Shock Frosters - GFN: WWW - Guentner.de
Shock Frosters - GFN: WWW - Guentner.de
www.guentner.de
GFN | 2015-12
page 2 / 61
Contents
2 Safety..........................................................................................12
2.1 Labelling on the unit:.....................................................................12
2.1.1 Safety signs on the unit................................................................... 13
2.1.2 Other signs and notes on the unit....................................................15
2.2 Basic safety notices.......................................................................17
2.2.1 How to act in an emergency............................................................ 17
2.2.2 Personnel, care requirements.......................................................... 18
2.3 Proper intended use.......................................................................18
2.3.1 Proper intended use.........................................................................18
2.3.2 Operating conditions.........................................................................19
2.3.3 Improper use.................................................................................... 19
2.4 Mechanical residual hazards.........................................................21
2.4.1 Fins, sharp unit corners and edges................................................. 21
2.4.2 Fans.................................................................................................. 21
2.5 Electrical residual hazards............................................................ 22
3 Technical data........................................................................... 28
3.1 Unit................................................................................................... 28
3.2 Fans..................................................................................................28
5 Fan motor.................................................................................. 30
8 Operation................................................................................... 47
8.1 Safety............................................................................................... 47
8.2 Putting the unit into operation......................................................47
8.3 Taking the unit out of operation...................................................47
9 Troubleshooting........................................................................ 50
9.1 Safety............................................................................................... 50
9.2 Service............................................................................................. 50
9.3 Troubleshooting table....................................................................50
10 Maintenance...............................................................................51
10.1 Safety............................................................................................... 51
10.1.1 Before starting all maintenance........................................................51
10.1.2 With all maintenance work............................................................... 51
10.1.3 After all maintenance work...............................................................52
10.2 Inspection and maintenance plan................................................ 53
10.2.1 Fans.................................................................................................. 53
10.2.2 Unit heat exchanger......................................................................... 53
10.3 Maintenance work.......................................................................... 55
10.3.1 Remove leaks...................................................................................55
10.4 Clean unit........................................................................................ 55
10.4.1 General............................................................................................. 55
10.4.2 Clean and defrost heat exchanger...................................................55
10.4.3 Cleaning fans....................................................................................57
10.5 Defrosting the unit......................................................................... 58
10.5.1 Notes on defrosting.......................................................................... 58
10.5.2 Defrost control.................................................................................. 59
10.5.3 Circulation air defrosting...................................................................60
10.5.4 Electric defrosting ............................................................................60
10.5.5 Hot gas defrosting (option)...............................................................60
10.5.6 Further notes on defrosting.............................................................. 60
11 Plans/diagrams..........................................................................61
11.1 Electrics documentation................................................................61
11.1.1 Fan motor connection diagram........................................................ 61
11.1.2 Connection diagram electrical defrost..............................................61
CAUTION
Always keep the operating instructions in the unit's immediate vicinity at all times.
Ensure that the operating instructions are accessible to all people that have anything at all to do with
the unit at all times.
Ensure that the operating instructions are read and understood by all people that have anything at all
to do with the unit.
1.3 Responsibilities
The materials used in the construction and for soldering and welding are designed to withstand
the foreseeable mechanical, thermal and chemical stresses, and are resistant to the working fluids
used and to mixtures of such working fluids and the oils used to lubricate refrigeration compressors.
The working fluid-carrying parts of the unit (core tubes, distributor tube and header outlet) are con-
figured so that they remain tight with the foreseeable mechanical, thermal and chemical stresses,
and withstand the maximum permissible operating pressure.
Material, wall thickness, tensile strength, corrosive resistance, shaping process and testing are suit-
able for the working fluid used and withstand the possible pressures and stresses that might occur.
All responsibility for the equipment into which the unit is integrated, are the exclusive responsibility
of the people involved in the individual workflows.
The owner or operator must ensure that when operating, monitoring and maintaining the system
the working fluid and version must not deviate from the details specified in the order-related docu-
ments.
Planning and preparing emergency measures: To avoid consequential damage caused by opera-
tional disruptions, a warning system must be installed on the customer's premises. Prepare emer-
gency measures that prevent consequential damage for people and property should faults occur.
Responsibility remains with the owner or operator of the system , if the system are used by any-
body else, unless there is a contrary agreement on sharing responsibility.
1.5.1 Scope
These operating instructions series for all blast freezers of the GFN series.
NOTICE
You will find the precise type of your unit in the attached order-related documents.
1.6 Conventions
Abbreviations Meaning
CFC/HFC Alkane group refrigerant, e.g. R134a, R404A, R407C, ...
EN 378 European Norm 378: Refrigeration systems and heat pumps; safety-related
and environmental requirements
EN European Norm
DIN German industrial standard (specification of a standard)
ISO International Standardization Organization .
°C Degrees Celsius (Celsius scale temperature)
is Unit of pressure
I Litre (liquid volume)
Vol% Volume percent (concentration level relative to a volume)
IP Insulation protection
Q 6,3 Balancing quality
ppm parts per million, concentration figure, stands for “millionth part”.
Hz Hertz (frequency)
D Delta connection (alternating current: high speed)
S Star connection (alternating current: low speed)
3~ 3-phase current
1~ 1-phase alternating current
VDE “Verband der Elektrotechnik, Elektronik und Informationstechnik” (Association
for Electrical, Electronic & Information Technologies)
TCC Technical Connection Conditions
EPC Electric Power Company
VDI “Verein Deutscher Ingenieure” (German engineers’ association)
1.7.1 General safety signs and their meaning in these operating instructions
DANGER
Dangerous situation that will definitely cause serious injury or death if it is not avoided.
WARNING
Dangerous situation that could cause serious injury or death if it is not avoided.
CAUTION
Dangerous situation that could cause slight to moderate injury if it is not avoided.
NOTICE
Refers you to possible damage to property.
No smoking!
Smoking is forbidden.
2 Safety
4413 - “Do not use wrench” warning sign beside tray drain
3083 - “Protection grill” warning sign (only used with separate removable protection grill)
2119 – Logo
WARNING
Danger of injuries!
the CFC/HFC refrigerants that are used (R134a, R404A, R407C, ...) are Group L1/A1 refrigerants
compliant with classification according to flammability (L) and toxicity (A) in compliance with EU Direc-
tive 97/23/EC for pressure equipment (Pressure Equipment Directive):
• Refrigerants that, when gaseous, are non-flammable irrelevant of their concentration in air.
• Refrigerants with a time-weighted, averaged concentration that have no adverse effects on the ma-
jority of staff that are exposed every day during a normal 8 hour working day and a 40 hour working
week to this concentration, which is greater than or equal to 400 ml/m 3 (400 ppm (V/V)).
There is no imminent danger for the staff. However, refrigerants of the Group L1/A1 are generally
heavier than air and may flow off to rooms on a lower level. In still air there may be an increase of the
ground level concentration. With high concentrations there is a danger of suffering from disordered
cardiac rhythm and suffocation due to a reduced oxygen concentration, especially at ground level.
Unauthorised people must not have access to the unit. Please ensure that the CFC/HFC refrigerant
escaping from the unit cannot penetrate the interior of the building or put people at risk in any other
way.
Safety measures and procedure:
• In the event of serious unexpected leakage of refrigerant, leave the set-up room immediately and
activate the emergency measures provided, e.g. if:
– Visibly escaping refrigerant liquid or vapour from the heat exchanger or pipe components.
