Carrier 38ap

Download as pdf or txt
Download as pdf or txt
You are on page 1of 76
At a glance
Powered by AI
The document discusses Carrier's 38AK and 38AKS commercial air-cooled split systems and their features such as efficiency, controls for performance, and safety standards.

The 38AK and 38AKS condensing units include highly efficient compressors, high and low pressure switches, anti-short cycling protection, a control circuit transformer, and a crankcase heater (for some models).

The 40RM Series packaged air handlers include direct-expansion cooling coils, 2-in disposable filters, thermal insulation with an anti-microbial agent, and an optional economizer to improve indoor air quality.

38AK007-012

Product 38AKS008-044
Data with 40RM007-034 and
28CB,LA008,012
Commercial Air-Cooled
Split Systems
6 to 40 Nominal Tons

Feature/Benefits
These dependable split sys-
tems match Carriers indoor-
air handlers and direct-
expansion coils with outdoor
condensing units for a wide
selection of commercial
cooling solutions.
Constructed for long life
Model 38AK (hermetic compressor
38AK007,008,012 units) and 38AKS (semi-hermetic
38AKS008,009,012
compressor units) are designed and
built to last. The copper tube-aluminum
fin outdoor coil construction provides
years of trouble-free operation. Where
conditions require them, copper fin
coils are also available. Cabinets are
constructed of prepainted galvanized
steel, delivering unparalleled pro-
tection from the environment. Inside
and outside surfaces are protected
to ensure long life, good looks, and
reliable operation. Safety controls are
used for enhanced system protec-
38AKS013-024 tion and reliability.
Efficient operation
Building owners will appreciate the
high unit EERs (Energy Efficiency
Ratios) offered by the 38AK and
38AKS units. These units provide
greater efficiency than similar units in
the marketplace, which translates
into year-round operating savings.
Controls for performance
dependability
The 38AK and 38AKS condensing
units offer the building owner operat-
ing controls and components designed
for performance dependability. The
40RM007-012 highly efficient hermetic and semi-
hermetic compressors are engineered

Copyright 1998 Carrier Corporation Form 38A-3PD


for long life and durability. The com- The pitched PVC drain pan can be Easier installation and service
pressors include overload protection adjusted for a right- or left-hand connec- The multipoise design and component
and vibration isolation for enhance- tion to suit many applications and pro- layout help you to get the unit installed
ment of quiet operation. The high- vide positive drainage and to prevent and running quickly. The DX coils
pressure switch protects the entire refrig- standing condensate. have factory-installed TXVs with match-
eration system from abnormally high The 40RM accessory economizer can ing distributor nozzles. Units can be
operating pressures. A low-pressure provide ventilation air to improve converted from horizontal to vertical op-
switch protects the system from indoor air quality. When used in con- eration by simply repositioning the
low-pressure conditions, including loss junction with Carrier Comfort Sys- unit. Drain pan connections are dupli-
of charge. tem thermostats and CO2 sensors, the cated on both sides of the unit. The
The 38AK007-012 and 38AKS008- economizer admits fresh outdoor air filters, motor, drive, TXVs, and coil con-
012 units include Cycle-LOC anti- to replace stale, recirculated indoor air. nections are all easily accessed by re-
short-cycling protection which helps to moving a single side panel.
Economy The 40RM Series
protect the units against compressor packaged air handlers have low initial
failure. The 38AKS013-044 units costs, and they continue to save money 28CB and 28LA direct-
include a compressor recycle delay timer by providing reduced installation ex- expansion evaporator coils
to prevent short-cycling. The 24-v con- pense and energy-efficient performance. matched with 38AK and
trol circuit transformer permits quick,
easy wiring of standard and Quick installation is ensured by the 38AKS units provide efficient
programmable 24-vthermostats. multipoise design. Units can be installed cooling for furnace systems
in either the horizontal or vertical con- If your light commercial application calls
38AKS008-044 units include a crank- figuration without modifications. All
case heater to eliminate liquid slugging for direct-expansion evaporator coils in
units have drain-pan connections on both the popular 712 to 10 ton nominal
at start-up. Units with semi-hermetic sides, and pans can be pitched for
compressors are also equipped with an capacity range, consider Carriers
right- or left-hand operation with a performance-proven 28CB and LA
oil-level sight glass. simple adjustment. Fan motors and con- coils. Matched for use with Carriers
Latest safety standards for 38AK and tactors are prewired and TXVs are 38AK007 and 38AKS008 condensing
38AKS units are assured through UL factory-installed on all 40RM models. units, these versatile coils can be used in
(Underwriters Laboratories) and CSA High efficiency, precision-balanced either new construction or renovation
(Canadian Standards Association) fans minimize air turbulence, surging, projects.
approvals. and unbalanced operation, cutting opera- Whether the application is with a duct
tion expenses. furnace, or an upflow or horizontal fur-
Innovative Carrier 40RM pack- nace, 28CB and LA coils offer cost-
aged air handlers are custom The economizer accessory precisely
controls the blend of outdoor air and saving heat transfer performance. Coil
matched to 38AK and 38AKS room air to achieve comfort levels. enclosures are fully insulated to maxi-
condensing units When the outside air enthalpy is suit- mize cooling power and optimize oper-
The 40RM Series has excellent fan per- able, outside air dampers can fully open ating economy.
formance, efficient direct-expansion to provide free cooling without en- The 28LA upflow coil offers a variety
(DX) coils, a unique combination of ergizing mechanical cooling. of piping possibilities...thru the front
indoor- air quality features, and easy in- Rugged dependability 40RM units access panel or at either end of the unit,
stallation. Its versatility and state-of- are made to last. The die-formed gal- whichever best suits the conditions at
the-art features help to ensure that your vanized steel panels ensure structural the jobsite. Includes factory-matched
split system provides economical per- integrity under all operating conditions. and installed thermostatic expansion
formance now and in the future. Galvanized steel fan housings are se- valve for R-22.
Indoor-air quality (IAQ) features curely mounted to a die-formed galva- The 28CB horizontal coil matches
The unique combination of IAQ fea- nized steel fan deck. horizontal and duct furnaces, or can be
tures in the 40RM Series air handlers Rugged pillow-block bearings applied within the duct.
help to ensure that only clean, fresh, (40RM014-034) are securely fastened
conditioned air is delivered to the occu- System ratings using the 28CB and
to the solid steel fan shaft with split col- 28LA coils are ARI certified, and have
pied space. lets and clamp locking devices. Smaller been tabulated and selected for com-
Direct-expansion (DX) cooling coils unit sizes have spider-type bearings. binations that represent reliable,
prevent the build-up of humidity in Coil flexibility Model 40RM direct- balanced cooling systems. The coils are
the room, even during part-load condi- expansion coils have galvanized steel easy to install; just gasket furnace-to-coil
tions. Unit sizes of 10 tons and above casings; inlet and outlet connections are contacting surfaces and you are set to
feature dual-circuit coils for improved on the same end. The coils are de- connect field piping in a matter of
temperature control. signed for use with Refrigerant 22 and minutes.
Standard 2-in. disposable filters re- have 38-in. diameter copper tubes
move dust and airborne particles from mechanically bonded to aluminum sine-
the occupied space for cleaner air. wave fins. The coils include matched,
Thermal insulation contains an EPA- factory-installed thermostatic expansion
registered immobilized anit-microbial valves (TXVs) with matching distribu-
agent to inhibit the growth of bacteria tor nozzles.
and fungi.

2
Features/Benefits (cont)

28LA

28CB

Table of contents
Page
Features/Benefits . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1-3
Model Number Nomenclature 38AK Units . . . . . . . . . . . . . . . . . . . . . . . . . . 4
Model Number Nomenclature 38AKS Units . . . . . . . . . . . . . . . . . . . . . . . . . 4
Model Number Nomenclature 40RM Units . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Model Number Nomenclature 28CB, LA Units . . . . . . . . . . . . . . . . . . . . . . 5
ARI Capacities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Options and Accessories . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7-10
Physical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11-14
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15-23
Selection Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24
Performance Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25-39
Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40-45
Typical Piping and Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46-50
Typical Wiring Schematic . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 51,52
Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 53
Typical Control Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54-56
Application Data 38AK007-012, 38AKS008-012 . . . . . . . . . . . . . . . . . . . 57
Application Data 38AKS013-024 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58,59
Application Data 38AKS028-044 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59,60
Application Data 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61-64
Guide Specifications 38AK007-012, 38AKS008-012 . . . . . . . . . . . . . . . . 65,66
Guide Specifications 38AKS013-024 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67,68
Guide Specifications 38AKS028-044 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69-71
Guide Specifications 40RM . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 72,73
Guide Specifications 28CB, LA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74

3
Model number nomenclature 38AK units
38AK 007 5 0 1

38AK Commercial Air-Cooled Not Used


Condensing Units (Hermetic)
Packaging
Not Used 0 Base Unit
1 Domestic
Nominal Tons
007 6 Revision Number
008 7-1/2 0 Original
012 10
Voltage Designation
Not Used 5 208/230-3-60
6 460-3-60
Condenser Coil Fin Material 1 575-3-60
Aluminum (Standard)
C Copper (Optional)
V Pre-Coated Aluminum Fins

Model number nomenclature 38AKS units


38AKS 008 5 0 1

38AKS Commercial Air-Cooled Not Used


Condensing Units (Semi-Hermetic)
Packaging
Nominal Tons 0 Base Unit
008 7-1/2 016 15 1 Domestic
009 8-1/2 024 20 3 Export
012 10 028 25
013 10 034 30 Revision Number
014 12-1/2 044 40 0 Original

Not Used Voltage Designation


5 208/230-3-60
Condenser Coil Fin Material 6 460-3-60
Aluminum (Standard) 1 575-3-60
C Copper (Optional) 2 380-3-60 (Export Only)
V Pre-Coated Aluminum Fins
SO Post-Coated Aluminum Fin (Factory Special)
SO Post-Coated Copper Fins (Factory Special)

LEGEND
SO Special Order

38AKS013-044 UNITS
38AK, 38AKS008-012 UNITS

4
Model number nomenclature 40RM units
40RM 016 B 5 0 1 GC

40RM Commercial Packaged Factory-Installed Options


Air Handler GC Unpainted, Standard Motor
and Standard Drive
Cooling Coil HC Unpainted, Standard Motor
Direct Expansion and Medium-Static Drive
Q Direct Expansion for Heat Pump Duty* (Not available for 028 size)
S Chilled Water TC Unpainted, Alternate Motor
and Medium-Static Drive
Nominal Capacity --- Tons (028 size only)
007 6 016 15 YC Unpainted, Alternate Motor and
008 7-1/2 024 20 High-Static Drive
010 8-1/2 028 25 ED Painted, Standard Motor and
012 10 034 30 Standard Drive
014 12-1/2 FD Painted, Standard Motor and
Medium-Static Drive
Not Used (Not available for 028 size)
RD Painted, Alternate Motor and
Expansion Device Medium-Static Drive
None (40RMS) (028 size only)
B Thermostatic Expansion Valves (40RM, 40RMQ) WD Painted, Alternate Motor
High-Static Drive
Voltage Designation (V-Ph-Hz)
1 575-3-60
3 208/230-1-60 (007-010 sizes only) Packaging
5 208/230-3-60 1 Standard Domestic
6 208/230/460 (all sizes 007-014; size 016
except YC and WD options)
460-3-60 (sizes 016 with YC or WD options and all Revision Number
size 024-034 units) 0 Original Model

*For 40RMQ heat pump system performance information, refer to 38AQS Product
Data catalog.
The YC and WD option codes for 034 size units and 008, 010 units with
208/230-1-60 power designate standard motor and high-static drive. Standard mo-
tor and high-static drive.

40RM UNITS

Model number nomenclature 28CB, LA units

5
ARI* capacities
AIR CONDENSING UNIT
AIR HANDLER/ SYSTEM ONLY**
CONDENSING HANDLER/ INDOOR COIL
UNIT INDOOR COIL AIRFLOW Net Cap. Net Cap.
(Btuh) EER (Btuh) EER
(Cfm)
28CB008 2400 71,000 9.0
28LA008 2400 69,000 9.0
38AK007 75,000 11.1
40RM007 2400 71,000 9.8
40RM008 2600 74,000 9.9
40RM007 2400 84,000 9.1
38AK008 40RM008 3000 90,000 9.3 97,000 10.7
40RM012 3450 93,000 9.3
40RM007 2400 84,000 9.8
28CB008 3000 88,000 9.0
28LA008 3000 86,000 9.0
38AKS008 28CB012 3300 89,000 9.0 97,000 11.5
28LA012 3000 89,000 9.0
40RM008 3000 90,000 9.9
40RM012 3450 93,000 9.9
40RM008 3000 101,000 9.0
38AKS009 115,000 10.7
40RM012 4000 109,000 9.0
40RM012 4000 120,000 9.0
38AK012 129,000 10.2
40RM014 4650 124,000 9.3
40RM008 3000 102,000 9.1
38AKS012 40RM012 4000 109,000 9.0 117,000 10.6
40RM014 4200 114,000 9.6
40RM008 3000 104,000 9.3
38AKS013 40RM012 4000 112,000 9.4 120,000 10.8
40RM014 4300 117,000 9.9
40RM012 4000 130,000 9.6
38AKS014 40RM014 5000 136,000 9.9 149,000 11.8
40RM016 5300 144,000 10.0
40RM014 5000 166,000 8.9
38AKS016 40RM016 6000 178,000 9.1 192,000 10.5
40RM024 7000 186,000 9.1
40RM016 6000 206,000 8.7
38AKS024 40RM024 7000 216,000 8.7 248,000 9.9
40RM028 8600 230,000 8.8
LEGEND
EER Energy Efficiency Ratio
SST Saturated Suction Temperature
*Air Conditioning and Refrigeration Institute.
Ratings in accordance with ARI Standard 210/240-89, 270-84, or 360-86.
**Condensing unit only ratings are at 45 F SST and 95 F entering-air temperature.
NOTE: Ratings for 38AKS028-044 units combined with 40RM air-handling units ex-
ceed the scope of the ARI certification program. See pages 34 and 35 for ratings for
these unit combinations.

6
Options and accessories
38AK, 38AKS accessories Hot-gas bypass kit (38AKS028-044) prevents the
Electric unloader package (38AKS012-044) includes indoor coil from freezing up during low airflow or low return-
hardware and solenoid valve to convert a pressure-operated air temperature applications by maintaining minimum suc-
unloader to electric unloading. tion pressure.
Part-winding-start timing relay (38AKS028-044) re-
20 F low-ambient temperature kit (Motormastert I
duces inrush current and locked rotor amps on start-up. This
38AK007, 38AKS013-044; Motormaster III
accessory may require a special-order unit. See table below.
38AK008,012, 38AKS008-012) controls outdoor-fan
motor operation to maintain the correct head pressure at
low outdoor ambient temperatures. Only one low ambient PART-WINDING-START TABLE
temperature kit is required per unit.
UNIT SIZE VOLTAGE (60 Hz)
Gage panel package provides a suction and a discharge 38AKS 208/230 380 460 575
pressure gage for the refrigerant circuit. 028
Carriers line of thermostats provide both program- 034 Note 1 Note 2 Note 3 Note 2
mable and non-programmable capability with the new Debo- 044
nair line of commercial programmable thermostats, the NOTES:
TEMP System controls offer communication capability with 1. Can be field modified to part winding start by adding a time delay
relay (part no. HN67ZA001).
staged heating and cooling, the Commercial Electronic 2. Requires special order to change circuit breakers and contactors.
thermostats provide 7-day programmable capability for eco- 3. Requires special order to change circuit breakers and contactors,
nomical applications, while the non-programmable ther- and cannot use triple-voltage compressor.
mostats offer a multitude of staged heating and cooling
subbase options.
Winter start package (38AK007-012, 38AKS008- Condenser coil grille package (38AK007-012,
024) bypasses the low-pressure switch to permit unit start-up 38AKS008-024) protects condensing unit coil from
at low ambient temperatures. impact by large objects and vandalism.
Hail guard package (38AK007-012, 38AKS008- Condenser coil options are available to match coil con-
012) protects coils against damage from flying debris and struction to site conditions for the best corrosion durability.
hail. Pre-coated coils provide protection in mild coastal environ-
ModuPanel control box allows 38AKS028-044 sys- ments. All copper coils are best suited for moderate coastal
tems to operate as VAV (variable air volume) systems. applications, while post-coated coils provide superior pro-
Includes microprocessor, satellite sequencer, 4 status lights, tection in severe coastal and industrial applications.
5-hour bypass timer, and locked enclosure.

CONDENSER COIL PROTECTION APPLICATIONS


ENVIRONMENT*
DESCRIPTION Combined
(Enviro-Shield Option) Standard, Mild Moderate Severe Industrial Coastal
Non-Corrosive Coastal Coastal Coastal and Industrial
Standard, Al/Cu X
Pre-Coated al/Cu X
Cu/Cu X
Post-Coated Al/Cu X
Post-Coated Cu/Cu X X

LEGEND
Al/Cu Aluminum Fin with Copper Tube Coil
Cu/Cu Copper Fin with Copper Tube Coil
Enviro-Shield Family of Coil Protection Options
Post-Coated Organic Coating applied to Entire Coil Assembly
Pre-Coated Epoxy Coating Applied to Fin Stock Material
*See Selection Guide: Environmental Corrosion Protection Catalog No. 811-839 for more information.

7
Options and accessories (cont)
40RM options Return-air grille provides a protective barrier over
Alternate fan motors and drives are available to pro- the return-air opening and gives a finished appearance to
vide the widest possible range of performance. units installed in the occupied space. Accessory is available
unpainted or painted.
Prepainted steel units are available from the factory for
applications that require painted units. Units are painted Subbase provides a stable, raised platform and room for
with American Sterling Gray color. condensate drain connection for floor-mounted units.
Accessory is available unpainted or painted.
40RM accessories Overhead suspension package includes necessary brack-
Two-row hot water coils have 58-in. diameter copper ets to support units in horizontal ceiling installations.
tubes mechanically bonded to aluminum plate fins. Coils
have non-ferrous headers. Condensate drain trap includes an overflow shutoff switch
than can be wired to turn off the unit if the trap becomes
One-row steam coil has 1-in. OD copper tube and alu- plugged. Kit also includes a wire harness that can be con-
minum fins. The Inner Distributing Tube (IDT) design pro- nected to an alarm if desired. The transparent trap is
vides uniform temperatures across the coil face. The steam designed for easy service and maintenance.
coil has a broad operating pressure range; up to 175 psig
at 400 F and up to 300 psig at 300 F. IDT steam coils are Carriers line of thermostats provide both program-
especially suited to applications where sub-freezing air mable and non-programmable capability with the new Debo-
enters the unit. nair line of commercial programmable thermostats, the
TEMP System controls offer communication capability
Electric resistance heat coils have a 2-stage, open-wire with staged heating and cooling, the Commercial Elec-
design and are mounted in a rigid frame. Safety cutouts for tronic thermostats provide 7-day programmable capability
high temperature conditions are standard. for economical applications, while the non-programmable
Economizer (enthalpy controlled) provides ventilation thermostats offer a multitude of staged heating and cooling
air and provides free cooling if outside ambient tempera- subbase options.
ture and humidity are suitable. Can also be used in conjunc- CO2 sensors can be used in conjunction with the econ-
tion with Carrier Comfort System thermostats and CO2 omizer accessory to help meet indoor air quality require-
sensors to help meet indoor air quality requirements. ments. The sensor signals the economizer to open when
Discharge plenum directs the air discharge directly into the CO2 level in the space exceeds the set point. A Carrier
the occupied space; integral horizontal and vertical louvers Comfort System programmable thermostat can also be used
enable redirection of airflow. Accessory is available un- to override the sensor if the outside air temperature is too
painted or painted. high or too low.

8
CARRIER THERMOSTATS
DEBONAIR COMMERCIAL PROGRAMMABLE TEMP SYSTEM THERMOSTAT
THERMOSTAT WITH TIMECLOCK

Carrier

Pm
COOL
AUTO
HEAT

COMMERCIAL ELECTRONIC THERMOSTAT NON-PROGRAMMABLE THERMOSTAT

H C

9
Options and accessories (cont)
40RM WITH DISCHARGE PLENUM, RETURN 40RM WITH HOT WATER OR STEAM COIL
GRILLE, AND SUBBASE
HOT WATER OR
STEAM COIL

DISCHARGE
PLENUM

RETURN-AIR
GRILLE

SUBBASE
FAN
COIL
UNIT FAN COIL
UNIT

40RM WITH ECONOMIZER


40RM WITH CONDENSATE TRAP

ECONOMIZER

FAN COIL UNIT

10
Physical data
38AK007-012, 38AKS008-012
UNIT 38 AK007 AK008 AK012 AKS008 AKS009 AKS012
NOMINAL CAPACITY (tons) 6 712 10 712 812 10
OPERATING WEIGHT (lb)
Aluminum Coils (Std) 340 370 395 510 564 564
Copper Coils (Optional) 386 438 472 578 632 632
RIGGING WEIGHT (lb)
Aluminum Coils (Std) 390 420 445 560 614 614
Copper Coils (Optional) 436 488 522 628 682 682
REFRIGERANT* R-22
Operating Charge
Typical (lb) 11.4 13.6 16.5 14.3 16.4 16.4
Shipping Charge (lb) 2.0 2.0 2.0 2.0 2.0 2.0
COMPRESSOR Reciprocating, Hermetic Reciprocating, Semi-Hermetic
Qty...Type 1...SF5572E 1...SF5594E 1...SF5612E/F 1...06DA818 1...06DA824 1...06DH824
(See Note)
Qty Cylinders (ea) 4 4 4 4 6 6
Speed (rpm) 3450 3450 3450 1750 1750 1750
Oil Charge (oz) (ea) 65 65 65 88 128 128
CONDENSER AIR FAN Propeller; Direct Drive
Qty...Rpm 1...850 1...1100 1...1100 1...1100 1...1100 1...1100
Diameter (in.) 26 26 26 26 26 26
Motor Hp (NEMA) 13 3 4 34 34 3 4 3 4

Watts 444 976 960 930 930 930


Nominal Cfm Total 3800 6500 7000 6500 6500 6500
CONDENSER COIL Enhanced Copper Tubes, Aluminum Lanced Fins
Rows...Fins/in. 2...17
Face Area (sq ft) 12.24 18.0 20.50 18.0 18.0 18.0
Storage Capacity (lb)** 11.26 16.56 18.87 16.56 16.56 16.56
CONNECTIONS (sweat)
Suction (in.) 118 118 118 118 118 118
Liquid (in.) 12 1 2 58 12 5 8 5 8

CONTROLS
Pressurestat Settings (psig)
High Cutout 426 7
Cut-in 320 20
Low Cutout 7 3
Cut-in 22 5
LEGEND
NEMA National Electrical Manufacturers Association
*Unit is factory supplied with holding charge only.
Typical operating charge with 25 ft of interconnecting piping
**Storage capacity of condenser coil with coil 80% full of liquid R-22 at 124 F.
NOTE: Unit 38AKS012 has one step of unloading. Full load is 100% of capac-
ity, and one step of unloading is 67% capacity. Unit 38AKS012 has the follow-
ing unloader settings: load is 70 1 psig and unload is 60 2 psig.

11
Physical data (cont)
38AKS013-024
UNIT 38AKS 013 014 016 024
NOMINAL CAPACITY (tons) 10 1212 15 20
OPERATING WEIGHTS (lb)
With Aluminum-Fin Coil 732 779 789 900
With Copper-Fin Coil 825 919 929 1040
REFRIGERANT* R-22
Shipping Charge (lb) 2.1 3.1 3.1 3.1
Operating Charge, Typical (lb) 22 23 23 28
COMPRESSOR Reciprocating, Semi-Hermetic
Model 06DD824 06DD328 06DD537 06EA250
No. Cylinders 6 6 6 4
Speed (rpm) 1750
Capacity Steps 33**, 66, 100 33**, 66, 100 33**, 66, 100 50, 100
Crankcase Heater Watts 125
Unloader Setting (psig)
Load 70 1
Unload 60 2
OIL CHARGE (pt) 10 10 10 15.5
CONDENSER FANS Axial Flow, Direct Drive
Quantity...Diameter (in.) 2...26
Nominal Hp 12

Nominal Airflow (cfm, total) 11,000


Speed (rpm) 1075
Watts (total) 1460
CONDENSER COIL Copper Tubes, Aluminum Fins
Rows...Fins/in. 2...15 3...15 3...15 3...15
Total Face Area (sq ft) 29.2 29.2 29.2 29.2
Storage Capacity (lb) 27.2 40.3 39.8 39.8
CONTROLS
Pressurestat (psig)
High Pressure
Cutout 395 10
Cut-in 295 20
Low Pressure
Cutout 27 4
Cut-in 67 7
FAN CYCLING CONTROLS
No. 2 Fan:
Close (psig) 255 10
Open (psig) 160 10
PRESSURE RELIEF Fusible Plug
Location Compressor Compressor Compressor Liquid Line
Temperature (F) 200 200 200 210
PIPING CONNECTIONS (in. ODM)
Suction 118 138 138 158
Liquid
58

Hot Gas Stub 38

*Unit is factory-supplied with holding charge only.


With 25 ft of interconnecting piping. Operating charge is approximate for maximum system
capacity.
**Indicates capacity step (%) with electric unloader accessory.
Storage capacity is measured at liquid saturated temperatures of 125 F for 38AKS013, 123 F
for 38AKS014, and 130 F for 38AKS016 and 024.

12
38AKS028-044
UNIT 38AKS 028 034 044
NOMINAL CAPACITY (tons) 25 30 40
OPERATING WEIGHTS (lb)
With Aluminum-Fin Coils 1650 1803 2437
With Copper-Fin Coils 1804 2009 2745
COMPRESSOR Reciprocating, Semi-Hermetic
Model 06E9265 06E9275 06E9299
Oil (pt) 20.0 20.0 19.0
No. Cylinders (ea)...Speed (rpm) 6...1750 6...1750 6...1750
Capacity Steps
Unloader Setting (psig) 100%, 66%, 33%
No. 1 Load 76
Unload 58
No. 2 Load 78
Unload 60
REFRIGERANT (R-22)
Operating Charge, Typical (lb) 30.5 43.5 65.0
CONDENSER FANS Propeller Type Direct Drive
Quantity...Diameter (in.) 2...30 3...30
Nominal Airflow (cfm) 15,700
Speed (rpm) 1140
Power Consumption (Watts ea) 1490 1750 1520
CONDENSER COIL Enhanced Copper Tubes, Lanced Aluminum Fins
Rows...Fins/in. 2...19 3...17 3...17
Total Face Area (sq ft) 39.2 39.2 58.4
Coil Storage Capacity (lb) 80% Full at 125 F 37.7 56.6 84.4
ELECTRIC CONTROLS Time GuardT Device
HIGH-PRESSURE SWITCH (psig)
Cutout 426 6 7
Cut-in 320 6 20
LOW-PRESSURE SWITCH (psig)
Cutout 27 6 3
Cut-in 44 6 5
OIL PRESSURE SWITCH (psig)
Close on Rise 9.0
Open on Fall 6.2
FAN CYCLING CONTROLS
Operating Pressure (psig)
No. 2 Fan, Close 255 6 10
Open 160 6 10
PRESSURE RELIEF Fusible Plug
PIPING CONNECTIONS
Suction in. OD 158 218 218
Liquid in. OD 78

Hot Gas Stub in. OD 58

28CB, 28LA

28CB 28LA
UNIT
008 012 008 012
OPERATING WT (lb) 90 125 100 142
REFRIGERANT R-22
DISTRIBUTOR NOZZLE
Size J5* G8* G8 E10
COIL
Face Area (sq ft) 7.37 10.35 7.44 9.79
Rows...Fins/in. 3...11 3...12
AIR QUANTITY (Cfm)
Nominal 3000 4000 3000 4000
Range 2250-3375** 3000-4650** 2250-3375** 3000-4500**

*Refrigerant control is field supplied.


Refrigerant control is factory installed (including TXV [thermostatic expansion valve]).
**Air quantities in excess of values shown may result in moisture blow-off.

