Air Cooled Chillers: Direct Expansion

Download as pdf or txt
Download as pdf or txt
You are on page 1of 27

Air cooled chillers

LX R134a
Cooling capacity : 370 to 850 kW

Screw compressors
CIAT direct expansion
shell and tubes evaporator
Hydraulic pack versions
“Plug and Cool”
H.P.S. equipment

PROPELLER
(High Power System)

FANS
N TA L LY F R
NME IEN
RO
VI D

EN

LY
HFC R134a

PR

T
EN
TE

O
CT EM
IO N NN
cooling Hydraulic D E L'E N VI RO

pack

USE
The new generation of POWERCIAT water chillers LX Units in accordance with EN 60-204 - EN 378-2 regulations
offers an optimal solution to all the refrigeration applications and directives :
encountered in the air conditioning or industrial process. - Machines (98/37 CEE) modified
- CEM (89/336 CEE) modified 92/31 CEE - 93/68 CEE
This range is designed with the latest generation of
- Low voltage (73/23 CEE) modified 92/31 CEE - 93/68 CEE
components : accessible hermetic twin screw compressors,
- DESP 97/23 CEE
modulating capacity control, communicating control and
management by Xtra Connect microprocessor, components ➝ LX - LXH - LXC
optimized for the ecological refrigerant HFC R134a. group 3 sizes 1800X (HPS) to 2800X (HPS)
group 4 sizes 3050X HPS to 3750X HPS
This range is also proposed with an integral hydraulic
equipment : POWERCIAT LXH. This one includes all the
elements required for a right operation of the unit :
buffer tank, expansion vessel, single or twin pump, air vent ,
pressure relief valves , shut off valves , manometers...
A range with compact hydraulic equipment (without buffer
tank) is also available : POWERCIAT LXC.

RANGE
POWERCIAT LX - LXH - LXC ■ CONFIGURATION

a - STANDARD Version
2 compressors, 2 refrigerant circuits : Ventilation 905 rpm
8 models : 1800X, 1800X HPS, 2150X, 2150X HPS, 2500X, b - LOW NOISE Version
2500X HPS, 2800X, 2800X HPS. Ventilation 715 rpm + compressors sound insulation
3 compressors, 3 refrigerant circuits c - XTRA LOW NOISE Version
3 models : 3050X HPS, 3400X HPS, 3750X HPS Specific mounting for 715 rpm fan + compressors sound
insulation

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 53


Air cooled chillers

LX R134a
DESCRIPTION
POWERCIAT LX serie ■ Electrical panel
■ Compressors ■ IP 44
■ Electrical supply 400 V - 3 ph. - 50 Hz + earth (+/- 10 %)
■ Accessible hermetic twin screw type
■ Wires numbering and electrical components referencing.
■ Optimized profile of rotors ensuring a high efficiency
■ Main safety switch with outside handle
■ Electrical motor incorporated with part winding starting
■ Transformer for control circuit
■ Motor integral electronic protection
■ Compressors motors contactors
■ Control of the phases balance and rotation direction
PROPELLER

■ Fans motors contactors


■ Integrated overpressure valve
■ Compressors motors protection by magneto-thermal circuit
FANS

■ Discharge temperature control


breakers (25 KA or 35 KA depend of sizes of compressors).
■ Lubrication under controlled pressure
■ Fans motors protection by magneto-thermal circuit
■ 3-stage integrated oil separator breakers
■ Crankcase heater ■ Main electrical ground
■ Suction filter
■ Discharge valve ■ Electronic control with microprocessor
■ Slide for modulating capacity control Xtra connect
■ Compressors fitted on antivibration mounts ensuring the following main functions :
- 2 remote switchable set points
- chilled water temperature control
■ Evaporator - Possibility of water temperature variation as a function of
■ Direct expansion shell and tube type the outside temperature (water law)
■ High performance copper tubes bundle - Low temperature ice storage control
■ Steel shell - Condensing pressure control
■ Corrosion resistant baffles - Compressors discharge temperature control
■ Thermal insulation by cellular foam with UV resistant - Compressors anti-short cycle control
polyurethane film - Control and optimisation of operating parameters
- Counting and balancing of compressors, pumps operating
times
■ Air cooled condenser - Automaticity control
■ Copper tubes coils, aluminium fins - LCD display panel, 2 lines of 20 characters allowing :
■ Direct drive propeller fans ■ parametering of the unit
■ Rotation speed : 905 or 715 rpm ■ direct reading of all informations : settings, water inlet/outlet
■ 3 phase electrical motors, IP 54 temperatures, outside temperature, HP/LP pressures, unit
operating status...
■ Faults control with memorization of the last 9 faults and

■ HPS (High Power system) operating reading when those faults occur
on models LX/LXH...HPS ■ Weekly management of the unit
■ The HPS system allows to increase cooling capacity, ■ Unit general fault display on terminals
improves the performance coefficients (EER) of your ■ Automaticity control on terminals
installation, particulary in part load, and ensures therefore an
optimal operation of POWERCIAT during all the year. ■RS 485 output for bus connection with centralized Building
Management System(MODBUS/JBUS protocol)

■ Refrigerant accessories
■ Capacity control
■ Filter dryers with rechargeable cartridges
■ Liquid sight glasses ■ Modulating capacity control :

■ Solenoid valves on liquid refrigerant lines - from 25 to 100 % (sizes 1800X (HPS) to 2800X (HPS))
■ Thermostatic expansion valves - from 17 to 100 % (sizes 3050X HPS to 3750X HPS)

■ Safety and regulation devices


■ HP/LP pressure sensors ■ Frame and casing
■ Low and high pressure safety valves
■ Frame in RAL 7035 and 7024 painted metal sheet
■ Chilled water control sensor (inlet or outlet)
■ External temperature sensor ■ Casing in RAL 7035 and 7024 lacquered metal sheet
■ Evaporator antifreeze sensor
■ Compressors discharge sensor
■ Evaporator water flow switch

54 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
POWERCIAT LXH serie
The design of POWERCIAT units LXH is identical to the OPTIONS
one of POWERCIAT LX
■ LOW NOISE version : ABS phonic insulation casing with
These units integrate the complete hydraulic equipment for
sound proof material + 715 rpm fans
standard installation :
■ XTRA LOW NOISE version : ABS sound insulation casing
■ 1 buffer thank insulated, capacity : 950 liters
with soundproof material + specific mounting for 715 rpm
■ 1 monocellular centrifugal hydraulic pump (single or twin fans
pump)
■ Compressors isolating suction valves
■ 1 expansion vessel (80 liters)
■ Evaporator antifreeze protection (LX serie)
■ 1 automatic air vent
■ Evaporator antifreeze protection + piping + hydraulic
■ 1 manual air vent equipment (LXH - LXC series)

■ 1 safety valve calibrated at 4 bars ■ Condenser coil treatment :

PROPELLER
■ A draining hole - polyurethane coated fins

FANS
■ 2 shut off valves for the pump - polual blygold coating

■ 1 set of manometers ■ Anti-vibration mounts

■ Contactors, protection devices and control for pumps ■ Evaporator flexible connection
inside the unit electrical panel.
■ Remote control box
■ Voltage free relay card

POWERCIAT LXC serie ■ Low temperature glycol water (LX unit only)
The design of POWERCIAT units LXC is identical to the one ■ Phases control relay
of POWERCIAT LX
■ Electronic expansion valve
These units integrate the a compact hydraulic equipment
■ 1 monocellular centrifugal hydraulic pump
(single or twin pump)
■ 1 expansion vessel (80 liters)
■ 1 automatic air vent
■ 1 manual air vent
■ 1 safety valve calibrated at 4 bars
■ A draining hole
■ 2 shut off valves for the pump
■ 1 set of manometers
■ Contactors, protection devices and control for pumps
inside the unit electrical panel.