– there is a sizeable sudden escape (escape and evaporation of the greater part of the entire re-
frigerant filling within a short time, e.g. in less than 5 minutes);
– Activation of the refrigerant detector (limit value in accordance with EN 378-1; Annex E):
• Have experienced, trained personnel with prescribed protective clothing perform all necessary pro-
tective and other measures:
– Use respiratory protection.
– Use a room air-independent breathing apparatus with maintenance work in high refrigerant con-
centrations in the room air.
– Ensure the set-up room is well ventilated .
– Divert escaped refrigerant vapour and escaped refrigerant liquid safely.
– Ensure that no refrigerant enters water systems or sewage.
CAUTION
The unit may be installed, put into operation, operated, maintained and repaired only by trained, expe-
rienced and qualified personnel. In order to be considered qualified, people who are to be responsible
for the operation, maintenance, repair and evaluation of systems and their components must have the
necessary training and specialist knowledge for such work, as stipulated in EN 378-1. Qualified or ex-
pert means the ability to satisfactorily perform the activities required for the operation, maintenance, re-
pair and evaluation of refrigeration systems and their components.
The unit may be operated by operating personnel that have no specific knowledge of refrigeration engi-
neering, but have sufficient knowledge and experience with regard to the mode of operation, operation
and daily monitoring of this system, . This operating personnel may not make any interventions or set-
tings on the system.
Changes to the unit, which the manufacturer has first agreed to in writing, may only be made by the in-
structed and qualified personnel.
Electrical installation:
Work on the electrical equipment may only be performed by personnel that have the required expertise
(e.g. an electrician or an electro-technically instructed person), and who are authorised by the operator,
in compliance with the respective VDE regulations (and national and international provisions) and the
TCCs of the EPCs.
WARNING
Danger of injuries and damage to property!
The unit may be used only in accordance with the proper intended use. The operator must ensure that
when operating, monitoring and maintaining the unit, the fluid used and the mode of operation do not
deviate from the order-related information specified in the order-specific documents.
The operator must ensure that maintenance measures are performed in compliance with the system’s
operating instructions manual.
Filling the unit with a different fluid is permitted only following written approval by the manufacturer. You
will find the order-related proper use as intended in the order-specific documents.
Do not exceed the max. operating pressure given on the unit’s type plate.
WARNING
Danger of injuries and damage to property!
Working fluids and their combinations with water or other substances in the working fluid-carrying com-
ponents have chemical and physical effects from the inside on the materials surrounding them. The
unit may be pressurised only with CFC/HFC refrigerant . Pressurising the unit with another working fluid
would have the effect that
■ the structural, soldering and welding materials used do not withstand the foreseeable mechanical,
thermal and chemical stresses, and the pressure that can occur during operation and when shut
down is not withstood.
■ material, wall thickness, tensile strength, corrosive resistance, shaping process and testing are not
suitable for the working fluid used and do not withstand the possible pressures and stresses that
might occur.
■ the unit would not be resistant to the other working fluid and the combination of the other working flu-
id and
■ the unit not remaining tight during operation and when shut down.
■ a possible sudden escape of working fluids could directly endanger people and/or property and the
environment.
The maximum permissible operating temperature specified on the type plate must not be exceeded! If
the operating temperature is exceeded,
• the unit would be exposed to an impermissibly high pressure (pressure/temperature correlation),
• signs of material fatigue would emerge,
The maximum permissible operating pressure specified on the type plate must not be exceeded! If the
operating pressure is exceeded,
■ the parts of the unit carrying the working fluid might not withstand the foreseeable mechanical, ther-
mal and chemical stresses and the pressures that may occur during operation and when shut down,
■ the unit would not remain tight during operation and when shut down,
■ there may be a possible sudden escaping of working fluids after a break or leakage on working flu-
id-carrying components, which would result in the following dangers:
– Danger of escaping materials
– Danger of poisoning
– Dangers caused by oxygen displacement
– Fire hazard (caused by refrigerator oil parts)
– danger of frostbite (caused by liquid coolant squirting/splashing),
– Suffocation hazard
– hazards caused by panic reactions,
– Environmental pollution
WARNING
CFC/HFC Shock frosters may not be used
■ where it is possible that short or prolonged effect caused by contact, inhalation or ingestion of the
working fluid might result in harmful hazards.
■ where the possibility exists of a sudden large release (release and evaporation) of the greater part of
the entire working fluid filling in a short time (e.g. in less than 5 minutes).
The unit must not be changed without the prior written consent of Güntner GmbH & Co. KG . Changes
to the unit are:
■ Changing the operating point (as specified in section see Unit, page 28)
■ Changing the fan capacity (air volume)
■ Changing the working fluid flow-through volume
■ Changing over to another working fluid
The unit must not be operated if safety devices recommended by the manufacturer are not available, not
properly installed or not fully functional.
The unit must not be operated if it is damaged or demonstrates faults. All damage and faults must be
reported to Güntner GmbH & Co. KG immediately and dealt with promptly.
Work on the unit must not be performed without the personal protective equipment specified in these op-
erating instructions.
WARNING
Warns against hand injuries!
Danger of cuts on hands and fingers on the fins and on sharp corners and edges of
the unit.
2.4.2 Fans
WARNING
Danger of cutting off, pulling in!
There is a danger of cutting off fingers on the rotating fan blades, injury hazard for the
hands and pulling in danger for loose elements such as hair, necklaces or clothing
parts.
Do not operate fans without guard grille. Pinch/trap point hazard!
With automatic fan start during maintenance work there is a danger of pinching/trap-
ping for the hands and fingers.
Power off the unit before you begin maintenance work with which you must remove
the guard grille. Secure the unit against unintentional switching on again by removing
the electric fuses for the unit. Secure the unit with a suitable warning sign referring to
unintentional switching on.
WARNING
Warns against dangerous electrical voltage!
Direct and indirect contact with voltage-carrying parts of motors and electrical lines can
cause serious injuries or death .
Power off the unit before you begin maintenance work. See the refrigeration system's
system documentation for this. Secure the unit against unintentional switching on
again by removing the electric fuses for the unit. Secure the unit with a suitable warn-
ing sign referring to unintentional switching on.
Please note that the mains cables may also be carrying voltage, even if the unit is
powered off.
Work on electrical equipment may be performed only by people that have the required
expertise (e.g. an electrician or an electro-technically instructed person) and who are
authorised to do so by the operator.
WARNING
Warns against cold!
In refrigerationoperation the heat exchanger and pipes have a temperature below ±0
°C. Contact can cause frostbite.
Use hand protection!
WARNING
Danger of harm to health and environmental damage!
Refrigerants of the Group L1/A1 are generally heavier than air and may flow off to rooms on a lower lev-
el. In still air there may be an increase of the ground level concentration. With high concentrations there
is a danger of suffering from disordered cardiac rhythm and suffocation due to a reduced oxygen con-
centration, especially at ground level.
• Unauthorised people must not have access to the unit.
• Ensure working rooms are well-ventilated in order to prevent inhalation of high vapour concentra-
tions.
• Please ensure that the CFC/HFC refrigerant escaping from the unit cannot penetrate the interior of
the building or put people at risk in any other way. CFC/HFC refrigerant vapourgas or must be kept
from penetrating neighbouring rooms, staircases, yards, passages or drainage systems and must
be discharged without risk
• Monitor the CFC/HFC refrigerant concentration in the ambient air to ensure constant compliance with
limit values.