13
Physical data (cont)
40RM
UNIT 40RM 007 008 012 014 016 024 028 034
NOMINAL CAPACITY (Tons) 6 712 10 1212 15 20 25 30
OPERATING WEIGHT (lb)
Base Unit with TXV 381 385 405 670 685 690 1020 1030
Plenum 97 97 97 140 140 140 180 180
FANS
Qty...Diam. (in.) 1...15 1...15 1...15 2...15 2...15 2...15 2...18 2...18
Nominal Airflow (cfm) 2400 3000 4000 5000 6000 8000 10,000 12,000
Airflow Range (cfm) 1800-3000 2250-3750 3000-5000 3750-6250 4500-7500 6000-10,000 7500-12,500 9000-15,000
Nominal Motor Hp (Standard Motor)
208/230-1-60 1.3 2.4
208/230-3-60 and 460-3-60 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0
575-3-60 1.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0
Motor Speed (rpm)
208/230-1-60 1725 1725
208/230-3-60 and 460-3-60 1725 1725 1725 1725 1725 1745 1745 1745
575-3-60 1725 1725 1725 1725 1725 1745 1755 1755
REFRIGERANT R-22
Operating charge (lb) 3.0 3.0 1.5/1.5 2.0/2.0 2.5/2.5 3.5/3.5 4.5/4.5 5.0/5.0
(approx per circuit)*
DIRECT-EXPANSION COIL Enhanced Copper Tubes, Aluminum Sine-Wave Fins
Max Working Pressure (psig) 435
Face Area (sq ft) 6.67 8.33 10.0 13.25 17.67 19.88 24.86 29.83
No. of Splits 1 1 2 2 2 2 2 2
Split Type...Percentage Face...50/50
No. of Circuits per Split 12 15 9 9 12 13 15 18
Rows...Fins/in. 3...15 3...15 3...17 3...15 3...15 3...17 3...15 3...15
STEAM COIL
Max Working Pressure (psig) 175 at 400 F
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 1...9 1...9 1...9 1...10 1...10 1...10 1...10 1...10
HOT WATER COIL
Max Working Pressure (psig) 150
Total Face Area (sq ft) 6.67 6.67 6.67 13.33 13.33 13.33 15.0 15.0
Rows...Fins/in. 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...8.5 2...12.5 2...12.5
PIPING CONNECTIONS,
Quantity...Size (in.)
DX Coil Suction (ODF) 1...118 1...118 2...118 2...118 2...118 2...118 2...138 2...138
DX Coil Liquid Refrigerant (ODF) 1...58 1...58
Steam Coil, In (MPT) 1...212 1...212
Steam Coil, Out (MPT) 1...112 1...212
Hot Water Coil, In (MPT) 1...112 1...112 1...2
Hot Water Coil, Out (MPT) 1...112 1...112 1...2
Condensate (Male PVC) 1...114
FILTERS Throwaway Factory Supplied
Quantity...Size (in.) 4...16 x 24 x 2 4...16 x 20 x 2 4...20 x 24 x 2
4...16 x 24 x 2 4...20 x 25 x 2
Access Location Either Side
LEGEND
TXV Thermostatic Expansion Valve
*Units are shipped without refrigerant charge.

14
Dimensions
38AK007-012, 38AKS008-012
DIMENSIONS ELECTRICAL CONNECTIONS
(ft-in.)
CONNECTION SIZES
UNIT 38 A B C D E F AA 1389 Dia Field Power Supply Hole
With Aluminum Coils (Standard) BB 29 Dia Power Supply Knockout
AK007 1-612 1-234 1-214 1-4516 2-9516 CC 2129 Dia Power Supply Knockout
AK008 1-8 1-612 2-91316 1-3 2-516 3-5716 DD 789 Dia Field Control Wiring Hole

AK012 1-9 1-8 2-0 1-3 2-516 3-5716


AKS008 1-6 1-434 2-91316 1-3 2-516 3-5716 SERVICE VALVE CONNECTIONS
AKS009 1-7 1-5 2-91316 1-3 2-516 3-5716 UNIT 38 SUCTION LIQUID
AKS012 1-7 1-5 2-91316 1-3 2-516 3-5716 AK007 1189 129

With Copper Coils (Optional) AK008 1189 129

AK007 1-8 1-3 1-214 1-4516 2-9516 AK012 1189 589

AK008 1-912 1-6 2-91316 1-3 2-516 3-5716 AKS008 1189 129

AK012 1-10 1-7 2-0 1-3 2-516 3-5716 AKS009 1189 589

AKS008 1-712 1-412 2-91316 1-3 2-516 3-5716 AKS012 1189 589

AKS009 1-712 1-4 2-91316 1-3 2-516 3-5716


AKS012 1-712 1-4 2-91316 1-3 2-516 3-5716
WEIGHT CHART (lb)
UNIT STD UNIT CORNER W CORNER X
38 Al Cu Al Cu Al Cu
AK007 340 386 86 106 53 65
AK008 370 438 86 114 78 95
AK012 395 472 89 118 92 116
AKS008 510 578 114 143 89 106
AKS009 564 632 133 161 97 114
AKS012 564 632 133 161 97 114

UNIT CORNER Y CORNER Z


38 Al Cu Al Cu
AK007 77 82 124 133
AK008 99 108 107 121
AK012 109 119 105 119
AKS008 133 142 173 187
AKS009 141 150 193 207
AKS012 141 150 193 207
NOTE: Al indicates weight with aluminum-fin coil (stand-
ard); Cu indicates weight with copper-fin coil (optional).
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Center of Gravity. See chart for dimensions.

3. Direction of airflow.
4. Minimum clearance (local codes or jurisdiction may prevail):
a. Bottom to combustible surfaces, 0 inches.
b. Either left or rear side of condensing unit must have 36-in. clearance for
proper airflow; the remaining side(s) must have 12-in. clearance each.
c. Overhead, 60 in., to assure proper condenser fan operation.
d. Between units, control box side, 42 in. per NEC (National Electrical Code).
e. Between unit and ungrounded surfaces, control box side, 36 in. per NEC.
f. Between unit and block or concrete walls and other grounded surfaces,
control box side, 42 in. per NEC.
5. With the exception of the clearance for the condenser coil as stated in Note
4b, a removable fence or barricade requires no clearance.
6. Units may be installed on combustible floors made from wood or Class A, B,
or C roof covering material.
7. Certified dimension drawings available on request.

15
Dimensions (cont)
38AKS013-024

NOTES:
1. Service clearances are as follows:
Side (compressor) 312 ft (1067 mm)
Side (opposite compressor) 3 ft (914 mm)
Ends 2 ft (610 mm)
Top 5 ft (1524 mm)
2. See page 17 for corner weights and unit center of
gravity.

16
38AKS013-024 (cont)

CENTER OF GRAVITY TOTAL OPERATIONAL CORNER WEIGHTS


UNIT (in.) UNIT (lb)
WEIGHT
38AKS 38AKS
X Y (lb) A B C D E F
013 38 17 013 732 94 93 93 149 151 152
013C 38 19 013C 825 119 116 115 157 159 159
014 38 16 014 779 95 94 94 164 166 166
014C 38 18 014C 919 131 129 128 176 177 178
016 38 16 016 789 95 95 96 167 168 168
016C 38 18 016C 929 131 130 130 178 180 180
024 37 17 024 900 119 114 113 179 185 190
024C 37 19 024C 1040 155 150 146 191 196 202

LEGEND
C Copper Fin Coils

17
Dimensions (cont)
38AKS028, 034

NOTES:
1. There must be 4 ft [1220 mm] for service and for
unrestricted airflow on all sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air
space above unit.
3. The approximate operating weight of the unit is:

UNIT WEIGHT WEIGHT


38AKS (lb) (kg)
028 1650 748
028C 1804 818
034 1803 818
034C 2009 911

NOTE: A C in model number indicates unit has


optional factory-installed copper-fin coil.

APPROX. OPER. WT (lb)


AT SUPPORT POINTS*
UNIT
1 2 3 4 TOTAL
38AKS
028 418 626 242 364 1650
034 459 673 272 399 1803

*Standard copper tube aluminum-fin coil.

18
38AKS044

NOTES:
1. There must be 4 ft [1220 mm] for service and for
unrestricted airflow on all sides of unit.
2. There must be minimum 8 ft [2440 mm] clear air
space above unit.
3. The approximate operating weight of the unit is:

UNIT WEIGHT WEIGHT


38AKS (lb) (kg)
044 2437 1106
044C 2745 1246

NOTE: A C in model number indicates unit has


optional factory-installed copper-fin coil.

APPROX. OPER. WT (lb)


AT LIFTING HOLES*
UNIT
1 2 3 4 TOTAL
38AKS
044 864 1077 221 275 2437

*Standard copper tube aluminum-fin coil.

19
Dimensions (cont)
40RM007-012
LEGEND
TXV Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
Rear: 39
Front: 28-69
Right side: 28-69
Left Side: 28-69
Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field installed.

UNIT UNIT WEIGHT


40RM (lb)
007 381
008 385
012 405

20
40RM014-024

LEGEND
TXV Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
Rear: 39
Front: 28-69
Right side: 28-69
Left Side: 28-69
Local codes or jurisdiction may prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.

UNIT UNIT WEIGHT


40RM (lb)
014 670
016 685
024 690

21
Dimensions (cont)
40RM028, 034

LEGEND
TXV Thermostatic Expansion Valve
NOTES:
1. Dimensions in [ ] are in millimeters.
2. Direction of airflow.
3. Recommended clearance:
Rear: 39
Front: 28-69
Right side: 28-69
Left Side: 28-69
Local codes or jurisdiction may
prevail.
4. Liquid piping not supplied by Carrier.
5. Duct flange is factory supplied and field
installed.

UNIT UNIT WEIGHT


40RM (lb)
028 1020
034 1030

22
28CB, 28LA

*Inlet flange dimensions.


Left and right ends have optional knockouts.
NOTE: Unit 28CB012 is supplied with 78 in. ODF to 58 in. SAE flare nut adapter for use with field-
supplied expansion valve.

UNIT A B C D E F G H
28CB
008 48 44
18 118
34
58
28CB 64 6018 138 1
78
012
28LA
008 42 118 1512 3558 4012 158 314 3316
28LA
012 53 138 1378 4858 5112 134 4116 2316

23
Selection procedure
NOTE: Pages 27 through 35 contain combination ratings III Determine sizes of liquid and suction lines.
for 38AK and 38AKS units matched with 40RM Series air Enter Refrigerant Piping Sizes table (page 57). The sizes
handlers and 28 Series coils. If a 38AK or 38AKS unit is shown are based on an equivalent length of pipe. This
used with a 39L or 39NX air handler, use the Carrier equivalent length is equal to the linear length of pipe
Electronic Catalog AHU (Air-Handling Unit) selection pro- indicated at the top of each sizing column, plus a 50%
gram to obtain combined ratings. allowance for fitting losses. (For a more accurate de-
I Determine cooling load, evaporator-air tempera- termination of actual equivalent length in place of us-
ture, and quantity. ing the estimated 50% value, refer to Carrier System
Given: Design Manual.) For this example, note in the linear
length column that the proper pipe size is 58 in. for
Total Cooling Capacity the liquid line and 138 in. for the suction line.
Required (TC) . . . . . . . . . . . . . . . . . . 180,000 Btuh
Sensible Heat Capacity IV Determine fan rpm and bhp (brake horsepower).
Required (SHC) . . . . . . . . . . . . . . . . . 140,000 Btuh At the Air Handler Fan Performance table (page 36),
Temperature Air Entering Condenser (Edb) . . . 95 F enter the 40RM016 section at 6000 cfm and move to
Temperature Air Entering the External Static Pressure (ESP) column. Note that
Evaporator (db/wb) . . . . . . . . . . . 80 F db, 67 F wb the conditions require 801 rpm at 2.34 bhp.
Evaporator Air Quantity . . . . . . . . . . . . . . . 6,000 cfm V Determine motor and drive
External Static Pressure . . . . . . . . . . . . . . . 0.8 in. wg
Enter the Fan Motor Data tables on pages 61 and 62,
Length of Interconnecting
and find that the standard motor for 40RM016 unit is
Refrigerant Piping . . . . . . . . . . . . . . . . 25 ft (Linear)
rated at 3.7 Hp. Since the bhp required is 2.34, a stand-
II Select condensing unit air-handler combination. ard motor satisfies the requirement and should be used.
For this example, select a 38AKS016 matched with a Next, find the type of drive that satisfies the 801 rpm
40RM016 (See Combination Ratings table, page 33.) requirement in the Drive Data tables on pages 63 and
This 38AKS016/40RM016 condensing unit air- 64. For the 40RM016 unit, the Medium-Static Drive
handler combination provides 183,000 Btuh of total table on page 63 shows an rpm range of 742-943.
cooling capacity and 141,400 Btuh of sensible capac- Since the rpm required is 801, the medium-static drive
ity at the given conditions. If other temperatures or satisfies the requirement and should be used. Select
airflow values are required, interpolate the values from the standard motor and medium-static drive combina-
the combination ratings. tion (option code HC or FD).

24
Performance data
CONDENSING UNIT RATINGS

38AK007 38AKS008
SST Air Temperature Entering Condenser (F) SST Air Temperature Entering Condenser (F)
(F) 80 85 95 100 105 115 (F) 80 85 95 100 105 115
TC 52.3 50.3 46.1 43.9 41.6 37.4 TC 68.8 66.2 61.2 58.6 56.1 50.9
25 kW 4.87 5.04 5.38 5.51 5.65 5.93 25 kW 5.69 5.89 6.24 6.41 6.55 6.79
CDT 104 109 118 123 127 137 CDT 102 106 116 120 125 134
TC 60.2 58.0 53.6 51.2 48.8 44.3 TC 78.4 75.6 70.1 67.4 64.6 59.0
30 kW 5.08 5.27 5.63 5.79 5.94 6.25 30 kW 5.92 6.14 6.55 6.74 6.91 7.20
CDT 107 111 121 125 130 140 CDT 104 108 118 122 127 136
TC 68.2 65.8 61.0 58.5 56.1 51.2 TC 87.9 85.0 79.1 76.1 73.1 67.2
35 kW 5.29 5.49 5.88 6.06 6.23 6.57 35 kW 6.15 6.40 6.86 7.07 7.27 7.62
CDT 110 114 123 128 132 142 CDT 106 111 120 124 129 138
TC 76.1 73.5 68.5 65.9 63.3 58.1 TC 97.5 94.3 88.0 84.8 81.7 75.3
40 kW 5.50 5.72 6.14 6.33 6.52 6.90 40 kW 6.38 6.65 7.17 7.41 7.63 8.04
CDT 112 117 126 130 135 144 CDT 109 113 122 127 131 140
TC 84.0 81.3 75.9 73.2 70.5 65.0 TC 107 104 97.0 93.6 90.2 83.4
45 kW 5.72 5.94 6.39 6.60 6.82 7.22 45 kW 6.61 6.91 7.48 7.74 7.99 8.46
CDT 115 119 128 133 137 146 CDT 111 115 124 129 133 142
TC 91.9 89.1 83.4 80.5 77.7 71.9 TC 117 113 106 103 99.2 92.0
50 kW 5.93 6.17 6.65 6.88 7.11 7.54 50 kW 6.83 7.16 7.78 8.08 8.36 8.88
CDT 118 122 131 135 139 148 CDT 114 118 127 131 136 144

38AK008 38AKS009
SST Air Temperature Entering Condenser (F) SST Air Temperature Entering Condenser (F)
(F) 80 85 95 100 105 115 (F) 80 85 95 100 105 115
TC 69.1 66.7 61.6 59.1 56.7 51.9 TC 82.9 79.7 73.2 70.1 66.9 60.3
25 kW 6.31 6.53 6.91 7.10 7.27 7.58 25 kW 7.52 7.75 8.16 8.35 8.51 8.78
CDT 102 107 116 120 125 134 CDT 106 111 119 124 128 137
TC 78.6 76.0 70.5 67.8 65.1 59.9 TC 94.1 90.7 83.7 80.4 76.8 69.7
30 kW 6.55 6.79 7.22 7.43 7.62 7.98 30 kW 7.94 8.20 8.66 8.88 9.07 9.40
CDT 104 109 118 123 127 137 CDT 109 114 122 127 131 140
TC 88.1 85.2 79.3 76.5 73.6 67.9 TC 105.3 101.4 94.1 90.5 86.7 79.2
35 kW 6.78 7.04 7.52 7.76 7.98 8.39 35 kW 8.36 8.64 9.16 9.41 9.63 10.0
CDT 107 111 120 125 129 139 CDT 112 116 125 129 134 142
TC 97.6 94.5 88.2 85.1 82.0 75.8 TC 116.9 113.0 104.3 100.6 96.6 88.7
40 kW 7.01 7.29 7.83 8.09 8.33 8.79 40 kW 8.78 9.09 9.66 9.93 10.2 10.6
CDT 109 114 123 127 132 141 CDT 115 119 128 132 136 145
TC 107 104 97.1 93.8 90.5 83.8 TC 127.5 123.6 115.0 111.1 106.3 98.5
45 kW 7.24 7.55 8.14 8.42 8.69 9.19 45 kW 9.20 9.53 10.2 10.5 10.7 11.3
CDT 111 116 125 129 134 143 CDT 118 122 131 135 139 147
TC 117 114 106 103 99.3 92.3 TC 139.1 135.2 125.6 121.7 116.9 108.2
50 kW 7.47 7.80 8.44 8.75 9.04 9.60 50 kW 9.62 9.99 10.7 11.0 11.3 11.9
CDT 114 118 127 132 136 145 CDT 121 125 134 138 142 150

38AK012 38AKS012
SST Air Temperature Entering Condenser (F) SST Air Temperature Entering Condenser (F)
(F) 80 85 95 100 105 115 (F) 80 85 95 100 105 115
TC 92.6 89.2 81.8 78.5 75.1 68.1 TC 84.4 81.1 74.4 71.3 68.0 61.4
25 kW 8.88 9.19 9.73 10.0 10.3 10.7 25 kW 7.51 7.74 8.15 8.34 8.50 8.78
CDT 106 110 119 124 128 138 CDT 106 110 119 124 128 137
TC 105 102 93.7 90.1 86.3 78.8 TC 95.8 92.3 85.1 81.7 78.1 71.1
30 kW 9.29 9.62 10.2 10.5 10.8 11.3 30 kW 7.92 8.17 8.64 8.86 9.05 9.40
CDT 108 113 122 126 131 140 CDT 109 113 122 126 131 139
TC 118 114 106 102 97.6 89.6 TC 107 103 95.8 92.1 88.3 80.7
35 kW 9.70 10.1 10.7 11.0 11.4 11.9 35 kW 8.33 8.61 9.14 9.38 9.61 10.0
CDT 111 116 124 129 133 142 CDT 112 116 125 129 133 142
TC 131 126 118 113 109 100 TC 119 115 107 102 98.4 90.3
40 kW 10.1 10.5 11.2 11.6 11.9 12.5 40 kW 8.74 9.05 9.63 9.91 10.2 10.6
CDT 114 118 127 131 136 145 CDT 115 119 127 132 136 145
TC 143 139 129 125 120 111 TC 130 126 117 113 109 100
45 kW 10.5 10.9 11.7 12.1 12.4 13.2 45 kW 9.15 9.49 10.1 10.4 10.7 11.2
CDT 117 121 130 134 138 147 CDT 118 122 130 134 139 147
TC 157 152 142 137 132 122 TC 142 138 128 124 119 110
50 kW 11.0 11.4 12.2 12.6 13.0 13.8 50 kW 9.57 9.94 10.6 11.0 11.3 11.9
CDT 120 124 132 137 141 150 CDT 121 125 133 137 141 150

LEGEND NOTE: For 380-v units, increase compressor power as follows:


CDT Saturated Discharge Temperature at Compressor (F) 38AKS008 Increase by 3%.
kW Compressor Power 38AKS009,012 Increase by 1%.
SST Saturated Suction Temperature (F)
TC Gross Cooling Capacity (1000 Btuh)

25
Performance data (cont)
CONDENSING UNIT RATINGS (cont)

38AKS013 38AKS024
SST Air Temperature Entering Condenser (F) SST Air Temperature Entering Condenser (F)
(F) 85 95 100 105 115 (F) 80 85 95 100 105 115
TC 86 79 75 72 66 TC 179 172 157 149 142 128
25 kW 7.5 8.0 8.2 8.4 8.8 25 kW 16.0 16.4 17.1 17.4 17.7 18.1
CDT 109 118 123 127 137 CDT 106 111 119 123 128 136
TC 96 88 85 81 74 TC 203 195 180 172 164 149
30 kW 7.9 8.4 8.7 8.9 9.3 30 kW 17.1 17.6 18.4 18.8 19.1 19.6
CDT 111 120 124 129 138 CDT 110 114 123 127 131 140
TC 106 98 94 91 83 TC 227 219 203 194 186 170
35 kW 8.3 8.8 9.1 9.4 9.8 35 kW 18.2 18.7 19.7 20.1 20.5 21.1
CDT 113 122 126 131 140 CDT 113 118 126 130 134 143
TC 117 109 105 101 93 TC 251 243 225 217 208 191
40 kW 8.6 9.3 9.6 9.8 10.4 40 kW 19.3 19.9 21.0 21.5 21.9 22.7
CDT 115 124 128 133 142 CDT 117 121 129 133 137 146
TC 129 120 116 111 103 TC 275 266 248 239 230 212
45 kW 9.0 9.7 10.0 10.3 10.9 45 kW 20.4 21.1 22.3 22.8 23.3 24.2
CDT 117 126 131 135 144 CDT 121 125 133 137 141 149
TC 141 132 127 122 113 TC 299 290 271 262 252 232
50 kW 9.4 10.1 10.5 10.8 11.5 50 kW 21.5 22.2 23.5 24.1 24.7 25.7
CDT 120 129 133 137 146 CDT 124 128 136 140 144 152

38AKS014 38AKS028
SST Air Temperature Entering Condenser (F) SST Air Temperature Entering Condenser (F)
(F) 85 95 100 105 115 (F) 80 85 95 100 105 115
TC 104 97 93 89 82 TC 238 230 213 204 196 180
25 kW 9.1 9.7 10.0 10.2 10.7 25 kW 21.9 22.2 23.2 23.7 24.1 24.9
CDT 109 119 124 129 139 CDT 107 111 120 124 129 138
TC 117 109 105 101 93 TC 269 261 242 233 224 206
30 kW 9.4 10.0 10.4 10.7 11.3 30 kW 23.3 23.6 24.8 25.4 25.9 26.8
CDT 109 119 124 129 139 CDT 110 114 123 127 131 140
TC 131 122 118 113 104 TC 300 292 271 261 252 232
35 kW 9.7 10.4 10.7 11.1 11.8 35 kW 24.7 25.0 26.4 27.0 27.6 28.7
CDT 110 120 124 129 139 CDT 112 117 125 130 134 143
TC 145 135 131 126 117 TC 333 323 301 290 279 258
40 kW 10.0 10.8 11.2 11.5 12.3 40 kW 26.1 26.4 28.0 28.7 29.3 30.6
CDT 112 121 126 130 140 CDT 115 120 128 133 137 145
TC 159 149 144 139 130 TC 365 354 330 319 307 284
45 kW 10.4 11.2 11.6 12.0 12.8 45 kW 27.3 27.8 29.5 30.3 31.1 32.4
CDT 114 123 127 132 141 CDT 118 123 131 135 140 148
TC 174 164 159 153 143 TC 398 386 361 348 336 312
50 kW 10.7 11.6 12.1 12.5 13.3 50 kW 28.8 29.3 31.2 32.0 32.9 34.4
CDT 116 124 129 134 143 CDT 121 126 134 138 142 151

38AKS016 38AKS034
SST Air Temperature Entering Condenser (F) SST Air Temperature Entering Condenser (F)
(F) 85 95 100 105 115 (F) 80 85 95 100 105 115
TC 140 131 127 122 114 TC 268 260 241 232 223 205
25 kW 13.1 13.9 14.3 14.7 15.3 25 kW 25.0 25.1 26.2 26.6 27.0 27.7
CDT 110 119 124 128 138 CDT 106 110 119 124 128 137
TC 155 145 140 136 126 TC 302 293 273 264 254 234
30 kW 13.7 14.6 15.1 15.5 16.2 30 kW 26.5 26.6 27.9 28.4 28.9 29.8
CDT 112 121 126 130 139 CDT 109 113 122 126 131 140
TC 170 160 155 150 140 TC 337 326 305 295 284 263
35 kW 14.4 15.4 15.8 16.3 17.1 35 kW 27.9 28.1 29.6 30.2 30.8 31.9
CDT 114 123 128 132 141 CDT 112 116 125 129 133 142
TC 187 176 170 165 154 TC 371 359 337 326 314 292
40 kW 15.1 16.1 16.6 17.1 18.1 40 kW 29.3 29.6 31.3 32.1 32.8 34.0
CDT 117 126 130 135 144 CDT 115 119 128 132 136 145
TC 204 192 186 180 168 TC 405 393 369 357 345 321
45 kW 15.9 16.9 17.5 18.0 19.0 45 kW 30.7 31.1 33.0 33.9 34.7 36.1
CDT 119 128 133 137 146 CDT 117 122 130 135 139 147
TC 222 209 203 197 184 TC 440 428 402 390 377 351
50 kW 16.4 17.7 18.3 18.9 20.0 50 kW 32.3 32.7 34.8 35.7 36.6 38.2
CDT 122 131 135 140 148 CDT 120 125 133 138 142 150

LEGEND
CDT Saturated Discharge Temperature at Compressor (F)
kW Compressor Power
SST Saturated Suction Temperature (F)
TC Gross Cooling Capacity (1000 Btuh)

26
CONDENSING UNIT RATINGS (cont)
LEGEND
38AKS044
CDT Saturated Discharge Temperature at Compressor (F)
SST Air Temperature Entering Condenser (F) kW Compressor Power
(F) 80 85 95 100 105 115 SST Saturated Suction Temperature (F)
TC Gross Cooling Capacity (1000 Btuh)
TC 362 352 330 319 308 287
25 kW 33.6 34.0 35.5 36.2 36.8 38.0
CDT 103 107 117 122 126 136
TC 410 398 374 362 350 326
30 kW 35.6 36.0 37.8 38.6 39.4 40.8
CDT 105 110 119 124 129 138
TC 456 444 417 404 391 365
35 kW 37.6 37.1 40.1 41.0 41.9 43.5
CDT 109 113 122 126 131 140
TC 503 490 461 447 433 405
40 kW 40.0 40.2 42.4 43.5 44.4 46.2
CDT 111 115 124 129 133 142
TC 551 536 505 489 474 444
45 kW 41.5 42.2 44.7 45.9 47.0 49.0
CDT 114 118 127 131 136 145
TC 599 584 550 534 518 485
50 kW 43.6 44.4 47.1 48.3 49.6 51.8
CDT 116 120 129 134 138 147

COMBINATION RATINGS
UNIT 38AK007

38AK007/28LA008 38AK007/40RM007
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 2000/0.14 2500/0.17 3000/0.19 Air Entering 1800/0.06 2400/0.10 3000/0.12
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 80.5 74.0 67.8 83.3 76.7 70.7 85.3 78.7 73.2 TC 78.8 72.7 66.1 82.4 76.4 70.0 84.6 79.1 73.1
85 SHC 40.7 50.6 60.2 44.0 55.9 67.1 47.1 60.9 72.5 85 SHC 39.9 49.5 62.4 44.4 58.1 70.0 50.2 64.6 73.1
kW 5.92 5.73 5.55 6.00 5.81 5.64 6.06 5.87 5.71 kW 5.87 5.70 5.51 5.97 5.80 5.62 6.03 5.88 5.71
TC 77.0 70.6 64.7 79.6 73.2 67.6 81.5 75.0 70.2 TC 75.3 69.5 63.3 78.7 72.9 67.1 80.6 75.4 70.1
95 SHC 39.3 49.2 58.7 42.6 54.5 65.4 45.7 59.5 70.1 95 SHC 38.4 48.3 60.2 43.0 56.8 67.1 48.9 63.3 70.1
kW 6.43 6.21 6.00 6.52 6.30 6.11 6.58 6.36 6.19 kW 6.37 6.17 5.97 6.48 6.29 6.09 6.55 6.37 6.19
TC 75.3 68.9 63.1 77.7 71.4 66.0 79.5 73.2 68.7 TC 73.6 67.8 61.8 76.8 71.1 65.6 78.6 73.6 68.5
100 SHC 38.7 48.5 57.9 42.0 53.8 64.4 45.1 58.8 68.7 100 SHC 37.7 47.6 58.9 42.3 56.0 65.6 48.2 62.6 68.5
kW 6.69 6.45 6.23 6.77 6.54 6.34 6.84 6.61 6.44 kW 6.61 6.40 6.18 6.73 6.52 6.32 6.80 6.61 6.43
TC 73.4 67.2 61.6 75.8 69.6 64.4 77.5 71.3 67.2 TC 71.8 66.2 60.3 74.9 69.3 64.0 76.7 71.7 66.9
105 SHC 38.0 47.8 57.2 41.3 53.1 63.4 44.4 58.1 67.2 105 SHC 36.9 47.0 57.7 41.6 55.3 64.0 47.6 61.9 66.9
kW 6.94 6.69 6.46 7.03 6.78 6.57 7.10 6.85 6.68 kW 6.87 6.64 6.39 7.00 6.77 6.55 7.08 6.87 6.67
TC 69.6 63.7 58.3 71.8 65.8 61.2 73.3 67.4 64.1 TC 68.1 62.7 57.2 70.9 65.6 60.8 72.5 67.8 63.7
115 SHC 36.6 46.4 55.5 39.9 51.7 61.1 43.0 56.6 64.1 115 SHC 35.3 45.6 55.1 40.1 53.8 60.8 46.2 60.4 63.6
kW 7.44 7.16 6.91 7.55 7.26 7.04 7.61 7.33 7.18 kW 7.36 7.11 6.86 7.50 7.25 7.02 7.57 7.35 7.16

38AK007/28CB008 38AK007/40RM008
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 2000/0.12 2500/0.14 3000/0.16 Air Entering 2250/0.06 3000/0.10 3750/0.12
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 82.9 76.1 69.7 85.8 79.0 72.9 87.8 81.0 75.5 TC 85.1 78.5 72.0 87.6 82.0 76.4 89.7 84.6 79.7
85 SHC 41.9 52.2 62.2 45.4 57.9 69.5 48.7 63.1 75.1 85 SHC 44.3 57.1 69.9 52.2 66.1 76.4 57.0 74.8 79.7
kW 5.99 5.79 5.61 6.07 5.88 5.69 6.13 5.94 5.77 kW 6.05 5.86 5.68 6.12 5.96 5.80 6.18 6.03 5.89
TC 79.3 72.7 66.6 81.9 75.3 69.6 83.8 77.1 72.4 TC 81.2 74.9 68.8 83.4 78.1 73.0 85.3 80.5 76.2
95 SHC 40.5 50.7 60.6 44.0 56.4 67.6 47.3 61.7 72.4 95 SHC 42.7 55.5 67.1 50.8 64.4 73.0 55.5 73.2 76.2
kW 6.50 6.28 6.07 6.59 6.37 6.17 6.66 6.43 6.27 kW 6.57 6.36 6.15 6.64 6.46 6.29 6.71 6.55 6.40
TC 77.4 70.9 64.9 79.9 73.4 67.9 81.7 75.2 70.8 TC 79.2 73.1 67.1 81.3 76.1 71.3 83.2 78.5 74.5
100 SHC 39.9 50.0 59.8 43.3 55.6 66.6 46.6 60.9 70.8 100 SHC 41.9 54.7 65.6 50.1 63.6 71.3 54.7 72.4 74.4
kW 6.76 6.52 6.30 6.86 6.62 6.41 6.92 6.68 6.52 kW 6.82 6.59 6.37 6.90 6.71 6.53 6.97 6.80 6.65
TC 75.5 69.1 63.3 77.9 71.5 66.3 79.6 73.2 69.2 TC 77.3 71.2 65.4 79.2 74.1 69.5 81.0 76.5 72.7
105 SHC 39.2 49.3 59.0 42.6 54.9 65.6 45.9 60.1 69.2 105 SHC 41.1 53.9 64.2 49.4 62.7 69.5 54.0 71.6 72.7
kW 7.01 6.76 6.53 7.12 6.86 6.64 7.18 6.93 6.77 kW 7.10 6.85 6.61 7.18 6.97 6.78 7.26 7.07 6.91
TC 71.6 65.4 59.9 73.7 67.6 63.0 75.3 69.2 66.0 TC 73.2 67.3 61.8 74.8 70.0 65.8 76.4 72.2 68.9
115 SHC 37.7 47.8 57.2 41.2 53.4 63.0 44.4 58.5 66.0 115 SHC 39.4 52.2 61.1 47.9 61.0 65.8 52.4 69.9 68.9
kW 7.52 7.24 6.98 7.63 7.35 7.13 7.70 7.42 7.27 kW 7.60 7.33 7.07 7.68 7.45 7.26 7.75 7.55 7.40

LEGEND
Out of Range ENTERING-AIR DRY BULB TEMP (F)
BF Bypass Factor BYPASS 79 78 77 76 76 Under 75
Edb Entering Dry Bulb FACTOR
Ewb Entering Wet Bulb (BF) 81 82 83 84 85 Over 85
kW Compressor Motor Power Input Correction Factor
SHC Sensible Heat Capacity (1000 Btuh) Gross
TC Total Capacity (1000 Btuh) Gross .05 1.04 2.07 3.11 4.14 5.18
.10 .98 1.96 2.94 3.94 4.91 Use formula
NOTES: .20 .87 1.74 2.62 3.49 4.36 shown
1. For 380-v units, increase compressor power as follows: below.
.30 .76 1.53 2.29 3.05 3.82
38AKS008 Increase by 3% 38AKS009, 012 Increase by 1%
2. SHC is based on 80 F edb temperature of air-entering evaporator coil. Interpolation is permissible.
Below 80 F edb, subtract (corr factor x cfm) from SHC. Correction Factor =1.10 x (1 BF) x (edb 80).
Above 80 F edb, add (corr factor x cfm) to SHC.