POWERCIAT LXH serie

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 55


Air cooled chillers

LX R134a
VERSION WITH HYDRAULIC EQUIPMENT
LXH - LXC series ■ Hydraulic equipment LXH serie

The “all integrated” solution

The Plug and Cool solution offered by


POWERCIAT LXH - LXC
The hydraulic equipment integrates all the components
necessary for the correct operation of the installation :
PROPELLER

- 950 liters insulated buffer tank (LXH only)


- 80 liters expansion vessel
FANS

- Large choice of single or twin pumps for high head


pressure (1)
- Manometers with shut off valves
- Pressure relief valves (calibrated at 4 bars)
- Draining circuit
- Manual and automatic air vent
- Control of the assembly
- Antifreeze protection (optional)
The hydraulic equipment, whose components have been
selected in an optimal way, mounted and tested in factory,
makes the installation of units easy and economical.
The preparation/commissioning times and the space
required on site are therefore perfectly optimised.

(1) Our pumps are designed for operation on a closed water loop (low
NPSH). For other applications, consult us (open water circuit, important
intake height, etc).
LXH uniquement
Ballon

56 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
STANDARD EQUIPMENT / AVAILABLE OPTIONS

1800X 2150X 2500X 2800X


POWERCIAT 1800X 2150X 2500X 2800X
HPS HPS HPS HPS
Refrigerant R134a ● ● ● ● ● ● ● ●
2 refrigerant circuits ● ● ● ● ● ● ● ●
High Power System (H.P.S.) - ● - ● - ● - ●
Main safety switch ● ● ● ● ● ● ● ●
Standard Control circuit transformer ● ● ● ● ● ● ● ●
Wiring numbering ● ● ● ● ● ● ● ●
Condensing pressure control ● ● ● ● ● ● ● ●
RS 485 communication interface ● ● ● ● ● ● ● ●
Compressors Part Winding starting ● ● ● ● ● ● ● ●

PROPELLER
LOW NOISE version ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲

FANS
XTRA LOW NOISE version ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
Compressors isolating suction valves ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
Antifreeze protection ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
Coil treatment ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
Single pump (LXH - LXC versions) ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
Twin pump (LXH - LXC versions) ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
Options Antivibration mounts
▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
Hydraulic connectors ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
Remote control box ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
Free voltage relay card ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
Phases control relay ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
Electronic expansion valve ▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
Low temperature glycol water
▲ ▲ ▲ ▲ ▲ ▲ ▲ ▲
from 0 °C to - 8 °C (LX units only)

3050X 3400X 3750X


POWERCIAT
HPS HPS HPS
Refrigerant R134a ● ● ●
2 refrigerant circuits ● ● ●
High Power System (H.P.S.) ● ● ●
Main safety switch ● ● ●
Standard Control circuit transformer ● ● ●
Wiring numbering ● ● ●
Condensing pressure control ● ● ●
RS 485 communication interface ● ● ●
Compressors Part Winding starting ● ● ●
LOW NOISE version ▲ ▲ ▲
XTRA LOW NOISE version ▲ ▲ ▲
Compressors isolating suction valves ▲ ▲ ▲
Antifreeze protection ▲ ▲ ▲
Coil treatment ▲ ▲ ▲
Single pump (LXH - LXC versions) ▲ ▲ ▲
Twin pump (LXH - LXC versions) ▲ ▲ ▲
Options Antivibration mounts
▲ ▲ ▲
Hydraulic connectors ▲ ▲ ▲
Remote control box ▲ ▲ ▲
Free voltage relay card ▲ ▲ ▲
Phases control relay ▲ ▲ ▲
Electronic expansion valve ▲ ▲ ▲
Low temperature glycol water
▲ ▲ ▲
from 0 °C to - 8 °C (LX units only)

● Standard supply ▲ Option - Not available

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 57


Air cooled chillers

LX R134a
TECHNICAL CHARACTERISTICS
POWERCIAT LX - LXH - LXC 1800X 1800X HPS 2150X 2150X HPS 2500X 2500X HPS
Cooling capacity (1) kW 379 403 456 491 515 571
Standard version Electrical consumption (2) kW 130 131 154 162 178 193
EER 2.92 3.08 2.96 3.03 2.89 2.96
Cooling capacity (1) kW 374 402 445 486 503 569
Low noise and
Electrical consumption (2) kW 132 135 159 171 184 207
xtra low noise versions
EER 2.83 2.98 2.80 2.84 2.73 2.75
Type Twin screw
Number 2
PROPELLER

Rotation speed rpm 2900


Compressor R134a refrigerant charge kg 2 x 58 2 x 59 71 + 58 72 + 59 2 x 71 2 x 77
FANS

Modulating from 25 to 100%


Capacity control
(50 to 100% on each compressor)
Type of oil for R134a BITZER BSE 170
Oil charge for compressor liters 2 x 15 22 + 15 2 x 22
Type Direct expansion shell and tubes
Number 1
Water capacity liters 122 194
Evaporator
Hydraulic connections VICTAULIC type
Maximum pressure on water side bar 10
Maximum water flow m3/h 135 150
Fans Direct drive propeller type - 800 mm diameter
Number of fans 8
Rotation speed rpm STANDARD version 905 rpm
Air cooled Air flow m3/h 184 000 180 000 176 000
condenser Motor power kW 2,6
Rotation speed rpm LOW NOISE - XTRA LOW NOISE versions 715 rpm
Air flow m3/h 152 000 148 400 144 800
Motor power kW 1,8
Standard version Lw / Lp (3) dB(A) 98 / 66 100 / 67 101 / 68
Low noise version Lw / Lp (3) dB(A) 91 / 59 94 / 61 95 / 62
Xtra low noise version Lw / Lp (3) dB(A) 86 / 54 88 / 55 89 / 56

POWERCIAT LX - LXH - LXC 2800X 2800X HPS 3050X HPS 3400X HPS 3750X HPS
Cooling capacity (1) kW 602 649 703 777 846
Standard version Electrical consumption (2) kW 198 204 230 261 293
EER 3.04 3.18 3.06 2.98 2.89
Cooling capacity (1) kW 593 646 692 762 831
Low noise and xtra low
Electrical consumption (2) kW 203 212 238 272 308
noise version
EER 2.92 3.05 2.91 2.80 2.70
Type Twin screw
Number 2 3
Rotation speed rpm 2900
Compressor R134a refrigerant charge kg 2 x 80 2 x 81 80 + 2 x 64 2 x 77 + 58 3 x 77
Modulating from 25 to 100% Modulating from 17 to 100%
Capacity control
(50 to 100% on each compressor) (50 to 100% on each compressor)
Type of oil for R134a BITZER BSE 170
Oil charge for compressor liters 2 x 22 22 + 2 x 15 2 x 22 + 15 3 x 22
Type Direct expansion shell and tubes
Number 1
Water capacity liters 194 336
Evaporator
Hydraulic connections VICTAULIC type
Maximum pressure on water bar 10
Maximum water flow m3/h 150 240
Fans Direct drive propeller type - 800 mm diameter
Number of fans 12
Rotation speed rpm STANDARD version 905 rpm
Air cooled Air flow m3/h 276 000 272 000 268 000 264 000
condenser Motor power kW 2,6
Rotation speed rpm LOW NOISE - XTRA LOW NOISE versions 715 rpm
Air flow m3/h 228 000 224 400 220 800 217 200
Motor power kW 1,8
Standard version Lw / Lp (3) dB(A) 101 / 68 101 / 68 102 / 69
Low noise version Lw / Lp (3) dB(A) 97 / 64 96 / 63 97 / 64
Xtra low noise version Lw / Lp (3) dB(A) 91 / 58 89 / 56 90 / 57

