System 800xa Hardware: Data Sheet

Download as pdf or txt
Download as pdf or txt
You are on page 1of 3

Data sheet

SS823
System 800xA Hardware

The Voting Units SS822Z, SS823 and SS833 have


been specifically designed to be employed as a control
unit within a redundant power supply configuration.
The output connections from two Power Supply Units
are connected to the Voting Unit.
The Voting Unit separates the redundant Power
Supply Units, supervises the voltage supplied, and
generates supervision signals to be connected to the
power consumer. Green LEDs, mounted on the front
panel of the voting unit, provide a visual indication that
the correct output voltage is being delivered.
Simultaneously with the green LED illuminating, a
voltage free contact closes the path to the
corresponding OK connector. Voting Unit trip levels,
are factory preset.
The AC 800M High Integrity and the connected S880
High Integrity I/O system (including field power) shall
be supplied from a SELV or PELV power supply (e.g.
SD83x) connected through the power voter SS823.
The SS823 Voting Unit has double overvoltage
protection circuit on both inputs. It is also able to
detect both short and open circuit in the voting
element.

Features and benefits


Simple DIN-rail mounting
Class I Equipment, (when connected to Protective Earth, (PE))
Over-voltage Category III for connection to primary main
TN network
Protective separation of secondary circuit from primary circuit
Accepted for SELV and PELV applications
The output of the units is protected against over current
(current limit) and over voltage (OVP)
The SS823 unit is also G3 compliant

1(3) SS823 2016-12-18 | Copyright 2016 ABB


General info

Detailed data Voter and Over Voltage


Article number 3BSE038226R1 Type
Protection
Mains voltage variation Mains/input voltage, max.
Rated output current -20 A Rated output power 60
- V d.c.
allowed (a.c.= 45-65 Hz)
Rated
Primaryoutput voltagecurrent at
peak inrush - Rated input power 500 W
- Load sharing Yes
power on voltage, nominal
Mains/input 1x24 V d.c. Applications -
Power Factor
Efficiency (at rated output
factor - Heat dissipation 24 W at 20 A and 6 W at 5 A
power)
Output voltage regulation at
1.2 V lower than input Ripple (peak to peak) -
max. current
Secondary voltage holdup
- Maximum output current (min) 35 A (Overload)
time at mains blackout
Maximum ambient Primary: Recommended
55 C -
temperature external fuse (1)
Secondary: Over-Voltage
Secondary: Short circuit - < 30 V
protection

Environmental and
certification
CE mark Yes Electrical safety IEC 61131-2, EN 50178
Hazardous Location ATEX Zone 2 Marine certification ABS, BV, DNV-GL, LR, RS, CCS
Corrosive atmosphere ISA-
Protection rating IP20 according to IEC 60529 G3
S71.04
Mechanical operating
Pollution degree Degree 2, IEC 60664-1 IEC 61131-2
conditions
EMC EN 61000-6-4 and EN 61000-6-2 Overvoltage Categories -
Class 1 according to EN 50718;
Equipment class
3.56

Dimensions
145 mm (5.8") including
Width 116 mm(4.6") Depth
connector
Height 132 mm (5.3") Weight (lbs.) 870 g (1.9 lbs.)
Mounting spacing W mm 15 mm (0.59") Mounting spacing H mm 30 mm (1.2")

2(3) SS823 2016-12-18 | Copyright 2016 ABB


Contact us

www.abb.com/800xA Note:
www.abb.com/controlsystems We reserve the right to make technical
changes to the products or modify the contents
of this document without prior notice. With
regard to purchase orders, the agreed
particulars shall prevail. ABB does not assume
any responsibility for any errors or incomplete
information in this document.
We reserve all rights to this document and the
items and images it contains. The reproduction,
disclosure to third parties or the use of the
content of this document including parts
thereof are prohibited without ABBs prior
written permission.
Copyright 2016 ABB All rights reserved