27
Performance data (cont)
COMBINATION RATINGS (cont)
UNIT 38AK008

38AK008/40RM007 38AK008/40RM012
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 1800/0.06 2400/0.10 3000/0.12 Air Entering 3000/0.05 4000/0.07 5000/0.12
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 92.0 84.7 96.8 89.6 80.9 99.9 93.0 84.3 TC 110.2 102.0 94.2 114.0 106.3 99.8 116.1 108.9 104.3
85 SHC 45.6 54.1 49.8 63.4 80.9 55.3 69.9 84.3 85 SHC 58.1 76.0 91.5 66.0 87.2 99.7 74.8 99.6 104.3
kW 7.22 7.02 7.35 7.16 6.92 7.44 7.25 7.01 kW 7.72 7.50 7.28 7.82 7.61 7.43 7.88 7.68 7.56
TC 88.2 81.3 73.7 92.7 85.8 77.9 95.4 89.0 81.2 TC 105.0 97.2 90.0 108.3 101.2 95.3 110.2 103.5 99.8
95 SHC 43.9 52.8 68.6 48.3 61.9 77.8 53.8 68.4 81.2 95 SHC 55.9 74.0 88.0 63.8 84.8 95.3 72.7 97.4 99.8
kW 7.83 7.59 7.32 7.99 7.75 7.47 8.08 7.86 7.59 kW 8.41 8.14 7.89 8.53 8.28 8.08 8.60 8.36 8.23
TC 86.3 79.6 72.1 90.6 83.9 76.3 93.2 87.0 79.5 TC 102.5 94.9 87.9 105.7 98.7 93.1 107.5 100.9 97.6
100 SHC 43.1 52.1 67.4 47.5 61.2 76.2 53.1 67.6 79.5 100 SHC 54.9 73.0 86.3 62.8 83.7 93.1 71.8 96.3 97.6
kW 8.14 7.88 7.60 8.30 8.04 7.75 8.40 8.16 7.88 kW 8.75 8.46 8.20 8.87 8.61 8.39 8.94 8.69 8.56
TC 84.4 77.8 70.5 88.5 81.9 74.6 91.0 84.9 77.9 TC 100.0 92.5 85.8 103.0 96.2 90.9 98.2 95.3
105 SHC 42.3 51.4 66.1 46.7 60.4 74.6 52.3 66.8 77.9 105 SHC 53.9 71.9 84.5 61.8 82.5 90.9 95.2 95.3
kW 8.43 8.15 7.84 8.61 8.33 8.02 8.71 8.45 8.15 kW 9.09 8.78 8.49 9.22 8.93 8.71 9.02 8.89
TC 80.3 74.1 67.3 84.1 77.9 71.3 86.3 80.7 74.4 TC 94.6 87.6 81.3 97.3 90.9 86.2 92.7 90.6
115 SHC 40.6 50.0 63.4 45.0 58.8 71.3 50.8 65.3 74.4 115 SHC 51.7 69.8 80.8 59.6 80.1 86.2 93.0 90.6
kW 9.02 8.70 8.37 9.21 8.89 8.56 9.32 9.03 8.72 kW 9.73 9.38 9.07 9.86 9.55 9.31 9.63 9.53

38AK008/40RM008
Evaporator Air Cfm/BF
Temp (F)
Air Entering 2250/0.06 3000/0.10 3750/0.12
Condenser Evaporator Air Ewb (F)
(Edb)
72 67 62 72 67 62 72 67 62
TC 100.1 92.4 84.3 104.2 97.3 89.3 107.1 100.5 93.0
85 SHC 50.5 63.2 80.4 57.7 72.5 89.3 63.1 81.2 93.0
kW 7.44 7.23 7.01 7.56 7.37 7.15 7.63 7.45 7.25
TC 95.8 88.4 80.9 99.4 92.8 85.6 102.0 95.9 89.2
95 SHC 48.7 61.4 77.5 56.1 70.6 85.6 61.3 79.3 89.2
kW 8.09 7.84 7.57 8.22 7.99 7.74 8.31 8.10 7.87
TC 93.6 86.4 79.1 97.0 90.6 83.7 99.5 93.6 87.3
100 SHC 47.8 60.5 75.9 55.3 69.7 83.7 60.4 78.4 87.3
kW 8.41 8.14 7.86 8.54 8.30 8.04 8.64 8.41 8.17
TC 91.4 84.3 77.2 94.6 88.4 81.8 97.0 91.3 85.3
105 SHC 46.9 59.6 74.3 54.5 68.8 81.8 59.6 77.5 85.3
kW 8.73 8.43 8.13 8.86 8.60 8.32 8.96 8.72 8.47
TC 86.8 80.1 73.5 89.6 83.8 77.9 91.7 86.5 81.3
115 SHC 45.0 57.8 71.1 52.9 66.8 77.9 57.7 75.6 81.3
kW 9.34 9.01 8.67 9.48 9.19 8.89 9.59 9.32 9.06

UNIT 38AK012

38AK012/40RM012 38AK012/40RM014
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 3000/0.05 4000/0.07 5000/0.12 Air Entering 3750/0.06 5000/0.08 6250/0.10
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 133.6 123.2 112.5 139.7 129.6 119.2 143.4 133.7 124.2 TC 141.9 130.2 120.2 147.2 136.2 127.6 150.9 140.1 133.5
85 SHC 67.7 85.1 106.7 75.9 97.9 119.2 84.2 109.7 124.2 85 SHC 75.2 95.6 116.3 85.0 111.2 127.6 94.8 125.0 133.5
kW 10.73 10.41 10.08 10.92 10.61 10.29 11.03 10.74 10.45 kW 10.99 10.63 10.32 11.15 10.81 10.55 11.27 10.93 10.73
TC 127.5 118.2 108.8 132.6 123.7 114.9 135.6 127.2 119.6 TC 134.5 124.1 115.6 138.9 129.3 122.3 142.1 132.7 127.6
95 SHC 65.2 82.9 103.7 73.2 95.2 114.8 81.5 107.0 119.5 95 SHC 72.4 92.8 112.4 81.9 108.3 122.3 91.8 121.5 127.6
kW 11.63 11.21 10.78 11.86 11.46 11.06 12.00 11.62 11.27 kW 11.95 11.48 11.09 12.15 11.71 11.39 12.29 11.87 11.64
TC 124.8 115.0 105.3 130.1 120.7 111.7 133.2 124.3 116.7 TC 132.2 121.1 112.4 136.7 126.5 119.4 140.0 130.1 125.0
100 SHC 64.1 81.6 100.7 72.2 93.8 111.7 80.7 105.9 116.7 100 SHC 71.4 91.4 109.6 81.1 107.1 119.4 91.1 120.3 125.0
kW 12.09 11.68 11.28 12.31 11.92 11.54 12.44 12.07 11.75 kW 12.40 11.94 11.57 12.59 12.16 11.87 12.73 12.31 12.10
TC 121.5 112.3 103.2 126.3 117.6 109.3 129.1 120.8 114.1 TC 128.2 117.8 109.8 132.3 122.9 116.5 135.4 126.1 121.8
105 SHC 62.7 80.4 99.0 70.7 92.3 109.3 79.2 104.4 114.1 105 SHC 69.9 89.9 107.4 79.5 105.5 116.5 89.5 118.4 121.8
kW 12.47 12.05 11.64 12.69 12.29 11.91 12.81 12.44 12.13 kW 12.77 12.30 11.94 12.96 12.53 12.24 13.10 12.68 12.48
TC 115.5 106.4 97.6 120.0 111.4 103.7 122.6 114.4 108.6 TC 121.9 111.5 104.0 125.8 116.4 110.7 119.5 116.0
115 SHC 60.2 77.9 94.3 68.3 89.5 103.7 77.0 101.8 108.6 115 SHC 67.5 87.0 102.5 77.1 102.7 110.7 115.4 116.0
kW 13.49 12.91 12.35 13.77 13.22 12.73 13.94 13.42 13.05 kW 13.89 13.23 12.75 14.14 13.54 13.18 13.74 13.52

LEGEND ENTERING-AIR DRY BULB TEMP (F)


Out of Range BYPASS 79 78 77 76 76 Under 75
BF Bypass Factor FACTOR
Edb Entering Dry Bulb (BF) 81 82 83 84 85 Over 85
Ewb Entering Wet Bulb Correction Factor
kW Compressor Motor Power Input
SHC Sensible Heat Capacity (1000 Btuh) Gross .05 1.04 2.07 3.11 4.14 5.18 Use formula
TC Total Capacity (1000 Btuh) Gross .10 .98 1.96 2.94 3.94 4.91 shown
.20 .87 1.74 2.62 3.49 4.36 below.
NOTES: .30 .76 1.53 2.29 3.05 3.82
1. For 380-v units, increase compressor power as follows:
38AKS008 Increase by 3% 38AKS009, 012 Increase by 1%
2. SHC is based on 80 F edb temperature of air-entering evaporator coil. Interpolation is permissible.
Below 80 F edb, subtract (corr factor x cfm) from SHC. Correction Factor =1.10 x (1 BF) x (edb 80).
Above 80 F edb, add (corr factor x cfm) to SHC.

28
COMBINATION RATINGS (cont)
UNIT 38AKS008

38AKS008/28LA008 38AKS008/28CB012
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 2250/0.14 3000/0.18 3375/0.19 Air Entering 3000/0.17 4000/0.21 4650/0.23
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 97.8 89.9 82.4 103 94.5 87.1 104 96.1 88.9 TC 106 97.2 89.4 110 101 94.4 112 103 97.5
85 SHC 48.6 59.8 70.8 53.6 67.8 81.4 55.9 71.6 85.8 85 SHC 54.7 69.0 82.7 60.7 78.7 93.6 64.3 84.6 97.5
kW 6.75 6.53 6.30 6.88 6.66 6.45 6.92 6.71 6.50 kW 6.96 6.74 6.51 7.07 6.84 6.66 7.11 6.89 6.74
TC 93.7 86.0 78.8 98.1 90.3 83.2 99.6 91.8 85.1 TC 101 92.8 85.4 105 96.5 90.4 106 98.1 93.5
95 SHC 47.0 58.1 69.0 52.0 66.1 79.3 54.3 69.9 83.4 95 SHC 53.0 67.2 80.6 58.9 76.8 90.3 62.6 82.6 93.5
kW 7.37 7.10 6.83 7.51 7.25 7.00 7.57 7.30 7.06 kW 7.61 7.34 7.08 7.73 7.46 7.25 7.79 7.52 7.36
TC 91.6 84.0 76.9 95.8 88.1 81.3 97.2 89.6 83.2 TC 98.5 90.5 83.4 102 94.0 88.5 104 95.6 91.5
100 SHC 46.2 57.3 68.1 51.2 65.3 78.2 53.5 69.0 82.1 100 SHC 52.1 66.2 79.4 58.0 75.9 88.5 61.6 81.6 91.5
kW 7.67 7.38 7.09 7.83 7.54 7.27 7.88 7.59 7.34 kW 7.93 7.63 7.35 8.05 7.76 7.55 8.11 7.82 7.66
TC 89.5 82.0 75.0 93.4 85.9 79.3 94.8 87.3 81.2 TC 96.0 88.1 81.3 99.5 91.6 86.5 101 93.1 89.5
105 SHC 45.3 56.4 67.2 50.3 64.4 77.1 52.6 68.1 80.7 105 SHC 51.2 65.3 78.3 57.1 74.9 86.5 60.7 80.6 89.5
kW 7.97 7.65 7.34 8.12 7.81 7.53 8.19 7.87 7.61 kW 8.23 7.91 7.61 8.37 8.05 7.84 8.43 8.12 7.97
TC 85.0 77.9 71.2 88.6 81.4 75.4 89.9 82.7 77.4 TC 91.0 83.5 77.3 94.1 86.5 82.5 95.5 88.0 85.3
115 SHC 43.7 54.7 65.3 48.6 62.6 74.6 50.9 66.3 77.4 115 SHC 49.4 63.4 75.9 55.3 73.0 82.5 58.9 78.4 85.3
kW 8.54 8.17 7.82 8.71 8.36 8.04 8.78 8.42 8.15 kW 8.83 8.46 8.14 8.98 8.62 8.40 9.05 8.68 8.55

38AKS008/28CB008 38AKS008/40RM007
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 2250/0.13 3000/0.16 3375/0.18 Air Entering 1800/0.06 2400/0.10 3000/0.12
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 99.6 91.4 83.8 104 96.2 88.6 106 97.8 90.5 TC 91.8 84.5 96.7 89.4 80.6 99.8 92.8 84.1
85 SHC 49.4 60.8 71.9 54.5 69.0 82.8 57.0 72.9 87.3 85 SHC 45.5 54.0 49.8 63.4 80.6 55.3 69.8 84.1
kW 6.80 6.57 6.34 6.93 6.70 6.49 6.97 6.75 6.54 kW 6.57 6.37 6.71 6.50 6.26 6.79 6.60 6.36
TC 95.4 87.5 80.1 99.8 91.8 84.7 101 93.4 86.5 TC 88.1 81.2 73.5 92.6 85.7 77.7 95.4 88.9 81.0
95 SHC 47.8 59.1 70.1 52.9 67.3 80.7 55.3 71.1 84.9 95 SHC 43.9 52.8 68.5 48.2 61.9 77.7 53.8 68.3 81.0
kW 7.43 7.15 6.88 7.57 7.31 7.05 7.63 7.36 7.11 kW 7.17 6.93 6.67 7.33 7.09 6.81 7.42 7.20 6.93
TC 93.2 85.5 78.2 97.4 89.6 82.7 98.9 91.1 84.6 TC 86.1 79.4 71.9 90.5 83.7 76.0 93.1 86.8 79.3
100 SHC 46.9 58.2 69.2 52.0 66.4 79.6 54.4 70.2 83.6 100 SHC 43.1 52.1 67.1 47.4 61.1 76.0 53.0 67.5 79.3
kW 7.73 7.43 7.14 7.89 7.60 7.32 7.94 7.65 7.39 kW 7.46 7.21 6.92 7.62 7.37 7.08 7.72 7.48 7.20
TC 90.9 83.4 76.2 95.0 87.4 80.6 96.4 88.8 82.6 TC 84.2 77.6 70.4 88.3 81.8 74.4 90.8 84.7 77.7
105 SHC 46.1 57.3 68.3 51.2 65.5 78.4 53.5 69.4 82.2 105 SHC 42.2 51.4 65.9 46.6 60.3 74.4 52.3 66.8 77.7
kW 8.03 7.70 7.39 8.19 7.88 7.59 8.25 7.94 7.67 kW 7.73 7.46 7.15 7.91 7.63 7.32 8.02 7.76 7.46
TC 86.4 79.1 72.4 90.1 82.7 76.6 91.4 84.0 78.7 TC 82.6 73.0 63.1 88.8 78.9 68.9 92.7 83.3 73.6
115 SHC 44.4 55.5 66.3 49.4 63.6 75.9 51.8 67.5 78.7 115 SHC 41.5 49.6 60.0 46.8 59.1 68.9 52.9 66.2 73.6
kW 8.60 8.24 7.88 8.79 8.42 8.11 8.85 8.49 8.22 kW 8.21 7.99 7.76 8.35 8.12 7.89 8.44 8.23 8.00

38AKS008/28LA012 LEGEND
Evaporator Air Cfm/BF Out of Range
Temp (F) BF Bypass Factor
Air Entering 3000/0.15 3750/0.18 4500/0.20
Edb Entering Dry Bulb
Condenser Evaporator Air Ewb (F) Ewb Entering Wet Bulb
(Edb) kW Compressor Motor Power Input
72 67 62 72 67 62 72 67 62
SHC Sensible Heat Capacity (1000 Btuh) Gross
TC 106 97.3 89.7 109 100 93.5 111 103 97.2 TC Total Capacity (1000 Btuh) Gross
85 SHC 55.1 69.6 83.5 59.7 77.2 92.1 64.1 84.2 97.2
kW 6.96 6.74 6.52 7.05 6.82 6.63 7.10 6.88 6.73 NOTES:
TC 101 92.9 85.7 104 95.8 89.5 106 97.8 93.3 1. For 380-v units, increase compressor power as follows:
95 SHC 53.3 67.8 81.4 58.0 75.4 89.2 62.3 82.3 93.3 38AKS008 Increase by 3% 38AKS009, 012 Increase by 1%
kW 7.62 7.34 7.09 7.70 7.44 7.22 7.77 7.50 7.66 2. SHC is based on 80 F edb temperature of air-entering evaporator coil.
Below 80 F edb, subtract (corr factor x cfm) from SHC.
TC 98.6 90.6 83.7 101 93.4 87.6 103 95.3 91.3 Above 80 F edb, add (corr factor x cfm) to SHC.
100 SHC 52.5 66.9 80.2 57.1 74.5 87.5 61.4 81.3 91.3
kW 7.93 7.63 7.36 8.03 7.74 7.51 8.09 7.81 7.66 ENTERING-AIR DRY BULB TEMP (F)
TC 96.1 88.3 81.6 98.7 90.9 85.6 101 92.8 89.2 BYPASS 79 78 77 76 76 Under 75
105 SHC 51.6 66.0 79.0 56.2 73.5 85.6 60.5 80.2 89.2 FACTOR
kW 8.23 7.91 7.63 8.34 8.02 7.80 8.41 8.10 7.95 (BF) 81 82 83 84 85 Over 85
TC 91.1 83.6 77.5 93.5 86.0 81.7 95.1 87.8 85.1 Correction Factor
115 SHC 49.7 64.1 76.5 54.4 71.5 81.7 58.6 78.1 85.1 .05 1.04 2.07 3.11 4.14 5.18
kW 8.83 8.46 8.16 8.95 8.58 8.37 9.03 8.67 8.55 .10 .98 1.96 2.94 3.94 4.91 Use formula
shown
.20 .87 1.74 2.62 3.49 4.36 below.
.30 .76 1.53 2.29 3.05 3.82
Interpolation is permissible.
Correction Factor =1.10 x (1 BF) x (edb 80).

29
Performance data (cont)
COMBINATION RATINGS (cont)
UNIT 38AKS008 (cont)

38AKS008/40RM008 38AKS008/40RM012
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 2250/0.06 3000/0.10 3750/0.12 Air Entering 3000/0.05 4000/0.07 5000/0.12
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 100.1 92.2 84.1 104.2 97.2 89.1 107.1 100.4 92.9 TC 110.3 102.0 94.1 114.1 106.4 99.7 116.3 109.0 104.3
85 SHC 50.4 63.1 80.2 57.7 72.4 89.1 63.1 81.2 92.9 85 SHC 58.1 76.0 91.4 66.0 87.2 99.7 74.8 99.6 104.3
kW 6.80 6.58 6.36 6.92 6.72 6.49 7.00 6.81 6.60 kW 7.08 6.85 6.63 7.19 6.98 6.79 7.25 7.05 6.92
TC 95.7 88.3 80.7 99.3 92.7 85.5 101.9 95.8 89.1 TC 105.0 97.2 89.9 108.4 101.2 95.2 110.3 103.4 99.8
95 SHC 48.6 61.4 77.3 56.1 70.6 85.5 61.3 79.3 89.1 95 SHC 55.9 73.9 87.9 63.8 84.8 95.2 72.8 97.4 99.7
kW 7.44 7.18 6.92 7.56 7.33 7.08 7.65 7.44 7.21 kW 7.75 7.49 7.24 7.87 7.62 7.42 7.94 7.70 7.57
TC 93.5 86.2 78.8 96.9 90.5 83.5 99.4 93.4 87.1 TC 102.4 94.8 87.7 105.6 98.6 93.0 107.4 100.8 97.5
100 SHC 47.7 60.5 75.7 55.3 69.6 83.5 60.4 78.4 87.1 100 SHC 54.9 72.9 86.1 62.8 83.6 93.0 71.8 96.3 97.5
kW 7.74 7.46 7.19 7.86 7.62 7.36 7.96 7.73 7.50 kW 8.07 7.78 7.52 8.19 7.93 7.72 8.26 8.01 7.89
TC 91.2 84.1 77.0 94.4 88.2 81.6 96.8 91.1 85.2 TC 99.7 92.3 85.6 102.7 96.0 90.7 98.0 95.1
105 SHC 46.8 59.6 74.2 54.5 68.7 81.6 59.5 77.4 85.2 105 SHC 53.8 71.9 84.3 61.7 82.4 90.7 95.1 95.1
kW 8.03 7.73 7.43 8.17 7.91 7.63 8.27 8.03 7.78 kW 8.39 8.08 7.79 8.52 8.23 8.01 8.32 8.20
TC 93.3 82.4 71.9 98.6 88.7 78.8 102.7 93.3 84.1 TC 107.4 95.3 84.5 113.0 101.5 92.5 105.2 99.4
115 SHC 47.7 58.8 69.8 55.9 68.9 78.8 61.5 78.3 84.1 115 SHC 56.9 73.1 83.4 65.6 85.0 92.5 98.1 99.4
kW 8.46 8.21 7.96 8.58 8.35 8.12 8.68 8.46 8.24 kW 8.79 8.50 8.25 8.91 8.65 8.44 8.73 8.60

UNIT 38AKS009

38AKS009/40RM008 38AKS009/40RM012
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 2250/0.06 3000/0.10 3750/0.12 Air Entering 3000/0.05 4000/0.07 5000/0.12
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 111.9 103.3 117.3 109.3 99.5 120.7 113.0 103.5 TC 123.9 114.9 105.9 128.7 120.1 111.8 131.5 123.4 116.4
85 SHC 55.3 68.0 62.1 77.6 99.4 67.8 86.2 103.4 85 SHC 63.7 81.5 101.2 71.6 93.5 111.8 80.1 105.5 116.4
kW 9.05 8.69 9.27 8.94 8.53 9.41 9.09 8.69 kW 9.54 9.17 8.79 9.74 9.39 9.04 9.86 9.52 9.23
TC 106.6 98.1 89.2 111.5 103.7 94.4 114.8 107.4 98.5 TC 118.1 109.1 100.4 122.6 114.2 106.3 125.3 117.2 111.1
95 SHC 53.1 65.6 84.6 60.2 75.2 94.4 65.8 83.9 98.5 95 SHC 61.3 79.1 96.6 69.3 90.8 106.3 77.9 103.0 111.1
kW 9.78 9.34 8.90 10.02 9.63 9.16 10.19 9.81 9.37 kW 10.36 9.90 9.46 10.59 10.16 9.76 10.72 10.31 10.00
TC 104.3 95.9 87.2 109.0 101.4 92.4 112.2 104.9 96.4 TC 115.4 106.6 98.1 119.8 111.4 104.0 122.3 114.4 108.8
100 SHC 52.2 64.7 82.9 59.3 74.2 92.4 64.8 83.0 96.4 100 SHC 60.2 78.0 94.7 68.2 89.5 103.9 76.9 101.8 108.7
kW 10.13 9.67 9.20 10.38 9.97 9.49 10.56 10.16 9.70 kW 10.73 10.26 9.79 10.97 10.52 10.11 11.11 10.68 10.37
TC 101.6 93.6 85.4 105.8 98.7 90.4 108.7 102.0 94.2 TC 111.9 103.5 95.6 115.8 108.0 101.2 118.0 110.6 105.8
105 SHC 51.1 63.7 81.4 58.3 73.1 90.4 63.6 81.8 94.2 105 SHC 58.8 76.7 92.7 66.7 88.0 101.2 75.4 100.3 105.8
kW 10.46 10.05 9.62 10.67 10.31 9.88 10.83 10.48 10.08 kW 10.99 10.56 10.15 11.19 10.79 10.44 11.30 10.92 10.67
TC 96.6 88.7 80.7 100.5 93.5 85.8 103.3 96.7 89.6 TC 106.5 98.2 90.5 110.2 102.5 96.1 105.0 100.9
115 SHC 49.0 61.6 77.3 56.5 70.9 85.8 61.7 79.7 89.6 115 SHC 56.6 74.4 88.4 64.5 85.4 96.1 98.0 100.9
kW 11.16 10.60 10.03 11.44 10.94 10.39 11.64 11.17 10.66 kW 11.87 11.28 10.73 12.13 11.58 11.13 11.76 11.47

LEGEND ENTERING-AIR DRY BULB TEMP (F)


Out of Range BYPASS 79 78 77 76 76 Under 75
BF Bypass Factor FACTOR
Edb Entering Dry Bulb (BF) 81 82 83 84 85 Over 85
Ewb Entering Wet Bulb Correction Factor
kW Compressor Motor Power Input
SHC Sensible Heat Capacity (1000 Btuh) Gross .05 1.04 2.07 3.11 4.14 5.18
Use formula
TC Total Capacity (1000 Btuh) Gross .10 .98 1.96 2.94 3.94 4.91 shown
.20 .87 1.74 2.62 3.49 4.36
NOTES: .30 .76 1.53 2.29 3.05 3.82 below.
1. For 380-v units, increase compressor power as follows:
38AKS008 Increase by 3% 38AKS009, 012 Increase by 1% Interpolation is permissible.
2. SHC is based on 80 F edb temperature of air-entering evaporator coil. Correction Factor =1.10 x (1 BF) x (edb 80).
Below 80 F edb, subtract (corr factor x cfm) from SHC.
Above 80 F edb, add (corr factor x cfm) to SHC.

