymmetrically. At positive slip
frequency (f) as in the shown example a setting of - to -10 and + to +5 would
have as a result that synchronising after top of more than 5 would not be possible.
Page 18 of 20 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com
Page 20 of 20 Tel.: (+45) 9614 9614 Fax: (+45) 9614 9615 E-mail: deif@deif.com