Diagnosing and Solving Common Control Loop Problem
Diagnosing and Solving Common Control Loop Problem
Abstract
A substantial percentage of industrial control loops perform poorly. This decreases product quality, lowers
profitability, and makes processes difficult to operate. A few types of problems are commonly responsible for
degraded loop performance. To improve control loop performance, problems need to be accurately diagnosed
and the correct steps taken for solving them. This paper describes the most common problems affecting control
loop performance and how to identify and solve them.
Oscillations Due to a Cyclic Setpoint oscillating positioner was eliminated in the previous
step. The next step would be to discriminate between
The first cause of loop oscillations to test for would overly aggressive tuning and valve problems as the
be a cyclic controller setpoint. This problem can cause of the cycle.
be determined by visually inspecting a time trend
of the controllers setpoint. If the setpoint is not Valve or damper problems can obviously be ruled
visually cycling, this cause can be ruled out. out if the controller output is not connected to such
a device, for example, the primary controller in a
A cyclic setpoint is most often due to incorrect cascade control arrangement. In this case, tuning
tuning settings in a higher-level controller. This should be suspected, as previously stated.
controller should be tuned to correct this problem.
Setpoint cycling in a cascade control arrangement If the controller output drives a mechanical control
can also be due to excessive interaction between the element, the shape of time trends of the oscillating
primary and secondary controllers. This cause can controller output and process variable should be
be verified by comparing the integral-action settings visually inspected to differentiate between control
of both controllers. They should differ by at least valve stiction and overly aggressive tuning as the
a factor of five to minimize cyclic interaction. The cause of cycling. If the oscillation is caused by
same applies for the derivative settings, if used. tuning, the process variable will tend to cycle in
the shape of a sine wave. The amplitude of the
Oscillations Due to a Cyclic Disturbance cycle will normally grow until the process variable,
or Control Valve Positioner controller output, or both become bounded by
physical or programmatic limits.
If the oscillations are not setpoint-driven, the next
step would be to determine if they are generated
within the loop itself or by a cyclic external
disturbance. To test this, a time trend of the process
variable behavior with the controller in manual can
be inspected visually. If cycling is present while
the controller is in manual, it could be caused by
an oscillating control valve positioner or by a cyclic
external disturbance.
Stiction can also be detected by placing the controller Hysteresis can affect control performance in three
in manual and periodically making small (0.5%) step possible ways. First, because of the dead-band, the
changes in the controller output. A time trend of process variable cannot be controlled very precisely
the process variable can then be inspected to see if under the influence of disturbances. A loop with
the valve responds to every step made in controller hysteresis will display almost the same symptoms as
output or only to every few steps. The latter will sluggish controller tuning.
indicate a sticky control valve.
Second, a level control loop will continuously
Stiction might be caused by an over-tight valve stem oscillate after a setpoint change in the presence
seal, sticky valve internals, an undersized actuator, of hysteresis. This is as a result of the overshoot
or a sticky positioner. It can sometimes be solved (discussed earlier), combined with the control loops
by lubricating the valve stem while stroking its inability to immediately do an effective reversal of
position between limits. Most often, stiction can the excessive control action due to the dead band.
only be solved by servicing the control valve and/
Finally, control loop instability can occur if
or its positioner.
controller tuning is attempted without consideration
The author has found in some cases, lengthening of hysteresis. During a tuning test on a loop with
the integral time setting of the controller (or using hysteresis, part of the controller output change can
a lower integral gain depending on the integral unit be absorbed by the dead band and result in less
of measure) can reduce the tendency of a control valve movement. The process gain would seem to
loop to cycle due to stiction. This is possibly due be less than it actually is. As a result, the controller
to mechanical vibrations in the pipes and structures gain could be set too high. This problem may go
causing a slow creep in control valve position to unnoticed in the presence of minor disturbances or
balance the excessive force or torque coming from if small setpoint changes are made. However, once
the actuator. However, detuning the controller a significantly large setpoint change or disturbance
will lead to sub-optimal and sluggish control loop occurs, the effect of the hysteresis will be small in
performance and is therefore not the recommended comparison with the controller output change and
solution, but a temporary suppression of the cycle the control loop will be at a high risk of becoming
at best. unstable.
EMPOWERING PEOPLE. DRIVING ASSETS.
of the controller (gain, integral, and derivative). Once new tuning settings are obtained, they should
be entered into the controller and a setpoint change
should be made to verify the expected behavior.
Then the loop performance should be monitored
over several hours or days to ensure the desired
performance objectives are met.
will have virtually no effect on the level of the large Work Process for Improving
tank. The effect of the fast cycle on the upstream Control Loop Performance
or downstream processes could also be attenuated
to undetectable levels. Optimizing control loops and sustaining long-
term performance can be done very effectively
by implementing this seven-step approach
developed by PAS, Inc.:
References
[1] D.B. Ender, Process Control Performance: Not as Good as You Think, Control Engineering 40 (10), 1993,
173 186.
[2] W.L. Bialkowski, Dreams Versus Reality: A View From Both Sides of the Gap, Pulp & Paper Canada, 1993,
94 (11), 19 27.
[3] L. Desborough and R. Miller, Increasing Customer Value of Industrial Control Performance Monitoring:
Honeywells Experience, Proc. 6th Int. Conf. on Chemical Process Control (CPC VI), Arizona, USA, 2001,
172192.
[4] L. Desborough, P. Nordh, R. Miller, Control System - Process out of Control, Industrial Computing, August
2001, 52 55.
[5] V. VanDoren, Advances in Control Loop Optimization, Control Engineering, March 2008, 48 52.
[6] J.F. Smuts, Common Loop Problems, Internal Report, ControlServe Ltd., July 1999.
[7] N.F. Thornhill and T. Hagglund, Detection and diagnosis of oscillation in control loops, Control Engineering
Practice 5 (10) (1997) 1343.
[8] Fisher Controls International LLC, Control Valve Handbook, Fourth Edition, Emerson Process Management,
2005.
[9] S. Skogestad, Simple analytic rules for model reduction and PID controller tuning, Journal of Process Control
13 (2003) 291309.
[10] J.F. Smuts, Process Control in Practice, PAS Inc. Training Course Manual, August, 2002.
[11] L. Desborough and T. Harris, Performance assessment measures for univariate feedback control, The Canadian
Journal of Chemical Engineering 70 (1992) 1186-1197
[12] K.J. strm and T. Hgglund, PID controllers: theory, design, and tuning, Instrument Society of America,
1995.
About PAS
PAS is a leading supplier of software products and consulting services to the process industries worldwide and
has been delivering value to customers since 1993. Solutions offered include Alarm Management, Automation
Configuration Management, Knowledge Management, and Control Loop Performance Management.
PAS offers a comprehensive suite of products and services to support our customers control performance
improvement initiatives through the seven steps above. These include software for monitoring and improving
loop performance, process control training, and consulting and optimization services.