30
COMBINATION RATINGS (cont)
UNIT 38AKS012

38AKS012/40RM008 38AKS012/40RM014
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 2250/0.06 3000/0.10 3750/0.12 Air Entering 3750/0.06 5000/0.08 6250/0.10
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 113.1 104.3 118.7 110.5 100.3 122.3 114.3 104.4 TC 132.4 122.0 113.7 136.7 127.2 120.4 139.8 130.5 125.6
85 SHC 55.8 68.4 62.6 78.1 100.3 68.4 86.7 104.4 85 SHC 71.6 91.8 110.7 81.1 107.4 120.4 91.0 120.5 125.6
kW 8.98 8.62 9.20 8.87 8.46 9.34 9.02 8.62 kW 9.75 9.33 9.00 9.92 9.54 9.26 10.04 9.67 9.48
TC 108.2 100.0 91.3 113.0 105.5 96.4 116.2 109.0 100.3 TC 125.5 115.8 108.4 129.3 120.5 114.7 132.0 123.4 119.7
95 SHC 53.8 66.5 86.4 60.7 76.0 96.4 66.3 84.6 100.3 95 SHC 68.9 89.0 106.3 78.4 104.5 114.7 88.3 117.2 119.7
kW 9.69 9.30 8.89 9.91 9.56 9.13 10.06 9.73 9.31 kW 10.50 10.04 9.70 10.68 10.26 9.99 10.81 10.40 10.22
TC 105.2 96.6 87.6 110.1 102.3 93.0 113.5 105.9 97.1 TC 123.3 112.9 105.3 127.2 117.8 112.0 130.2 121.0 117.3
100 SHC 52.6 65.0 83.3 59.7 74.6 93.0 65.3 83.4 97.1 100 SHC 68.0 87.6 103.6 77.6 103.4 112.0 87.7 116.1 117.2
kW 10.05 9.67 9.27 10.27 9.92 9.51 10.42 10.09 9.69 kW 10.86 10.39 10.06 11.03 10.62 10.35 11.16 10.76 10.59
TC 103.0 94.5 85.9 107.6 100.0 91.1 110.7 103.5 95.1 TC 120.2 110.0 102.9 123.9 114.8 109.4 117.8 114.5
105 SHC 51.6 64.1 81.8 58.9 73.6 91.1 64.3 82.4 95.1 105 SHC 66.8 86.3 101.5 76.4 102.1 109.4 114.6 114.5
kW 10.41 10.02 9.61 10.63 10.27 9.86 10.78 10.44 10.05 kW 11.23 10.75 10.41 11.40 10.97 10.72 11.12 10.96
TC 97.5 89.7 81.7 101.5 94.5 86.7 104.3 97.7 90.5 TC 113.0 103.4 97.2 107.8 103.3 110.4 108.2
115 SHC 49.4 62.0 78.2 56.8 71.3 86.7 62.1 80.1 90.5 115 SHC 64.1 83.3 96.7 99.0 103.3 111.1 108.2
kW 11.05 10.56 10.07 11.29 10.86 10.38 11.47 11.06 10.61 kW 12.00 11.41 11.02 11.68 11.40 11.85 11.70

38AKS012/40RM012 LEGEND
Evaporator Air Cfm/BF Out of Range
Temp (F)
Air Entering 3000/0.05 4000/0.07 5000/0.12 BF Bypass Factor
Edb Entering Dry Bulb
Condenser Evaporator Air Ewb (F) Ewb Entering Wet Bulb
(Edb) kW Compressor Motor Power Input
72 67 62 72 67 62 72 67 62
SHC Sensible Heat Capacity (1000 Btuh) Gross
TC 125.5 116.2 106.9 130.5 121.7 113.0 133.4 125.1 117.7 TC Total Capacity (1000 Btuh) Gross
85 SHC 64.3 82.1 102.1 72.4 94.2 113.0 80.7 106.2 117.7
kW 9.47 9.10 8.73 9.67 9.32 8.97 9.79 9.45 9.16 NOTES:
1. For 380-v units, increase compressor power as follows:
TC 119.3 110.7 102.3 123.7 115.6 108.0 126.3 118.6 112.5 38AKS008 Increase by 3% 38AKS009, 012 Increase by 1%
95 SHC 61.8 79.7 98.2 69.7 91.4 108.0 78.3 103.5 112.5 2. SHC is based on 80 F edb temperature of air-entering evaporator coil.
kW 10.21 9.81 9.41 10.42 10.03 9.68 10.53 10.17 9.89 Below 80 F edb, subtract (corr factor x cfm) from SHC.
TC 116.8 107.7 98.9 121.4 112.8 104.9 124.0 115.8 109.8 Above 80 F edb, add (corr factor x cfm) to SHC.
100 SHC 60.8 78.4 95.4 68.8 90.1 104.9 77.5 102.4 109.8
kW 10.57 10.16 9.77 10.77 10.39 10.04 10.89 10.53 10.26 ENTERING-AIR DRY BULB TEMP (F)
TC 114.0 105.2 96.7 118.3 110.0 102.6 120.8 112.9 107.4 BYPASS 79 78 77 76 76 Under 75
105 SHC 59.6 77.4 93.6 67.7 88.9 102.6 76.4 101.2 107.4 FACTOR
kW 10.94 10.52 10.12 11.14 10.75 10.40 11.26 10.88 10.63 (BF) 81 82 83 84 85 Over 85
TC 107.5 99.2 91.5 111.2 103.5 97.1 106.0 101.8 Correction Factor
115 SHC 57.0 74.8 89.2 64.9 85.9 97.1 98.4 101.8 .05 1.04 2.07 3.11 4.14 5.18
kW 11.66 11.15 10.67 11.89 11.42 11.02 11.57 11.31 Use formula
.10 .98 1.96 2.94 3.94 4.91
shown
.20 .87 1.74 2.62 3.49 4.36
below.
.30 .76 1.53 2.29 3.05 3.82
Interpolation is permissible.
Correction Factor =1.10 x (1 BF) x (edb 80).

UNIT 38AKS013

NOTES:
38AKS013/40RM008 1. Direct interpolation is permissible. Do not extrapolate.
Evaporator Air Cfm/BF 2. Evaporator fan heat not deducted from ratings.
Temp (F) 3. Ratings based on approximately 12 F superheat leaving coil.
Air Entering 2250/0.06 3000/0.10 3750/0.12
4. Formulas:
Condenser Evaporator Air Ewb (F) sensible heat capacity (Btuh)
(Edb) Leaving db =entering db
72 67 62 72 67 62 72 67 62 1.1 x cfm
TC 114.2 104.9 120.2 111.5 100.6 124.0 115.5 104.9 Leaving wb =wet-bulb temperature corresponding to enthalpy of air leaving
85 SHC 56.3 68.6 63.1 78.5 100.6 69.0 87.2 104.9 coil (hlwb).
kW 8.51 8.20 8.71 8.42 8.05 8.83 8.55 8.20
total capacity (Btuh)
TC 109.5 100.7 91.6 114.7 106.7 96.9 118.2 110.5 101.0 hlwb =hewb
95 SHC 54.3 66.8 86.6 61.2 76.5 96.9 66.9 85.2 101.0 4.5 x cfm
kW 9.32 9.00 8.67 9.51 9.22 8.86 9.64 9.35 9.01 where hewb =enthalpy of air entering coil
TC 107.1 98.4 89.3 112.1 104.2 94.7 115.5 107.9 98.8 5. SHC is based on 80 F db temperature of air-entering evaporator coil.
100 SHC 53.3 65.8 84.7 60.4 75.4 94.7 66.0 84.1 98.8 Below 80 F db, subtract (corr factor x cfm) from SHC.
kW 9.67 9.36 9.03 9.86 9.57 9.22 9.98 9.70 9.37 Above 80 F db, add (corr factor x cfm) to SHC. See italic type below.
TC 104.4 96.3 87.8 109.0 101.6 92.9 112.1 105.0 96.8
105 SHC 52.2 64.9 83.4 59.3 74.3 92.9 64.8 83.0 96.8 ENTERING-AIR DRY BULB TEMP (F)
kW 9.97 9.56 9.14 10.20 9.83 9.39 10.35 10.00 9.59 BYPASS 79 78 77 76 75 Under 75
TC 99.4 91.4 83.1 103.6 96.4 88.2 106.5 99.7 92.1 FACTOR
115 SHC 50.2 62.7 79.4 57.5 72.1 88.2 62.9 80.9 92.1 (BF) 81 82 83 84 85 Over 85
kW 10.72 10.32 9.91 10.93 10.57 10.16 11.07 10.73 10.35 Correction Factor
.10 .98 1.96 2.94 3.94 4.91 Use formula
LEGEND .20 .87 1.74 2.62 3.49 4.36 shown
.30 .76 1.53 2.29 3.05 3.82 below.
Out of Range
BF Bypass Factor Interpolation is permissible.
Edb Entering Dry Bulb Correction Factor =1.1 x (1 BF) x (db 80).
Ewb Entering Wet Bulb
kW Compressor Motor Power Input at Rated Voltage
SHC Gross Sensible Heat Capacity (1000 Btuh)
TC Gross Total Capacity (1000 Btuh)

31
Performance data (cont)
COMBINATION RATINGS (cont)
UNIT 38AKS013 (cont)

38AKS013/40RM012 38AKS013/40RM014
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 3000/0.05 4000/0.07 5000/0.12 Air Entering 3750/0.06 5000/0.08 6250/0.10
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 127.4 117.6 107.7 132.8 123.4 114.1 136.0 127.1 119.0 TC 134.9 123.8 114.9 139.6 129.3 121.9 132.9 127.5
85 SHC 65.1 82.7 102.7 73.2 95.0 114.1 81.6 107.0 119.0 85 SHC 72.5 92.7 111.7 82.2 108.3 121.9 121.6 127.5
kW 8.95 8.62 8.29 9.13 8.81 8.50 9.23 8.94 8.67 kW 9.20 8.83 8.53 9.35 9.01 8.76 9.13 8.95
TC 121.5 112.3 103.2 126.3 117.6 109.3 120.8 114.1 TC 128.2 117.8 109.8 132.3 122.9 116.5 126.1 121.8
95 SHC 62.7 80.4 99.0 70.7 92.3 109.3 104.4 114.1 95 SHC 69.9 89.9 107.4 79.5 105.5 116.5 118.4 121.8
kW 9.75 9.42 9.09 9.93 9.61 9.31 9.73 9.48 kW 10.00 9.62 9.33 10.15 9.80 9.57 9.92 9.76
TC 118.8 109.7 100.7 123.5 114.8 106.8 118.0 111.7 TC 125.4 115.0 107.2 129.4 120.0 113.9 123.2 119.2
100 SHC 61.6 79.3 96.9 69.6 91.1 106.8 103.3 111.7 100 SHC 68.8 88.6 105.2 78.5 104.3 113.9 117.1 119.2
kW 10.10 9.77 9.44 10.27 9.96 9.66 10.07 9.84 kW 10.34 9.96 9.68 10.49 10.14 9.92 10.26 10.12
TC 115.2 106.7 98.4 119.4 111.4 104.1 114.2 108.8 TC 121.2 111.4 104.4 116.0 110.7 118.9 115.7
105 SHC 60.1 78.0 95.0 68.1 89.5 104.1 101.7 108.8 105 SHC 67.2 87.0 102.9 102.6 110.7 115.1 115.7
kW 10.51 10.08 9.67 10.72 10.32 9.96 10.46 10.19 kW 10.81 10.32 9.97 10.55 10.28 10.70 10.53
TC 109.7 101.3 93.3 105.7 99.0 108.3 103.7 TC 115.4 105.7 99.1 110.1 105.4 112.9 110.3
115 SHC 57.9 75.7 90.7 86.9 99.0 99.4 103.7 115 SHC 65.0 84.3 98.3 100.1 105.4 112.3 110.3
kW 11.24 10.81 10.41 11.04 10.70 11.17 10.94 kW 11.52 11.03 10.70 11.26 11.02 11.40 11.27

UNIT 38AKS014

38AKS014/40RM012 38AKS014/40RM016
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 3000/0.05 4000/0.07 5000/0.12 Air Entering 4500/0.03 6000/0.05 7500/0.08
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 145.6 134.4 122.6 152.8 141.8 129.6 157.1 146.6 134.6 TC 165.7 153.7 142.4 170.8 160.6 150.8 175.3 165.0 157.4
85 SHC 72.5 89.9 115.1 80.9 103.4 129.6 88.9 115.0 134.6 85 SHC 90.0 114.1 139.2 99.4 130.5 150.8 111.0 146.0 157.4
kW 10.02 9.70 9.36 10.22 9.91 9.56 10.34 10.05 9.70 kW 10.59 10.25 9.92 10.74 10.45 10.16 10.87 10.57 10.35
TC 139.5 128.4 116.9 146.3 135.5 123.9 150.3 140.0 129.1 TC 158.6 147.0 136.0 163.4 153.6 144.2 167.8 157.8 150.8
95 SHC 70.0 87.3 110.5 78.4 100.5 123.9 86.6 112.3 129.1 95 SHC 87.5 111.1 133.6 96.7 127.1 144.2 108.4 142.4 150.8
kW 10.93 10.61 10.28 11.12 10.81 10.48 11.24 10.94 10.63 kW 11.47 11.14 10.83 11.61 11.33 11.06 11.74 11.45 11.25
TC 136.7 126.3 115.4 143.1 132.8 122.1 146.8 137.1 127.1 TC 154.5 143.6 133.3 158.9 149.8 141.0 163.0 153.7 147.4
100 SHC 68.9 86.4 109.1 77.2 99.3 122.1 85.3 111.1 127.1 100 SHC 86.1 109.6 131.2 94.9 125.3 141.0 106.6 140.3 147.3
kW 11.38 11.05 10.72 11.57 11.26 10.93 11.69 11.39 11.08 kW 11.92 11.59 11.27 12.06 11.78 11.51 12.18 11.90 11.70
TC 133.6 123.2 112.5 139.7 129.6 119.2 143.4 133.7 124.2 TC 150.9 140.2 130.0 155.1 146.2 137.7 159.2 150.0 144.0
105 SHC 67.7 85.1 106.7 75.9 97.9 119.2 84.2 109.7 124.2 105 SHC 84.8 108.0 128.3 93.5 123.5 137.7 105.3 138.5 144.0
kW 11.79 11.39 10.98 12.03 11.64 11.24 12.17 11.80 11.43 kW 12.46 12.05 11.65 12.62 12.28 11.95 12.78 12.42 12.19
TC 128.0 117.6 107.2 133.7 123.8 113.9 137.1 127.6 119.1 TC 144.4 134.0 124.1 148.3 139.8 131.6 152.3 143.4 137.9
115 SHC 65.3 82.7 102.4 73.6 95.2 113.9 82.0 107.2 119.1 115 SHC 82.5 105.3 123.1 91.0 120.4 131.6 102.8 135.2 137.9
kW 12.72 12.32 11.92 12.94 12.56 12.18 13.07 12.71 12.38 kW 13.35 12.95 12.57 13.50 13.18 12.86 13.66 13.31 13.10

NOTES:
38AKS014/40RM014 1. Direct interpolation is permissible. Do not extrapolate.
Evaporator Air Cfm/BF 2. Evaporator fan heat not deducted from ratings.
Temp (F) 3. Ratings based on approximately 12 F superheat leaving coil.
Air Entering 3750/0.06 5000/0.08 6250/0.10
4. Formulas:
Condenser Evaporator Air Ewb (F) sensible heat capacity (Btuh)
(Edb) Leaving db =entering db
72 67 62 72 67 62 72 67 62 1.1 x cfm
TC 155.0 142.8 131.1 161.2 149.4 138.9 165.4 153.8 145.0 Leaving wb =wet-bulb temperature corresponding to enthalpy of air leaving
85 SHC 80.2 101.4 125.5 90.1 116.9 138.9 99.8 131.4 145.0 coil (hlwb).
kW 10.29 9.94 9.60 10.46 10.12 9.82 10.58 10.25 10.00
total capacity (Btuh)
TC 148.5 136.3 125.2 154.4 142.7 133.0 158.5 147.0 139.1 hlwb =hewb
95 SHC 77.7 98.4 120.5 87.6 114.0 133.0 97.4 128.2 139.1 4.5 x cfm
kW 11.19 10.84 10.52 11.35 11.02 10.74 11.47 11.14 10.92 where hewb =enthalpy of air entering coil
TC 145.2 133.5 123.2 150.7 139.6 130.6 154.4 143.6 136.5 5. SHC is based on 80 F db temperature of air-entering evaporator coil.
100 SHC 76.5 97.2 118.8 86.2 112.7 130.6 96.0 126.6 136.5 Below 80 F db, subtract (corr factor x cfm) from SHC.
kW 11.64 11.28 10.96 11.80 11.46 11.19 11.92 11.59 11.37 Above 80 F db, add (corr factor x cfm) to SHC. See italic type below.
TC 141.9 130.2 120.2 147.2 136.2 127.6 150.9 140.1 133.5
105 SHC 75.2 95.6 116.3 85.0 111.2 127.6 94.8 125.6 133.5 ENTERING-AIR DRY BULB TEMP (F)
kW 12.11 11.66 11.28 12.31 11.89 11.56 12.46 12.04 11.79 BYPASS 79 78 77 76 75 Under 75
TC 135.9 124.2 114.8 140.9 130.0 122.2 144.5 133.9 128.0 FACTOR
115 SHC 72.9 92.9 111.6 82.7 108.6 122.2 92.6 122.1 128.0 (BF) 81 82 83 84 85 Over 85
kW 13.03 12.58 12.21 13.22 12.80 12.50 13.36 12.95 12.72 Correction Factor
.10 .98 1.96 2.94 3.94 4.91 Use formula
LEGEND .20 .87 1.74 2.62 3.49 4.36 shown
.30 .76 1.53 2.29 3.05 3.82 below.
Out of Range
BF Bypass Factor Interpolation is permissible.
Edb Entering Dry Bulb Correction Factor =1.1 x (1 BF) x (db 80).
Ewb Entering Wet Bulb
kW Compressor Motor Power Input at Rated Voltage
SHC Gross Sensible Heat Capacity (1000 Btuh)
TC Gross Total Capacity (1000 Btuh)

32
COMBINATION RATINGS (cont)
UNIT 38AKS016

38AKS016/40RM014 38AKS016/40RM024
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 3750/0.06 5000/0.08 6250/0.10 Air Entering 6000/0.03 8000/0.06 10,000/0.07
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 181.7 167.9 190.3 176.1 160.9 195.7 181.8 167.7 TC 214.1 198.7 185.1 221.3 206.0 195.8 224.4 212.1 204.4
85 SHC 90.5 113.0 100.8 128.3 160.8 110.2 144.5 167.7 85 SHC 115.8 151.5 181.2 131.8 175.4 195.8 145.7 196.7 204.4
kW 14.85 14.20 15.25 14.59 13.87 15.51 14.86 14.19 kW 16.37 15.65 15.01 16.71 15.99 15.51 16.86 16.28 15.92
TC 175.1 161.7 183.0 169.5 155.6 188.0 174.9 162.2 TC 205.0 190.4 177.9 211.6 197.1 188.2 214.2 202.8 196.4
95 SHC 88.0 110.2 98.1 125.5 155.6 107.6 141.2 162.2 95 SHC 112.3 148.1 175.0 128.3 171.6 188.2 142.1 192.5 196.4
kW 16.06 15.39 16.45 15.77 15.08 16.70 16.04 15.41 kW 17.55 16.82 16.20 17.88 17.15 16.71 18.01 17.44 17.12
TC 171.4 158.0 143.9 179.0 165.7 152.3 184.0 171.0 158.9 TC 200.6 186.2 174.0 207.1 192.6 184.2 209.6 198.4 192.5
100 SHC 86.5 108.5 136.4 96.6 123.9 152.3 106.2 139.4 158.9 100 SHC 110.7 146.4 171.5 126.7 169.8 184.2 140.5 190.4 192.5
kW 16.68 15.93 15.13 17.11 16.36 15.60 17.39 16.65 15.97 kW 18.32 17.51 16.82 18.69 17.87 17.40 18.83 18.20 17.86
TC 168.2 155.3 142.0 175.3 162.6 150.0 180.0 167.6 156.4 TC 195.5 181.8 170.4 201.6 187.8 180.3 203.7 193.3 188.2
105 SHC 85.3 107.2 134.8 95.3 122.5 150.0 104.8 137.8 156.4 105 SHC 108.7 144.6 168.4 124.7 167.7 180.3 138.4 188.1 188.2
kW 17.29 16.52 15.72 17.72 16.96 16.20 18.00 17.25 16.58 kW 18.93 18.11 17.43 19.29 18.47 18.02 19.42 18.80 18.49
TC 160.9 148.6 136.4 167.4 155.4 144.2 171.7 160.0 150.3 TC 185.7 172.9 162.6 191.2 178.3 172.0 192.9 183.4 179.5
115 SHC 82.5 104.1 130.0 92.4 119.4 144.2 102.0 134.2 150.3 115 SHC 105.0 140.9 161.6 120.9 163.7 172.0 134.6 183.6 179.5
kW 18.54 17.75 16.97 18.96 18.19 17.47 19.24 18.48 17.86 kW 20.14 19.31 18.65 20.49 19.66 19.26 20.60 19.99 19.74

38AKS016/40RM016
Evaporator Air Cfm/BF
Temp (F)
Air Entering 4500/0.03 6000/0.05 7500/0.08
Condenser Evaporator Air Ewb (F)
(Edb)
72 67 62 72 67 62 72 67 62
TC 196.7 181.4 167.0 204.2 190.6 177.3 209.9 196.4 184.8
85 SHC 100.9 126.5 160.9 111.9 145.0 177.3 123.4 161.7 184.8
kW 15.55 14.84 14.16 15.91 15.27 14.64 16.18 15.54 15.00
TC 188.8 174.5 161.0 195.6 183.0 170.7 200.9 188.4 178.0
95 SHC 98.2 123.4 155.6 108.7 141.4 170.7 120.2 157.7 178.0
kW 16.74 16.03 15.35 17.08 16.45 15.84 17.35 16.72 16.20
TC 184.7 170.6 157.4 191.3 179.0 167.0 196.6 184.3 174.2
100 SHC 96.7 121.7 152.4 107.1 139.4 167.0 118.6 155.6 174.2
kW 17.43 16.64 15.89 17.80 17.11 16.43 18.09 17.40 16.84
TC 180.6 167.3 154.8 186.7 175.2 163.9 191.7 180.1 170.8
105 SHC 95.3 120.2 150.1 105.4 137.6 163.9 116.9 153.6 170.8
kW 18.04 17.24 16.49 18.40 17.71 17.03 18.70 18.01 17.45
TC 172.1 159.8 148.1 177.5 167.0 156.7 182.1 171.5 163.3
115 SHC 92.3 116.8 144.3 101.9 133.6 156.7 113.5 149.2 163.3
kW 19.26 18.47 17.72 19.61 18.93 18.27 19.91 19.22 18.70

UNIT 38AKS024

NOTES:
38AKS024/40RM016 1. Direct interpolation is permissible. Do not extrapolate.
Evaporator Air Cfm/BF 2. Evaporator fan heat not deducted from ratings.
Temp (F) 3. Ratings based on approximately 12 F superheat leaving coil.
Air Entering 4500/0.03 6000/0.05 7500/0.08
4. Formulas:
Condenser Evaporator Air Ewb (F) sensible heat capacity (Btuh)
(Edb) Leaving db =entering db
72 67 62 72 67 62 72 67 62 1.1 x cfm
TC 232.1 211.5 243.6 224.3 205.7 251.3 232.6 214.6 Leaving wb =wet-bulb temperature corresponding to enthalpy of air leaving
85 SHC 113.4 140.0 126.7 161.4 205.7 138.2 179.8 214.6 coil (hlwb).
kW 19.33 18.26 19.93 18.93 17.95 20.33 19.36 18.42
total capacity (Btuh)
TC 221.4 201.5 232.1 213.7 196.0 239.6 221.7 204.9 hlwb =hewb
95 SHC 109.7 135.5 122.4 156.3 196.0 134.0 174.3 204.9 4.5 x cfm
kW 20.79 19.67 21.40 20.36 19.36 21.83 20.81 19.86 where hewb =enthalpy of air entering coil
TC 216.6 197.5 179.9 226.8 209.2 192.2 234.0 216.8 201.0 5. SHC is based on 80 F db temperature of air-entering evaporator coil.
100 SHC 108.0 133.7 172.2 120.4 154.1 192.2 132.0 171.9 201.0 Below 80 F db, subtract (corr factor x cfm) from SHC.
kW 21.48 20.35 19.31 22.08 21.04 20.04 22.50 21.49 20.55 Above 80 F db, add (corr factor x cfm) to SHC. See italic type below.
TC 211.1 192.4 175.1 221.0 203.8 187.3 228.1 211.2 196.0
105 SHC 106.0 131.4 168.0 118.2 151.5 187.3 129.9 169.1 196.0 ENTERING-AIR DRY BULB TEMP (F)
kW 22.10 20.91 19.81 22.73 21.63 20.58 23.18 22.10 21.14 BYPASS 79 78 77 76 75 Under 75
TC 200.5 182.9 166.7 209.4 193.5 178.3 216.1 200.4 186.8 FACTOR
115 SHC 102.3 127.2 160.6 113.9 146.5 178.3 125.6 163.7 186.8 (BF) 81 82 83 84 85 Over 85
kW 23.38 22.12 20.96 24.02 22.88 21.79 24.49 23.37 22.40 Correction Factor
.10 .98 1.96 2.94 3.94 4.91 Use formula
LEGEND .20 .87 1.74 2.62 3.49 4.36 shown
.30 .76 1.53 2.29 3.05 3.82 below.
Out of Range
BF Bypass Factor Interpolation is permissible.
Edb Entering Dry Bulb Correction Factor =1.1 x (1 BF) x (db 80).
Ewb Entering Wet Bulb
kW Compressor Motor Power Input at Rated Voltage
SHC Gross Sensible Heat Capacity (1000 Btuh)
TC Gross Total Capacity (1000 Btuh)

33
Performance data (cont)
COMBINATION RATINGS (cont)
UNIT 38AKS024 (cont)

38AKS024/40RM024 38AKS024/40RM028
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 6000/0.03 8000/0.06 10,000/0.07 Air Entering 7500/0.04 10,000/0.06 12,500/0.08
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 256.4 236.5 216.9 267.0 247.5 229.7 272.9 255.3 240.0 TC 275.0 253.1 235.5 284.8 262.9 249.6 289.9 271.6 261.5
85 SHC 131.9 167.0 208.9 148.3 192.9 229.7 162.8 216.4 240.0 85 SHC 148.4 191.3 231.9 168.6 222.7 249.6 188.3 250.8 261.5
kW 20.60 19.56 18.54 21.15 20.13 19.21 21.46 20.54 19.75 kW 21.57 20.43 19.51 22.08 20.94 20.25 22.35 21.39 20.87
TC 224.8 225.2 206.5 255.0 235.6 219.4 260.3 243.3 229.7 TC 262.7 240.6 224.5 272.2 250.1 238.8 276.9 258.9 250.7
95 SHC 127.5 162.4 199.9 144.0 187.9 219.4 158.3 211.0 229.7 95 SHC 143.9 186.3 221.9 164.2 217.4 238.8 184.0 245.3 250.6
kW 22.12 21.01 19.96 22.69 21.60 20.68 22.99 22.04 21.27 kW 23.13 21.88 20.97 23.67 22.42 21.78 23.93 22.91 22.45
TC 234.0 220.1 202.3 248.6 229.9 214.8 253.5 237.4 224.9 TC 256.1 234.5 219.6 265.0 243.6 233.5 269.4 252.1 245.1
100 SHC 125.3 160.3 196.2 141.7 185.5 214.8 156.0 208.2 224.9 100 SHC 141.5 183.8 217.3 161.7 214.7 233.5 181.5 242.4 245.1
kW 22.80 21.68 20.63 23.37 22.26 21.37 23.66 22.70 21.97 kW 23.81 22.53 21.65 24.34 23.07 22.47 24.60 23.57 23.16
TC 233.1 214.3 197.1 242.5 223.9 209.6 247.1 231.3 219.6 TC 249.9 228.2 214.0 258.6 237.1 228.0 262.8 245.7 239.5
105 SHC 123.0 157.9 191.6 139.5 182.9 209.6 153.7 205.5 219.6 105 SHC 139.2 181.2 212.2 159.4 212.1 228.0 179.3 239.5 239.5
kW 23.50 22.30 21.20 24.09 22.91 22.00 24.39 23.38 22.64 kW 24.56 23.18 22.28 25.12 23.75 23.17 25.39 24.30 23.91
TC 221.0 203.1 187.2 229.7 211.8 199.4 233.6 218.9 209.2 TC 236.6 215.4 203.1 244.7 223.8 216.8 248.4 232.1 228.0
115 SHC 118.4 153.3 183.1 134.8 177.8 199.4 149.0 199.8 209.2 115 SHC 134.3 176.1 202.2 154.6 206.6 216.8 174.5 233.6 228.0
kW 24.84 23.56 22.43 25.46 24.18 23.30 25.74 24.69 24.00 kW 25.96 24.44 23.56 26.54 25.04 24.54 26.80 25.64 25.34