• Test the tightness of the unit regularly, as specified in these operating instructions
see Inspection
(
and maintenance plan, page 53).
Frostbite hazard
Splashes of CFC/HFC refrigerant that is superheated can cause frostbite to the eyes
and skin.
• When removing faults after spills of CFC/HFC refrigerant, you must be vigilant for
any remaining superheated CFC/HFC refrigerant.
Danger of poisoning!
CFC/HFC refrigerant contact with fire can form toxic combustion products.
• Prevent CFC/HFC refrigerant contact with open fire.
• Welding and soldering may therefore take place only after completely draining the
relevant section of the system of the CFC/HFC refrigerant. Ensure good ventilation
here!
• With emergency work in high refrigerant concentrations in the room air wear a
room air-independent breathing apparatus.
WARNING
Danger of injuries and damage to property caused by escaping materials
If fans are damaged during fan operation, flying parts of the fan blades can injure people or cause dam-
age to property close to the fan.
Fans, components and cables in system, must be designed, constructed and integrated so that dangers
caused by vibrations that it or other parts of the system generate ,, are reduced to an absolute minimum,
while incorporating all available means for reducing vibrations, preferably at the source.
NOTICE
Damage to property caused by vibrations
Vibrations that are increased by imbalances, as created by dirt, frosting, icing or fan blade damage, are
regularly caused with fan operation. The vibrations are transferred to the unit, where they can cause
damage and damage the unit mounting or components connected to the unit.
Check fan blades and protection grill regularly for contamination and frost and/or ice and make sure
the fans run smoothly ( see Fans, page 53).
WARNING
Injury and damage to property caused by pressurised parts that contain CFC/HFC refrigerant!
Breaks in pressurised pipes or pressurised components of the unit can cause injuries or damage to
property caused by escaping materials ( A sudden large release of the working fluid with its hazardous
properties after a break or leak on pressurised components of the unit can cause the following hazards:
■ Toxicity
■ Oxygen displacement
■ Flammability caused by proportion of lubricating oil for refrigerating compressors present
■ Frostbite (caused by liquid refrigerant squirting/splashing)
■ Suffocation
■ Panic,
■ Environmental pollution
Ensure that the unit in question is pressure-free before maintenance work begins or remove the working
fluid from the unit in question.
Perform maintenance work – especially soldering and welding – on the unit in question only after com-
pletely removing the working fluid from the unit.
WARNING
Injuries and damage to property caused by defective installation!
Defective installation results in hazards caused by:
■ Break or leak on liquid-carrying unit components and pipes
■ Taking the refrigerant pumps out of service: When switching over a duty pump to a reserve pump:
If the duty pump is shut off at both ends from the previous operating state, liquid, cold refrigerant re-
mains in the pump. In shutdown state the refrigerant heats up in the pump and causes leaks with
housing or flange cracks.
■ Uneven load distribution on the fixtures with the danger of stresses within the unit or unit displace-
ment (breaks or leaks on fluid-carrying components of the unit and pipes; danger of breaking off).
■ Insufficient securing of working fluid-carrying lines against mechanical damage! On-site connections:
loaded installation; effect of forces on the distribution and header pipes with the danger of breaks or
leaks on fluid-carrying components of the unit and pipes; danger of breaking off!
■ Break-off danger of the unit with hazard of escaping working fluid and exposed electrical cables.
■ Danger of damage caused by environment-conditional hazard sources (production, transport and
other processes at the set-up point).
■ Unit functional faults caused by air inlet/outlet obstructions.
■ Obstruction of all-side inspection, checks and maintenance, i.e. no unobstructed accessibility to the
working fluid-carrying and electrical components, connections and cables, no recognisable identifiers
on the pipes and insufficient space for tests.
Ensure that:
• The units are to be installed on the fixing points corresponding with their weights and tightened with
fixing bolts. The operator or installer is responsible for ensuring that the bolted connections are of an
adequate strength.
• The diameters of the mounting holes have been statically determined by the manufacturer and the
fixing bolts are adapted accordingly.
• The fixing bolts are secured against loosening by means of an appropriate locking device.
• The fixing bolts are not overtightened or stripped.
• All fixing bolts are tightened equally to achieve a load distribution on the connections that is as bal-
anced as possible.
• All fixing points maintain the same spacing to the fixing level permanently and under load, so that no
mechanical stress occurs in the unit structure. The units are anchored in their fixing position in order
to prevent the equipment from moving.
• The functional safety of the fixing bolts is tested as part of the maintenance periods. see Mainte-
nance, page 51,
• The unit is fixed and set up so that it is not damaged by environment-conditional hazard sources
(production, transport and other processes at the set-up point) or its functioning is not disturbed by
the interventions of unauthorised persons.
• The units are fixed and set up with sufficient slopes for drip water flow.
• The units are fixed and set up so that unobstructed air inlet/outlet is constantly available without any
air short circuiting.
• The units are fixed and set up so that unobstructed heater rod exchange with electric defrosting is
constantly available (option: accessory at customer’s request).
• The units are fixed so that they can be inspected, checked and maintained from all sides at all
times, i.e. there must be unobstructed access to the refrigerant-carrying and electrical components,
connections and lines, the pipeline labelling must be identifiable and adequate space must be avail-
able for testing.
• The working fluid-carrying lines must be protected against mechanical damage. On-site connec-
tions: when installing keep the unit free of load; force must not be exerted on the distribution and
header pipes.
• The following must be observed without fail when installing the unit:
– Imperative adherence to spacing from objects that could be endangered by an effect of the CFC/
HFC refrigerant.
– Provision of measures to safeguard protective objects from a CFC/HFC refrigerant concentration
higher than that permitted by EN 378-3.
– Easily flammable materials must not be placed below the unit.
– Set up and fix units as follows: In areas that are used for inner-plant traffic, the pipelines to and
from the unit must be installed only with connections and fittings that cannot be removed.
– That when switching over a duty pump to a reserve pump no liquid, cold refrigerant remains in
the pump.
WARNING
Injuries and damage to property caused by break during operation!
• Defective installation (see Residual hazards caused by defective installation, page 25).
• Non-compliance with maximum permissible operating pressure ( see Operating conditions, page
19).
• Disregarding pressurised line sections with maintenance ( see Residual hazards caused by pres-
surised parts, page 24).
• Disregarding residual hazards caused by vibrations ( see Residual hazards caused by vibrations,
page 24).
result in ruptures during operation and maintenance. This results in dangers caused by
• escaping materials (see Residual hazards caused by pressurised parts, page 24).
• released working fluid (see Residual hazards due to CFC/HFC refrigerants , page 22).
Ensure that:
• The installation is fault-free.
• The maximum permissible operating pressure is always adhered to.
• Pressurised line sections are de-pressurised before all maintenance and repair work.
• Vibrations from the refrigeration system, from the (vibrations caused by system compressors, , com-
ponents and lines) and from the fan (imbalances caused by frosting, icing or dirt build-up or dam-
ages) are reduced with all available means and brought down to an absolute minimum.
• Release devices to prevent liquid escapes are provided and available.
• Undercooled liquid is only present in the lowest possible amount in system sections in shutdown
state – minimized number of "fluid sacks".
• When switching over a duty pump to a reserve pump no liquid, cold refrigerant remains in the pump.