(1) Cooling capacity for 12°C / 7°C evaporator chilled water and 35°C condenser air inlet.
(2) Compressors + fans electrical consumption
(3) Lw : Global sound power level - Lp : Global sound pressure level at 10 meters, in free field, following ISO 3744 regulation

58 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
ELECTRICAL CHARACTERISTICS
POWERCIAT LX - LXH - LXC 1800X 1800X HPS 2150X 2150X HPS 2500X 2500X HPS
COMPRESSORS (1)
324 358 392
Maximum nominal current A
(2 x 162) (196 + 162) (2 x 196)
Starting current (3) A 585 774 808
FAN MOTORS (1)
STANDARD version905 rpm
Maximum nominal current A 48
LOW NOISE - XTRA LOW NOISE versions 715 rpm
Maximum nominal current A 25.6
LX ANTIFREEZE PROTECTION (OPTION) (2)
Evaporator heating element power W 320
Maximum nominal current A 1.4

PROPELLER
LXC ANTIFREEZE PROTECTION (OPTION) (2)
Evaporator + hydraulic pipe +
W 560

FANS
expansion vessel heating element power
Maximum nominal current A 2.5
LXH ANTIFREEZE PROTECTION (OPTION)
Evaporator heating element power +
W 560
piping
Maximum nominal current A 2.5 (2)
Hydraulic module heating element power W 1500
Maximum nominal current A 2,3 (1)
CONTROL AUXILIARY CIRCUIT (2)
Maximum nominal current A 4
Transformer power VA 1600

POWERCIAT LX - LXH - LXC 2800X 2800X HPS 3050X HPS 3400X HPS 3750X HPS
COMPRESSORS (1)
428 520 554 588
Maximum nominal current A
(2 x 214) (196 + 2 x 162) (2 x 196 + 162) (3 x 196)
Starting current (3) A 879 936 970 1004
FAN MOTORS (1)
STANDARD version905 rpm
Maximum nominal current A 72
LOW NOISE - XTRA LOW NOISE versions 715 rpm
Maximum nominal current A 38,4
LX ANTIFREEZE PROTECTION (OPTION) (2)
Evaporator heating element power W 320
Maximum nominal current A 1.40
LXC ANTIFREEZE PROTECTION (OPTION) (2)
Evaporator + hydraulic pipe +
W 560
expansion vessel heating element power
Maximum nominal current A 2.5
LXH ANTIFREEZE PROTECTION (OPTION)
Evaporator heating element power +
W 500
piping
Maximum nominal current A 2,2 (2)
Hydraulic module heating element power W 1500
Maximum nominal current A 2.3 (1)
CONTROL AUXILIARY CIRCUIT (2)
Maximum nominal current A 4
Transformer power VA 1600 2000
SINGLE PUMPS (LXH - LXC ONLY) (1)
Number 102 103 104 105 106 107 108 109 110 111 112 113 114 115
Power kW 3 4 4 5,5 5,5 7,5 7,5 11 11 11 15 15 18,5 22
Maximum nominal current A 6,3 8,0 8,0 10,3 10,3 13,8 13,8 20,0 20,0 20,0 26,5 26,5 32,5 39
TWIN PUMPS (LXH - LXC ONLY) (1)
Number 202 203 204 205 206 207 208 209 210 211 212 213 214 215
Power kW 3 4 4 5,5 5,5 7,5 7,5 11 11 11 15 15 18,5 22
Maximum nominal current A 6,3 8,0 8,0 10,3 10,3 13,8 13,8 20,0 20,0 20,0 26,5 26,5 32,5 39
(1) Current for 400V / 3PH / 50HZ voltage Nominal current for cables selection = add the maximum nominal currents
(2) Current for 230V / 1PH / 50HZ voltage indicated in the above tables
(3) Starting current of the biggest compressor + maximum current of others
compressors in full load

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 59


Air cooled chillers

LX R134a
PERFORMANCES
POWERCIAT LX-LXH-LXC
STANDARD version
CONDENSER AIR INLET TEMPERATURE °C
LX
Evaporator water 25 30 35 40 45 50
LXH outlet temperature Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa
LXC °C kW kW kW kW kW kW kW kW kW kW kW kW
-8 234 98 220 105 206 112 191 121
PROPELLER

-6 254 100 239 106 224 114 208 123


-4 279 102 263 108 245 116 226 124 209 136 191 149
FANS

Glycol water
-2 301 103 284 110 267 118 249 127 229 138 208 151
0 325 105 307 112 289 120 270 129 250 141 229 154
2 352 108 333 115 314 123 294 132 272 144 250 157
1800 X 5 395 111 375 119 353 127 330 137 305 148 283 162
6 410 113 388 120 366 129 342 138 317 150 294 164
7 424 114 402 122 379 130 355 140 329 151 305 165
Pure water 8 438 115 415 123 392 132 367 142 340 153 316 167
10 472 119 447 126 422 135 395 145 365 156 342 171
12 503 122 478 129 451 138 422 148 389 160 366 175
15 553 126 525 134 496 144 465 154 432 165 404 180
-8 258 100 247 108 236 117 225 128
-6 281 101 266 109 254 118 242 130
-4 296 101 285 109 274 119 259 130 244 144 229 156
Glycol water
-2 317 102 307 111 294 121 280 132 264 147 250 158
0 340 104 328 113 315 123 300 134 284 149 269 162
2 366 106 354 115 340 125 324 137 305 151 293 170
R134a

1800 X 5 408 109 394 118 378 129 360 141 342 156 326 175
6 421 110 406 119 390 130 372 142 353 157 336 176
7 434 111 419 121 403 131 383 143 364 158 347 178
Pure water 8 448 112 433 122 416 132 396 145 376 160 356 179
10 479 115 463 125 445 135 424 148 402 163 381 182
12 507 117 492 127 472 138 451 151 427 166
15 555 122 537 131 515 143 490 155 466 171
-8 286 113 269 121 251 130 230 140
-6 311 115 293 123 273 132 252 143
-4 336 117 316 126 295 135 274 146 252 158 228 171
Glycol water
-2 363 120 342 128 321 138 298 149 275 161 249 175
0 391 122 369 131 346 141 323 152 298 165 272 179
2 423 125 401 134 377 144 350 157 326 169 299 184
2150 X 5 476 131 451 140 425 150 396 163 368 176 338 190
6 493 132 468 142 440 152 410 165 382 178 351 193
7 510 134 485 144 456 154 424 167 399 180 365 195
Pure water 8 527 136 501 145 472 156 439 169 412 183 379 197
10 567 140 538 150 508 161 475 174 443 187 410 203
12 604 144 574 154 542 165 506 177 473 192 447 204
15 665 150 630 160 596 171 561 184 523 199
-8 322 119 307 129 288 141 278 156
-6 346 121 330 131 316 144 301 159
-4 362 121 344 132 333 146 316 159 296 176
Glycol water
-2 387 122 375 134 358 147 341 163 322 180
0 418 125 402 137 384 150 365 166 346 184
2 448 127 434 140 414 153 394 170 370 188
2150 X 5 499 132 480 145 462 159 440 176 415 195
6 515 133 500 147 477 161 453 178 434 197
7 531 135 511 148 491 162 468 180 444 200
Pure water 8 549 136 532 150 508 165 484 182 458 202
10 585 140 563 154 544 169 514 185 487 205
12 621 143 598 158 576 172 548 189 510 209
15 681 150 652 162 627 178 599 197
Pf : Cooling capacity calculated with : Glycol water is necessary
- water inlet/outlet differential as per curves page 16 Low temperature option necessary (valid only on LX versions).
- 0.00005 m2 °C/W fouling factor EUROVENT conditions
Pa : Compressors + fans absorbed power