UNIT 38AKS028

38AKS028/40RM024 38AKS028/40RM034
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 6000/0.03 8000/0.05 10,000/0.07 Air Entering 9000/0.04 12,000/0.06 15,000/0.08
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 305.1 279.8 320.3 295.8 330.3 305.7 279.5 TC 353.9 325.8 300.2 367.2 339.2 318.4 374.7 350.2 378.8
85 SHC 150.5 184.8 167.6 213.3 183.0 239.4 279.5 85 SHC 186.0 238.4 293.9 212.4 276.3 318.4 234.9 311.5 272.3
kW 25.59 24.45 26.28 25.17 26.73 25.62 24.44 kW 27.80 26.53 25.37 28.40 27.13 26.19 28.74 27.63 28.92
TC 292.8 268.8 306.8 283.5 257.9 315.7 292.9 269.6 TC 337.9 310.6 288.0 350.0 323.1 305.6 356.7 333.7 327.6
95 SHC 145.8 180.3 162.7 208.1 257.9 177.8 233.6 269.6 95 SHC 179.9 232.4 282.8 206.6 269.8 305.6 228.9 304.2 309.3
kW 27.58 26.34 28.30 27.09 25.77 28.76 27.58 26.38 kW 29.91 28.50 27.33 30.53 29.14 28.24 30.88 29.69 29.37
TC 286.3 262.5 237.6 300.0 276.8 252.2 308.6 286.1 263.9 TC 330.6 303.1 281.4 342.4 315.4 299.1 348.8 326.0 305.6
100 SHC 143.3 177.7 227.0 160.3 205.3 252.2 175.3 230.5 263.9 100 SHC 177.2 229.4 276.8 204.0 266.7 299.1 226.3 300.9 325.3
kW 28.50 27.18 25.81 29.25 27.97 26.61 29.72 28.49 27.26 kW 30.94 29.42 28.23 31.59 30.10 29.20 31.94 30.69 29.56
TC 279.8 256.7 232.8 292.9 270.3 247.1 300.9 279.4 258.6 TC 322.2 295.2 274.9 333.4 307.1 292.3 339.4 317.4 283.3
105 SHC 140.8 175.3 222.8 157.7 202.5 247.1 172.6 227.4 258.6 105 SHC 174.0 226.2 270.9 210.0 263.4 292.3 223.1 297.1 341.4
kW 29.35 27.86 26.33 30.19 28.74 27.25 30.71 29.32 27.99 kW 32.08 30.34 29.04 32.80 31.10 30.15 33.19 31.77 29.57
TC 266.8 245.0 223.2 278.7 257.4 236.9 285.7 265.9 248.0 TC 305.6 279.5 262.0 315.7 290.5 278.7 300.4 244.7
115 SHC 135.9 170.5 214.4 152.6 197.1 236.9 167.3 221.3 248.0 115 SHC 167.7 220.0 259.2 195.0 256.7 278.7 289.6 369.4
kW 31.21 29.70 28.19 32.03 30.56 29.14 32.52 31.15 29.91 kW 33.90 32.09 30.88 34.59 32.85 32.04 33.54 29.68

NOTES:
38AKS028/40RM028 1. Direct interpolation is permissible. Do not extrapolate.
Evaporator Air Cfm/BF 2. Evaporator fan heat not deducted from ratings.
Temp (F) 3. Ratings based on approximately 12 F superheat leaving coil.
Air Entering 7500/0.04 10,000/0.06 12,500/0.08
4. Formulas:
Condenser Evaporator Air Ewb (F) sensible heat capacity (Btuh)
(Edb) Leaving db =entering db
72 67 62 72 67 62 72 67 62 1.1 x cfm
TC 330.8 305.4 277.1 344.8 318.8 293.3 353.4 329.1 307.4 Leaving wb =wet-bulb temperature corresponding to enthalpy of air leaving
85 SHC 168.9 212.4 270.1 189.8 245.6 293.3 209.5 275.9 307.3 coil (hlwb).
kW 26.75 25.61 24.33 27.39 26.21 25.06 27.77 26.67 25.69
total capacity (Btuh)
TC 316.6 292.0 266.5 329.6 304.5 282.3 337.3 314.4 295.9 hlwb =hewb
95 SHC 163.7 207.0 260.4 184.4 239.8 282.3 204.1 269.5 295.9 4.5 x cfm
kW 28.81 27.54 26.22 29.48 28.18 27.03 29.88 28.69 27.73 where hewb =enthalpy of air entering coil
TC 309.7 285.0 260.4 322.5 297.3 276.3 329.8 307.2 289.9 5. SHC is based on 80 F db temperature of air-entering evaporator coil.
100 SHC 161.2 204.2 254.8 181.9 236.8 276.3 201.6 266.4 289.9 Below 80 F db, subtract (corr factor x cfm) from SHC.
kW 29.79 28.42 27.07 30.49 29.10 27.94 30.90 29.65 28.69 Above 80 F db, add (corr factor x cfm) to SHC. See italic type below.
TC 302.3 277.9 254.8 314.5 289.8 270.4 321.4 299.5 283.8
105 SHC 158.4 201.3 249.7 179.1 233.7 270.4 198.8 263.0 283.7 ENTERING-AIR DRY BULB TEMP (F)
kW 30.80 29.23 27.75 31.58 29.99 28.75 32.03 30.62 29.61 BYPASS 79 78 77 76 75 Under 75
TC 287.5 264.0 243.6 298.6 274.9 258.7 304.6 284.3 271.5 FACTOR
115 SHC 153.0 195.7 239.4 173.5 227.6 258.7 193.2 256.4 271.5 (BF) 81 82 83 84 85 Over 85
kW 32.64 31.01 29.60 33.41 31.77 30.65 33.83 32.42 31.53 Correction Factor
.10 .98 1.96 2.94 3.94 4.91 Use formula
LEGEND .20 .87 1.74 2.62 3.49 4.36 shown
.30 .76 1.53 2.29 3.05 3.82 below.
Out of Range
BF Bypass Factor Interpolation is permissible.
Edb Entering Dry Bulb Correction Factor =1.1 x (1 BF) x (db 80).
Ewb Entering Wet Bulb
kW Compressor Motor Power Input at Rated Voltage
SHC Gross Sensible Heat Capacity (1000 Btuh)
TC Gross Total Capacity (1000 Btuh)

34
COMBINATION RATINGS (cont)
UNIT 38AKS034

38AKS034/40RM028 38AKS034/40RM034
Evaporator Air Cfm/BF Evaporator Air Cfm/BF
Temp (F) Temp (F)
Air Entering 7500/0.04 10,000/0.06 12,500/0.08 Air Entering 9000/0.04 12,000/0.06 15,000/0.08
Condenser Evaporator Air Ewb (F) Condenser Evaporator Air Ewb (F)
(Edb) (Edb)
72 67 62 72 67 62 72 67 62 72 67 62 72 67 62 72 67 62
TC 352.5 326.2 368.2 341.0 310.1 378.3 351.7 324.8 TC 378.5 349.4 319.1 393.6 364.1 338.1 402.6 375.7 354.0
85 SHC 176.9 220.8 198.0 254.7 310.1 217.8 285.8 324.8 85 SHC 195.3 247.7 311.0 221.4 286.4 338.1 244.2 322.7 354.0
kW 29.31 28.15 30.01 28.81 27.44 30.45 29.28 28.09 kW 30.46 29.18 27.84 31.13 29.83 28.68 31.52 30.34 29.38
TC 339.4 313.7 283.7 354.1 327.7 300.1 363.2 338.1 314.4 TC 363.6 335.2 307.9 377.5 349.0 326.3 385.6 360.2 341.7
95 SHC 172.1 215.8 276.1 193.0 249.3 300.1 212.7 279.9 314.4 95 SHC 189.7 242.1 300.8 215.9 280.3 326.3 238.5 315.9 341.7
kW 31.43 30.06 28.47 32.21 30.80 29.34 32.69 31.36 30.10 kW 32.71 31.20 29.75 33.45 31.94 30.73 33.88 32.53 31.55
TC 332.6 307.3 278.7 346.8 320.8 294.9 355.4 331.0 308.9 TC 355.9 327.8 302.0 369.2 341.3 320.2 376.8 352.2 335.3
100 SHC 169.6 213.2 271.5 190.4 246.4 294.9 210.1 276.8 308.9 100 SHC 186.7 239.2 295.5 213.1 277.1 320.2 235.6 312.4 335.3
kW 32.48 31.01 29.35 33.30 31.80 30.29 33.81 32.39 31.11 kW 33.83 32.21 30.71 34.61 32.99 31.76 35.05 33.62 32.64
TC 325.3 299.8 272.2 339.1 313.1 288.5 347.5 323.3 302.6 TC 348.1 319.8 295.0 361.1 333.1 313.3 368.4 344.1 328.4
105 SHC 166.9 210.2 265.6 187.8 243.3 288.5 207.5 273.4 302.6 105 SHC 183.8 236.0 289.2 210.4 273.8 313.3 232.8 308.8 328.4
kW 33.49 31.93 30.24 34.34 32.74 31.24 34.85 33.37 32.10 kW 34.89 33.16 31.64 35.69 33.97 32.75 36.14 34.64 33.70
TC 311.0 286.2 261.5 323.8 298.6 277.4 331.2 308.5 291.0 TC 331.9 304.5 282.6 343.8 316.8 300.3 350.2 327.4 314.8
115 SHC 161.6 204.7 255.8 182.4 237.3 277.4 202.1 267.0 290.9 115 SHC 177.7 229.9 277.9 204.5 267.3 300.3 226.7 301.5 314.8
kW 35.38 33.58 31.79 36.30 34.48 32.94 36.84 35.20 33.92 kW 36.89 34.90 33.32 37.75 35.80 34.60 38.22 36.57 35.65

UNIT 38AKS044

NOTES:
38AKS044/40RM034 1. Direct interpolation is permissible. Do not extrapolate.
Evaporator Air Cfm/BF 2. Evaporator fan heat not deducted from ratings.
Temp (F) 3. Ratings based on approximately 12 F superheat leaving coil.
Air Entering 9000/0.04 12,000/0.06 15,000/0.08
4. Formulas:
Condenser Evaporator Air Ewb (F) sensible heat capacity (Btuh)
(Edb) Leaving db =entering db
72 67 62 72 67 62 72 67 62 1.1 x cfm
TC 455.4 423.2 477.5 442.9 491.9 456.4 Leaving wb =wet-bulb temperature corresponding to enthalpy of air leaving
85 SHC 224.5 277.0 249.8 318.1 274.0 358.1 coil (hlwb).
kW 38.70 37.29 39.66 38.15 40.28 38.74
total capacity (Btuh)
TC 439.8 407.8 460.5 426.6 473.8 439.8 403.1 hlwb =hewb
95 SHC 218.6 270.9 244.0 311.5 267.9 350.9 403.1 4.5 x cfm
kW 41.29 39.62 42.38 40.60 43.07 41.29 39.37 where hewb =enthalpy of air entering coil
TC 432.2 400.8 452.0 419.0 379.6 464.6 431.9 397.4 5. SHC is based on 80 F db temperature of air-entering evaporator coil.
100 SHC 215.7 268.2 241.2 308.5 379.6 264.9 347.4 397.4 Below 80 F db, subtract (corr factor x cfm) from SHC.
kW 42.65 40.86 43.79 41.90 39.65 44.51 42.63 40.67 Above 80 F db, add (corr factor x cfm) to SHC. See italic type below.
TC 424.2 393.0 443.4 410.7 373.4 455.4 423.4 390.9
105 SHC 212.7 265.1 238.2 305.1 373.3 261.8 343.7 390.9 ENTERING-AIR DRY BULB TEMP (F)
kW 43.84 41.86 45.06 42.98 40.62 45.82 43.79 41.73 BYPASS 79 78 77 76 75 Under 75
TC 407.7 376.9 340.2 425.6 393.7 360.3 436.6 406.1 377.5 FACTOR
115 SHC 206.4 258.7 330.1 232.2 298.3 360.3 255.5 336.1 377.5 (BF) 81 82 83 84 85 Over 85
kW 46.40 44.18 41.55 47.68 45.39 42.99 48.47 46.28 44.22 Correction Factor
.10 .98 1.96 2.94 3.94 4.91 Use formula
LEGEND .20 .87 1.74 2.62 3.49 4.36 shown
Out of Range .30 .76 1.53 2.29 3.05 3.82 below.
BF Bypass Factor
Edb Entering Dry Bulb Interpolation is permissible.
Ewb Entering Wet Bulb Correction Factor =1.1 x (1 BF) x (db 80).
kW Compressor Motor Power Input at Rated Voltage
SHC Gross Sensible Heat Capacity (1000 Btuh)
TC Gross Total Capacity (1000 Btuh)

40RM FAN PERFORMANCE DATA 0.0-1.2 ESP

EXTERNAL STATIC PRESSURE (in. wg)


UNIT AIRFLOW
40RM (Cfm) 0.0 0.2 0.4 0.6 0.8 1.0 1.2
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1,800 320 0.22 442 0.32 534 0.42 611 0.52 678 0.61 739 0.70 795 0.80
2,100 373 0.31 483 0.42 569 0.53 642 0.63 708 0.73 767 0.82 821 0.92
007 2,400 427 0.42 526 0.53 606 0.64 676 0.75 739 0.86 796 0.96 849 1.06
2,700 480 0.54 570 0.67 646 0.78 712 0.89 773 1.00 828 1.11 880 1.21
3,000 533 0.69 616 0.82 687 0.94 750 1.05 808 1.16 862 1.28 912 1.39
2,250 359 0.32 472 0.44 560 0.55 634 0.65 700 0.75 759 0.86 814 0.96
2,600 415 0.45 516 0.57 599 0.68 669 0.79 732 0.90 790 1.01 843 1.11
008 3,000 478 0.62 569 0.75 645 0.86 712 0.98 773 1.09 828 1.20 879 1.32
3,400 542 0.82 624 0.95 695 1.08 758 1.20 815 1.31 869 1.43 918 1.55
3,750 598 1.03 673 1.17 740 1.29 800 1.42 855 1.60 906 1.66 954 1.78

35
Performance data (cont)
40RM FAN PERFORMANCE DATA 0.0-1.2 ESP (cont)

EXTERNAL STATIC PRESSURE (in. wg)


UNIT AIRFLOW 0.0 0.2 0.4 0.6 0.8 1.0 1.2
40RM (Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
3,000 444 0.58 541 0.71 621 0.83 691 0.94 753 1.05 809 1.17 862 1.28
3,500 518 0.82 604 0.95 677 1.08 742 1.20 801 1.32 855 1.44 906 1.56
012 4,000 592 1.11 669 1.25 736 1.38 797 1.51 853 1.63 904 1.75 953 1.88
4,500 666 1.44 735 1.59 797 1.72 854 1.86 907 1.99 956 2.12 1003 2.24
5,000 740 1.83 803 1.98 861 2.12 914 2.26 964 2.39 1010 2.53 1055 2.66
3,750 363 0.37 475 0.58 566 0.80 645 1.02 715 1.24 779 1.47 839 1.69
4,300 416 0.53 517 0.78 601 1.02 676 1.26 743 1.50 805 1.74 862 1.99
014 5,000 484 0.81 573 1.08 650 1.35 719 1.62 782 1.89 841 2.16 896 2.44
5,700 552 1.17 631 1.47 702 1.76 766 2.06 826 2.36 881 2.66 934 2.96
6,250 605 1.51 678 1.83 744 2.15 805 2.47 862 2.79 915 3.11 966 3.43
4,500 391 0.51 495 0.75 581 1.00 657 1.25 725 1.50 787 1.76 845 2.02
5,300 460 0.80 551 1.08 629 1.35 700 1.63 764 1.91 823 2.20 878 2.48
016 6,000 521 1.13 602 1.43 675 1.73 741 2.04 801 2.34 858 2.65 911 2.96
6,800 590 1.60 663 1.93 730 2.26 791 2.59 847 2.92 901 3.26 951 3.60
7,500 651 2.10 718 2.45 779 2.81 837 3.16 890 3.52 941 3.88 990 4.24
6,000 503 1.07 587 1.37 661 1.67 727 1.97 789 2.28 846 2.59 900 2.90
7,000 586 1.64 660 1.98 726 2.31 787 2.65 844 2.99 898 3.33 948 3.67
024 8,000 670 2.37 735 2.74 795 3.12 851 3.49 904 3.86 954 4.23 1001 4.61
9,000 754 3.28 812 3.69 867 4.09 918 4.50 967 4.90 1014 5.31 1059 5.72
10,000 838 4.39 891 4.83 941 5.27 988 5.70 1034 6.14 1077 6.85 1120 7.02
7,500 412 1.15 492 1.53 568 2.00 640 2.56 710 3.22 776 3.98 840 4.83
8,750 481 1.76 550 2.17 616 2.66 680 3.22 742 3.86 802 4.58 860 5.38
028 10,000 549 2.55 610 2.99 669 3.50 726 4.07 782 4.70 836 5.40 889 6.17
11,250 618 3.52 672 4.00 725 4.53 777 5.12 827 5.76 876 6.45 925 7.21
12,500 687 4.71 735 5.22 783 5.78 830 6.38 876 7.04 922 7.74 966 8.49
9,000 471 1.78 539 2.17 604 2.63 667 3.17 728 3.78 788 4.46 845 5.22
10,500 550 2.72 608 3.15 665 3.64 720 4.18 774 4.79 827 5.45 878 6.18
034 12,000 628 3.93 679 4.40 730 4.92 779 5.48 827 6.09 874 6.76 921 7.47
13,500 707 5.44 752 5.94 797 6.49 841 7.08 885 7.71 928 8.38 970 9.10
15,000 785 7.27 826 7.81 867 8.39 907 9.01 947 9.66 986 10.35 1024 11.07

LEGEND FACTORY-SUPPLIED FILTER PRESSURE DROP


Bhp Brake Horsepower Input to Fan (in. wg)
ESP External Static Pressure
UNIT AIRFLOW PRESSURE DROP
Bold indicates field-supplied drive required. 40RM (Cfm) (in. wg)
Plain type indicates standard drive and standard motor. 1,800 0.05
Underline indicates a different motor and drive combination other 007 2,400 0.08
than the standard motor and standard drive combination is required. 3,000 0.11
Refer to fan motor and drive tables, pages 61-64, to complete the 2,250 0.07
selection. 008 3,000 0.11
3,750 0.15
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and 3,000 0.11
034; 1200 rpm for all other sizes. 012 4,000 0.17
2. Fan performance is based on deductions for wet coil, clean 2-in. 5,000 0.23
filters, and unit casing. See right for factory-supplied filter pressure 3,750 0.06
drop. 014 5,000 0.10
3. The medium-static drive and standard motor combination is not avail- 6,250 0.13
able for the 028 size. Use the alternate motor if the medium-static 4,500 0.08
drive is required for the 028 size. 016 6,000 0.12
4. Alternate motor not available for 034 size units. 7,500 0.17
6,000 0.12
024 8,000 0.19
10,000 0.26
7,500 0.15
028 10,000 0.22
12,500 0.30
9,000 0.19
034 12,000 0.29
15,000 0.40

36
40RM FAN PERFORMANCE DATA 1.4-2.4 ESP

EXTERNAL STATIC PRESSURE (in. wg)


UNIT AIRFLOW 1.4 1.6 1.8 2.0 2.2 2.4
40RM (Cfm)
Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp
1,800 847 0.89 896 0.98 942 1.07 986 1.16 1027 1.25
2,100 872 1.02 920 1.11 965 1.21 1008 1.30 1050 1.40
007 2,400 899 1.16 946 1.26 990 1.36 1033 1.46 1073 1.55
2,700 928 1.32 974 1.42 1018 1.52 1059 1.63 1099 1.73
3,000 959 1.49 1004 1.60 1046 1.71 1087 1.81 1126 1.92
2,250 865 1.06 913 1.16 958 1.27 1001 1.37 1042 1.47
2,600 893 1.22 940 1.33 984 1.43 1027 1.54 1067 1.65
008 3,000 928 1.43 973 1.54 1017 1.65 1058 1.76 1098 1.87
3,400 965 1.66 1010 1.78 1052 1.89 1092 2.00 1131 2.12
3,750 1000 1.90 1043 2.02 1084 2.13 1124 2.25 1162 2.37
3,000 911 1.39 958 1.50 1002 1.61 1044 1.72 1084 1.83 1123 1.94
3,500 953 1.67 998 1.79 1041 1.90 1082 2.02 1122 2.13 1159 2.25
012 4,000 999 2.00 1042 2.12 1084 2.24 1124 2.36 1162 2.48 1199 2.60
4,500 1047 2.37 1089 2.50 1129 2.62 1168 2.74
5,000 1097 2.79 1138 2.92 1177 3.05
3,750 894 1.91 947 2.14 996 2.37 1044 2.60 1089 2.83
4,300 916 2.23 967 2.48 1016 2.73 1062 2.98 1107 3.24
014 5,000 948 2.71 997 2.98 1044 3.26 1089 3.53 1133 3.81
5,700 984 3.25 1031 3.55 1076 3.86 1120 4.16 1162 4.46
6,250 1014 3.75 1060 4.07 1104 4.39 1147 4.71 1188 5.03
4,500 899 2.29 951 2.56 999 2.84 1046 3.12 1091 3.41 1133 3.70
5,300 930 2.78 980 3.08 1027 3.38 1072 3.68 1116 3.99 1157 4.30
016 6,000 961 3.28 1009 3.60 1055 3.92 1098 4.24 1141 4.57 1181 4.91
6,800 999 3.94 1045 4.28 1089 4.63 1132 4.98 1173 5.33
7,500 1036 4.60 1080 4.97 1123 5.34 1164 5.71
6,000 950 3.21 999 3.53 1045 3.85 1089 4.17 1131 4.50 1172 4.83
7,000 996 4.02 1042 4.37 1086 4.72 1129 5.07 1169 5.43
024 8,000 1047 4.99 1091 5.37 1133 5.75 1173 6.13
9,000 1102 6.13 1143 6.54 1183 6.96
10,000 1160 7.46 1200 7.91
7,500 903 5.79 963 6.83 1021 7.98 1078 9.21
8,750 917 6.26 972 7.22 1025 8.26 1078 9.38
028 10,000 941 7.01 991 7.91 1040 8.89 1089 9.93
11,250 972 8.02 1019 8.89 1064 9.83
12,500 1010 9.29 1053 10.15 1095 11.05
9,000 901 6.07 955 6.98 1008 7.98 1060 9.05
10,500 928 6.98 978 7.84 1026 8.76 1073 9.74
034 12,000 966 8.24 1011 9.07 1055 9.95 1098 10.88
13,500 1011 9.86 1052 10.67 1092 11.52
15,000 1062 11.84

LEGEND
Bhp Brake Horsepower Input to Fan
ESP External Static Pressure
Bold indicates field-supplied drive required.
Plain type indicates standard drive and standard motor.
Underline indicates a different motor and drive combination other
than the standard motor and standard drive combination is required.
Refer to fan motor and drive tables, pages 61-64, to complete the
selection.
NOTES:
1. Maximum allowable fan speed is 1100 rpm for unit sizes 028 and
034; 1200 rpm for all other sizes.
2. Fan performance is based on deductions for wet coil, clean 2-in.
filters, and unit casing. See page 36 for factory-supplied filter pres-
sure drop.
3. The medium-static drive and standard motor combination is not avail-
able for the 028 size. Use the alternate motor if the medium-static
drive is required for the 028 size.
4. Alternate motor not available for 034 size units.

37
Performance data (cont)
40RM ACCESSORY PLENUM AIR THROW DATA
(ft)

UNIT AIRFLOW VANE DEFLECTION


40RM (Cfm) Straight 2212 45
007 2,400 39 33 24
008 3,000 45 38 28
012 4,000 55 46 33
014 5,000 45 38 28
016 6,000 50 43 31
024 8,000 60 51 37
028 10,000 76 65 47
034 12,000 85 72 52
NOTE: Throw distances shown are for 75 fpm terminal velocity. Use the following mul-
tipliers to determine throw values for other terminal velocities.

TERMINAL VELOCITY THROW FACTOR


(Fpm)
50 X 1.50
100 X 0.75
150 X 0.50

40RM ACCESSORY PRESSURE DROP


(in. wg)

UNIT AIRFLOW DISCHARGE RETURN AIR HEATING COILS


ECONOMIZER
40RM (Cfm) PLENUM GRILLE Hot Water Steam Electric
1,800 0.06 0.01 0.10 0.10 0.04 0.05
007 2,400 0.10 0.01 0.16 0.16 0.06 0.07
3,000 0.14 0.02 0.23 0.23 0.10 0.09
2,250 0.09 0.01 0.15 0.15 0.06 0.06
008 3,000 0.14 0.02 0.23 0.23 0.10 0.09
3,750 0.21 0.03 0.35 0.35 0.15 0.15
3,000 0.14 0.02 0.23 0.23 0.10 0.09
012 4,000 0.22 0.04 0.37 0.37 0.17 0.17
5,000 0.32 0.06 0.53 0.53 0.26 0.28
3,750 0.07 0.01 0.11 0.11 0.04 0.05
014 5,000 0.12 0.02 0.17 0.17 0.07 0.07
6,250 0.17 0.02 0.25 0.25 0.11 0.11
4,500 0.10 0.01 0.15 0.15 0.06 0.06
016 6,000 0.16 0.02 0.23 0.23 0.10 0.09
7,500 0.23 0.03 0.33 0.33 0.15 0.15
6,000 0.16 0.02 0.23 0.23 0.10 0.09
024 8,000 0.26 0.04 0.37 0.37 0.17 0.17
10,000 0.37 0.06 0.53 0.53 0.26 0.28
7,500 0.15 0.02 0.28 0.28 0.09 0.06
028 10,000 0.24 0.03 0.44 0.44 0.16 0.09
12,500 0.34 0.05 0.63 0.63 0.24 0.14
9,000 0.20 0.03 0.37 0.37 0.13 0.08
034 12,000 0.32 0.05 0.59 0.59 0.22 0.14
15,000 0.46 0.07 0.85 0.85 0.34 0.21

38
40RM HYDRONIC HEATING CAPACITIES 40RM HEATING CORRECTION FACTORS

1-ROW 2-ROW HOT WATER COIL


UNIT AIRFLOW STEAM* HOT WATER COIL
40RM (Cfm) Water Temp Ent Water Entering-Air Temp (F)
Cap. Ldb Cap. Ldb Gpm PD Drop Temp
(F) (F) 40 50 60 70 80
1,800 146 134 156.0 140 15.6 3.4
007 2,400 173 126 183.0 131 18.3 4.3 140 0.72 0.64 0.57 0.49 0.41
3,000 209 123 206.0 124 20.6 5.2 160 0.89 0.81 0.74 0.66 0.58
2,250 168 129 174.0 133 17.4 4.0 10 180 1.06 0.98 0.90 0.83 0.75
008 3,000 209 123 206.0 124 20.6 5.2 200 1.22 1.15 1.07 1.00 0.92
3,750 240 117 238.0 118 23.8 6.5 220 1.39 1.32 1.24 1.17 1.09
3,000 209 123 299.0 152 29.9 5.0 140 0.64 0.57 0.49 0.41 0.33
012 4,000 243 115 275.0 124 27.5 6.6 160 0.81 0.74 0.66 0.58 0.51
5,000 279 111 316.0 119 31.6 8.2 20 180 0.98 0.91 0.83 0.75 0.68
200 1.15 1.08 1.00 0.93 0.85
3,750 370 150 362.0 149 36.2 4.2 220 1.32 1.25 1.17 1.10 1.02
014 5,000 425 137 409.0 136 40.9 5.1
6,250 465 128 456.0 128 45.6 6.0 140 0.56 0.49 0.41 0.33 0.24
160 0.74 0.66 0.58 0.51 0.43
4,500 402 141 412.0 145 41.2 4.5 30 180 0.91 0.83 0.76 0.68 0.60
016 6,000 458 129 471.0 133 47.1 5.5 200 1.08 1.00 0.93 0.85 0.78
7,500 479 118 529.0 125 52.9 6.6 220 1.25 1.18 1.10 1.03 0.95
6,000 458 129 506.0 138 50.6 5.1
024 8,000 487 115 584.0 128 58.4 6.3
10,000 499 105 652.0 120 65.2 7.5
7,500 511 122 649.0 140 64.9 5.7 STEAM COIL
028 10,000 575 112 752.0 130 75.2 7.1 Steam Pressure Entering-Air Temp (F)
12,500 626 106 842.0 122 84.2 8.5 (psig) 40 50 60 70 80
9,000 560 117 735.0 136 73.5 6.2 0 1.06 0.98 0.91 0.85 0.78
034 12,000 621 107 850.0 126 85.0 7.8 2 1.09 1.02 0.95 0.89 0.82
15,000 670 101 950.0 119 95.0 9.3 5 1.13 1.06 1.00 0.93 0.87
LEGEND NOTE: Multiply capacity given in the Hydronic Heating Capacities table
Cap. Capacity (Btuh in thousands) by the correction factor for conditions at which unit is actually operating.
Ldb Leaving-Air Dry-Bulb Temp (F) Correct leaving-air temperature using formula in Note 3 of Hydronic
PD Pressure Drop (ft water) Heating Capacities table.
*Based on 5 psig steam, 60 F entering-air temperature. All steam coils
are non-freeze type.
Based on 200 F entering water, 20 F water temperature drop, 60 F
entering-air temperature.
NOTES:
1. Maximum operating limits for steam heating coils:
175 psig at 400 F.
2. Maximum operating limit for hot water heating coils is 150 psig.
Capacity (Btuh)
3. Leaving db =ent db (F) +
1.1 x cfm
4. See Heating Correction Factors table.