WARNING
Injuries and damage to property caused by escaping objects or liquids!
Residual hazards caused by escaping objects and liquids ( see Residual hazards with break during oper-
ation, page 26).
WARNING
Danger of injuries and damage to property caused by CFC/HFC working fluid, , !
The following notes are recommendations for the proper professional disposal of the unit. Applicable
waste disposal laws are binding for the country of operation:
■ Disposal must only be carried out by experts.
■ All unit components, e.g. working fluids, refrigerator oil, heat exchangers, fans, must be disposed of
properly as specified.
■ Used working fluid that is not determined for reuse, must be treated as waste and safely disposed
of. There must be no emissions into the environment.
■ The CFC/HFC refrigerant must be filled into a special refrigerant container in compliance with the
respective safety measures. This special refrigerant container must be suitable for the refrigerant. It
must be easy to identify and labelled for the refrigerant, e.g. "HFC R-4304A recovered".
■ A disposable single-use container must not be used, as refrigerant vapour residues in the container
escape during disposal.
■ The working liquid receiver must not be overfilled. The maximum permissible pressure of the working
fluid container must not be exceeded during the work process.
■ The working fluid must not be filled in a liquid container that contains another or an unknown working
fluid. This other or unknown working fluid must not be released into the atmosphere, but rather identi-
fied, treated again, or properly disposed of as specified.
■ An officially authorised facility can be used for destroying the working fluid.
■ Used refrigerator oil that has been recovered from the unit and cannot be treated again, must be
kept in a separate, suitable container, treated as waste and safely disposed of.
■ It must be ensured that all unit components containing working fluids and refrigerator oil, are dis-
posed of properly as specified.
■ The unit consists predominantly of the basic materials, copper, aluminium, (heat exchangers and
casings), steel and aluminium, copper, polyamide (motors), steel, copper, insulating material (heater
rods with electric defrosting – option; accessory at customer's request). These materials can be han-
dled by the waste industry, including in paint-treated state, to recycling via mechanical and thermal
separation.
■ Before scrapping the working fluid-carrying unit components must be drained, whereby the pressure
must be reduced to at least 0.6 bar absolute for a unit pipe volume up to and including 200 l, and
to 0.3 bar absolute for a unit pipe volume over 200 l. The pressure reduction process is then ended
when the pressure no longer increases and remains constant, and the unit is at ambient tempera-
ture.
WARNING
Danger of environmental pollution!
The facility for recovering or disposing of the refrigerant must be operated so that the danger of a refrig-
erant or refrigerator oil emission into the environment is kept as low as possible.
• Ensure that no working fluid enters water systems or sewage.
• Operate the facility for recovering or disposing of working fluids so that the danger of a working fluid
or refrigerator oil emission into the environment is kept as low as possible.
Güntner GmbH & Co. KG’s transportation packaging is made from environmentally compatible ma-
terial and is suitable for recycling.
3 Technical data
3.1 Unit
NOTICE
The fans’ capacity values depend on the ambient temperature and on the air resistance at the set-up
point.
Güntner GmbH & Co. KG recommends electric fan ring heating with use in the temperature range.
Please consult the manufacturer when operating the unit below -40°C because of the special material
requirements and selection.
All electrical parts must be installed in accordance with EN standards.
3.2 Fans
5 Fan motor
NOTICE
During longer periods of storage or standstill, the fans must be activated during 2 to 4 hours per month.
NOTICE
For fans with the protection rating IP55 or higher, existing closed condensation water holes must be
opened at least once every six months.
AC technology
The AC motors are protected against overheating by a thermocontact (or PTC resistor).
For motors with a thermocontact, the thermocontact must be switched in such a way that the motor
cannot be powered on when the thermocontact is triggered. A locking mechanism is recommended
to prevent renewed power-on.
Motors with a PTC resistor need an additional external trigger unit for the installed thermistors. A
locking mechanism is recommended to prevent renewed power-on. The test voltage at the thermis-
tors is not permitted to exceed 2.5 V, or only current-limiting test devices may be used.
When using a star-delta connection, a corresponding delay must be considered.
For motors with direct starting and a connection value > 4.0 kW, an inrush current limitation (soft
start using a thyristor) could be required.
If frequency converters are to be used for speed control, the following points must be considered for
external rotor fans:
Between the frequency converter and fans, all-pole sine-wave filters must always be installed (sine
wave-shaped output voltage; filter effect between phase to phase and phase to earth).
All Güntner frequency converters are equipped with this function as standard. Conventional three-
phase motors are suitable for direct operation with frequency converters.
With star-delta connection, the three-phase fan motors can be operated with two speeds or with
speed control. The direction of rotation must be checked. A change in the direction of rotation, if it is
wrong, is made by interchanging two phases.
6.1 Safety
WARNING
Crushing danger with falling down!
The unit weighs between approx. 215 kg and 935 kg. It can slip and fall off the transporting device,
causing serious injuries or death. Heavy impacts or vibrations can damage the unit.
Ensure that the assigned staff is trained for proper unloading.
Ensure that nobody is under the unit or near the loaded area during the transport.
Ensure even weight distribution. Ensure that the bulk of the weight is always on the fan side. Observe
the transport labels on the packed unit ( see Other signs and notes on the unit, page 15).
Secure the unit against slipping and mechanical damage.
When transporting by crane: The hooks and lifting gear of the load lifting equipment must be only at-
tached at the points specified by the manufacturer. Ensure that the unit casing is not crushed by slings.
Use auxiliary transport equipment where required. Use a transporting device appropriate for the unit’s
weight. You will find the weight of the unit in the order-related documents
see( Set-up and other applic-
able documents, page 7). Do not use connection pieces and header pipes as hooking points for lifting,
pulling, fixing or mounting. This can cause leaks.
Transport the unit carefully. Particularly avoid setting the unit down hard.
NOTICE
Read and observe all transport signs on the units’ packaging!
Prolonged mechanical stresses caused by uneven road surfaces and potholes and vibrations during
transport by ship can cause transportation damage. Before transportation by sea or in countries with dif-
ficult transport routes, attachment parts that are likely to vibrate – in particular fans and base stands –
must be removed for transportation.
Use suitable equipment to transport the packed unit to the destination installation site (for exam-
ple, a crane or fork-lift).
Unload the unit.
NOTICE
Danger of corrosion and dirt build-up!
Moisture and dirt must be prevented from entering the unit.
Protect the unit against dust, dirt, moisture and wetness, damage and other harmful effects. Harmful
effects: see Safety instructions for set-up and start-up, page 33
Do not store the unit for longer than necessary. Only store the units in their original packaging until
installation. Always only place packaging units of the same size on top of one another.
Store the unit at a protected place free of dust, dirt, moisture and damage-free until its set-up
(well-ventilated halls or roofed storage site).
If the unit set-up is delayed with regard to the planned installation time: protect the unit against
weather and other harmful effects and dirt and other contaminants with an appropriate cover.
The unit must also be well-ventilated here.
7.1 Safety
WARNING
Danger of injuries and damage to property with escaping CFC/HFC refrigerant!
Incorrect installation causes the danger of working fluid escaping when the unit is operated and injuries
or damage to property (see Residual hazards due to CFC/HFC refrigerants , page 22).
Follow the set-up instructions in this chapter precisely and apply extreme care!
NOTICE
Damage to the system's !