60 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
PERFORMANCES
POWERCIAT LX-LXH-LXC
STANDARD version
CONDENSER AIR INLET TEMPERATURE °C
LX
Evaporator water 25 30 35 40 45 50
LXH outlet temperature Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa
LXC °C kW kW kW kW kW kW kW kW kW kW kW kW
-8 326 129 305 138 285 145 263 160
-6 353 132 332 141 310 149 286 164
-4 382 134 359 144 334 154 311 167 285 180 258 195
Glycol water
-2 412 137 388 147 361 159 338 171 311 185 282 200
0 444 140 417 150 389 162 366 176 337 189 306 204
2 481 144 455 154 426 166 394 181 369 195 337 210

PROPELLER
2500 X 5 542 150 512 161 482 174 448 189 419 203 383 219
6 561 152 531 163 499 176 463 192 434 206 398 222

FANS
7 581 154 550 165 515 178 480 194 451 209 414 225
Pure water 8 601 156 569 168 536 181 496 197 467 211 429 228
10 646 161 612 173 577 186 535 202 502 217 474 236
12 689 166 653 178 616 191 576 206 537 223 490 244
15 757 174 718 186 678 199 635 214 593 232
-8 375 138 359 152 343 166 323 183
-6 401 139 383 154 368 170 348 186
-4 422 140 411 154 387 169 369 188 344 209
Glycol water
-2 446 142 438 157 418 174 394 192 377 215
0 488 146 464 160 450 178 424 197 407 220
2 521 148 500 164 480 182 457 203 431 225
R134a

2500 X 5 565 152 546 166 535 189 510 210 482 234
6 588 155 571 172 553 191 525 212 500 238
7 619 158 597 175 571 193 544 216 515 241
Pure water 8 638 160 616 178 589 196 563 219 536 246
10 680 164 657 181 630 201 599 224 571 251
12 722 169 693 188 669 206 637 229 605 253
15 787 176 753 195 729 213 697 238
-8 376 148 357 159 335 172 315 186
-6 408 151 385 162 363 174 342 189
-4 441 153 417 164 393 177 370 192 344 210 314 230
Glycol water
-2 476 156 451 167 424 180 399 196 372 214 341 234
0 513 159 486 170 458 184 430 199 401 218 370 238
2 556 162 527 174 497 188 466 204 434 222 400 243
2800 X 5 627 167 595 180 561 194 526 211 484 228 447 249
6 651 169 616 182 581 196 545 213 503 231 463 252
7 672 171 637 183 602 198 565 215 522 233 483 255
Pure water 8 695 173 660 185 622 200 584 217 541 236 500 257
10 748 177 711 190 671 205 629 222 580 241 537 263
12 798 181 758 194 716 210 672 227 622 246 574 269
15 876 187 833 201 788 217 741 235 689 255 638 278
-8 423 152 409 166 397 183 380 194
-6 453 154 439 168 422 185 415 200
-4 474 154 460 168 443 185 428 203 403 227
Glycol water
-2 508 156 493 171 475 188 461 208 435 231
0 544 159 527 173 509 191 487 211 465 235
2 584 161 567 176 547 194 524 215 500 239
2800 X 5 649 165 633 181 610 200 584 219 557 246
6 674 167 655 183 629 201 604 222 573 248
7 696 169 673 184 649 204 617 224 591 250
Pure water 8 718 170 695 186 669 204 642 227 611 252
10 766 173 743 190 716 209 688 231 654 257
12 814 177 787 193 760 213 727 235 692 261
15 881 181 860 199 828 218 793 242 755 269

Pf : Cooling capacity calculated with : Glycol water is necessary


- water inlet/outlet differential as per curves page 16 Low temperature option necessary (valid only on LX versions).
- 0.00005 m2 °C/W fouling factor EUROVENT conditions
Pa : Compressors + fans absorbed power

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 61


Air cooled chillers

LX R134a
PERFORMANCES
POWERCIAT LX-LXH-LXC
STANDARD version
CONDENSER AIR INLET TEMPERATURE °C
LX
Evaporator water 25 30 35 40 45
LXH outlet temperature Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa
LXC °C kW kW kW kW kW kW kW kW kW kW
-8 452 168 433 183 415 200 392 220
PROPELLER

-6 485 170 466 186 447 203 421 223


-4 521 173 502 189 478 206 453 227 423 251
FANS

Glycol water
-2 555 175 540 192 513 210 487 231 459 256
0 591 178 571 195 550 214 522 236 488 260
2 642 182 614 199 592 218 562 241 532 267
3050 X 5 704 188 682 207 660 226 627 249 593 276
6 738 190 710 209 681 228 647 251 613 279
7 761 192 731 211 703 230 668 254 633 282
Pure water 8 785 194 752 213 724 233 687 257 653 285
10 836 199 809 218 772 238 735 262 698 291
12 887 203 853 223 820 243 780 268 739 297
15 968 211 930 231 893 251 850 276 805 301
R134a

-8 502 186 479 204 460 224 433 246


-6 540 189 524 208 494 228 467 251
-4 578 192 553 211 534 233 504 256 467 282
Glycol water
-2 620 196 598 215 568 236 539 261 497 287
0 662 199 635 219 609 241 578 267 541 295
2 712 203 680 223 654 246 623 273 587 304
3400 X 5 796 211 758 231 730 255 694 283 657 315
6 816 212 783 234 753 258 716 286 678 320
7 842 215 812 236 777 261 738 289 700 323
Pure water 8 869 217 835 239 801 264 763 293 723 327
10 925 222 886 246 857 271 810 299 771 334
12 982 228 941 252 907 276 862 306 819 343
15 1070 237 1026 262 989 286 939 317 886 340
-8 551 206 529 226 502 248 474 273
-6 593 209 570 230 542 253 509 279
-4 635 213 610 234 581 259 550 286 519 317
Glycol water
-2 679 217 652 241 622 264 590 293 557 325
0 726 221 698 244 667 270 640 299 598 334
2 776 225 751 250 714 276 679 307 642 342
3750 X 5 865 234 838 259 797 287 759 320 718 357
6 891 236 852 261 821 290 783 324 740 361
7 919 239 886 265 846 293 806 327 765 366
Pure water 8 952 243 921 269 875 297 839 331 789 371
10 1012 248 979 275 935 305 891 341 843 381
12 1073 255 1038 282 990 312 942 348 885 388
15 1167 265 1129 292 1078 323 1027 361 974 399

Pf : Cooling capacity calculated with : Glycol water is necessary


- water inlet/outlet differential as per curves page 16 Low temperature option necessary (valid only on LX versions).
- 0.00005 m2 °C/W fouling factor EUROVENT conditions
Pa : Compressors + fans absorbed power

NOTES

...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................