39
Electrical data
38AK007-012, 38AKS008-012

UNIT NOMINAL VOLTAGE VOLTAGE RANGE* COMPR OFM POWER SUPPLY


38 (V-Ph-Hz) Min Max RLA LRA FLA MCA MOCP
208/230-3-60 187 254 19.0 142 2.8 26.6 35
AK007 460-3-60 414 508 9.5 72 1.1 13.0 15
575-3-60 518 632 7.6 58 2.8 12.3 15
208/230-3-60 187 254 25.0 185 3.8 35.1 45
AK008 460-3-60 414 508 12.4 89 1.9 17.4 20
575-3-60 518 632 10.4 78 1.9 14.9 20
208/230-3-60 187 254 34.5 239 3.8 46.9 60
AK012 460-3-60 414 508 17.0 119 1.9 23.2 30
575-3-60 518 632 14.3 90 1.9 19.8 25
208/230-3-60 187 254 31.5 160 3.8 43.2 50
AKS008 380-3-60 342 418 19.0 75 2.2 26.0 35
460-3-60 414 508 15.7 80 1.9 21.5 25
575-3-60 518 632 12.6 64 1.9 17.7 20
208/230-3-60 187 254 39.7 198 3.8 53.4 60
AKS009 380-3-60 342 418 24.0 93 2.2 32.2 40
460-3-60 414 508 19.9 99 1.9 26.8 35
575-3-60 518 632 15.9 79 1.9 21.8 25
208/230-3-60 187 254 39.7 198 3.8 53.4 60
380-3-60 342 418 24.0 93 2.2 32.2 40
AKS012 460-3-60 414 508 19.9 99 1.9 26.8 35
575-3-60 518 632 15.9 79 1.9 21.8 25

LEGEND *Units are suitable for use on electrical systems where voltage supplied
CSA Canadian Standards Association to the unit terminals is not below or above the listed limits.
FLA Full Load Amps 380-v units are export models not listed with UL or CSA.
HACR Heating, Air Conditioning and NOTES:
Refrigeration 1. In compliance with NEC (National Electrical Code) requirements for
LRA Locked Rotor Amps multimotor and combination load equipment (refer to NEC Articles
MCA Minimum Circuit Amps 430 and 440), the overcurrent protective device for the unit shall be
MOCP Maximum Overcurrent Protection fuse or HACR breaker.
OFM Outdoor (Condenser) Fan Motor 2. The MCA and MOCP values are calculated in accordance with the
RLA Rated Load Amps NEC, Article 440.
3. Motor RLA and LRA values are established in accordance with Un-
derwriters Laboratories (UL), Standard 1995.
4. The 575-v units are CSA-listed only.

38AKS013-024
UNIT COMPRESSOR FAN MOTORS (Single Phase) POWER SUPPLY
UNIT Nominal Voltage Range* FLA (ea)
38AKS Model Voltage RLA LRA Total Fan No. kW MCA ICF MOCP
(3-Ph, 60 Hz) Fans
Min Max 1 2
501 208-230 187 253 43.6 170 4.3 3.7 62.5 178 100
201 380** 342 418 24.0 93 4.3 3.7 35.0 101 50
013 601 460 414 528 20.0 77 2 2.3 1.9 1.41 29.1 81 40
101 575 518 660 15.7 62 1.8 1.8 22.8 67 35
501 208-230 187 253 49.3 191 4.3 3.7 69.6 199 100
014 201 380** 342 418 26.5 104 2 4.3 3.7 1.41 38.5 112 60
601 460 414 528 22.1 80 2.3 1.9 31.7 84 50
101 575 518 660 17.9 69 1.8 1.8 25.6 73 40
501 208-230 187 253 63.6 266 4.3 3.7 87.5 274 125
016 201 380** 342 418 36.0 145 2 4.3 3.7 1.41 49.3 153 80
601 460 414 528 29.3 120 2.3 1.9 40.7 124 60
101 575 518 660 23.8 96 1.8 1.8 33.0 100 50
501 208-230 187 254 67.9 345 4.3 3.7 93.4 353 150
024 201 380** 342 418 34.6 191 2 4.3 3.7 1.41 49.7 199 80
601 460 414 508 34.7 173 2.3 1.9 48.1 177 80
101 575 518 632 28.8 120 1.8 1.8 40.1 124 60

LEGEND *Units are suitable for use on electrical systems where voltage supplied
CSA Canadian Standards Association to the unit terminals is not below or above the listed limits.
FLA Full Load Amps Fuse or HACR circuit breaker.
HACR Heating, Air Conditioning and **380-v units are export models not listed with UL or CSA.
Refrigeration NOTES:
ICF Maximum Instantaneous Current Flow 1. The MCA and MOCP values are calculated in accordance with the
During Start-Up (LRA of compressor National Electrical Code (NEC), Article 440.
plus total FLA of fan motors) 2. Motor RLA and LRA values are established in accordance with Un-
kW Total Fan Motor Input (kilowatts) derwriters Laboratories (UL), Standard 1995.
LRA Locked Rotor Amps 3. The 575-v units are CSA-listed only.
MCA Minimum Circuit Amps per NEC,
Section 430-24
MOCP Maximum Overcurrent Protection (amps)
RLA Rated Load Amps (compressor)

40
38AKS028-044
UNIT COMPRESSOR FAN MOTORS POWER SUPPLY
UNIT Nominal Voltage
38AKS Voltage Range* FLA RLA LRA Qty FLA MCA ICF MOCP
(3 Ph, 60-Hz) (ea)
Min Max
208/230 187 254 102.2 89.8 446 6.2 124.6 452.2 200
028 380** 342 418 53.3 45.5 247 2 3.9 64.7 250.9 110
460 414 508 49.8 43.6 223 3.1 60.7 226.1 100
575 518 632 43.3 36.5 164 3.4 52.5 167.4 80
208/230 187 254 118.4 106.5 506 6.2 145.5 512.2 250
034 380** 342 418 60.4 52.6 280 2 3.9 72.5 283.9 125
460 414 508 56.2 50.0 253 3.1 68.7 256.1 110
575 518 632 45.3 38.5 176 3.4 54.9 179.4 90
208/230 187 254 165.6 147.5 690 6.2 203.0 702.4 350
044 380** 342 418 91.2 79.5 382 3 3.9 111.1 389.8 175
460 414 508 74.7 65.4 345 3.1 91.0 351.2 150
575 518 632 67.3 57.1 276 3.4 81.5 282.8 125

\EGEND *Units are suitable for use on electrical systems where voltage supplied
CSA Canadian Standards Association to the unit terminals is not below or above the listed minimum and
FLA Full Load Amps maximum limits.
HACR Heating, Air Conditioning, and Refrigeration Fuse or HACR circuit breaker.
ICF Maximum Instantaneous Current Flow during starting. (The **The 380-v units are export models not listed with UL or CSA.
point in the starting sequence where the sum of of the LRA
for the starting compressor, plus the total RLA for all run-
ning compressors, plus the total FLA for all running motors
is maximum.)
LRA Locked Rotor Amps
MCA Minimum Circuit Amps (Complies with National Electrical
Code [NEC], Section 430-24)
MOCP Maximum Overcurrent Protection
RLA Rated Load Amps
UL Underwriters Laboratories

41
Electrical data (cont)
40RM STANDARD MOTORS
FAN MOTOR POWER SUPPLY
UNIT V*-PH-Hz VOLTAGE Minimum
40RM LIMITS Hp FLA Circuit MOCP
Amps
208/230-1-60 187-253 1.3 7.6 9.5 15
208/230-3-60 187-253 2.4 5.2 6.5 15
007 460-3-60 414-506 2.4 2.6 3.3 15
575-3-60 518-632 1.0 1.4 8.0 15
208/230-1-60 187-253 2.4 11.0 13.8 20
008 208/230-3-60 187-253 2.4 5.2 6.5 15
460-3-60 414-506 2.4 2.6 3.3 15
575-3-60 518-632 2.0 2.3 2.9 15
208/230-3-60 187-253 2.4 5.2 19.5 20
012 460-3-60 414-506 2.4 2.6 3.3 15
575-3-60 518-632 2.0 2.3 2.9 15
208/230-3-60 187-253 2.9 7.5 9.4 15
014 460-3-60 414-506 2.9 3.4 4.3 15
575-3-60 518-632 3.0 3.8 4.8 15
208/230-3-60 187-253 3.7 10.2 12.8 20
016 460-3-60 414-506 3.7 4.8 6.0 15
575-3-60 518-632 3.0 3.8 4.8 15
208/230-3-60 187-253 5.0 15.3/12.8 19.1/16.0 30/25
024 460-3-60 414-506 5.0 6.4 8.0 15
575-3-60 518-632 5.0 5.1 6.4 15
208/230-3-60 187-253 7.5 22.4/19.4 28.0/24.3 50/40
028 460-3-60 414-506 7.5 9.7 12.1 20
575-3-60 518-632 7.5 7.8 9.8 15
208/230-3-60 187-253 10.0 29.3/26.8 36.6/33.5 60/60
034 460-3-60 414-506 10.0 13.4 16.8 30
575-3-60 518-632 10.0 10.3 12.9 20

LEGEND *Motors are designed for satisfactory operation within 10% of nominal
FLA Full Load Amps voltages shown. Voltages should not exceed the limits shown in the
Hp Horsepower Voltage Limits column.
MOCP Maximum Overcurrent Protection

40RM ALTERNATE MOTORS


FAN MOTOR POWER SUPPLY
UNIT V*PH-Hz VOLTAGE Minimum
40RM LIMITS HP (kW) FLA Circuit MOCP
Amps
208/230-1-60 187-253 2.4 (1.79) 11.0 13.8 20
007 208/230-3-60 187-253 2.9 (2.16) 7.5 9.4 15
460-3-60 414-506 2.9 (2.16) 3.4 4.3 15
575-3-60 518-632 2.0 (1.50) 2.3 2.9 15
208/230-1-60 187-253 2.4 (1.79) 11.0 13.8 15
008 208/230-3-60 187-253 2.9 (2.16) 7.5 9.4 15
460-3-60 414-506 2.9 (2.16) 3.4 4.3 15
575-3-60 518-632 3.0 (2.24) 3.8 4.8 15
208/230-3-60 187-253 3.7 (2.76) 10.2 12.8 20
012 460-3-60 414-506 3.7 (2.76) 4.8 6.0 15
575-3-60 518-632 3.0 (2.24) 3.8 4.8 15
208/230-3-60 187-253 3.7 (2.76) 10.2 12.7 20
014 460-3-60 414-506 3.7 (2.76) 4.8 6.0 15
575-3-60 518-632 5.0 (3.73) 5.1 6.4 15
208/230-3-60 187-253 5.0 (3.73) 15.3/12.8 19.1/16.0 30/25
016 460-3-60 414-506 5.0 (3.73) 6.4 8.0 15
575-3-60 518-632 5.0 (3.73) 5.1 6.4 15
208/230-3-60 187-253 7.5 (5.60) 22.4/19.4 28.0/24.3 50/40
024 460-3-60 414-506 7.5 (5.60) 9.7 12.1 20
575-3-60 518-632 7.5 (5.60) 7.8 9.8 15
208/230-3-60 187-253 10.0 (7.46) 29.3/26.8 36.6/32.3 60/50
028 460-3-60 414-506 10.0 (7.46) 13.4 16.8 25
575-3-60 518-632 10.0 (7.46) 10.3 12.9 20

LEGEND *Motors are designed for satisfactory operation within 10% of nominal
FLA Full Load Amps voltages shown. Voltages should not exceed the limits shown in the
Hp Horsepower Voltage Limits column.
MOCP Maximum Overcurrent Protection

42
40RM ELECTRIC HEATER DATA
ELECTRIC HEATERS (S)
UNIT HEATER FAN MOTOR
V-PH-Hz Nominal Actual Capacity (kW) MCA* MOCP*
40RM PART NO. Capacity FLA
Hp kW FLA (kW) Stage 1 Stage 2 Total
1.3 0.97 7.6 5 5.0 5.0 12.0 24.5 25
2.4 1.79 11.0 5 5.0 5.0 12.0 28.8 35
CAELHEAT001A00 240-3-60 2.4 1.79 5.2 5 5.0 5.0 12.0 21.5 25
2.9 2.16 7.5 5 5.0 5.0 12.0 24.4 25
3.7 2.76 10.2 5 5.0 5.0 12.0 27.8 30
2.4 1.79 2.6 5 5.0 5.0 6.00 10.8 15
CAELHEAT002A00 480-3-60 2.9 2.16 3.4 5 5.0 5.0 6.00 11.8 15
3.7 2.76 4.8 5 5.0 5.0 6.00 13.5 15
1.0 0.75 1.4 5 5.0 5.0 5.00 8.0 15
CAELHEAT003A00 575-3-60 2.0 1.49 2.3 5 5.0 5.0 5.00 9.2 15
3.0 2.24 3.8 5 5.0 5.0 5.00 11.0 15
1.3 0.97 7.6 10 10.0 10.0 24.1 39.6 40
2.4 1.79 11.0 10 10.0 10.0 24.1 43.8 50
CAELHEAT004A00 240-3-60 2.4 1.79 5.2 10 10.0 10.0 24.1 36.6 40
2.9 2.16 7.5 10 10.0 10.0 24.1 39.4 40
3.7 2.76 10.2 10 10.0 10.0 24.1 42.8 50
2.4 1.79 2.6 10 10.0 10.0 12.0 18.3 20
CAELHEAT005A00 480-3-60 2.9 2.16 3.4 10 10.0 10.0 12.0 19.3 20
3.7 2.76 4.8 10 10.0 10.0 12.0 21.0 25
1.0 0.75 1.4 10 10.0 10.0 10.0 14.3 15
CAELHEAT006A00 575-3-60 2.0 1.49 2.3 10 10.0 10.0 10.0 15.4 20
3.0 2.24 3.8 10 10.0 10.0 10.0 17.3 20
007-012
1.3 0.97 7.6 15 15.0 15.0 36.1 54.6 60
2.4 1.79 11.0 15 15.0 15.0 36.1 58.9 60
CAELHEAT007A00 240-3-60 2.4 1.79 5.2 15 15.0 15.0 36.1 51.6 60
2.9 2.16 7.5 15 15.0 15.0 36.1 54.5 60
3.7 2.76 10.2 15 15.0 15.0 36.1 57.9 60
2.4 1.79 2.6 15 15.0 15.0 18.0 25.8 30
CAELHEAT008A00 480-3-60 2.9 2.16 3.4 15 15.0 15.0 18.0 26.8 30
3.7 2.76 4.8 15 15.0 15.0 18.0 28.6 30
1.0 0.75 1.4 15 15.0 15.0 15.1 20.6 25
CAELHEAT009A00 575-3-60 2.0 1.49 2.3 15 15.0 15.0 15.1 21.7 25
3.0 2.24 3.8 15 15.0 15.0 15.1 23.6 25
1.3 0.97 7.6 25 15.0 10.0 25.0 60.1 84.7 90
2.4 1.79 11.0 25 15.0 10.0 25.0 60.1 88.9 90
CAELHEAT010A00 240-3-60 2.4 1.79 5.2 25 15.0 10.0 25.0 60.1 81.7 90
2.9 2.16 7.5 25 15.0 10.0 25.0 60.1 84.6 90
3.7 2.76 10.2 25 15.0 10.0 25.0 60.1 87.9 90
2.4 1.79 2.6 25 15.0 10.0 25.0 30.1 40.8 50
CAELHEAT011A00 480-3-60 2.9 2.16 3.4 25 15.0 10.0 25.0 30.1 41.8 50
3.7 2.76 4.8 25 15.0 10.0 25.0 30.1 43.6 50
1.0 0.75 1.4 25 15.0 10.0 25.0 25.1 33.1 35
CAELHEAT012A00 575-3-60 2.0 1.49 2.3 25 15.0 10.0 25.0 25.1 34.3 35
3.0 2.24 3.8 25 15.0 10.0 25.0 25.1 36.1 40

LEGEND NOTES:
FLA Full Load Amps 1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
Hp Horsepower determine heater capacity (kW) at unit nameplate multiply the 240-v,
MCA Minimum Circuit Amps 480-v, or 575-v capacity (kW) by the factor shown in the table below
MOCP Maximum Overcurrent Protection (Amps) for the unit voltage.
2. The following equation converts kW of heat energy to Btuh: kW x
*Values shown are for single-point connection of electric heat acces- 3,412 = Btuh.
sory and air handler. 3. Heater contactor coils are 24 v and require 8 va holding current.
Single-phase motors. All other motors are 3-phase. 4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-
supplied motors.

HEATER ACTUAL HEATER VOLTAGE


RATING
VOLTAGE 200 208 230 240 400 440 460 480 550 575 600
240 0.694 0.751 0.918 1
480 0.694 0.84 0.918 1
575 0.915 1 1.089

43
Electrical data (cont)
40RM ELECTRIC HEATER DATA (cont)
ELECTRIC HEATERS (S)
UNIT HEATER FAN MOTOR
V-PH-Hz Nominal Actual Capacity (kW) MCA* MOCP*
40RM PART NO. Capacity FLA
Hp kW FLA (kW) Stage 1 Stage 2 Total
2.4 1.79 11.0 35 20.0 15.0 35.0 84.2 119.0 125
CAELHEAT013A00 240-3-60 2.4 1.79 5.2 35 20.0 15.0 35.0 84.2 111.7 125
2.9 2.16 7.5 35 20.0 15.0 35.0 84.2 114.6 125
3.7 2.76 10.2 35 20.0 15.0 35.0 84.2 118.0 125
008,012 2.4 1.79 2.6 35 20.0 15.0 35.0 42.1 55.9 60
CAELHEAT014A00 480-3-60 2.9 2.16 3.4 35 20.0 15.0 35.0 42.1 56.9 60
3.7 2.76 4.8 35 20.0 15.0 35.0 42.1 58.6 60
CAELHEAT015A00 575-3-60 2.0 1.49 2.3 35 20.0 15.0 35.0 35.1 46.8 50
3.0 2.24 3.8 35 20.0 15.0 35.0 35.1 48.7 50
2.9 2.16 7.5 10 10.0 10.0 24.1 39.4 40
CAELHEAT016A00 240-3-60 3.7 2.76 10.2 10 10.0 10.0 24.1 42.8 50
5.0 3.73 12.8 10 10.0 10.0 24.1 46.1 50
7.5 5.59 19.4 10 10.0 10.0 24.1 54.4 70
2.9 2.16 3.4 10 10.0 10.0 12.0 19.3 20
CAELHEAT017A00 480-3-60 3.7 2.76 4.8 10 10.0 10.0 12.0 21.0 25
5.0 3.73 6.4 10 10.0 10.0 12.0 23.0 25
7.5 5.59 9.7 10 10.0 10.0 12.0 27.2 30
3.0 2.24 3.8 10 10.0 10.0 10.0 17.3 20
CAELHEAT018A00 575-3-60 5.0 3.73 5.1 10 10.0 10.0 10.0 19.6 20
7.5 5.59 7.8 10 10.0 10.0 10.0 22.1 25
2.9 2.16 7.5 20 20.0 20.0 48.1 69.5 70
3.7 2.76 10.2 20 20.0 20.0 48.1 73.4 80
CAELHEAT019A00 240-3-60 5.0 3.73 12.8 20 20.0 20.0 48.1 76.1 80
7.5 5.59 19.4 20 20.0 20.0 48.1 84.4 90
2.9 2.16 3.4 20 20.0 20.0 24.1 34.3 35
014-024 CAELHEAT020A00 480-3-60 3.7 2.76 4.8 20 20.0 20.0 24.1 36.1 40
5.0 3.73 6.4 20 20.0 20.0 24.1 39.1 40
7.5 5.59 9.7 20 20.0 20.0 24.1 43.2 50
3.0 2.24 3.8 20 20.0 20.0 20.1 29.9 30
CAELHEAT021A00 575-3-60 5.0 3.73 5.1 20 20.0 20.0 20.1 31.5 35
7.5 5.59 7.8 20 20.0 20.0 20.1 34.9 35
2.9 2.16 7.5 30 20.0 10.0 30.0 72.2 99.6 100
3.7 2.76 10.2 30 20.0 10.0 30.0 72.2 103.0 110
CAELHEAT022A00 240-3-60 5.0 3.73 12.8 30 20.0 10.0 30.0 72.2 106.2 110
7.5 5.59 19.4 30 20.0 10.0 30.0 72.2 114.5 125
2.9 2.16 3.4 30 20.0 10.0 30.0 36.1 49.4 50
CAELHEAT023A00 480-3-60 3.7 2.76 4.8 30 20.0 10.0 30.0 36.1 51.1 60
5.0 3.73 6.4 30 20.0 10.0 30.0 36.1 53.1 60
7.5 5.59 9.7 30 20.0 10.0 30.0 36.1 57.2 60
3.0 2.24 3.8 30 20.0 10.0 30.0 30.1 42.4 50
CAELHEAT024A00 575-3-60 5.0 3.73 5.1 30 20.0 10.0 30.0 30.1 44.0 50
7.5 5.59 7.8 30 20.0 10.0 30.0 30.1 47.4 50
3.7 2.76 10.2 50 30.0 20.0 50.0 120.3 163.1 175
CAELHEAT025A00 240-3-60 5.0 3.73 12.8 50 30.0 20.0 50.0 120.3 166.4 175
7.5 5.59 19.4 50 30.0 20.0 50.0 120.3 174.6 200
3.7 2.76 4.8 50 30.0 20.0 50.0 60.1 81.2 90
016,024 CAELHEAT026A00 480-3-60 5.0 3.73 6.4 50 30.0 20.0 50.0 60.1 83.2 90
7.5 5.59 9.7 50 30.0 20.0 50.0 60.1 87.3 90
3.0 2.24 3.8 50 30.0 20.0 50.0 50.2 67.5 70
CAELHEAT027A00 575-3-60 5.0 3.73 5.1 50 30.0 20.0 50.0 50.2 69.1 70
7.5 5.59 7.8 50 30.0 20.0 50.0 50.2 72.5 80
CAELHEAT028A00 240-3-60 7.5 5.59 19.4 20 20.0 20.0 48.1 84.3 90
10.0 7.46 26.8 20 20.0 20.0 48.1 94.0 110
CAELHEAT029A00 480-3-60 7.5 5.59 9.7 20 20.0 20.0 24.1 42.2 50
10.0 7.46 13.4 20 20.0 20.0 24.1 46.8 50
028,034
CAELHEAT030A00 575-3-60 7.5 5.59 7.8 20 20.0 20.0 20.1 34.9 35
10.0 7.46 10.3 20 20.0 20.0 20.1 38.0 40
CAELHEAT031A00 240-3-60 7.5 5.59 19.4 40 20.0 20.0 40.0 96.2 144.5 150
10.0 7.46 26.8 40 20.0 20.0 40.0 96.2 153.8 175

44
40RM ELECTRIC HEATER DATA (cont)
ELECTRIC HEATERS (S)
UNIT HEATER FAN MOTOR
V-PH-Hz Nominal Actual Capacity (kW) MCA* MOCP*
40RM PART NO. Capacity FLA
Hp kW FLA (kW) Stage 1 Stage 2 Total

CAELHEAT032A00 480-3-60 7.5 5.59 9.7 40 20.0 20.0 40.0 48.1 72.3 80
10.0 7.46 13.4 40 20.0 20.0 40.0 48.1 76.9 80
CAELHEAT033A00 575-3-60 7.5 5.59 7.8 40 20.0 20.0 40.0 40.2 60.0 60
10.0 7.46 10.3 40 20.0 20.0 40.0 40.2 63.1 70
CAELHEAT034A00 240-3-60 7.5 5.59 19.4 50 30.0 20.0 50.0 120.3 174.6 200
10.0 7.46 26.8 50 30.0 20.0 50.0 120.3 183.9 200
CAELHEAT035A00 480-3-60 7.5 5.59 9.7 50 30.0 20.0 50.0 60.1 87.3 90
10.0 7.46 13.4 50 30.0 20.0 50.0 60.1 91.9 100
028,034
CAELHEAT036A00 575-3-60 7.5 5.59 7.8 50 30.0 20.0 50.0 50.2 72.5 80
10.0 7.46 10.3 50 30.0 20.0 50.0 50.2 75.6 80
CAELHEAT037A00 240-3-60 7.5 5.59 19.4 70 40.0 30.0 70.0 168.4 192.6 200
10.0 7.46 26.8 70 40.0 30.0 70.0 168.4 201.9 225
CAELHEAT038A00 480-3-60 7.5 5.59 9.7 70 40.0 30.0 70.0 84.2 96.3 100
10.0 7.46 13.4 70 40.0 30.0 70.0 84.2 100.9 110
CAELHEAT039A00 575-3-60 7.5 5.59 7.8 70 40.0 30.0 70.0 70.3 80.0 90
10.0 7.46 10.3 70 40.0 30.0 70.0 70.3 83.2 90

LEGEND NOTES:
FLA Full Load Amps 1. Electrical resistance heaters are rated at 240 v, 480 v, or 575 v. To
Hp Horsepower determine heater capacity (kW) at unit nameplate multiply the 240-v,
MCA Minimum Circuit Amps 480-v, or 575-v capacity (kW) by the factor shown in the table below
MOCP Maximum Overcurrent Protection (Amps) for the unit voltage.
2. The following equation converts kW of heat energy to Btuh: kW x
*Values shown are for single-point connection of electric heat acces- 3,412 = Btuh.
sory and air handler. 3. Heater contactor coils are 24 v and require 8 va holding current.
Single-phase motors. All other motors are 3-phase. 4. Electric heaters are tested and ETL approved at maximum total
external static pressure of 1.9 in. wg.
5. MCA and MOCP values apply to both standard and alternate factory-
supplied motors.

HEATER ACTUAL HEATER VOLTAGE


RATING
VOLTAGE 200 208 230 240 400 440 460 480 550 575 600
240 0.694 0.751 0.918 1
480 0.694 0.84 0.918 1
575 0.915 1 1.089

45
Typical piping and wiring
ROOFTOP INSTALLATION 38AK007-012, 38AKS008-012

LEGEND 2. All wiring must comply with the applicable local and national codes.
NEC National Electrical Code 3. Wiring and piping shown are general points-of-connection guides
TXV Thermostatic Expansion Valve only and are not intended for, or to include all details for, a spe-
cific installation.
*Accessory item. 4. Liquid line solenoid valve (solenoid drop control) is recommended
Field supplied. to prevent refrigerant migration to the compressor.
NOTES: 5. Internal factory-supplied TXVs not shown.
1. All piping must follow standard refrigerant piping techniques. Re-
fer to Carrier System Design Manual for details.

46
ROOFTOP INSTALLATION 38AKS013-024

LEGEND NOTES:
NEC National Electrical Code 1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design
TXV Thermostatic Expansion Valve Manual for details.
Piping 2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended
*Field supplied. for, or to include all details for, a specific installation.
Double riser may be required. Consult Ap- 4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant
plication section for details. migration to the compressor.
5. Internal factory-supplied TXVs not shown.

47
Typical piping and wiring (cont)
GROUND LEVEL INSTALLATION 38AKS013-024

LEGEND NOTES:
TXV Thermostatic Expansion Valve 1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design
Piping Manual for details.
2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended
*Field supplied. for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant mi-
gration to the compressor.
5. Internal factory-supplied TXVs not shown.

48
ROOFTOP INSTALLATION 38AKS028-044

LEGEND NOTES:
NEC National Electrical Code 1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design
TXV Thermostatic Expansion Valve Manual for details.
Piping 2. All wiring must comply with the applicable local and national codes.
3. Wiring and piping shown are general points-of-connection guides only and are not intended
*Field supplied. for, or to include all details for, a specific installation.
Double riser may be required. Consult Ap- 4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant
plication section for details. migration to the compressor.
5. Internal factory-supplied TXVs not shown.

49
Typical piping and wiring (cont)
GROUND-LEVEL INSTALLATION 38AKS028-044

LEGEND NOTES:
TXV Thermostatic Expansion Valve 1. All piping must follow standard refrigerant piping techniques. Refer to Carrier System Design
Piping Manual for details.
2. All wiring must comply with the applicable local and national codes.
*Field supplied. 3. Wiring and piping shown are general points-of-connection guides only and are not intended
for, or to include all details for, a specific installation.
4. Liquid line solenoid valve (solenoid drop control) is recommended to prevent refrigerant
migration to the compressor.