Foreign materials and contaminants in the working fluid circuit can impair the effectiveness or damage
components. Particularly harmful contaminants are:
– Moisture
– Atmospheric air
– Welding and soldering residues
– Rust
– Soot/ash/cinders
– Metal cuttings
– Unstable oils
– Dust and dirt of all kinds
Moisture in the working fluid-carrying components of the unit can have the following consequences:
– Water separation and ice formation cause faults in the switching and control fittings of the refrigera-
tion system
– Acidification
– Ageing and refrigerator oil decay
– Corrosion
Atmospheric air and other non-condensable gases can have the following consequences:
– Refrigerator oil oxidation
– Chemical reactions between working fluid and refrigerator oil
– Increased condensing pressure in the system
Chemical reactions between working fluid and refrigerator oil with the absence of moisture or atmospher-
ic air with ageing and working fluid and refrigerator oil decay can have the following consequences:
During the installation (connecting the working fluid-carrying components of the unit to the working flu-
id-carrying system of the installation’s ensure that internal contamination is strictly avoided.
Perform the installation with extreme cleanliness.
Finish all on-site pipe installation work before releasing the transport pressure!
Only release the transport pressure on the Schrader valve immediately before installation.
Only remove the sealing caps on the distribution and header pipe immediately before installation.
NOTICE
Danger of corrosion and dirt build-up!
Moisture and dirt must be prevented from entering the unit. If moisture and dirt penetrate the unit there
is also the danger of damage to fittings and other system components of the .
Protect the unit against dust, contamination, moisture and wetness, damage and other harmful influ-
ences. Harmful influences are, for example:
– Mechanical: Damages caused by impacts, objects falling on or against, collisions with transport
equipment, etc.
– Physical: Damages caused by close by concentrated flammable gases
– Chemical: Damages caused by contaminated atmospheres (salt, acid, chlorine, sulpher-containing,
or similar)
– Thermal: Damages caused by close by heat sources
Begin with the installation as soon as possible.
WARNING
The electrical installation may be performed only by electricians (or by expert technicians with appropriate
qualifications) in compliance with the relevant VDE rules (or applicable national and international regula-
tions) and the TCCs of the EPCs!
• The electrical motor, repairs switch, terminal box and switching cabinet connections must be
provided in acc. with the respective connection diagrams.
• It must be possible to shut off the unit if a leak occurs.
• People wearing ambient air-independent breathing apparatus in full protective clothing must al-
so be able to activate all safety-relevant shut-off fittings.
• It must be possible to activate all devices meant for diverting escaping working fluids from a
safe position.
WARNING
Danger of injuries!
The unit contains CFC/HFC refrigerant ( see Residual hazards due to CFC/HFC refrig-
erants, page 22).
The CFC/HFC refrigerants that are used (R134a, R404A, R407C, R507, R22 ...) are
Group L1/A1 refrigerants classified according to their flammability (L) and toxicity (A)
in compliance with EU Directive 2014/68/EG for pressure equipment (Pressure Equip-
ment Directive):
– Refrigerants that, when gaseous, are non-flammable irrelevant of their concentra-
tion in air.
– Refrigerants with a time-weighted, averaged concentration that have no adverse
effects on the majority of staff that are exposed every day during a normal 8 hour
working day and a 40 hour working week to this concentration, which is greater
than or equal to 400 ml/m 3 (400 ppm (V/V)).
There is no imminent danger for the staff. However, refrigerants of the Group L1/A1
are generally heavier than air and may flow off to rooms on a lower level. In still air
there may be an increase of the ground level concentration. With high concentrations
there is a danger of suffering from disordered cardiac rhythm and suffocation due to a
reduced oxygen concentration, especially at ground level.
Unauthorised people must not have access to the unit. Please ensure that CFC/HFC
refrigerant escaping from the unit cannot reach the interior of the building or put people
at risk in any other way.
Comply with the requirements of EN 378-3 for refrigerants, filling weight and cold
transfer systems.
Install the unit in accordance with EN 378-1 only in the commissioned configuration
and only in a set-up room that the unit manufacturer has configured the unit for.
Install the unit in accordance with EN 378-3, section 5 in a special machine room if an
explosion or a CFC/HFC refrigerant concentration of more than that permissible under
EN 378-3 could endanger the work environment. Take effective protective precautions
if such a spatial separation were to be required, but is not possible.
Install the electrical equipment (for fan operation, for ventilation, for lighting and for the
alarm system) in the set-up room while observing the condensing-out of moisture and
drip water formation, as well as the risk level of CFC/HFC refrigerant in accordance
with EN 378-3; section 6.
Arrange CFC/HFC refrigerant detectors and alarm systems to warn of explosion or
fire dangers and CFC/HFC refrigerant concentrations that are hazardous to health
and for control purposes in the unit set-up room in accordance with EN 378-3; section
7.
Ensure that the device in the set-up room is not exposed to any inadmissible high
temperature effects. Effectively protect the unit against heat sources or temporary
high temperatures.
WARNING
Danger of environmental pollution!
• Ensure that no refrigerant enters water systems or sewage.
• Operate the facility for recovering or disposing of refrigerant so that the danger of a refrigerant or re-
frigerator oil emission into the environment is kept as low as possible.
Check the delivery for completeness. You will find a list of the contents of the package in the or-
der-related documents.
Any transport damage and/or missing parts must be recorded on the bill of delivery. The facts
must be immediately reported to the manufacturer in writing. Damaged fins can be straightened
on-site with a fin comb.
The units are delivered packed in the installation position.
Check transport overpressure: The units are delivered from the manufacturer with approx. 1 bar
transport overpressure (cleaned and dried air). Read the transport pressure on the Schrader
valve (pressure measurement). With unpressurised unit: Immediate report to manufacturer and
noting on bill of delivery. An unpressurised unit indicates a leak on the unit!
CAUTION! Danger of injuries and damage to property with escaping working fluid!
An unpressurised unit indicates a leak due to transport damage. Escaping working fluid
through leaks on the unit can cause injuries or ( see Residual hazards due to CFC/HFC refrig-
erants, page 22). Do not put the unit into operation!
Check transport pressure and release (only immediately before installation).
Remove blanking plugs.
NOTICE
Danger of corrosion and dirt build-up!
Moisture and dirt must be prevented from entering the unit.
Protect the unit against dust, dirt, moisture and wetness, damage and other harmful effects. Harmful ef-
fects: see Safety instructions for set-up and start-up, page 33
Begin with the installation as soon as possible.
7.4 Installation
The units must be installed on fixing points that are appropriate for the unit's weight and then
bolted with fixing bolts. The operator or installer of the equipment is responsible for ensuring
that the bolted connections are of an adequate strength. The following instructions must be ob-
served when fixing the units:
– The diameter of the mounting holes have been statically determined by the manufactur-
er; the fixing bolts must be adapted accordingly. When calculating the transferring bearing
strength it is imperative to take into account the total weight of the unit (= structural weight +
weight of pipe content + additional weight, such as water, frost, ice, dirt or similar).
– The fixing bolts must be secured against loosening with an appropriate locking device.
– The fixing bolts must not be overtightened or stripped.
– All fixing bolts must be tightened equally.
Prevent the unit from shifting in its position. Fix the unit in its position. Tighten the fixing bolts
and secure then against loosening.