62 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
PERFORMANCES
POWERCIAT LX-LXH-LXC
LOW NOISE - XTRA LOW NOISE versions
CONDENSER AIR INLET TEMPERATURE °C
LX
Evaporator water 25 30 35 40 45 50
LXH outlet temperature Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa
LXC °C kW kW kW kW kW kW kW kW kW kW kW kW
-8 232 99 218 106 204 113 189 122
-6 252 101 237 107 222 115 206 124
-4 277 103 260 109 242 117 224 126 206 137 189 151
Glycol water
-2 299 104 282 111 264 119 246 129 226 140 206 154
0 321 106 304 114 285 122 266 131 246 143 226 157
2 348 109 329 116 310 125 289 134 268 146 246 160

PROPELLER
1800 X 5 391 113 370 121 348 129 326 139 302 151 279 165
6 404 114 383 122 361 131 337 141 313 153 289 167

FANS
7 418 116 396 124 374 132 349 143 325 154 296 168
Pure water 8 433 117 410 125 385 134 362 145 336 156 311 170
10 465 121 441 129 416 138 388 149 363 160 335 176
12 496 124 470 132 443 141 416 152 387 164 359 177
15 544 129 516 137 487 147 457 157 426 170
-8 256 101 244 109 236 119 224 131
-6 280 102 267 110 252 120 240 132
-4 301 104 288 112 274 122 260 134 245 148
Glycol water
-2 322 105 311 114 295 124 282 136 266 151
0 345 107 327 116 318 126 302 139 285 153
2 371 109 357 118 342 129 321 140 307 156
R134a

1800 X 5 412 112 396 122 379 133 361 146 336 160
6 425 114 409 123 391 134 373 147 353 162
7 438 115 421 124 402 135 384 148 362 163
Pure water 8 451 116 435 125 416 137 394 149 375 165
10 482 119 464 128 445 140 423 153 401 169
12 511 122 492 131 471 143 449 157 425 172
15 558 126 537 136 513 148 488 161 462 178
-8 285 115 265 123 250 132 227 142
-6 307 117 288 125 269 134 248 145
-4 336 120 311 128 292 137 270 148 247 160 205 174,0
Glycol water
-2 357 122 336 131 315 140 292 152 268 164 225 178,1
0 386 125 361 134 340 144 317 155 291 168 282 181,6
2 417 128 392 138 370 148 344 159 319 173 290 188,7
2150 X 5 468 134 441 144 416 154 388 167 360 180 329 195,9
6 485 136 457 146 430 156 403 168 373 182 342 197,1
7 501 137 471 148 445 159 417 171 387 185 360 197,7
Pure water 8 518 139 488 150 462 160 431 173 407 187 374 198,9
10 556 144 524 154 496 165 464 178 433 193
12 592 148 560 158 528 170 496 183 462 198
15 649 155 615 165 580 177 545 191 507 206
-8 320 121 303 132 289 145 272 159
-6 343 123 331 135 308 146 294 163
-4 367 126 352 137 337 151 321 166 297 184
Glycol water
-2 391 127 376 140 358 154 343 170 320 188
0 420 130 404 143 386 157 369 175 338 191
2 452 133 434 146 414 161 393 178 371 198
2150 X 5 501 138 483 152 462 168 440 186 413 206
6 517 141 497 154 470 168 450 188 426 208
7 533 142 513 156 486 171 463 190 443 209
Pure water 8 552 144 527 157 503 173 478 192 459 210
10 586 147 563 162 539 178 512 197
12 619 151 598 166 574 184 542 202
15 675 157 651 173 622 190 585 208
Pf : Cooling capacity calculated with : Glycol water is necessary
- water inlet/outlet differential as per curves page 16 Low temperature option necessary (valid only on LX versions).
- 0.00005 m2 °C/W fouling factor EUROVENT conditions
Pa : Compressors + fans absorbed power

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 63


Air cooled chillers

LX R134a
PERFORMANCES
POWERCIAT LX-LXH-LXC
LOW NOISE - XTRA LOW NOISE versions
CONDENSER AIR INLET TEMPERATURE °C
LX
Evaporator water 25 30 35 40 45 50
LXH outlet temperature Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa
LXC °C kW kW kW kW kW kW kW kW kW kW kW kW
-8 318 131 300 141 280 151 257 162
PROPELLER

-6 349 134 327 144 304 154 280 166


-4 375 137 353 147 330 158 307 170 279 184 250 196
Glycol water
FANS

-2 405 140 378 151 356 162 331 175 303 188 274 201
0 433 144 408 155 384 166 358 179 329 193 300 210
2 474 147 441 159 416 171 388 185 360 200 333 215
2500 X 5 530 153 497 167 470 179 440 193 406 208 372 221
6 549 156 514 169 486 181 456 196 422 211 391 225
7 568 158 531 171 503 184 471 198 438 214 407 228
Pure water 8 587 161 550 174 520 186 487 201 455 217 420 232
10 632 166 592 180 560 192 524 207 486 223
12 673 172 635 184 598 198 559 213 522 230
15 738 180 697 192 656 206 614 223 574 240
-8 372 141 354 155 338 171 318 188
-6 400 144 386 159 363 175 347 194
-4 427 147 409 163 388 178 368 198 345 219
Glycol water
-2 455 150 437 165 419 182 401 206 373 226
0 487 153 470 170 446 188 429 211 398 232
2 520 156 503 173 478 192 460 217 429 239
R134a

2500 X 5 582 165 559 181 535 202 503 225 477 250
6 601 167 576 183 547 203 517 227 492 254
7 619 168 594 186 569 207 534 229 511 255
Pure water 8 638 170 610 188 584 209 556 235 529 256
10 678 175 652 194 622 215 592 241
12 726 182 691 199 660 221 627 247
15 782 188 756 208 720 231 675 256
-8 373 150 352 161 332 174 311 189
-6 403 153 382 164 359 177 338 192
-4 437 155 413 167 389 180 365 196 338 213 311 233
Glycol water
-2 470 158 446 170 420 183 394 199 367 218 340 238
0 506 161 480 173 453 187 423 204 396 222 369 242
2 549 165 520 177 490 191 459 207 428 226 401 246
2800 X 5 619 171 586 183 553 198 513 216 477 234 450 254
6 640 173 607 186 572 200 535 218 495 236 454 257
7 662 175 628 188 593 203 552 221 514 239 471 261
Pure water 8 684 176 650 190 613 205 573 222 531 242 490 263
10 736 181 698 195 659 210 615 228 571 248 534 265
12 784 185 745 199 703 215 656 234 606 253 565 270
15 862 192 817 206 771 223 723 242 673 263
-8 421 155 409 169 390 186 378 205
-6 450 157 438 172 419 188 405 208
-4 483 159 470 174 450 192 428 211 412 233
Glycol water
-2 517 162 496 177 482 195 463 216 447 238
0 551 164 533 179 513 198 490 219 471 243
2 592 167 572 183 550 201 525 223 510 248
2800 X 5 659 172 642 189 610 207 583 230 566 256
6 680 174 657 190 630 209 606 233 586 257
7 702 175 677 192 646 212 623 235 603 259
Pure water 8 723 177 703 194 669 213 640 237 629 262
10 772 181 746 198 722 219 684 242 656 266
12 817 184 789 202 755 221 725 247 685 270
15 890 190 858 208 819 228 780 254 743 280