50
Typical wiring schematic
(38AKS024-044 shown)

51
Typical wiring schematic
(38AKS024-044 shown) (cont)

LEGEND
AFS Airflow Switch TC Thermostat-Cooling
ATS Air Temperature Switch TRAN Transformer
BPR Bypass Relay
C Contactor, Compressor Terminal Block
CB Circuit Breaker Connection
CH Crankcase Heater Marked Terminal
CM Control Module
COMP Compressor Motor Unmarked Terminal
CR Control Relay
EQUIP Equipment Marked Splice
FC Fan Contactor
FCPS Fan Cycling Unmarked Splice
Pressure Switch
FM Fan Motor Factory Wiring
FU Fuse
GND Ground Field Control Wiring
HPS High-Pressure Switch Field Power Wiring
LLSV Liquid Line Solenoid Indicates Common
Valve Potential, Does No
LPS Low-Pressure Switch Represent Wiring
OPS Oil Pressure Switch
TB Terminal Block
NOTES: 7. Wiring for field power supply must be rated 60 C. Use copper, copper-clad
1. Connect TRAN2 to Terminal H3 for 230 V, H4 for 460 V, and H2 for 575 V units. aluminum or aluminum conductors.
If 208/230 V units are run with a 208 V power supply connect to Terminal H2. 8. Terminals G/6, Y2/3 and C/7 of TB3 are for Class 2 (24 V) field external
2. Connect TRAN1 to ORN lead for 230 V, BLK lead for 460 V, and WHT lead for interlock connections. Class 1 field interlock contacts must have minimum rat-
575 V units. If 208/230 V units are run with a 208 V power supply connect to ing of 180 VA, 220 V, 50/60 Hz pilot duty. Class 2 field interlock contacts must
RED lead. have minimum rating of 70 VA, 24 V, 50/60 Hz pilot duty.
3. Compressor and fan motors thermally protected. Three-phase motors pro- 9. Thermostat for standard units:
tected against primary single phasing conditions. HH01AD042, HH07AT172 and HH07AT174.
4. Replacement of original wires must be with Type 90 C wire or its equivalent. Subbase:
5. Line # indicates location of contacts, #,# signifies single-pole double- HH93AZ042, HH93AZ176 and HH93AZ180.
10. Control module internal illustrated to indicate components orientational
throw contacts. # signifies a normally closed contact. # signifies a normally sequence. All items illustrated are theoretically represented as internal to
open contact. component.
6. Factory wiring is in accordance with National Electrical Code (NEC). Field modi- 11. The factory supplied LLSV drop control is shipped with the 38AKS unit but
fications or additions must be in compliance with all applicable codes. field installed at the indoor unit.

52
Controls
Operating sequences 38AKS028-044 When space thermostat calls for cool-
38AK007-012, 38AKS008-012 At start-up, the ther- ing, the no. 1 condenser fan and compressor starts after
mostat calls for cooling. With all safety devices satisfied, the control module (CM) initial time delay of 3 (+2/1) sec-
compressor contactor and fan contactor energize, causing onds. If an optional airflow switch is used, compressor and
the compressor and outdoor fan motor to operate. Con- no. 1 condensing fan will not start until sufficient indoor
tacts energize, allowing the field-supplied and -installed airflow has closed the switch. After 3 seconds the compres-
indoor-fan contactor to function. A field-supplied and -installed sor starts and the liquid line solenoid valve (for solenoid drop
liquid line valve also opens, allowing the system to function control) opens. The crankcase heater is deenergized. If the
in Cooling mode. As cooling demand is satisfied, the ther- head pressure reaches 260 psig, the second condenser fan
mostat contacts break, deenergizing the contactor and starts.
causing the system to shut off. The liquid line solenoid valve If cooling demand is low, suction pressure at the com-
closes, minimizing the potential for refrigerant migration. pressor drops. As the pressure drops, the compressor
The compressor does not restart until the thermostat again unloads 2 banks of cylinders as required. If cooling demand
calls for cooling. The system is protected with a Cycle- is high and 2-stage operation is used, the second step
LOC device so that the compressor will not start if a of the thermostat activates the capacity control liquid line
high-pressure or low-pressure fault occurs. To reset the solenoid which activates the second stage evaporator coil.
Cycle-LOC device, set the thermostat to eliminate the cool- The compressor cylinders load or unload in response to com-
ing demand, then return to original set point. This should pressor suction pressure to meet evaporator load.
be done only once, and if system shuts down due to the Two minutes after the compressor starts, the bypass re-
same fault, determine the problem before attempting to lay (BPR) timer is deenergized and the low-pressure switch
reset the Cycle-LOC device. (LPS) bypass is deactivated. If the LPS trips during the first
38AKS013-024 When the first stage of cooling ther- 2 minutes of operation, the compressor remains opera-
mostat closes, the timer starts. After approximately 3 sec- tional. If a high-pressure switch (HPS) trips at any time, or
onds, the timer activates the compressor and fan motor the LPS trips after 2 minutes, the compressor cannot
no. 1 contactors. When the liquid pressure builds to restart until the control circuit power is interrupted due to
approximately 257 psig fan motor no. 2 is energized. the CM lockout feature.
On demand for additional cooling capacity, the second As the space cooling load is satisfied, the second stage of
stage of the cooling thermostat closes, energizing a field- the thermostat opens, and closes the field-supplied capac-
supplied liquid line solenoid (LLS) valve, which opens. This ity control liquid line solenoid valve to deactivate the sec-
increases the suction pressure, causing the compressor to ond stage coil. The compressor adjusts the number of active
operate at higher capacity (compressor loads). cylinders to meet the new load. When the space tempera-
When the fan switch is set at AUTO, the indoor-air fan ture is satisfied, the first stage of the thermostat opens and
cycles with the compressor. When the switch is set at CONT, the control relay and the BPR open. This closes the sole-
the indoor-air fan runs continuously. noid drop control valve. The compressor stops and the
crankcase heater is energized, preventing refrigerant from
At shutdown, the Time Guard II timer prevents the com-
migrating to the compressor during the off cycle (solenoid
pressor from restarting for approximately 5 minutes.
drop refrigerant control). The CM anti-short-cycling timer
In addition, a field-supplied solenoid valve wired in par- is energized and runs for approximately 5 minutes. During
allel with the compressor contactor coil shuts off the liquid this time, the compressor is not able to restart.
line to prevent refrigerant migration back to the compres-
sor during the off cycle.

53
Typical control wiring
TEMP SYSTEM APPLICATIONS 38AK007-012, 38AKS008-012

LEGEND
DX Direct Expansion Marked Terminal
IFC Indoor Fan Contactor
LLSV Liquid Line Solenoid Valve Factory Wiring
RV Reversing Valve Field Control Wiring
TB Terminal Block

*Jumper is removed only when separate 24-v power source is used to


power the 33CSUCE-06 relay pack.
33CSUCE-06 relay pack requires 10 va.
**Available as option for the 33CSUCE-06 relay pack.
Field-supplied.

54
TEMP SYSTEM APPLICATIONS 38AKS013-024

LEGEND
C Compressor Contactor
HD Heating Device
IFC Indoor Fan Contactor
LLSV Liquid Line Solenoid Valve
R Heat Control Relay (field-supplied,
24-volt seated coil,10-va max rating)
Factory Wiring
Field Wiring
*Field-supplied.

NOTES:
1. Combination LLSV plus IFC VA should not exceed 30 VA.
2. Do not exceed 5 VA (24 VAC) per coil.
3. If the VA values in Notes 1 and 2 must be exceeded, use accessory relay-transformer pack-
age 38AE900001.
4. Wiring diagrams are general guides only and are not intended for a specific installation.
Refer to individual product installation and wiring literature.

55
56

Typical control wiring (cont)


TEMP SYSTEM APPLICATIONS 38AKS028-044
LEGEND NOTES:
AFS Airflow Switch 1. Factory wiring in accordance with NEC. Any field
CB Circuit Breaker modifications or additions must be in compli-
EQUIP Equipment ance with all applicable codes.
FU Fuse 2. All field interlock contacts must have minimum
GND Ground rating of 180-va pilot duty plus capacity required
LLS1 Liquid Line Solenoid for for field-installed equipment. All field interlock con-
Solenoid Drop Control tacts in the 24-v control circuit must have mini-
LLS2 Liquid Line Solenoid for mum rating of 70-va pilot duty plus capacity
Capacity Control required for field-installed equipment.
NEC National Electrical Code 3. For internal unit wiring, reference wiring book or
TB Terminal Block unit wiring label diagram. TB2 is 115-1-60, TB3
TC Thermostat, Cooling is 24-1-60.
Field Power Wiring 4. The following components are not located in the
Field Control Wiring 38AKS unit control box: LLS1, LLS2, field con-
Factory-Installed Wiring trol thermostat, AFS, alarm shut-off switch, and
alarm or light.
*Field-supplied.
Application data
38AK007-012, 38AKS008-012
Operating limits REFRIGERANT PIPING SIZES
Maximum cooling load. . . . . . . . . . . . . . . . . . . . . . . . . 115 F LINEAR LENGTH OF PIPING FT
Minimum return-air temperature . . . . . . . . . . . . . . . . . 55 F 0-25 25-50 50-75 75-100
Maximum return-air temperature . . . . . . . . . . . . . . . . 95 F UNIT Line Size (in. OD)
38
Range of acceptable saturation L S L S L S L S
suction temperature . . . . . . . . . . . . . . . . . . . . 25 to 55 F AK007 12 118 1 2 118 1 2 118 12 118
Maximum discharge temperature . . . . . . . . . . . . . . . 275 F AK008 12 118 1 2 118 5 8 118 5 8 138
Minimum discharge superheat . . . . . . . . . . . . . . . . . . . 60 F AK012 58 118 5 8 138 5 8 138 5 8 138
AKS008 12 1 8
1 1 2 1 8
1 5 8 118 5 8 138
NOTES:
AKS009 58 118 5 8 118 5 8 138 5 8 138
1. Select air handler at no less than 300 cfm/ton (nominal
AKS012 58 118 5 8 118 5 8 138 5 8 138
condensing unit capacity).
2. Total combined draw of the field-supplied liquid line LEGEND
solenoid valve and air handler fan contactor must not L Liquid Line S Suction Line
exceed 22 va. If the specified va must be exceeded, use NOTES:
a remote relay to control the load. 1. Pipe sizes are based on a 2 F loss for liquid and suction lines.
2. Pipe sizes are based on the maximum linear length, shown for each
column, plus a 50% allowance for fittings.
3. Charge units with R-22 in accordance with unit installation
LIQUID LINE DATA instructions.
MAX LIQUID LINE
UNIT ALLOWABLE Max Allowable Max Allowable THERMOSTATIC EXPANSION VALVE (TXV),
38 LIQUID LIFT Pressure Drop Temp Loss DISTRIBUTOR, AND NOZZLE DATA
(ft) (psi) (F)
AK007 86 CONDENSING TXV PART NOZZLE
AK008 60 INDOOR COIL
UNIT 38 NO. CODE
AK012 70 28LA008 Included G8*
AKS008 60 7 2 AK007 28CB008 P530-FE0750HCD J5
AKS009 65
AKS012 65 28LA008 Included G8*
AKS008 28LA012 Included E10*
NOTE: Values shown are for units operating at 45 F saturated suction 28CB008 P530-FE0750HCD J5
and 95 F entering air. 28CB012 P530-FE1000HC35D G8
*Nozzles are factory installed and are correct for these applications.
Replace factory-installed nozzle with part number in Nozzle Code
column.
MINIMUM OUTDOOR-AIR OPERATING NOTE: See page 61 for 40RM TXV, distributor, and nozzle data.
TEMPERATURE
MINIMUM FACTORY-INSTALLED NOZZLE AND
COND OUTDOOR TEMP
UNIT COMPR (F) DISTRIBUTOR DATA
TEMP
38 CAPACITY (F) With
Std MotormasterT COIL
I or III INDOOR EVAPORATOR FACE SPORLAN DISTRIBUTOR*
NOZZLE CONNECTION
AK007 100% 90 53 COIL SECTION AREA PART NO. (in.)
AK008 100% 90 60 (sq ft)
AK012 100% 90 52 28LA008 Single 7.44 G8 ODF
58
AKS008 100% 90 60 20
AKS009 100% 90 53 28LA012 Single 9.79 E10 ODF
58

100% 90 48 28CB008 Single 7.37 J5 58 Flare


AKS012* 67% 80 52 28CB012 Single 10.35 G8 78 ODF

*Unit has one step of unloading. LEGEND


ODF Outside Diameter, Female
ODM Outside Diameter, Male
*Sporlan distributors are factory installed and require Sporlan nozzles.
NOTE: See page 61 for 40RM TXV, distributor, and nozzle data.

57
Application data 38AKS013-024
Installation LIQUID LINE DATA
Select equipment to match or to be slightly less than peak LIQUID LINE
load. This provides better humidity control, less unit cycling, MAX
UNIT ALLOW. Max Allow. Max Allow.
and less part-load operation. 38AKS LIFT Pressure Temp
(ft) Drop Loss
When selecting vapor line sizes, oil return must be evalu- (psi) (F)
ated, particularly at part-load conditions. 013 52
014 67
The indoor fan must always be operating when outdoor 016 82 7 2
unit is operating. 024 87
Ductwork should be sized according to unit size, not build- NOTE: Data above is for units operating at 45 F saturated suction and
ing load. 95 F entering air.
To minimize the possibility of air recirculation, avoid the
use of concentric supply/return grilles. LOCATION OF ONE LIQUID LINE SOLENOID
Indoor equipment should be selected at no less than VALVE SERVING 2 COIL CIRCUITS
(Solenoid Drop Control)
300 cfm/ton.

OPERATING LIMITS
Maximum Outdoor Ambient 115 F
See Minimum Outdoor-Air
Minimum Outdoor Ambient Operating Temperature
table below.
Minimum Return-Air 55 F
Temperature
Maximum Return-Air 95 F
Temperature
Normal Acceptable Saturation 25 to 55 F
Suction Temperature Range
Maximum Discharge
Temperature 295 F TXV Thermostatic Expansion Valve
Minimum Discharge 60 F
Superheat

FACE-SPLIT COIL SUCTION AND


LIQUID LINE PIPING

MINIMUM OUTDOOR-AIR OPERATING


TEMPERATURE
MINIMUM
OUTDOOR-AIR
OPERATING
UNIT NO. OF FULL LOAD TEMPERATURE
CAPACITY (F)
38AKS CYLINDERS (%)
With
Base Low-Ambient
Unit Control
6 100 35
013 4 67 45
2* 33* 55
6 100 37
014 4 67 48
2* 33* 57 20
6 100 23
016 4 67 36
2* 33* 50
4 100 15
024
2 50 20

*Requires field-installed unloader.

TXV Thermostatic Expansion Valve

58
REFRIGERANT PIPING SIZES
SUCTION LINE PIPING
LENGTH OF INTERCONNECTING PIPING (FT)
UNIT 0-15 16-25 26-50 51-75 76-100
38AKS Line Size (in. OD)
L S L S L S L S L S
013 12 118 12 118 58 138 58 138 58 158*
014 12 118 12 138 58 138 58 158* 78 158*
016 12 138 58 138 58 158 78 158 78 218*
024 58 158 58 158 78 158 78 218 78 218

LEGEND
L Liquid
S Suction

Close-coupled.
*Requires a double suction riser if 2 unloaders are used and the LEGEND
evaporator is below the condensing unit. See Refrigerant Piping Sizes
Double Suction Risers table below and Suction Line Piping figure at Suction Riser Without Trap
right for more information.
Suction Riser With Trap
NOTES:
1. Pipe sizes are based on a 2 F loss for liquid lines and a 1.5 F loss Suction Line to Condensing Unit
for suction lines. Short Vertical Riser Into
2. Pipe sizes are based on an equivalent length equal to the maximum Condensing Unit:
length of interconnecting piping plus 50% for fittings. A more accu-
rate estimate may result in smaller sizes. 38AKS013 118 in. OD
38AKS014, 016 138 in. OD

REFRIGERANT PIPING SIZES


DOUBLE SUCTION RISERS
LENGTH OF INTERCONNECTING PIPING (FT)
UNIT 51-75 76-100
38AKS Line Size (in. OD)
A B C A B C
013 118 138 158
014 118 138 158 118 138 158
016 138 158 218

NOTES:
1. See Suction Line Piping figure at right for A, B, and C
dimensions.
2. No double suction risers are needed for unit size 024.

Application data 38AKS028-044


Installation
Select equipment to match or to be slightly less than peak IMPORTANT: When application is in a variable air
load. This provides better humidity control, less unit cycling, volume (VAV) system, total building load is not the
and less part-load operation. sum of the individual peak loads. If individual peak
loads are summed, the equipment tends to be over-
When selecting vapor line sizes, oil return should be evalu- sized for the load.
ated, particularly at part-load conditions.
The indoor fan must always be operating when outdoor To minimize return-air temperature extremes, use the
fan is operating. equipment room as a return-air plenum when applying VAV
Unit cycles should be limited to 3 or less per hour. systems with supply-to-return air recycle as used with
Multiple outdoor units may be used with a single indoor Carrier VVTt Control Systems.
unit; this involves multiple refrigeration circuits. Indoor equipment should be selected at no less than
300 cfm/ton.

59
Application data 38AKS028-044 (cont)
OPERATING LIMITS
SUCTION LINE PIPING
Maximum Cooling Load 115 F
Additional head pressure
Minimum Cooling Load control may be required
below 35 F outdoor
ambient.
Minimum Return-Air
Temperature 55 F
Maximum Return-Air 95 F
Temperature
Normal Acceptable Saturation 30 to 55 F
Suction Temperature Range
Maximum Discharge Temperature 295 F
Minimum Discharge Superheat 60 F

LEGEND
MINIMUM OUTDOOR-AIR OPERATING
TEMPERATURE (F) Suction Riser Without Trap

COMPR COND MIN OUTDOOR TEMP Suction Riser With Trap


UNIT CAP. TEMP
38AKS Standard Low Ambient Horizontal Suction Line
(%) (F) Unit Control to Condensing Unit
100 90 31 Short Vertical Riser
028 67 80 35 38AKS028 158 in. OD
33 70 43
38AKS034,044 218 in. OD
100 90 30
034 67 80 34 20
33 70 42
100 90 25
044 67 80 30
33 70 35

MAXIMUM LIQUID LIFT


UNIT 38AKS FT
028 76
034 67
044 76

REFRIGERANT PIPING SIZES


SINGLE SUCTION RISERS

LENGTH OF INTERCONNECTING PIPING, FT


UNIT 16-25 26-50 51-75 76-100 101-200
38AKS
L S L S L S L S L S
028 78 158 78 218* 78 218* 78 218* 78 218*
034 78 218 78 218 7 8 218 118 218 118 258*
044 78 218 78 218 118 258* 118 258* 118 258*

LEGEND * IMPORTANT: Requires a double suction riser, if evaporator is be-


L Liquid Line low condensing unit. See table below.
S Suction Line
NOTE: Liquid and suction line sizes are OD (in.)

DOUBLE SUCTION RISERS

LENGTH OF INTERCONNECTING PIPING, FT


UNIT 26-50 51-75 76-100 101-200
38AKS
A B C A B C A B C A B C
028 138 158 218 138 158 218 138 158 218 138 158 218
034 158 218 258
044 158 218 258 158 218 258 158 218 258

NOTE: A, B, and C dimensions relate to reference diagram above.

60
Application data 40RM
Operating limits The air handler fan must always be operating when the
Maximum fan speed condensing unit is operating.
40RM007-024 . . . . . . . . . . . . . . . . . . . . . . . . . . 1200 rpm Ductwork should be sized according to unit size, not
Maximum fan speed building load. For larger units with two fans, a split duct
40RM028,034 . . . . . . . . . . . . . . . . . . . . . . . . . . 1100 rpm transition is recommended at the fan outlets, but a plenum
can be used with slight reduction in external static pressure
General capability.
Select equipment to match or to be slightly less than peak
For variable air volume (VAV) systems with supply-to-
load. This provides better humidity control, less unit cycling,
return air recycling, use the equipment room as a return air
and less part-load operation. Equipment should be selected
plenum.
to perform at no less than 300 cfm/ton.

FACTORY-INSTALLED TXV, DISTRIBUTOR, AND NOZZLE DATA

UNIT TXV DISTRIBUTOR FEEDER TUBES NOZZLE


40RM Qty...Part No. Qty...Part No. PER DISTRIBUTOR Qty...Part No.
Qty...Size (in.)
007 1...XVE-5 1...1116 12...14 1...E5
008 1...SVE-8 1...1126 15...14 1...C6
012 2...XVE-4 2...1115 9...14 2...E4
014 2...XVE-5 2...1115 9...14 2...E5
016 2...XVE-8 2...1116 12...14 2...E6
024 2...XVE-10 2...1116 13...14 2...E8
028 2...EBSVE-11 2...1126 15...14 2...C10
034 2...SVE-15 2...1126 18...14 2...C12
NOTE: Hot gas bypass applications require field-supplied auxiliary side connector.

STANDARD FAN MOTOR DATA


230-1-60 MOTORS

UNIT 007 008


40RM
Speed (rpm) 1725 1725
Hp 1.3 2.4
Frame (NEMA) 56Y 56Y
Shaft Dia (in.) 58 58

LEGEND
NEMA National Electrical Manufacturers
Association

208/230-3-60 AND 460-3-60 MOTORS

UNIT 007 008 012 014 016 024 028 034


40RM
Speed (rpm) 1725 1725 1725 1725 1725 1745 1745 1745
Hp 2.4 2.4 2.4 2.9 3.7 5.0 7.5 10.0
Frame (NEMA) 56Y 56Y 56Y 56Y 56Y S184T S213T S215T
Shaft Dia (in.) 58 5 8 5 8 7 8 7 8 118 138 138

LEGEND
NEMA National Electrical Manufacturers Association

61
Application data 40RM (cont)
STANDARD FAN MOTOR DATA (cont)
575-3-60 MOTORS

UNIT 007 008 012 014 016 024 028 034


40RM
Speed (rpm) 1725 1725 1725 1725 1725 1745 1755 1755
Hp 1.0 2.0 2.0 3.0 3.0 5.0 7.5 10.0
Frame (NEMA) 56 56HZ 56HZ 56HZ 56HZ 184T S213T S215T
Shaft Dia (in.) 58 7 8 7 8 7 8 78 118 138 138

LEGEND
NEMA National Electrical Manufacturers Association

ALTERNATE FAN MOTOR DATA


230-1-60 MOTORS

UNIT 007 008


40RM
Speed (rpm) 1725 1725
Hp 2.4 2.4
Frame (NEMA) 56Y 56Y
Shaft Dia (in.) 58 5 8

LEGEND
NEMA National Electrical Manufacturers Association

208/230-3-60 AND 460-3-60 MOTORS

UNIT 007 008 012 014 016 024 028


40RM
Speed (rpm) 1725 1725 1725 1725 1745 1745 1750
Hp 2.9 2.9 3.7 3.7 5.0 7.5 10.0
Frame (NEMA) 56Y 56Y Y56Y Y56Y S184T S213T S215T
Shaft Dia (in.) 78 7 8 7 8 7 8 118 138 138

LEGEND
NEMA National Electrical Manufacturers Association

575-3-60 MOTORS

UNIT
40RM 007 008 012 014 016 024 028
Speed (rpm) 1725 1725 1725 1745 1745 1755 1750
Hp 1.0 3.0 3.0 5.0 5.0 7.5 10.0
Frame (NEMA) 56HZ 56HZ 56HZ 184T 184T S213T S215T
Shaft Dia (in.) 78 7 8 7 8 118 118 138 138

LEGEND
NEMA National Electrical Manufacturers Association

62
STANDARD DRIVE DATA
UNIT 007 008 012 014 016 024 028 034
40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter 2.4-3.4 2.8-3.8 3.4-4.4 2.8-3.8 2.8-3.8 3.7-4.7 4.3-5.3 4.3-5.3
Pulley Factory Setting 2.5 2.5 2.5 2.5 2.5 3.0 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.) 8.8 8.8 8.8 9.0 9.0 9.4 11.0 11.0
Pulley Bore (in.) 1 1 1 1716 1716 1716 11516 11516
Belt No. Section 1A 1A 1A 1A 1A 2B 2B* 2B*
Belt Pitch (in.) 40.3 41.3 42.3 42.3 42.3 41.8 (2) 42.8 (2) 42.8
(2) 43.8 (2) 43.8
FAN SPEEDS (rpm)
Factory Setting 568 647 764 632 632 771 752 752
Range 470-666 549-745 666-863 537-728 537-728 679-863 682-841 674-831
Max Allowable Speed 1200 1200 1200 1200 1200 1200 1100 1100
Change per 12 Turn of
Moveable Motor Pulley 19.6 19.6 19.7 19.1 19.1 15.3 13.1 13.1
Flange
MAX FULL TURNS FROM 5 5 5 5 5 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 10.44- 9.12- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 12.32 10.99 9.43 9.43
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

MEDIUM-STATIC DRIVE DATA

UNIT 007 008 012 014 016 024 028 034


40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter 3.4-4.4 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.3-5.3 4.3-5.3 4.3-5.3
Pulley Factory Setting 2.5 2.5 2.5 2.5 3.0 3.0 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.) 8.8 8.0 8.0 8.2 8.6 9.4 9.4 9.4
Pulley Bore (in.) 1 1 1 1716 1716 1716 11516 11516
Belt No. Section 1A 1A 1A 1A 1B 2B 2B* 2B*
Belt Pitch (in.) 42.3 40.3 40.3 41.3 41.8 41.8 (2) 38.8 (2) 38.8
(2) 39.8 (2) 39.8
FAN SPEEDS (rpm)
Factory Setting 764 841 841 820 842 881 881 881
Range 666-863 733-949 733-949 715-926 742-943 798-984 798-984 798-984
Max Allowable Speed 1200 1200 1200 1200 1200 1200 1100 1100
Change per 12 Turn of
Moveable Motor Pulley 19.7 21.6 21.6 21.1 16.7 15.3 15.3 15.3
Flange
MAX FULL TURNS FROM
CLOSED POSITION 5 5 5 5 6 6 6 6
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 10.44- 9.16- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 12.32 10.99 9.43 9.43
*Four belts shipped with unit. Use correct set of 2 belts sized according to the pulley setting.

63
Application data 40RM (cont)
HIGH-STATIC DRIVE DATA

UNIT 007 008 012 014 016 024 028 034


40RM
MOTOR DRIVE
Motor Pulley Pitch Diameter 3.4-4.4 3.4-4.4 3.4-4.4 3.7-4.7 4.3-5.3 4.3-5.3 4.3-5.3 4.3-5.3
Pulley Factory Setting 2.5 2.5 2.5 3.0 2.5 3.0 3.0 3.0
Full Turns Open
FAN DRIVE
Pulley Pitch Dia (in.) 7.0 6.0* 6.0 7.4 7.9 7.4 8.6 8.6
Pulley Bore (in.) 1 1 1 1716 1716 1716 11516 11516
Belt No. Section 1A 1A 1A 1B 1B 2B 2B 2B
Belt Pitch (in.) 41.3 37.3 37.3 39.8 39.8 36.8 37.8 37.8
FAN SPEEDS (rpm)
Factory Setting 961 1121 1121 979 1060 1118 1024 1024
Range 838-1084 978-1200* 978-1200 873-1096 950-1171 1014-1200 873-1075 873-1075
Max Allowable Speed 1200 1200 1200 1200 1200 1200
Change per 12 Turn of
Moveable Motor Pulley 24.6 28.7 28.7 19.4 30.8 19.4 16.7 16.7
Flange
MAX FULL TURNS FROM 5 5 5 6 5 6 6 6
CLOSED POSITION
SHAFTS CENTER DISTANCE 10.44- 10.44- 10.44- 10.44- 9.16- 8.16- 6.67- 6.67-
(in.) 12.32 12.32 12.32 12.32 10.99 10.02 9.43 9.43
*Values for 3-phase motor shown. For single-phase motor, pulley pitch diameter is 7 in.
and resulting fan speed range is 837-1096 rpm.
575-v unit has a center distance of 9.16-10.99.

64
Guide specifications 38AK007-012
38AKS008-012
Commercial Air-Cooled Condensing Units B. Unit Cabinet:
HVAC Guide Specifications 1. Unit cabinet shall be constructed of galvanized steel,
bonderized and coated with a prepainted baked
Size Range: 6 to 10 Tons, Nominal
enamel finish.
Carrier Model Numbers: 38AK, Sizes 007-012
38AKS, Sizes 008-012 2. A heavy-gage roll-formed perimeter base rail with
forklift slots and lifting holes shall be provided to
Part 1 General facilitate rigging.
1.01 SYSTEM DESCRIPTION C. Fans:
1. Condenser fans shall be direct driven, propeller-
Outdoor-mounted, air-cooled condensing unit suit- type, discharging air vertically upward.
able for on-the-ground or rooftop installation. Unit
shall consist of a reciprocating air-conditioning com- 2. Fan blades shall be balanced.
pressor assembly, an air-cooled coil, propeller-type 3. Condenser fan discharge openings shall be equipped
condenser fan, and a control box. Unit shall discharge with PVC coated steel wire safety guards.
supply air upward as shown on contract drawings. 4. Condenser fan and motor shaft shall be corrosion
Unit shall be used in a refrigeration circuit matched resistant.
with a packaged air-handling unit.
D. Compressor:
1.02 QUALITY ASSURANCE 1. Compressor shall be of the hermetic reciprocat-
A. Unit shall be rated in accordance with ARI Standard ing type (AK) or semi-hermetic reciprocating type
210/240-89 and 270-84. (AKS).
B. Unit construction shall comply with ANSI/ASHRAE 2. Compressor shall be mounted on vibration
15 safety code latest revision and comply with NEC. isolators.
C. Unit shall be constructed in accordance with UL 1995 3. Compressors shall include overload protection.
standard and shall carry the UL label. Unit shall have E. Condenser Coil:
CSA approval. 1. Condenser coil shall be air-cooled and circuited for
D. Unit cabinet shall be capable of withstanding integral subcooler.
500-hour salt spray exposure per ASTM B117 (scribed 2. Coil shall be constructed of aluminum fins (cop-
specimen). per fins optional) mechanically bonded to inter-
E. Air-cooled condenser coils for semi-hermetic com- nally grooved seamless copper tubes which are then
pressor units (38AKS) shall be leak tested at 150 psig cleaned, dehydrated, and sealed.
and pressure tested at 480 psig. Air-cooled condenser F. Refrigeration Components:
coils for hermetic compressor units (38AK) shall Refrigeration circuit components shall include liquid
be leak tested at 200 psig, and pressure tested at line service valve, suction line service valve, liquid fil-
428 psig. ter drier, a full charge of compressor oil, and a hold-
F. Unit shall be manufactured in a facility registered to ing charge of refrigerant. Unit 38AK012 shall include
ISO 9001 manufacturing quality standard. an accumulator. Units with semi-hermetic compres-
1.03 DELIVERY, STORAGE, AND HANDLING sors (38AKS) shall have oil-level sight glass and crank-
case heater.
Unit shall be shipped as single package only, and shall
be stored and handled according to unit manufac- G. Controls and Safeties:
turers recommendations. 1. Minimum control functions shall include:
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING a. Control wire terminal blocks.
ENGINEER.) b. Compressor lockout on auto-reset safety un-
til reset from thermostat.
Part 2 Products 2. Minimum safety devices which are equipped with
2.01 EQUIPMENT automatic reset (after resetting first at thermostat),
A. General: shall include:
Factory-assembled, single piece, air-cooled condens- a. High discharge pressure cutout.
ing unit. Contained within the unit enclosure shall be b. Loss-of-charge cutout.
all factory wiring, piping, controls, compressor, hold-
ing charge (R-22), and special features required prior
to field start-up.