Ensure that the drip water drains correctly. Set up the unit horizontally with a sufficient slope for
the drip water run-off. The units are delivered in the installation position with mounted drip tray.
Only fix the unit to the intended fixing points.
1 Fixing of unit
WARNING
Danger of injuries and damage to property with escaping CFC/HFC refrigerant!
Incorrect installation risks working fluid escaping when the unit is operated, causing injuries or damage to
property (see Residual hazards due to CFC/HFC refrigerants , page 22).
Prevent working fluid from escaping from the unit into the environment.
• Secure all working fluid-carrying lines against mechanical damage.
• In areas that are used for internal traffic, only lay the pipelines to and from the unit with connections
and fittings that cannot be removed.
Ensure that the on-site connections do not exercise any forces upon the distribution and header points.
This can cause leaks on the working fluid connection points of the unit and on connection points of the
on-site pipe-laying.
Connections
NOTICE
After mounting, check that the capillary tubes of the refrigerant distributor are not blocked.
Lay drain line completely strain-free. The diameter of the drip water drain line must be at least
that of the drip water drain of the unit, and the drip water drain line should be laid with a slope (3
– 5°).
Tighten connection nuts with the hand only!
NOTICE
Danger of damaging! The plastic threads can be damaged by over-tightening if you use a wrench.
This results in leaks with drip water damage on the produce to be cooled. Do not tighten the con-
nection nuts with a wrench!
WARNING
Danger of injuries and damage to property!
Improper connection to the the system causes hazards:
• Leaks result in escaping CFC/HFC refrigerant ( see Residual hazards due to CFC/HFC refrigerants ,
page 22).
• Soldering and welding work on pressurised parts can result in fires or explosions.
• Smoking or open light can cause fires due to the presence of refrigerator oil.
• Ensure that stresses and vibrations from the system are not passed on to the unit.
• Only lay working fluid-side connections stress-free! The on-site pipeline system must be braced be-
fore connecting to the unit!
• Soldering and welding work is only permitted on unpressurised units!
• Evacuate the unit professionally in acc. with EN 378-2.
• The use of open fire at the installation site is forbidden. Fire extinguishers and extinguishing agents
used to protect the equipment and the operating staff must comply with the requirements of EN
378-3.
• Ensure that refrigerant detectors and alarm systems for warning about fire dangers, about health-
endangering concentrations and for control purposes at the unit set-up point are arranged in acc.
with EN 378-3; section 7.
Install the pipes in acc. with EN 378-1 and EN 378-3. Ensure here:
– Release devices to prevent liquid escapes must be provided and available.
– That in shutdown state under-cooled liquid is only present in the lowest possible amount in sys-
tem sections – minimized number of "fluid sacks".
– That the pipeline installation is kept as short as possible. Use as few bends as possible, and if
bends are necessary, use big radii!
– Avoid transmitting vibrations to the unit via conduits or pipes. If necessary, use vibration
dampers.
– Always lay the fluid supply and return lines separately from one another. Make sure they do not
touch.
– It must be possible to shut off the unit if a leak occurs. It must be possible to activate all devices
used for diverting escaping working fluids from a safe position.
– With connection of the liquid and suction line, the thermostatic expansion valve, including its
overheating sensor, must be protected against high heat stresses from the soldering process!
– Observe the following when soldering:
° All connections must be hard-soldered!
° Caution! Use silver solder with TS < -40 °C! Ask manufacturer about solder specification if
required!
° Avoid percussive soldering joints; use copper pipe ends that are widened on one side (capil-
lary soldering)!
° Prevent leaks, solder precisely and carefully!
° Prevent overheating when soldering (danger of excessive scaling)!
° Use shielding gas when soldering (prevent excessive scaling)!
Seal all electrical lines to the connection boxes in acc. with their protection class. The connec-
tion class is specified in the order-related offer documents.
WARNING
Danger of damaging! If the fuse rating is too high there is the danger of injuries to people
and damage to property.
Max. fuse rating for the defrost heater rods feed : see order-related offer documents. The
supply lines must always be fused as appropriate for the smallest wire cross-section.
WARNING
Danger of injuries and damage to property!
Escaping CFC/HFC refrigerant can cause injuries or even death ( see Residual hazards due to CFC/
HFC refrigerants, page 22).
Perform the following acceptance test with an expert before starting up the unit after making important
changes and after a unit exchange.
Ensure that the temperature and air humidity at the set-up point are in line with the technical da-
ta (see Technical data, page 28).
Ensure that sufficient air can be sucked in and released.
Ensure that the supply feed is sufficient for the required energy. Compare the unit inside of the
systemwith the plans of the systemand the electrical wiring diagrams.
Test the unit for vibrations and movements that can be caused by the fans and operation of the
system . Remove oscillations, vibrations and movements following consultation with the manu-
facturer or independently.
Perform visual inspection of the structural design, the brackets and fixtures (materials, se-
quence, connections), the ability to operate and the arrangement of the fittings.
Check and if necessary re-tighten all threaded connections, especially on the fans.
Check installation of pipe connections.
Check laying of working fluid-carrying connection pipes.
Ensure that the unit is protected against mechanical damage.
Ensure that the unit is protected against inadmissible heating up and cooling down.
Check the fan blades protection.
Ensure that optimum unit control and accessibility are guaranteed.
– Is the unit placed so that it can be monitored and controlled from all sides at all times?
– Is sufficient space provided for maintenance?
– Are all liquid-carrying components, connections and lines and all electrical connections and
lines easy to access?
– Are the pipes easy to identify?
Check heat exchanger surfaces for dirt and clean as required (see Clean unit, page 55).
Perform function tests on the fans (rotation direction, power consumption, etc.).
Check electrical connections of the fan motors and, where app., the heater rods with electric de-
frosting for damage.
Check the soldering and welding connections, the electrical connections and the fixture connec-
tions.
Perform pressure test with test gas and with a test pressure of 1.1-times the permissible operat-
ing pressure: check the connection seals and detect leaks, e.g. with foaming agent, or similar.
Check corrosion protection: Perform a visual inspection on all bends, components and compo-
nent holders that are not heat-insulated. Document and archive test results.
Perform test run. Observe and check unit during test run, in particular for:
– Fan smooth running (bearing noises, contact noises, imbalances, etc.).
– Fan power consumption:
– Leaks
Report all defects to the manufacturer immediately. Remove defects following consultation with
the manufacturer.
Check the unit and the unit’s interaction with of the system again after 48 operating hours, espe-
cially on the connections and on the fans, and document the test results.
7.8 Putting the unit into operation for the first time
WARNING
Danger of injuries and damage to property!
Escaping CFC/HFC refrigerant can cause injuries or even death ( see Residual hazards due to CFC/
HFC refrigerants, page 22).
You can put the unit into operation, only when:
• The unit has been properly mounted and connected ( see Installation, page 38).
• You have performed a complete acceptance test see
( Perform acceptance test, page 44).
• You have checked the unit’s readiness for operationsee ( Test readiness for operation, page
45).
• All safety precautions (see Safety, page 33) have been taken.
Follow the operating instructions manual of the system!
Contact the manufacturer immediately if you want to operate the unit under different operating conditions
as those defined in the order-related offer documents.
Wait until the operating point is reached. After the operating point is reach the unit is ready to
operate (see system).
Parameters for setting the operating point, see order-related offer documents.