Pf : Cooling capacity calculated with : Glycol water is necessary


- water inlet/outlet differential as per curves page 16 Low temperature option necessary (valid only on LX versions).
- 0.00005 m2 °C/W fouling factor EUROVENT conditions
Pa : Compressors + fans absorbed power

64 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
PERFORMANCES
POWERCIAT LX-LXH-LXC
LOW NOISE - XTRA LOW NOISE versions
CONDENSER AIR INLET TEMPERATURE °C
LX
Evaporator water 25 30 35 40 45
LXH outlet temperature Pf Pa Pf Pa Pf Pa Pf Pa Pf Pa
LXC °C kW kW kW kW kW kW kW kW kW kW
-8 453 171 430 184 415 205 387 228
-6 481 174 458 187 440 207 413 230
-4 516 177 495 193 472 211 443 232 421 258
Glycol water
-2 553 180 531 196 507 215 473 235 454 263
0 591 183 569 200 542 219 515 242 479 268
2 634 187 610 204 584 224 551 247 520 274

PROPELLER
3050 X 5 706 193 680 212 650 233 619 258 582 285
6 730 196 700 215 670 235 636 259 603 289

FANS
7 755 199 723 217 692 238 653 263 620 292
Pure water 8 774 200 742 219 713 241 672 265 648 293
10 826 205 795 225 761 247 721 272
12 875 211 843 230 806 253 767 279
15 953 219 915 239 877 262 833 289
R134a

-8 497 191 475 209 452 229 422 252


-6 534 194 513 213 488 234 455 256
-4 572 198 549 217 523 238 494 264 463 291
Glycol water
-2 613 201 589 221 561 244 514 266 499 301
0 654 205 628 226 599 249 550 272 536 307
2 700 210 674 231 644 255 592 280 573 314
3400 X 5 781 218 749 240 717 266 678 296 642 328
6 805 220 774 243 738 269 698 298 660 328
7 830 223 798 246 762 272 722 302 683 332
Pure water 8 855 226 821 249 785 275 744 305 700 335
10 911 232 876 256 837 283 797 314
12 966 238 928 262 888 290 844 323
15 1051 248 1009 272 965 301 917 335
-8 545 211 522 232 496 255 457 282
-6 584 215 562 237 534 260 489 289
-4 625 220 601 242 571 266 536 297 511 328
Glycol water
-2 671 225 640 246 611 273 575 303 546 337
0 716 231 691 253 655 280 620 310 585 346
2 761 235 734 258 702 287 667 319 629 356
3750 X 5 849 246 819 270 782 300 743 334 675 367
6 874 248 842 273 813 307 767 339 704 372
7 901 252 871 277 831 308 791 344 749 377
Pure water 8 928 256 896 280 861 313 818 349 776 372
10 988 260 955 288 908 319 870 360
12 1053 268 1011 296 968 330 921 370
15 1144 279 1100 308 1051 343 999 385

Pf : Cooling capacity calculated with : Glycol water is necessary


- water inlet/outlet differential as per curves page 16 Low temperature option necessary (valid only on LX versions).
- 0.00005 m2 °C/W fouling factor EUROVENT conditions
Pa : Compressors + fans absorbed power

NOTES

...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................
...........................................................................

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 65


Air cooled chillers

LX R134a
CORRECTION FACTORS FOR ETHYLENE GLYCOL
■ Evaporator
Mass Multiplying coefficient
concentration % Cooling capacity Chilled water flow Chilled water pressure drops
10 0.99 1.05 1.05
20 0.985 1.10 1.10
30 0.98 1.15 1.15
40 0.97 1.20 1.23
■ Glycol concentration necessary
PROPELLER

Mass concentration % 0 10 20 30 40
FANS

Freezing point °C 0 -4 -9 -16 -23


Ethylene glycol
Minimum water outlet °C 4 2 0 -5 -11
Freezing point °C 0 -3 -7 -13 -22
Propylene glycol
Minimum water outlet °C 4 3 -2 -4 -10

OPERATION RANGES
■ Standard version
905 rpm fan speed

LX - LXH - LXC 1800X (HPS) LX - LXH - LXC 2150X (HPS) - 2500X (HPS)

D D
50 50
C C
45 45
Condenser air inlet temperature °C
Condenser air inlet temperature °C

40 40

B A B A

-15 -15
-8 -4 5 10 15 -8 -4 5 12 15
Evaporator water outlet temperature °C Evaporator water outlet temperature °C

LX - LXH - LXC 2800X (HPS) à 3750X HPS

D
50
C
45
Condenser air inlet temperature °C

40 A - Full load operation with pure water


B - Full load operation with glycol compulsory
C - Operation without HPS
D - Part load operation
B A

-15
-8 -4 5 15
Evaporator water outlet temperature °C

66 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
■ Low noise - Xtra low noise versions
715 rpm fan speed

LX - LXH - LXC 1800X (HPS) LX - LXH - LXC 2150X (HPS) - 2500X (HPS)
LX - LXH - LXC 3050X HPS à 3750X HPS

50 D 50 D
C 45 C
45

Condenser air inlet temperature °C


Condenser air inlet temperature °C

40 40

PROPELLER
B A B A

FANS
-15 -15
-8 -4 5 12 15 -8 -4 5 8 15

Evaporator water outlet temperature °C Evaporator water outlet temperature °C

LX - LXH - LXC 2800X (HPS)

50 D
C
45
Condenser air inlet temperature °C

40
A - Full load operation with pure water
B - Full load operation with glycol compulsory
C - Operation without HPS

B A D - Part load operation

-15
-8 -4 5 12 15
Evaporator water outlet temperature °C

EVAPORATOR LIMITS
∆T between chilled water
inlet / outlet difference ˚C

The curve below represents the min. and max. admissible


temperature differences on pure water or glycol water as a
function of the fluid outlet temperature at the evaporator.
Check also minimum and maximum temperature differences
according to minimum and maximum flow (see curves "Hydraulic
characteristics").

Difference of temperature for performances calculation tables


Example :
For a water outlet : + 5 °C (∆T for performances calculation 5 °C)
∆T minimum : 3,1 °C Water temp : 8,1 / 5 °C
∆T maximum : 7,2 °C Water temp : 12,2 / 5 °C

Chilled water outlet temperature (˚C)

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 67


Air cooled chillers

LX R134a
HYDRAULIC CHARACTERISTICS
■ Water pressure drop POWERCIAT LX - LXC
→ Pumps head of water mWG
PROPELLER
FANS

)
PS
(H
X
PS
) 00
(H - 28
X S)
00 HP
18 X
(
00 S
-2
5 HP
) 0X
PS 75
X
(H -3
50 S
21 HP
0X
40
-3
S
HP
X
50
30

→ Water flow in m3/h

Do not extrapolate the values. Minimum and maximum water flow must be respected.