65
Guide specifications 38AK007-012
38AKS008-012 (cont)
H. Operating Characteristics: c. Post-Coated Aluminum-Fin Coils:
1. The capacity of the condensing unit shall meet or Shall have a durable organic coating uniformly
exceed Btuh at a suction temperature of F. applied over all coil surfaces. Coating shall
The power consumption at full load shall not be deep brown color applied by a dip and
exceed kW. bake process to ensure complete encapsula-
2. The combination of the condensing unit and the tion of all coil surfaces. Coated coil shall with-
evaporator or fan coil unit shall have a total net stand 1,000-hour salt spray test in accordance
cooling capacity of Btuh or greater at con- with ASTM B117. Coil construction shall be
ditions of cfm entering-air temperature at aluminum fins mechanically bonded to cop-
the evaporator at F wet bulb and F per tubes.
dry bulb, and air entering the condensing unit at d. Post-Coated Copper-Fin Coils:
F. Shall have a durable organic coating uniformly
3. The system shall have an EER of Btuh/ applied over all coil surfaces. Coating shall
Watt or greater at standard ARI conditions. be deep brown color applied by a dip and
I. Electrical Requirements: bake process to ensure complete encapsula-
tion of all coil surfaces. Coated coil shall with-
1. Nominal unit electrical characteristics shall be stand 1,000-hour salt spray test in accordance
v, 3-ph, 60 Hz. The unit shall be capable with ASTM B117. Coil construction shall be
of satisfactory operation within voltage limits of copper fins mechanically bonded to copper
v to v.
tubes.
2. Unit electrical power shall be single-point
4. Thermostat Controls:
connection.
a. Debonair programmable multi-stage thermo-
3. Unit control circuit shall contain a 24-v trans-
stat with 7-day clock, holiday scheduling, large
former for unit control.
Thermoglow display, remote sensor capa-
J. Special Features: bility, and Title 24 compliance.
1. Low-Ambient Temperature Control Accessory: b. TEMP System programmable communi-
Low-ambient control shall regulate speed of cating multi-stage thermostat with fan
condenser-fan motor in response to the saturated switch, timeclock, LCD display, F/C capa-
condensing temperature of the unit. The control bility, and CCN (Carrier Comfort Network)
shall maintain correct condensing pressure at out- compatibility.
door temperatures down to 20 F (motor change c. Commercial Electronic Thermostat with 7-day
required). timeclock, auto-changeover, multi-stage ca-
2. Gage Panel Package: pability, and large LCD temperature display.
Gage panel package shall include a suction and d. Non-programmable thermostat with fan switch
discharge pressure gage. subbase.
3. Optional Condenser Coil Materials: 5. Hail Guard Package:
a. Pre-Coated Aluminum-Fin Coils: Hail guard package shall protect coils against dam-
Shall have a durable epoxy-phenolic coating age from hail and other flying debris.
to provide protection in mildly corrosive coastal 6. Winter Start Package:
environments. Coating shall be applied to the Package shall provide a timed bypass of low-
aluminum fin stock prior to the fin stamping pressure switch on start-up at low-ambient
process to create an inert barrier between the temperatures.
aluminum fin and copper tube. Epoxy-phenolic
7. Condenser Coil Grille:
barrier shall minimize galvanic action between
dissimilar metals. Grille shall add decorative appearance to unit and
protect condenser coil after installation.
b. Copper-Fin Coils:
8. Electric Solenoid Unloader:
Shall be constructed of copper fins mechan-
ically bonded to copper tubes. All copper Electric unloader valve piston, coil, and hardware
construction shall provide protection in mod- shall be supplied to convert the pressure-operated
erate coastal applications. compressor unloader to electric unloading
(38AKS012 only).

66
Guide specifications 38AKS013-024
Commercial Air-Cooled C. Fans:
Condensing Units 1. Condenser fans shall be direct-drive propeller type,
HVAC Guide Specifications Section 15675 discharging air vertically upward.
Size Range: 10 to 20 Tons, Nominal 2. Condenser fan motor no. 1 shall be ball bear-
Carrier Model Number: 38AKS, Sizes 013-024 ing type compatible with accessory low-ambient
control.
Part 1 General
3. Shafts shall have inherent corrosion resistance.
1.01 SYSTEM DESCRIPTION
4. Fan blades shall be statically and dynamically
Outdoor-mounted, air-cooled condensing unit suit- balanced.
able for on-the-ground or rooftop installation. Unit
shall consist of a semi-hermetic reciprocating com- 5. Condenser fan openings shall be equipped with
pressor, an air-cooled coil, propeller-type condenser PVC-coated steel wire safety guards.
fans, and a control box. Unit shall discharge supply D. Compressor:
air upward as shown on contract drawings. Unit shall 1. Compressor shall be serviceable, reciprocating,
be used in a refrigeration circuit to match a packaged semi-hermetic type.
fan coil unit.
2. Compressor shall be equipped with an automati-
1.02 QUALITY ASSURANCE cally reversible oil pump, operating oil charge, suc-
A. Unit shall be rated in accordance with ARI Standard tion and discharge shutoff valves, and an insert-
360, latest edition, and shall be certified and listed in type, factory-sized crankcase heater to control oil
the latest ARI directory. dilution.
B. Unit shall be manufactured in a facility registered to 3. Compressor shall be mounted on spring vibration
ISO 9002 manufacturing quality standard. isolators with an isolation efficiency of no less than
C. Unit construction shall comply with latest edition of 95%.
ANSI/ASHRAE and with NEC. 4. Compressor speed shall not exceed 1750 rpm.
D. Unit shall be constructed in accordance with UL stand- 5. Compressor shall unload using suction cutoff un-
ards and shall carry the UL label. Unit shall have CSA loading (electrical solenoid unloading shall be avail-
approval. able as an accessory).
E. Unit cabinet shall be capable of withstanding E. Condenser Coil:
500-hour salt spray exposure per ASTM B117 (scribed 1. Condenser coil shall be air cooled, circuited for
specimen) integral subcooler.
F. Air-cooled condenser coils shall be leak tested at 2. Coil shall be constructed of aluminum fins me-
150 psig and pressure tested at 480 psig. chanically bonded to copper tubes which are then
1.03 DELIVERY, STORAGE, AND HANDLING cleaned, dehydrated, and sealed. Copper fins shall
Unit shall be shipped as a single package only, and be available as an option.
shall be stored and handled per manufacturers F. Refrigeration Components:
recommendations. Refrigeration circuit components shall include hot gas
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING muffler, high-side pressure relief device, liquid line shut-
ENGINEER.) off valve, suction and discharge shutoff valves, hold-
ing charge of refrigerant R-22, and compressor oil.
Part 2 Products
2.01 EQUIPMENT G. Controls and Safeties:
A. General: 1. Minimum control functions shall include:
Factory assembled, single piece, air-cooled condens- a. Power and control terminal blocks.
ing unit. Contained within the unit enclosure shall be b. Five-minute Time Guardt protection to pre-
all factory wiring, piping, controls, compressor, hold- vent compressor short-cycling.
ing charge (R-22), and special features required prior c. Capacity control on the compressor shall be
to field start-up. by suction cutoff unloader in response to com-
B. Unit Cabinet: pressor suction pressure. Electric solenoid un-
Unit cabinet shall be constructed of G-90 galvanized loading shall be available as an accessory.
steel, bonderized and coated with a prepainted, baked d. Head pressure control by fan cycling. One
enamel finish. condenser fan shall be cycled by discharge
pressure to maintain proper head pressure.

67
Guide specifications 38AKS013-024 (cont)
2. Minimum safety devices shall include: 5. Gage Panel Package:
Automatic reset (after resetting first at Gage panel package shall include a suction and
thermostat) discharge pressure gage.
a. High discharge-pressure cutout. 6. Optional Condenser Coil Materials:
b. Low suction pressure cutout. a. Pre-Coated Aluminum-Fin Coils:
c. Condenser fan motors to be protected against Shall have a durable epoxy-phenolic coating
overload condition by internal overloads. to provide protection in mildly corrosive coastal
Manual reset at the unit environments. Coating shall be applied to the
aluminum fin stock prior to the fin stamping
Electrical overload protection through the use of process to create an inert barrier between the
definite-purpose contactors and calibrated, ambi- aluminum fin and copper tube. Epoxy-phenolic
ent compensated, magnetic trip circuit breakers. barrier shall minimize galvanic action between
Circuit breakers shall open all 3 phases in the event dissimilar metals.
of an overload in any one of the phases or a single-
phase condition. b. Copper-Fin Coils:
H. Operating Characteristics: Shall be constructed of copper fins mechan-
ically bonded to copper tubes. All copper
1. The capacity of the condensing unit shall meet or construction shall provide protection in mod-
exceed Btuh at a suction temperature of erate coastal applications.
F. The power consumption at full load shall
not exceed kW. c. Post-Coated Aluminum-Fin Coils:
2. The combination of the condensing unit and the Shall have a durable organic coating uniformly
evaporator or fan coil unit shall have a total net applied over all coil surfaces. Coating shall
cooling capacity of Btuh or greater at con- be deep brown color applied by a dip and
ditions of cfm entering-air temperature at bake process to ensure complete encapsula-
the evaporator at F wet bulb and tion of all coil surfaces. Coated coil shall with-
F dry bulb, and air entering the condens- stand 1,000-hour salt spray test in accordance
ing unit at F. with ASTM B117. Coil construction shall be
aluminum fins mechanically bonded to cop-
3. The system shall have an EER of Btuh/ per tubes.
Watt or greater at standard ARI conditions.
d. Post-Coated Copper-Fin Coils:
I. Electrical Requirements:
Shall have a durable organic coating uniformly
1. Nominal unit electrical characteristics shall be applied over all coil surfaces. Coating shall
v, 3-ph, 60 Hz. The unit shall be capable be deep brown color applied by a dip and
of satisfactory operation within voltage limits of bake process to ensure complete encapsula-
v to v.
tion of all coil surfaces. Coated coil shall with-
2. Unit electrical power shall be single point stand 1,000-hour salt spray test in accordance
connection. with ASTM B117. Coil construction shall be
3. Unit control circuit shall contain a 24-v trans- copper fins mechanically bonded to copper
former for unit control, with capacity to operate tubes.
an indoor fan interlock. 7. Thermostat Controls:
J. Special Features: a. Debonair programmable multi-stage thermo-
1. Low-Ambient Control: stat with 7-day clock, holiday scheduling, large
Control shall regulate fan motor speed in response Thermoglow display, remote sensor capa-
to the saturated condensing temperature of the unit. bility, and Title 24 compliance.
The control shall allow the unit to operate down b. TEMP System programmable communi-
to an ambient temperature of 20 F. cating multi-stage thermostat with fan
2. Electric Solenoid Unloader: switch, timeclock, LCD display, F/C capa-
bility, and CCN (Carrier Comfort Network)
Unloader valve piston, coil, and hardware shall be
compatibility.
supplied to convert the pressure-operated com-
pressor unloader to electric unloading. c. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage ca-
3. Winter Start:
pability, and large LCD temperature display.
A winter start control shall be provided to prevent
nuisance tripouts at low ambient temperatures. d. Non-programmable thermostat with fan switch
subbase.
4. Condenser Coil Grille Package:
Grilles shall protect the condenser coils after unit
installation.

68
Guide specifications 38AKS028-044
Commercial Air-Cooled C. Fans:
Condensing Units 1. Condenser fans shall be direct-drive propeller type,
HVAC Guide Specifications Section 15675 discharging air vertically upward.
Size Range: 25 to 40 Tons, Nominal 2. Condenser fan motors shall be totally enclosed,
Carrier Model Number: 38AKS, Sizes 028-044 3-phase type with class B insulation and perma-
nently lubricated bearings.
Part 1 General
3. Shafts shall have inherent corrosion resistance.
1.01 SYSTEM DESCRIPTION
4. Fan blades shall be statically and dynamically
Outdoor-mounted, air-cooled condensing unit suit- balanced.
able for on-the-ground or rooftop installation. Unit
shall consist of a semi-hermetic reciprocating com- 5. Condenser fan openings shall be equipped with
pressor, an air-cooled coil, propeller-type condenser PVC-coated steel wire safety guards.
fans, and a control box. Unit shall discharge supply D. Compressor:
air upward as shown on contract drawings. Unit shall 1. Compressor shall be serviceable, reciprocating,
be used in a refrigeration circuit to match a packaged semi-hermetic type.
fan coil unit.
2. Compressor shall be equipped with an automati-
1.02 QUALITY ASSURANCE cally reversible oil pump, operating oil charge, suc-
A. Unit shall be rated in accordance with ARI Standard tion and discharge shutoff valves, and an insert-
365, latest edition and shall be certified and listed in type, factory-sized crankcase heater to control oil
the latest ARI directory. dilution.
B. Unit shall be manufactured in a facility registered to 3. Compressor shall be mounted on spring vibration
the ISO 9002 manufacturing quality standard. isolators with an isolation efficiency of no less than
C. Unit construction shall comply with latest edition of 95%.
ANSI/ASHRAE and with NEC. 4. Compressor speed shall not exceed 1750 rpm.
D. Unit shall be constructed in accordance with UL stand- 5. Compressor shall unload using suction cutoff un-
ards and shall carry the UL label of approval. Unit loading (electrical solenoid unloading shall be avail-
shall have CSA approval. able as an accessory).
E. Unit cabinet shall be capable of withstanding E. Condenser Coil:
500-hour salt spray exposure per ASTM B117 (scribed 1. Condenser coil shall be air cooled, circuited for
specimen). integral subcooler.
F. Air-cooled condenser coils shall be leak tested at 2. Coil shall be constructed of aluminum fins me-
150 psig and pressure tested at 480 psig. chanically bonded to internally grooved, seamless
1.03 DELIVERY, STORAGE AND HANDLING copper tubes which are then cleaned, dehydrated,
Unit shall be shipped as single package only, and shall and sealed.
be stored and handled per unit manufacturers 3. Coil shall be protected by a sheet metal casing to
recommendations. eliminate the need for wind baffles for low ambi-
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING ent temperature operation.
ENGINEER.) 4. Coil shall be protected to avoid damage due to the
Part 2 Products elements and vandalism.
2.01 EQUIPMENT F. Refrigeration Components:
A. General: Refrigeration circuit components shall include hot gas
muffler, high-side pressure relief device, liquid line shut-
Factory assembled, single piece, air-cooled condens- off valve, suction and discharge shutoff valves, hold-
ing unit. Contained within the unit enclosure shall be ing charge of refrigerant R-22, and compressor oil.
all factory wiring, piping, controls, compressor, hold-
ing charge (R-22), and special features required prior G. Controls and Safeties:
to field start-up. 1. Minimum control functions shall include:
B. Unit Cabinet: a. Power and control terminal blocks.
1. Unit cabinet shall be constructed of galvanized steel, b. Five-minute anti-short-cycling timer to pre-
bonderized and coated with a prepainted, baked vent compressor short-cycling.
enamel finish. c. Lockout on auto-reset safety until reset from
2. End unit access panel shall be hinged for compres- thermostat.
sor and control box service access.
3. Lifting holes shall be provided to facilitate rigging.

69
Guide specifications 38AKS028-044 (cont)
d. Capacity control on the compressor shall be J. Special Features:
by suction cutoff unloaders in response to 1. Low-Ambient Control:
compressor suction pressure. Electric sole- Control shall regulate fan motor speed in response
noid unloading shall be available as an to the saturated condensing temperature of the
accessory. unit. The control shall be capable of maintaining
e. A 115-v solenoid shall be provided for sole- a condensing temperature of 100 F 10 F with
noid drop control. outdoor temperatures at 20 F (motor change
f. Head pressure control to 35 F by fan cycling. required).
One condenser fan shall be cycled by dis- 2. Electric Solenoid Unloader:
charge pressure to maintain proper head Unloader valve piston, coil, and hardware shall
pressure. be supplied to convert any pressure-operated
g. Winter start control to prevent nuisance trip- compressor unloader to 115-v electric unloading.
outs at low ambient temperatures. Accessory ModuPanel control box or field-supplied
2. Minimum safety devices shall include: step controller shall be provided for electrical
unloading.
Automatic reset (after resetting first at control
circuit power supply) 3. Hot-Gas Bypass:
a. High discharge-pressure cutout. A hot-gas bypass valve and a 115-v pilot line
solenoid valve shall be provided for low-load op-
b. Low suction-pressure cutout. eration of the refrigeration system.
c. Condenser fan motors to be protected against 4. Part-Winding Start:
overload or single-phase condition by inter-
nal overloads. Part-winding start shall be provided to reduce in-
rush current and locked rotor amps on start-up.
Manual reset at the unit
5. Gage Panel:
a. Low oil-pressure cutout.
A gage panel package shall be provided which in-
b. Compressor electrical overload protection cludes a suction and discharge pressure gage for
through the use of definite-purpose contac- the refrigerant circuit.
tors and calibrated, ambient-compensated,
6. ModuPanel Control Box:
magnetic-trip circuit breakers. Circuit break-
ers shall open all 3 phases in the event of an Control box shall be provided to allow system to
overload in any one of the phases or a single- operate as a VAV system.
phase condition. 7. Optional Condenser Coil Materials:
H. Operating Characteristics: a. Pre-Coated Aluminum-Fin Coils:
1. The capacity of the condensing unit shall meet or Shall have a durable epoxy-phenolic coating
exceed Btuh at a suction temperature of to provide protection in mildly corrosive coastal
F. The power consumption at full load shall environments. Coating shall be applied to the
not exceed kW. aluminum fin stock prior to the fin stamping
2. The combination of the condensing unit and the process to create an inert barrier between the
evaporator or fan coil unit shall have a total net aluminum fin and copper tube. Epoxy-phenolic
cooling capacity of Btuh or greater at barrier shall minimize galvanic action between
conditions of: cfm entering-air temper- dissimilar metals.
ature at the evaporator at F wet bulb and b. Copper-Fin Coils:
F dry bulb, and air entering the condens- Shall be constructed of copper fins mechan-
ing unit at F. ically bonded to copper tubes. All copper
3. The system shall have an EER of Btuh/ construction shall provide protection in mod-
Watt or greater at standard ARI conditions. erate coastal applications.
I. Electrical Requirements: c. Post-Coated Aluminum-Fin Coils:
1. Nominal unit electrical characteristics shall be Shall have a durable organic coating uniformly
v, 3-ph, 60 Hz. The unit shall be capable applied over all coil surfaces. Coating shall
of satisfactory operation within voltage limits of be deep brown color applied by a dip and
v to v. bake process to ensure complete encapsula-
2. Unit electrical power shall be single point tion of all coil surfaces. Coated coil shall with-
connection. stand 1,000-hour salt spray test in accordance
with ASTM B117. Coil construction shall be
3. Unit control circuit shall contain a 24-v trans-
aluminum fins mechanically bonded to cop-
former for unit control, with capacity to operate
per tubes.
an indoor fan interlock.

70
d. Post-Coated Copper-Fin Coils: 8. Thermostat Controls:
Shall have a durable organic coating uniformly a. Debonair programmable multi-stage thermo-
applied over all coil surfaces. Coating shall stat with 7-day clock, holiday scheduling, large
be deep brown color applied by a dip and Thermoglow display, remote sensor capa-
bake process to ensure complete encapsula- bility, and Title 24 compliance.
tion of all coil surfaces. Coated coil shall with- b. TEMP System programmable communi-
stand 1,000-hour salt spray test in accordance cating multi-stage thermostat with fan
with ASTM B117. Coil construction shall be switch, timeclock, LCD display, F/C capa-
copper fins mechanically bonded to copper bility, and CCN (Carrier Comfort Network)
tubes. compatibility.
c. Commercial Electronic Thermostat with 7-day
timeclock, auto-changeover, multi-stage ca-
pability, and large LCD temperature display.
d. Non-programmable thermostat with fan switch
subbase.

71
Guide specifications 40RM
Commercial Packaged Air-Handling Unit A. Base Unit:
1. Cabinet shall be constructed of mill-galvanized steel.
HVAC Guide Specifications
2. Cabinet panels shall be fully insulated with 12-in.
Size Range: 2,400 to 12,000 Cfm, Nominal Airflow fire-retardant material. Insulation shall contain an
6 to 30 Tons, Nominal Cooling EPA-registered immobilized antimicrobial agent to
Carrier Model Number: 40RM (Direct-Expansion Coil) effectively resist the growth of bacteria and fungi
Part 1 General as proven by tests in accordance with ASTM stand-
ards G21 and 22.
1.01 SYSTEM DESCRIPTION
3. Unit shall contain PVC condensate drain pans for
A. Indoor, packaged air-handling unit for use in commer- both vertical and horizontal applications. Drain
cial split systems. Unit shall have a multipoise design pans shall have connections on right and left sides
and shall be capable of horizontal or vertical installa- of unit to facilitate field connection. Drain pans
tion on a floor or in a ceiling, with or without duct- shall have the ability to be sloped toward the right
work. (Only vertical units are to be applied without or left side of the unit to prevent standing water
ductwork.) from accumulating in pans.
B. Unit shall have a direct-expansion coil and shall be 4. Unit shall have factory-supplied 2-in. throwaway-
used in a refrigerant circuit with a matching air-cooled type filters installed upstream from the cooling coil.
condensing unit. Filter access shall be from either the right or left
1.02 QUALITY ASSURANCE side of the unit.
A. Coils shall be designed and tested in accordance with B. Coils:
ASHRAE 15 Safety Code for Mechanical Refrigera- Coils shall consist of 3 rows of 38-in. copper tubes
tion, latest edition. with sine-wave aluminum fins bonded to the tubes by
B. Unit shall be constructed in accordance with ETL and mechanical expansion. Coil tubing shall be internally
ETL, Canada standards and shall carry the ETL and rifled to maximize heat transfer. Suction and liquid
ETL, Canada labels. line connections shall be made on the same side of
C. Unit insulation and adhesive shall comply with the coil. Direct-expansion coils shall feature factory-
NFPA-90A requirements for flame spread and smoke installed thermostatic expansion valves (TXVs) for
generation. Insulation shall contain an EPA-registered refrigerant control. The TXVs shall be capable of
immobilized antimicrobial agent to effectively resist external adjustment.
the growth of bacteria and fungi as proven by tests in C. Operating Characteristics:
accordance with ASTM standards G21 and 22. Unit shall be capable of providing cfm airflow
D. Unit shall be manufactured in a facility registered to at an external static pressure of in. wg.
the ISO 9002 manufacturing quality standard. D. Motor:
E. Direct-expansion coils shall be burst tested at 435 psi Fan motor of the size and electrical characteristics
and leak tested at 150 psi. specified on the equipment schedule shall be factory
1.03 DELIVERY AND STORAGE supplied and installed.
Units shall be stored and handled per manufacturers E. Factory-Installed Options:
recommendations. 1. Alternate Motor and Drive:
1.04 WARRANTY (FOR INCLUSION BY SPECIFYING An alternate motor and medium- or high-static drive
ENGINEER) shall be available to meet the airflow and external
static pressure requirements specified on the equip-
Part 2 Products ment schedule.
2.01 EQUIPMENT 2. External Paint:
Indoor mounted, draw-thru, packaged air-handling unit Where conditions require, units shall be painted
that can be used with or without ductwork in a sus- with an American Sterling Gray finish.
pended horizontal configuration or free-standing ver-
tical configuration. Unit shall consist of forward-curved F. Field-Installed Accessories:
belt-driven centrifugal fan(s), motor and drive assem- 1. Hot Water Coil:
bly, prewired fan motor contactor, factory-installed Coil shall be 2-row, U-bend coil with copper tubes
refrigerant metering devices, cooling coil, 2-in. dis- and aluminum plate fins bonded to the tubes by
posable air filters, and condensate drain pans for ver- mechanical expansion. Coil shall be mounted in
tical or horizontal configurations. a galvanized steel housing that shall be fastened
to the units fan deck for blow-thru heating op-
eration. Coil shall have maximum working pres-
sure of 150 psig.

72
2. Steam Distributing Coil: 7. Economizer:
Coil shall consist of one row of copper tubes with Economizer for ventilation or free cooling shall
aluminum plate fins, and shall have inner steam be factory provided for field installation. For free
distributing tubes. Coil shall be mounted in a gal- cooling applications, economizer shall be compat-
vanized steel housing and shall be fastened to the ible with factory-supplied thermostat; economizer
units fan deck for blow-thru heating operation. dampers shall open when outdoor air enthalpy is
Coil shall have maximum working pressure of suitable for free cooling. Economizer shall be com-
175 psig at 400 F. patible with factory-supplied CO2 sensor; econo-
3. Electric Heaters: mizer dampers shall open when indoor CO2 level
rises above predetermined set point.
Heaters for nominal 240, 480, or 575-volt, 3-phase,
60 Hz power supply shall be factory-supplied for 8. Thermostat Controls:
field installation as shown on the equipment draw- a. Debonair programmable multi-stage thermo-
ings. Electric heat assembly shall be ETL agency stat with 7-day clock, holiday scheduling, large
approved, and shall have single-point power wir- Thermoglow display, remote sensor capa-
ing. Heater assembly shall include contactors with bility, and Title 24 compliance.
24-v coils, power wiring, 24-v control wiring ter- b. TEMP System programmable communi-
minal blocks, and a hinged access panel. cating multi-stage thermostat with fan
4. Air Discharge Plenum: switch, timeclock, LCD display, F/C capa-
Plenum shall be factory supplied to provide free- bility, and CCN (Carrier Comfort Network)
blow air distribution for vertical floor-mounted units. compatibility.
A grille with moveable vanes for horizontal or ver- c. Commercial Electronic Thermostat with 7-day
tical airflow adjustment shall be included. Plenum timeclock, auto-changeover, multi-stage ca-
housing shall be field-installed on the units fan deck pability, and large LCD temperature display.
for blow-thru air distribution. d. Non-programmable thermostat with fan switch
5. Return-Air Grille: subbase.
Grille shall be factory supplied for field installation 9. Overhead Suspension Package:
on the units return air opening. Package shall include necessary brackets to sup-
6. Unit Subbase: port units in a horizontal ceiling installation.
Subbase assembly shall be factory supplied for field 10. CO2 Sensor:
installation. Subbase shall elevate floor-mounted Sensor shall provide the ability to signal the econo-
vertical units to provide access for correct conden- mizer to open when the space CO2 level exceeds
sate drain connection. the predetermined set point.

73
Guide specifications 28CB,LA
Commercial Direct Expansion Coils Cooling coil shall have a face area of not less than
sq ft and be constructed with aluminum plate fins
HVAC Guide Specifications mechanically bonded to nonferrous tubing with all joints
Size Range: 3000-4000 Cfm, Nominal Airflow brazed. Coil shall be rows deep with a nominal fin
712 and 10 Tons, Nominal Cooling spacing of fins per inch.
Carrier Model Numbers: 28CB, 28LA The casing of encased coils shall be insulated and finished
Furnish and install a direct-expansion cooling coil with baked enamel or equivalent corrosion-resistant sur-
in the location and manner shown on the plan. face. The casing material shall be cold-rolled steel (28LA)
Total cooling capacity of the coil shall be Btuh or galvanized steel (28CB). The 28CB coil casing shall al-
or greater and sensible capacity shall be Btuh or low space for attaching field-supplied thermostatic expan-
greater with cfm of air entering coil at F sion valve.
wet-bulb and F dry-bulb. Coil refrigerant tempera- Maximum unit dimensions shall be width of in.,
ture shall be F. depth of in., and overall height of inches.

74
Carrier Corporation Syracuse, New York 13221 10-98
Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.
Book 1 2 4 Page 76 Catalog No. 523-844 Printed in U.S.A. PC 111 Form 38A-3PD
Tab 3a 1a 2a Replaces: 38A-2PD