Operating point:
• Evaporation temperature
• Airflow volume
• Air inlet temperature
• Relative air humidity
To ensure the specified operating point is complied with the actuators for the operating point setting
must be secured against unauthorized access (e.g. by sealing, screwing on caps, removing hand
wheels, etc.).
8 Operation
8.1 Safety
WARNING
Danger of cutting off, pulling in!
There is a danger of cutting off fingers on the rotating fan blades, injury hazard for the
hands and pulling in danger with loose elements such as hair, necklaces or clothing
parts.
Do not operate fans without guard grille!
WARNING
Danger of frostbite/burning!
Danger of frostbite or burns if the parts are touched ( see Thermal residual hazards,
page 22).
Do not touch any parts of the unit without protective gloves when the unit is in opera-
tion or if it has not yet warmed up or cooled down after operation.
NOTICE
With shutdown times of a month or longer put the fans into operation for approx. 2-4 hours a month to
maintain their functionality.
WARNING
Danger of injuries and damage to property!
Escaping CFC/HFC refrigerant can cause injuries ( see Residual hazards due to CFC/HFC refrigerants ,
page 22, and see Residual hazards caused by pressurised parts, page 24).
Ensure that the maximum operating pressure is not exceeded after the shutdown either!
NOTICE
Danger of corrosion and dirt build-up!
Moisture and dirt must be prevented from entering the unit.
Protect the unit against dust, contamination, moisture and wetness, damage and other harmful influ-
ences (see Safety instructions for set-up and start-up, page 33).
With shutdown times of a month or longer put the fans into operation for approx. 2-4 hours a month to
maintain their functionality.
Take the unit out of operation (see Taking the unit out of operation, page 47).
Secure the unit:
– When shutdown consider max. operating pressure (see Technical data, page 28)! If neces-
sary, take precautions so that it cannot be exceeded.
– Secure the fan motor drives and, where applicable, the heater rods with electric defrosting
against switching on again.
– Secure working fluid-carrying lines against pressurizing with working fluid.
– Protect against damaging effects at the set-up point or intermediate storage location (see
Safety instructions for set-up and start-up, page 33), so that the unit’s components are kept
properly looked after and the proper intentional use and usability of the unit are maintained.
The corresponding storage conditions must be provided for this (see Storage before instal-
lation, page 32); precautionary corrosion protection measures, regular checking of the fans’
functionality and regular checks on the shutdown unit.
Evacuate the unit: Completely release working fluid and, if applicable, refrigerator oil (see
Residual hazards with disposal, page 27).
WARNING
Danger of injuries and damage to property!
Considerable dangers can be caused with operation with another working fluid without prior manufactur-
er approval (see Improper use, page 19).
Without prior written consent from Güntner GmbH & Co. KG , the unit must not be changed over to use
a different working fluid.
9 Troubleshooting
9.1 Safety
WARNING
Danger of injuries and damage to property!
Faults that are not described in these operating instructions may be resolved only by Güntner. Contact
the Güntner hotline.
Faults that are described in these operating instructions must only be removed by appropriately trained
personnel (see Personnel, care requirements, page 18).
If any faults occur during the operation, monitoring or maintenance of the system as a whole, inform
Güntner GmbH & Co. KG immediately.
9.2 Service
Office hours
10 Maintenance
10.1 Safety
WARNING
Danger of injuries and damage to property with escaping working fluid! see Residual hazards due to
CFC/HFC refrigerants , page 22).
Only perform maintenance work – especially welding work – on the leaking unit after completely remov-
ing the working fluid from the leaking unit!
Perform the following safety measures before beginning all maintenance work:
■ drain the unit's heat exchanger
■ Clean and blow out the unit's heat exchanger.
WARNING
Danger of injuries and damage to property with escaping CFC/HFC refrigerant!
Escaping refrigerant with leaks on the evaporator can cause the following hazard situations and in-
juries:
Warning against explosion-risk and fire-risk substances in the set-up room!
Unintentionally carried in oil residues can ignite.
• Ensure that there is no unintentionally carried in oil in the set-up room.
• Keep the risk area free of direct and indirect ignition sources.
• Before releasing for maintenance obtain the required approvals for work for the unit
that can involve ignition sources (e.g. grinding, welding, soldering, etc.).
• With all work involving ignition sources (e.g. grinding, welding, soldering, etc.) in the
work area, keep suitable fire extinguishing equipment that meets the requirements
of EN 378-3 at hand.
• Do no bring any open flames or hot gases (e.g. candles, matches, welding beads,
welding sparks, glowing cinders or tobacco) into the set-up room.
• Ensure that there are no warmed up or hot surfaces (e.g. heaters, hotplates,
bulbs, motor housings) in the set-up room.
• Ensure that no frictional heat develops in the set-up room (e.g. overheated stores).
Warns against health-endangering irritants in the set-up room!
CFC/HFC refrigerant under defervescence still present can evaporate. Inhalation of re-
frigerant vapour causes harmful to health irritations and lack of oxygen.
• Escaping refrigerant vapour and escaping refrigerant liquid must not reach adjacent
rooms, staircases, yards, passages or drainage systems.
• Use respiratory protection.
• Use a room air-independent breathing apparatus with maintenance work in high
CFC/HFC refrigerant concentrations in the room air.
• Ensure the set-up room is well ventilated.
• Divert escaped refrigerant vapour and escaped refrigerant liquid safely.
• Ensure that the unit in question is pressure-free before maintenance work begins or the working fluid
is sucked up from the unit in question.
• Power off the electrical system and secure it against unintentional switching on again.
• Separate the unit to be maintained from the refrigeration system and secure it.
NOTICE
Danger of damage to property!
With work in the inlet and outlet feeds of the fans and heat exchanger, objects can get
into the fans and therefore cause faults and damage on the components.
• Power off the fans and, where applicable, the heater rods with electric defrosting
before beginning maintenance work and secure them against switching on again.
• After the work has finished do not allow any objects to get back into the inlet and
outlet feeds of the fans or the set-up room.
WARNING
Danger of injuries and damage to property with escaping CFC/HFC refrigerant! see Residual hazards
due to CFC/HFC refrigerants , page 22)!
Perform the following safety measures after finishing all maintenance work:
• Ensure the switching and activation devices, the measuring and display devices and the safety de-
vices function properly.
• Ensure the working fluid fittings are functioning.
• Ensure that the swivel fan units (optional) and the hinged side covers are fixed in their original posi-
tion and secured against unintentional or unauthorised opening.
• Check the identification of the pipelines and ensure this is visible and legible.
• Check the fixing and corrosion protection of the components in question.
• Ensure the electrical connections (e.g. fans and, where applicable, the heating rods with electrical
defrosting) are functioning.
• Ensure the temperature and air humidity at the set-up point are the same as that in the order-relat-
ed offer documents.
• Perform a pressure test and a tightness test (see operating instructions manual annex).
• Perform an acceptance test (see Perform acceptance test, page 44).
• Perform a pressure test (see operating instructions manual annex).
10.2.1 Fans
The manufacturer’s operating specifications take priority for this component. Güntner GmbH & Co.
KG recommends proceeding according to the following inspection and maintenance plan:
WARNING
Danger of injuries and damage to property with escaping CFC/HFC refrigerant! see Residual hazards
due to CFC/HFC refrigerants , page 22)!
WARNING
Danger of injuries and damage to property with CFC/HFC refrigerant ( see Residual hazards due to
CFC/HFC refrigerants , page 22)!