HYDRAULIC CHARACTERISTICS
■ Water pressure drop POWERCIAT LXH
→ Pumps head of water mWG

S
HP
0X
) 75
PS -3
(H PS
X H
8 00 X
)
-2 00
PS 4
(H PS) -3
0X S
0 (H HP
18 0 X X
50 50
)-
2 30
S
(HP
5 0X
21

→ Water flow in m3/h

68 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
■ Pumps selection

102 - 116 : single pumps 202 - 216 : twin pumps

PROPELLER
FANS
Do not extrapolate the values. Minimum and maximum water flow must be respected.

MINIMUM CHILLED WATER PIPING VALUMES

POWERCIAT LX - LXH - LXC

Xtra Connect microprocessor fitted on POWERCIAT units allows a very flexible adjustement of the operation in comparison with
the drift of parameters, especially for hydraulic installation with low water volume.
The auto adaptive control of the units and modulating capacity control on each compressor avoid the use of anti-short cycle
function and the installation of buffer tank.

Minimum water volume ot the installation following sizes of units as below

Models 1800 X 2150 X 2500 X 2800 X 3050 X 3400 X 3750 X


1800 X 2150 X 2500 X 2800 X
LX - LXH - LXC HPS HPS HPS HPS HPS HPS HPS

Minimum volume
1236 1322 1401 1548 1651 1849 1963 2167 1377 1557 1725
of installations (liters)

Minimum chilled water piping volumes calculation for the following conditions :
- chilled water temperature : 12°C / 7°C
- condenser air inlet temperature : 35°C

NOTE :
Installations with important thermal variation or some industrial process designed to supply very constant water
temperature, must be equipped with buffer tank. (LXH alternative selection)

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 69


Air cooled chillers

LX R134a
SOUND LEVELS

STANDARD version
High speed fans (905 rpm)

■ Acoustic pressure levels ref 2 x 10-5 Pa ± 3 dB (Lp)


PROPELLER

SOUND PRESSURE LEVEL SPECTRUM (dB)


FANS

LX - LXH Total pressure


LXC level dB(A)
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz

1800X
53 65 64 62 63 56 51 66
1800X HPS
2150X
52 65 64 65 64 59 53 67
2150X HPS
2500X
53 66 65 66 65 60 54 68
2500X HPS
2800X
55 67 66 64 65 58 53 68
2800X HPS
3050X HPS 55 67 66 64 65 58 53 68

3400X HPS 56 68 67 65 66 59 54 69

3750X HPS 56 68 67 65 66 59 54 69

■ Acoustic power levels ref 10-12 W ± 3 dB (Lw)

SOUND POWER LEVEL SPECTRUM (dB)


LX - LXH Total power
LXC level dB(A)
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz

1800X
85 97 96 94 95 88 83 98
1800X HPS
2150X
85 98 97 98 97 92 86 100
2150X HPS
2500X
86 99 98 99 98 93 87 101
2500X HPS
2800X
88 100 99 97 98 91 86 101
2800X HPS
3050X HPS 88 100 99 97 98 91 86 101

3400X HPS 89 101 100 98 99 92 87 102

3750X HPS 89 101 100 98 99 92 87 102

Acoustic pressure levels are calculated following ISO 3744 regulation Lp = Lw - 10 log S, in free field and at 10 meters
from the unit.
We remind that the acoustic pressure level is given as an indication and that only the sound power level is
comparable and certified.

70 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
SOUND LEVELS

LOW NOISE version


Low speed fans (715 rpm) + compressors phonic insulation

■ Acoustic pressure levels ref 2 x 10-5 Pa ± 3 dB (Lp)

SOUND PRESSURE LEVEL SPECTRUM (dB)


LX - LXH Total pressure
LXC level dB(A)
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz

PROPELLER
1800X
58 54 63 53 58 49 42 59
1800X HPS

FANS
2150X
59 54 64 58 58 52 42 61
2150X HPS
2500X
60 55 65 59 59 53 43 62
2500X HPS
2800X
62 57 67 61 62 55 46 64
2800X HPS
3050X HPS 62 56 67 59 61 52 45 63

3400X HPS 63 57 68 60 62 53 46 64

3750X HPS 63 57 68 60 62 53 46 64

■ Acoustic power levels ref 10-12 W ± 3 dB (Lw)

SOUND PRESSURE LEVEL SPECTRUM (dB)


LX - LXH Total pressure
LXC level dB(A)
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz

1800X
90 86 95 85 90 81 74 91
1800X HPS
2150X
92 87 97 91 91 85 75 94
2150X HPS
2500X
93 88 98 92 92 86 76 95
2500X HPS
2800X
95 90 100 94 95 88 79 97
2800X HPS
3050X HPS 95 89 100 92 94 85 78 96

3400X HPS 96 90 101 93 95 86 79 97

3750X HPS 96 90 101 93 95 86 79 97

Acoustic pressure levels are calculated following ISO 3744 regulation Lp = Lw - 10 log S, in free field and at 10 meters
from the unit.
We remind that the acoustic pressure level is given as an indication and that only the sound power level is
comparable and certified.

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 71


Air cooled chillers

LX R134a
SOUND LEVELS

XTRA LOW NOISE version


Specific mounting for low speed fans (715 rpm) + compressors sound insulation

■ Acoustic pressure levels ref 2 x 10-5 Pa ± 3 dB (Lp)


PROPELLER
FANS

SOUND PRESSURE LEVEL SPECTRUM (dB)


LX - LXH Total pressure
LXC level dB(A)
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz

1800X
51 44 55 48 52 45 35 54
1800X HPS
2150X
59 52 54 52 51 42 31 55
2150X HPS
2500X
60 53 54 53 51 42 31 56
2500X HPS
2800X
62 56 55 56 53 44 32 58
2800X HPS
3050X HPS 61 53 55 53 53 44 32 56

3400X HPS 62 54 56 54 54 45 33 57

3750X HPS 62 54 56 54 54 45 33 57

■ Acoustic power levels ref 10-12 W ± 3 dB (Lw)

SOUND POWER LEVEL SPECTRUM (dB)


LX - LXH Total power
LXC level dB(A)
63 Hz 125 Hz 250 Hz 500 Hz 1000 Hz 2000 Hz 4000 Hz

1800X
83 76 87 80 84 77 67 86
1800X HPS
2150X
92 85 87 85 84 75 64 88
2150X HPS
2500X
93 86 87 86 84 75 64 89
2500X HPS
2800X
95 89 88 89 86 77 65 91
2800X HPS
3050X HPS 94 86 88 86 86 77 65 89

3400X HPS 95 87 89 87 87 78 66 90

3750X HPS 95 87 89 87 87 78 66 90

Acoustic pressure levels are calculated following ISO 3744 regulation Lp = Lw - 10 log S, in free field and at 10 meters
from the unit.
We remind that the acoustic pressure level is given as an indication and that only the sound power level is
comparable and certified.

72 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
DIMENSIONS LX - LXH

Door FIG 1
opening

2470
2 2a

D
C A (LXH)
A (LX)

PROPELLER
1 2a
B

** For XTRA LOW NOISE version only

FANS
2

453 288
LX 8 holes (+4 LXH) ∅ 20.2
for ground fitting

FIG 2
900
Door
opening
2470
460

1 2
2a

4525 4274
2880 ** For XTRA LOW NOISE version only
B

2a
1

453 288
LX 12 holes (+4 LXH) ∅ 20.2
for ground fitting
Chilled water Weight kg
Models inlet LX / LXH outlet LX outlet LXH
Fig A B C D empty in operation
1 2 2a
LX 1800X (HPS) 2690 4617 4739
LXH 1800X (HPS)
1
4330
597 1736 402 Victaulic DN 150 * 5528 6750
LX 2150X (HPS) 2880 5240 5434
LXH 2150X (HPS)
1
4472
Victaulic DN 150 * 6166 7460
635 1594 463
LX 2500X (HPS) 2880 5669 5863
LXH 2500X (HPS)
1
4472
Victaulic DN 150 * 6596 7890
LX 2800X (HPS) 6688 6882
LXH 2800X (HPS)
2 - 765 4525 - Victaulic DN 150 * 7612 8906
* 2a according to the selected pump (see page 22)

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 73


Air cooled chillers

LX R134a
DIMENSIONS LX - LXH

FIG 3

900
PROPELLER

Door
FANS

opening

540
2 2a

5161 3640
2780 ** For XTRA LOW NOISE version only
1 2a
887

453 288
LX 12 holes (+4 LXH) ∅ 20.2
for ground fitting

Chilled water Weight kg


Modèles Fig. inlet LX / LXH outlet LX outlet LXH
empty in operation
1 2 2a
LX 3050X HPS 7555 7891
3 Victaulic DN 200 *
LXH 3050X HPS 8478 9914
LX 3400X HPS 7970 8306
3 Victaulic DN 200 *
LXH 3400X HPS 8893 10329
LX 3750X HPS 8380 8716
3 Victaulic DN 200 *
LXH 3750X HPS 9303 10739

Models 1800 - 2150 - 2500 - 2800 - 3050 - 3400 - 3750


Single pumps 102 - 103 - 105 - 107 - 109 104 - 106 - 108 - 110 - 112 111 - 113 - 114 - 115 - 116
Twin pumps 202 - 203 - 205 - 207 - 209 204 - 206 - 208 - 210 - 212 211 - 213 - 214 - 215 - 216
Flanges DN 65 - PN 16 DN 80 - PN 16 DN 100 - PN 16
X (LXH) 364 374 448

* 2a according to the selected pump select above

74 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
DIMENSIONS LXC
FIG 1

Door
opening

2 1

B
A ** For XTRA LOW NOISE version only
1

PROPELLER
FANS
2

8 holes ∅ 20.2
for ground fitting
FIG 2

900
Door
opening

2
1
460

5290

** For XTRA LOW NOISE version only

4525
1

2
858

8 holes ∅ 20.2
for ground fitting

Chilled water Weight kg


Modèles inlet LXC outlet LXC
Fig. A B C empty in operation
1 2
LXC 1800X (HPS) 1 1736 3 402 VICTAULIC DN 150 * 4912 5084

LXC 2150X (HPS) 1 1594 8 463 VICTAULIC DN 150 * 5540 5784

LXC 2500X (HPS) 1 VICTAULIC DN 150 * 5969 6213

LXC 2800X (HPS) 2 - VICTAULIC DN 150 * 7149 7393

*2 according to the selected pump (see page 24)

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 75


Air cooled chillers

LX R134a
DIMENSIONS LXC

FIG 3

900
Door
opening
PROPELLER

2470
FANS

1 2 1

540
542
540

6657 2125

** For XTRA LOW NOISE version only

5161
1

2
858

12 holes ∅ 20.2
for ground fitting

Chilled water Weight kg


Models Fig. inlet LXC outlet LXC
empty in operation
1 2
LXC 3050X HPS 3 VICTAULIC DN 200 * 8003 8389

LXC 3400X HPS 3 VICTAULIC DN 200 * 8418 8804

LXC 3750X HPS 3 VICTAULIC DN 200 * 8828 9214

Models 1800 - 2150 - 2500 - 2800 - 3050 - 3400 - 3750


Single pumps 102 - 103 - 105 - 107 - 109 104 - 106 - 108 - 110 - 112 111 - 113 - 114 - 115 - 116
Twin pumps 202 - 203 - 205 - 207 - 209 204 - 206 - 208 - 210 - 212 211 - 213 - 214 - 215 - 216
Flanges DN 65 - PN 16 DN 80 - PN 16 DN 100 - PN 16

* 2 according to the selected pump above

76 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
ANTIVIBRATIL MOUNTS (OPTION)
For applications with very low vibrations, it is necessary to install antivibration mounts underneath the unit.
The fitting of mounts must be made according to the drawings below

POWERCIAT LX

LX 1800X - 2150X - 2500X (HPS) - 4V

PROPELLER
FANS
LX 2800X (HPS) - 3050X HPS - 3400X HPS - 3750XHPS - 6V

POWERCIAT LXH

LXH 1800X - 2150X - 2500X (HPS) - 4V

LXH 2800X (HPS) - 3050X HPS - 3400X HPS - 3750XHPS - 6V

AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A 77


Air cooled chillers

LX R134a
ANTIVIBRATIL MOUNTS (OPTION)
For applications with very low vibrations, it is necessary to install antivibration mounts underneath the unit.
The fitting of mounts must be made according to the drawings below

POWERCIAT LXC
PROPELLER
FANS

LXC 1800X - 2150X - 2500X (HPS) - 4V

LXC 2800X (HPS) - 3050X HPS - 3400X HPS - 3750XHPS - 6V

NOTE
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................
...................................................................................................

78 AIR CONDITIONING - REFRIGERATION - AIR HANDLING - HEAT EXCHANGE - 2006 EDITION - NA 0 6 . 0 1 A


Air cooled chillers

LX R134a
ADVISES FOR INSTALLATION
■ Location POWERCIAT LX

■ The POWERCIAT packaged units LX - LXC and LXH are ■ Hydraulic connections
designed for outdoor installation.
■ The hydraulic connections must be made following good
■ A free space of 2 meters around the unit is necessry for a engineering practice
good air circulation and maintenance.
■ Plan all the necessary accessories for an hydraulic
■ Choose the location in order to respect environement circuit :
(Acoustic level, etc,...)
- expansion vessel
■ The sound level problems must be analysed in detail
- Drains at low points
So, before installation of the unit, study the best position, if

PROPELLER
necessary with a sound technician. - Shut off valves
- Air vent at high points, etc.

FANS
If necessary, install the unit on antivibration mounts and
equip the hydraulic pipes with flexible connectors - Check sure that the installation water contents is sufficient
(recommended equipments)
- Plan, if required, a buffer tank

■ Electrical connections
■ Commissioning
■All the indications concerning electrical connections are
mentioned on the wiring diagram enclosed with the unit (they ■ In accordance with our commissioning and maintenance
must be respected). brochure
■ These connections must be made following good
engineering practice and in accordance to the norm in force.
■ Maintenance
■ Leave the control auxiliary circuit under voltage to allow
■ In accordance with our maintenance brochure
operation fo the crankcase heater and the antifreeze heater
(option)
■ The customer electrical supply line must be fitted with a ■ Subscribe to a maintenance contract
circuit breaker protection (to be supplied by the customer)

POWERCIAT LX - LXH - LXC

■ Antifreeze protection
■ If there is a risk of freezing :
a - either supply evaporator antifreeze protection option (LX
model) or evaporator antifreeze protection + hydraulic
equipment option (LXH - LXC models) if installation runs with
pure water
b - or protect the installation with glycol concentration
c - or drain the installation
NOTE : With the antifreeze protection, if there is a electrical
supply failure, the unit is not protected against freezing
anymore.