• Have leaks removed as quickly as possible by an expert.
• Do not fill with a working fluid other than that specified in acc. with the order-related offer documents!
• Only put the unit back into operation when all leaks have been repaired.
Perform all work including pressure, acceptance and functional test (see Perform acceptance
test, page 44, and see Test readiness for operation, page 45).
10.4.1 General
The following applies for cleaning: The operator must ensure that the cleaning agents are environ-
mental friendly and compatible for the materials in the system. Harmful to the environment sub-
stances, e.g. acid-forming, are forbidden.
Clean casing by rinsing with warm water (approx. +25°C) and/or with environmentally friendly
cleaning agents.
Rinse thoroughly with water after using cleaning agents.
Allow casing to dry completely.
Check working fluid-side and electrical connections (see Test readiness for operation, page 45).
NOTICE
Danger of damage to property!
The fins can be damaged with too high a pressure, too small a distance or a cleaning jet that hits the
fins at an angle. Mechanical cleaning with hard objects (e.g. steel brushes, screw drivers, or similar)
damages the heat exchanger.
• Use a pressure of max. 50 bar with hydraulic cleaning and max. 80 bar with cleaning with com-
pressed air!
• Maintain a minimum distance from the fins of 200 mm!
• Always aim the jet vertically (max. ±5 degree deviation) at the fins!
• Do not use any hard objects when cleaning!
Blast heat exchanger (max. 80 bar pressure) with compressed air to remove dirt and contami-
nants.
NOTE! Hold the jet of the cleaner vertical to the fins (max. deviation of ±5 degrees) to prevent
fins from bending.
WARNING
Warns against dangerous electrical voltage!
Direct and indirect contact with voltage-carrying parts of motors and electrical lines can
cause serious injuries or death. Water and cleaning agents conduct electricity.
• Power off the fans for cleaning with water or steam jet and where applicable the
heater rods for electrical defrost and ensure them against switching on again.
NOTICE
Danger of damage to property!
Water or steam jets can damage fans, electrical lines or other components.
• Ensure that electrical connections and motors, as well as components and stored goods at the set-
up point are not touched by water or steam jets. Cover these if required.
Heavier moisture or greasy dirt must be removed with a high-pressure water jet (max. 50 bar
pressure), steam pressure jet (max. 50 bar pressure), min. 200 mm distance with flat jet nozzle,
or using neutral cleaning agent where applicable, always against the airflow direction. Ensure
here:
– With oily and greasy dirt it helps to add a cleaning agent to the water.
– When applying chemical agents ensure that they are not aggressive towards the unit's mate-
rials. Rinse the unit off after the treatment.
– Cleaning should be done from inside to the outside (but always opposing the dirt onset) and
from top to bottom, so that the dirt can be removed without returning.
– Hold the jet of the cleaner vertical to the fins (heat exchanger – max. deviation of ±5 de-
grees) to prevent fins from bending.
WARNING
Danger of cutting off, pulling in!
There is a danger of cutting off fingers on the rotating fan blades, injury hazard for the hands and pulling
in danger for loose elements such as hair, necklaces or clothing parts.
• Power off the unit before you begin maintenance work. Secure the unit against unintentional switch-
ing on again by removing the electric fuses for the unit. Secure the unit with a suitable warning sign
referring to unintentional switching on.
• Put fans and guard grilles that were removed or opened for maintenance back into their original
status without fail before you put the unit back into operation!
Dirt build-ups and frost and/or icing on the fans and the fan guard grilles must be removed regu-
larly, otherwise they will cause imbalances or destruction and power losses. The fan motors them-
selves are maintenance-free.
Power off the unit and secure it against unintentional switching on.
Clean fans with one of the following procedures:
NOTE! Danger of damage to property! Mechanical cleaning with hard objects (e.g. steel
brushes, screw drivers, or similar) damages the fan. Forbidden!
– Cleaning with compressed air: Blow fans with compressed air (max. 10 bar pressure; min.
distance 200 mm) to remove dirt and contaminants. Continue cleaning until all dirt has been
removed.
– Cleaning with compressed air and brushes: Remove dry dust or dirt with a brush, a hand
brush or with compressed air (max. 10 bar pressure, min. distance of 200 mm) or with a
powerful industrial vacuum cleaner. Ensure here: use soft brushes (no steel brushes or simi-
lar)! Continue cleaning until all dirt has been removed.
Mount guard grille
Switch unit on
WARNING
Warning against personal injury and damage to property!
Danger of falling unit parts, masses of water or ice when the drip tray is flapped out.
Nobody is allowed to be in the danger area below the unit during cleaning or maintenance work. The
drip tray can be flapped down for cleaning and is protected from falling down by a safety catch. Unit
parts, masses of water or ice can nonetheless fall down when it is flapped down.
Defrosting the unit at the correct times guarantees continuous operational reliability and the preven-
tion of inaccessibilities that could result in a shutdown and disruptions. As the local conditions have
a very big influence of the unit's performance and the need for defrosting, the operation must be
checked regularly and specifically for frost and/or icing on the heat exchanger. The following notes
apply for defrosting the unit:
• Regularly check for frost and/or icing. With a frost thickness of max. 1 mm per fin side the unit
must be defrosted to be able to guarantee fault-free operation.
• Defrosting process must start in good time.
The defrosting frequency depends on the effects of penetrating moisture (e.g. cold storage room
door) or introduced moisture (e.g. goods to be cooled, .). It must be noted here that the tempera-
ture difference between the working fluid and the air inlet temperature is critical for the defrosting
frequency:
• Unit with greater temperature difference: Frequent defrosting
• Unit with lesser temperature difference: Less defrosting
Alternating operating states, e.g. usage changes at the set-up point, must also be considered. The
defrosting frequency can be influenced by effects on the air side. Insufficient unit-wall distance, dis-
tance between two opposing units too low, underdraughts shortly before the air outlet, incorrect
goods storage (too high, no wall distance, across the airflow direction) cause increased defrosting
frequency.
Defrosting completeness
When finishing the defrosting process you must ensure that the defrosting is absolutely complete.
Selecting the right defrosting temperature is an important requirement in this respect.
• If the defrosting temperature is set too low this impairs the unit's effectiveness from one defrost-
ing to another with the removal of "ice-spots".
• If the defrosting temperature is set too high this causes extreme water vapour formation, which
causes frost and ice to form around the unit.
Settling time
A period (approx. 5 to 8 minutes) between when the defrosting finishes and when the unit is activat-
ed has been proven to be necessary, as the unit's heat exchanger can drip off completely and the
defrosting water can flow away through the drip water tray drain during this period.
If the fans' activation is delayed by a further period (approx. 3 to 5 minutes), then the defrosting
heat from the heat exchanger is absorbed and it is not given off into the room as warm-moist air.
Electric defrosting
Cold operation X
Suction operation X
Defrost operation X
Drip phase X
Freeze on phase X
Cold operation X
Fans Operation Operation Off Off Off Operation
The duration of the individual phases depends from a variety of factors (e.g. temperature, moisture,
etc.) in the particular application.
Cold operation X
Suction operation X
Defrost operation X
Drip phase X
Freeze on phase X
Cold operation X
Fans Operation Operation Off Off Off Operation
The duration of the individual phases depends from a variety of factors (e.g. temperature, moisture,
etc.) in the particular application.
11 Plans/diagrams